SM-25xx/ETA2
SM-25x7 (Symbolfoto)
The protocol elements described herein are used in several automation units based on
SICAM RTUs platforms.
SICAM AK
SICAM TM
SICAM BC
Protocol elements process speficic communication protocols when SICAM RTUs automation
units communicate with each other oder with devices of third-party manufacturers, in the field
of telecontrol, automation, and protection.
Due to its features, protocol element technology has a successful tradition for many years at
SIEMENS. A fundamental characteristic is the separation of protocol-bound communication
from application tasks of an automation unit.
SM-2546/ETA2
Protocol element based on a Serial Interface Module (SIM) with one LAN interface:
The SIM can be expanded for one serial interface via SM-0551/PROTOCOL optionally and
can be attached to the master control element of SICAM BC.
SM-2556/ETA2
Protocol element based on a Serial Interface Module (SIM) with one LAN interface:
The SIM can be expanded for one serial interface via SM-0551/PROTOCOL optionally and
can be attached to master control and communication elements of SICAM RTUs platforms
Protocol element based on a Serial Interface Module (SIM) with dual LAN interface and
integrated switch for ring or star topology:
The SIM can be attached to the master control element of SICAM BC.
SM-2557/ETA2
Protocol element based on a Serial Interface Module (SIM) with dual LAN interface and
integrated switch for ring or star topology:
The SIM can be attached to master control and communication elements of SICAM RTUs
platforms
Hint
The above mentioned functions are described in detail in the document SICAM RTUs • Ax 1703 Common
Functions Protocol Elements, section "LAN Communication (104)"..
For the stations to communicate with each other, suitable transmission facilities and/or
network components may be needed in addition.
Own Station 100Base-FX (optical)
For the stations to communicate with each other, suitable transmission facilities and/or
network components may be needed in addition.
Own Station 100Base-FX (electrical)
SM-2546
The following table lists supported configurations. In addition to one SM-2546 (SI0/SI1) all
parts (carrier module, patch plug, etc.) listed for the choosen configuration are needed:
Configuration Interfaces
1)
Carrier Module Patch Module SI0 SI1 SI2 SI3
1) 2)
CP-5000, CP-5014 one integrated patch module per SIx
1)
each variant of the SICAM BC (Bay Controller) which can be ordered comes with a determined
patch module for each interface
2)
serial interface (V.28) – can be added optionally (SM-0551)
SM-2556
The following table lists supported configurations. In addition to one (SI0/SI1 or SI2/SI3) or
two (SI0/SI1 and SI2/SI3) SM-2556, all parts (carrier module, connection board, patch plug,
etc.) listed for the choosen configuration are needed:
Configuration Interfaces
Carrier Module Connection Board 1) Patch Plug 1) SI0 SI1 SI2 SI3
2) 4)
CP-2010, CP-2014 CM-2837
2) 4) 4)
CP-2012, CP-2017 CM-2838
3) 4)
CP-5000, CP-5014 one integrated patch module per SIx
2) 4)
CP-6003,CP-6014 ---
1)
one connection board for each carrier module, one patch plug for each
interface
2)
For patch plugs for standard protocols in standard configurations as
supported see modes of operation of the respective protocol element; for
patch plugs in other than standard configurations see SICAM RTUs
Platforms Configuration Automation Units and Automation Networks (DC0-
021-2)
3)
each variant of the SICAM BC (Bay Controller) which can be ordered
comes with a determined patch module for each interface
4)
serial interface (V.28) – can be added optionally (SM-0551)
SM-2547
The following table lists supported configurations. In addition to one SM-2546 (SI0/SI1) all
parts (carrier module, patch plug, etc.) listed for the choosen configuration are needed:
Configuration Interfaces
1)
Carrier Module Patch Module SI0 SI1 SI2 SI3
1) 2)
CP-5000, CP-5014 one integrated patch module per SIx
1)
each variant of the SICAM BC (Bay Controller) which can be ordered comes with a determined
patch module for each interface
Configuration Interfaces
1) 1)
Carrier Module Connection Board Patch Plug SI0 SI1 SI2 SI3
2)
CP-2010, CP-2014 CM-2837
2)
CP-2012, CP-2017 CM-2838
3)
CP-5000, CP-5014 one integrated patch module per SIx
2)
CP-6003, CP-6014 ---
1)
one connection board for each carrier module, one patch plug for each
interface
2)
For patch plugs for standard protocols in standard configurations as
supported see modes of operation of the respective protocol element; for
patch plugs in other than standard configurations see SICAM RTUs
Platforms Configuration Automation Units and Automation Networks (DC0-
021-1)
3)
each variant of the SICAM BC (Bay Controller) which can be ordered
comes with a determined patch module for each interface
SM-2546
Communication Circuits
Optical LAN interface Fast Ethernet acc. to IEEE 802.3, 100Base-FX
(multimode fibre optic) Data rate 100 Mbps
Line lengths
50/125 µm up to 1000 m
62.5/125 µm up to 1000 m
Power Supply
Operating voltage 4.75 .. 5.25 VDC, typ. 400 mA, max. 500 mA @5 V
(without SM-0551)
4.75 .. 5.25 VDC, typ. 525 mA, max. 770 mA @5 V
(with SM-0551)
4.75 .. 5.25 VDC, typ. 90 mA, max. 120 mA @5 V
(CM-5861)
The voltage is supplied by the carrier module.
Mechanics
Dimensions 227.3 x 63.5 mm
Weight Approx. 90 g
SM-2556
Communication Circuits
Electrical LAN interface Ethernet / Fast Ethernet acc. to IEEE 802.3, 10/100Base-TX
(twisted pair) Data rate: 10 Mbps / 100 Mbps
Line lengths up to 100 m
1 serial interface For Technical Specifications, see SM-x551/PROTOCOL
(SM-0551 can be added optionally) (MC0-003-2)
Power Supply
Operating voltage 4.75 .. 5.25 VDC, typ. 400 mA, max. 500 mA @5 V
(without SM-0551)
4.75 .. 5.25 VDC, typ. 525 mA, max. 770 mA @5 V
(with SM-0551)
The voltage is supplied by the carrier module.
Mechanics
Dimensions 227.3 x 63.5 mm
Weight Approx. 90 g
Communication Circuits
Optical LAN interface Fast Ethernet acc. to IEEE 802.3, 100Base-FX
(multimode fibre optic) Data rate 100 Mbps
Line lengths
50/125 µm up to 1000 m
62.5/125 µm up to 1000 m
Power Supply
Operating voltage 4.75 .. 5.25 VDC, typ. 400 mA, max. 500 mA @5 V
4.75 .. 5.25 VDC, typ. 90 mA, max. 120 mA @5 V
(CM-5861)
The voltage is supplied by the carrier module.
Mechanics
Dimensions 227.3 x 63.5 mm
Weight Approx. 90 g
SM-2557
Communication Circuits
Electrical LAN interface Ethernet / Fast Ethernet acc. to IEEE 802.3, 10/100Base-TX
(twisted pair) Data rate: 10 Mbps / 100 Mbps
Line lengths up to 100 m
Power Supply
Operating voltage 4.75 .. 5.25 VDC, typ. 400 mA, max. 500 mA @5 V
The voltage is supplied by the carrier module.
Mechanics
Dimensions 227.3 x 63.5 mm
Weight Approx. 90 g
SM-25x6
They use the LEDs of the master control unit or communication elements. The meaning of
these LED displays is described in the manual of the concerning system element.
SIM0
SM-0551
SIM0
SIM1
Communication element CP-2017
(symbolic illustration)
SIM0
RES
LOC
TM 1703 ACP CP-6014
RY
SI0
SI1
SI2
SI3
SIM1
CPY
ERx RX TX
/ LK
/ LK
X1
COM
/PK
/PK
ER
RELEAS E
P USH TO
SICAM
X15
X16
X14
X5
X11
X10
X12
X3
X6
X7
X8
X9
FB X4
WD
ER
SIM0
TB
SI1 (ETO)
RELEA SE
PUS H TO
M-PRE/0
M-PRE/1
M-PRE/2
M-PRE/3
SI2 (FB)
PUSH TO UNLOCK
1 2 3 4 5 6
SI0
SI3
NC
24-60VDC
X2
X13
PWR
SIM0 SM-0551
Hint
SICAM BC has no LED's for status and function display of protocol elements.
SM-2556, SM-2546
Hardware
Designation Item-Number/MLFB
SM-2546 Ethernet 100FX + 1 SS BC2-546
(optional) 6MF10130CF460AA0
Designation Item-Number/MLFB
ETA2 Ethernet Interface SC0-555-1
IEC60870-5-104
TU ETA2 TB II-Update SC0-555-1.XX/53
Accessories
Designation Item-Number/MLFB
CM-2860 Patch Plug Standard CA2-860
V28,ET,TR 6MF12110CJ600AA0