Professional Documents
Culture Documents
Page No.
2. Features 2
3. Guide Specifications 4
5. Technical Data 6
6. Performance Data 10
7. Electrical Data 19
8. Unit Dimensions 21
Example: 30 RM - 20
In TR
Family Name
Unit Models
30RM - 15
30RM - 20
30RM - 25
30RM - 30
30RM - 35
30RM - 40
30RM - 45
30RM - 50
1
2. FEATURES
As a result of Carrier continuous development, 30RM Series water chillers, have been carefully designed and
manufactured under strict quality conditions to give you full satisfaction through efficient operation with
minimum maintenance and service.
Carrier 30RM series were born of a very simple concept:
" An excellent product isn't enough; it must offer more than its competitors ".
In addition to true cooling, Carrier 30RM series have advanced features and performance level, which our
competitors will find difficult to equal, maintaining the same quality/ price ratio.
2
FEATURES (Cont.)
- The control panel is located in a separate - 5 minutes time delay for compressor protection against
compartment and can be inspected without short cycling when power off or thermostat off.
disturbing unit operation. Pumping down
valves fitted in liquid lines to enable - 1 minute time delay for to avoid simultaneous starting
refrigerant to be temporarily stored in the of two compressors.
condenser coil if the refrigerant is to be
repaired or some part of the refrigeration - Internal pressure relief valve for compressor protection
system to be replaced. against high discharge pressures.
- Rotalock suction and discharge valves fitted - Crankcase heater to guard compressor against flood
on compressor for servicing. back conditions and to eliminate oil fluffing on start up
- The unit is completely factory assembled, - Internal overloads for compressors protection against
electrically wired, and charged with total R22 excessive temperature and/or excessive current
charge, tested against extreme conditions caused by overloading, low refrigeration flow, phase
and quality control approved before leaving loss or incorrect of compressor motor.
the factory.
- Internal overloads for fan/motors protection against
- All compressors are equipped with a sight excessive temperature
glass to determine the amount and condition
of the oil contained within the sump. - External sensitive quick trip overloads for compressors
and motors protection against excessive current.
-
- The compressors SM185 are equipped with These overloads mounted on definite purpose
an oil drain connection to allow oil to be contactors of quite operation.
removed from the sump for changing oil,
testing, etc. - Anti freeze water thermostat.
-
- Phase protector against phase reversal and phase loss.
3
3. GUIDE SPECIFICATIONS
REFRIGERANT CIRCUIT COMPRESSOR
- Entirely deoxidized dehydrated copper tubes Heavy-duty hermetic Scroll compressor use R-22.
with joints brazed by sliver brazing alloys.
* Resilient rubber grommets for vibration isolation.
- Independent refrigerant circuits built up of * F class insulation class for compressor motor.
components and materials selected for
compatibility, reliability and high efficiency. * 100 % suction gas cooled.
The independent circuits design ensures * Well-designed suction and discharge lines.
partial load operation.
- Precoated aluminum fins for condenser coils. • Refrigerant side working pressure of 360 Psi
• Water side working pressure of 150 Psi
• Insulated with closed cell foam insulation.
4
4. STANDARD UNIT COMPONENTS
9
10 11
See
details
8 7
Unit Side
Unit Front
3 3
2
LEGEND
1. Compressor
2. Condenser Coils
3. Fan / Motors
4. Dual High / Low Pressure Controls
5. Liquid Line Filter Driers
6. Shell & Tube Cooler
7. Starters For Module (A) Unit Back
Starters ( Contactors + Thermal overloads ) for Compressors 45 1
Starters ( Contactor + Thermal overloads ) for Condenser Fan / Motors
8. Starters For Module (B)
Starters ( Contactors + Thermal overloads ) for Compressors
Starters ( Contactor + Thermal overloads ) for Condenser Fan / Motors
9. Phase Protector
10. Two Stage Water Thermostat
11. Cold Water Thermostat
5
5. TECHNICAL DATA
* Cooling capacity is based on 44.6°F / 53.6°F leaving / entering water temperature and 95°F ambient temperature.
* 1 TR = 12000 Btu/hr 1 Kw = 3412 Btu/hr
6
TECHNICAL DATA (Cont.)
9
6. PERFORMANCE DATA
30 RM 15
Air Temp Ent. Condenser ( o F)
LWT ( o F)
90 95 100 105 110 115 125
TC 180 174 168 162 156 150 138
41 KW 15.52 16.52 17.52 18.52 19.52 20.52 23.52
SDT 114 119 124 129 134 139 169
TC 182 176 170 164 158 152 140
42 KW 15.54 16.54 17.54 18.54 19.54 20.54 22.54
SDT 114.5 119.5 124.5 129.5 134.5 139.5 14.9
TC 184 178 172 166 160 154 142
43 KW 15.56 16.56 17.56 18.56 19.56 20.56 22.56
SDT 115 120 125 130 135 140 120
TC 186 180 174 168 162 156 144
44 KW 15.58 16.58 17.58 18.58 19.58 20.58 22.58
SDT 115.5 120.5 125.5 130.5 135.5 140.5 150.5
TC 188 182 176 170 164 158 146
45 KW 15.60 16.60 17.60 18.60 19.60 20.60 22.6
SDT 116 121 126 131 136 141 151
TC 190 184 178 172 166 160 148
47 KW 15.62 16.62 17.62 18.62 19.62 20.62 22.62
SDT 116.5 121.5 126.5 131.5 136.5 141.5 151.5
TC 196 190 184 178 172 166 154
50 KW 15.68 16.68 17.68 18.68 19.68 20.68 22.68
SDT 118 123 128 133 138 143 153
30 RM 20
Air Temp Ent. Condenser ( o F)
LWT ( o F)
90 95 100 105 110 115 125
TC 230 224 218 212 206 200 188
41 KW 19.52 20.72 21.92 23.12 24.32 25.52 27.92
SDT 114.5 119.5 124.5 129.5 134.5 139.5 149.5
TC 232 226 220 214 208 202 190
42 KW 19.54 20.74 21.94 23.14 24.34 25.54 27.94
SDT 115 120 125 130 135 140 150
TC 234 228 222 216 210 204 192
43 KW 19.56 20.76 21.96 23.16 24.36 25.56 27.96
SDT 115.5 120.5 125.5 130.5 135.5 140.5 150.5
TC 236 230 224 218 212 206 194
44 KW 19.58 20.78 21.98 23.18 24.38 25.58 27.98
SDT 116 121 126 131 136 141 151
TC 238 232 226 220 214 208 196
45 KW 19.60 20.80 22.00 23.20 24.40 25.60 28.00
SDT 116.5 121.5 126.5 131.5 136.5 141.5 151.5
TC 240 234 228 222 216 210 198
47 KW 19.62 20.82 22.02 23.22 24.42 25.62 28.02
SDT 117 122 127 132 137 142 152
TC 246 240 234 228 222 216 204
50 KW 19.68 20.88 22.08 23.28 24.48 25.68 28.08
SDT 118.5 123.5 128.5 133.5 138.5 143.5 153.5
TC Gross Cooling Capacity ( 1000 x Btu/Hr )
KW Compressor Power Consumption
SDT Saturated Discharge Temperature at Compressor ( ° F )
SST Saturated Suction Temperature ( ° F )
LWT Leaving Water Temperature ( ° F )
* All cooling capacities are based on 44.6°F / 53.6°F
leaving / entering water temperature.
10
PERFORMANCE DATA ( Cont.)
30 RM 25
Air Temp Ent. Condenser ( o F)
LWT ( o F)
90 95 100 105 110 115 125
TC 270 264 258 252 246 240 228
41 KW 23.32 24.72 26.12 27.52 28.92 30.32 33.12
SDT 115 120 125 130 135 140 150
TC 272 266 260 254 248 242 230
42 KW 23.34 24.74 26.14 27.54 28.94 30.34 33.14
SDT 115.5 120.5 125.5 130.5 135.5 140.5 150.5
TC 274 268 262 256 250 244 232
43 KW 23.36 24.76 26.16 27.56 28.96 30.36 33.16
SDT 116 121 126 131 136 141 151
TC 276 270 264 258 252 246 234
44 KW 23.38 24.78 26.18 27.58 28.98 30.38 33.18
SDT 116.5 121.5 126.5 131.5 136.5 141.5 151.5
TC 278 272 266 260 254 248 236
45 KW 23.40 24.80 26.20 27.60 29.00 30.40 33.2
SDT 117 122 127 132 137 142 152
TC 280 274 268 262 256 250 238
47 KW 23.42 24.82 26.22 27.62 29.02 30.42 33.22
SDT 117.5 122.5 127.5 132.5 137.5 142.5 152.5
TC 286 280 274 268 262 256 244
50 KW 23.48 24.88 26.28 27.68 29.08 30.48 33.28
SDT 119 124 129 134 139 144 154
30 RM 30
Air Temp Ent. Condenser ( o F)
LWT ( o F)
90 95 100 105 110 115 125
TC 360 348 336 324 312 300 276
41 KW 31.04 33.04 35.04 37.04 39.04 41.04 45.04
SDT 114 119 124 129 134 139 149
TC 364 352 340 328 316 304 280
42 KW 31.08 33.08 35.08 37.08 39.08 41.08 45.08
SDT 114.5 119.5 124.5 129.5 134.5 139.5 149.5
TC 368 356 344 332 320 308 284
43 KW 31.12 33.12 35.12 37.12 39.12 41.12 45.12
SDT 115 120 125 130 135 140 150
TC 372 360 348 336 324 312 288
44 KW 31.16 33.16 35.16 37.16 39.16 41.16 45.16
SDT 115.5 120.5 125.5 130.5 135.5 140.5 150.5
TC 376 364 352 340 328 316 292
45 KW 31.20 33.20 35.20 37.20 39.20 41.20 45.2
SDT 116 121 126 131 136 141 151
TC 380 368 356 344 332 320 296
47 KW 31.24 33.24 35.24 37.24 39.24 41.24 45.24
SDT 116.5 121.5 126.5 131.5 136.5 141.5 151.5
TC 392 380 368 356 344 332 308
50 KW 31.36 33.36 35.36 37.36 39.36 41.36 45.36
SDT 118 123 128 133 138 143 153
TC Gross Cooling Capacity ( 1000 x Btu/Hr )
KW Compressor Power Consumption
SDT Saturated Discharge Temperature at Compressor ( ° F )
SST Saturated Suction Temperature ( ° F )
LWT Leaving Water Temperature ( ° F )
* All cooling capacities are based on 44.6°F / 53.6°F
leaving / entering water temperature.
11
PERFORMANCE DATA ( Cont.)
30 RM 35
Air Temp Ent. Condenser ( o F)
LWT ( o F)
90 95 100 105 110 115 125
TC 410 398 386 374 362 350 326
41 KW 35.04 37.24 39.44 41.64 43.84 46.04 50.44
SDT 114.25 119.25 124.25 129.25 134.25 139.25 149.25
TC 414 402 390 378 366 354 330
42 KW 35.08 37.28 39.48 41.68 43.88 46.08 50.48
SDT 114.75 119.75 124.75 129.75 134.75 139.75 149.75
TC 418 406 394 382 370 358 334
43 KW 35.12 37.32 39.52 41.72 43.92 46.12 50.52
SDT 115.25 120.25 125.25 130.25 135.25 140.25 150.25
TC 422 410 398 386 374 362 338
44 KW 35.16 37.36 39.56 41.76 43.96 46.16 50.56
SDT 115.75 120.75 125.75 130.75 135.75 140.75 150.75
TC 426 414 402 390 378 366 342
45 KW 35.20 37.40 39.60 41.80 44.00 46.20 50.60
SDT 116.25 121.25 126.25 131.25 136.25 141.25 151.25
TC 430 418 406 394 382 370 346
47 KW 35.24 37.44 39.64 41.84 44.04 46.24 50.64
SDT 116.75 121.75 126.75 131.75 136.75 141.75 151.75
TC 442 430 418 406 394 382 388
50 KW 35.36 37.56 39.76 41.96 44.16 46.36 50.76
SDT 118.25 123.25 128.25 133.25 138.25 143.25 153.25
30 RM 40
Air Temp Ent. Condenser ( o F)
LWT ( o F)
90 95 100 105 110 115 125
TC 460 448 436 424 412 400 376
41 KW 39.04 41.44 43.84 46.24 48.64 51.04 55.84
SDT 114.5 119.5 124.5 129.5 134.5 139.5 149.5
TC 464 452 440 428 416 404 380
42 KW 39.08 41.48 43.88 46.28 48.68 51.08 55.88
SDT 115 120 125 130 135 140 150
TC 468 456 444 432 420 408 384
43 KW 39.12 41.52 43.92 46.32 48.72 51.12 55.92
SDT 115.5 120.5 125.5 130.5 135.5 140.5 150.5
TC 472 460 448 436 424 412 388
44 KW 39.16 41.56 43.96 46.36 48.76 51.16 55.96
SDT 116 121 126 131 136 141 151
TC 476 464 452 440 428 416 392
45 KW 39.20 41.60 44.00 46.40 48.80 51.20 56
SDT 116.5 121.5 126.5 131.5 136.5 141.5 151.5
TC 480 468 456 444 432 420 396
47 KW 39.24 41.64 44.04 46.44 48.84 51.24 56.04
SDT 117 122 127 132 137 142 152
TC 492 480 468 456 444 432 408
50 KW 39.36 41.76 44.16 46.56 48.96 51.36 56.16
SDT 118.5 123.5 128.5 133.5 138.5 143.5 153.5
TC Gross Cooling Capacity ( 1000 x Btu/Hr )
KW Compressor Power Consumption
SDT Saturated Discharge Temperature at Compressor ( ° F )
SST Saturated Suction Temperature ( ° F )
LWT Leaving Water Temperature ( ° F )
* All cooling capacities are based on 44.6°F / 53.6°F
leaving / entering water temperature.
12
PERFORMANCE DATA ( Cont.)
30 RM 45
Air Temp Ent. Condenser ( o F)
LWT ( o F)
90 95 100 105 110 115 125
TC 500 488 476 464 452 440 416
41 KW 42.84 45.44 48.04 50.64 53.24 55.84 61.04
SDT 114.75 119.75 124.75 129.75 134.75 139.75 149.75
TC 504 492 480 468 456 444 420
42 KW 42.88 45.48 48.08 50.68 53.28 55.88 61.08
SDT 115.25 120.25 125.25 130.25 135.25 140.25 150.25
TC 508 496 484 472 460 448 424
43 KW 42.92 45.52 48.12 50.72 53.32 55.92 61.12
SDT 115.75 120.75 125.75 130.75 135.75 140.75 150.75
TC 512 500 488 476 464 452 428
44 KW 42.96 45.56 48.16 50.76 53.36 55.96 61.16
SDT 116.25 121.25 126.25 131.25 136.25 141.25 151.25
TC 516 504 492 480 468 456 432
45 KW 43.00 45.60 48.20 50.80 53.40 56.00 61.20
SDT 116.75 121.75 126.75 131.75 136.75 141.75 151.75
TC 520 508 496 484 472 460 436
47 KW 43.04 45.64 48.24 50.84 53.44 56.04 61.24
SDT 117.25 122.25 127.25 132.25 137.25 142.25 152.25
TC 532 520 508 496 484 472 448
50 KW 43.16 45.76 48.36 50.96 53.56 56.16 61.36
SDT 118.75 123.75 128.75 133.75 138.75 143.75 153.75
30 RM 50
Air Temp Ent. Condenser ( o F)
LWT ( o F)
90 95 100 105 110 115 125
TC 540 528 516 504 492 480 456
41 KW 46.64 49.44 52.24 55.04 57.84 60.64 66.24
SDT 115 120 125 130 135 140 150
TC 544 532 520 508 496 484 460
42 KW 46.68 49.48 52.28 55.08 57.88 60.68 66.28
SDT 115.5 120.5 125.5 130.5 135.5 140.5 150.5
TC 548 536 524 512 500 488 464
43 KW 46.72 49.52 52.32 55.12 57.92 60.72 66.32
SDT 116 121 126 131 136 141 151
TC 552 540 528 516 504 492 468
44 KW 46.76 49.56 52.36 55.16 57.96 60.76 66.36
SDT 116.5 121.5 126.5 131.5 136.5 141.5 151.5
TC 556 544 532 520 508 496 472
45 KW 46.80 49.60 52.40 55.20 58.00 60.80 66.40
SDT 117 122 127 132 137 142 152
TC 560 548 536 524 512 500 476
47 KW 46.84 49.64 52.44 55.24 58.04 60.84 66.44
SDT 117.5 122.5 127.5 132.5 137.5 142.5 152.5
TC 572 560 548 536 524 512 488
50 KW 46.96 49.76 52.56 55.36 58.16 60.96 66.56
SDT 119 124 129 134 139 144 154
TC Gross Cooling Capacity ( 1000 x Btu/Hr )
KW Compressor Power Consumption
SDT Saturated Discharge Temperature at Compressor ( ° F )
SST Saturated Suction Temperature ( ° F )
LWT Leaving Water Temperature ( ° F )
* All cooling capacities are based on 44.6°F / 53.6°F
leaving / entering water temperature.
13
PERFORMANCE DATA ( Cont.)
30 RM 15 -- Circuit No. 1 OR 2*
Air Temp Ent. Condenser ( o F)
LWT ( o F)
90 95 100 105 110 115 125
TC 90 87 84 81 78 75 69
41 KW 7.76 8.26 8.76 9.26 9.76 10.26 11.26
SDT 114 119 124 129 134 139 149
TC 91 88 85 82 79 76 70
42 KW 7.77 8.27 8.77 9.27 9.77 10.27 11.27
SDT 114.5 119.5 124.5 129.5 134.5 139.5 149.5
TC 92 89 86 83 80 77 71
43 KW 7.78 8.28 8.78 9.28 9.78 10.28 11.28
SDT 115 120 125 130 135 140 150
TC 93 90 87 84 81 78 72
44 KW 7.79 8.29 8.79 9.29 9.79 10.29 11.29
SDT 115.5 120.5 125.5 130.5 135.5 140.5 150.5
TC 94 91 88 85 82 79 73
45 KW 7.80 8.30 8.80 9.30 9.80 10.30 11.30
SDT 116 121 126 131 136 141 151
TC 95 92 89 86 83 80 74
47 KW 7.81 8.31 8.81 9.31 9.81 10.31 11.31
SDT 116.5 121.5 126.5 131.5 136.5 141.5 151.5
TC 98 95 92 89 86 83 77
50 KW 7.84 8.34 8.84 9.34 9.84 10.34 11.34
SDT 118 123 128 133 138 143 153
30 RM 20 -- Circuit No. 1 OR 2*
Air Temp Ent. Condenser ( o F)
LWT ( o F)
90 95 100 105 110 115 125
TC 115 112 109 106 103 100 94
41 KW 9.76 10.36 10.96 11.56 12.16 12.76 13.96
SDT 114.5 119.5 124.5 129.5 134.5 139.5 149.5
TC 116 113 110 107 104 101 95
42 KW 9.77 10.37 10.97 11.57 12.17 12.77 13.97
SDT 115 120 125 130 135 140 150
TC 117 114 111 108 105 102 96
43 KW 9.78 10.38 10.98 11.58 12.18 12.78 13.98
SDT 115.5 120.5 125.5 130.5 135.5 140.5 150.5
TC 118 115 112 109 106 103 97
44 KW 9.79 10.39 10.99 11.59 12.19 12.79 13.99
SDT 116 121 126 131 136 141 151
TC 119 116 113 110 107 104 98
45 KW 9.80 10.40 11.00 11.60 12.20 12.80 14.00
SDT 116.5 121.5 126.5 131.5 136.5 141.5 151.5
TC 120 117 114 111 108 105 99
47 KW 9.81 10.41 11.01 11.61 12.21 12.81 14.01
SDT 117 122 127 132 137 142 152
TC 123 120 117 114 111 108 102
50 KW 9.84 10.44 11.04 11.64 12.24 12.84 14.04
SDT 118.5 123.5 128.5 133.5 138.5 143.5 153.5
TC Gross Cooling Capacity ( 1000 x Btu/Hr )
KW Compressor Power Consumption
SDT Saturated Discharge Temperature at Compressor ( ° F )
SST Saturated Suction Temperature ( ° F )
LWT Leaving Water Temperature ( ° F )
* Circuits no. 1 and 2 on 30 RM 15 and 20 have identical capacities.
* All cooling capacities are based on 44.6°F / 53.6°F
leaving / entering water temperature.
14
PERFORMANCE DATA ( Cont.)
30 RM 25 -- Circuit No. 1 OR 2*
o Air Temp Ent. Condenser ( o F)
LWT ( F)
90 95 100 105 110 115 125
TC 135 132 129 126 123 120 114
41 KW 11.66 12.36 13.06 13.76 14.46 15.16 16.56
SDT 115 120 125 130 135 140 150
TC 136 133 130 127 124 121 115
42 KW 11.67 12.37 13.07 13.77 14.47 15.17 16.57
SDT 115.5 120.5 125.5 130.5 135.5 140.5 150.5
TC 137 134 131 128 125 122 116
43 KW 11.68 12.38 13.08 13.78 14.48 15.18 16.58
SDT 116 121 126 131 136 141 151
TC 138 135 132 129 126 123 117
44 KW 11.69 12.39 13.09 13.79 14.49 15.19 16.59
SDT 116.5 121.5 126.5 131.5 136.5 141.5 151.5
TC 139 136 133 130 127 124 118
45 KW 11.70 12.40 13.10 13.80 14.50 15.20 16.60
SDT 117 122 127 132 137 142 152
TC 140 137 134 131 128 125 119
47 KW 11.71 12.41 13.11 13.81 14.51 15.21 16.61
SDT 117.5 122.5 127.5 132.5 137.5 142.5 152.5
TC 143 140 137 134 131 128 1222
50 KW 11.74 12.44 13.14 13.84 14.54 15.24 16.64
SDT 119 124 129 134 139 144 154
30 RM 30 -- Circuit No. 1 To 4**
Air Temp Ent. Condenser ( o F)
LWT ( o F)
90 95 100 105 110 115 125
TC 90 87 84 81 78 75 69
41 KW 7.76 8.26 8.76 9.26 9.76 10.26 11.86
SDT 114 119 124 129 134 139 149
TC 91 88 85 82 79 76 70
42 KW 7.77 8.27 8.77 9.27 9.77 10.27 11.87
SDT 114.5 119.5 124.5 129.5 134.5 139.5 149.5
TC 92 89 86 83 80 77 71
43 KW 7.78 8.28 8.78 9.28 9.78 10.28 11.88
SDT 115 120 125 130 135 140 150
TC 93 90 87 84 81 78 72
44 KW 7.79 8.29 8.79 9.29 9.79 10.29 11.89
SDT 115.5 120.5 125.5 130.5 135.5 140.5 150.5
TC 94 91 88 85 82 79 73
45 KW 7.80 8.30 8.80 9.30 9.80 10.30 11.90
SDT 116 121 126 131 136 141 151
TC 95 92 89 86 83 80 74
47 KW 7.81 8.31 8.81 9.31 9.81 10.31 11.91
SDT 116.5 121.5 126.5 131.5 136.5 141.5 151.5
TC 98 95 92 89 86 83 77
50 KW 7.84 8.34 8.84 9.34 9.84 10.34 11.94
SDT 118 123 128 133 138 143 153
TC Gross Cooling Capacity ( 1000 x Btu/Hr )
KW Compressor Power Consumption
SDT Saturated Discharge Temperature at Compressor ( ° F )
SST Saturated Suction Temperature ( ° F )
LWT Leaving Water Temperature ( ° F )
* Circuits no. 1 and 2 on 30 RM 15 and 20 have identical capacities.
** Circuits no. 1, 2, 3 and 4 on 30 RM 30 have identical capacities.
* All cooling capacities are based on 44.6°F / 53.6°F
leaving / entering water temperature.
15
PERFORMANCE DATA ( Cont.)
30 RM 35 -- Circuit No. 1 OR 2*
o Air Temp Ent. Condenser ( o F)
LWT ( F)
90 95 100 105 110 115 125
TC 115 112 109 106 103 100 94
41 KW 9.76 10.36 10.96 11.56 12.16 12.76 14.26
SDT 114.5 119.5 124.5 129.5 134.5 139.5 149.5
TC 116 113 110 107 104 101 95
42 KW 9.77 10.37 10.97 11.57 12.17 12.77 14.27
SDT 115 120 125 130 135 140 150
TC 117 114 111 108 105 102 96
43 KW 9.78 10.38 10.98 11.58 12.18 12.78 14.28
SDT 115.5 120.5 125.5 130.5 135.5 140.5 150.5
TC 118 115 112 109 106 103 97
44 KW 9.79 10.39 10.99 11.59 12.19 12.79 14.29
SDT 116 121 126 131 136 141 151
TC 119 116 113 110 107 104 98
45 KW 9.80 10.40 11.00 11.60 12.20 12.80 14.30
SDT 116.5 121.5 126.5 131.5 136.5 141.5 151.5
TC 120 117 114 111 108 105 99
47 KW 9.81 10.41 11.01 11.61 12.21 12.81 14.31
SDT 117 122 127 132 137 142 152
TC 123 120 117 114 111 108 102
50 KW 9.84 10.44 11.04 11.64 12.24 12.84 14.34
SDT 118.5 123.5 128.5 133.5 138.5 143.5 153.5
30 RM 35 -- Circuit No. 3 OR 4**
o Air Temp Ent. Condenser ( o F)
LWT ( F)
90 95 100 105 110 115 125
TC 90 87 84 81 78 75 69
41 KW 7.76 8.26 8.76 9.26 9.76 10.26 11.86
SDT 114 119 124 129 134 139 149
TC 91 88 85 82 79 76 70
42 KW 7.77 8.27 8.77 9.27 9.77 10.27 11.87
SDT 114.5 119.5 124.5 129.5 134.5 139.5 149.5
TC 92 89 86 83 80 77 71
43 KW 7.78 8.28 8.78 9.28 9.78 10.28 11.88
SDT 115 120 125 130 135 140 150
TC 93 90 87 84 81 78 72
44 KW 7.79 8.29 8.79 9.29 9.79 10.29 11.89
SDT 115.5 120.5 125.5 130.5 135.5 140.5 150.5
TC 94 91 88 85 82 79 73
45 KW 7.80 8.30 8.80 9.30 9.80 10.30 11.9
SDT 116 121 126 131 136 141 151
TC 95 92 89 86 83 80 74
47 KW 7.81 8.31 8.81 9.31 9.81 10.31 11.91
SDT 116.5 121.5 126.5 131.5 136.5 141.5 151.5
TC 98 95 92 89 86 83 77
50 KW 7.84 8.34 8.84 9.34 9.84 10.34 11.94
SDT 118 123 128 133 138 143 153
TC Gross Cooling Capacity ( 1000 x Btu/Hr )
KW Compressor Power Consumption
SDT Saturated Discharge Temperature at Compressor ( ° F )
SST Saturated Suction Temperature ( ° F )
LWT Leaving Water Temperature ( ° F )
* Circuits no. 1 and 2 on 30 RM 35 have identical capacities.
** Circuits no. 3 and 4 on 30 RM 35 have identical capacities.
* All cooling capacities are based on 44.6°F / 53.6°F
leaving / entering water temperature.
16
PERFORMANCE DATA ( Cont.)
30 RM 40 -- Circuit No. 1 To 4*
o Air Temp Ent. Condenser ( o F)
LWT ( F)
90 95 100 105 110 115 125
TC 115 112 109 106 103 100 94
41 KW 11.76 12.36 12.96 13.56 14.16 14.76 16.26
SDT 114.5 119.5 124.5 129.5 134.5 139.5 149.5
TC 116 113 110 107 104 101 95
42 KW 11.77 12.37 12.97 13.57 14.17 14.77 16.27
SDT 115 120 125 130 135 140 150
TC 117 114 111 108 105 102 96
43 KW 11.78 12.38 12.98 13.58 14.18 14.78 16.28
SDT 115.5 120.5 125.5 130.5 135.5 140.5 150.5
TC 118 115 112 109 106 103 97
44 KW 11.79 12.39 12.99 13.59 14.19 14.79 16.29
SDT 116 121 126 131 136 141 151
TC 119 116 113 110 107 104 98
45 KW 11.80 12.40 13.00 13.60 14.20 14.80 16.30
SDT 116.5 121.5 126.5 131.5 136.5 141.5 151.5
TC 120 117 114 111 108 105 99
47 KW 11.81 12.41 13.01 13.61 14.21 14.81 16.31
SDT 117 122 127 132 137 142 152
TC 123 120 117 114 111 108 102
50 KW 11.84 12.44 13.04 13.64 14.24 14.84 16.34
SDT 118.5 123.5 128.5 133.5 138.5 143.5 153.5
30 RM 45 -- Circuit No. 1 OR 2**
Air Temp Ent. Condenser ( o F)
LWT ( o F)
90 95 100 105 110 115 125
TC 115 112 109 106 103 100 94
41 KW 9.76 10.36 10.96 11.56 12.16 12.76 14.26
SDT 114.5 119.5 124.5 129.5 134.5 139.5 149.5
TC 116 113 110 107 104 101 95
42 KW 9.77 10.37 10.97 11.57 12.17 12.77 14.27
SDT 115 120 125 130 135 140 150
TC 117 114 111 108 105 102 96
43 KW 9.78 10.38 10.98 11.58 12.18 12.78 14.28
SDT 115.5 120.5 125.5 130.5 135.5 140.5 150.5
TC 118 115 112 109 106 103 97
44 KW 9.79 10.39 10.99 11.59 12.19 12.79 14.29
SDT 116 121 126 131 136 141 151
TC 119 116 113 110 107 104 98
45 KW 9.80 10.40 11.00 11.60 12.20 12.80 14.3
SDT 116.5 121.5 126.5 131.5 136.5 141.5 151.5
TC 120 117 114 111 108 105 99
47 KW 9.81 10.41 11.01 11.61 12.21 12.81 14.31
SDT 117 122 127 132 137 142 152
TC 123 120 117 114 111 108 102
50 KW 9.84 10.44 11.04 11.64 12.24 12.84 14.34
SDT 118.5 123.5 128.5 133.5 138.5 143.5 153.5
TC Gross Cooling Capacity ( 1000 x Btu/Hr )
KW Compressor Power Consumption
SDT Saturated Discharge Temperature at Compressor ( ° F )
SST Saturated Suction Temperature ( ° F )
LWT Leaving Water Temperature ( ° F )
* Circuits no. 1, 2, 3 and 4 on 30 RM 40 have identical capacities.
** Circuits no. 1 and 2 on 30 RM 45 have identical capacities.
* All cooling capacities are based on 44.6°F / 53.6°F
leaving / entering water temperature.
17
PERFORMANCE DATA ( Cont.)
30 RM 45 -- Circuit No. 3 OR 4*
o Air Temp Ent. Condenser ( o F)
LWT ( F)
90 95 100 105 110 115 125
TC 115 112 109 106 103 100 94
41 KW 11.76 12.36 12.96 13.56 14.16 14.76 16.26
SDT 114.5 119.5 124.5 129.5 134.5 139.5 149.5
TC 116 113 110 107 104 101 95
42 KW 11.77 12.37 12.97 13.57 14.17 14.77 16.26
SDT 115 120 125 130 135 140 150
TC 117 114 111 108 105 102 96
43 KW 11.78 12.38 12.98 13.58 14.18 14.78 16.28
SDT 115.5 120.5 125.5 130.5 135.5 140.5 150.5
TC 118 115 112 109 106 103 97
44 KW 11.79 12.39 12.99 13.59 14.19 14.79 16.29
SDT 116 121 126 131 136 141 151
TC 119 116 113 110 107 104 98
45 KW 11.80 12.40 13.00 13.60 14.20 14.80 16.30
SDT 116.5 121.5 126.5 131.5 136.5 141.5 151.5
TC 120 117 114 111 108 105 99
47 KW 11.81 12.41 13.01 13.61 14.21 14.81 16.31
SDT 117 122 127 132 137 142 152
TC 123 120 117 114 111 108 102
50 KW 11.84 12.44 13.04 13.64 14.24 14.84 16.34
SDT 118.5 123.5 128.5 133.5 138.5 143.5 153.5
30 RM 50 -- Circuit No. 1 To 4**
o Air Temp Ent. Condenser ( o F)
LWT ( F)
90 95 100 105 110 115 125
TC 135 132 129 126 123 120 114
41 KW 11.66 12.36 13.06 13.76 14.46 15.16 16.56
SDT 115 120 125 130 135 140 150
TC 136 133 130 127 124 121 115
42 KW 11.67 12.37 13.07 13.77 14.47 15.17 16.57
SDT 115.5 120.5 125.5 130.5 135.5 140.5 150.5
TC 137 134 131 128 125 122 116
43 KW 11.68 12.38 13.08 13.78 14.48 15.18 16.58
SDT 116 121 126 131 136 141 151
TC 138 135 132 129 126 123 117
44 KW 11.69 12.39 13.09 13.79 14.49 15.19 16.59
SDT 116.5 121.5 126.5 131.5 136.5 141.5 151.5
TC 139 136 133 130 127 124 118
45 KW 11.70 12.40 13.10 13.80 14.50 15.20 16.6
SDT 117 122 127 132 137 142 152
TC 140 137 134 131 128 125 119
47 KW 11.71 12.41 13.11 13.81 14.51 15.21 16.6
SDT 117.5 122.5 127.5 132.5 137.5 142.5 152.5
TC 143 140 137 134 131 128 122
50 KW 11.74 12.44 13.14 13.84 14.54 15.24 16.64
SDT 119 124 129 134 139 144 154
TC Gross Cooling Capacity ( 1000 x Btu/Hr )
KW Compressor Power Consumption
SDT Saturated Discharge Temperature at Compressor ( ° F )
SST Saturated Suction Temperature ( ° F )
LWT Leaving Water Temperature ( ° F )
* Circuits no. 3 and 4 on 30 RM 45 have identical capacities.
** Circuits no. 1, 2, 3 and 4 on 30 RM 50 have identical capacities.
* All cooling capacities are based on 44.6°F / 53.6°F
leaving / entering water temperature.
18
7. ELECTRICAL DATA
Note:
* Cooling capacity is based on 44.6°F / 53.6°F leaving / entering water temperature and 95°F ambient temperature.
* 1 TR = 12000 Btu/hr 1 Kw = 3412 Btu/hr
19
ELECTRICAL DATA (Cont.)
Note:
* Cooling capacity is based on 44.6°F / 53.6°F leaving / entering water temperature and 95°F ambient temperature.
* 1 TR = 12000 Btu/hr 1 Kw = 3412 Btu/hr
20
8. UNIT DIMENSIONS (IN MM)
Comp.
Comp.
Comp.
Comp.
Comp.
21
9. CONSIDERATIONS FOR SELECTING INSTALLATION LOCATION
e. Cleanness of location
The installation location of chiller unit should be free of dust or any material, which can cause
clogging of condenser coil. When installing unit on the ground, select a location not subjected to
flooding.
CHILLERS CHILLERS
30RM15-20-25 30RM30-35-40-45-50
*
*
22
CONSIDERATIONS FOR SELECTING INSTALLATION LOCATION (Cont.)
CHILLERS
30RM15-20-25
1500 mm
CHILLERS
30RM30-35-40-45-50
1500 mm
23
Specifications are subject to change without notice according
to Carrier Policy of continuous development
24