Zelio Control

EIO0000001301 09/2012

Zelio Control
REG Communication and ZelioControl
Soft Installation
User Guide
09/2012
EIO0000001301.00

www.schneider-electric.com
Schneider Electric assumes no responsibility for any errors that may appear in this
document. If you have any suggestions for improvements or amendments or have
found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic
or mechanical, including photocopying, without express written permission of
Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when
installing and using this product. For reasons of safety and to help ensure
compliance with documented system data, only the manufacturer should perform
repairs to components.
When devices are used for applications with technical safety requirements, the
relevant instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware
products may result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2012 Schneider Electric. All rights reserved.

2 EIO0000001301 09/2012
Table of Contents

Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Part I Software Configuration . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 1 Software Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
How to install ZelioControl Soft and Equipment . . . . . . . . . . . . . . . . . . . . 12
Connect and Load ZelioControl Soft . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
How to Use ZelioControl Soft . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
How to Save the Controller Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Part II Communication Modbus . . . . . . . . . . . . . . . . . . . . . . 25
Chapter 2 Communication Modbus . . . . . . . . . . . . . . . . . . . . . . . . . 27
Integration in a Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Chapter 3 Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
RS-485 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
List of Setting Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Parameters Setting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Address Map and Data Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Part III Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Chapter 4 Data Address Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4.1 Mapping Modbus of REG24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Discrete Input Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Holding Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Input Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
4.2 Mapping Modbus of REG48/REG96 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Discrete Input Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Holding Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Input Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

EIO0000001301 09/2012 3
4 EIO0000001301 09/2012
Safety Information
§

Important Information

NOTICE
Read these instructions carefully, and look at the equipment to become familiar with
the device before trying to install, operate, or maintain it. The following special
messages may appear throughout this documentation or on the equipment to warn
of potential hazards or to call attention to information that clarifies or simplifies a
procedure.

EIO0000001301 09/2012 5
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by
qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction
and operation of electrical equipment and the installation, and has received safety
training to recognize and avoid the hazards involved.

6 EIO0000001301 09/2012
About the Book

At a Glance

Document Scope
This manual will acquaint you with the PC loader software which can work with
REG24, REG48 and REG96. The ZelioControl Soft is an auxiliary tool for setting
parameters and tuning the temperature controller. The setting conditions can be
edited and saved with this software. By setting, editing and saving parameters on
your PC, the setting can be copied to multiple temperature controllers. The PV, SV
and MV can also be displayed the trend on the software and do data logging in csv
format. There are 2 versions of Zelio Control Soft. Version 1.6 and Version 2.1 (new
version).

Validity Note
This document is valid for the ZelioControl Soft v2.1 and the Temperature
Controllers (REG24, REG48, and REG96)
Registered Trademarks
Microsoft® and Windows® are registered trademarks of Microsoft Corporation.

EIO0000001301 09/2012 7
Related Documents

Title of Documentation Reference Number


Zelio Control, REG24 Temperature Controller User Guide EIO0000001300 (Eng),
EIO0000001303 (Fre),
EIO0000001306 (Ger),
EIO0000001332 (Ita),
EIO0000001335 (Spa),
EIO0000001338 (Chs)
Zelio Control, REG48/96 Temperature Controller User Guide EIO0000001299 (Eng),
EIO0000001302 (Fre),
EIO0000001305 (Ger),
EIO0000001331 (Ita),
EIO0000001334 (Spa),
EIO0000001337 (Chs)
Zelio Control Soft 2.1 Instruction Manual HRB3446500 (Supply with
ZelioControl Soft v2.1)

You can download these technical publications and other technical information from
our website at www.schneider-electric.com.

User Comments
We welcome your comments about this document. You can reach us by e-mail at
techcomm@schneider-electric.com.

8 EIO0000001301 09/2012
Zelio Control
Software Configuration
EIO0000001301 09/2012

Software Configuration

EIO0000001301 09/2012 9
Software Configuration

10 EIO0000001301 09/2012
Zelio Control
Software Tools
EIO0000001301 09/2012

Software Tools

1
What Is in This Chapter?
This chapter contains the following topics:
Topic Page
How to install ZelioControl Soft and Equipment 12
Connect and Load ZelioControl Soft 14
How to Use ZelioControl Soft 20
How to Save the Controller Parameters 23

EIO0000001301 09/2012 11
Software Tools

How to install ZelioControl Soft and Equipment

Required Operating System


ZelioControl Soft requires one of the following operating systems to be present on
the terminal:
 Windows XP Professional Edition® SP2 and SP3
 Windows 7 Professional Edition® 32 bits system

Other Requirements
The following are required before installing ZelioControl Soft:
 Internet Explorer V6.0 or later
 .NET 4.0 Framework, SP2
 Windows Installer V3.1 or later
 Visual C++ 2008 Runtime

Terminal Configuration ZelioControl Soft V2.1


The following table provides the minimum and recommended terminal character-
istics necessary to install ZelioControl Soft V2.1:

Minimum and recommended terminal configuration with Microsoft Windows XP


Professional Edition with SP3 / Windows 7 Professional Edition_32
RAM 128 MBytes or more recommended
Hard disk space 500 MBytes or more recommended
Operating System Microsoft Windows XP Professional Edition with SP3 / Windows 7
Professional edition 32 bit system
Display SVGA 1024x768 or higher resolution monitor with high color 24 bits
Other USB port on the computer
Microsoft Office Excel
Adobe Acrobat

12 EIO0000001301 09/2012
Software Tools

Downloading and Installing ZelioControl Soft


Before installing the software, please follow the instruction on Zelio Control Soft 2.1
Instruction Manual (see page 8).
Download and install the ZelioControl Soft to your PC:

Step Action
1 Enter the web address for Schneider Electric (www.schneider-electric.com) in
an Internet browser.
2 In the Search from input field, enter the phrase ZelioControl Soft and press
Enter.
3 Examine the search results and select the appropriate entry for the ZelioControl
Soft.
4 Follow the on-screen instructions to download both the ZelioControl installation
software.
5 Run the setup file (ZelioControl Soft V2.1.exe) and follow the instructions (on
the screen and in the downloaded documentation) to install ZelioControl Soft.

NOTE: The communication between a computer and a controller is performed with


the TWDXCAFJ010 and the VW3A8118.
The driver VW3A8118_Drivers.exe for the converter is needed. The previous
procedure can be used to retreive the VW3A8118 driver.

Modbus Communication Accessories


The following table shows the accessories for modbus communication:

Part Number Description


TWDXCAFJ010 1 x RJ45 connector and 1 end with flying leads
VW3A8118 USB to RJ45 converter
TWDXCAISO Isolated RS-485 T-junction box
TWDXCAT3RJ T-junction box
LU9GC3 Modbus splitter box

EIO0000001301 09/2012 13
Software Tools

Connect and Load ZelioControl Soft

Prepare and load ZelioControl Soft

Step Action
1 Install the driver of the VW3A8118 and the ZelioControl Soft v2.1 (see page 13)
NOTE: The correct adapter driver needs to be installed before connecting the PC to the module. Use
the Schneider Electric website (www.schneider-electric.com) to download the latest version of the
adapter driver.
2 Plug the VW3A8118 converter to your computer.

14 EIO0000001301 09/2012
Software Tools

Step Action
3 Connect the TWDXCAFJ010 Ethernet cable to the VW3A8118 converter.

NOTE: Performing a Parameters Copy with ZelioControl Soft v2.1 can be done with up to 31 units
can be connected at the same time through the serial communication.
4 Connect the TWDXCAFJ010 Ethernet cable to the REG terminal block:

RJ45

+
RS-485

The pin assigment depends on the controller:

EIO0000001301 09/2012 15
Software Tools

Step Action
5 Use a ring clamp EMC near connection to have a correct grounding:

6 Load ZelioControl Soft.


The following flash screen appears:

ZelioControl Soft

© Schneider Electric Industries


1131-1411-8516-7348-8585

16 EIO0000001301 09/2012
Software Tools

Step Action
7 The following Mode select dialog box appears:

Select one of each mode:


 Initial values startup mode(N)
 The project start with all the parameters at initial value.

 File selection startup mode(O)


 A configuration file (.red) previously saved can be used.

 REG data reception launch mode(D)


If Connection Designation(M)
 is not selected the program scanned the station number 0 to 31. Each parameters of the
connected station are read automatically.
 is selected the program scanned the station number selected. Each parameters of a selected
station are read automatically.

EIO0000001301 09/2012 17
Software Tools

Step Action
8 After selecting the mode the Properties dialog Box appears:

NOTE: To start with ZelioControl Soft set as follow:


 Port No.: select the correct COM port
 Baudrate: 19200 bps
 Parity: Even
 Online/Offline: Online
 Data lenght: use default value
 Stop bit: use default value
 Online/Offline: Online

18 EIO0000001301 09/2012
Software Tools

Step Action
9 The main screen appears:

1 Parameter tree view


2 Parameter setting view
3 Selection tabs

EIO0000001301 09/2012 19
Software Tools

How to Use ZelioControl Soft

Overview
There are three main tabs available in the main screen:
 Setting
 Report
 Monitoring

Setting Tab: Configure Parameters


A parameter tree is displayed on the left and setting a parameter can be made on
the right field.

1 Parameter tree: Show the type of the model and the parameters are shown.
2 Parameter setting view: Show the controller parameters set values and station number.
3 Selection tabs
For more details refer to Zelio Control Soft 2.1 Instruction Manual (see page 8).

20 EIO0000001301 09/2012
Software Tools

Report Tab: Saving Parameters Setting


All parameters setting can be printed, saved or displayed in .csv or .html format.
The following procedure explains how to save/print the parameters setting:

Step Action
1 Click on the Report tab:

1 Report tab
2 Report option
2 Select:
 Save report as CSV...
 Save report as HTML...
 Print...

3 Name the file and select the folder to save the report.
4 Click Save to confirm your choice.

For more details refer to Zelio Control Soft 2.1 Instruction Manual (see page 8).

EIO0000001301 09/2012 21
Software Tools

Monitoring Tab: Trend display of PV, SV and MV.


The figure below shows the monitoring tab configuration:

When pressing the Start button the data monitoring begin. The Trend Display
button is used to show is real time the PV, SV and MV data.
NOTE: After pressing the Stop button, the values of the monitored data can be
saved (Save button) in a .csv file.
For more details refer to Zelio Control Soft 2.1 Instruction Manual (see page 8).

22 EIO0000001301 09/2012
Software Tools

How to Save the Controller Parameters

Overview
The controller parameters can be saved into a file on your computer.
The extension of the file will be .red

Saving Parameters
The following table explains how to save the parameters:

Step Action
1

Click on File →Save


2 Name the file.
NOTE: By default the file is saved on the Desktop. It is possible to choose an
other folder using Save as....
3 Click Save to confirm your choice.

EIO0000001301 09/2012 23
Software Tools

24 EIO0000001301 09/2012
Zelio Control
Communication Modbus
EIO0000001301 09/2012

Communication Modbus

II
What Is in This Part?
This part contains the following chapters:
Chapter Chapter Name Page
2 Communication Modbus 27
3 Functions 29

EIO0000001301 09/2012 25
Communication Modbus

26 EIO0000001301 09/2012
Zelio Control
Communication Modbus
EIO0000001301 09/2012

Communication Modbus

2
Integration in a Network

Overview
The controller is equipped with Modbus slave protocol from the RS-485 interface
and PC loader interface, which enable the transmission and reception of data
between devices such as the personal computer, the programmable controller, and
the graphic panel.
The communication system is composed of a master and slave relationship. Up to
thirty-one slaves (micro controllers) may be connected to one master (such as a
programmable logical controller) based on a "single master/multiple slave" method.
However, the master can only communicate with one slave at a time and is in charge
of managing the link with each device. Therefore, each slave is specified by the
Station No. setting.
In order to have proper communication between master and slave, the transmission
data must be in the same format for all the devices.
Systems constructed with the micro controller as slaves do not respond to
messages issued by the master with broadcast queries where the Station No. is
"0".

EIO0000001301 09/2012 27
Communication Modbus

How to install
The following table explains the procedure of the temperature controller connection
to a Modbus network:

Step Action
1 Connect the VW3A8118 and coaxial cable on the port L1 of the Modbus TAP
(TWDXCAT3RJ) junction. The port L2 is used to connect the temperature controller.
The port L3 is used to connect the port L1 of the second Modbus TAP junction. Use
the switches of the TAP to configure the end line impedance and polarization.
2 Repeat the same operation for each device.
3 For the end line of the last device, the switches of the TAP can be used as the
integrated end line of the device if it is present.
4 Plug the VW3A8118 converter to your computer.

The following figure explains the integration in a network:

RS-485

TWDXCAT3RJ TWDXCAT3RJ TWDXCAT3RJ TWDXCAT3RJ

1 Programmable Controller
2 Zelio Temperature Controller

28 EIO0000001301 09/2012
Zelio Control
Functions
EIO0000001301 09/2012

Functions

3
What Is in This Chapter?
This chapter contains the following topics:
Topic Page
RS-485 Specifications 30
List of Setting Parameters 33
Parameters Setting Procedure 34
Address Map and Data Format 36

EIO0000001301 09/2012 29
Functions

RS-485 Specifications

Recommendation
 Please use a shielded twist pair cable.
 The maximum cable length should be 500m. One master and up to thirty-one
micro controllers (slaves) can be connected per circuit.
 Terminate both ends of the circuit with a terminating resistance of 100 Ohms
(1/2W or more).
 Ground the shielded cable once towards the master side.

Specifications
Specifications of the terminal:

Item Specifications
Electrical specifications EIA RS-485 compliant
Communication method Two wire system, half double-bit serial
Synchronous method Asynchronous
Max No. of connections 31 units
Communication distance Max 500 m (total length)
Communication speed 9600 and 19200 bps
Data format  Data length: 8 bits
 Stop bit: 1 bit
 Parity: None / Even / Odd (selectable)

Transmission code HEX value (MODBUS RTU mode)


Error detection CRC-16
Insulation Functional Insulation for the transmission area and other areas
(withstanding 500 Vac)

30 EIO0000001301 09/2012
Functions

Wiring Principle
This following figure explains the principle of wiring:

1
4

+ 3
+



SG
5

+
7

+
6

1 Master
2 VW3A8118 Polarization Switch (terminating resistance - 100W (1/2W))
3 Shielded twist per cable
4 Slave
5 Zelio Temperature Controller
6 Terminating Resistance - 100W (1/2W)
7 RS-485 Interface or RS-485 Side of VW3A8118
NOTE: SG does not have to be connected, but it can be used as an effective
countermeasure against detected communication errors due to electromagnetic
interference.

EIO0000001301 09/2012 31
Functions

Electromagnetic Interference Filter Utilization


When using the controller in an area where the imposed electromagnetic
interference level is expected to exceed 1000V, we recommend using an
electromagnetic interference filter on the master side as seen in the figure below.
The following figure represents the wiring with the electromagnetic interference filter
(recommended ZRAC2203-11, made by TDK Corporation):

RS-485

3
1 Programmable Controller or Personal Computer
2 Electromagnetic Interference Filter
3 Zelio Temperature Controller
NOTE:
 If there are problems with EMC during communication, the electromagnetic
interference level can be reduced by using communication cable with a ferrite
core.
 Ferrite Core recommended:
 ZCAT series, made by TDK Corporation.
 MSCF series, made by Morimiya Electric Co., Ltd.

32 EIO0000001301 09/2012
Functions

List of Setting Parameters

Overview
The setting parameters are shown in the chart below. Change the settings using the
keys on the front of the micro controller.

RS-485 Parameters
For the :

Display Parameter Name Function Setting Range Remarks


STno Station No. Set the station number. 1 to 247 RST
NOTE: Need to restart the
(11)
controller once station No.
change.
CoM Baud Rate / Sets the baud rate and parity 96od (9600 bps/odd) RST
Parity setting check. 96ev (9600 bps/even)
96no (9600 bps/non)
19od (19200 bps/odd)
19ev (Default)
(19200 bps/even)
19no (19200 bps/none)
SCC Communication Sets wheter or not overwriting r (read only) RST
permissions is possible from the master rW (read and write)
side (PC and etc.)
11 Station number No 32 to No 247 is forbidden to use. Maximum up to 31 units can be connected only.

Loader Interface Parameters


The parameters do not need to be set. Set the loader software (master) with the
following settings:
 Communication speed: 19200 bps
 Parity: even

NOTE: These two parameters depend on the chosen configuration.

EIO0000001301 09/2012 33
Functions

Parameters Setting Procedure

Procedure
The following steps explain how to change the settings to station number "3", parity
setting "9600bps/none", and communication permissions "read and write" as an
example.

Step Action Remarks


1 Press and hold the key to display . The MV1 of the monitoring screen is displayed.

2 Press and hold the key to display the setup The communication menu is displayed.

mode operation menu , then use the


keys to display .

3 Press and hold the key, then use the The station number is displayed.

keys to display .

4 Press the key, then use the keys to This sets the parameter to "3".
set station number to "3" when the bottom part of the
display begins to blink.
5 Press the key to confirm the setting. -

6 Use the keys to select the parity setting -

.
7 Press the key, then use the keys to The parity setting is set to "9600 bps/none".
set the parity setting to "96no" when the bottom part
of the display begins to blink.
8 Press the key to confirm the setting. -

9 Use the keys to select the communication -


permissions .

10 Press the key, then use the keys to "read/write" is selected.


set the protocol to "rW" when the bottom part of the
display begins to blink.
11 Press the key to confirm the setting. -

34 EIO0000001301 09/2012
Functions

Step Action Remarks


12 Press the key to return to the operation -

mode PV/SV display.


13 Turn the power to the micro controller off and on The changes to the communication parameters
again. become effective after the power turns off and on
again.

EIO0000001301 09/2012 35
Functions

Address Map and Data Format

Function Codes Supported


For MODBUS protocol, coil numbers or register numbers are assigned by the
function code, and each function code only works for the assigned coil number or
register number.
The correspondence between the function code and the coil number or register
number is as follows:

The message length for each function is as follows:

Code Contents Assignable Command Message Response Message


Data Number Minimum Maximum Minimum Maximum
02H Read bit data (read-only) 8 bit 8 8 6 6
03H Read word data 60 words 8 8 7 125
04H Read word data (read-only) 37 words 8 8 7 79
06H Write word data 1 word 8 8 8 8
10H Continuously write word data 60 words 11 129 8 8

NOTE: "Assignable Data Number" above is limited by the data number that is
assigned by the micro controller to the coil number or address number (excluding
function code 06H).

Sent Data Format


The MODBUS protocol used by this equipment employs RTU (Remote Terminal
Unit) mode. The data is sent as "numerical value", not as ASCII code.

36 EIO0000001301 09/2012
Functions

Internal Calculation Value and Engineering Unit


In this unit, parameter data and data dependent of an input range can handle the
two following types of data:
 Internal Calculation Value:
 Values listed as percentage of the input range (0.00...100.00, without decimal
point).
 Engineering Unit:
 Values subjected to scaling to actual values depending on the input range.
Engineering Unit address = 1000 + Internal Calculation Value address
Example: the value is calculated as follows when the full scale is 400° C and the PV
value is "150".

Class Register Number Data (HEX) Data


Internal Calculation 30001 0EA6H 3750 (37,5%)
Value
Engineering Unit 31001 0096H 150

The PV value is received as follows: 37.50 (%) x 400 (full scale ° C) = 150 ° C
The Internal Calculation Value will be the same as the Engineering Unit:
 If the parameter is not depend of an input range
 with Discrete Input Register.

NOTE: Pay attention to the position of the decimal point when changing the input
range by writing with communication. When changing the position of the decimal
point by writing with communication, change the lower limit and upper limit of the
input range at the same time.

Managing the Decimal Point


Some of the internally stored data may contain digits lower than the decimal point
on the front display. Also, the decimal point is not added to sent data.
Carry out processes for the decimal point position (erasing the decimal point when
sending data and adding the decimal point when receiving data).
Attention must be paid to the position of the decimal point for data where the
parameters are dependent on a range.
NOTE: For more information refer to the Data Address Map (see page 41)

Data During Detected Input Error


For situations such as overrange, underrange, and input breaks where or
display on the front, read PV value becomes 105% or -5% of the input range.
Input errors can be detected via communication using "register number 30008 (or
31008): Input/Unit Error Status".

EIO0000001301 09/2012 37
Functions

Written Data
When writing data to each parameter, set that written data within the range for the
data. Controller can accept written data outside of the range, but do so with care as
correct operations are not guaranteed.

Addresses Not Written

WARNING
UNINTENDED EQUIPMENT OPERATION
Use only the addresses contained in this manual.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

38 EIO0000001301 09/2012
Zelio Control
Appendices
EIO0000001301 09/2012

Appendices

III

EIO0000001301 09/2012 39
Appendices

40 EIO0000001301 09/2012
Zelio Control
Data Address Map
EIO0000001301 09/2012

Data Address Map

4
What Is in This Chapter?
This chapter contains the following sections:
Section Topic Page
4.1 Mapping Modbus of REG24 42
4.2 Mapping Modbus of REG48/REG96 55

EIO0000001301 09/2012 41
Data Address Map

4.1 Mapping Modbus of REG24

What Is in This Section?


This section contains the following topics:
Topic Page
Discrete Input Register 43
Holding Register 44
Input Register 52

42 EIO0000001301 09/2012
Data Address Map

Discrete Input Register

Bit Data (Read only)


The following table represents the address of the Discrete Input Register
(see page 36) parameters accessible using the function code 02H:

Relative address Coil Number Memory Contents Read-out Data


0000H 10001 Alarm 1 ON/OFF  0: Alarm 1 OFF
 1: Alarm 1 ON

0001H 10002 (Reserve) -


0002H 10003 (Reserve) -
0003H 10004 (Reserve) -
0005H 10006 (Reserve) -
0006H 10007 (Reserve) -
0007H 10008 (Reserve) -
0008H 10009 Alarm 1 output (Calculation result of  0: Relay output of Alarm 1 OFF
non-exciting alarm)  1: Relay output of Alarm 1 ON

000CH 10013 Alarm 1 ON/OFF  0: Alarm 1 OFF


 1: Alarm 1 ON

EIO0000001301 09/2012 43
Data Address Map

Holding Register

Overview
Handles data dependent on an input range as an internal value before scaling
(0.00...100.00%).

Word Data (Read/Write)


The following table represents the Internal parameters address map (first line the
Internal Calculation Value and second line the Engineering Unit value).
The following table represents the addresses of the Holding Registers
(see page 36) parameters accessible using the function code 03H, 06H, 10H:

Parameters Relative Register Description Read-out Data Write-in Data Factory Dependent
Name address Number default on Range
Setting
- 0000H 40001 Non-volatile 0: Not writing-in 0: No Write-in -
03E8H 41001 memory write-in 1: Writing in request
memory 1: Request to
write in
CTrL 0001H 40002 Control methods 0: PiD (PID control) 0 -
03E9H 41002 selection 1: FUZY (Fuzzy Pid control)
2: SELF (Self-tuning control)
SV 0002H 40003 Front SV set 0...10000 (within 0.00...100.00% FS 0.0 O
03EAH 41003 value within set value limits)
STbY 0003H 40004 Switches 0: oFF (during RUN) oFF -
03EBH 41004 between RUN 1: on (during standby)
and standby
AT 0004H 40005 Auto tuning 0: Auto tuning 0: Disable auto 0 -
03ECH 41005 command disabled tuning
1: While 1: Request
executing execution of
standard type standard type
AT executed 2: Request
2: While execution of low
executing low PV type AT
PV type AT
executed
P 0005H 40006 Proportional 0...9999 (0.0...999.9%) 5.0 -
03EDH 41006 band
i 0006H 40007 Integration time 0...32000 (0...3200.0 sec.) 240 -
03EEH 41007
D 0007H 40008 Derivative time 0...9999 (0.0...999.9 sec.) 60.0 -
03EFH 41008

44 EIO0000001301 09/2012
Data Address Map

Parameters Relative Register Description Read-out Data Write-in Data Factory Dependent
Name address Number default on Range
Setting
HyS 0008H 40009 ON/OFF control 0...5000 (0.00...50.00%FS) 1 O
03F0H 41009 hysteresis
CooL 0009H 40010 Cooling 0...1000 (0.0...100.0) 1 -
03F1H 41010 proportional
band coefficient
db 000AH 40011 Dead band -5000...5000 (-50.00...+50.00%) 0.0 -
03F2H 41011
Ar 000BH 40012 Anti-reset 0...10000 (0.00...100.00% FS) 100 O
03F3H 41012 windup
bAL 000CH 40013 Output -10000...10000 (-100.00...100.00% 0.0 -
03F4H 41013 convergence FS)
value
PvoF 000DH 40014 PV input shift -1000...1000 (-10.00...10.00%FS) 0 O
03F5H 41014
SvoF 000EH 40015 SV offset -5000...5000 (-50.00...50.00%FS) - O
03F6H 41015
P-n2 000FH 40016 Input type code 0 to 16 - -
03F7H 41016
P-F 0010H 40017 Temperature unit  0: ° C 0 -
03F8H 41017  1: ° F

P-SL 0011H 40018 Input scale lower -1999...9999 ° C - -


03F9H 41018 limit
P-SU 0012H 40019 Input scale upper -1999...9999 ° C - -
03FAH 41019 limit
P-dP 0013H 40020 Decimal point 0 to 2 0 -
03FBH 41020 place
- 0014H 40021 (Do not use) -
03FCH 41021
P-dF 0015H 40022 Input filter time 0...900 (0.0...900.0 sec.) -
03FDH 41022 constant
rCJ 0016H 40023 RCJ yes/no  Disable RCJ compensation (do -
03EEH 41023 not perform reference cold
junction compensation)
 Enable RCJ compensation
(perform reference cold junction
compensation)
PCUT 0017H 40024 MV limit kind 0 to 15 -
03FFH 41024

EIO0000001301 09/2012 45
Data Address Map

Parameters Relative Register Description Read-out Data Write-in Data Factory Dependent
Name address Number default on Range
Setting
PLC1 0018H 40025 Output 1 lower -300...10300 (-3.00...103.00%) O
0400H 41025 limit
PHC1 0019H 40026 Output 1 upper -300...10300 (-3.00...103.00%) O
0401H 41026 limit
PLC2 001AH 40027 Output 2 lower -300...10300 (-3.00...103.00%) -
0402H 41027 limit
PHC2 001BH 40028 Output 2 upper -300...10300 (-3.00...103.00%) -
0403H 41028 limit
- 001CH 40029 (Do not use) - -
0405H 41029
- 001DH 40030 (Do not use) - -
0406H 41030
SV-L 001EH 40031 Set value (SV) 0...10000 (0.00...100.00%FS) O
0407H 41031 lower limit
SV-H 001FH 40032 Set value (SV) 0...10000 (0.00...100.00%FS) O
0408H 41032 upper limit
- 0020H 40033 (Do not use) - -
... ...
040DH 41038
LoC 0027H 40040 Setting lock 0 to 5 0 -
040FH 41040
ALM1 0028H 40041 Alarm 1 type 0 to 31 10 -
0410H 41041
AL1 002BH 40044 Alarm 1 set value For absolute value alarm: 0...10000 10 O
A1-L 0413H 41044 or alarm 1 lower (0.00...100.00%FS)
limit set value For deviation alarm: -10000...10000
(-100.00...100.00%FS)
A1-H 002EH 40047 Alarm 1 upper For absolute value alarm: 0...10000 10 O
0416H 41047 limit set value (0.00...100.00%FS)
For deviation alarm: -10000...10000
(-100.00...100.00%FS)
A1hy 0031H 40050 Alarm 1 0...5000 (0.00...50.00%FS) 0 O
0419H 41050 hysteresis
dLy1 0034H 40053 Alarm 1 ON- 0...9999 (0...9999 sec.) 0 -
041CH 41053 delay set value
- 0037H 40056 (Do not use) - -
041FH 41056

46 EIO0000001301 09/2012
Data Address Map

Parameters Relative Register Description Read-out Data Write-in Data Factory Dependent
Name address Number default on Range
Setting
Sv-1 0038H 40057 Ramp/soak No. 1 0...10000 (0.00...100.00%FS within 0% FS O
0420H 41057 target value set value limit)
Sv-2 0039H 40058 Ramp/soak No. 2
0421H 41058 target value
Sv-3 003AH 40059 Ramp/soak No. 3
0422H 41059 target value
Sv-4 003BH 40060 Ramp/soak No. 4
0423H 41060 target value
Sv-5 003CH 40061 Ramp/soak No. 5
0424H 41061 target value
Sv-6 003DH 40062 Ramp/soak No. 6
0425H 41062 target value
Sv-7 003EH 40063 Ramp/soak No. 7
0426H 41063 target value
Sv-8 003FH 40064 Ramp/soak No. 8
0427H 41064 target value

EIO0000001301 09/2012 47
Data Address Map

Parameters Relative Register Description Read-out Data Write-in Data Factory Dependent
Name address Number default on Range
Setting
TM1r 0040H 40065 Ramp/soak No. 1 0...5999 (0...5999 min.) 0.00 -
0428H 41065 ramp time
TM1S 0041H 40066 Ramp/soak No. 1
0429H 41066 soak time
TM2r 0042H 40067 Ramp/soak No. 2
042AH 41067 ramp time
TM2S 0043H 40068 Ramp/soak No. 2
042BH 41068 soak time
TM3r 0044H 40069 Ramp/soak No. 3
042CH 41069 ramp time
TM3S 0045H 40070 Ramp/soak No. 3
042DH 41070 soak time
TM4r 0046H 40071 Ramp/soak No. 4
042EH 41071 ramp time
TM4S 0047H 40072 Ramp/soak No. 4
042FH 41072 soak time
TM5r 0048H 40073 Ramp/soak No. 5
0430H 41073 ramp time
TM5S 0049H 40074 Ramp/soak No. 5
0431H 41074 soak time
TM6r 004AH 40075 Ramp/soak No. 6
0432H 41075 ramp time
TM6S 004BH 40076 Ramp/soak No. 6
0433H 41076 soak time
TM7r 004CH 40077 Ramp/soak No. 7
0434H 41077 ramp time
TM7S 004DH 40078 Ramp/soak No. 7 -
0435H 41078 soak time
TM8r 004EH 40079 Ramp/soak No. 8 -
0436H 41079 ramp time
TM8S 004FH 40080 Ramp/soak No. 8 -
0437H 41080 soak time
Mod 0050H 40081 Ramp/soak 0 to 15 0 -
0438H 41081 mode

48 EIO0000001301 09/2012
Data Address Map

Parameters Relative Register Description Read-out Data Write-in Data Factory Dependent
Name address Number default on Range
Setting
ProG 0051H 40082 Ramp/soak 0: oFF: 0: oFF: stop 0 -
0439H 41082 command Ramp/soak Ramp/soak
stopped 1: rUn: start
1: rUn: Ramp/soak
Ramp/soak 2: HLd: halt
operated Ramp/soak
2: HLd:
Ramp/soak
halted
3: End:
Ramp/soak
ended
PTn 0052H 40083 Ramp/soak 0: Execute No. 1 to 4 ramp/soak 1 -
043AH 41083 pattern selection (PTn=1)
1: Execute No. 5 to 8 ramp/soak
(PTn=2)
2: Execute No. 1 to 8 ramp/soak
(PTn=3)
- 0053H 40084 (Do not use) - - -
043BH 41084
SLFb 0054H 40085 PV stable range 0...10000 (0.00...100.00%FS) 8 O
043CH 41085
- 0055H 40086 (Do not use) - - -
043DH 41086
Pn-1 0057H 40088 Control action 0 to 3 0 -
043FH 41088 type code
TC 0058H 40089 Output 0: Current output type 30: SSR -
0440H 41089 proportional 1...150 sec.): Relay, SSR drive 2: Relay
cycle (output) output type
- 005AH 40091 (Do not use) - - -
0442H 41091
A1op 005BH 40092 Alarm 1 option 0 to 7 (binary data 000B to 111B) 000 -
0443H 41092 function
onoF 0060H 40097 Hysteresis mode 0: oFF (main unit parameter setting) oFF -
0448H 41097 setting 1: oN (main unit parameter setting)
- 0061H 40098 (Do not use) - - -
0449H 41098
ADJ0 0062H 40099 PV display zero -5000...5000 (-50.00...50.00%FS) 0 O
044AH 41099 adjustment
ADJS 0063H 40100 PV display Splan -5000...5000 (-50.00...50.00%FS) 100 O
044BH 41100 adjustment

EIO0000001301 09/2012 49
Data Address Map

Parameters Relative Register Description Read-out Data Write-in Data Factory Dependent
Name address Number default on Range
Setting
dSP1 0064H 40101 DSP1 0 to 255 - -
044CH 41101 (parameter mask
designation)
dSP2 0065H 40102 DSP2 0 to 255 - -
044DH 41102 (parameter mask
designation)
dSP3 0066H 40103 DSP3 0 to 255 - -
044EH 41103 (parameter mask
designation)
dSP4 0067H 40104 DSP4 0 to 255 - -
044FH 41104 (parameter mask
designation)
dSP5 0068H 40105 DSP5 0 to 255 - -
0450H 41105 (parameter mask
designation)
dSP6 0069H 40106 DSP6 0 to 255 - -
0451H 41106 (parameter mask
designation)
dSP7 006AH 40107 DSP7 0 to 255 - -
0452H 41107 (parameter mask
designation)
dSP8 006BH 40108 DSP8 0 to 255 - -
0453H 41108 (parameter mask
designation)
dSP9 006CH 40109 DSP9 0 to 255 - -
0454H 41109 (parameter mask
designation)
dSP10 006DH 40110 DSP10 0 to 255 - -
0455H 41110 (parameter mask
designation)
dSP11 006EH 40111 DSP11 0 to 255 - -
0456H 41111 (parameter mask
designation)
dSP12 006FH 40112 DSP12 0 to 255 - -
0457H 41112 (parameter mask
designation)
dSP13 0070H 40113 DSP13 0 to 255 - -
0458H 41113 (parameter mask
designation)

50 EIO0000001301 09/2012
Data Address Map

Parameters Relative Register Description Read-out Data Write-in Data Factory Dependent
Name address Number default on Range
Setting
CMod 0074H 40117 Local/remote  0: Local - -
045CH 41117 operation  1: Remote
changeover
rEM0 0075H 40118 Remote SV input -5000...5000 (-50...50% of input 0%FS O
045DH 41118 zero adjustment scale)
rEMS 0076H 40119 Remote SV input -5000...5000 (-50...50% of input 0%FS O
045EH 41119 span adjustment scale)
r-dF 0077H 40120 Remote SV input 0...9000 (0.0...900.0 sec.) - -
045FH 41120 filter time
constant
Legend:
O Range available
- No range available

EIO0000001301 09/2012 51
Data Address Map

Input Register

Overview
Handles data dependent on an input range as an internal value before scaling
(0.00...100.00%).

Word Data (Read/Write)


The following table represents the Internal parameters address map (first line the
Internal Calculation Value and second line the Engineering Unit value).
The following table represents the addresses of the Input Registers (see page 36)
parameters accessible using the function code 04H:

Parameters Relative Register Description Read-out Data Dependent


name address Number on Range
PV 0000H 30001 Process value 0...10000 (0.00...100.00%) O
03E8H 31001
SV 0001H 30002 Currently used set value 0...10000 (0.00...100.00%) O
03E9H 31002 (SV)
DV 0002H 30003 Currently used deviation -10000...10000 (-100.00...100.00%) O
03EAH 31003 (DV)
OUT1 0003H 30004 Displays the output value of -300...10300 (-3.00...103.00%) -
03EBH 31004 the control output (OUT1)
STno 0005H 30006 Station No. 0 to 255 -
03EDH 31006
ALM 0006H 30007 Alarm (see Alarm Status Register -
STATUS 03EEH 31007 Description (see page 53))
- 0007H 30008 Input/main unit abnormal (see Input/main unit abnormal -
03EFH 31008 status Register Description (see page 53))
STAT 0008H 30009 Ramp/soak current running 0 to 17 (see Ramp/Soak current -
03F0H 31009 position running position Register
Description (see page 54))
CT 0009H 30010 Heater current 0...500 (0.0...50.0A) -
03F1H 31010
TM-1 000AH 30011 Timer 1 current count 0...9999 (0.0...999.9 sec.) -
03F2H 31011
- 000DH 30014 (Reserve) - -
03F5H 31014
Legend:
O Range available
- No range available

52 EIO0000001301 09/2012
Data Address Map

Alarm Status Register Description


The following table explains the register numbers 30007 and 31007 (Alarm status
contents):

Bit Description Read-out


0 Alarm 1 output (calculation result of de-energizing 0: Alarm 1 relay output OFF
alarm) 1: Alarm 1 relay output ON
3 (Reserve) –
4 Alarm 1 ON/OFF 0: Alarm 1 OFF
1: Alarm 1 ON
7 (Reserve) –

Input/Main Unit Abnormal Status Register Description


The following table explains the register numbers 30008 and 31008 (Input/main unit
abnormal status):

Bit Description Read-out


0 Input Lower open-circuit 0: Lower open-circuit absent
1: Lower open -circuit present
1 Input Upper open-circuit 0: Lower open-circuit absent
1: Lower open -circuit present
2 Input under-range 0: Under-range absent
1: Under-range present
3 Input over-range 0: Over-range absent
1: Over-range present
4 (Reserve) -
5 (Reserve) -
6 Setting range error detected 0: Setting range normal
1: Setting range abnormal
7 EEPROM error detected 0: EEPROM normal
1: EEPROM abnormal

EIO0000001301 09/2012 53
Data Address Map

Ramp/Soak current running position Register Description


The following table explains the register numbers 30009 and 31009 (Ramp/Soak
current running position):

Read-out Data Indication of parameter “STAT” Running Position (status)


0 OFF Stop status of ramp/soak
1 1-rP No. 1 ramp time
2 1-Sk No. 1 soak time
3 2-rP No. 2 ramp time
4 2-Sk No. 2 soak time
5 3-rP No. 3 ramp time
6 3-Sk No. 3 soak time
7 4-rP No. 4 ramp time
8 4-Sk No. 4 soak time
9 5-rP No. 5 ramp time
10 5-Sk No. 5 soak time
11 6-rP No. 6 ramp time
12 6-Sk No. 6 soak time
13 7-rP No. 7 ramp time
14 7-Sk No. 7 soak time
15 8-rP No. 8 ramp time
16 8-Sk No. 8 soak time
17 End End status of ramp/soak

54 EIO0000001301 09/2012
Data Address Map

4.2 Mapping Modbus of REG48/REG96

What Is in This Section?


This section contains the following topics:
Topic Page
Discrete Input Register 56
Holding Register 57
Input Register 78

EIO0000001301 09/2012 55
Data Address Map

Discrete Input Register

Bit Data (Read only)


The following table represents the address of the Discrete Input Register
(see page 36) parameters accessible using the function code 02H:

Relative Coil Description Read data REG48 REG96


address Number
0000H 10001 ALM1 ON/OFF  0: Alarm OFF x x
 1: Alarm ON

00001H 10002 ALM2 ON/OFF  0: Alarm OFF x x


 1: Alarm ON

00002H 10003 ALM3 ON/OFF1  0: Alarm OFF - x


 1: Alarm ON

00008H 10009 D01 ON/OFF  0: Alarm OFF x x


 1: Alarm ON

00009H 10010 D02 ON/OFF  0: Alarm OFF x x


 1: Alarm ON

0000AH 10011 D03 ON/OFF  0: Alarm OFF x x


 1: Alarm ON
1
For REG96 only
x Available
- Not available

56 EIO0000001301 09/2012
Data Address Map

Holding Register

Overview
Handles data dependent on an input range as an internal value before scaling
(0.00...100.00%).

Word Data (Read/Write)


The following table represents the Internal parameters address map (first line the
Internal Calculation Value and second line the Engineering Unit value).
The following table represents the addresses of the Holding Registers
(see page 36) parameters accessible using the function code 03H, 06H, 10H:

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
CTrL 0001H 40002 Control methods 0: PID (PID control) 0 -
41002 selection 1: FUZY (Fuzzy Pid control)
2: SELF (Self-tuning control)
3: PiD2 (Pid2 control)
SV 0002H 40003 Front SV set 0...10000 (within 0.00...100.00% FS 0.0 O
41003 value within set value limits)
STbY 0003H 40004 Switches 0: oFF (during RUN) oFF -
41004 between RUN 1: on(during standby)
and standby
AT 0004H 40005 Auto-Tuning 0: oFF (Stop/finish) oFF
1: on (normal type)
2: SELF (Low PV type)
P 0005H 40006 Proportional 0...9999 (0.0...999.9%) 5.0% -
41006 band
I 0006H 40007 Integration time 0...32000 (0...3200.0 sec.) 240 sec. -
41007
D 0007H 40008 Derivative time 0...9999 (0.0...999.9 sec.) 60.0 sec. -
41008
hYS 0008H 40009 ON/OFF control 0...5000 (0.00...50.00%FS) 1° C O
41009 hysteresis (33.8° F)
CoL 0009H 40010 Cooling 0...1000 (0.0...100.0) 1.0 -
41010 proportional band
coefficient
db 000AH 40011 Dead band -5000...5000 (-50.00...+50.00%) 0% -
41011
Ar 000BH 40012 Anti-reset windup 0...10000 (0.00...100.00%) 400 ° C O
41012 (752 ° F)

EIO0000001301 09/2012 57
Data Address Map

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
bAL 000CH 40013 Output -1000...1000 (-10.00...10.00%FS) 0.0 % -
41013 convergence
value
PvoF 000DH 40014 PV input shift -1000...1000 (-10.00...10.00%FS) 0 -
41014
SvoF 000EH 40015 SV offset -5000 to 5000 (-50.00% to 50.00% - -
41015 FS)
PvT 000FH 40016 PV input type 0 (JPT 100 Ohm) 3 (K) -
41016 1 (PT 100 Ohm)
2 (J)
3 (K)
4 (R)
5 (B)
6 (S)
7 (T)
8 (E)
9 (no function)
10 (no function)
11 (no function)
12 (N)
13 (PL-2)
14 (no function)
15 (0V to 5V/0mA...20mA)
16 (1V...5V/4mA...20mA)
17 (0mV...10V)
18 (2V...10V)
19 (0mV...100mV)
Pvb 0011H 40018 PV input lower -1999...9999 ° C 0° C -
41018 limit (32° F)
PvF 0012H 40019 PV input upper -1999...9999 ° C 400° C -
41019 limit (752° F)
Pvd 0013H 40020 Decimal position 0 (no decimal point) 0 -
41020 1 (one decimal place)
2 (two decimal places)
TF 0015H 40022 PV input filter 0...1200 (0.0...120.0 sec.) 5 sec. -
41022
RCJ 0016H 40023 Cold Junction 0: oFF (off) 1: on -
41023 Compensation 1: on (on)
PCUT 0017H 40024 Selects the 0 to 15 0 -
41024 output limiter
type

58 EIO0000001301 09/2012
Data Address Map

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
PLC1 0018H 40025 OUT1 lower limit -300...10300 (-3.00...103.00%) -3.0 % -
41025
PhC1 0019H 40026 OUT1 upper limit -300...10300 (-3.00...103.00%) 103.0 % -
41026
PLC2 001AH 40027 OUT2 lower limit -300...10300 (-3.00...103.00%) -3.0 % -
41027
PhC2 001BH 40028 OUT2 upper limit -300...10300 (-3.00...103.00%) 103.0 % -
41028
SvL 001EH 40031 SV limit (lower) 0...10000 (0.00...100.00%FS) 0 % FS O
41031
Svh 001FH 40032 SV limit (upper) 0...10000 (0.00...100.00%FS) 100 % FS O
41032
LoC 0027H 40040 Key lock 0: no lock - -
41040 1: all lock
2: All but SV locked
do1T 0028H 40041 DO1 output event 0 to 102 0 -
41041 type setting
do2T 0029H 40042 DO2 output event 0 to 102 0 -
41042 type setting
do3T 002AH 40043 DO3 output event 0 to 102 0 -
41043 type setting1
AL1 002BH 40044 ALM1 set value 0...10000 (0.00...100.00%FS) 10 ° C O
41044 or A1-L (50° F)
AL2 002CH 40045 ALM2 set value 0...10000 (0.00...100.00%FS) 10 ° C O
41045 or A2-L (50° F)
AL3 002DH 40046 ALM3 set value 0...10000 (0.00...100.00%FS) 10° C O
41046 or A3-L (50° F)
A1hY 0031H 40050 ALM1 hysteresis 0...5000 (0.00...50.00%FS) 1° C O
41050 (33.8° F)
A2hY 0032H 40051 ALM2 hysteresis 0...5000 (0.00...50.00%FS) 1° C O
41051 (33.8° F)
A3hY 0033H 40052 ALM3 0...5000 (0.00...50.00%FS) 1° C O
41052 hysteresis1 (33.8° F)

dLY1 0034H 40053 ALM1 delay 0-9999 [sec./min.] 0 -


41053
dLY2 0035H 40054 ALM2 delay 0...9999 [sec./min.] 0 -
41054

EIO0000001301 09/2012 59
Data Address Map

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
dLY3 0036H 40055 ALM3 delay1 0...9999 [sec./min.] 0 -
41055
Mod 0050H 40081 Ramp/soak 0 to 15 0 -
41081 mode
PrG 0051H 40082 Ramp/soak 0: oFF (during 0: oFF (stop) oFF -
41082 controls stop) 1: rUn (run)
Command 1: rUn (during 2: hLd (hold)
run)
2: hLd (during
hold)
rEv 0057H 40088 Sets 0: rv-- (heat (reverse) / cool (none)) 0: rv-- -
41088 normal/reverse 1: no-- (heat (normal) / cool (none))
operations 2: rvno (heat (reverse)/cool (normal))
3: norv (heat (normal) / cool
(reverse))
4: rvrv (heat (reverse) / cool
(reverse))
5: nono (heat (normal)/cool (normal))
TC1 0058H 40089 OUT1 proportion 1...150 sec. 30 or 2 -
41089 cycle sec.
TC2 0059H 40090 OUT2 proportion 1...150 sec. 30 or 3 -
41090 cycle sec.
ADJ0 0062H 40099 PV display zero 0...5000 (0.00...50.00%FS) - O
41099 adjustment
ADJS 0063H 40100 PV display Splan 0...5000 (0.00...50.00%FS) O
41100 adjustment
AoL 0072H 40115 AO lower limit -10000...10000 (0.00...100.00%FS) 0% -
41115 scaling
Aoh 0073H 40116 AO upper limit -10000...10000 (0.00...100.00%FS) - -
41116 scaling
rEM 0074H 40117 Switches to 0: LoCL (during 0: LoCL (Local) LoCL -
41117 remote mode Local) 1: rEM (Remote)
1: rEM (during
Remote)
rEM0 0075H 40118 RSV zero -5000...5000 (0.00...50.00%FS) 0%FS -
41118 adjustment
rEMS 0076H 40119 RSV span -5000...5000 (0.00...50.00%FS) 0%FS -
41119 adjustment

60 EIO0000001301 09/2012
Data Address Map

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
MAn 0078H 40121 Switches to 0: oFF (during 0: oFF (auto) oFF -
41121 manual mode auto) 1: on (manual)
1: on (during
manual)
MV 0079H 40122 Front MV set -300...10300 (-3.00...103.00%) - -
41122 value
UKEY 008CH 40141 USER key  0 (no function) - -
41141 assignment  1 (Switches between STBY
settings ON/OFF)
 2 (Switches between
Auto/Manual)
 3 (no function)
 4 (Do not set)
 5 (Starts AT (standard))
 6 (Starts AT (low PV))
 7 (Do not set)
 8 (Ramp SV HOLD)
 9 (Ramp/soak RUN/OFF)
 10 (Ramp/soak RUN/HOLD)
 11 (Do not set)
 12 (Latch cancel (all))
 13 (Latch cancel (DO1))
 14 (Latch cancel (DO2))
 15 (Latch cancel (DO3))
 16 (no function)
 17 (no function)
 18 (no function)
 19 (no function)
 20 (no function)
 21 (no function)
 22 (no function)
 23 (SV No.+1 (send))
 24 (PID No. +1 (send))
 25 (Do not set)
 26 (Pattern No.+1 (send))
 27 (SV No. + 1, PID No. + 1
(send))
LACh 00A0H 40161 Cancels the DO 0: oFF oFF -
41161 output latch 1: rST (latch reset)
Command
AL1L 00A2H 40163 AL1L set value 0...10000 (0.00...100.00%FS) - O
41163 (absolute alarm)
-10000...10000 (-100...100.00%FS)
(deviation alarm)

EIO0000001301 09/2012 61
Data Address Map

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
AL1h 00A3H 40164 AL1h set value 0...10000 (0.00...100.00%FS) - O
41164 (absolute alarm)
-10000...10000 (-100...100.00%FS)
(deviation alarm)
doP1 00A5H 40166 Sets DO1 option 0000 to 1111 0 -
41166 function  bit0: event output latch function
 bit1: error alarm function
 non-excitation output alarm
function
 bit3: hold reset function

0000-1111

bit0 : event output latch function


bit1 : error alarm function
bit2 : non-excitation output
alarm function
bit3 : hold reset function

dL1U 00A7H 40168 ALM1 delay time 0: sec. - -


41168 units 1: Min.
AL2L 00A9H 40170 AL2L set value 0...10000 (0.00...100.00%FS) - O
41170 (absolute alarm)
-10000...10000 (-100...100.00%FS)
(deviation alarm)
AL2h 00AAH 40171 AL2h set value 0...10000 (0.00...100.00%FS) - O
41171 (absolute alarm)
-10000...10000 (-100...100.00%FS)
(deviation alarm)
doP2 00ACH 40173 DO2 option 0000 to 1111 0 -
41173 function setting  bit0: event output latch function
 bit1: error alarm function
 non-excitation output alarm
function
 bit3: hold reset function

0000-1111

bit0 : event output latch function


bit1 : error alarm function
bit2 : non-excitation output
alarm function
bit3 : hold reset function

dL2U 00AEH 40175 ALM1 delay time 0: sec. - -


41175 units 1: Min.

62 EIO0000001301 09/2012
Data Address Map

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
AL3L 00B0H 40177 AL3L set value 0...10000 (0.00...100.00%FS) - O
41177 (absolute alarm)
-10000...10000 (-100...100.00%FS)
(deviation alarm)
AL3h 00B1H 40178 AL3h set value 0...10000 (0.00...100.00%FS) - O
41178 (absolute alarm)
-10000...10000 (-100...100.00%FS)
(deviation alarm)
doP3 00B3H 40180 DO3 option 0000 to 1111 0 -
41180 function setting  bit0: event output latch function
 bit1: error alarm function
 non-excitation output alarm
function
 bit3: hold reset function

0000-1111

bit0 : event output latch function


bit1 : error alarm function
bit2 : non-excitation output
alarm function
bit3 : hold reset function

dL3U 00B5H 40182 ALM3 delay time 0: sec. - -


41182 units 1: Min.
LbTM 00CCH 40205 Loop break 0...9999 (0% to 100% FS) 0 sec. -
41205 detection time
LbAb 00CDH 40206 Loop break 0...9999 (0% to 100% FS) 10 ° C O
41206 detection range (50 ° F)
Svn 00DCH 40221 Selectable SV 0: Sv0 (Local SV)1: Sv1 (SV = SV-1) Sv0 -
41121 numbers 2: Sv2 (SV = SV-2)
3: Sv3(SV = SV-3)
4: Sv4 (SV = SV-4)
5: Sv5 (SV = SV-5)
6: Sv6(SV = SV-6)
7: Sv7 (SV = SV-7)
PLn1 00DDH 40222 Currently 0: PID0 (PID group local) PID0 -
41222 selected PID No. 1: PID1 (PID group No. 1)
2: PID2 (PID group No. 2)
3: PID3 (PID group No. 3)
4: PID4 (PID group No. 4)
5: PID5 (PID group No. 5)
6: PID6 (PID group No. 6)
7: PID7 (PID group No. 7)

EIO0000001301 09/2012 63
Data Address Map

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
SvMX 00DFH 40224 Selectable SV 0: Sv0 (Local SV) Sv7 -
41224 numbers 1: Sv1 (SV = SV-1)
2: Sv2 (SV = SV-2)
3: Sv3 (SV = SV-3)
4: Sv4 (SV = SV-4)
5: Sv5 (SV = SV-5)
6: Sv6 (SV = SV-6)
7: Sv7 (SV = SV-7)
PL1M 00E0H 40225 Currently 0: PID0 (PID group local) PID7 -
41225 selected PID No. 1: PID1 (PID group No. 1)
2: PID2 (PID group No. 2)
3: PID3 (PID group No. 3)
4: PID4 (PID group No. 4)
5: PID5 (PID group No. 5)
6: PID6 (PID group No. 6)
7: PID7 (PID group No. 7)
Sv1 00F0H 40241 SV set value 1 0...10000 (0.00...100.00%FS) 0 % FS O
41241
P1 00F1H 40242 Proportional 0...9999 (0.0...999.9%) 5.0 % -
41242 band 1
I1 00F2H 40243 Integration time 1 0...32000 (0...3200.0 sec.) 240 sec. -
41243
D1 00F3H 40244 Derivation time 1 0...9999 (0.0...999.9 sec.) 60.0 sec. -
41244
hYS1 00F4H 40245 ON/OFF Control 0...5000 (0.00...50.00%FS) 1° C O
41245 hysteresis 1 (33.8° F)
CoL1 00F5H 40246 Cooling 0...10000 (0.00...100.00%FS) 1.0 -
41246 proportional band
1
db1 00F6H 40247 Dead band 1 -5000...5000 (-50.00...+50.00%) 0% -
41247
bAL1 00F7H 40248 Output -10000...10000 (-100.00...100.00%) 0% -
41248 convergence
value 1
Ar1 00F8H 40249 Anti-reset windup 0...10000 (0.00...100.00%FS) 400 ° C O
41249 1 (752 ° F)

64 EIO0000001301 09/2012
Data Address Map

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
rEv1 00F9H 40250 Normal/Reverse 0: rv-- (heat (reverse)/cool (none)) 0: rv-- -
41250 setting 1 1: no-- (heat (normal)/cool (none))
2: rvno (heat (reverse)/cool (normal))
3: norv (heat (normal)/cool (reverse))
4: rvrv (heat (reverse)/cool (reverse))
5: nono (heat (normal)/cool (normal))
Sv2 00FAH 40251 SV set value 2 0...10000 (0.00...100.00%FS) 0% FS O
41251
P2 00FBH 40252 Proportional 0...9999 (0.0...999.9%) 5.0% -
41252 band 2
I2 00FCH 40253 Integration time 2 0...32000 (0...3200.0 sec.) 240 sec. -
41253
D2 00FDH 40254 Derivation time 0...9999 (0.0...999.9 sec.) 60.0 sec. -
41254
hYS2 00FEH 40255 ON/OFF control 0...5000 (0.00...50.00%FS) 1° C O
41255 hysteresis 2 (33.8° F)
CoL2 00FFH 40256 Cooling 0...10000 (0.00...100.00%FS) 1.0 -
41256 proportional band
2
db2 0100H 40257 Dead band 2 -5000...5000 (-50.00...+50.00%) 0% -
41257
bAL2 0101H 40258 Output -10000...10000 (-100.00...100.00%) 0% -
41258 convergence
value 2
Ar2 0102H 40259 Anti-reset windup 0...10000 (0.00...100.00%FS) 400 ° C O
41259 2 (752 ° F)
rEv2 0103H 40260 Normal/Reverse 0: rv-- (heat (reverse)/cool (none)) 0: rv-- -
41260 setting 2 1: no-- (heat (normal)/cool (none))
2: rvno (heat (reverse)/cool (normal))
3: norv (heat (normal)/cool (reverse))
4: rvrv (heat (reverse)/cool (reverse))
5: nono (heat (normal)/cool (normal))
Sv3 0104H 40261 SV set value 3 0...10000 (0.00...100.00%FS) 0% FS O
41261
P3 0105H 40262 Proportional 0...9999 (0.0...999.9%) 5.0% -
41262 band 3
I3 0106H 40263 Integration time 3 0...32000 (0...3200.0 sec.) 240 sec. -
41263
D3 0107H 40264 Derivation time 3 0...9999 (0.0...999.9 sec.) 60.0 sec. -
41264

EIO0000001301 09/2012 65
Data Address Map

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
hYS3 0108H 40265 ON/OFF control 0...5000 (0.00...50.00%FS) 1° C O
41265 hysteresis 3 (33.8° F)
CoL3 0109H 40266 Cooling 0...10000 (0.00...100.00%FS) 1.0 -
41266 proportional band
3
db3 010AH 40267 Dead band 3 -5000...5000 (-50.00...+50.00%) 0% -
41267
bAL3 010BH 40268 Output -10000...10000 (-100.00...100.00%) 0% -
41268 convergence
value 3
Ar3 010CH 40269 Anti-reset windup 0...10000 (0.00...100.00%FS) 400 ° C O
41269 3 (752 ° F)
rEv3 010DH 40270 Normal/Reverse 0: rv-- (heat (reverse)/ cool (none) 0: rv-- -
41270 setting 3 1: no-- (heat (normal) / cool (none))
2: rvno (heat (reverse) / cool
(normal)
3: norv (heat (normal)/ cool
(reverse))
4: rvrv (heat (reverse) / cool
(reverse))
5: nono (heat (normal) / cool
(normal)
Sv4 010EH 40271 SV set value 4 0...10000 (0.00...100.00%FS) 0% FS O
41271
P4 010EFH 40272 Proportional 0...9999 (0.0...999.9%) 5.0% -
41272 band 4
I4 0110H 40273 Integration time 4 0...32000 (0...3200.0 sec.) 240 sec. -
41273
d4 0111H 40274 Derivation time 4 0...9999 (0.0...999.9 sec.) 60.0 sec. -
41274
hYS4 0112H 40275 ON/OFF control 0...5000 (0.00...50.00%FS) 1° C O
41275 hysteresis 4
CoL4 0113H 40276 Cooling 0...10000 (0.00...100.00%FS) 1.0 -
41276 proportional band
4
db4 0114H 40277 Dead band 4 -5000...5000 (-50.00...+50.00%) 0% -
41277
bAL4 0115H 40278 Output -10000...10000 (-100.00...100.00%) 0% -
41278 convergence
value 4

66 EIO0000001301 09/2012
Data Address Map

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
Ar4 0116H 40279 Anti-reset windup 0...10000 (0.00...100.00%FS) 400 ° C O
41279 4 (752 ° F)
rEv4 0117H 40280 Normal/Reverse 0: rv-- (heat (reverse) / cool (none)) 0: rv-- -
41280 setting 4 1: no-- (heat (normal) / cool (none))
2: rvno (heat (reverse) / cool
(normal))
3: norv (heat (normal) / cool
(reverse))
4: rvrv (heat (reverse) / cool
(reverse))
5: nono (heat (normal) / cool
(normal))
Sv5 0118H 40281 SV set value 5 0...10000 (0.00...100.00%FS) 0% FS O
41281
P5 0119H 40282 Proportional 0...9999 (0.0...999.9%) 5.0% -
41282 band 5
I5 011AH 40283 Integration time 5 0...32000 (0...3200.0 sec.) 240 sec. -
41283
D5 011BH 40284 Derivation time 5 0...9999 (0.0...999.9 sec.) 60.0 sec. -
41284
hYS5 011CH 40285 ON/OFF control 0...5000 (0.00...50.00%FS) 1° C O
41285 hysteresis 5 (33.8° F)
CoL5 011DH 40286 Cooling 0...10000 (0.00...100.00%FS) 1.0 -
41286 proportional band
5
db5 011EH 40287 Dead band 5 -5000...5000 (-50.00...+50.00%) 0% -
41287
bAL5 011FH 40288 Output -10000...10000 (-100.00...100.00%) 0% -
41288 convergence
value 5
Ar5 0120H 40289 Anti-reset windup 0...10000 (0.00...100.00%FS) 400 ° C O
41289 5 (752 ° F)

EIO0000001301 09/2012 67
Data Address Map

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
rEv5 0121H 40290 Normal/Reverse 0: rv-- (heat (reverse) / cool (none)) 0: rv-- -
41290 setting 5 1: no-- (heat (normal) / cool (none))
2: rvno (heat (reverse) / cool
(normal))
3: norv (heat (normal) / cool
(reverse))
4: rvrv (heat (reverse) / cool
(reverse))
5: nono (heat (normal) / cool
(normal))
Sv6 0122H 40291 SV set value 6 0...10000 (0.00...100.00%FS) 0% FS O
41291
P6 0123H 40292 Proportional 0...9999 (0.0...999.9%) 5.0% -
41292 band 6
I6 0124H 40293 Integration time 6 0...32000 (0...3200.0 sec.) 240 sec. -
41293
D6 0125H 40294 Derivation time 6 0...9999 (0.0...999.9 sec.) 60.0 sec -
41294
hYS6 0126H 40295 ON/OFF control 0...5000 (0.00...50.00%FS) 1° C O
41295 hysteresis 6 (33.8° F)
CoL6 0127H 40296 Cooling 0...10000 (0.00...100.00%FS) 1.0 -
41296 proportional band
6
db6 0128H 40297 Dead band 6 -5000...5000 (-50.00...+50.00%) 0% -
41297
bAL6 0129H 40298 Output -10000...10000 (-100.00...100.00%) 0% -
41298 convergence
value 6
Ar6 012AH 40299 Anti-reset windup 0...10000 (0.00...100.00%FS) 400° C O
41299 6 (752° F)
rEv6 012BH 40300 Normal/Reverse 0: rv-- (heat (reverse) / cool (none)) 0: rv-- -
41300 setting 6 1: no-- (heat (normal) / cool (none))
2: rvno (heat (reverse) / cool
(normal))
3: norv (heat (normal) / cool
(reverse))
4: rvrv (heat (reverse) / cool
(reverse))
5: nono (heat (normal) / cool
(normal))

68 EIO0000001301 09/2012
Data Address Map

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
Sv7 012CH 40301 SV set value 7 0...10000 (0.00...100.00%FS) 0% FS O
41301
P7 012DH 40302 Proportional 0...9999 (0.0...999.9%) 5.0% -
41302 band 7
I7 012EH 40303 Integration time 7 0...32000 (0...3200.0 sec.) 240 sec. -
41303
d7 012FH 40304 Derivation time 7 0...9999 (0.0...999.9 sec.) 60.0 sec -
41304
hYS7 0130H 40305 ON/OFF control 0...5000 (0.00...50.00%FS) 1° C O
41305 hysteresis 7 (33.8° F)
CoL7 0131H 40306 Cooling 0...10000 (0.00...100.00%FS) 1.0 -
41306 proportional band
7
db7 0135H 40307 Dead band 7 -5000...5000 (-50.00...+50.00%) 0% -
41307
bAL7 0133H 40308 Output -10000...10000 (-100.00...100.00%) 0% -
41308 convergence
value 7
Ar7 0134H 40309 Anti-reset windup 0...10000 (0.00...100.00%FS) 400° C O
41309 7 (752° F)
rEv7 0135H 40310 Normal/Reverse 0: rv-- (heat (reverse) / cool (none)) 0: rv-- -
41310 setting 7 1: no-- (heat (normal) / cool (none))
2: rvno (heat (reverse) / cool
(normal))
3: norv (heat (normal) / cool
(reverse))
4: rvrv (heat (reverse) / cool
(reverse))
5: nono (heat (normal) / cool
(normal))
PvU 0136H 40345 Unit display 0: ° C 0 -
41345 1: ° F
rEMr 0137H 40358 RSV Input Range 0: 0-5 v (0 V...5 V) 1-5 -
41358 1: 1-5 v (1 V...5 V)
rTF 0138H 40359 RSV input filter 0.0...120.0 sec. 0.0 sec. -
41359
C1r 017CH 40381 OUT1 range 4: 0...20 (0 mA to 20 mA) 4 to 20 -
41381 5: 4...20 (4 mA to 20 mA) (current)
C2r 017DH 40382 OUT2 range 4: 0...20 (0 mA...20 mA) 4 to 20 -
41382 5: 4...20 (4 mA...20 mA) (current)

EIO0000001301 09/2012 69
Data Address Map

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
FLo1 0185H 40390 Output 1 set -300...10300 (-3.00...103.00%) -3 % -
41390 value during
FALT
FLo2 0186H 40391 Output 2 set -300...10300 (-3.00...103.00%) -3 % -
41391 value during
FALT
SFo1 0187H 40392 Soft start OUT1 -300...10300 (-3.00...103.00%) 103 % -
41392 set value
SFTM 0189H 40394 Soft start 00:00 to 99:59 (hour:min.) 00:00 -
41394 detection time (hour:min.)
Sbo1 018DH 40398 During standby, -300...10300 (-3.00...103.00%) - -
41398 OUT1 set value
Sbo2 018EH 40399 During standby, -300...10300 (-3.00...103.00%) - -
41399 OUT2 set value
SbMd 018FH 40400 Standby mode 0 to 7 0 -
41400 setting
rMPL 01ADH 40430 Ramp SV - 0...10000 (0.00...100.00%FS) 0° C O
41430 Decline
rMPh 01AEH 40431 Ramp SV - 0...10000 (0.00...100.00%FS) 0° C O
41431 Incline
rMPU 01AFH 40432 Ramp SV slope 0: hour (slope degree/hr) hoUr -
41432 time unit 1: Min. (slope degree/min.)
SvT 01B0H 40433 Ramp SV - SV 0: rMP (Display current Ramp SV) rMP -
41433 display mode 1: TrG (Display target SV)
selection
STMd 01B1H 40434 Startup mode 0: AUTo (Auto mode startup) AUTo -
41434 1: MAn (Manual mode startup
2: rEM (Remote mode startup
3: Standby (Standby mode startup
DP01 01C2H 40451 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41451 display mask depend-
ing on
model
DP02 01C3H 40452 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41452 display mask depend-
ing on
model

70 EIO0000001301 09/2012
Data Address Map

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
DP03 01C4H 40453 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41453 display mask depend-
ing on
model
DP04 01C5H 40454 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41454 display mask depend-
ing on
model
DP05 01C6H 40455 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41455 display mask depend-
ing on
model
DP06 01C7H 40456 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41456 display mask depend-
ing on
model
DP07 01C8H 40457 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41457 display mask depend-
ing on
model
DP08 01C9H 40458 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41458 display mask depend-
ing on
model
DP09 01CAH 40459 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41459 display mask depend-
ing on
model
DP10 01CBH 40460 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41460 display mask depend-
ing on
model
DP11 01CCH 40461 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41461 display mask depend-
ing on
model
DP12 01CDH 40462 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41462 display mask depend-
ing on
model

EIO0000001301 09/2012 71
Data Address Map

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
DP13 01CEH 40463 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41463 display mask depend-
ing on
model
DP14 01CFH 40464 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41464 display mask depend-
ing on
model
DP15 01D0H 40465 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41465 display mask depend-
ing on
model
DP16 01D1H 40466 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41466 display mask depend-
ing on
model
DP17 01D2H 40467 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41467 display mask depend-
ing on
model
DP18 01D3H 40468 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41468 display mask depend-
ing on
model
DP19 01D4H 40469 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41469 display mask depend-
ing on
model
DP20 01D5H 40470 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41470 display mask depend-
ing on
model
DP21 01D6H 40471 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41471 display mask depend-
ing on
model
DP22 01D7H 40472 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41472 display mask depend-
ing on
model

72 EIO0000001301 09/2012
Data Address Map

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
DP23 01D8H 40473 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41473 display mask depend-
ing on
model
DP24 01D9H 40474 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41474 display mask depend-
ing on
model
DP25 01DAH 40475 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41475 display mask depend-
ing on
model
DP26 01DBH 40476 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41476 display mask depend-
ing on
model
DP27 01DCH 40477 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41477 display mask depend-
ing on
model
DP28 01DD9H 40478 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41478 display mask depend-
ing on
model
DP29 01DEH 40479 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41479 display mask depend-
ing on
model
DP30 01DFH 40480 Parameter -32768 to 32767 (8000 to 7FFF) Different -
41480 display mask depend-
iNg on
model.
PAS1 0209H 40522 Password1 setup -32768 to 32767 (8000 to 7FFF) 0 -
41522
PAS2 020AH 40523 Password2 setup -32768 to 32767 (8000 to 7FFF) 0 -
41523
PAS3 02BH 40524 Password3 setup -32768 to 32767 (8000 to 7FFF) 0 -
41524

EIO0000001301 09/2012 73
Data Address Map

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
PTn 0230H 40561 Ramp/Soak 0 (uses steps 1 to 4) 6 -
41561 Activation 1 (uses steps 5 to 8)
Pattern 2 (uses steps 1 to 8)
3 (uses steps 9 to 12)
4 (uses steps 13 to 16)
5 (uses steps 9 to 16)
6 (uses steps 1 to 16)
TIMU 031H 40562 Ramp/soak time 0: hh.MM (hour: min.) hh.MM -
41562 units 1: MM.SS (min.: sec.)
PTnM 0233H 40564 Sets the max 0 to 6 6 -
41564 pattern selection
GSoK 023AH 40571 Guaranty soak 0: oFF (guaranty soak off) oFF O
41571 ON/OFF 1: on (guaranty soak on)
GS-L 023BH 40572 Guaranty soak 0...5000 (0.00...50.00%FS) 5° C O
41572 (lower limit)
GS-h 023CH 40573 Guaranty soak 0...5000 (0.00...50.00%FS) 5° C -
41573 (upper limit)
SV-1 0244H 40581 Ramp/Soak 1 0...1000 (0.00...100%) 0% FS O
41581 seg/SV Set Value
TM1R 0245H 40582 Ramp/Soak 1 00.00-99.59 (hour:min/min.: sec.) 00.00 -
41582 seg ramp time (hour:min)
TM1S 0246H 40583 Ramp/Soak 1 00.00-99.59 (hour:min/min.: sec.) 00.00 -
41583 seg soak time (hour:min)
SV-2 0247H 40584 Ramp/Soak 2 0...1000 (0.00...100%) 0% FS O
41584 seg/SV Set Value
TM2R 0248H 40585 Ramp/Soak 2 00.00-99.59 (hour:min/min.: sec.) 00.00 -
41585 seg ramp time (hour:min)
TM2S 0249H 40586 Ramp/Soak 2 00.00-99.59 (hour:min/min.: sec.) 00.00 -
41586 seg soak time (hour:min)
SV-3 024AH 40587 Ramp/Soak 3 0...1000 (0.00...100%) 0% FS O
41587 seg/SV Set Value
TM3R 024BH 40588 Ramp/Soak 3 00.00-99.59 (hour:min/min.: sec.) 00.00 -
41588 seg ramp time (hour:min)
TM3S 024CH 40589 Ramp/Soak 3 00.00-99.59 (hour:min/min: sec) 00.00 -
41589 seg soak time (hour:min)
SV-4 024DH 40590 Ramp/Soak 4 0...1000 (0.00...100%) 0% FS O
41590 seg/SV Set Value
TM4R 024EH 40591 Ramp/Soak 4 00.00-99.59 (hour:min/min: sec) 00.00 -
41591 seg ramp time (hour:min)

74 EIO0000001301 09/2012
Data Address Map

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
TM4S 024FH 40592 Ramp/Soak 4 00.00-99.59 (hour:min/min: sec) 00.00 -
41592 seg soak time (hour:min)
SV-5 0250H 40593 Ramp/Soak 5 0...1000 (0.00...100%) 0% FS O
41593 seg/SV Set Value
TM5R 0251H 40594 Ramp/Soak 5 00.00-99.59 (hour:min/min: sec) 00.00 -
41594 seg ramp time (hour:min)
TM5S 0252H 40595 Ramp/Soak 5 00.00-99.59 (hour:min/min: sec) 00.00 -
41595 seg soak time (hour:min)
SV-6 0253H 40596 Ramp/Soak 6 0...1000 (0.00...100%) 0% FS O
41596 seg/SV Set Value
TM6R 0254H 40597 Ramp/Soak 6 00.00-99.59 (hour:min/min: sec) 00.00 -
41597 seg ramp time (hour:min)
TM6S 0255H 40598 Ramp/Soak 6 00.00-99.59 (hour:min/min: sec) 00.00 -
41598 seg soak time (hour:min)
SV-7 0256H 40599 Ramp/Soak 7 0...1000 (0.00...100%) 0% FS O
41599 seg/SV Set Value
TM7R 0257H 40600 Ramp/Soak 7 00.00-99.59 (hour:min/min: sec) 00.00 -
41600 seg ramp time (hour:min)
TM7S 0258H 40601 Ramp/Soak 7 00.00-99.59 (hour:min/min: sec) 00.00 -
41601 seg soak time (hour:min)
SV-8 0259H 40602 Ramp/Soak 8 0% to 100% FS 0% FS O
41602 seg/SV Set Value
TM8R 025AH 40603 Ramp/Soak 8 00.00-99.59 (hour:min/min: sec) 00.00 -
41603 seg ramp time (hour:min)
TM8S 025BH 40604 Ramp/Soak 8 00.00-99.59 (hour:min/min: sec) 00.00 -
41604 seg soak time (hour:min)
SV-9 025CH 40605 Ramp/Soak 9 0...1000 (0.00...100%) 0% FS O
41605 seg/SV Set Value
TM9R 025DH 40606 Ramp/Soak 9 00.00-99.59 (hour:min/min: sec) 00.00 -
41606 seg ramp time (hour:min)
TM9S 025EH 40607 Ramp/Soak 9 00.00-99.59 (hour:min/min: sec) 00.00 -
41607 seg soak time (hour:min)
SV10 025FH 40608 Ramp/Soak 10 0...1000 (0.00...100%) 0% FS O
41608 seg/SV Set Value
T10R 0260H 40609 Ramp/Soak 10 00.00-99.59 (hour:min/min: sec) 00.00 -
41609 seg ramp time (hour:min)
T10S 0261H 40610 Ramp/Soak 10 00.00-99.59 (hour:min/min: sec) 00.00 -
41610 seg soak time (hour:min)

EIO0000001301 09/2012 75
Data Address Map

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
SV11 0262H 40611 Ramp/Soak 11 0...1000 (0.00...100%) 0% FS O
41611 seg/SV Set Value
T11R 0263H 40612 Ramp/Soak 11 00.00-99.59 (hour:min/min: sec) 00.00 -
41612 seg ramp time (hour:min)
T11S 0264H 40613 Ramp/Soak 11 00.00-99.59 (hour:min/min: sec) 00.00 -
41613 seg soak time (hour:min)
SV12 0265H 40614 Ramp/Soak 12 0...1000 (0.00...100%) 0% FS O
41614 seg/SV Set Value
T12R 0266H 40615 Ramp/Soak 12 00.00-99.59 (hour:min/min: sec) 00.00 -
41615 seg ramp time (hour:min)
T12S 0267H 40616 Ramp/Soak 12 00.00-99.59 (hour:min/min: sec) 00.00 -
41616 seg soak time (hour:min)
SV13 0268H 40617 Ramp/Soak 13 0...1000 (0.00...100%) 0% FS O
41617 seg/SV Set Value
T13R 0269H 40618 Ramp/Soak 13 00.00-99.59 (hour:min/min: sec) 00.00 -
41618 seg ramp time (hour:min)
T13S 026AH 40619 Ramp/Soak 13 00.00-99.59 (hour:min/min: sec) 00.00 -
41619 seg soak time (hour:min)
SV14 026BH 40620 Ramp/Soak 14 0% to 100% FS 0% FS O
41620 seg/SV Set Value
T14R 026CH 40621 Ramp/Soak 14 00.00-99.59 (hour:min/min: sec) 00.00 -
41621 seg ramp time (hour:min)
T14S 026DH 40622 Ramp/Soak 14 00.00-99.59 (hour:min/min: sec) 00.00 -
41622 seg soak time (hour:min)
SV15 026EH 40623 Ramp/Soak 15 0...1000 (0.00...100%) 0% FS O
41623 seg/SV Set Value
T15R 026FH 40624 Ramp/Soak 15 00.00-99.59 (hour:min/min: sec) 00.00 -
41624 seg ramp time (hour:min)
T15S 0270H 40625 Ramp/Soak 15 00.00-99.59 (hour:min/min: sec) 00.00 -
41625 seg soak time (hour:min)
SV16 0271H 40626 Ramp/Soak 16 0...1000 (0.00...100%) 0% FS O
41626 seg/SV Set Value

76 EIO0000001301 09/2012
Data Address Map

Parame- Relative Register Description Read Data Written Data Factory Dependent
ters Address Number Range default on Range
Name Setting
T16R 0272H 40627 Ramp/Soak 16 00.00-99.59 (hour:min/min: sec) 00.00 -
41267 seg ramp time (hour:min)
T16S 0273H 40628 Ramp/Soak 16 00.00-99.59 (hour:min/min: sec) 00.00 -
41628 seg soak time (hour:min)
Legend:
O Range available
- No range available

EIO0000001301 09/2012 77
Data Address Map

Input Register

Overview
Handles data dependent on an input range as an internal value before scaling
(0.00...100.00%).

Word Data (Read/Write)


The following table represents the Internal parameters address map (first line the
Internal Calculation Value and second line the Engineering Unit value).
The following table represents the addresses of the Input Registers (see page 36)
parameters accessible using the function code 04H:

Parameters Relative Register Description Read Data Written Data Dependent


Name Address Number Range on Range
PV 0000H 30001 Process value 0...10000 (0.00...100.00%FS) O
31001
SV 0001H 30002 Currently used set 0...10000 (0.00...100.00%FS) O
31002 value (SV)
DV 0002H 30003 Currently used -10000...10000 (-100.00...100.00%FS) O
31003 deviation (DV)
OUT1 0003H 30004 Displays the -300...10300 (-3.00...103.00%FS) -
31004 output value of the
control output
(OUT1)
MV2 0004H 30005 Output 2 -300...10300 (-3.00...103.00%FS) -
31005
STNo 0005H 30006 Station No. 1 to 247 -
31006
ALM STATUS 0006H 30007 Alarm (See Alarm Status Register Description -
31007 (see page 80))
FALT 0007H 30008 FALT STATUS  0bit:PFB input underflow -
31008  1bit:PFB input overflow
 8bit: PV input underflow
 9bit: PV input overflow
 10bit: underrange
 11bit: overrange
 12bit: RSV underrange
 13bit: RSV overrange
 14bit: range setting error
 15bit: EEPROM error
RJC (Cold 000FH 30016 -  oFF (off) -
junction 31016  on (on)
compensation)

78 EIO0000001301 09/2012
Data Address Map

Parameters Relative Register Description Read Data Written Data Dependent


Name Address Number Range on Range
STAT 0028H 30041 Ramp/soak  oFF (ramp/soak is stopped) -
31041 current running  1rP (Step 1 Ramp)
position  ...
 16rP (Step 16 Ramp)
 16Sk (Step 16 Soak)
 End (ramp/soak is finished)
MV1 0029H 30042 Control output 1 -300...10300 (-3.00...103.00%) -
31042
MV2 002AH 30043 Control output 2 -300...10300 (-3.00...103.00%) -
31043
PFb 002BH 30044 PFB Input Value -300...10300 (-3.00...103.00%) -
31044 Display
TM1 0031H 30050 Remaining time 0...9999 sec / 0...9999 min -
31050 on timer 1
TM2 0032H 30051 Remaining time 0...9999 sec / 0...9999 min -
31051 on timer 2

TM31 0033H 30052 Remaining time 0...9999 sec / 0...9999 min -


31052 on timer 3
FALT 0036H 30055 Error source  0bit:PFB input underflow -
31055 display  1bit:PFB input overflow
 8bit: PV input underflow
 9bit: PV input overflow
 10bit: underrange
 11bit: overrange
 12bit: RSV underrange
 13bit: RSV overrange
 14bit: range setting error
 15bit: EEPROM error
Legend:
1
TM3 only applicable to REG96
O Range available
- No range available

EIO0000001301 09/2012 79
Data Address Map

Alarm Status Register Description


The following table explains the register numbers 30007 and 31007 (Alarm status
contents):

Bit Description Read-out


0 Alarm 1 output (calculation result of de-energizing alarm)  0: Alarm 1 relay output OFF
 1: Alarm 1 relay output ON

1 Alarm 2 output (calculation result of de-energizing alarm)  0: Alarm 2 relay output OFF
 1: Alarm 2 relay output ON

2 Alarm 2 output (calculation result of de-energizing alarm)  0: Alarm 2 relay output OFF
 1: Alarm 2 relay output ON

3 (Reserve) –
4 Alarm 1 ON/OFF  0: Alarm 1 OFF
 1: Alarm 1 ON

5 Alarm 2 ON/OFF  0: Alarm 2 OFF


 1: Alarm 2 ON

6 Alarm 3 ON/OFF  0: Alarm 3 OFF


 1: Alarm 3 ON

7 (Reserve) –

80 EIO0000001301 09/2012
Zelio Control
Index
EIO0000001301 09/2012

Index
B
AC
A M
Address Map and Data Format, 36 Mapping Modbus of REG24, 42
Mapping Modbus of REG48/REG96, 55

C
Connect and Load ZelioControl Soft, 14 P
Parameters Setting Procedure Modbus, 34

F
Function Code 02 (H) of REG48/REG96, 56 R
Function Code 03 (H), 06 (H), 10 (H) of Read Only Bit Registers of REG24, 43
REG24, 44 RS-485 Specifications, 30
Function code 03 (H), 06 (H), 10 (H) of
REG48/96, 57
Function Code 04 (H) of REG24, 52
Function code 04 (H) of REG48/REG96, 78

H
How to Save Controller Parameters, 23
How to Use the Software, 20

I
Integration in a Network, 27

L
List of Setting Parameters of Modbus, 33

EIO0000001301 09/2012 81
Index