NOARK Electric (Shanghai) Co.

, Ltd, as a subsidiary of CHINT Group and located in Shanghai with an area of approximately 391 acres, is
committed to bring a high-end brand to the low voltage electrical market. With over 45 million US dollar investment, NOARK Electric is
equipped with the most up-to-date technologies and production facilities. A professional R&D team, comprised of more than 100 professors
and doctors possessing some exclusive technologies patents such as modern simulation, has been working hard to achieve the intelligent low
voltage distribution and control products line with high quality, performance and stability.

The first generation Ex9 series of intelligent low voltage electrical products, incorporating the latest design, electronic and simulation
technologies, reach the top industry expectations. This product series not only sets multiple functions into ever smaller size, but also includes
data acquisition, communications, and intelligent remote control modules, which reward Noark with up to 54 exclusive patents including
invention, practical application and design. We firmly adhere to the concept of "best products derive from best raw materials", which is also
the principle of production. It is realized by cooperating with qualified suppliers with a very high selection standard. NOARK Electric is the
first Chinese company in the low voltage electrical industry implementing ISO/TS 16949 quality system. Besides complying with all compulsory
domestic standards,the full range of products is accredited by CB organization based on up-to-date IEC standards.

Through a global marketing network, Noark has successfully contributed its efforts to provide complete solution and highly-efficient, highly-
reliable, highly-intelligent and energy-saving low voltage products to some sophisticated industry areas, such as power, smart grid, renewable
energy, petrochemical, machinery manufacturing, real estate and construction.

We Believe,
Remarkable technical innovations bring reliable products!
Advanced technical ideas create intelligent electrical apparatus for the future!

Contents

Features 01
Features 1
Advantages 3
Standards and Certificates 9
Operating Conditions 10

Control Unit 11

Description of Control Unit 11


Summary of Functions 12
Characteristics 13
Parameter Setting 14
Measuring Range & Accuracy 16
Method of Communication 16
Operation Overview 18

Parameters 19

Accessories 21
Connecting Accessories 21
Lock & Interlock Accessories 21
Accessories for Remote Control & Signal Indication 22
Control Unit-related Accessories 23

Selection 24
Selection Rules 24
Order Specifications 25
Features
Product Overview

The Ex9A series Air Circuit Breaker is used for power distribution and protection of main lines of low-voltage distribution
networks with a rated current ranging between 400 A and 4,000 A, and also for the protection of motors and generators.

As a new generation of smart product, the Ex9A not only has muiliple protective functions, but also performs the functions
of measurement, communication, and electric power management, able to truly give the electric characteristics of the line
on which it is mounted, exchange data with other devices, and receive control commands from a higher level.

Air Circuit Breaker Ex9A16 Ex9A32 Ex9A40 Ex9A63


Load switch Ex9ASD04 Ex9ASD06 Ex9ASD08 Ex9ASD10 Ex9ASD12 Ex9ASD16
Ex9ASD16b Ex9ASD20 Ex9ASD25 Ex9ASD29 Ex9ASD32 Ex9ASD40

Four frame rated 1600A 3200A 4000A 6300A


current levels :

Withdrawable Withdrawable Withdrawable Withdrawable

3P
Fixed Fixed Fixed

Withdrawable Withdrawable Withdrawable Withdrawable

4P

Fixed Fixed Fixed

Note:The news about the Ex9A63's lauch will be in another notice.

01
Features

Each air circuit breaker model covers several breaking capacities and rated current.

Short-time withstand Dimension


Fram

Rated current level Breaking capacity current Withdrawable Fixed


3P/4P 3P/4P
kA kA/1s
400A 65 H
55 42 352 323
50 (mm)
630A
30 25
800A W
Ex9A16

282/382 254/324
1000A (mm)

V
1250A V D
N Q N Q N/Q N/Q 394 255
1600A (mm)
415 690 415 690
kA kA/1s
H
1600A 430 354
100 (mm)
2000A
85 75 65 85
65 65 50
50 50 40 W
Ex9A32

2500A 35 437/552 424/539


(mm)
2900A
V V
D
3200A Q R H Q R H Q R H Q R H 401 329
(mm)
415 690 415 690
kA kA/1s
H
2000A 430 354
100 (mm)
2500A
85 75 65 85
65 65 50 50
50 40 W
35
Ex9A40

2900A 437/552 424/539


(mm)
3200A
V V
D
4000A Q R H Q R H Q R H Q R H 401 329
(mm)
415 690 415 690
kA kA/1s
120 H
100 471 424/539
(mm)
4000A 85 85
Ex9A63

5000A W
835/928
(mm)
6300A
V V V V
D
440
415 690 415 690 (mm)

Note:Breaking capacity of circuit breaker is:N-55KA,Q-65KA,R-85KA,H-100KA,V-125KA(under Ue=415V)

02
Features

Load switch
The Ex9ASD series load switch is used for communication between different busbars and the switching of the on/off
control for electric equipment, providing a cost-effective solution to the users.

Be able to isolate.
Be able to make/break current and overload current at a certain level.
Be unable to break the short-circuit current, to be used with a fuse if necessary.
No intelligent control unit.
Accord with IEC 60947-3, 14048.3 GB standard.

Short-time withstand Dimension


Short circuit off ability
Model Rated current level current Withdrawable Fixed
Icm
1s 3P/4P 3P/4P

Ex9ASD04 400A 42 105 H


kA/1s kA 352 323
(mm)
Ex9ASD06 630A
Ex9ASD08 800A W
282/382 254/324
Ex9ASD10 1000A (mm)
V V
Ex9ASD12 1250A
D
394 255
Ex9ASD16 1600A 400/690 400/690 (mm)

Ex9ASD16b 1600A H
kA/1s kA 187 430 354
(mm)
Ex9ASD20 2000A 85

Ex9ASD25 2500A W
437/552 424/539
(mm)
Ex9ASD29 2900A

Ex9ASD32 3200A V V
D
401 329
Ex9ASD40 4000A 400/690 400/690 (mm)

03
Features
Advantages
True arcing circuit breaker

NOARK's unique high-efficiency arc quenching & extinguishing technology enables the


Ex9A to become a genuine zero arcing circuit breaker.

The new design of arcing chamber includes:

Magnetic-blow arcing technology: to extends the arc and introduces it into the arcing chamber.

Metal grid: Split arc, to accelerate heat dissipation and prevent high temperature generated by arc.

Metal mesh: to filter out and absorb the hazardous substances contained in the gas generated
from the arc.

High breaking capacity: Ics=Icu=120KA;

Saving space: the Ex9A series circuit breaker has different structural dimensions for differ-
ent frame sizes, but every size is characterized in "large capacity and miniature, "saving
mounting space and reducing the cost for users.

Sophisticated technology

NOARK employs unique technology for the wiring terminals and conductor blocks of its
Ex9A air circuit breaker in order to effectively lower the rise of temperature.

T(℃)

80
General technology
70 Unique technology

60

50

40

30

20

10

0 30 60 90 120 150 180 210 240 t(min)

Comparison of Temperature Increases at Different Process Conditions

04
Features

Highly-intelligent circuit breaker

The Ex9A air circuit breaker uses a more sophisticated smart unit, besides
preventing circuit / power supply device against hazards from various kinds
of faults and adding abundant expansion functions:

Highly reliable protection

Up to 18 alarm and protective functions.

Wide-range protection, not only suitable for power distribution and mot-
ors, but also available especially for the protection of generators.
Protection of high accuracy and high sensitivity

Highly reliable protection.

Complete measurement & maintenance

Several measurement functions: current, voltage, powerfrequency, ener-


gy, demand, and harmonic wave.
Multiple maintenance functions: the record of operating & maintenance
parameters such as faults, alarms, operation,currents, maximum historic
values, and contact wear.

Powerful communication function

Able to realize remote terminal, remote ensing, remote signaling, remote


control,remote regulation, etc.
Multiple protocols supportable, to meet the requirements of different net-
works.

Easy-to-use HMIs

.
LCD data display.

Multiple-language operating system.

Double regulation function for parameters, tuning supportable.

Abundant space for expansion

Programmable signaling unit.

Zone selective interlock (ZSI).

Measurement of demand values.

05
Features

Modularization
模块化设计 Design

抽屉式
Withdrawable

4 5 6

06
8

13

9
7

6
14

15

10

11

12
No. Designation
1 Smart Unit
Fixed
固定式 2 Operating Mechanism
3 Electric Motor
4 Shunt Release
5 Closing Release
6 Undervoltage Release
17 7 Auxiliary Contact
Wiring Terminal on the
8
Secondary Circuit
9 Arcing Chamber
10 Handle
16
11 Side Plate
12 Panel
13 Withdrawable Indicator
14 On Button
15 Off Button
16 Retaining Plate
17 Cover

07
Features

Energy storage way

The operating mechanism of the Ex9A is a spring energy storage type. When switching
on/off, the storage spring releases energy and drives the contacts to move. The operating
mechanism may have the following ways of energy storage:

Manual energy storage to make the actuating mechanism store energy by activating the
storage handle with hand.

Energy storage with a motor


To make the operating mechanism store energy with storage motor.

A type of durable circuit breaker

Longer product service life, extending replacement duration and lowering costs.

Electrical service life (cycle)

6000

5000

3000

Mechanical life (cycle) 500

500
12500 Ex9A16
Standard 500
Ex9A32 500
10000 Standard 500
Ex9A40
Standard
8000 Ex9A63
Standard

2500

1500

1500 2000
Ex9A16
Standard
1500
Ex9A32
Standard
Ex9A40
Standard
Ex9A63
Standard

Standard data are sourced from GB 14048.2-2008

08
Features

Wiring Flexibility

The user may experience the flexibility and convenience of the Ex9A air circuit breaker even
though it is provided on a main or a secondary circuit.

Ex9A air circuit breaker, fixed or withdrawable, is featured by:

Control Circuit
The most sophisticated screwless wiring technology, while maintaining its high degree of
protection (IP40), enabling a safer & easier operation and maintenance by the user.

Several wiring connections for the main circuit:

Flexibility of the Ex9A *The user may select either a horizontal or vertical connection

Vertical Connection
Horizontal Connection

*Also, the user may select a front connection

Front Connection

*Hybrid connection supportable and suitable for more stringent mounting


conditions and saving space

Hybrid Connection Hybrid Connection

09
Features

Environmentally Friendly

Design/Manufacturing
Haloid The Ex9A does not contain any noxious or hazardous sub-
element
Asbestos
stances, and its manufacturing and processing processes
Cadmium
are performed in accordance with the requirements of the
Chloro flouro
carbon(CFC) ISO 14001.

Operation
Low temperature rise, low power consumption, and minor
influences to the surrounding environment during operation.

Distribution
Environmentally-protective materials are used in the course
of distribution.

Recycling
Over 80% of its component materials can be recycled and
reused at the end of its service life.

Standards and Certificate

International standards National standards



Product standards
IEC 60947-1 (General provisions) GB 14048.1
IEC 60947-2 (Circuit breakers) GB 14048.2
EN 60947-2 (Circuit breakers) GB 14048.2
IEC 60947-3 (Switches, isolation) GB 14048.3
Extreme environmental test standards
IEC 60068-2-1 (Low temperature) GB/T 2423.1
IEC 60068-2-2 (Dry heat) GB/T 2423.2
IEC 60068-2-11 (Salty mist test) GB/T 2423.17
IEC 60068 -2-30 (Moist heat) GB/T 2423.4

10
Features
Operating Conditions
Environment temperature

Could be used in temperatures from -10℃~+40℃.

If the necessary working temperature is below -10℃ or above +40℃, use it according to
those specified in the table of temperature compensation coefficient or please contact
400-1092-111.

Altitude

Normally, the altitude of installation site should not exceed 2,000m.

If having to install at an altitude above 2,000m, use it according to those specified in the
table of altitude-derating factors or please contact 400-1092-111 if you have any questions
and/or concerns.

Humidity

The following conditions must be met during normal operation:

If the ambient temperature is +40℃, the atmospheric relative humidity can not exceed 50%.
If the temperature is lower, use it under the conditions for a higher degree of humidity.

The monthly mean relative humidity needs to be below 90% in the dampest month.

The effects of condensation on the product surface impacts its performance and needs to
be taken into consideration.
(Every product has been tested by strictly following the requirements given by IEC 60068-
2-30,and use advanced anti-condensation technology)

Pollution Degree

Level Ⅲ

Electromagnetic Compatibility (EMC)


Electromagnetic phenomena due to the following factors may interfere with normal
operation of the electronics (the smart control unit) on a circuit breaker:
Harmonic wave of the power grid

Sudden current drop or sudden trip on the power grid

Radio waves

Electrostatic discharge

The product has been strictly tested in accordance with IEC 60947-2, making sure that:

No missed trip occurs

Trip time is not affected

11
Control Unit
Overview of the Control Unit

The control unit is the core component of air circuit breaker, mainly used to identify electric faults auto-
matically and control the circuit breaker in order to trip for protection of the circuit.
The Ex9A smart unit uses electronic technology with the 32-bit DSP (digital signal processor) as its core.
Besides enhancement of its protection performance and the addition of protection types, it is able to per-
form multiple functions such as the measurement of electric parameters, visual operation, memory, and
communication.
The Ex9A air circuit breaker provided with the smart unit is fully applicable to the new-type automation &
digitalization power distribution system.

Advanced Type(protection of
Standard Type Advanced Type(protection of power distribution)
generator)
Harmonic
classification Basic Type Harmonic Wave Energy Type
Current Type Voltage Type Energy Type WaveType
Type for Generator
(A) (D) (P) for Generator
(H) (GP)
(GH)

3.0
Three-Section
Selective
Protection

4.0
3.0+Earth-
Fault
Protection

5.0
3.0+Earth-
leakage
Protection

12
Control Unit
Summary of Functions
3.0/4.0/5.0A 3.0/4.0/5.0D 3.0/4.0/5.0P 3.0/4.0/5.0H 3.0GP 3.0GH
Overload Protection ■ ■ ■ ■ ■ ■
Short-circuit Short Delay Protection ■ ■ ■ ■ ■ ■
Short-circuit Instantaneous Protection ■ ■ ■ ■ ■ ■
Grounding Protection ■(Only 4.0) ■(Only 4.0) ■(Only 4.0) ■(Only 4.0) — —
Earth Leakage Protection ■(Only 5.0) ■(Only 5.0) ■(Only 5.0) ■(Only 5.0) — —
MCR & HSISC Protection ■ ■ ■ ■ ■ ■
Pr o t ec t i on Func t i on

Unbalanced Current Protection ■ ■ ■ ■ ■ ■


Overload Pre-alarm ■ ■ ■ ■ ■ ■
Neutral Conductor Protection ■ ■ ■ ■ ■ ■
Temperature Protection ■ ■ ■ ■ ■ ■
Overvoltage Protection — ■ ■ ■ ■ ■
Undervoltage Protection — ■ ■ ■ ■ ■
Unbalanced Voltage Protection — ■ ■ ■ ■ ■
Over-frequency Protection — ■ ■ ■ ■ ■
Under-frequency Protection — ■ ■ ■ ■ ■
Phase Sequence Protection — ■ ■ ■ ■ ■
Reverse Power Protection — — ■ ■ ■ ■
Harmonic Wave Protection — — — ■ — ■
Current Measurement ■ ■ ■ ■ ■ ■
Thermal Capacity ■ ■ ■ ■ ■ ■
Measu r eme n t Func t i on

Voltage Measurement — ■ ■ ■ ■ ■
Freq. Measurement — ■ ■ ■ ■ ■
Voltage Unbalance Measurement — ■ ■ ■ ■ ■
Phase Sequence Detection — ■ ■ ■ ■ ■
Power Measurement — — ■ ■ ■ ■
Power Factor Measurement — — ■ ■ ■ ■
Electric Energy Measurement — — ■ ■ ■ ■
Harmonic Wave Detection — — — ■ — ■
8-times Fault Record ■ ■ ■ ■ ■ ■
8-times Alarm Record ■ ■ ■ ■ ■ ■
Ma i n t enance Func t i on

8-times Shift Record ■ ■ ■ ■ ■ ■


Historic Current Peak Value ■ ■ ■ ■ ■ ■
Contact Equivalent ■ ■ ■ ■ ■ ■
Operating Cycles ■ ■ ■ ■ ■ ■
Clock Function ■ ■ ■ ■ ■ ■
Self Diagnosis ■ ■ ■ ■ ■ ■
Test Port ■ ■ ■ ■ ■ ■
Signal Output Unit (4DO) □ □ □ □ □ □
Op t i ona l Func t i on

Signal Output / Input Unit


□ □ □ □ □ □
(4DO2DI)

Demand Value Measurement Current □ Current □ Current / Power□ Current / Power□ Current / Power□ Current / Power□
Zone Selective Interlock (ZSI) □ □ □ □ □ □
Communication Function — □ □ □ □ □

■ Fault □ Optional —None

13
Control Unit
Characteristics

Overload Long-time Delay Protection


=1.05 <2h not trip
I/IR
=1.3 <1h trip
Delay Reverse Time Limit t=(6IR/I)2×tR
Characteristics Accuracy ±15%
Short-circuit Short-time Delay Protection
≤0.9 not trip
I/Isd
>1.1 trip
Definite Time Limit tsd=0.1~0.4s
Delay
Reverse Time Limit t=(6IR/I)2×tR/10 @≥10Isd switch to definite time limit protection
Characteristics
Accuracy ±10%
Short-circuit Instantaneous Protection
<0.85 not trip
I/Ii
>1.15 <40ms trip
Delay Characteristics Inherent Error 40ms
MCR & HSISC Protection
<0.8 not trip
I/Ii
>1.0 trip
Delay Characteristics Accuracy <20ms
Earth-fault Protection
Differential Type to detect vector and current
Type
Vagabond Current to measure vagabond current directly with Type transformer
<0.8 not trip
I/Ig
>1.0 trip
Definite Time Limit tg=0.1~1s
t=tg×Cr×Ig/I @I/Ig<Cr
Delay Characteristics Reverse Time Limit
switch to a definite time limit protection automatically @I/Ig≥Cr or Crset to OFF
Accuracy ±10%
Earth-leakage Protection
<0.8 not trip
I/I△n
>1.0 trip
△t 0 0.06 0.08 0.17 0.25 0.33 0.42 0.5 0.58 0.67 0.75 0.83
I△n 0.04 0.36 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
Max. Off Time
2I△n 0.04 0.18 0.25 0.5 0.75 1 1.25 1.5 1.75 2 2.25 2.5
(s)
5I△n 0.04 0.072 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
10I△n 0.04 0.072 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Delay Characteristics Accuracy ±10%
Overvoltage Protection
When the three line voltages UAB, UBC UCA exceed the setpoints simultaneously, protection activates.
Voltage / Startup <0.9 not trip
Value >1.1 trip
Voltage / <0.9 reversion
Reversion Value >1.1 no reversion
Accuracy ±10%
Delay Characteristics
Inherent Error 40ms

14
Control Unit

Renewal above
Undervoltage Protection
When the three Line Voltages UAB, UBC,UCA drop below the setpoints simultaneously, protection activates.
Voltage Value / >1.1 not trip
Startup Value <0.9 trip
Voltage Value / >1.1 return
Return Value <0.9 no return
Permissible Accuracy ±10%
Delay Characteristics
Inherent Error 40ms
Temperature Protection
Voltage Value / >1.1 trip
Startup Value <0.9 not trip
Voltage Value / >1.1 no return
Return Value <0.9 return
Permissible Accuracy ±10%
Delay Characteristics
Inherent Error 40ms
Harmonic Wave Protection
When the threshold voltage and current are higher than its setpoint respectively, protection activates.
THD Value / >1.1 trip
Startup Value <0.9 not trip
THD Value / >1.1 no return
Return Value <0.9 return
Permissible Accuracy ±10%
Delay Characteristics
Inherent Error 40ms

Actual Current

I Actual Current
IR Setting Current for Long Delay & Reverse Time Limit Protection
tR Setting Time for Long Delay & Reverse Time Limit Protection
Isd Setting Current for Short Delay & Definite Time Limit Protection
tsd Setting Time for Short Delay & Definite Time Limit Protection
Is Setting Current for Short Delay & ReverseTime Limit Protection
ts Setting Time for Short Delay & Reverse Time Limit Protection
Ii Setting Time for Instantaneous Protection
Ig Setting Current for Grounding Protection
tg Setting Time for Grounding Protection
Cr Clipping Coefficient for Grounding Reverse Time Limit
I△n Setting Current for Leakage Protection
△t Setting Time for Leakage Protection

15
Control Unit
Parameter Settings

Protection Type Parameter Setting Knob Keypad


IR=0.4-0.5-0.6-0.7-0.8-0.9-0.95-0.98-1.0×In Tuning within Span
Current Setpoint (A) (General Protection) IR=0.4-0.5-0.6-0.7- In≤2000A Step 1A
Overload Long- 0.8-0.9-1.0-1.1-1.2×In(Generator Protection) In>2000A Step 2A
time Delay
Protection Delay Time(s) tR=1-2-4-8-12-16-20-24-30
Cooling Duration for Thermal
10-20-30-45-60-120-180
Capacity (min)
Is≤Isd,Isis set by keypad (Reverse Time Limit) Tuning within Span
Short-circuit Current Setpoint(A) Isd=1.5-2-2.5-3-4-5-6-8-10×IR+OFF(Definite In≤2000A Step 1A
Short Delay Time Limit) In>2000A Step 2A
Protection tsd=0.1-0.2-0.3-0.4+OFF(Definite Time Limit)
Delay Time(s)
ts=(6IR/I)2×tR/10(Reverse Time Limit)
Short-circuit Tuning within Span
Instantaneous Current Setpoint(A) Ii=2-3-4-5-6-8-10-12-15×In+OFF In≤2000A Step 1A
Protection In>2000A Step 2A
Current Setpoint(A) Ig=0.2-0.3-0.4-0.5-0.6-0.7-0.8-0.9-1.0×In Tuning within Span Step1A
Earthing Delay Time(s) tg=0.1-0.2-0.3-0.4-0.5-0.6-0.7-0.8-0.9-1.0+OFF
Protection
Clipping Coefficient for Reverse
1.5~6 Step 0.5
Time Limit Cr

Leakage Current Setpoint(A) I△n=0.5-1-2-3-5-7-10-20-30 Tuning within Span Step0.5A


Protection Delay Time(s) △t=0-0.06-0.17-0.25-0.33-0.42-0.58-0.75-0.83 Tuning within Span Step0.02s
Startup Value (V) — Return Value-1200 Step 1V
Return Value (V) — 100-Startup Step 1V
High-voltage
Startup Time(s) — 0.2~60 Step 0.1s
Protection
Return Time(s) — 0.2~60 Step 0.1s
Method of Activation — Alarm+Trip+Off
Startup Value(V) — 100-Return Value Step 1V
Return Value (V) — Startup Value-1200 Step 1V
Low-voltage
Startup Time(s) — 0.2~60 Step 0.1s
Protection
Return Time(s) — 0.2~60 Step 0.1s
Method of Activation — Alarm+Trip+Off
Startup Value(℃) — Return Value-120℃ Step0.5℃
Return Value (℃) — 25℃-Startup Value Step 0.5℃
Temperature
Startup Time(s) — 1~1200 Step 1s
Protection
Return Time(s) — 1~1200 Step 1s
Method of Activation — Alarm+Trip+Off
THD(I)Startup Value — 8%~60% Step 0.5%
THD(I)Return Value — 8%- Startup Value Step 1%
THD(I)Startup Time(s) — 1~120 Step 1s
THD(I)Return Time(s) — 1~120 Step 1s
Harmonic Wave
THD(U)Startup Value — 4%~10% Step 1%
Protection
THD(U)Return Value — 4%- Startup Value Step 5%
THD(U)Startup Time(s) — 1~120 Step 1s
THD(U)Return Time(s) — 1~120 Step 1s
Method of Activation — Alarm+Trip+Off

16
Control Unit
Measuring Range & Accuracy

Designation Parameters Range Accuracy


≤2In±3%
Current (RMS) IA/IB/IC/IN 0~25In
>2In±5%
≤In±3.5%
Earth-fault Current Ig 0~10In
>In±5%
≤30A±3.5%
Leak Current I△n 0.5~180A
>30A±5%
Voltage (RMS) UAB/UBC/UCA 0~1000V ±3%
Active Power P -32767~32767kW ±1.5%
Reactive Power Q -32767~32767kVar ±1.5%
Apparent Power S 0~65535kVA ±1.5%
Power Factor PF -1.0~1.0 ±0.02
Input / Output Active Electric ±2.5%
EPin/EPout 0~4294967295kWh
Energy

Input /Output Reactive Electric ±2.5%


EQin/EQout 0~4294967295kVarh
Energy

Input / Output Apparent ±2.5%


ESin/ESout 0~4294967295kVAh
Electric Energy
IA/IB/IC/IN ±3.5%
Harmonic Wave 31次
UAB/UBC/UCA
Frequency f 40~65Hz ±0.05Hz

Method of Communication

Communication Protocol Modbus(default)


Communication Address 0~255
Baud Rate (bit/s) 9.6k/19.2k/38.4k/115.2k

17
Control Unit

Smart unit can be realized Modbus communication access through the Modbus communication protocol to the industrial network, to
achieve Ex9A the smart management and smart control, industrial network structure as shown:
NPower to realize intelligent power distribution system details can be call or access to intelligence, Jacques's sample distribution system.

Firewall GPRS wireless module


Realize the wireless
transmission

Internet

LAN

nServer
Ethernet
Communication server
(TCP/IP/Modbus)
View

View
GSM
Massage warning module

Modbus
Modbus

Ex9M PMA 700


PMR 700
Power parameter
Ex9A Intelligent
measurement
motor protector
instrument

18
Control Unit
Operation Overview

11 1 Control Unit Model

22 33 This indicator flashes in case of long delay fault until


2 “IR”Indicator
the deletion of fault.
44 55
During normal running, this indicator flashes all the
66 3 Running Indicator
time.
This indicator flashes in case of short delay fault until
4 “Isd”Indicator
77 the deletion of the fault.
This indicator flashes in case of a grounding fault,
“Ig or
5 neutral conductor fault, or a current leak fault until the
I△n”Indicator
deletion of the fault.
88
This indicator flashes in case of instantaneous fault
6 “Ii”Indicator
until the deletion of the fault.
99 10
10
The standard model is in white backlight and the multi-
11
11 12
12 function type is in tri-color backlight, normal operation
7 LCD
in green, the overload in yellow and the protection
13
13 activation in red.
14
14
At the current menu, move the submenu in the
15 16
16 selection box to change the position of the selection
8 “Up” Key
box upward, and perform a parameter setting “+”
17
17 at the parameter setup menu.
18
18
19
19 Shift to the default menu for the setting (on the setup
9 “Setup” Key interface, if it is necessary to move left/right, use the
20
20 21
21 “Left”key).
22
22 Exit from the current menu and return to the previous
10 “Esc” Key
menu or cancel the parameter currently set.
Shift to the default menu to be viewed (on the setup
11 “View” Key interface, if it is necessary to move leftward/rightward,
use the “Right”key).
Go to the next menu in the selection box currently
12 “Enter” Key selected. (When in the setup mode on the setup
interface, double click to exit the setup mode).
At the current menu, move the submenu in the
selection box to change the position of the selection
13 “Down” Key
box downward and perform a parameter setting: “-”
at the parameter setup menu.
The rotary knob can be used to change the trip
14 “tg”Knob
duration due to a grounding fault.
The rotary knob can be used to change the current
15 “Ig”Knob
regulation times for a grounding fault.
The rotary knob can be used to change the trip
16 “tR”Knob
duration due to a long delay fault.
8-pin Sport, used to connect with a hand-held
17 Test Port
programming or test device.
The rotary knob can be used to change the current
18 “IR”Knob
regulation times for a long delay fault.

19 “test”Knob For an instantaneous trip test.

The rotary knob can be used to change the current


20 “Isd”Knob
regulation times for a short delay fault.
The rotary knob can be used to change the current
21 “Ii”Knob
regulation times for an instantaneous fault.
The rotary knob can be used to change the trip
22 “tsd”Knob
duration due to a short delay fault.

19
Parameter
Ex9A Series Air Circuit Breaker

Ex9A Series Air Circuit Breaker Ex9A16 Ex9A32 Ex9A40 Ex9A63

(IEC / EN 60947-2, GB 14048.2)

Rated frame current (A) 1600 3200 4000 6300


Electrical performance
Number of poles (P) 3P/4P 3P/4P 3P/4P 3P/4P
Operating frequency (Hz) 50/60 50/60 50/60 50/60
Version Fixed / Withdrawable Fixed / Withdrawable Fixed / Withdrawable Withdrawable
Rated voltage Ue (V) 380/400/415/660/690
400-630-800- 1600-2000-2500- 2000-2500-2900- 4000-5000-
Rated current +40℃ In (A)
1000-1250-1600 2900-3200 3200-4000 6300
Rated insulation voltage Ui (V) 1000
Rated impulse withstand voltage Uimp (kV) 12
Type of breaking capacity N/Q Q/R/H Q/R/H V
Ultimate breaking capacity 415V 55/65 65/85/100 65/85/100 120
Icu (kA) 690V 30 50/65/75 50/65/75 85
Rated service breaking capacity 415V 75% 100% 100% 100%
Ics(100%Icu)(kA) 690V 100%
Short-time withstand current 415V 42 50/65/85 50/65/85 100
Icw (kA) 1s 690V 25 35/40/50 35/40/50 85
Rated making current Icm 415V 121 143/187/220 143/187/220 220
(kA) 690V 63 105/143/165 105/143/165 187
Breaking and closing time Breaking 20~30
(ms) Closing <60 <70 <70 <70
Arcing distance 0
Maintenance-free 12500 10000 8000 2000
Service Mechanical
Maintenance 25000 15000 15000 5000
life
(C-O) (415V) 6000 5000 3000 500
Electrical
(690V) 3000 1500 1000 500
Isolation function ■
Protection
Smart unit ■
N-pole protection capacity (only available for 4P&3P+N) □
Connection and Installation
Service category B
Installing Circuit breaker(including coil at primary side) IV
category Auxiliary circuit(except coil at primary side) III
Pollution degree 3
Connection mode Horizontal/Vertical/Hybrid
Power supply Top/Bottom
Installation mode Fixed Withdrawable Fixed Withdrawable Fixed Withdrawable Withdrawable
W(3P/4P) 254/324 282/382 424/539 437/552 424/539 437/552 835/928
External dimensions (mm) H 323 352 354 430 354 430 471
D 255 394 329 401 329 401 440
Weight 3P 22 38 52.5 98 72.5 118 200
(kg) 4P 26.5 55 66.5 121 86.5 141 230

■Standard configuration □ Optional —None

20
Parameter
Ex9ASD Series Load Switch

Ex9ASD04 Ex9ASD06 Ex9ASD08 Ex9ASD16b Ex9ASD20 Ex9ASD25


Ex9ASD Series Load Switch
Ex9ASD10 Ex9ASD12 Ex9ASD16 Ex9ASD29 Ex9ASD32 Ex9ASD40

(IEC / EN 60947-3, GB 14048.3)

Electrical performance
Number of poles (P) 3P/4P
Operating frequency (Hz) 50/60
Version Fixed / Withdrawable
Rated voltage Ue (V) 380/400/415/660/690
Rated current +40℃ In (A) 400-630-800-1000-1250-1600 1600-2000-2500-2900-3200-4000
Rated insulation voltage Ui (V) 1000
Rated impulse withstand voltage Uimp(kV) 12
Short-time withstand
400V 42 85
current Icw (kA) 1s
Rated making current
400V 105 187
(peak)Icm(kA)
Breaking and closing Breaking 20~30
time (ms) Closing <60 <70
Arcing distance 0
Service life
Electrical (415V) 6000 3000
(C-O)
Isolation function ■
Connection and Installation
Load category AC22A/AC23A
Installing category IV
Pollution degree 3
Operating frequency (cycles/h) 20
Connection mode Horizontal/Vertical/Hybrid
Power supply Top/Bottom
Installation mode Fixed Withdrawable Fixed Withdrawable
W(3P/4P) 254/324 282/382 424/539 437/552
Weight
H 322 352 354 430
(mm)
D 255 394 329 401
Weight 3P 20 36 70/84 116
(kg) 4P 24 52 116/138 138

■ Standard configuration □ Optional —None

21
Accessories
Connecting Accessories
Phase Barrier

The phase board is used to improve the insulation level between phases at
the connection of a circuit breaker.

Locking and Interlocking Component


Off-position Keylock

Keep the breaking button on a circuit breaker at its depressed state with a
Keylock, thus maintaining the circuit breaker in its breaking lock status.
One circuit breaker is provided with one lock and one key.

Two circuit breakers are provided with two locks and one key.

Three circuit breakers are provided with three locks and two keys.

Button Lock

The button stop is used to prevent the “Off” and “On” buttons against
incorrect operation and can be locked in position with a keyed lock provided.

Door Interlock

Ensures that the door is not be opened when a circuit breaker is at its operating
or test position.

Mechanical Interlock

It is used for the switchover between circuit breakers on a double-loop or multi-loop


power supply system.It is made in mechanical connections, providing high reliability.

It is made in the lever mode, suitable for two or three circuit breakers.

It is made in steel cable mode, suitable for two or three circuit breakers.

Electric Interlock

Interlock of a circuit breaker is made electrically and able to switch over au-
tomatically.

22
Accessories
Accessories for Remote Control and Signal Indication
Shunt Release (SHT)

It is used to operate a circuit breaker remotely, making the circuit breaker break off.
Actuation Characteristics.

Power Supply Voltage Us(V) AC 230V AC 400V DC 220V DC 110V


Operating Voltage (0.7~1.1) Us
Power Consumption 200VA 200W
Breaking Time 50±10ms

Closing Release (XF)


After the spring has stored energy, a circuit breaker can be closed remotely with the closing
release.
Actuation Characteristics:

Power Supply Voltage Us(V) AC 230V AC 400V DC 220V DC 110V


Actuation Voltage (0.85~1.1) Us
Power Consumption 200VA 200W
Breaking Time 50±10ms

Electric Motor (MD)


The operating mechanism can store energy on the mechanism spring immediately after
closing the circuit breaker, making sure that the circuit breaker can be closed immediately
after the next breaking.
Actuation Characteristics:

Power Supply Voltage Us(V) AC 230V AC 400V DC 220V DC 110V


Actuation Voltage (0.85~1.1) Us
Power Consumption(9A16/9A32) 75/150VA 75/150W
Energy Storage Duration <4s
Operating Frequency ≤3 cycles/min

Undervoltage Release (UVT)


It breaks off the circuit breaker when the circuit protection is at a low voltage.
The undervoltage release is provided with an instantaneous trip/delay trip function, with
trip durations selectable 0.5 s,1 s, 2 s, and 3 s. When within 1/2 delay, if the circuit voltage
restores to above 85% rated value, no trip activates.
Actuation Characteristics:

Rated Operational Voltage Ue(V) AC 230V AC 400V


Actuation Voltage (0.35~0.7) Ue
Reliable Closing Voltage (0.85~1.1) Ue
Reliable Non-closing Voltage ≤0.35Ue
Power Consumption 20VA

Auxiliary Contact (AX)


It is mounted on a circuit breaker in order to supervise the status of the corresponding
circuit breaker. Two types: 4 NOs 4 NCs and 6 NOs 6 NCs.
Actuation Characteristics:

Rated Operational Voltage Ue(V) Rated Thermal Current Powe


AC 230V
5A 300VA
AC 400V
DC 220V
0.3A 60W
DC 110V

23
Accessories
Control Unit-related Accessories
Earth leakage Transformer(WEC)

WEC: A special external transformer that corresponds with the rated current of the circuit
breaker. Each rated current corresponds to one type of transformer.

Residual mutual inductor(LEC)

LEC: A rectangular leakage transformer that corresponds with the rated current of the cir-
cuit breaker. Each rated current corresponds to one type of transformer.

Pole-N Transformer(NEC)

NEC: A transformer dedicated for usage on a 3P+N circuit breaker that is mounted on
pole-N to provide protection.

Power Module(AD)

AD:An auxiliary power supply to a smart control unit powered by double power supplies,
ensuring normal operation of the smart control unit when the corresponding circuit breaker
is off.

Power Module(M6C)

M6C:Relay the signal module is used to amplify the control unit orders signal, remote con-
trol, alarm and other functions, need to supply DC24V AD when the power supply module
used.

24
Selection
9A16、9A32、9A40 Selection Explain
Ex9A 16 N 3P 1600 D/O SU 30A AC230 OTHER

Power Special
Product Rated Breaking Poles Rated Version Smart Unit Voltage Code Require-
Code Frame Capacity Current for Control ment
Current
Circuit

N:55kA D/O:Drawer- Smart Unit No code if


16:1600A 3P:3 Poles 16: AC230:
Q:65kA (Protection of Power) no special
1600A,1250A, type (May be AC230V
requirements
32:3200A R:85kA 4P:4 Poles 1000A,800A, omitted) ① AC400:
H:100kA 630A,400A AC400V A code
SU30:Basic Type30
9A16 may choose
40:4000A N、Q② F: SU40:Basic Type40 shall be
9A32 may choose
32: Fixed SU50:Basic Type50 DC220: made timely
Q、R、H
9A40 may choose 3200A,2900A, DC220V according to
Q、R、H
2500A,2000A, SU30A:Current Type30A DC110: the
1600A SU40A:Current Type40A DC110V requirements
SU50A:Current Type50A DC24: in case
40: DC24V of special
SU30D:Voltage Type30D requirements
4000A,3200A,
SU40D:Voltage Type40D
2900A,2500A,
SU50D:Voltage Type50D
2000A
SU30P:Power Type30P
SU40P:Power Type40P
SU50P:Power Type50P

SU30H:Harmonic Wave Type30H


SU40H:Harmonic Wave Type40H
SU50H:Harmonic Wave Type50H

SU30GP:
Power Type30GP
SU30GH:Harmonic
Wave Type30GP

Example:
“Ex9A16 3P 1250 F SU40P AC230” means a circuit breaker of the Ex9A series, 1,600 housing, 3 poles,1250A, stationary-type, multi-
function electric power 4.0P control unit, and 230 V AC power voltage on the control loop.
Note①: SU30, SU40, and SU50 are new products without liquid crystal display and have basic protection function. (Time to market –fur-
ther notice)
Note②: 9A16 Qbreaking capacity type is a new product. (Time to market – further notice)

25
Selection
9A63 Selection Explain
Ex9A 63 V 3P 5000 M AC230 OTHER

Power
Product Rated Breaking Poles Rated Smart Special
Voltage Code
Code Frame Capacity Current Unit Require-
for Control
Current ment
Circuit

3P:3 Poles
① No code if
63:6300A V:120kA 63: AC230:
M:standard no special
(May be 6300A,5000A, AC230V
Type requirements
omitted) 4P:4 Poles 4000A AC400:
AC400V A code
H:multi- shall be
functionType DC220: made timely
DC220V according to
DC110: the
DC110V requirements
in case
of special
requirements

Example:

“Ex9A63 3P 5000 M AC230”means an air circuit breaker of the Ex9A series, 6300 housing, 3 poles, 5000A,
withdrawable-type, standard electric power 4.0P control unit, and 230 VAC power voltage on the control loop.

Note①:9A63 series product only have withdrawable type;6300A product only have 3P.

26
Selection
Ex9ASD Series Load Switch Selection Explain
Ex9ASD 08 3P F AC230 OTHER

9ASD Series Power


Current Poles Version Voltage Code Special
Product Require-
Level for Control
Code ment
Circuit
04:400A 3P:3 Poles D/O: AC230: No code if
withdrawable no special
06:630A AC230V
(May be omitted) requirements
08:800A 4P:4 Poles AC400:
F:fixed AC400V Optional
10:1000A accessories
Example:
W:only
12:1250A DC220: code can be
drawer seat “Ex9ASD08 3P F AC230” means a load
DC220V marked in here
16:1600A switch of the Ex9ASD series,800A, 3 poles,
B:only body DC110:
16b:1600A fixed-type,and 230 V AC power voltage on
DC110V
20:2000A the control loop.
DC24:
25:2500A DC24V
In the basis of this rule, when compiling the
29:2900A Only drawer code, functional structure space should be
32:3200A seat without
this code reserved according to the requirement for
40:4000A example.

Note:16b~40 are 32 or 40 frame product.


Ex9ASD Series Load Switch Order Specifications

Body See "Features"&"Parameters" P1-P11 Optional Accessories:


Undervoltage Release(UVT)(Optional)
Device Type Voltage: (one out of two) □ AC 230V □ AC 400V
□ Load Switch Tripping Type:(one out of five) □ Instantaneous
Time-delay □0.5s □1s □3s □5s
Rated current Auxiliary Contact(AX)
□ SD04 □ SD06 □ SD08 □ SD10 □ SD12 □ SD16 □ 6 NOs 6 NCs(optional)
□ SD16b □ SD20 □ SD25 □ SD29 □ SD32 □ SD40
Doorframe(Required,one out of two)
Number of Poles(Required,one out of two) □ Fixed(CDP) □ Withdrawable(DDP)
□ P □ 4P
Phase Partition(Optional,one out of two)
Installation Mode(Required,one out of four) □ Fixed(PHS) □ Withdrawable(DPS)
□Fixed(F) □Withdrawable □Onlydrawer seat(W) □Only body(B)
□ Position Indicator of Withdrawable Type(Optional)
Connection Mode(Required,one out of five) □ Switch-in Readiness Contact Point(PF)(Optional)
□Front Connection(only for Ex9A32) □Vertical Connection Key Lock(KLK)(Optional,one out of three)
□Horizontal Connection□Hybrid Connection(with connection mode indicated) □ one set: one lock and one key □ two sets: two locks and
one key □ three sets: three locks and two keys
□Extended busbar(TEX)(Only Ex9A16 can be chose)
□ Door Interlock(VPEC)(Optional)
□ Button Lock(VBP)(Optional)
Accessorie See catalogue "Accessories" P22-P24
Machanical Interlock(Optional,one out of two)
Linkage(MIT) □ Two sets
Standard Accessories: Steel Cable(IPA) □ Two sets
Electric Motor (MD) Auto Power Converter Controller (Optional)
□ Automatic switch and automatic reset (R-type)
□ AC 400V □ AC 230V □ DC 220V □ DC 110V
□ Automatic switch and non-automatic reset (S-type)
Shunt Release(SHT) □ Mutual Alternate(I-type) Note:Standard Auto power converter controller standard:
□ AC 400V □ AC 230V □ DC 220V □ DC 110V Switch Control Unit SU601、Machenical interlock IPA、2 Adapter ADP、Cable 2 meters.

Closing Release(XF)
□ AC 400V □ AC 230V □ DC 220V □ DC 110V
Remarks
Auxiliary Contact(AX)
□ 4 NOs 4 NCs(required)

Note:SD series load switch are new product,time to market further notice,is expected to for August 30.

27
9A16、9A32、9A40 Order Specifications

Body See "Features"&"Parameters" P1-P11 Accessorie See catalogue "Accessories"P22-P24

Device Type
□ Circuit Breaker Standard Accessories:
Frame&Current Electric Motor (MD)(Required,one out of five)
Ex9A16 Ex9A32 Ex9A40 □ AC 230V □ AC 400V □ DC 220V □ DC 110V □ DC 24V
□ 400A □ 1600A □ 2000A
□ 630A □ 2000A □ 2500A Closing Release(XF)(Required,one out of five)
□ 800A □ 2500A □ 2900A □ AC 230V □ AC 400V □ DC 220V □ DC 110V □ DC 24V
□ 1000A □ 2900A □ 3200A
Shunt Release(SHT)(Required,one out of five)
□ 1250A □ 3200A □ 4000A
□ AC 230V □ AC 400V □ DC 220V □ DC 110V □ DC 24V
□ 1600A
Auxiliary Contact(AX)
Breaking Capacity (Required,one out of four)
□ 4 NOs 4 NCs(required)
□ N:55kA □ Q:65kA □ R:85kA □ H:100kA
Note:Ex9A16 breaking capacity can choose now,Ex9A32/40 have three kinds of Q/R/H. Optional Accessories:
Ex9A16 Q breaking capacity type is new product,time to market further notice.
Undervoltage Release(UVT)(Optional)
Number of Poles(Required,one out of two) Voltage:(one out of two) □ AC 230V □ AC 400V
□ 3P □ 4P Tripping Type:(one out of five) □ Instantaneous
Installation Mode(Required,one out of two) □ Time-delay :□ 0.5s □ 1s □ 3s □ 5s
□ Fixed(F) □ Withdrawable Auxiliary Contact(AX)
□ 6 NOs 6 NCs(optional)
Connection Mode(Required,one out of five)
□ Front Connection(only for Ex9A32) □ Vertical Connection Doorframe(Required,one out of two)
□ Horizontal Connection □ Hybrid Connection(with connection mode indicated) □ Fixed(CDP) □ Withdrawable(DDP)

□ Extended busbar(TEX)(Only Ex9A16 can be chose) Phase Partition(Optional,one out of two)


□ Fixed(PHS) □ Withdrawable(DPS)
□ Position indicator of withdrawable type(Optional)
□ Switch-in Readiness Contact Point(PF)(Optional)
See catalogue "Control Unit"P12-P19 Key Lock(KLK)(Optional,one out of three)
Control Unit (Only to be filled out by the circuit breaker user) □ one set: one lock and one key
□ two sets: two locks and one key
Model of Control Unit(Required,one out of seventeen) □ three sets: three locks and two keys
Protection of Power Distribution and Electric Motor Protection of Generator
□ Door Interlock(VPEC)(Optional)
Basic Type Current Type Voltage Type Energy Type
(Basic (Standard (Advanced (Advanced
Harmonic Wave Type
EnergyType
(Advanced
Harmonic
WaveType
□ Button Lock(VBP)(Optional)
(Advanced Type)
Three-section Type) Type) Type) Type) Type) (Advanced Type)
Protection Machanical Interlock(Optional,one out of two)
□3.0 □3.0A □3.0D □3.0P □3.0H □3.0GP □3.0GH
Racking interlock(MIT) □ Two sets
Three-section
□4.0 □4.0A □4.0D □4.0P □4.0H — — Steel Cable(IPA) □ Two sets
+Grounding Protection
Three-section
□5.0 □5.0A □5.0D □5.0P □5.0H — —
Auto Power Converter Controller(Optional)
+Leakage Protection
□ Automatic switch and automatic reset (R-type)
□ Automatic switch and non-automatic reset (S-type)
Auxiliary voltage for smart unit(Required,one out of five) □ Mutual Alternate(I-type)
□ AC 230V □ AC 400V □ DC 24V □ DC 220V Note:Automatic switching power system with standard supporting accessorie:Switch Control Unit
□ DC 110V Note:AD Power module should be chosen if use DC110/220V SU601、Machenical interlock IPA、2 Adapter ADP、Cable 2 meters.

Additional function(multi choice is allowed,for additional charge)


Neutral Pole Protection
□ 3P+N
With N pole transformer(NEC)
□ earth-current
With earth-current transformer((WEC)
Remarks
Signalling output unit: □ 4DO(without ZSI) □ 4DO+2DI(with ZSI)
□ ZSI note:this part should be used with OS2

Measurement of Demand Value□ current(CDS)(only for standard type)


□ current+power(PCS)(only for advanced type)

Protection of Demand Value □ current(CDP)

Communication(COM)(only for advanced type) □ Modbus


note:If it takes another to achieve remote control need for adding AD and M6C。

Power Module(AD)(Optional,one out of four)


□ AC 230V □ AC 400V □ DC 220V □ DC 110V
□ M6C Relay Signal Module(M6C)(Optional)

28
9A63 Order Specifications

Body See "Features"&"Parameters" P1-P11

Device Type
□ Circuit Breaker Key Lock(KLK)
□ one set: one lock and one key
Frame&Current
□ two sets: two locks and one key
Ex9A63 □ three sets: three locks and two keys
□ 4000A
□ 5000A Machanical Interlock
□ 6300A □ Steel Cable(IPA 14) □ Racking(MIT 14)
Breaking Capacity □ V:120kA Auxiliary Contact
Number of Poles(Required,one out of two) □ 6 NOs 6 NCs(AX 14)
□ 3P □ 4P Power Module(AD)
□ AC400V □ AC230V □ DC220V □ DC110V
Installation Mode □ Withdrawable
□ M6C Relay Signal Module(M6C)
Connection Mode(Required,one out of four)
□ Front Connection □ Vertical Connection □ Doorframe(DDP)
□ Horizontal Connection □ Hybrid Connection
□ Button Lock(VBP)
□ Phase Barrier(DPS)

See the user manual 9A63 □ Flap Position Lock(FL)


Control Unit (Only to be filled out by the circuit breaker user)
□ Door Interlock(VPEC)

Model of Control Unit(Required) □ Withdrawable Position Lock(EF)


□ Standard Type(M)
□ Multi-function Type(H)
H-type communication function with standard,still can add
choose the following functions:□P function □H function
Note:"H" in multi-function and "H" in can add choose function meaning different,often
put "H" in multi-function as H-type control unit,and add choose function H for H function,
please distinguish.
Control Unit Auxiliary Working Voltage(Required,one out of five)
□ AC 230V □ AC 400V □ DC 24V □ DC 220V □ DC 110V
Note:Choose DC 220V、DC 110V voltage should be chosen AD power supply module.
Remarks
Multi-function type(H-type) additional choice function explain
P function include:Voltage Measurement、Voltage Unbalance Measurement、Freq.
Measurement、Phase Sequence Detection、Power Measurement、Power Factor Me-
asurement、Load Monitoring Function、Signal Output UnitUnit 、Signal Input Unit、
Zone Selective Interlock、Undervoltage Protection、Overvoltage Protection.
H function include:Voltage Measurement、Voltage Unbalance Measurement、Freq.
Measurement、Phase Sequence Detection、Power Measurement、Power Factor Me-
asurement、Load Monitoring Function、Signal Output UnitUnit 、Signal Input Unit、
Zone Selective Interlock、Undervoltage Protection、Overvoltage Protection、Harm-
onic Wave Detection、Neutral Conductor Protection.

Accessorie See catalogue "Accessories"P22-P24

Standard Accessories:
Electric Motor (MD)
□ AC 400V □ AC 230V □ DC 220V □ DC 110V

Shunt Release(SHT)
□ AC 400V □ AC 230V □ DC 220V □ DC 110V
Closing Release(XF)
□ AC 400V □ AC 230V □ DC 220V □ DC 110V
Auxiliary Contact(AX)
□ 4 NOs 4 NCs

Optional Accessories:
Undervoltage Release (UVT 14)
□ Instantaneous □ Time-delays(provide 0.5-1-3-5s,optional adjustable )
□ AC 400V □ AC 230V

29