You are on page 1of 14

FLOW INDICATOR TOTALISER 1008V masibus

Ref No: m18V/om/101


Issue No: 07

Operator’s Manual

F L O W I N D I C A T O R T O T A L I S ER 1 0 0 8 V

Masibus Automation And Instrumentation Pvt. Ltd.


B/30, GIDC Electronics Estate,
Sector-25, Gandhinagar-382044, Gujarat, India.
Ph: 91 79 23287275-79
Fax: 91 79 23287281/82
Email: support@masibus.com
Web: www.masibus.com

Operator’s Manual Page 1 of 14


FLOW INDICATOR TOTALISER 1008V masibus
Ref No: m18V/om/101
Issue No: 07

CONTENTS

1. TECHNICAL DETAILS

2. SPECIFICATIONS

3. DIMENSIONS & PANEL CUTOUT

4. FRONT FASCIA

5. CONNECTIONS DETAIL

6. USER GUIDE

7. MODE OF OPERATION

8. MODBUS PROTOCOL

Operator’s Manual Page 2 of 14


FLOW INDICATOR TOTALISER 1008V masibus
Ref No: m18V/om/101
Issue No: 07

1. TECHNICAL DETAILS The unit has following optional features.

1) Flow Alarms /Batch


This is a versatile micro controller Relays Output(Factory
based Flow Indicator Totaliser unit. Set)
With very high performance to price Two High/low alarm
ratio. relays with one
changeover contact type
The features offered in this product are having 2A/230 VAC
better than any other Totaliser available Contact rating.
in similar price range. 2) Rs-232/485 serial port.
3) 24V DC power supply.
The instrument is made in 144 x 72 x 4) 4-20 mA Retransmission
175 mm³ size with standard cutout of Output
138 x 68 mm². Front is sealed
membrane type to withstand dusty
environment. On back plate, detachable
terminals are provided for easy
connections. The programming of the
instrument is done by a 6-button
keypad, equipped with two independent
displays for flow rate and integrated
total. Status of alarm relays are
displayed by 3 mm red LED.

The operation of the instrument is


menu- driven with user-friendly
prompts. For protecting programmed
data password protection facility is
provided. Integrated total is stored in
NVRAM and can be erased from using
specific password.

The product is made to accept the


standard inputs, 4 - 20mA, 0- 20mA,
1-5 Volt, 0- 5 volt ,0- 10 volt and 0-
10kHZ pulse inputs. It is available as a
single input version only. The
calibration of the unit is done through
trim pots.

There are four relays, which can be used


either as Hi, Lo alarms for process
variable and Prewarn, End of program
set point for batch total.

Provision for zero and span setting is


made to restrict range of usage and
programming. This restricts accidental
wrong setting of set-point beyond the
range of interest. Outside this range the
display will start flashing process
variable. This zero and span setting is

Operator’s Manual Page 3 of 14


FLOW INDICATOR TOTALISER 1008V masibus
Ref No: m18V/om/101
Issue No: 07

2. SPECIFICATIONS • On load resistance: 500E or


less
• Output accuracy: ± 0.25% of
DISPLAY
full scale +1 count
• Resolution: 12 bits (5mA)
• 4 digit 0.56" Red LEDs for Flowrate
• 8 digit 0.36" Red LEDs for
C. Communication
Integrated total.
• Protocol: Modbus RTU serial
• Four individual discrete 3 mm Red
• Standard: EIA RS-485 / RS -
LEDs to indicate relay status of
232.
batch & Alarm relays.
• Max. Communication
distance: ≤1200 mtrs. (For
INPUT (Factory Set)
9600 bps RS 485)
• Communication rate:9600,
• 0-20 mA, 4-20mA.
19200 bps
• 0-5V, 1-5V, 0-10V.
• Max. Connectable
• 0-10kHz pulse input.
controllers/Indicator: 32
• Accuracy: • Address range: 1 to 99
± (0.25% of F.S + 1Digit) - For
I/P signal D. Digital input
• Usage : To start a new
± (0.45% of reading + 1Digit) - batch.
Integrated / Batch total GENERAL

# for pulse input low voltage level: • Power supply:


0-5Volt and high voltage level 110V/230V +/-10% AC 50Hz
5-15 Volt. (Jumper selectable on Terminals)
• Transmitter Power supply:
CALIBRATION 24VDC +/- 5% @ 50mA
• Ambient Temperature:
• Zero and Span adjusted by trim pot 0 to 55 °C
only. • Humidity:
Up to 95% RH non-condensing
CONTROL KEYS AND TERMINALS • Power consumption:
Less than 10 VA
• Index, Enter, Digit Select (→), Warm-up time: 10 minute
Increment (↑) START & STOP for
operation, programming and PHYSICAL
calibration.
• Case:
OPTIONAL FEATURES M.S. powder coated with ABS
molded bezel
A. Contact Output: • Terminals:
• Usage: Flow alarm & batch Detachable PCB type terminal
(Factory Set) block can accept up to 2.5 mm²
• Number of relay contact wire
outputs: • Bezel size:
• Two High/low alarm relays. 144(H) X 72(W) mm²
• Relay contact rating: • Depth behind Panel:
• 250VAC/2Amps. 175 mm maximum including
• Relay contact terminal: 3 terminals
• Panel cutout:
B. Retransmission Output: 138(H) X 68(W) mm²
• Number of output points: 1 • Weight:
• Output Signal: 4 to 20 mA DC Approximately: 1.58 kg.

Operator’s Manual Page 4 of 14


FLOW INDICATOR TOTALISER 1008V masibus
Ref No: m18V/om/101
Issue No: 07

3. DIMENSIONS & . 4. FRONT FASCIA


PANEL CUTOUT
• Process Variable : Process Value
• Integrated total: indicates
integration of process value.
• AL1: Low Alarm(for PV)
• AL2: High Alarm(for PV)
• WP: Pre warn process indication (for
batch process).
• EP: End of process indication (for
batch process)
• INDEX: Indexing Parameter in
Various Modes
• ENTER: Saves Desired Parameter in
Various Modes.
• Digit Select (→): Select next digit
and also can be used as START key
while batching.
• Increment (↑): Increment the
Selected Parameter Value to Desired
Value.
• RXD&TXD: Indication of
communication.

FLOW RATE

BATCH TOTAL/INTEGRATED TOTAL

RXD
INDEX
TXD

AL1
ENTER
AL2

WP
START STOP
EP

m asibus 1008V

Operator’s Manual Page 5 of 14


FLOW INDICATOR TOTALISER 1008V masibus
Ref No: m18V/om/101
Issue No: 07

5. CONNECTIONS read the instructions carefully before


altering any configuration.
DETAIL
6.2 INSTALLATION GUIDE
The description of the Back Panel
terminals is as follows:
Unpack the instrument from the packing
box carefully.
Low Flow Analog Input/ Mount the instrument in the panel cut-
Alarm Relay: TPS out of 138 mm X 68mm. Fix the
AL1 instrument with the panel using side
1: NO 15: Analog input 1 brackets.
+VE
2: COMMON 16: +24VDC@ All the electrical connections to be done
50mA (TPS) at the back panel of the unit using spade
3: NC 17: Input/TPS -VE lugs. Refer the manual for back panel
High Flow Serial Interface connections.
Alarm Relay:
AL2 Make sure that no wire is connected
4: NO 18: RXD/RxTxA loosely to avoid generation of spark and
5: COMMON 19: TXD/RxTxB RFI.
6: NC 20: GND (Digital)
Batching Mains +24VDC Connect mains cord on the back panel
Relay: WP Input Supply on the P,N and E terminals.
7: NO 21 N2:
Neutral Before connecting the mains, check the
8: COMMON 22 N1: +VE mains configuration inside the
9: NC 23 L2: -VE instrument.
Batching 24 L1:
Relay: EP Phase Earth the instrument properly.
10: NO 25 : Earth
11: COMMON For 230VAC Supply: short Some of the contacts are powered.
L2 & N1 Hence don’t touch any terminal directly
12: NC (22&23)
when power is applied to the instrument.
Retransmissio For 115VAC Supply: short
L1&L2(21&22) short Whenever any connection is to be made
n
N1&N2(23&24) or removed from the unit, always switch
13: Output –VE off the power.
14: Output +VE I/P TYPE SELECTION
JUMPER PULSE mA
J1 1-2 2-3 6.3 DISPLAY & KEY BOARD
J2 2-3 1-2
Display on top row is organized as 4
digit 0.56" Red LEDs for Flowrate
6. USER GUIDE variable. The second group of display is
eight digits it indicates integration of
process variable. In normal mode of
6.1 INTRODUCTION
operation, it displays integrated / Batch
total. While in EDIT mode, parameters
1008V is flow indicator totaliser user-
are displayed in this window.
friendly key-pad and display for guiding
the user with programming and
There are six keys for operation of the
calibration operation. The levels of
instrument. For understanding the
protections decide access to set-points,
operation first let us see the operation of
configuration and calibration. The
keys.
manual covers all aspects of operation of
the instrument. Users are requested to
Unit has 6 key membrane keypad
organized as 6 x 1 matrix.

Operator’s Manual Page 6 of 14


FLOW INDICATOR TOTALISER 1008V masibus
Ref No: m18V/om/101
Issue No: 07

List of keys and their functions: Press ‘Index’ key to enter into edit
mode.
KEYS FUNCTION
Index Enter into Entry/Verification mode First three parameter displayed in Lower
select parameter
display window with each depression of
Enter Save New Data and terminate
Edit mode. If ‘Enter’ key is ‘Index’ Key is: Integrated Total, Batch
pressed twice, unit comes out of Total & Roll count. These are non-
EDIT mode. (i.e. comes to normal editable parameters.
mode)
Digit Shift (™) Select Digit
Increment (↑) Increment selected digit value
Fourth Parameter is Password. When
Start Clear Batch Total (to be use with ‘Index’ Key is pressed after third
Batching) parameter, lower display window will
Stop Stop/Reset Batch (to be use with show ‘PASS’ for a moment and then it
Batching)
will start displaying ‘0000’ with flashing
Left most digit .The unit is prompting
When Instrument is in Edit mode, for Password. Password is a four digit
Increment and Digit Select will be used as no. There are two different passwords.
data entry keys and when the instrument
is in Normal mode of operation the keys Operator's Password: 0101
will be Batching (START / STOP) Key.
Engineer's Password: 1234

7. MODE OF Enter any one of the above password


OPERATION using data entry keys. When ‘Enter’ key
is pressed, the validity of Password is
checked. If wrong password is entered
There are following modes of operations. the unit comes out of edit mode and
• Normal mode displays engineering value.
• Edit mode
Press ‘Index’ key again if you want to
7.1 NORMAL MODE enter into edit mode.

When ever mains is switched on to If correct password is entered, then also


The unit, engineering value Proportional the unit starts Indicating Engineering
to the input signal will be displayed as value of input. Now press ‘Index’ key,
Process variable. Decimal point is the display will show name of the
displayed at selected position. parameter to be modified and its value
after a moment.
Last saved integrated/batch total
will also be displayed on the lower Now press ‘INDEX’ key to go to any one
window as per selection in “Different of the listed parameters as below. When
Display” parameter. the parameter is selected its current
value is being displayed in the totaliser
7.2 EDIT MODE field of display.

In this mode user can verify or modify: The data field of the display will show
Calibration zero, Calibration span, Zero, parameter one by one. The various
Full scale, decimal point, Time base and parameters that will appear on the
Conversion mode settings. Integrated display with successive pressing of the
total can also be cleared to Zero using a ‘INDEX’ Key are:
command from this mode. Entry into
Edit mode is protected by Password. It Integrated Total
bt Batch Total
Press ‘Index’ key to enter into edit rC Roll count
mode. PS Password

Operator’s Manual Page 7 of 14


FLOW INDICATOR TOTALISER 1008V masibus
Ref No: m18V/om/101
Issue No: 07

CALZ Calibration Zero/Offset Press ‘INCREMENT’ key the no. at the


CALS Calibration Span selected digit position will increment and
bd Baud Rate rolls back to ‘0’ when it reaches at ‘9’.
(19200,9600,4800)
dP Decimal Point Once desired digit is set, press digit
Un Unit Number select key (→) to select next digit. The
FS Full Scale next selected digit will flash. Set it to
Id Unit Identification No. desired value as per the above step.
In Input Type (4-20mA,
0-20mAPULSE,0-5V,0-10V) Once all the digits are set, press ‘ENTER’
F1 Flow Alarm 1 key. The display will stop flashing.
F2 Flow Alarm 2
INDICATION
Pr Pre warm
SP Set Point
In normal mode of operation, input is
CF Conversion Factor
converted to frequency using V to F
CI Clear Integrated Total and
converter.
Roll Over Count
The same is measured by the unit. Full
d.d Default display (Integrated
scale value of frequency is 10 KHz.
Total & Batch Total)
In linear indication mode (Unit no. 1 to
Following the above process, one can 4), the measured input current is
select any of the above listed converted to engineering value as per
parameters. When the parameter is the following equation using the set
selected its current value is being values of FS.
displayed in the totaliser field of display
and display will start flashing, indicating Flow Rate Indication =
that you can modify the digit. (I/P current – 4) * FS / 16

Use ‘Digit shift’ and ‘INCREMENT’ key to Re-transmitted output current will be
modify the selected parameter. linearly proportional to calculated flow
rate.
Once new data is set for the particular
mode, press ‘ENTER’ Key to save that Output will be 4.00mA DC for Zero and
data in NVRAM. Otherwise it will not 20.00mA for full scale.
save. On pressing ‘ENTER’ key will stop
display flashing. Integration is done as per the set time
base (unit) and conversion factor.
By pressing ‘START’ key in between. the
display shows flow rate and batch total. SQUARE ROOT EXTRACTION:

If no key is pressed for more than 25 This is a built-in feature of this unit.
seconds, the Data entry/programming Indication can be linear or square root of
mode is terminated automatically and input.
display will show flow rate and
Integrated / batch total. Square root extraction when unit no. is
set from 5 to 8.
ENTER/MODIFY PARAMETER VALUE:
For square root extraction mode:
Use Digit shift (→), increment ( ↑), and Indication = N * Full scale
‘ENTER’ key to enter or modify any N= square root ((input current – 4)/16)
numeric data.

Where in data entry/edit mode, the


selected digit will be flashing.

Operator’s Manual Page 8 of 14


FLOW INDICATOR TOTALISER 1008V masibus
Ref No: m18V/om/101
Issue No: 07

UNIT No. SETTING IS INTERPRETED


AS PER FOLLOWING TABLE. The value of ‘It’ depends on FS, Time
base (Unit), Conversion Factor and
UNIT NO TIME BASE SCALING Decimal Point settings. If these
1 Second Linear parameters are changed, the stored
value of ‘It’ will not be correct. Before
2 Minute Linear
making any change in FS, Unit,
3 Hour Linear
Conversion Factor (CF) and/or DP,
4 Day Linear Integrated total should be cleared using
5 Second Square root ‘CI’ function.
6 Minute Square root
7 Hour Square root For updating it value, the flow rate is
8 Day Square root divided by value of conversion factor
(CF).
REMOTE OPERATION: (Optional)
Conversion factor is a six digit no. with
Normally the parameter values are two digits after decimal point. Format is
set/Verified using membrane keypad on XXXX.XX.
the front.
CLEAR INTEGRATED & BATCH
But for applications when unit is to be TOTAL:
housed in Explosion proof enclosure or
some other enclosure, parameter setting In edit mode, select parameter CI.
and verification can be done using Enter value of ‘654321’.
remote keypad. The It & bt will be reset to Zero; Roll
over count (rC) will also be reset to
On Back panel of the unit, parallel Zero.
connections to the membrane keypad
are provided for remote keyboard wiring WARM-UP-TIME:
is on a 9-pin D-type connector.
Once you switch – on your instrument, it
For remote keyboard wiring is to be need 10 minutes for warm up. Wait for
done by following schematic. It should this period before getting correct
be a 4 x 2 matrix. indication. Once unit is switched on, it
shows actual flow rate. Integration is
INCR DIGIT ENTER INDEX START also performed as per flow rate and
STOP other related settings. In normal
operation, batch total (bt) is indicated.
Return line (RL)
K1 K2 K3 K4 K5 K6 ALARM RELAYS:

INTEGRATED TOTAL (It): There are two alarm relays available


with the unit (F1 & F2). Value of both
As per the selected time base (unit), Full the alarms is settable. Alarm F1 is
scale (FS) and Conversion Factor (CF) configurable for low alarm and alarm F2
setting, integrated total is updated. This is configured for High Flow alarm. When
is an eight no. If the number rolls over, flow is lower then F1 setting, Relay F1
the roll over count (rC) will be will switch On, LED on front also will
incremented by one. This total is non glow. When flow is more then F1, the
reset able. relay F1 is switched off.

It is stored in serial NVRAM, which does If flow is greater then F2 setting,relay


not need battery back up. On power for Alarm F2 is switched On, LED on
down, current data is stored on NVRAM front also glows. During normal flow
by early sensing of power failure.

Operator’s Manual Page 9 of 14


FLOW INDICATOR TOTALISER 1008V masibus
Ref No: m18V/om/101
Issue No: 07

condition, F1<Flow<F2, no alarm relay INPUT TYPE (In):


will be on.
Type of process input to instruments is
Change over contacts from both the keyboard selectable. Through edit mode,
relays is available on the back panel. select appropriate input type
(0-20mA/4-20mA/0-5V/1-5V/0-10V/
BATCHING OPERATION: pulse) as per your process. Apply your
process input between terminal no. as
This unit has two batching relays. With shown in back plate connection table.
help of this batching operation can be
performed. It supports two stage There is two input type. It is selectable
batching control. There are two relays: through jumper inside the CPU card
pre warn and set point. One can set PCB.
value for each relay (Pr and SP). These INPUT 1: In case of pulse input short
are six digit settings including decimal jumper J1.
point. Using Edit mode one can set value INPUT 1: In case of 4-20mA Dc short
of Pr and SP. Value of Pr should be less jumper J2.
then SP. If Pr is set more than SP, it is
truncated to SP. CALIBRATION:

To start batch operation, press ‘START’ CALIBRATION PROCEDURE:


Key. Value of ‘bt’ is reset to zero. Relays
for both Pr and Sp are switched On. The Instrument is duly calibrated at the
When integrated total for current batch factory. For any reason, if re-calibration
i.e. ‘bt ‘reaches to set value of Pr, relay is required follow the procedure as
of Pr is switched Off. Once Batch total defined below.
(bt) crosses set point (sp) value, relay As explained earlier, One can do
for SP is switched OFF. calibration thro' the keyboard itself, no
trimming of potentiometer is required.
Contacts for Both the relays are The Zero and Full-scale values are stored
available on the back panel. LED in NVRAM. The calibration is allowed
Indications are available on the front. only in Engineer's Password mode.
One can terminate the batch by pressing
‘Stop’ key. If stop key is pressed, both 1. Switch on the instrument and allow 15
the relays are switched off. If you press minutes of warm up time before starting
stop key again batch will start from the calibration.
same value where it has been stopped. 2. Take a standard source. Set it’s
One can start new batch by pressing output at desired Zero (CALZ) value.
Start key again. Apply output of the source to the input
terminals (1 & 3) of the indicator.
If mains power goes OFF during 3. Go to EDIT mode:
batching is going. On, the status of  Enter engineers: Password '1234'.
batching stored in NVRAM. When Power  Press INDEX key after entering
comes, batching is resumed from the this Password.
point it has stopped.  The parameter 'CALZ ' for Zero
will be displayed.
IDENTIFICATION No. (ID)  Actual row counts will be
displayed.
When the FIT is connected on RS485  Allow the reading to settle, press
multi-drop environment, is to be 'Enter' Key.
addressed by this identification code  This count will be stored as
(unit no.) Zero/Offset reading.
4. Now apply input equal to Full
scale/Span (CALS):
 Press 'Index' key again.

Operator’s Manual Page 10 of 14


FLOW INDICATOR TOTALISER 1008V masibus
Ref No: m18V/om/101
Issue No: 07

 ‘CALS' for Span calibration will be


displayed. CONVERSION FACTOR (CF):
 Row counts of VFC will be
displayed. It is a constant which simply divides
 Allow the reading to settle and process value by the factor set.
Press ' Enter' key. Usually, it is set as ONE (1).
 This reading will be stored as For example, if process value is 100
Span/Full scale. liters/minute & conversion factor is
1 then it will simply integrate
Now the instrument is calibrated. process value as it is. If we change
conversion factor = 2, then it will
For again entering into calibration mode, divide process value by that factor
you have to wait till the instruments go i.e. 100/2 = 50 & it integrates that
to normal mode. After that go to EDIT value (in both integral and batch
mode thro' Engineers' Password and total) but on the display it shows
perform calibration. original process value.

An OPEN msg. will appear in Upper DEFAULT DISPLAY (d.d):


Display window, when input is 5% less Depending up on selection of
than its minimum value. “Default Display” parameter in menu
as batch total or integral total the
An OVER msg. will be displayed, when respective value of the parameter
input is 5% higher than its maximum (batch total/integral total) will be
value. displayed in normal mode.

If input terminals are open, then also


upper window will show ‘OPEN’
message.

Operator’s Manual Page 11 of 14


FLOW INDICATOR TOTALISER 1008V masibus
Ref No: m18V/om/101
Issue No: 07

8. Modbus Protocol

REGESTERS TABLE
DIGITAL PARAMETERS READ:
HEX ADDRESS Register No. Parameter Function
00 00001 Lo alarm Status Relay Status 1
01 00002 Hi alarm Status Relay Status 2
02 00003 Pre-warn Status Relay Status 3
03 00004 Set-point Status Relay Status 4

MSB 3 2 1 ISB
WP: Pre warn process (for batch process) Relay4 Relay3 Relay2 Relay1
EP: end of process (for batch process) (EP) (WP) (AL12) (AL1)

Bit will be ‘0’ if relay is off


Bit will be ‘1’ if relay is on

DIGITAL PARAMETER WRITE:

Hex Address Register No. Parameter Function


00 00005 Start/stop Start/Stop Batching
If Data=0000 Start batch
Data= 0001 toggle batch status
Between start/stop

ANALOG PARAMETERS:
Hex Register Parameter Function
Address No.
00 40001 Batch Total L5W (2 Byte) Read the Batch Total Value
01 40002 Batch Total MSW (2 Byte) (4 Byte)
02 40003 Integrated Total L5W(2 Byte) Read the Integrated Total Value
03 40004 Integrated Total MSW(2 Byte) (4 Byte)
04 40005 Set Point L5W (2 Byte) Read/Write the Set Point Value
05 40006 Set Point MSW (2 Byte) (4 Byte)
06 40007 Pre warn L5W (2 Byte) Write the Pre warn value
07 40008 Pre warn MSW (2 Byte) (4 Byte)
08 40009 Conversion Factor L5W Read/Write conversion factor
(2 Byte) value (4 Byte)
09 40010 Conversion Factor MSW
(2 Byte)
OA 40011 Flow Rate (2 Byte) Read the Flow Rate Value
OB 40012 Full Scale (2 Byte) Read/Write the Full Scale Value
OC 40013 Low Alarm (2 Byte) Read/Write the Low Alarm Value

OD 40014 High Alarm (2 Byte) Read/Write the High Alarm


Value
OE 40015 RC + Null Read the RC (roll count)
OF 40016 DP Value + Null Read/Write the DP Value
(0,1,2,3)
10 40017 Unit No. + Null Read/Write the Unit No. (0001
to 0008)

Operator’s Manual Page 12 of 14


FLOW INDICATOR TOTALISER 1008V masibus
Ref No: m18V/om/101
Issue No: 07

How to Test: -

To test this all parameters in MODSCAN32 application, do the following settings:


1. Set Device Id to1 for all.

2. Set Length according to requirements.

3. Set Modbus point Type according to the parameter type.

a). For Analog parameters READ: Set the Modbus point Type to HOLDING
REGISTER and
Address from 0001 to 0017 in Modbus application.
For Example1:
Suppose the Batch total Value displayed is 562017 (or 56201.7), To read
it, Set address to 0001 and Modbus point Type to HOLDING REGISTER.
(Length -for displaying only batch total could be to 2).
Its hex value will be 0x00089361. Four bytes are used to display batch
total (bt) in serial application according to the table shown above.
So, the modscan32 will show at address
40001 [9361](lower 2 byte)
40002 [0008](higher 2 byte)
Example2:
If Full-scale value (FS) = 800.0(hex will be 1F40, converted according to
8000, no decimal point consideration) Two bytes for full scale (FS).
Then the modscan32 will show at address
40012 [1F40]
Note: In serial decimal point is not taken into consideration.

b). For Digital parameters READ:


To read the relay status, set the Modbus point Type to COIL STATUS
and Address to 0001 to 0004
Example1:
If Lo alarm relay is on , Modbus application will show at Address:
00001 [1].
00002 [0] (Hialarm led is off)

Operator’s Manual Page 13 of 14


FLOW INDICATOR TOTALISER 1008V masibus
Ref No: m18V/om/101
Issue No: 07

Example2:
If start is given then Loalarm, SP and WP relay will be on and Hialarm
relay will be off .Set Address to 0001 and Length to 4. So, Modbus App.
will show:
00001 [1]. (Lo alarm relay will be off)
00002 [0]. (Hi alarm relay will be off)
00003 [1]. (PreWarn relay will be on)
00004 [1]. (SP relay will be on)

c). For digital /Analog parameters WRITE:


We can only do START and STOP function from serial Application.
For this the address should be displayed in the application first. Then double click
on the address to be modified and then a screen will be opened with name
1. Write coil (for digital parameter –start -stop)
2. Write Register (for analog parameter –for all)
Change the status or value according to parameter (for start stop on off is to be
done, but for analog parameters value should be entered) and click on UPDATE
icon. The value will be updated.

Operator’s Manual Page 14 of 14