Application Area § 1
• Shopping facilities
• Congregational areas
• Hospitals and care-homes
• Accommodation
• Skyscrapers
• Car parking facilities
• General educational and vocational schools
Testing § 2 (1)
• Technical systems must be test by a Specialist for effectiveness
and reliability. This includes emergency power supplies.
Testing § 2 (2 - 4)
• Tests are required:
• Before first use
• Immediately after a technical change in the physical structure
• Immediately after a significant change in the technical system
• Within a period of 3 years (recurring tests)
• The tests are to be undertaken by the owner or operator.
• The owner or operator is required to keep records of periodic inspections
for a minimum of 5 years.
With the introduction of DIN VDE 0100-560, most sections of the DIN VDE 0100-718, which
have been associated with safety lighting, have been replaced.
The following sections of DIN VDE 0100-718 are however still to be considered for safety
lighting.
Inspect (718.61.1)
• Compliance to operational norms?
• Ventilation in battery areas, in accordance with EN 50272-2
• Ventilation in areas with internal combustion engines
• Exhaust systems of internal combustions engines
• Capacity or rather fuel supply from generators
The static load is taken into account, as well as other possible operating state
(recurring motor starting, harmonic currents etc.)
• Selectivity
As well as
- Preliminary Standard-
DIN V VDE V 0108-100
Emergency Lighting Systems
• For all other systems, the tests are to be carried out under 7.3 and the results
must be logged.
• The operator of the building must designate a competent person to observe the
maintenance of the system.
Initial Testing(7.2)
• Measurement of photometric values acc. DIN 5035-6 and EN 1838
• Initial testing in line with DIN VDE 0100-600 and following the norm DIN VDE
0100-560:1995-07
General (7.3.1)
• This can be achieved with a central signalling device that displays the
system status of the central power supply system (System non-
maintained, feed from the power source for safety purposes/battery
operation, system interrupted), while the required operating time is
continuously monitored .
CGVision
Replacing the batteries with less than 2/3 rated operating time (VDE 0108
10 /89 Part 1 Paragraph 9.3.1)
Replacing the batteries with less than 100% rated operating time (EN
50171)
Circuit monitoring
Circuit
Influencing factors:
monitoring
• Fluctuating battery voltage (186 - 275 V)
• Ageing lamps
• Fluctuations in ambient temperature
• Mixed configuration (large and small power)
Request Request
2000 - 4. Generation
2-wire technology, request Mixed battery
Gemischte type in
Betriebsarten
by current measurement, one
in final circuit
einem Endstromkreis
reverse polarity
Request Request