Technical report

MVCables (34,5 kV)


Talinay WindFarm
1. Electric current carrying capacity

This study was based on the following assumptions:


•The maximum conductor temperature: +90ºC.
•Mutual heating due to the presence of other cables/heat sources laid on the vicinity was
not considered
• Temperature and soil conditions as per Figure 1.
• Depth at the centre of the trefoil: 1100 mm.

The electric current rating was calculated in accordance to the IEC standard 287 –
Calculation of the continuous current rating of cables (100% load factor)).
The current carrying capacity is given by:

Δθ  WD 0.5 T1  T 3  T 4 
I
R T1  (1  λ) (T 3  T 4 )
Where:
: temperature difference between the conductor and surrounding soil (K)
WD: dielectric losses (W/m)
T1: Thermal resistance between the conductor and the metallic screen (K.m/W)
T3: Thermal resistance of the external serving of the cable (K.m/W)
T4: Thermal resistance between the cable outer surface and the surrounding medium
(K.m/W)
R: Alternating current resistance of the conductor at 90ºC (/m)
: Ratio of the losses in the metallic screen to the total losses in all the conductors in that
cable.

T=1.5 K.m/W
=1 5 K m/W
1100 mm

30ºC

Fig. 1: Trench layout.

Doc.HVS070311A 2
1. Cable RHZ1-OL 1x95RM/16

Description Unit 1 2 3

Cable type no 1 1 1
Resistances (DC/AC)
DC Resistance of Conductor @ 20°C /km 0,32 0,32 0,32
DC Resistance of Conductor @ Operating Temperature /km 0,41027 0,41027 0,41011
AC Resistance of Conductor @ 20°C /km 0,32022 0,32022 0,32022
AC Resistance of Conductor @ Operating Temperature /km 0,41055 0,41055 0,41038
DC Resistance of Concentric Wires @ 20°C /km 1,13261
, 1,13261
, 1,13261
,
DC Resistance of Concentric Wires @ Operating Temperature /km 1,40369 1,40369 1,40313
Losses
Conductor Losses W/m 16,12164 16,12164 16,12164
Dielectric Losses W/m 0 0 0
Metallic Screen Losses W/m 0 0816
0,0816 0 0816
0,0816 0 08163
0,08163
Total Losses W/m 16,20324 16,20324 16,20327
Capacitance, Inductance, Impedance
Capacitance F/km 0,17676 0,17676 0,17676
Inductance of Conductor mH/km 0,43462 0,43462 0,43462
R
Reactance off Conductor
C d /k
/km 0 13654
0,13654 0 13654
0,13654 0 13654
0,13654

Inductance of Metallic Sheath mH/km 0,17204 0,17204 0,17204

Reactance of Metallic Sheath /km 0,05405 0,05405 0,05405

0.41055 + 0.41055 + 0.41038 +


Positive Sequence Impedance /km
j0.13654 j0.13654 j0.13654

0.41055 - 0.41055 - 0.41038 -


Negative Sequence Impedance /km
j0.13654 j0.13654 j0.13654

1.45276 + 1.45276 + 1.45276 +


Zero Sequence Impedance /km
j0.05405 j0.05405 j0.05405

Doc.HVS070311A 3
Symbol Description Unit 1 2 3

Cable type no 1 1 1
Normal Operation IEC 60287-1-1
Ro Conductor DC Resistance at 20°C /m 3,20E-04 3,20E-04 3,20E-04
R' Conductor DC Resistance at Max Temp /m 4,10E-04 4,10E-04 4,10E-04
R Conductor AC Resistance at Max Tempp /m 4,11E-04
, 4,11E-04
, 4,10E-04
,
Ks Factor Used in Calculating Xs (Skin Effect) 1,00E+00 1,00E+00 1,00E+00
Kp Factor Used in Calculating Xp (Proximity Effect) 1,00E+00 1,00E+00 1,00E+00
ys Skin Effect Factor 4,88E-04 4,88E-04 4,89E-04
yp Proximity Effect Factor 1,83E-04 1,83E-04 1,83E-04
dc Conductor Diameter m 1 14E-02
1,14E-02 1 14E-02
1,14E-02 1 14E-02
1,14E-02
c Distance Between Conductor Axes m 0,00E+00 0,00E+00 0,00E+00
C Cable Capacitiance F/m 1,77E-10 1,77E-10 1,77E-10
tan  Dielectric Loss Factor 4,00E-03 4,00E-03 4,00E-03
 Insulation Relative Permitivity 2,50E+00 2,50E+00 2,50E+00
Wd C bl Dielectric
Cable Di l t i Losses
L Per
P Phase
Ph W/
W/m 0 00E+00
0,00E+00 0 00E+00
0,00E+00 0 00E+00
0,00E+00
1 Screen Loss Factor 5,06E-03 5,06E-03 5,06E-03
'1 Screen Loss Factor Caused by Circulating Current 5,06E-03 5,06E-03 5,06E-03
''1 Screen Loss Factor Caused by Eddy Current 0,00E+00 0,00E+00 0,00E+00
2 Armour Loss Factor 0,00E+00 0,00E+00 0,00E+00
Rs Screen AC Resistance at Cable Normal Operation /m 0,00E+00 0,00E+00 0,00E+00
gs Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1 0,00E+00 0,00E+00 0,00E+00
1 Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1 0,00E+00 0,00E+00 0,00E+00
s Screen Electrical Resistivity @ Operating Temp. .m 0,00E+00 0,00E+00 0,00E+00
Normal Operation IEC 60287-2-1
T1 Thermal Resistance Between Conductor-Screen C.m/W 0,56439 0,56439 0,56439
t3 Thickness of Jacket m 0,003 0,003 0,003
T j Thermal Resistivity of Jacket C.m/W 3,5 3,5 3,5
C. Cable Direct Buried
T4 Thermal Resistance of Surrounding C.m/W 3,04836 3,04836 3,04056
L Depth of cable axis m 1,111 1,111 1,077
I Cable Current Ampacity A 198,2 198,2 198,2

Doc.HVS070311A 4
2. Cable RHZ1-OL 1x150RM/16

Description Unit 1 2 3

Cable type no 1 1 1
Resistances (DC/AC)
DC Resistance of Conductor @ 20°C /km 0,206 0,206 0,206
DC Resistance of Conductor @ Operating Temperature /km 0,26411 0,26411 0,26397
AC Resistance of Conductor @ 20°C /km 0,20637 0,20637 0,20637
AC Resistance of Conductor @ Operating Temperature /km 0,26459 0,26459 0,26445
DC Resistance of Concentric Wires @ 20°C /km 1,14432 1,14432 1,14432
DC Resistance of Concentric Wires @ Operating Temperature /km 1,42292 1,42292 1,42217
Losses
Conductor Losses W/m 16,67842 16,67842 16,67842
Dielectric Losses W/m 0 0 0
Metallic Screen Losses W/m 0,12526 0,12526 0,12533
Total Losses W/m 16,80369 16,80369 16,80375
Capacitance, Inductance, Impedance
Capacitance F/km 0 20489
0,20489 0 20489
0,20489 0 20489
0,20489
Inductance of Conductor mH/km 0,40181 0,40181 0,40181
Reactance of Conductor /km 0,12623 0,12623 0,12623

Inductance of Metallic Sheath mH/km 0,16938 0,16938 0,16938

Reactance of Metallic Sheath /km 0 05321


0,05321 0 05321
0,05321 0 05321
0,05321

0.26459 + 0.26459 + 0.26445 +


Positive Sequence Impedance /km
j0.12623 j0.12623 j0.12623

0.26459 - 0.26459 - 0.26445 -


Negative Sequence Impedance /km
j0.12623 j0.12623 j0.12623

1.35057 + 1.35057 + 1.35057 +


Zero Sequence Impedance /km
j0.05321 j0.05321 j0.05321

Doc.HVS070311A 5
Symbol Description Unit 1 2 3

Cable type no 1 1 1
Normal Operation IEC 60287-1-1
Ro Conductor DC Resistance at 20°C /m 2,06E-04 2,06E-04 2,06E-04
R' Conductor DC Resistance at Max Temp /m 2,64E-04 2,64E-04 2,64E-04
R Conductor AC Resistance at Max Temp /m 2,65E-04 2,65E-04 2,64E-04
Ks Factor Used in Calculating Xs (Skin Effect) 1,00E+00 1,00E+00 1,00E+00
Kp Factor Used in Calculating Xp (Proximity Effect) 1,00E+00 1,00E+00 1,00E+00
ys Skin Effect Factor 1,18E-03 1,18E-03 1,18E-03
yp Proximity Effect Factor 6,13E-04 6,13E-04 6,14E-04
dc Conductor Diameter m 1,45E-02 1,45E-02 1,45E-02
c Distance Between Conductor Axes m 0,00E+00 0,00E+00 0,00E+00
C p
Cable Capacitiance F/m 2,05E-10
, 2,05E-10
, 2,05E-10
,
tan  Dielectric Loss Factor 4,00E-03 4,00E-03 4,00E-03
 Insulation Relative Permitivity 2,50E+00 2,50E+00 2,50E+00
Wd Cable Dielectric Losses Per Phase W/m 0,00E+00 0,00E+00 0,00E+00
1 Screen Loss Factor 7,51E-03 7,51E-03 7,51E-03
'1
 Screen Loss Factor Caused by Circulating Current 7 51E-03
7,51E-03 7 51E-03
7,51E-03 7 51E-03
7,51E-03
''1 Screen Loss Factor Caused by Eddy Current 0,00E+00 0,00E+00 0,00E+00
2 Armour Loss Factor 0,00E+00 0,00E+00 0,00E+00
Rs Screen AC Resistance at Cable Normal Operation /m 0,00E+00 0,00E+00 0,00E+00
gs Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1 0,00E+00 0,00E+00 0,00E+00
1 C ffi i t Used
Coefficient U d in
i IEC 60287-1-1
60287 1 1 Clause
Cl 2.3.6.1
2361 0 00E+00
0,00E+00 0 00E+00
0,00E+00 0 00E+00
0,00E+00
s Screen Electrical Resistivity @ Operating Temp. .m 0,00E+00 0,00E+00 0,00E+00
Ds External diameter of Screen (Sheath) m 0,00E+00 0,00E+00 0,00E+00
ts Screen (Sheath) Thickness m 0,00E+00 0,00E+00 0,00E+00
m Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1 0,00E+00 0,00E+00 0,00E+00
Normal Operation IEC 60287-2-1
T1 Thermal Resistance Between Conductor-Screen C.m/W 0,48285 0,48285 0,48285
t3 Thickness of Jacket m 0,003 0,003 0,003
T j Thermal Resistivity of Jacket C.m/W 3,5 3,5 3,5
C. Cable Direct Buried
T4 Thermal Resistance of Surrounding C.m/W 3,00575 3,00575 2,9958
L Depth of cable axis m 1,112 1,112 1,076
I Cable Current Ampacity A 251,1 251,1 251,1

Doc.HVS070311A 6
3. Cable RHZ1-OL 1x240RM/16

Description Unit 1 2 3

Cable type no 1 1 1

DC R
Resistance
i t off Conductor
C d t @ 20°C /k
/km 0 125
0,125 0 125
0,125 0 125
0,125
DC Resistance of Conductor @ Operating Temperature /km 0,16026 0,16026 0,16014
AC Resistance of Conductor @ 20°C /km 0,12568 0,12568 0,12568
AC Resistance of Conductor @ Operating Temperature /km 0,16113 0,16113 0,16101
DC Resistance of Concentric Wires @ 20°C /km 1,16081 1,16081 1,16081
DC Resistance of Concentric Wires @ Operating Temperature /km 1,44786 1,44786 1,44675

Conductor Losses W/m 17,34335 17,34335 17,34335


Dielectric Losses W/m 0 0 0
Metallic Screen Losses W/m 0,20317 0,20317 0,20333
Total Losses W/m 17,54652 17,54652 17,54667

Capacitance F/km 0,24076 0,24076 0,24076


Inductance of Conductor mH/km 0,37124 0,37124 0,37124
Reactance of Conductor /km 0,11663 0,11663 0,11663

Inductance of Metallic Sheath mH/km 0,16652 0,16652 0,16652

Reactance of Metallic Sheath /km 0,05231 0,05231 0,05231

0.16113 + 0.16113 + 0.16101 +


Positive Sequence Impedance /km
jj0.11663 jj0.11663 jj0.11663

0.16113 - 0.16113 - 0.16101 -


Negative Sequence Impedance /km
j0.11663 j0.11663 j0.11663

1.28621 + 1.28621 + 1.28621 +


Zero Sequence Impedance /km
j0.05231 j0.05231 j0.05231

Doc.HVS070311A 7
Symbol Description Unit 1 2 3

Cable type no 1 1 1
Normal Operation IEC 60287-1-1
Ro Conductor DC Resistance at 20
20°C
C /m 1 25E-04
1,25E 04 1 25E-04
1,25E 04 1 25E-04
1,25E 04
R' Conductor DC Resistance at Max Temp /m 1,60E-04 1,60E-04 1,60E-04
R Conductor AC Resistance at Max Temp /m 1,61E-04 1,61E-04 1,61E-04
Ks Factor Used in Calculating Xs (Skin Effect) 1,00E+00 1,00E+00 1,00E+00
Kp Factor Used in Calculating Xp (Proximity Effect) 1,00E+00 1,00E+00 1,00E+00
ys Ski Eff
Skin Effectt Factor
F t 3 19E 03
3,19E-03 3 19E 03
3,19E-03 3 20E 03
3,20E-03
yp Proximity Effect Factor 2,25E-03 2,25E-03 2,25E-03
dc Conductor Diameter m 1,85E-02 1,85E-02 1,85E-02
c Distance Between Conductor Axes m 0,00E+00 0,00E+00 0,00E+00
C Cable Capacitiance F/m 2,41E-10 2,41E-10 2,41E-10
tan  Dielectric Loss Factor 4,00E-03 4,00E-03 4,00E-03
 Insulation Relative Permitivity 2,50E+00 2,50E+00 2,50E+00
Wd Cable Dielectric Losses Per Phase W/m 0,00E+00 0,00E+00 0,00E+00
1 Screen Loss Factor 1,17E-02 1,17E-02 1,17E-02
'1 Screen Loss Factor Caused by Circulating Current 1,17E-02 1,17E-02 1,17E-02
''1 Screen Loss Factor Caused by Eddy Current 0,00E+00 0,00E+00 0,00E+00
2 Armour Loss Factor 0,00E+00 0,00E+00 0,00E+00
Rs Screen AC Resistance at Cable Normal Operation /m 0,00E+00 0,00E+00 0,00E+00
gs Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1 0,00E+00 0,00E+00 0,00E+00
1 Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1 0,00E+00 0,00E+00 0,00E+00
s Screen Electrical Resistivity @ Operating Temp. .m 0,00E+00 0,00E+00 0,00E+00
Ds External diameter of Screen (Sheath) m 0,00E+00 0,00E+00 0,00E+00
ts Screen (Sheath) Thickness m 0,00E+00 0,00E+00 0,00E+00
m Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1 0,00E+00 0,00E+00 0,00E+00
Normal Operation IEC 60287-2-1
60287 2 1
T1 Thermal Resistance Between Conductor-Screen C.m/W 0,40825 0,40825 0,40825
t3 Thickness of Jacket m 0,003 0,003 0,003
T j Thermal Resistivity of Jacket C.m/W 3,5 3,5 3,5
C. Cable Direct Buried
T4 Thermal Resistance of Surrounding C.m/W
C m/W 2 93829
2,93829 2 93829
2,93829 2 92445
2,92445
L Depth of cable axis m 1,113 1,113 1,073
I Cable Current Ampacity A 328,1 328,1 328,1

Doc.HVS070311A 8
4. Cable RHZ1-OL 1x400RM/16

Description Unit 1 2 3

Cable type no 1 1 1
Resistances (DC/AC)
DC Resistance of Conductor @ 20°C /km 0,0778 0,0778 0,0778
DC Resistance of Conductor @ Operating Temperature /km 0,09975 0,09975 0,09966
AC Resistance of Conductor @ 20°C /km 0,07903 0,07903 0,07903
AC Resistance of Conductor @ Operating Temperature /km 0,10132 0,10132 0,10123
DC Resistance of Concentric Wires @ 20°C /km 1,18397 1,18397 1,18397
DC Resistance of Concentric Wires @ Operating Temperature /km 1,48093 1,48093 1,47968
Losses
Conductor Losses W/m 18,07722 18,07722 18,07722
Dielectric Losses W/m 0 0 0
Metallic Screen Losses W/m 0,31772 0,31772 0,31798
Total Losses W/m 18,39494 18,39494 18,3952
Capacitance, Inductance, Impedance
Capacitance F/km 0 28607
0,28607 0 28607
0,28607 0 28607
0,28607
Inductance of Conductor mH/km 0,34353 0,34353 0,34353
Reactance of Conductor /km 0,10792 0,10792 0,10792

Inductance of Metallic Sheath mH/km 0,16356 0,16356 0,16356

Reactance of Metallic Sheath /km 0 05138


0,05138 0 05138
0,05138 0 05138
0,05138

0.10132 + 0.10132 + 0.10123 +


Positive Sequence Impedance /km
j0.10792 j0.10792 j0.10792

0.10132 - 0.10132 - 0.10123 -


Negative Sequence Impedance /km
j0.10792 j0.10792 j0.10792

1.26241 + 1.26241 + 1.26241 +


Zero Sequence Impedance /km
j0.05138 j0.05138 j0.05138

Doc.HVS070311A 9
Symbol Description Unit 1 2 3

Cable type no 1 1 1
Normal Operation IEC 60287-1-1
Ro Cond ctor DC Resistance at 20°C
Conductor /m 7 78E 05
7,78E-05 7 78E 05
7,78E-05 7 78E 05
7,78E-05
R' Conductor DC Resistance at Max Temp /m 9,97E-05 9,97E-05 9,97E-05
R Conductor AC Resistance at Max Temp /m 1,01E-04 1,01E-04 1,01E-04
Ks Factor Used in Calculating Xs (Skin Effect) 1,00E+00 1,00E+00 1,00E+00
Kp Factor Used in Calculating Xp (Proximity Effect) 1,00E+00 1,00E+00 1,00E+00
ys Skin Effect Factor 8,21E-03 8,21E-03 8,23E-03
yp Proximity Effect Factor 7,52E-03 7,52E-03 7,53E-03
dc Conductor Diameter m 2,36E-02 2,36E-02 2,36E-02
c Distance Between Conductor Axes m 0,00E+00 0,00E+00 0,00E+00
C Cable Capacitiance F/m 2,86E-10 2,86E-10 2,86E-10
tan  Dielectric Loss Factor 4,00E-03 4,00E-03 4,00E-03
 Insulation Relative Permitivity 2,50E+00 2,50E+00 2,50E+00
Wd Cable Dielectric Losses Per Phase W/m 0,00E+00 0,00E+00 0,00E+00
1 Screen Loss Factor 1,76E-02 1,76E-02 1,76E-02
'1 Screen Loss Factor Caused by Circulating Current 1,76E-02 1,76E-02 1,76E-02
''1 Screen Loss Factor Caused by Eddy Current 0,00E+00 0,00E+00 0,00E+00
2 Armour Loss Factor 0,00E+00 0,00E+00 0,00E+00
Rs Screen AC Resistance at Cable Normal Operation /m 0,00E+00 0,00E+00 0,00E+00
gs Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1 0,00E+00 0,00E+00 0,00E+00
1 Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1 0,00E+00
, 0,00E+00
, 0,00E+00
,
s Screen Electrical Resistivity @ Operating Temp. .m 0,00E+00 0,00E+00 0,00E+00
Ds External diameter of Screen (Sheath) m 0,00E+00 0,00E+00 0,00E+00
ts Screen (Sheath) Thickness m 0,00E+00 0,00E+00 0,00E+00
m Coefficient Used in IEC 60287-1-1 Clause 2.3.6.1 0,00E+00 0,00E+00 0,00E+00
Normal Operation IEC 60287-2-1
T1 Thermal Resistance Between Conductor-Screen C.m/W 0,34192 0,34192 0,34192
t1 Insulation Thickness Between Conductor-Screen m 0 0 0
t3 Thickness of Jacket m 0,003 0,003 0,003
T j Thermal Resistivity of Jacket C.m/W 3,5 3,5 3,5
C. Cable
bl Direct
i Buried
i d
T4 Thermal Resistance of Surrounding C.m/W 2,85632 2,85632 2,84171
L Depth of cable axis m 1,115 1,115 1,07
I Cable Current Ampacity A 422,4 422,4 422,4

Doc.HVS070311A 10