You are on page 1of 5

>>> By William P. Bahnfleth, PhD, PE & Eric B.

Peyer

Varying Views
on Variable-Primary Flow
C H I L L E D - W A T E R S Y S T E M S

V
Variable -primary flow sur- ariable-primary flow chilled-water systems are of
much current interest. It has been suggested that
the primary/secondary chilled-water system con-
vey of designers, chiller cept has outlived its lifespan and that variable-pri-
mary flow is the answer to the problems that have led to its
“demise”. 1 This view is not universally held and certainly de-
manufacturers, and sys- serves close scrutiny before it is accepted. As part of a recent re-
search project investigating variable-primary flow systems, 2
the authors summarized available literature and conducted
tem users surveys and interviews of designers (43), chiller manufacturers
(4), and system owner/operators (8). This article presents se-
lected findings of this state-of-the-art review.

WHAT IS VARIABLE-PRIMARY FLOW?


For several decades, most large chilled water systems have
used primary/secondary pumping. A highly simplified
schematic of a primary/secondary system is shown in Figure 1.
Hydraulically, the system is com-
prised of two independent circuits
Secondary pumps separated by a decoupling bypass
pipe, through which water may flow
freely in either direction. On the pri-
mary (plant) side of the system,

Chiller Chiller Load Load A member of HPAC Engineering’s


Editorial Advisory Board, William P.
Bahnfleth PhD, PE, is an associate
Decoupling professor and director of the Indoor En-
bypass vironment Center in the Department
of Architectural Engineering at Penn
State University in University Park,
Primary
Pa. He can be reached at wbahn-
pumps fleth@psu.edu. Eric Peyer, an engi-
neer with Grumman/Butkus Assoc. in
Evanston, IL., can be reached at
FIGURE 1. Schematic of primary/secondary system. EBP@grummanbutkus.com

March 2004 CHILLED WATER ENGINEERING S5


C H I L L E D W A T E R E N G I N E E R I N G

less than the sum of the design


flows of operating chillers. In a
System pump(s) primary/secondary system, this
scenario would result in excess
primary flow and recirculation
from supply to return through
the bypass. This excess primary
Chiller 1 Chiller 2 Load 1 Load 2 flow does not occur in a variable-
primary flow system except
when cooling load is so low that
the bypass must open. Energy
Low-flow savings are also possible when
bypass
conditions permit flow to one or
more chillers to exceed design
flow. This is possible when the
system flow is within the sum of
the maximum flows of the active
chillers and cooling load is less
FIGURE 2. Schematic of a primary-only, variable-primary flow system. than or equal to the sum of their
capacities. In this case, chilled
pumps typically operating at pass as shown. This bypass is water pumping energy may not
constant speed are matched to normally closed and opens only be saved, but auxiliary energy
design evaporator flow rates of under low load conditions to en- consumption of cooling tower
the chillers. Primary flow occurs sure that minimum flow is fans and condenser water pumps
in steps as chillers are staged on maintained through the evapo- is saved if variable flow prevents
and off. On the secondary rators of operating chillers. the starting of an additional
(load) side of the system, pumps chiller.
typically operating at variable BENEFITS AND COSTS The first cost of a primary-
speed maintain a differential Proponents of variable-pri- only variable-primary flow plant
pressure set point at a hydrauli- mary flow systems point to three is likely to be lower than that of
cally remote location in the dis- main potential benefits of this a primary/secondary plant sim-
tribution system, while control system type relative to the pri- ply because two sets of pumps
valves modulate the flow of wa- mary/secondary system: energy are replaced with one.
ter as required to meet the cool- and operating cost savings, first The capacity produced by a
ing load. cost savings, and better ability to chiller is proportional to the
Variable-primary flow chilled- tolerate below-design chilled wa- product of the evaporator flow
water plants permit variation in ter temperature differentials. rate and the temperature differ-
evaporator-water flow rate to Energy savings are possible ence of entering and leaving
match the demand for flow of a whenever the secondary flow is chilled water. “Low ∆T syn-
variable-flow distribution
system. Consequently, it
is not necessary to have 2.0
separate primary and sec- 1.5
Percent design flow rate
Percent difference, KW per ton

ondary circuits, and only a 120


1.0 80
single set of pumps is re- 60
quired. A simple primary- 0.5 40
only, variable-primary
flow system is shown 0.0
schematically in Figure 2. -0.5
As in the primary/second-
-1.0
ary system, chilled water
flow rate is controlled to -1.5
meet the cooling load, and -2.0
variable-speed pumps 100 80 60 40 20
control differential pres- Percent design load
sure at a remote location
in the distribution system.
A variable-primary flow FIGURE 3. Chiller part-load performance (KW per ton) for various combinations of
system should have a by- flow rate and chilled-water temperature difference.4

S6 CHILLED WATER ENGINEERING March 2004


C H I L L E D W A T E R E N G I N E E R I N G

# of
flow are important application
Description respondents considerations. SYSTEM CONTROL
Flow rate ranges are deter- Successful system control in a
Energy savings/ mined by maximum and mini- variable-primary flow system re-
reduced 12 mum tube velocity limitations. quires working within the limi-
operating costs
A typical range is 3 to 12 ft per tations of system components to
Lower first cost 11 sec, although newer tube de- adjust flow and chiller capacity
signs may be capable of even to changing load conditions.
Less space 8 lower minimum velocities in The greatest risk to a variable-
required
the 1.5-ft-per-sec range. Maxi- primary flow system is a sudden
Minimize mum and minimum flows for a drop in flow rate when a new
number of
6 particular machine depend on chiller is started and flow is di-
chillers on line where the design tube velocity is verted from the evaporators of
and KW/ton
selected within this range. active chillers to the evaporator
Simplicity 4 Clearly, maximum turndown of the starting chiller.
cannot be lower than roughly For example, suppose that a
Owner 2 25 percent. In a plant with two variable-primary flow plant is
preference
or more chillers, this allows pri- just meeting a 50-percent cool-
TABLE 1. Survey respondents’ mary flow to vary over most of ing load with one of two identi-
reasons for using variable- the hours of a typical cooling cal chillers. Further increase of
primary flow. season. the load will require the addition
Manufacturers differ greatly of the second chiller. If its isola-
drome” can be a serious problem in their allowances for maxi- tion valve is opened,
for primary/secondary systems mum rate of change. These var- there will be a rapid re- # of
with constant primary flow be- ied from “not recommended” duction of flow Description respondents
cause it is not possible to reach for some models to as much as through the active
full chiller capacity, unless design 30 percent of design per minute chiller by as much as Lack of
∆T is available. Variable-pri- for others. One manufacturer 50 percent that is guidance/support from 13
mary flow controls permit flow recommends slower flow modu- likely to cause the ac- manufacturers
through evaporators to be in- lation for systems with shorter tive chiller to shut and literature
creased above design value, mak- “turnover time” (i.e., the time re- down. To prevent this Recent
ing it possible to adjust to less quired to circulate the entire vol- problem, the capacity technology 7
than ideal chilled-water return ume of the piping system of active chillers /unproven
temperatures. through the primary pumps). should be limited Concerned
The major challenges of vari- Absorption chillers can be used prior to staging and about chiller 5
able-primary flow are control in variable-primary flow applica- the isolation valve for performance
complexity and stability. Pri- tions, although their ability to the added chiller Have not found
mary/secondary system chiller accommodate high flow rate should open slowly. right client/ 4
staging sequences are relatively variations is not as good as that 5
Eppelheimer gives a application
simple, well understood, and do of vapor-compression chillers. detailed discussion of Complexity 4
not pose a serious challenge to The effect of evaporator-flow this issue that includes
the controls of packaged chillers. variation on the energy con- a comparison with Unfamiliarity 3
Variable-primary flow chiller sumption of chillers is also of in- chiller staging in pri- with the system
staging requires more care so terest to those considering the mary/secondary sys-
TABLE 2. Survey respondents’
that chillers are not inadvertently use of variable-primary flow. tems. He notes that
reasons for not using variable-
shut down during simultaneous Published research and data pro- the decoupling of pri-
primary flow.
flow and load changes. The de- vided by manufacturers indi- mary and secondary
signer must also understand and cates that to a first approxima- circuits makes it possible to
properly apply low flow bypass tion, the energy use maintain design flow in the ac-
controls. characteristics of constant speed tive chiller during staging, with
drive vapor compression chillers excess primary flow recirculating
HARDWARE ISSUES are not affected by flow varia- through the bypass.
The key component perform- tion.3,4 Figure 3 shows variation Control of the low flow by-
ance issue for variable-primary in energy consumption (KW per pass is also a potential concern.
flow systems is the ability of ton) of a chiller as both load and The bypass should operate when
chillers to respond to changes in evaporator flow rate are varied. one chiller is online and system
flow. The minimum and maxi- Energy use is within ±2 percent flow is lower than its minimum
mum chilled water flow rates of design in all cases and within flow. Modulation of the bypass
and maximum rate of change of ±1 percent in most cases. valve is controlled by the flow or

March 2004 CHILLED WATER ENGINEERING S7


C H I L L E D W A T E R E N G I N E E R I N G

pressure difference measured across the which is the minimum control head of signers, owner/operators, and manufac-
evaporator of the chiller. The valve, how- the system. An alternative to this ap- turers revealed a wide variety of experi-
ever, can be located almost anywhere in proach is to use a limited number of ence and opinion regarding the use of
the system, so it must be capable of func- three-way valves in the system to ensure
variable-primary flow. Roughly half of
tioning under the range of differential that system flow is always at or above the
the designers surveyed had some level of
pressure that it will experience.6 The chiller minimum. variable-primary flow experience. This
most critical constraint is that the bypass should not be taken as an indication of
valve be able to pass its maximum flow at ATTITUDES the proportion of all designers who are
the lowest possible pressure differential, Surveys of chilled-water-system de- currently applying variable-primary flow
concepts, but it does show that a variety
of engineers are utilizing this approach.
Reasons given for survey respondents’
decisions to use or not use variable-pri-
mary flow are shown in tables 1 and 2,
respectively. It is interesting to note that
simplicity was identified as a reason for
using variable-primary flow by those
with experience, while complexity was
cited as a negative factor by those with-
out experience. Those who favored vari-
able-primary flow focused on the bene-
fits to the owner, while those who were
not using it focused on the lack of de-
tailed information on how to apply it
and its relatively short track record.
Claims that technical support for vari-
able-primary flow from manufacturers
and in published literature is lacking are
somewhat contradicted by a growing
body of bulletins and articles (e.g.,
Schwedler and Bradley 7,8 ) that provide
specific guidance on variable-primary
flow system design. Well-documented
case studies, however, are still in short
supply.
By far, most of the variable-primary
flow systems designed by survey respon-

Chiller # of
selection
respondents
criteria

Velocity or
flow limits 14

Evaporator
water-side 6
pressure drop

Internal chiller
controls capable 4
of VPF

Rate of change 2
for flow rates

No particular
criteria specific 1
to VPF

TABLE 3. Variable primary flow


chiller selection criteria.
Circle 180

S8 CHILLED WATER ENGINEERING March 2004


C H I L L E D W A T E R E N G I N E E R I N G

dents were primary-only systems be- type that should lead to continued
cause of the first-cost advantage of that growth in its use in the future.
type of system. Respondents reported
having successfully applied variable-pri- ACKNOWLEDGMENT
mary flow to systems with water-cooled Survey data presented in this article
and air-cooled vapor-compression were collected as part of research project
chillers, as well as with absorption 611-20070 sponsored by the Air-Con-
chillers. When asked which chiller selec- ditioning and Refrigeration Technology
tion issues were of the greatest impor- Institute (ARTI) under its HVAC&R
tance, they gave the responses summa- Research for the 21st Century (21CR)
rized in table 3. Owners and operators of program.
systems who participated in the survey
had few negative comments to offer on
their experiences. Owners claimed that REFERENCES
conversion of their systems to variable- 1) Kirsner, W. (1996, November).
primary flow had resolved low ∆T prob- The demise of the primary-secondary
lems and reduced energy use. Most of pumping paradigm for chilled water
those surveyed would choose variable- plant design. HPAC Engineering, pp
primary flow systems in the future. This 73-79.
does not mean that variable-primary 2) Bahnfleth, W., & Peyer, E.
flow systems have not experienced prob- (2004). Variable-primary flow chilled
lems, but it does provide evidence that water systems: potential benefits and ap-
successful variable-primary flow systems plication issues. Final Report to the
are being built. Air-Conditioning and Refrigeration
Technology Institute (under review).
PERFORMANCE Arlington, VA.: ARI
Documentation of the energy- and 3) Redden, G. H. (1996). Effect of
cost-saving potential of variable-primary variable flow on centrifugal chiller
flow systems is not plentiful and based performance. ASHRAE Transactions,
mainly on simulation. These studies 102 (2), 684-687.
show significant reductions in pump en- 4) Berry, F. (2000). Personal com-
ergy savings and good economic per- munication.
formance. 7,9,10 Simulations have also 5) Eppelheimer, D. (1996). Vari-
demonstrated some key characteristics able flow—the quest for system en-
of variable-primary flow system behav- ergy efficiency. ASHRAE Transactions,
ior. Of particular importance is the rap- 102 (2), 673-678.
idly diminishing pump energy savings 6) Taylor, S. (2002, July). Piping
for variable-primary flow as the number chillers to variable volume chilled wa-
of parallel chillers in a plant increases be- ter systems. ASHRAE Journal, 36 (7),
cause the increments of flow possible in a 43-45.
primary/secondary plant become 7) Schwedler, M. & Bradley, B.
smaller and more nearly continuous. (2000, April). Variable-primary-flow
However, the promise of simulated per- systems. HPAC Engineering, pp 41-
formance needs to be confirmed by 44.
more and more rigorous, detailed meas- 8) Schwedler, M. & Bradley, B.
urements taken from actual systems. (2003, March). Variable-primary flow
in chilled-water systems. HPAC Engi-
CONCLUSION neering, pp 37-45.
Variable-primary flow chilled water 9) Bahnfleth, W. & Peyer, E. (2001,
systems may, in appropriate applica- May). Comparative analysis of vari-
tions, reduce both first cost and operat- able and constant primary-flow
ing cost relative to primary/secondary chilled-water-plant performance.
systems. Improved packaged chiller con- HPAC Engineering, pp 41-50.
trols make many current model chillers 10) Bellenger, L. (2003, Septem-
suitable for variable-primary flow appli- ber). Revisiting chiller retrofits to re-
cation. Designers of variable-primary place constant volume pumps. HPAC
flow systems are developing a record of Engineering, pp 75-76, 78-80, 82, 84,
success and experience with this system 86, 116.

Circle 152
March 2004 CHILLED WATER ENGINEERING S9

You might also like