I) Design Parametres:-
As per Table 1 of IS:2911(Part III)-1980,safe load carrying capacity 375mm dia DUR piles in medium compact
sandy soils or clayey soils of medium consistency for 3.75m depth = 360.00KN
As per clause 5.2.7.2 of IS:2911(Part III)-1980,the minimum spacing between the centre to centre of bored DUR
piles should not be less than 1.5Du.
Assuming water table in the pile bulb,the safe load carrying capacity is to be reduced by 25% as per the
clause B-1.6 of IS 2911(Part III)-1980.
Providing THREE piles,the load carrying capacity of the pile cap will be
Further as per clause 5.2.8.1,the load carrying capacity of each individual pile should be reduced by 10% due to
group action.
Y
Y
0.70
375mm Ø DUR
X X
2.09
186.45mm
186.45mm
The critical section of one way shear is at a distance of 'd' from the face of the column
The design shear strength of concrete for the above steel percentage from
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections located
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 1.81
0.521 >0.464
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile fo
resulting from truss action,because av/d ratio is not more than 2.
H = Pu/24Ld[3L2-b2] = 208.00KN
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-
848.07KN
84.81KN
932.88KN
269.12KN
807.37KN
726.63KN
Hence O.K
2.090m
1.910m
1.410m
0.700m
0.640m
0.710m
220.78KN-m
642.00mm
20.27mm
801.19sqmm
3.99Nos
9Nos
1808.64sqmm
0.147
254.99KN-m
220.78KN-m
642.00mm
20.27mm
801.19sqmm
3.99Nos
9Nos
1808.64sqmm
0.147
of the column
478.16sqmm
e value.Hence O.K
DESIGN OF PILE CAPS----PC2(2,3,4,5,7,9,10,12,13,14,17)
I) Design Parametres:-
As per Table 1 of IS:2911(Part III)-1980,safe load carrying capacity 375mm dia DUR piles in medium compact
sandy soils or clayey soils of medium consistency for 3.75m depth is = 360.00KN
As per clause 5.2.7.2 of IS:2911(Part III)-1980,the minimum spacing between the centre to centre of bored DU
piles should not be less than 1.5Du.
Assuming water table in the pile bulb,the safe load carrying capacity is to be reduced by 20% as per the
clause B-1.6 of IS 2911(Part III)-1980.
Providing two piles,the load carrying capacity of the pile cap will be
Reducing 10% per each pile due to group action,the net safe load carrying
capacity
2.09
375Ø DUR Piles
2.09
0 .7 0
1.41
293.06mm
The critical section of one way shear is at a distance of 'd' from the face of the column
The design shear strength of concrete for the above steel percentage from
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections locate
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 1.94
0.658 >0.657
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile
resulting from truss action,because av/d ratio is not more than 2.
Hd=(Pu/2)[L/2-a/4]
H = Pu/8d[2L-a] = 341.45KN
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-
679.95KN
68.00KN
747.95KN
574.13KN
516.72KN
Hence O.K
Ø DUR Piles
Ø DUR Piles
2.09m
0.75m
1.41m
0.710m
214.18KN-m
690.00mm
47.35mm
734.75sqmm
3.66Nos
5Nos
1004.80sqmm
0.194
v
times for the sections located
784.94sqmm
.Hence O.K
DESIGN OF PILE CAPS----PC3(1,6,18,19,20,21,22)
I) Design Parametres:-
As per Table 1 of IS:2911(Part III)-1980,safe load carrying capacity 300mm dia DUR piles in medium compact
sandy soils or clayey soils of medium consistency for 3.5m depth is = 240.00KN
As per clause 5.2.7.2 of IS:2911(Part III)-1980,the minimum spacing between the centre to centre of bored DU
piles should not be less than 1.5Du.
Assuming water table in the pile bulb,the safe load carrying capacity is to be reduced by 25% as per the
clause B-1.6 of IS 2911(Part III)-1980.
Providing two piles,the load carrying capacity of the pile cap will be
Reducing 10% per each pile due to group action,the net safe load carrying
capacity
1.73
0
300Ø DUR Piles
1.73
0.60
1.13
218.12mm
The design shear strength of concrete for the above steel percentage from
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections locate
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 1.93
0.691 >0.647
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile
resulting from truss action,because av/d ratio is not more than 2.
Hd=(Pu/2)[L/2-a/4]
H = Pu/8d[2L-a] = 209.45KN
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-
454.46KN
45.45KN
499.91KN
375.75KN
338.18KN
Hence O.K
DUR Piles
DUR Piles
1.73m
0.65m
1.13m
0.560m
102.82KN-m
540.00mm
33.42mm
449.40sqmm
2.24Nos
4Nos
803.84sqmm
0.229
v
times for the sections located
481.49sqmm
.Hence O.K
#DIV/0!
DESIGN OF PILES
Design Parametres:-
Item P5(15,16)
Note:-1)The above design is as per clauses 6.3, 6.3.1, 6.6 and 8.3.2.2 of IS 2911(PartIII)-1973 duly
reducing bearing resistance by 25% for submerged condition)
3.375
17.2615
13.3285
3.496
1.63875
11.799
3 16 603.4286
2 12 226.2857
5 12 565.7143
7 12 792
2 20 628.5714
1.000
16 201.1429
DESIGN OF ONE WAY SLAB:-
Design Parametres:-
Unit weight of RCC = 25KN/cum
Concrete mix : M25
Steel : Fe500
Cover to Reinforcement : 20mm
Characteristic compressive strength of concrete = 25N/sqmm
Yield strength of steel = 500N/sqmm
Item Slab panel Description
S5
10 12 1131.429
6 12 678.8571
2 20 628.5714
1 25 491.0714
2 16 402.2857
4 16 804.5714
8 12 905.1429
6 16 1206.857
15 12 1697.143