You are on page 1of 28

conventional detector to limit the current draw

in alarm. Resistors fitted into the


detection line
fault monitoring
system detector base are also used in
Standard conventional systems are

operation
some cases to distinguish between
able to monitor the zone for short
a short circuit fault and an alarm. circuit, open circuit and detector
The value of the base resistor is head removal.
detection line operation dependant on the control panel,
Conventional detection systems however a typical value is 470 When a short circuit occurs on a
normally operate on a 24VDC line. Ohms. If in any doubt, contact the zone, a high current will be drawn,
In the standby condition, the control panel manufacturer who and the line voltage will be pulled
detectors will draw a low current, should be able to specify which towards zero volts. The panel
typically less than 100µA. When the detector bases should be used detects the low voltage / high
detector senses a fire, it will switch with different detector brands. current and a fault is signalled.
into the alarm condition with it's
LED illuminated, and will collapse A manual call-point consists of a In order to detect an open circuit, or
the line voltage by drawing a larger simple switch with a resistor in detector head removal, a device is
current - dependant on the series with it, usually 470 Ohms or connected across the end of the
detectors and control panel, but 680 Ohms. When the call point is zone, which can be monitored.
typically 50-80mA. The control activated, the resistor is switched This device can take various forms
panel can sense this, and activate across the line, and a current of dependant on the control panel.
the appropriate alarms. The 50-80mA, dependant on the
detector will remain latched in the control panel, is drawn.
alarm state with its LEDs
illuminated, even if the smoke or
heat is removed until it has been
reset from the panel by momentarily +24V
removing power from the line.
This allows the fire to be located
even if the signal is intermittent, or
to locate possible sources of

Resistor
Contact Closed
nuisance alarms.
when detector
inserted in base
For some control panel - detector
combinations, when a standard
base is used, there is an
incompatibility between the current
specifications of the detector and
panel, leading to incorrect reporting
by the control panel, for example
signalling a fault in place of an 0V
alarm, and in some cases damage
to the detector due to over current Figure 2: Resistive end of line operation
in the alarm state. In these cases it
is necessary to use a base fitted
with a resistor in series with the

5
The simplest end of line device is removed detector, it will no longer head is removed, the diode is
a resistor, which will draw a current work, which contravenes the connected across the contact,
distinct from the quiescent and requirements of BS5839 part 1. To allowing power to continue to be
alarm currents drawn by the overcome this either all call points supplied to the remainder of the
detectors. Installation of detectors must be mounted at the start of zone, whilst still permitting the
into their bases closes a contact in each zone, or in completely removed detector to be monitored.
the base supplying the remainder of separate zones (both of these This is achieved in a number
the zone. Thus if the line is broken, solutions are often impractical and of ways.
or if a detector head is removed, too costly), or head removal
the current drawn by the zone will monitoring can be employed. An active end of line device uses a
fall, and a fault will be signalled switched resistor at the end of line
(See figure 2). Example zone current Active monitoring uses bases fitted and can thus be used with a
and voltage figures are with a diode across the contact in standard control panel. It sends a
given in figure 3. the base (fig 4). Whilst the detector periodic signal back along the
detection line, which is normally
quenched by the control panel.
Monitoring of detection line When a head is removed, the base
(example only) diode is switched into the line, and
Co n d i t i o n Cu r r en t Vo l t ag e pulse can be seen. The Active end
of line then switches the resistor out
Op en Ci r c u i t <3m A 24V
of the line, and a fault is signalled.
Normal 5mA (dependant on EOL device) 18V
Fire 50mA (dependant on control panel) 4-15V If a capacitive end of line is used,
Short Circuit High (dependant on control panel) the panel periodically drops the line
0V
voltage for a few milliseconds, and
Figure 3: Example resistive conventional system current and voltage figures
looks for the line voltage being held
up by the capacitor. When a head is
The problem with a simple resistive is mounted in the base, the base removed, the panel will see the line
end of line is that should a detector contact connects directly across the voltage drop immediately as the
head be removed, the remainder of diode, and links it out. There is capacitor's discharge will be
the zone beyond that detector is usually provision for manually inhibited by the diode, and thereby
lost and no alarm can be signalled linking the diode out to permit a fault can be signalled.
beyond this point. Should a call continuity testing during
point be mounted beyond the commissioning. When the detector A third type of end of line device is
a diode. With this the panel
+24V periodically reverses the line voltage
for a few milliseconds: If the line is
broken by the diode in the detector
base, then no current can flow in
E.O.L.

the reverse direction.

The type of end of line monitoring


used on a system will depend
Contact Closes
when detector on the control panel. However it
0V inserted in base is important, particularly when
Figure 4: Active end of line monitoring circuit using active end of line monitoring

6
to ensure that the detectors wires, see figure 5. In this instance, relay contacts are wired in series
are compatible with the type a base incorporating a change over with the normally closed contacts of
of monitoring being used. relay is used. This configuration is the detector relay base(s). Thus in
Reference must be made to known as a four-wir e system, and is the normal state the detection
the panel manufacturer to often seen when a fire zone is circuit is closed; in the case of fire
ensure compatibility. integrated into a security panel. or power failure the relevant relay
contacts will open.
Figure 5 shows the simplest form of
remote LEDs four-wire system, as used with most Normally after an alarm, the
Most system smoke detectors are security panels. This is used where detectors are reset by disconnecting
equipped with a terminal to allow the monitor line is able only to the power to the relevant zone for a
the connection of a remote LED. register an open or closed circuit - short period by pressing a central
Remote LEDs are often used there is no distinction between a panel reset button. Fire panels have
outside bedroom doors in hotels so fault and a fire. By using a normally this facility built in, however many
that in case of a fire, it is easy for closed relay at the end of the power security panels are unable to do this
the fire brigade to identify the line, it is possible to monitor for a without turning the entire panel off.
location of the fire without needing power failure to the detectors. The Therefore to allow the use of
to enter every room in the building.
They may also be used where a - 24VDC
+ 24VDC
POWER SUPPLY
END OF LINE
RELAY COIL

detector is located in a hidden


position, such as a floor or roof void
+24VDC IN

+24VDC IN
- 24VDC OUT

- 24VDC OUT
- 24VDC IN

- 24VDC IN
+ 24VDC OUT

+ 24VDC OUT
or cable tunnel, for example, to
provide a visual indication that the B EA M DETECTOR #1 B EA M DETECTOR #2
MAINTENANCE

MAINTENANCE
detector is in an alarm state.
RELAY (N/O)

RELAY (N/O)
RELAY (N/C)

RELAY (N/C)
RELAY (N/C)

RELAY (N/C)
ALARM

ALARM
FAULT

FAULT
four-wire system operation
In some cases it is necessary that
the power to the detectors and the
Resistor

Resistor

EOL
DETECTION CIRCUIT
fire detection signal be on separate

Figure 6: 4-wire system with full monitoring

detectors with security panels,


non-latching versions of the relay
Detection Line bases are usually made available,
(Open Circuit for
Alarm and Fault)
which automatically isolate the
FIRE detector from the supply every few
ALARM seconds. Thus once the fire
CONTROL
PANEL End of Line condition has passed the detector
Monitoring Relay

C NO NC C NO NC
will automatically reset (note that
Power Supply
(Nominal 12V
or 24V System)
the alarm condition should be
latched at the control panel.)

Four-wire type systems are also


often used with devices such as
Figure 5: Typical 4 wire system wiring
beam detectors where an auxiliary

7
27982.01_ConfFldrs:27982.01_ConfFldrs 2/12/08 10:46 Page 39

You might also like