Professional Documents
Culture Documents
140
120
100
Vertical Reach (Feet)
80
60
40
20
0
0 20 40 60 80 100 120 140 160 180 200 220 240
Horizontal Reach (Feet)
32 Deg Angle Above Horizontal 55 Deg Angle Above Horizontal 75 Deg Angle Above Horizontal
NOTE: All data provided in this chart is an engineering estimate and is provided for reference only. Chart depicts flow
rate of 1000 GPM @ 100 PSI nozzle pressure. Actual stream performance is affected by proportioning rate,
environmental conditions and fire water supply conditions at the site. All fire protection systems should be tested after
installation to verify installed water delivery reach and loft.
Elkhart Brass Mfg. Co., Inc. 1302 W. Beardsley Avenue • Elkhart, Indiana 46514 • 1-574-295-8330 • 1-800-346-0250
www.elkhartbrass.com
SM-1000-HF
Select-O-Matic Hydro-Foam Nozzle
350 – 1000 GPM Rated Flow
Narrow Spray Angle @ Elevations of 32, 55 & 75 Degrees
100 PSI (7 bar) Nozzle Pressure
80
70
60
Vertical Reach (Feet)
50
40
30
20
10
0
0 20 40 60 80 100 120 140
Horizontal Reach (Feet)
32 Deg Angle Above Horizontal 55 Deg Angle Above Horizontal 75 Deg Angle Above Horizontal
NOTE: All data provided in this chart is an engineering estimate and is provided for reference only. Chart depicts flow
rate of 1000 GPM @ 100 PSI nozzle pressure. Actual stream performance is affected by proportioning rate,
environmental conditions and fire water supply conditions at the site. All fire protection systems should be tested after
installation to verify installed water delivery reach and loft.
Elkhart Brass Mfg. Co., Inc. 1302 W. Beardsley Avenue • Elkhart, Indiana 46514 • 1-574-295-8330 • 1-800-346-0250
www.elkhartbrass.com
SM-1000-HF
Select-O-Matic Hydro-Foam Nozzle
350 - 1000 GPM Rated Flow
Wide Spray Angle @ Elevations of 32, 55 & 75 Degrees
100 PSI (7 bar) Nozzle Pressure
50
45
40
35
Vertical Reach (Feet)
30
25
20
15
10
0
0 10 20 30 40 50 60 70 80 90
Horizontal Reach (Feet)
32 Deg Angle Above Horizontal 55 Deg Angle Above Horizontal 75 Deg Angle Above Horizontal
NOTE: All data provided in this chart is an engineering estimate and is provided for reference only. Chart depicts flow
rate of 1000 GPM @ 100 PSI nozzle pressure. Actual stream performance is affected by proportioning rate,
environmental conditions and fire water supply conditions at the site. All fire protection systems should be tested after
installation to verify installed water delivery reach and loft.
Elkhart Brass Mfg. Co., Inc. 1302 W. Beardsley Avenue • Elkhart, Indiana 46514 • 1-574-295-8330 • 1-800-346-0250
www.elkhartbrass.com