I. MATERIALS TO BE USED
1. 13A, 2Pin + E Switched Type, Shuttered to BS 1363, duplex type in common plate.
2. 15A, 1 Gang, 250V, Switched Socket W/127V label! ( Laser Printing )
3. 15A, 2 Gang, 250V, Switched Socket w/127V label ( Laser Printing )
4. 13A", 250v, Switched type, conform to BS 546 type in common plate.
5. 13A, 1 Gang, 250V. Switched type w/220V label ( Laser Printing )
Page 1 of 5
STEEE BOXES:-
1. 7 x 7 cm, 7 x 1 4 cm Steel Boxes, compatible with A! - Fanar back boxes 1 Gang and 2 Gang
( Covered for the Model range of wiring devices ).
Page 2 of 5
1. On the already installed back boxes in plastered block walls switches are
mounted at height of 1250 mm. power, tel. and TV outlets at 450 mm and other
outlets in wet areas are mounted at height of 1250 mm or as given in
respective ceramic details drawing From finished floor level.
2. Before proceeding to install the outlets devices, the back boxes cleaned, surface
around the boxes will be repaired and made flush with the finished wall surfaces
using extension rings as needed.
3 . terminating the phase, neutral and earth wires to the internal devices block at
respective terminals it is installed and fixed in the back box.
4. Using sprit level and manufacturer provided screws, outlets front plates are fixed
parallel and perpendicular to floor and wall surfaces respectively, long machine
screws subject to engineers" approval will be used for plate fixing.
5.
Locations: Drawings generally show approximate locations of outlets and
equipment. Exact locations shall be determined from interior finishing
and detail drawings. Any condition that would place an outlet in an
unsuitable location shall be referred to the Engineer switches ,will be at
strike sides of doors ,In location outlets allow for overhead pipes, ducts, variations in
arrangements, thickness of finishing, window trim, paneling and other engineering features.
6. Mounting heights for outlet boxes and similar equipment will be uniform within the
same or similar areas. Mounting'iS3b be as shown on the drawings or as approved by the
Engineer. lighting switches and socket outlets;\general]y at 1250 mm and 450 mm from
finished floor level respectively. switches for long dimensions vertical and operating handle,
if the toggle type, up when in the on position.
Page 3 of 5
9. Appearance: install inspection boxes and plates plumb, square and parallel to finished
walls surface. Exposed plates covering recessed boxes rest neatly on wall surface without gaps,
and fully covering the box.
10.Grouped Outlets Arrange neatly so that use of fitting is convenient and clear.
1 . Single pole switches are to switch the phase wire .'"fife not run neutral wire through switches
having neutral shunt or bridge.
?•
2. Exposed Outlet Boxes: Securely fasten to wall with machine screws to permanent inserts
or lead anchors.
2- CONNECTION OF APPL1ANCES:-
Page 4 of 5
• -
3. Operation: Devices will be tested for operation and intended at full load
without an s i n s of heating.
4. Equipment will be insulation tested and observed, under full-load for not less than 3 days
operation, with respect to undue heating and performance in general.
4.INSPECTION & TESTING: work will be inspected for correct fixing and workman shop ,
outlet device are tested for voltages and polarity
5. CLEANING:
Internally clean devices, device outlet boxes, and enclosures.4 Replace stained or
improperly painted wall plates or devices.