Design Distribution Box of one House and Calculation of Size of Main ELCB and branch Circuit
MCB as following Load Detail. Power Supply is 430V (P-P), 230 (P-N), 50Hz. Consider
Demand Factor 0.6 for Non Continuous Load & 1 for Continuous Load for Each Equipment.
Branch Circuit-1: 4 No of 1Phase, 40W, Lamp of Non Continues Load + 2 No’s of 1Ph,
60W, Fan of Non Continues Load.
Branch Circuit-2: 2 No of 1Ph, 200W, Computer of Non Continues Load.
Branch Circuit-3: 1 No of 1Ph, 200W, Freeze of Continues Load.
Branch Circuit-4: 8 No of 1Ph, 40W, Lamp of Non Continues Load + 2 No’s of
1Ph 60W, Fan of Non Continues Load.
Branch Circuit-5: 4 No of 1Ph , 40W, Lamp of Non Continues Load + 1 No’s of 1Ph
60W, Fan of Non Continues Load.+ 1 No’s of 1Ph 150W, TV of Continues Load
Branch Circuit-6: 1 No of 1P , 1.7KW, Geyser of Non Continues Load.
Branch Circuit-7: 1 No of 1Ph, 3KW, A.C of Non Continues Load.
Branch Circuit-8: 1 No of 3Ph, 1HP, Motor-Pump of Non Continues Load.
Fault Current
Voltage Fault Current
230V 6KA
430V 10KA
11KV 25KA
Class of MCB/ELCB/RCCB
Type of Load Class Sensitivity
Lighting B Class I∆n:30ma
Heater B Class I∆n:30ma
Drive C Class I∆n:100ma
A.C C Class I∆n:30ma
Motor C Class I∆n:100ma
Ballast C Class I∆n:30ma
Induction Load C Class I∆n:100ma
Transformer D Class I∆n:100ma
Size of MCB/ELCB
Lighting Load MCB/ELCB Heating/Cooling/Motor-Pump
Current (Amp)
(Amp) Load MCB/ELCB (Amp)
1.0 to 4.0 6 16
6.0 10 16
10.0 16 16
16.0 20 20
20.0 25 25
25.0 32 32
32.0 40 40
40.0 45 45
45.0 50 50
50.0 63 63
63.0 80 80
80.0 100 100
100.0 125 125
125.0 225 225
225.0 600 600
600.0 800 800
800.0 1600 1600
1600.0 2000 2000
2000.0 3000 3000
3000.0 3200 3200
3200.0 4000 4000
4000.0 5000 5000
5000.0 6000 6000
6000.0 6000 6000
Calculation:
Size of MCB for Branch Circuit-1:
Total
Breaking
Size of MCB Class of
Brach Circuit Capacity of Pole of MCB
Current (Amp) MCB
MCB
(Amp)
circuit-1 0.73 6 Amp B Class 6KA SP
circuit-2 1.04 6 Amp B Class 6KA SP
circuit-3 0.87 6 Amp B Class 6KA SP
circuit-4 1.15 6 Amp B Class 6KA SP
circuit-5 1.39 6 Amp B Class 6KA SP
circuit-6 4.43 16 Amp C Class 6KA SP
circuit-7 7.83 16 Amp C Class 6KA SP
circuit-8 0.63 16 Amp C Class 10KA TP
Total 18.04
To Balance Load We need to try distribute Single Phase load on each Phase.
Suppose We connect Branch Circuit load on following Phase