You are on page 1of 2

Material submittal: PHCC-32-MT-HVAC-0002 Rev.

02

Revised and resubmit: Code C

Comments :

 AC unit selection shall be based on ambient condition 46 Deg C and


30000Btu/hr capacity as mentioned in equipment schedule.

 Final approval on given model of AC machine is subjected to PHCC and CCTV


specialist recommendation and approval

 Both the Units T1 and T3 shall be same model as attached in data sheet and
shall have same ambient temp. as mentioned in data sheets.

 Contractor to be ensure Indoor unit fan shall be 3 speed and AC units shall be
compatible to run in different modes as per specification Section HVAC Part 2
clause B.5

Yaseen Khan
Mechanical engineer