fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2765200, IEEE
Transactions on Smart Grid
1
Abstract-- Among short-circuit faults, those occurring during During power system disturbances, rotor angle may
power swings are more harmful to power system stability and experience severe oscillations which depend on the intensity of
thus, they should be detected quickly and reliably. However, the disturbance. From the transmission network viewpoint,
discrimination of power swing and such kinds of faults is not
always easy, especially in case of three-phase faults which are these oscillations, referred to as power swings, appear as
symmetrical similar to power swings. This paper shows that variations in the magnitudes and the phase angles of voltage
fundamental frequency phasors of voltage and current have some and current phasors. The power swings in heavily loaded
proper characteristics which can be used for the mentioned conditions could threaten the distance protection of transmission
discrimination. In doing so, two new fault detection methods are
lines. During power swings, the impedance trajectory seen by
proposed and tested on simulated systems considering single-mode
and multi-mode swings. Field data are also utilized to substantiate distance relays may encroach on their protection zones.
the presented analyses. The obtained results demonstrate the Among protection zones of distance relays, zone 3 is exposed
correctness of presented analyses and the efficiency of proposed to more maloperations in such conditions experienced in some
methods in fault detection during power swings. major blackouts [2]–[4].
Index Terms—Fault detection, fundamental frequency phasors, Conventional countermeasures for malfunctioning distance
power swing, power transmission, protective relaying. relays are to block them while power swings persist. However,
NOMENCLATURE faults which may occur during powers swings make swinging
generators more susceptible to out-of-step conditions, which
Ra Armature resistance per phase must be detected and cleared with a high degree of selectivity
id, iq d- and q-components of armature currents and dependability [5]. In some protection algorithms, such
ψd, ψq d- and q-components of flux linkages
kinds of faults are detected by inspecting zero sequence
ed, eq d- and q-components of stator terminal voltages
currents [6]. However, this method may not detect symmetrical
Ld, Lq d- and q-components of stator inductances
faults. Wavelet transform [7], high-frequency component of
Te, Tm, Td Electromagnetic, mechanical and damping torques
traveling waves [8], and moving window averaging of current
efd, Lfd Field voltage and field winding inductance
Rfd, ifd, ψfd Field winding resistance, current and flux linkage signals [9] are used in the literature to detect symmetrical
Lffd, Lad Field winding self and mutual inductances faults during power swings. However, they suffer from heavy
J Inertia constant computational burden, high sampling frequency besides
M, σ, φ Magnitude, damping and phase of a swinging mode special instrument transformers and requiring all phases
T'd0 Open-circuit transient time constant measurements, respectively. In [10], the rate of change of
ωr, ω0, ωp Rotor, synchronous and swing angular speeds swing-center voltage is used to provide a power swing
δ Rotor angle blocking (PSB) function which requires offline system stability
Xd, X'd Steady-state and transient d-component reactances studies for setting calculations [11].
XTh Thevenin reactance from the generator terminal Reference [12] introduces a method to modify the traditional
p Time differential operator (d/dt) concentric-circle characteristics used for power swing detection.
Efd Voltage proportional to efd This goal is pursued in [13] by calculating the center of
EI Voltage proportional to ifd admittance circular trajectory which requires additional digital
filtering and is susceptible to numerical instabilities. In [14],
I. INTRODUCTION the single-machine infinite-bus (SMIB) model of the system is
calculated online and the relative speed of the machine is used
T HE interconnected power system is a large non-linear
complex infrastructure which includes but not limited to
various types of generation units, transmission lines and
for blocking distance relays during stable power swings. In
[15], power swings and three-phase faults are distinguished by
transformers. Following large disturbances, generators try to a support vector machine (SVM) classifier involving numerous
preserve their synchronism and maintain the system stability. training and testing processes. The same task is carried out in
This type of stability, often referred to as rotor angle stability, [16] by using the so-called differential power which is
includes transient and small-signal stability [1]. calculated from the difference in predicted and actual samples
of voltage and current. Moreover, the change of magnitude of
S. M. Hashemi and M. Sanaye-Pasand are with the School of Electrical and negative sequence current is used in [17] for fault detection
Computer Engineering, College of Engineering, University of Tehran, Tehran during power swings in series-compensated lines. Although
14395-515, Iran (e-mail: hashemi93@ut.ac.ir; msanaye@ut.ac.ir). M.
Shahidehpour is with the Electrical and Computer Engineering Department, these papers provide valuable algorithms and results, their
Illinois Institute of Technology, Chicago, IL 60616, USA (e-mail: ms@iit.edu). performance can be still improved using more novel ideas.
This work was supported by the University of Tehran under Grant
8101064-1-10. Oscillations of fundamental frequency phasors during power
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2765200, IEEE
Transactions on Smart Grid
2
swings motivated the idea of employing dynamic phasors, rather calculated as [1]
than conventional static phasors, to improve the estimated 1
pE q (E fd E I ) (2)
accuracy of oscillations [18]–[20]. The transient variation of T d 0
dynamic phasors is used in [21] as a criterion to distinguish
Lad Lad Lfd
symmetrical and asymmetrical faults from power swings. Also, E q L fd , T d 0 R
a similar estimation and error calculation method is recently ffd fd
(3)
introduced in [22] based on Taylor series expansion. Other L
E ad e , E L i
fault detection methods are presented in [23] and [24] which fd R fd fd I ad fd
rely on the symmetrical properties of power swings. The classical generator model is valid when the time span is
This paper demonstrates that fundamental frequency smaller than T'd0 (typically several seconds). This model is
phasors of voltage and current have some useful properties
based on the constant field flux assumption which results in
which facilitate discrimination of power swings and faults,
constant ψfd and, according to (3), constant E'q. The model is
especially when a symmetrical three-phase fault occurs during
referred to as the constant voltage behind reactance since the
power swing. Based on these properties, two fault detection
generator is simply modeled by a reactance in series with a
methods, i.e. setting-free and faster than one cycle, are
constant voltage source. This model is widely used in power
proposed and implemented on each phase independently,
system stability studies, especially in large-scale multi-
which are capable of detecting symmetrical and asymmetrical
machine systems.
faults. The proposed methods also provide phase selection
capabilities in asymmetrical faults. The theoretical aspects of B. Phasor Calculations During Power Swings
the proposed methods are investigated mathematically and Using the classical swinging generator model, an SMIB
explained in detail. Various simulation cases and field data are system is shown in Fig. 1. The left-hand source is the swinging
provided to validate the extracted features of phasors during generator and the right-hand source is an infinite bus whose
power swings. The presented fault detection algorithms would voltage magnitude and phase angle are constant. The following
enhance the performance of distance protection and resolve the equations can be written.
traditional detection of symmetrical faults during power swings. 1 V
The major features and contributions of this paper are: I ( E a V b 0) b [K ( z ) 1 z ] (4)
Z Z
Extracting the properties of voltage and current phasors during
power swings with/without embracing short-circuit faults. V a E a jX d I (5)
Presenting two new fault detection algorithms during power where Z, K and θz are defined as
swings, which are setting-free, easy to implement and fast. Z jX Z Z
Detecting both asymmetrical and symmetrical faults which d l b
II. ANALYSES OF FUNDAMENTAL FREQUENCY VOLTAGE AND Meanwhile, the magnitudes of current and voltage phasors are
CURRENT PHASORS DURING POWER SWINGS V
I b K 2 1 2K cos (7)
In this section, principles of the proposed fault detection Z
methods during power swings are analyzed from both XV
mathematical and physical viewpoints. Meanwhile, a V a d b K 2 1 2K cos (8)
Z
discussion on fault current modeling during power swings is
provided. Besides, effects of variable electromotive force where K' = K(Z–Za)/Za. Considering high reactance to resistance
(EMF) as well as multi-mode swings are investigated in detail. ratio of transmission grids, (Z–Za)/Za can be assumed as a real
In order to extract the properties of voltage and current value and, therefore, K' would be a real number (as K is).
phasors, synchronous generators as sources of power swings in Power swings are originated from rotor angle oscillations.
transmission networks should be modeled properly as follows. The swing, while traveling over the transmission grid, would
A. Synchronous Generator Modeling for Stability Studies cause oscillations in magnitudes and phase angles of voltages
and currents. In order to show that how magnitudes of voltage
Stator transients (pψd and pψq) and rotor speed variations
and current phasors are affected by rotor angle variations, we
(pωr) are commonly neglected for representing synchronous
calculate derivatives of (7) and (8) with respect to δ as
machines in stability studies. The per unit equations which
I Va
disregard the effect of damper windings on generators are FI sin 0 , FV sin 0 (9)
stated as
where FI and FV are defined as (10) and (11), respectively.
ed q R a i d , eq d R a i q
| E a | |V a | v |V b | 0
d Ld i d Lad i fd , q Lq i q (1)
jXd I Zl=Rl+jXl
fd Lad i d Lffd i fd , e fd p fd R fd i fd
Accordingly, the voltage behind transient reactance ( E q ) is Fig. 1. Transmission system with a single-machine infinite-bus.
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2765200, IEEE
Transactions on Smart Grid
3
Zlink
Va
Ea
Ia jXd |V b 1 | 0
I Zl
Fig. 2. An appropriate system for investigating faults during power swings. Fig. 3. Modified PSRC standard test system.
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2765200, IEEE
Transactions on Smart Grid
4
8 Fault current 8 considering its negative sign, it can be deduced that the
6 6 Fault current variations of ΔVt are almost out of phase (by 180 degrees) with
4 4 Δδ. Furthermore, considering the sinusoidal variations of Δδ,
Current (kA)
2 2
general results.
0 0
To deal with such a complicated condition, unlike (5), I can
-2 -2
be calculated for the left hand side of Fig. 1 as
-4 -4
1
-6
10 1.50.5 2 0 0.5 1
-6
1.5 2 I (V a v V b 0) (17)
Time (s) Time (s) Zl
(c) (d)
The magnitude of I and its deviation are calculated as
Fig. 4. Fault current waveform during power swing; (a) IR3 one line AB; (b)
IR4 one line AB; (c) IR3 two lines AB; (d) IR4 two lines AB. 1 2 2
I V a V b 2 V a V b cos v (18)
Zl
accurate. In case of variable EMF, the change in E'q is a
V a 0 V a V b 0 cos v 0 V a
1
function of the change in field voltage and rotor angle [26]. I
Mathematically, using the Laplace transform, ΔE'q is Z l F0 (19)
expressed as V a 0 V b 0 sin v 0 v
AB B
E q (s ) (s ) E fd (s ) (13) 2 2
F0 V a 0 V b 0 2 V a 0 V b 0 cos v 0 (20)
(1 BT d 0s ) (1 BT d 0s )
X X d X X Th Focusing on the variations of variables in (19) with respect
A d V b sin 0 , B d (14) to Δδ, since Δ|Va|=αΔδ, |Va0|≈|Vb0|=1, Δδv≈Δδ and δv0 is usually
X d X Th X d X Th
small, we conclude that
If field dynamics are neglected (i.e., ΔEfd = 0), ΔE'q/Δδ is
1
approximated as –A/T'd0s. Assuming pure sinusoidal variations I (1 cos v 0 ) sin v 0
of Δδ, the Laplace operator s is equal to jωp and ΔE'q/Δδ is Z l F0
given by jA/T'd0ωp [26]. Accordingly, the variations of (21)
1 v20 v 0
generator EMF would lead those of rotor angle by π/2 radians. ( ) v 0
Z l F0 2 Z l F0
Before analyzing the effects of filed dynamics, the deviation
of generator terminal voltage (ΔVt) is given as [1]: Equation (21) implies that in the case of a variable EMF,
Δ|I|/Δδ is positive and therefore, Δ|V|/Δ|I| is negative. This is
V t fd the same result obtained in the case of constant EMF generator
V t V t (15) model. It should be noted that the subscripts 0 in (14) to (21)
@ fd 0, @ 0
fd denote the initial values of corresponding variables.
The sign of α in (15) depends on system operating E. Considerations of Multi-Machine Systems
conditions, external network impedance, and damping of To discuss multi-machine systems, we begin from the swing
generator voltage regulators. In practice, α is cited as negative equation in a turbo-generator as
especially when dealing with large values of external system d r
reactance and generator power output. Major power swings J T d T m T e (22)
dt
mostly occur under peak-load system conditions where where Td is approximately proportional to the rotor speed as Td
generators are loaded near their maximum capacity. Therefore, = Dωr. Accordingly, the swing equation can be expressed in
we consider a negative sign for α in the following. Referring to terms of the change in rotor angle (Δδ) as [26]:
Fig. 1, the value of α is calculated as [27]:
d 2 d
R E sin (X X )E cos M D K E 0 (23)
e 2 dt
d 0 X q l a02 0 l d a0 0 dt
Vt 0 R l (X l X d )(X l X q ) where M = Jωr and KE' is the synchronizing power coefficient.
(16) Based on the characteristic equation roots of (23), the rotor angle
eq 0 R l E a 0 cos 0 (X l X q )E a 0 sin 0
X d variation is underdamped and manifests exponentially damped
Vt 0 R l2 (X l X d )(X l X q ) sinusoidal variations during stable power swing as
Equation (16) implies that α has a real value and M exp( t ) cos(p t ) (24)
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2765200, IEEE
Transactions on Smart Grid
5
For a multi-machine power system, since our study is on frequency components incorporated with the main signal. In
protective relaying of transmission lines in which each line is the proposed derivative-based algorithm, voltage and current
connected to at least two substations, the system generators magnitudes are firstly estimated by the full-cycle DFT which
would likely result in multi-mode power swings on the effectively attenuates the effect of such components. On the
transmission line as other hand, voltage and current phasors would experience
N oscillating phase angles, as well as oscillating magnitudes,
M i exp( i t ) cos( pi t i ) (25) during power swing. As shown in Fig. 5, oscillation of phase
i 1 angle would emerge as high-frequency components
Each mode may emerge by a particular generator or due to superimposed on the estimated signal magnitude and make its
interactions among generators. The resulting multi-mode swing calculated derivative oscillatory. In order to purify the
would be like a distorted sinusoidal waveform. The presented calculated derivative from such bothering oscillations, it is
analyses on the features of fundamental frequency phasors are averaged over one power cycle. The result is shown in Fig. 5.
not limited to a particular wave shape of Δδ. Since the analyses The proposed delta-based algorithm is setting-free and easy
are based on deviations (or changes) of variables regardless of to implement. However, as will be shown in the simulation
their waveform, they correspond to the case of multi-mode results, it takes at least two cycles to detect the faults during
swings in multi-machine systems as well. This issue will be power swing. In some practical applications, all zones of
demonstrated in the simulation results. distance relays will be blocked during power swings, while at
times zone-1 will not be blocked. The latter is preferred for
III. PROPOSED FAULT DETECTION ALGORITHMS DURING
using the proposed delta-based algorithm.
POWER SWINGS
12
As mentioned earlier, during power swings, the magnitudes 10
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2765200, IEEE
Transactions on Smart Grid
6
During power swings, the admittance Y comprises an magnitudes are out-of-phase by almost 180 degrees. The
oscillating AC component plus a DC component. During fault, voltage and current of relay R5, located on the radial line, are
the AC component is well-attenuated and Y is mainly shown in Fig. 8. All represented voltages are phase-to-neutral.
composed of a DC component. Applying a full-cycle discrete Fig. 8(b) demonstrates that the changes of voltage and
Fourier transform (DFT) on Y would remove its DC current magnitudes seen by relay R5 are almost in-phase.
component. Meanwhile, as the admittance samples enter the Meanwhile, the comparison of Figs. 7(b) and 8(b) reveals that
DFT window, the output would change remarkably following the magnitude of impedance seen by relay R4 experiences
the fault inception. Therefore, it is easy to select a threshold remarkable variations during power swings, while the
value for the DFT of Y as F(Y). The setting rule for this impedance seen by relay R5 remains fixed, indicating that relay
threshold value (Ytr) is as follows. R5 is immune to maloperation during power swings. In other
During the power swing, the calculated admittance would words, it is not necessary to activate the PSB function for
have a DC offset which oscillates with the swing frequency. In distance relays used in the radial lines.
each power cycle, DFT covers only a fraction of the swinging In order to investigate short-circuit faults which occur
admittance. Moreover, the frequency response of DFT is so during power swings, a permanent three-phase fault is applied
that it inherently eliminates DC component and integer at t = 1s on the middle of line AB. The voltage and current of
harmonics of input signal. In practice, Yth can be selected as phase A are shown in Fig. 9(a) where the fault current
(26) where Imax and Vmin are the maximum load current and waveform confirms the analysis given in Section II.C. As
half of the rated voltage, respectively. shown in Fig. 9(b), once the fault occurs, the changes in
voltage and current magnitudes become in-phase. This feature
I Maximum Swing Frequency
Yth max (26) can discriminate three-phase faults from power swings. It should
Vmin Rated Power Frequency be noted that other phase voltages and currents represent
Fig. 6 shows the flowcharts of proposed fault detection similar characteristics during power swings and three-phase
algorithms which are implemented on each phase independently. faults. It means that, despite the symmetrical nature of these
The delta-based algorithm waits for five consecutive samples two phenomena, changes in voltage and current magnitudes
before making the final decision. This time delay is used to can be investigated independently in each phase.
increase the reliability of algorithm against transient variations The most challenging problem in fault detection during
in the magnitudes of voltage and current. power swings is the detection of three-phase faults.
va,b,c ia,b,c va,b,c ia,b,c Nonetheless, even in the case of asymmetrical faults, the stated
features of voltage and current magnitudes are still established
Calculate phasor Calculate phasor in faulty phases. This issue is demonstrated in Fig. 10 by
magnitude by DFT magnitude by DFT representing three-phase voltages and currents for a solid
phase A to ground fault initiated at t = 1s. During the fault, the
Calculate ∆V and ∆I Calculate Y = I/V magnitudes of voltage and current in the faulty phase are
K=1
experiencing in-phase variation. However, variations of voltage
No Sign(∆V)× Calculate F(Y) by and current magnitudes in other phases are out-of-phase by
Sign(∆I) full-cycle DFT almost 180 degrees. So, the coupling between the oscillating
≥ 0?
machine and the rest of system is established via healthy
Yes
phases, and electrical parameters (including power, voltage and
K = K+1 No
F(Y) > Ytr? 2 600
No Yes V 500
K = 5? 1
V,I (p.u.)
400
|Z| (ohm)
Yes
Fault detected Fault detected 0 300
during power swing during power swing 200
-1
(a) (b) I 100
Fig. 6. Proposed fault detection algorithms during power swing; (a) Delta-
-2 0
based algorithm; (b) Admittance-based algorithm. These algorithms are 0 0.5 1 1.5 2 0 0.5 1 1.5 2
executed only during power swings. Time (s) Time (s)
(a) (b)
IV. SIMULATION RESULTS Fig. 7. (a) Changes in voltage and current magnitudes measured by relay R4 (for
phase A) during power swing; (b) Magnitude of impedance seen by relay R4.
A. Modified IEEE-PSRC Benchmark System 2
V 1062
IEEE Power System Relaying Committee (PSRC) has 1 1060
V,I (p.u.)
I
[29]. This model is represented in Fig. 3 wherein a load branch 0 1058
is added to analyze the power swing seen by the radial line 1056
-1
relays. Power swing can be created by applying a three- 1054
phase fault at bus A and removing the fault before generator -2
0 0.5 1 1.5 2 0 0.5 1 1.5 2
S2 loses synchronism. In this study, the fault is applied from t = Time (s) Time (s)
0.20s to t = 0.25s and the voltage and current of relay R4 are (a) (b)
Fig. 8. (a) Changes in voltage and current magnitudes measured by relay R5 (for
monitored. In Fig. 7, the changes of voltage and current phase A) during power swing; (b) Magnitude of impedance seen by relay R5.
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2765200, IEEE
Transactions on Smart Grid
7
500 5 10 2
5 1 V
Current (kA)
V,I (p.u.)
V V
Voltage (kV)
V,I (p.u.)
0 0 0 0
I I
I
-5 -1
-500 -5 -10
0 0.5 1 1.5 2 0 0.5 1 1.5 -2
Time (s) Time (s) 0 1 2 3 40 1 2 3 4
Time (s) Time (s)
(a) (b) (a) (b)
Fig. 9. (a) Voltage and current of relay R4 (for phase A) when a three-phase 2
fault occurs during power swing; (b) Changes in voltage and current magnitudes.
300 3 1 V V
V,I (p.u.)
|Ia|
|Va| (kV)
|Ia| (kA)
200 2
0
100 |Va| 1
I I
-1
0 0.5 1 1.5 2 2.5 3 3.5 4 0
Time (s) -2
(a) 02 3 40 1 1 2 3 4
300 3 Time (s) Time (s)
|Vb|,|Vc| (c) (d)
|Vb|,|Vc| (kV)
250
|Ib|,|Ic| (kA)
Fig. 11. Effect of fault resistance on the changes of voltage and current
200 2 magnitudes; (a) Rf = 5 Ω; (b) Rf = 10 Ω; (c) Rf = 50 Ω; (d) Rf = 100 Ω.
150
100 1 magnitude of current shown in Fig. 13(b) during which the
50 |Ib|,|Ic|
0 0.5 oscillatory magnitudes of voltage and current phasors are
2 2.5 3 3.5 4 0 1 1.5
Time (s) distorted and not completely sinusoidal. However, the earlier
(b) mentioned relationship between the oscillatory magnitudes of
Fig. 10. Investigation of three-phase voltages and currents for a phase A to voltage and current phasors is still established.
ground fault during power swing; (a) Phase A; (b) Phases B and C. Fig. 14 illustrates the changes in the voltage and current
magnitudes of line 17-18 when a permanent three-phase fault
current) can oscillate freely. Therefore, oscillatory magnitudes
occurs at the middle of line during power swing. The fault
of voltage and current phasors provide the phase selection
inception instant is t = 5s. Following the fault, the changes of
capability to identify the faulty phases. On the other hand, the
voltage and current magnitudes become in-phase. This figure
presence of fault on phase A has a role of hard obstacle which
shows that the mentioned properties of voltage and current
forces voltage and current oscillations to become in-phase.
phasors are established during multi-mode swings, as well.
Investigation on the effect of fault resistance shows that this
obstacle is mitigated as much as the fault resistance increases. G10 G8
26 28 29
Fig. 11 illustrates the effect of fault resistance (up to 100 ohm) 30 37
on the changes of voltage and current magnitudes during
2 25 38
power swings. As the fault resistance increases, the fault tends 18 27 17 G9
3
to a heavy load which is connected as a tapped feeder to the 1 24
G1
line, and hence, the freedom of oscillations is fairly preserved. 15 16
4 G6
19
B. New England 39-Bus Multi-Machine System 39 14 21 35
12
In order to investigate voltage and current magnitudes in a 9 20
5 33
multi-machine system, the New England 10-machine 39-bus
11 22
system is simulated in DIgSILENT [30]. This system is shown 13 G4
34
in Fig. 12(a) and its data are provided in [31]. 8 6
10
23
G5
The swing frequency is determined by the dominant
31 36
32
electromechanical modes excited in the disturbance. The 7
Current (kA)
V,I (p.u.)
I
and the group of G4, G5 and G7 is exposed to a short-circuit 0.5
fault. This circumstance is simulated in Fig. 12(a) by applying a 200 0
three-phase fault at the middle of line 4-14. The fault inception -1
Multi-mode
instant is t = 1s and the line is opened after 100 ms. Fig. 13 shows swing
the magnitudes of phase A voltage and current of line 17-18 0 0 -2
0 5 10 15 0 5 10 15
which are measured at bus 17. When two or more machines Time (s) Time (s)
(a) (b)
participate in the oscillation, there would be a multi-mode Fig. 13. Voltage and current of line 17-18 (for phase A) during power swings;
power swing. The multi-mode swing can be observed in the (a) V and I magnitudes; (b) Changes in V and I magnitudes.
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2765200, IEEE
Transactions on Smart Grid
8
1.4 7 30 6×130 MW 10
Faulted
1.2 V 6 20 Area
Current (p.u.)
V, I (p.u.)
12
Voltage (p.u.)
1 5 10 9
V 10×160 MW 8
0.8 4 6×120 MW
0
0.6 3 11 7 4
-10 I
0.4 I 2 3- ph fault 2×100 MW 6
0.2 1 -20
Power swing
0 -30
3 4 50 1 2 6 70 0 1 2 3 4 5 6 7 13 14
2
Time(s) Time(s) 6×160 MW
(a) (b)
Fig. 14. Voltage and current of line 17-18 (for phase A) during power swings; 1
3
(a) V and I magnitudes, (b) Changes in V and I magnitudes. 5 4×250 MW
16 15
C. Field Data Results (a)
V(kV)
Fig. 15(a) shows a 230kV transmission network with 34 100 Line opening
generating units which was exposed to a large disturbance 50 from bus 11
event. Before this event, three transmission lines indicated by .
0.00 .
0.50 .
1.00 .
1.50 .
2.00 t/s
0
dashed lines were on outage. The event was initiated by a fault |Va| |Vb| |Vc|
I(kA)
on line 8-9. Following the line outage by operation of
0.75
protective relays, the red lines which are connecting the faulted 0.50
area to the rest of the grid became overloaded and the 0.25 .
0.00 .
0.50 .
1.00 .
1.50 .
2.00 t/s
generators within the faulted area began to induce power 0.00
|Ia| |Ib| |Ic|
swings on some transmission lines. Fig. 15(b) illustrates the (b)
three-phase voltages and currents of line 7-11 which are V(kV)
recorded at bus 7. As shown, the oscillatory magnitudes of 30
voltage and current phasors are out-of-phase in each phase. 20
10
Moreover, all voltages are oscillating coherently, so are the 0.00 0.50 1.00 1.50 2.00 2.50 t/s
0
currents. Due to the symmetry of power swing, the neutral |Va| |Vb| |Vc|
I(kA)
(zero sequence) voltage and current are almost zero.
15
Before t = 0.75s, the voltages were dropping while the 10
currents were rising. At t = 0.75s, line 7-11 is tripped from bus 5 0.00 0.50 1.00 1.50 2.00 2.50 t/s
0
11 by an incorrect operation of the line distance relay during |Ia| |Ib| |Ic|
power swing. As mentioned in Section II.A, the phase (c)
Fig. 15. Field data results; (a) Faulted system diagram; (b) Magnitudes of
difference feature between changes of voltage and current voltages and currents of line 7-11 at bus 7; (c) at the secondary side of a load
magnitudes of radial lines is different from that of double-end transformer connected to bus 3.
fed lines. This fact is demonstrated in Fig. 15(c) for one of the 4
4 3
outgoing radial feeders of a 230/63 kV load transformer which 3.5
V,I (p.u.)
0 0
is connected to bus 3. As shown, all voltages and currents 2 1 1.02 2 1.02 1.04
represent in-phase oscillations.
00 0.5 1 1.5 2 00 0.5 1 1.5 2
D. Evaluation of the Proposed Fault Detection Algorithms 0.1 0.1
Y (p.u.)
algorithm is faster than the delta-based one, which detects the 0.01
fault in less than a half-cycle. However, as mentioned earlier, 0
0.9 0.95 1 1.05 1.1 00.9 0.95 1 1.05 1.1
the delta-based method is setting-free and suitable for 1
1
unblocking the second or third zones of a distance relay.
Trip
@ 1.005s @ 1.018s
Moreover, the effect of decaying DC component of fault 0 0
0.9 0.95 1 1.05 1.1 0.9 0.95 1 1.05 1.1
current on the admittance-based algorithm is shown in Fig. 16. Time (s) Time (s)
In the absence of decaying DC, as shown in Fig. 16(a), the (a) (b)
fault is detected within 5 ms; while in its presence, Fig. 16(b) Fig. 16. Evaluation of the admittance-based algorithm for a three-phase fault
occurring at (a) t = 1s; (b) t = 1.015s. Only phase A is represented.
illustrates that the fault detection is increased to 18 ms which is
still less than one cycle and fast enough. As shown in Table I, power load models are similar.
the proposed algorithms can also be used for the detection of The features and requirements of the proposed and existing
asymmetrical faults during power swings. Three-phase faults fault detection schemes during power swings are compared in
are usually low-impedance, so their related fault resistances in Table II. Among 16 methods investigated in this table, it can
Table I are assumed to be zero. It is worth mentioning that the be informed that the proposed fault detection algorithms have
obtained results for both constant-impedance and constant- more desired features and lower requirements.
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2765200, IEEE
Transactions on Smart Grid
9
TABLE II
COMPARISON BETWEEN THE FEATURES OF PROPOSED AND EXISTING FAULT DETECTION METHODS DURING POWER SWINGS
Low Faster Setting Easy to
Asymmetrical Symmetrical Phase
No. Methodology computational than one
Fault detection Fault detection Segregated burden cycle Free implement
1 Conventional blinder scheme [6] Yes No Yes Yes No No Yes
2 Wavelet transform [7] Yes Yes Yes No Yes No No
3 Traveling waves [8] Yes Yes No No Yes No No
4 Moving window averaging [9] No Yes No Yes Yes Yes Yes
5 Swing center voltage tracer [10] No Yes No Yes No Yes Yes
6 Modified concentric characteristic [12] Yes Yes Yes Yes Yes No Yes
7 Admittance circular trajectory [13] Yes Yes Yes No No No No
8 SVM classifier [15] Yes Yes No No Yes No No
9 Differential power [16] Yes Yes Yes Yes Yes No Yes
10 Negative sequence current [17] Yes Yes No Yes Yes No Yes
11 Dynamic phasor transient [21] Yes Yes Yes Yes * No Yes
12 Taylor series [22] Yes Yes Yes Yes Yes No Yes
13 Instanteneous active power [23] No Yes No Yes Yes No Yes
14 Change of active/reactive power [24] No Yes No Yes Yes No Yes
15 Proposed delta-based algorithm Yes Yes Yes Yes No Yes Yes
16 Proposed admittance-based algorithm Yes Yes Yes Yes Yes No Yes
*Not reported
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2017.2765200, IEEE
Transactions on Smart Grid
10
[13] R. Jafari, N. Moaddabi, M. Eskandari-Nasab, G. B. Gharehpetian, and Mohammad Shahidehpour (F’01) is a University Distinguished Professor,
M. S. Naderi, “A novel power swing detection scheme independent of and the Bodine Chair Professor and Director of the Robert W. Galvin Center
the rate of change of power system parameters,” IEEE Trans. Power for Electricity Innovation at Illinois Institute of Technology, Chicago, IL,
Del., vol. 29, no. 3, pp. 1192–1202, Jun. 2014. USA. He was a recipient of the IEEE PES Outstanding Power Engineering
[14] D. Kang and R. Gokaraju, “A new method for blocking third zone Educator Award. Dr. Shahidehpour is a member of the U.S. National
distance relays during stable power swings,” IEEE Trans. Power Syst., Academy of Engineering and a Fellow of the American Association for the
vol. 31, no. 4, pp. 1836–1843, Aug. 2016. Advancement of Science (AAAS).
[15] N. G. Chothani, B. R. Bhalja, and U. B. Parikh, “New support vector
machine-based digital relaying scheme for discrimination between
power swing and fault,” IET Gener. Transm. Distrib., vol. 8, no. 1, pp.
17–25, 2014.
[16] J. G. Rao and A. K. Pradhan, “Differential power-based symmetrical
fault detection during power swing,” IEEE Trans. Power Del., vol. 27,
no. 3, pp. 1557–1564, Jul. 2012.
[17] P. K. Nayak, A. K. Pradhan, and P. Bajpai, “A fault detection technique
for the series-compensated line during power swing,” IEEE Trans.
Power Del., vol. 28, no. 2, pp. 714–722, Apr. 2013.
[18] J. A. de la O Serna, “Dynamic phasor estimates for power system
oscillations,” IEEE Trans. Instrum. Meas., vol. 56, pp. 1648–1657, 2007.
[19] R. K. Mai, L. Fu, Z. Y. Dong, K. P. Wong, Z. Q. Bo, and H. B. Xu, “Dynamic
phasor and frequency estimators considering decaying DC components,”
IEEE Trans. Power Syst., vol. 27, no. 2, pp. 671–681, May 2012.
[20] S. Vejdan, M. Sanaye-Pasand, and O. P. Malik, “Accurate dynamic phasor
estimation based on the signal model under off-nominal frequency and
oscillations,” IEEE Trans. Smart Grid, vol. 8, no. 2, pp. 708–719, Mar. 2017.
[21] J. Khodaparast and M. Khederzadeh, “Three-phase fault detection
during power swing by transient monitor,” IEEE Trans. Power Syst.,
vol. 30, no. 5, pp. 2558–2565, Sep. 2015.
[22] I. G. Tekdemir and B. Alboyaci, “A novel approach for improvement of
power swing blocking and deblocking functions in distance relays,”
IEEE Trans. Power Del., vol. 32, no. 4, pp. 1986–1994, Aug. 2017.
[23] B. Mahamedi and J. G. Zhu, “A novel approach to detect symmetrical
faults occurring during power swing by using frequency components of
instantaneous three-phase active power,” IEEE Trans. Power Del., vol.
27, no. 3, pp. 1368–1376, Jul. 2012.
[24] X. Lin, Y. Gao, and P. Liu, “A novel scheme to identify symmetrical
faults occurring during power swing,” IEEE Trans. Power Del., vol. 23,
no. 1, pp. 73–78, Jan. 2008.
[25] P. M. Anderson, Power System Protection. New York, NY, USA: IEEE-
Press, 1999.
[26] J. Machowski, J. W. Bialek, and J. R. Bumby, Power System Dynamics,
Stability and Control. 2nd ed. Chichester, UK: Wiley, 2008.
[27] F. P. Demello and C. Concordia, “Concepts of synchronous machine
stability as affected by excitation Control,” IEEE Trans. Power
Apparatus and Systems, vol. PAS-88, no. 4, pp. 316–329, Apr. 1969.
[28] S. H. Horowitz, A. G. Phadke, Power System Relaying. Chichester, West
Sussex, UK: Wiley, 2008.
[29] IEEE PSRC, “EMTP reference models for transmission line relay
testing”, 2005. [On-line]. Available: http://www.pes-psrc.org
[30] DIgSILENT GmbH: DIgSILENT Power Factory, Version 15, 2014.
[31] M. A. Pai, Energy Function Analysis for Power System Stability.
Norwell, Massachusetts, USA: Kluwer Academic Publishers, 1989.
1949-3053 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.