JOB NR/ FILE

382196-IOG-D00-XX-CA-H-0002
PROJECT: NR
DIV/DEPT GDI/HVAC
MAURITIUS MULTISPORTS COMPLEX CALC. BY Debasis Malick
CHECKED BY Sachin Saklani
EQUIPMENT SCHEDULE FOR MULTIPURPOSE GYMNASIUM DATE 22-Dec-16
Rev P01

INDICATIVE PACKAGED AIR CONDITIONER SCHEDULE


APPROX. MIN. MINIMUM SUPPLY FAN DX COOLING Heating FILTERS
RETURN BASIS OF
UNIT UNIT SIZE TOTAL AIR OUTDOOR ELEC. CURRENT MINIMUM NOMINAL DESIGN TOTAL SENSIBLE DESIGN
TAG UNIT TYPE AREA(S) Served ORIENTATION AIRFLOW AIRFLOW T.S.P. E.S.P. COIL EAT COIL EAT COIL LAT COIL LAT UNIT UNIT REFRING EAT DB LAT WB DESIGN BASIS OF DESIGN (MODEL) NOTES
WEIGHT (L x W x H) FLOW(L/S) AIRFLOW V/H/HZ AMPACITY MOTOR DRIVE TYPE CAPACITY CAPACITY CAPACITY CAPACITY CAPACITY EER AHRI TYPE EFF.
(L/S) (L/S) (Pa) (Pa) DB (° C) WB (° C) DB (° C) WB (° C) LAT DB LAT WB TYPE (° C) (° C) (MANUF.)
(kg) (L/S) (amps.) HP (MBH) (MBH) (MBH) (MBH) (kW)
PAHU 1 100 %Fresh Air Unit All indoor AC areas HORIZONTAL 3062 1600 X 1560 X 1320 1344 1344 - 380/3/49 43.2 1344 - 350 2.2 Belt - 119 119 69.4 30.6 23.9 18 17.4 - - R407c - - - - - - Petra 160-1
PAHU 2 100 %Fresh Air Unit FOP Seating Area HORIZONTAL 4125 5360 X 2230 X 2310 10000 10000 - 380/3/50 204.4 10000 - 350 20 Belt - 977.7 977.7 548.3 30.6 23.9 17.2 16.7 - - R407c 123.4 10 20.2 - - - Petra 900-2
PAHU 3 100 %Fresh Air Unit FOP Seating Area HORIZONTAL 4125 5360 X 2230 X 2310 10000 10000 - 380/3/50 204.4 10000 - 350 20 Belt - 977.7 977.7 548.3 30.6 23.9 17.2 16.7 - - R407c 123.4 10 20.2 - - - Petra 900-2
NOTES:
1. THE UNIT SHALL BE DOUBLE SKIN SUITABLE FOR OUTDOOR INSTALLATION.
2. THE PRESSURE DROP (EXTERNAL/ TOTAL) AND RATED MOTOR POWER INDICATED IN THIS SCHEDULE IS A GUIDELINE ONLY. CONTRACTOR SHALL PROVIDE POWER REQUIREMENT BASED ON THE FINAL SELECTIONS AND PROVIDE REQUIRED STARTERS,CABLES,ETC, WITHOUT ADDITIONAL COST.
3. UNIT SHALL BE SUPPLIED WITH REFRIGERANT CHARGE, PIPING, INSULATION, VALVE PACKAGES AND ALL CONTROLS.
4. ABOVE SELECTION CAPACITY IS BASED ON AMBIENT TEMPERATURE 35ºC AS PER BASIS OF DESIGN.
5. ALL THE ABOVE UNITS SHALL BE PROVIDED WITH CONTROL PANEL / STARTERS / ISOLATORS AND INTERCONNECTING CABLING, CONTROL W IRING AND THERMOSTATS. ONLY ONE INCOMING POWER SUPPLY ISOLATOR TO EACH UNIT HAS BEEN INCLUDED IN ELECTRICAL SCOPE. CONTROL W IRING FROM BMS HAS BEEN INCLUDED IN BMS SCOPE.