You are on page 1of 2

PIPING DRAWING OF MAKE-UP WATER PUMP HOUSE AT MARODA-I

(BSP/VL/10/078A/15/004/01/DE/00017(SHT-1TO 4)

MECON COMMENTS VOLTAS REPLY


All tying dimension and levels of VOLTAS indicated in the revised drawings.
MWPH shall be confirmed as per
civil drawings of previous
contractor
All piping and equipment’s shall VOLTAS indicated in the revised drawings.
be highlighted and civil work
which are not in scope of M/S
VOLTAS shall be fainted.
Support of valves shall be VOLTAS confirmed and is indicated in
provided below the valve body NOTE in the revised drawing.
as per site condition.
Separate drawing for electrical The electrical related routing e.g. conduit
portion including shall be connections, cable trench details etc. is
submitted. indicated in drawing no.
BSP/VL/10/078A/15/005/03/DE/03005
Separate drawing for ventilation Ventilation duct routing is indicated in
system shall be submitted. drawing no……………..
Drain pumps with submersible Presently VOLTAS kept hold of this
pump opening in grating shall be portion. After getting the pump details
shown. the same will be provided.
Recirculation line to be routed VOLTAS incorporated in their revised
up to outside of channel. By- drawing,
pass arrangement shall be BSP/VL/10/078A/15/004/01/DE/00004
provided as per approved P&ID. sh-01
Drain pumps and valves shall be Presently VOLTAS kept hold of this
shown. portion. After getting the pump details
the same will be provided.
Ventilation ducting system shall Ventilation duct routing to be submitted
be shown. in separate drawing.

Page 1 of 2
PIPING DRAWING OF MAKE-UP WATER PUMP HOUSE AT MARODA-I
(BSP/VL/10/078A/15/004/01/DE/00017(SHT-1TO 4)

MECON COMMENTS VOLTAS REPLY

Material handling facilities and VOLTAS incorporated the same in their


it`s operation and maintenance revised drawing.
platform (long & cross travel) BSP/VL/10/078A/15/004/01/DE/00004
shall be shown. sh-02 , 03, 04
Space below the bel mouth shall Voltas indicated the same in revised
be provided. drawing
BSP/VL/10/078A/15/004/01/DE/00004
sheet no. 03
Detail of valve operating Voltas indicated the same in revised
platform (dimension & level) drawing
shall be indicated. BSP/VL/10/078A/15/004/01/DE/00004
sheet no. 03
Spool piece between reducer Voltas indicated the same in revised
and expansion bellow shall be drawing
provided. BSP/VL/10/078A/15/004/01/DE/00004
sheet no. 03
Main header size shall be DN Voltas indicated the same in revised
900 size for flow measuring drawing
element. BSP/VL/10/078A/15/004/01/DE/00004
sheet no. 03
Approach to valve operation Voltas indicated the same in revised
platform to be shown. drawing
BSP/VL/10/078A/15/004/01/DE/00004
sheet no. 03 and sheet no. 04