Professional Documents
Culture Documents
Basics
1. Ohmic Current.
2. Dielectric Current.
These are a class of materials called "Insulators" which have very few
loose electrons. They present a near perfect wall, blocking flow of loose
electrons, if a voltage is applied across these. Some of these insulators
have free dipoles at the end of their obstacle wall.
These dipoles get charged positively and negatively during each half
cycle of and A. C. supply. A whole array of such dipoles between two
conducting plates under an A. C. voltage carry, positive and negative
charges from one plate to another during each half cycles. This
transformer of charge – also a current – measured in amps, forms
dielectric or capacitive current. It is entirely different from the Ohmic
Current.
3. Inductive Current.
On other hand, a choke coil which has built up full magnetic field,
starts sending out the current as the field collapses gradually. Here the
voltage leads the current or the current lags behind the voltage.
- Margins at ends.
- Insulation to body.
defects.
This happens mainly in badly & loosely wound capacitors. The coil ends
are normally sealed with an epoxy or the coils are immersed in an
insulating liquid to prevent this.
b) The zinc-spray & the aluminium deposit form a bi- metallic physical
joint- which corrodes aluminium preferentially in the presence of
moisture. This cuts off the entire healthy metallisation below from the
conducting edge, resulting in rapid fall of capacitor current. To prevent
this, the metallisation thickness just at the edge conducting edge is
increased by what is called a heavy edge deposit. Another method that
helps is - to deposit zinc on the lower deposit of aluminium - in what is
called an aluminium -alloy deposit.
c) Consider a large air gap between layers & an irregularity in the form
of a sharp point. As the voltage increases across the dielectric, at same
point there will be electron streamers originating from this sharp point
& cutting through the air path. This is the beginning of a partial
discharge. It will create hot spots & eventually fail the coil. Air has a
breakdown voltage of 4 KV/mm & can easily produce & sustain partial
discharges.
However if the air path is microscopic, air will breakdown and establish
a short circuit path, rather than sustain a partial discharge. This will
increase the leakage current. Leakage current is Ohmic. It makes the
coil hot.
d) The most critical portion of the S - H Capacitor is the edge gap. The
full coil voltage applies across this gap. It is spread on a very thin base
0.2 / 0.3 micron thick as against 5-6 micron thick in traditional
capacitors. The voltage stress is very high- leading to instant or even
sustained partial discharges, should the voltages cross the air gap
strength.
Normally a 2.5 mm gap across a 0.3 micron base can sutain A.C.
voltages upto 440 volts + 10%. This makes these capacitors unsuitable
where there are steady high voltages or sudden & continuous voltage
fluctuations.
Please note that European networks with distribution at 380 volts are
quite comfortable with S-H Capacitors.
A way to over come these defects would be to fill up these gaps with a
suitable oil under vacuum. The oil with breakdown values of 60-80
V/micron increases the gap strength considerably. Japan is carrying out
field trails with S-H Capacitors, filled with SF-6 gas, under pressure, on
networks rated at 3300 & 6600 volts AC.
e) In S-H Capacitor, current flows from one end of the coil to the other
end axially along the cross-section determined by the full length of the
wound foil. By contrast, in a traditional capacitor, it flows circularly
along the length of the winding with a cross-section determined by the
width of the wound foil. This gives a very low self inductance to S-H
coils as compared to traditional coils. These self inductance’s are
inadequate to inherently limit starting or paralleling currents between
two capacitors as compared to traditional capacitors. These
unrestricted current flows, create instant high voltages, puncture a
dielectric & blow up capacitors. Capacitor bursting is more common
with S-H Capacitors than with traditional capacitors.
A choke coil in S-H capacitor takes care of this problem & is a must.
In conclusion one can say that S-H Capacitors are highly economical &
could be used successfully if we understand what their limitations are
& under which circumstances - not to use them.
Madhav S-H Capacitors are not tightly wound. They are dried and
impregnated under high vacuums with capacitor oils. Further each unit
has internal or external choke coil. Besides, we study strictly where
they are being applied.
4) And of - course where one's budget for capacitors is rather tight, but
with attention to (1) & (3) above.
4) Areas with high short circuit level for distribution networks. (This is
likely to affect self healing).
Very thin films are costly and comparatively failure prone, since the
haziness comes at the cost of overall thickness.
4) Oil replaces air and moisture in the voids within the dielectric
portion. It gives strength and increases the life of a capacitors and as
such is a very critical component of the entire system. It itself must be
filtered to very fine degree and degassed. It is reinforced with anti-
oxidants and scavengers. The scavengers lock out acids and broken
chain lengths of oil molecules arising out of partial discharges.
These resistors form a sizeable - portion of the total heat loss defined
for a capacitor - although this portion of the loss does not reflect the
dielectric quality.
2. Their costs are in multiples of two and more, than the costs of
equivalent MPP
Capacitors.
A) KVAR DESIGN :-
1) Carry out a 24 hour load survey. Note down hourly KWs, P.F. and
voltages.
3. Design the bank for its, peak load conditions. Hold your desired
p.f. at 0.95.
4) If the load is small (less than 50 KWs), then split the bank in two
sections
5. If the load is of medium size and (say up to 200 KWs), then split
the bank in
6. If the laod is large sized and complex, then split the bank into a
simple sections corresponding to (2a) and combine sections (2b)
and (2c) and rearrange them in a multi - step, automatically
controlled bank.
B) VOLTAGE CHOICE :-
b. Category where loads fluctuate and voltages vary and also where
you suspect harmonics, specify 440 volts.
C) MODE OF OPERATION :-
basis - covering the duration of the average load. These need not be
switched
While the control panel will be on for twenty hour in a day, individual
sections
might come on or go off many times in 24 hours as per load conditions.
Typical Calculations:
0°
t
I x V x dt = 0°
t
500 x 106 x 200 x 103 x 106 x t2dt
= 0°
t
[10 x 1019 ] [t2]dt
= 24.3 Joules.
1. The voltage will climb up at this rate till the associated lightning
arrestor fires at its rated voltage or
2. The energy in the spikes is so small that the capacitor holds the
system to a safe enough small value.
a. Suppose that the surge energy is very large – say 5000 joules
and we want to restrict the peak voltage build up to 30KV only.
= 1200/C x 10-6
= 0.043 mfd.
It is essential:
The surge capacitors have fairly high built in safety factor. The
failures are very rare in actual practice.
How Does Your Capacitor Work?
APFC Panels
A) Sensing Parameters :-
2. Power Factor Sensing based APFC :- This relay senses the start of the
voltage current wave forms on a given feeder & measures the time
difference between them. It then converts this into a p.f. & compares
this with a set value. Upon finding a difference, it operates the power
contactor. This type of relay is most widely used. It has an advantage
of being able to show the laod p.f. on an indicating meter. It's
disadvantage :- It has no relation to the load magnitude & it's KVAR
requirement. It can lead to severe hunting.
16) Heater.
E) Rating of Components :-
1) Should an APFC panel develop a 'short' from the main bus to body or
between phases, a heavy current will flow till the back-up protection -
like an HRC fuse, isolates this short.
Should the length of this panel be large - then the bus bars must be
laterally & rigidly supported to prevent flexuring under s.c. forces.
The C.T. feeding this relay is the mains CT & not the CT within the
panel itself. The voltage connection to the relay should be from the
same phase from which the current is measured. These relays are
single phase relays.
D. M. TAGARE
Let us next consider the basic factors which contribute to the generation of these
harmonics. Of the four basic electric components, resistances & capacitors are
passive components i.e. they do not generate e.m.f.s. They modify the outputs of the
applied voltages in phase & applitude. On the other hand, Inductances & Switches
are active components. The magnetic fields associated with inductances influence
the output due to applied voltages to the extent they can produce distortions in
phase, amplitude as well as in frequencies. In other words they can act as harmonic
generators. Under electrical switching, we can group all aparata hich can disrupt an
applied voltage at any instant on the sine wave e.g. Rectifiers, Thyristors, Solid state
switching devices, an arc in an arc furnace which will break-down at any instant,
uncontrolled arcing between contacts & between live points & earth & so on. Thus a
square wave generated by a solid state circuit or a sine wave started & cut off at its
intermediate points, can be analysed as so many harmonic waves superimposed on
one another to give a final output, such as a square wave etc. A sharp rising &
diminishing surge across a line, can be considered as a grouping of very high
frequency sine waves superimposed on one another.
One might conclude that the superimposed group of harmonic sine waves which
produce in practice a distorted, sliced or spiked wave exist only on paper - as a
theoretical explanation. Not quite so. In practice, the effect on various electrical
apparata is, as if a separate harmonic distinctly existed.Consider a capacitor, for
example, subjected to a distorted wave shape with a large proportion of 3rd
harmonic. The output of a capacitor is given by
For the same voltage, if f becomes 3f, then kVAR 3f is 3kVARf. The losses in a
capacitor are given by KW = kVAR x Tan Delta. Thus for a 3rd harmonic, the losses
will become 3 times. The capacitor will get much hotter if a considerable 3rd
harmonic exists - since it now produces a basic kVAR at 50 Hz plus a high kVAR due
to the 3rd harmonic. Its life will be reduced & it will fail peraturely.
Let us further consider the case of a spike or a surge entering a capacitor. The
capacitor has a very low, limited life against this abuse, since the dielectric cannot
withstand the high rate of dv/dt repeatedly. As we traverse from 50 Hz to very high
frequencies, the capacitor life reduces. This logic should hold good for higher
harmonics as well.
Similarly a HRC Fuse will blow much more frequently if the current contained fairly
large harmonics. One can safely take frequent blowing up of fuses on apparently
healthy capacitors as a sign of existence of large harmonics.
Nowadays computerised controls are being extensively used in steel mills, chemical
plants & almost every industry which can drive economic benefits from these. Many
circuits in these are beased on detecting the start of a voltage/current! wave on the
50 Hz scale. Should a harmonic exist, which at any instant on a 50 Hz sine wave, has
a magnitude equal to or greater than that of the fundamental at that instant, the
actual voltage/current will cross zero & come up again. This will trigger the computer
circuitry falsely & lead to chaos. Thus filtering out all types of harmonics on the
supply lines to computerised controls becomes a high priority.
In a rotating machine the slot insulation is a critical factor due to very limited space
available. Harmonic currents raise the conductor temperatures to uncomfortable
levels for the partition to withstand on a long term basis.
Thus excessive harmonics into or out of a rotating machine will lead to frequent &
permature winding failures. The harmonics must be filtered out.
2) Interference with video signals as evidenced by bright light shafts traverse slowly
upwards. Voltage flicker due to operation of induction furnaces makes it impossible to
view TVs.
3) Rotating Discs in a meter or a protective relay are influenced by the magnetic field
produced by the mains currents at 50 Hz. Harmonic can cause phase unbalancing. All
this leads to wrong meter readings/relay operations.
The second most trouble- some source of harmonics are the steel-melting Arc-
Furnaces in India. A number of phenomenon are heaped together. First there are the
arcing frequencies. Secondly there are heavy surges when the entire currents are cut-
off for example when a melting mass sinks down suddenly & losses arc contact or
even when the electrode itself breaks or detaches.
Thirdly the transformer core in series with the inductance of the melting mass, gets
saturated & produces harmonics. The spread of these harmonics to some extent
depends on the composition & density of the melting mass as well. Well established
furnace manufacturers have data collected & categorised on harmonic generation
under various conditions & for different furnace designs.
This data is useful in designing the overall capacitor installation as well as the filter
banks for an Industrial Arc Furnace. Here again, the harmonic generation is voltage
based. This together with the presence of a no. of frequencies, leads one to prefer
wide-band filter circuits as against accurately tuned filter circuits.
Although we have not gone in for solid state controlled equipments as extensively as
the western countries have done, these drives are being set up in large sizes & more
quantities now. These include electro-chemical power supplies, adjustable speed
drives-both D.C. & A.C., uninterrupted power supplies & so on. By controlling the
switching actions on a fundamental A.C. sine wave at 50 Hz., they affect the power
factor in two ways :
1) The displacement component of the power factor gives the ratio of controlled
active power to the total supplied apparent power at the 50 Hz. This introduces
harmonics.
2) The distortion component of the power factor arises out of wave shaping of the
voltage & current to be used further. It is associated with the harmonic voltages &
current generated & transmitted backwards into the network.
Harmonic generation arising out of switching actions is mainly current based in that
the maximum harmonic current supply in capacity of the source is limited.
This results in several characterstics :
1) The fixed reactive power requirment is determined by the operating point & can be
predicted. Fixed capacitors can cater to this requirments.
2) The harmonic current requirment for various harmonics can be calculated. This
helps in designing finely tuned filter capacitor banks for various harmonics
accurately. The harmonics are not amplified beyond the capacity of the generating
source. IEEE Specifications 519-1981 discuss the Hamonic Control & Reactive
Compensation of Static Power Convertors in great detail.
We have presently only one HVDC transmission system in India. As these systems
appear, they will have to be fitted with suitable, large filter capacitor banks to avoide
system voltage distortions.
Harmonics can easily be detected with an oscilloscope probes across the ammeter
terminals inside a metering panel. There is no need for opening out any circuits. The
voltage harmonics can be detected by putting the probes across a voltmeter &
adjusting the oscilloscope range. This show the wave shapes & a preliminary idea of
distortions.
This brings us to various definitions so that we can define & tackle the harmonic
problems.
The filter bank balances the capacitive & inductive voltage drops at the tuned
frequency. As a result if one measures the input voltage to a filter bank. It will mainly
read the fundamental voltage & lead us no where with respect to the harmonics.
Therefore the starting point has to be the current measurment.
I & H suffices indicating fundamental & harmonic frequenncy values. Then kVAR
rating of the capacitor = Vc x IF x 10-3/phase at the given current IF.
Similarly, the kVAR rating of the series reactor is given by VLIF x 10-3/Phase.
1) As per IS-2834, the above rated kVAR can be upgrated by 135% to comply with the
requirments of overload capacity of a capacitor.
2) Unlike the fixed p.f. improvement capacitors, where IS-2834 standardises voltage
& kVAR ratings on the basic units, this cannot be done w.r.t. capacitors designed for a
filter bank.
3) The filter capacitors cannot be designed accurately at the rated voltages since this
will have a bearing on the nearest dielectric thicknesses, commertially available.
Then if the revised design voltage under the considerations (for a safe volts/micron
stress) is Vd, the kVAR rating of the capacitor will become Vd/Ve2 x kVAR as
calculated (i.e. Ve x IF). The costs will go up if compared on the previously rated kVAR
basis (i.e. Ve x IF).
4) While carrying out the factory testing for thermal stability, one will have to
superimpose the fundamental testing voltage with the designated harmonic at 1.2
times the rated value. This is impractical. Hence the testing voltage at 50 Hz will
have to be so adjusted that it will give the required total kVAR load on capacitors. If
Vt/1.2 is equal to or less than Vd under (3) above, then there is no problem.
Otherwise Vd will have to be upgraded so that Vd = Vt/1.2. This contingency should
not normally arise - uless the high harmonic currents are very large w.r.t. the current
It.
5) The filter bank contributes a kVAR at fundamental frequency to the system. This
value must be deducted from the requirment of the fixed capacitor bank. It is given
by kVAR = I2l (Xcl - Xll) x 10-3.
Harmonic Order 5 7 11 13 17 19 23 25
Let us first consider the incoming line to the installation, represented by two
impedance ZTRL & ZTX in series. These are mainly inductive. The voltage V1 will
send a harmonic current Vh(ZTX + ZTRL) into the supply & cause nuisance to other
consumers on the line.
In case the filter impedance Zf(Lf + Cf) tune to this harmonic, its value is almost zero
& Vh will fall to zero - putting out maximum possible current into the filter. In that
case, no harmonic current will flow into ZTX + ZTRL. Let us consider a likely condition
where ZTX + ZTRL resonates with the impedance of the capacitor branch (Zf + Zc) in
a parallel at a certain harmonic. Then very high harmonic currents will circulate
between the two systems, causing serious consequences. This can be prev
Design and costing of a Harmonic Filter.
Mr. Sachin V. Shelar. ( R & D Engineer )
For the designing purpose we require some data such as load details, existing
power factor, required new power factor, total harmonic distortion, individual
harmonic details etc. This data can be obtained from a harmonic analyser.
First calculate the total KVAR required to improve the power factor to the
desired value. Then distribute the total KVAR into two parts, a normal capacitor
bank (untuned) for power factor correction and a filter bank (tuned) for filtration
purpose. This is explained in detail in the example given below.
Load in KW = 606.20.
Power factor = 0.42 lag.
ITHD = 30.47.
Assuming required power factor to be 0.97, we calculate the total KVAR required
to raise the power factor from 0.42 to 0.97.
KW = 606.20
= 1157.80 KVAR.
1158 KVAR.
From the readings it can be seen that, ITHD is 30.47 but maximum harmonic
current distortion as recommended by IEEE specifications C-519-1992 is 4.0.
Out of 1158 KVAR to be installed we employ 30% KVAR towards filter duty and
remaining KVAR for power factor correction.
Thus,
= 347.4 KVAR.
Design of filter :
C = 9.21 mfd/Ph.
XL250 = XC250.
So,
L = 44 mH.
40 Amp
IRMS = 44 Amp.
Fig. 3 Parameters.
VL = VL50 + VL250
current.
= I50 x XL50
= 18.37 x 13.82
VL50 = 253.87 V.
current.
= I250 x XL250
= 40 x 69.16
VL250 = 2766.4 V.
Total voltage across reactor (VL) :
VL = VL50 + VL250
= 253.87 + 2766.40
= 3020.27
VL 3020 V.
= VL x IRMS
= 3020 x 44.
= 132.88 KVAR/Ph.
133 KVAR.
VC = VC50 + VC250
= 2766.4 V.
VC250 2766 V.
VC = VC50 + VC250
= 6350 + 2766
VC = 9116 V.
KVAR rating of capacitor :
= VC x IRMS
= 9116 x 44.
= 401.10KVAR/Ph.
401 KVAR.
Costing :
Total = 6,86,000
Total = 13,66,000
Conclusion :
When normal power factor correction bank is converted into the filter bank the
cost almost becomes twice, but with a load of 2000 KW and 40 amp of 5th
harmonic current at 11 kV it can be justified.
This particular consumer has been trying to maintain his power factor near 0.85
by -
He burns and replaces his LT capacitors within 2-3 months and then pays a
heavy penalty until a new set of capacitor is installed.
His monthly electricity bill is Rs. 10,60,000/-. His penalty will come to Rs.
1,06,000/- per month.
Now a days there is increasing awareness about saving energy, utilising the
available energy efficiently by employing energy efficient devices. Thus, there is
a trend to convert conventional systems to energy efficient systems.
Capacitor, which improves the power factor of the system, forms an integral part
of the energy efficient system.
Industry is rapidly changing over to energy efficient drives, devices these are
listed as below.
1. DC drives.
2. Variable speed AC drives.
3. Energy efficient lamps.
4. UPS.
etc.
Though these devices facilitate the use of energy efficiently they reduce the
power factor of the system, inject harmonics in the system. These problems
further gives rise to another problems and ultimately there is reduction in the
overall efficiency of the system.
1. DC drives :
DC drives are used as they give better efficiency than that of AC drives also the
speed control of DC drive is easy.
AC------> Converter------> DC
2. Frequency converters :
These are used to control the speed of AC drives. First AC supply is converted
into DC supply, which is again converted into AC with different frequency. This
also reduces the power factor and introduces harmonics.
3. Electronic items :
For accurate and automatic control there is increase in use of electronic controls,
also use of computers has been increased. All these electronic items require
switched mode power supply, which draws current over a part of each half cycle
as shown. This reduces the power factor.
All these devices form what is called as nonlinear load, which not
only causes the problem of low power factor but also problem of
harmonics.
Following tables and illustrations will enable you to properly select the
capacitor for your installation.
Capacitor KVAR for Power Factor Correction.
Existing
Power
0.85 0.90 0.95 0.96 0.97 0.98 0.99 1.00
Factor
Illustrative Example. :
The Capacitors are rated at 440 volts to allow for high voltages prevailing
on the systems. But they operate let us say at an average of 400 volts.
Therefore an upward revision by 1.21 times is called for. The customer
will require 1.21 x 89.74 = 108.6 KVAR. Choose 110 KVAR, which comes
within standard sizes.
We should not install more KVAR also we should not install less
KVAR than the required KVAR as both give disadvantages,
secondly we should decide optimum location of capacitors, it is
preferable to install the capacitors as near to the load as possible.
Further if there is wide variation in the load pattern we should go
for automatic power factor control method in which capacitors are
switched ON/OFF according to the load.
A. HARMONICS CONTROL :
A normal power factor correction bank is divided into two parts. One is
normal power factor correction bank, only for power factor correction
purpose and second is harmonic filter bank, which besides reducing the
harmonics also improves the power factor.
Now a days there is increasing awareness about the harmonics and its
control. Although, presently there is no legislation to control the level of
harmonics it will be introduced in near future and the consumer which is
generating harmonics beyond specified limits may have to pay penalty.
There are standards like IEEE 519-1992, which recommends limits on the
voltage and current distortion. CBIP has also taken steps in this direction
and has published a guide for limiting voltage harmonics while guide for
limiting current harmonics is in pipe line. Also current distortions limits
are gaining increasing importance over the voltage distortion limits.
The IEEE standard 519 specifies voltage distortion limits as per the table
below.
Following example gives general idea and values for harmonic filter.
Data :
By calculation :
Thus,
(It can be seen that individual rating of reactor and capacitor is quite high.)
The cost of harmonic filter is many times the normal capacitor bank but the
advantages gained are worth.
In near future all conventional drives will be replaced by energy efficient drives ,
which brings along with it the problems of low power factor and harmonics.
These problems can be easily solved by using capacitors and total system can be
made more energy efficient