You are on page 1of 10

International Journal of Refrigeration 29 (2006) 789–798

www.elsevier.com/locate/ijrefrig

Performance of a domestic refrigerator under influence


of varied expansion device capacity,
refrigerant charge and ambient temperature
Erik Björk*, Björn Palm
Department of Energy Technology, Royal Institute of Technology, SE 100 44 Stockholm, Sweden
Received 19 September 2005; received in revised form 18 November 2005; accepted 22 November 2005
Available online 13 March 2006

Abstract

This paper reports experimental results of an on/off cycling domestic refrigerator at varied expansion device capacity (EDC),
quantity of charge and ambient temperature. It was found that the energy consumption is insensitive to varied EDC and charge
within a wide range of settings. For the charge this is explained by the low side accumulator, which buffers over- and
undercharge. It was also found that the optimum charge increased at lower ambient temperature. The paper describes an
experimental procedure on how to determine the capillary tube length and the quantity of charge for a domestic
refrigerator/freezer. This procedure is recommended since it takes different thermal masses and loads into consideration and
since the potential for energy saving with a more sophisticated method appears to be limited.
q 2005 Elsevier Ltd and IIR. All rights reserved.

Keywords: Domestic refrigerator; Experiment; Performance; Parameter; Thermostatic expansion device; Refrigerant charge; Temperature

Performance d’un réfrigérateur domestique muni d’un détendeur à


capacité variable, selon la charge en frigorigène et la température
ambiante
Mots clés : Réfrigérateur domestique ; Expérimentation ; Performance ; Paramètre ; Détendeur thermostatique ; Charge en frigorigène ;
Température

1. Introduction important for devices produced in large numbers, such as


domestic refrigerators and freezers. These refrigeration
Recent energy price increases have once again put units are typically characterized by low cooling capacities
energy efficiency into focus. This topic is particularly (50–250 W), low quantities of charge (20–200 g), an
accumulator positioned at the evaporator outlet, a herme-
tically sealed cooling system, a capillary tube expansion
* Corresponding author. Tel.: C46 86 546449; fax: C46 82
device which is in heat exchange with the suction line, and a
03007.
E-mail address: bjork@energy.kth.se (E. Björk). cooling capacity control by intermittent run.

0140-7007/$35.00 q 2005 Elsevier Ltd and IIR. All rights reserved.


doi:10.1016/j.ijrefrig.2005.11.008
790 E. Björk, B. Palm / International Journal of Refrigeration 29 (2006) 789–798

Several research papers have provided information about 1.3. A simple method to determine the capillary tube length
the characteristics of such cooling systems [1–11]. Attempts and the quantity of charge
to simulate their behaviour are reported in [12–16]. The
capillary tube expansion device is investigated at adiabatic One method [29], based on trial and error, which is
[17–20] and diabatic [21–26] conditions. Experimental employed at a major manufacturer to find this optimum is
charge inventories are reported in [10,11,27,28]. outlined below. It is exemplified for climate class N [30] or
temperate conditions. First, the cabinet is arranged
1.1. The on/off cycling according to ISO7371 [30] conditions.

The most common way to control the cooling capacity in (1) The capillary tube dimension is determined in pull
domestic refrigerators and freezers is by intermittent run or down experiments (start-up from cabinet initially at
cycling control. The compressor starts as a preset ambient temperature) at 25 8C during which the
temperature in the refrigerated space is exceeded (cut-in evaporator dry-out point (position in evaporator where
temperature) and shuts down as a low temperature (cut-out superheat starts) must reach the low side accumulator
temperature) is reached. A typical course of events at inlet position within 30 min. In this experiment the
compressor start and stop is as follows: at the moment charge is guessed.
before the compressor starts, the evaporator is at its highest (2) The charge is determined during continuous running
temperature. Most refrigerant, by mass, is accumulated in steady state conditions at 32 8C ambient temperature. In
the evaporator and compressor whereas the condenser and this condition the dry-out point must just reach the
the capillary tube contain only superheated gas. As the accumulator inlet. Then, this charge is tested at
compressor starts, the initial compressor mass flow is high continuous running steady state conditions at 25 8C
(high evaporation pressure) whereas the capillary tube mass ambient temperature. In this condition the suction line
flow is low (superheated gas). The result is that refrigerant is downstream the capillary tube heat exchanger must not
displaced towards the condenser. The evaporator becomes be cold (i.e. part of suction line close to compressor).
more or less starved with any remaining refrigerant liquid In case the latter condition is unattainable, the
held up in the accumulator. After a short while a liquid layer accumulator volume is too small for the given
is formed at the condenser outlet and the evaporator starts to configuration.
refill with refrigerant liquid. That is, the dry-out point (3) The capillary tube dimension and amount of charge are
(position in evaporator where superheat starts) moves verified at on/off cycling conditions at 25 8C ambient
downstream thus gradually ‘activating’ the heat exchanger. temperature and 5 8C average cabinet air temperature.
This refilling process is somewhat accelerated as liquid, In this test, the evaporator dry-out point should reach
backed up in the condenser following the start-up, subcools the accumulator inlet within 1–2 min (depending on
and increases the capillary tube mass flow. It is important evaporator size) after a compressor start. If this
that this refilling process is short in comparison to the entire condition is unattainable the capillary tube should be
compressor on-period. shortened.
As the compressor stops, the pressure equalises within
the system. The condenser pressure decreases and slowly Note that the minimum length of the capillary tube was
approaches the saturation pressure in the evaporator while selected only to ensure the system operation. A condenser
refrigerant is pushed into the evaporator. subcooling was not a required condition in the outlined
These charge displacements at start-up and shut-down method.
affects the performance negatively. Totally, efficiency Why is then the outlined procedure used instead of a
losses of 5–37% are reported [4,7,13] due to these more scientific approach based on correlations for void
phenomena. fraction and capillary tube mass flow? The answer probably
lies in the complexity of the problem. For the capillary tube,
not only the influence of the suction line heat exchanger
1.2. Capillary tube capacity and quantity of charge
must be included but also the transient conditions with
varied inlet conditions. For the void fraction, correlations
A central issue in the development process of domestic
are yet not available for the internal geometries that are
refrigerators/freezers is to find the right capillary tube
capacity (combination of capillary tube length and diameter) common in domestic refrigerators and freezers (vertical
bends, odd cross section shapes and low side accumulator).
and quantity of charge. This should be done in such a way
that the lowest possible energy consumption is obtained
while other required performances are fulfilled. Whether 1.4. Reported work with relevance to the current study
this optimum is found is often questioned. Normally, these
parameters are determined experimentally at a late stage in For steady state conditions at a component level, the
the development process after the cabinet, heat exchangers ASHRAE handbook [31] suggests an experimental method
and compressor have been selected. to help selecting the capillary tube length. A separate test
E. Björk, B. Palm / International Journal of Refrigeration 29 (2006) 789–798 791

setup is described to find the capacity balance (combination knowledge of these authors no experimental studies have
of condensation and evaporation pressures that ensures a been conducted and published for on/off cycling systems
saturated liquid condition at the capillary tube inlet for a even though this method for capacity control is the most
given capillary tube length and compressor). However, even common in domestic refrigeration. It is the purpose of the
if this characteristic is known, and is used at an early stage of present paper to fill this gap. In particular, it is interesting to
the development process to size the cooling system, it is in detail explore the nature of the energy minimum, which
doubtful whether this condition can be maintained for more many engineers intuitively believe exists, for certain
than one steady state condition. The same source [31] also combinations of the EDC and the quantity of charge.
suggests an experimental method that can be used on an
existing system to find the optimum charge: An external
bottle (valved off and sitting on a scale) is heated or cooled
2. Methods and material
to vary the system charge.
Dmitriyev and Pisarenko [32] suggest a simple corre-
In order to investigate the energy consumption of a
lation to calculate the optimum charge in a domestic
domestic refrigerator at varied refrigerant charges and EDC
refrigerator in which the evaporator and condenser internal
a refrigerator was modified so that these parameters could be
volumes are the only parameters. They found that the COP
varied. The experimental setup was fully computer
was more sensitive to over than undercharging. They also
controlled. Hence, no manual intervention was needed
found that the optimum charge was independent of the
during an experimental run.
ambient temperature. Kuijpers et al. [12] theoretically
studied the influence of charge and capillary tube capacity
on the performance of a domestic freezer at varied operating 2.1. The test object
conditions. They found that the required system charge
(to obtain a small 0.1 K superheat) was less sensitive to The test object was an Electrolux ER8893C, single door
variations in the ambient temperature if a high capillary tube and single compartment domestic refrigerator with the
capacity was selected. Moreover, they pointed out that a following data:
high capillary tube capacity would result in a faster build-up
† Cabinet: (1.75!0.6!0.6 m3), 350 l internal volume,
of the liquid layer in the evaporator after a compressor start-
UA value 2.3 W/K. Declared energy consumption
up. Jakobsen [13] simulated varied capillary tube capacities
0.68 kW h/24 h. Energy class B.
and quantities of charge during steady state conditions for a
† Evaporator: free convection, (0.66!0.49!0.0014 m3),
domestic refrigerator. He found that the efficiency was more
aluminium, plate type, back wall positioned (20 mm
sensitive to a too low charge and a too low capillary tube
distance to wall), integrated downstream positioned
capacity than the opposite.
accumulator. Refrigerant line length (including accu-
mulator) 6.02 m. Internal hydraulic diameter 3.2 mm.
1.5. Motivation for this work Total internal volume 114 ml whereof accumulator
volume 46 ml in which approximately half the volume
It is well known from experiments and theoretical studies can store liquid at steady state condition. UA value
that a vapour compression cooling machine, at steady state 3.7 W/K.
conditions, has its highest efficiency for a certain expansion † Condenser: free convection, (1.33!0.51!0.008 m3),
device capacity and quantity of charge [33]. However, to the steel, wire on tube (53 vertical wires on each side of the

Fig. 1. Experimental apparatus (suction line heat exchanger not shown).


792 E. Björk, B. Palm / International Journal of Refrigeration 29 (2006) 789–798

Fig. 2. Cooling system with thermocouples position.

tubing, each of diameter 1.5 mm) positioned with 25 mm positions, connection pipes were kept short and with
distance to the cabinet back wall. The refrigerant flow is internal diameters close to the original system. As a
horizontally downward. Internal volume 135 ml. Inter- result, the behaviour of the modified system was close
nal/external tube diameter 3.5/5.0 mm. UA value to the behaviour of the original system. For example,
7.7 W/K. the cycle length, compressor-on and compressor-off
† Capillary tube expansion device (2.54 m length and time differed with less than 5% to the unmodified
0.6 mm internal diameter) with coaxial type suction line system at nominal charge.
heat exchanger of 2 m length. The capillary tube The adiabatic inlet part of the capillary tube (0.5 m
adiabatic inlet and outlet section is 0.5 and 0.04 m. between the filter drier and the suction line heat
† Filter drier: molecular sieve with internal free volume exchanger) was replaced by a step motor actuated needle
11.3 ml. valve (Swagelok L series). By this, the EDC could be
† Piston compressor (ZEM HQY75AA) with low pressure varied with settings higher and lower than the original
oil sump and 265 ml mineral oil charge. Cooling configuration. The total length of the remaining capillary
capacity 118 W and COP 1.49 at ASHRAE conditions
tube was 2.04 m including the 0.04 m adiabatic outlet
(55/K23.3 8C).
section.
† Refrigerant: nominal refrigerant charge 33 g of Iso-
A refrigerant tank was connected to the service line of
butane (R600a).
the compressor via a remotely controlled solenoid valve
† Capacity control by intermittent run (on/off cycling)
(Honeywell MC062). The tank, in turn was sitting on a scale
with self-defrosting in every off-period.
(Witre PV500) connected to a data logger. Through this
arrangement a measured quantity of refrigerant could
2.2. Modifications of test object be added to the cooling system. An electric energy meter
(Enermet Y120E), also connected to the data logger,
A drawing of the modified system is shown in enabled the compressor energy consumption to be
Figs. 1 and 2. Overall, small changes were made to the measured. Thermocouples (T-type) were attached at
original system. All components were at original different positions of the cooling system.
E. Björk, B. Palm / International Journal of Refrigeration 29 (2006) 789–798 793

2.3. Information exchange 2.6. Experimental procedure

A computer with software (developed in HP-VEE) Prior to each experimental run the system was carefully
controlled the compressor, the solenoid valve to the evacuated and charged to the lowest quantity that enabled
refrigerant tank, and the step motor actuated needle valve the system to operate at on/off cycling condition at the given
via a relay box (Utronix SwitchBox44) and a step motor cut-out temperature. The configurations to be tested were
controller (Basic stamp II BOE). The data from the entered into the program. After this the experimental
thermocouples, the scale, and the energy meter was apparatus was autonomous. An experimental run started
transferred via a data logger (HP 34970A) to the computer with 20 on/off cycles at the highest EDC (most open valve
where it was recorded for later analysis. setting) to reach steady cycling conditions. Then, the energy
consumption was measured for one complete on/off cycle.
2.4. Expansion device capacity (EDC) Next, the throttling valve was closed stepwise. For each
step, the energy consumption was measured for one on/off
The EDC is presented as the nitrogen vapour flow at the cycle. This was repeated until either the pre set most closed
outlet through the combined needle valve-capillary tube valve opening (lowest EDC) was reached or the cut-out
section, as measured in a separate experiment. In this temperature was unattainable. After this the throttling valve
experiment nitrogen was allowed to expand from 6 bar to was reset to its most open setting, more refrigerant was
atmospheric pressure at normal room temperature. The added, and five on/off cycles were completed (again to reach
original capillary tube capacity measured in this way was steady cycling conditions) before the stepwise valve
2.8 (l N2/min). However, since this capacity is measured closing-energy measurement process was repeated. The
solely with a capillary tube it cannot be directly compared to experimental run was stopped as the desired upper limit of
the EDC presented in this study (which also includes a charge was reached.
needle valve). Because of different flow conditions, at the
same Nitrogen capacity, the two-phase refrigerant flow
through the 0.5 m adiabatic capillary tube (that was 3. Results
removed for the test) is not necessarily the same as through
the needle valve. A total of almost 600 measurements were recorded at
different combinations of charges, EDC and ambient
temperatures. For each ambient temperature (16, 25,
2.5. Experimental conditions, data reduction
31 8C), the results are displayed in a contour map (Figs. 3
and uncertainty estimation
and 4) with the EDC/valve opening on the longitudinal axis
and the quantity of charge on the lateral axis. For the valve
The experimental apparatus was arranged according to
opening, a value of 0.25 (left side of maps) means a quarter
ISO 7371 [30] conditions at three different ambient
temperatures: 16, 25, and 31 8C. Note that, due to limitations
in the experimental facilities, the highest temperature
(31 8C) was one degree lower than what is stipulated by
the ISO 7371 standard.
The cabinet air temperature (averaged over two
positions) was controlled to approximately 5 8C with
cut-out and cut-in temperatures set to 4 and 6 8C,
respectively, (uncertainty in cut-in cut-out temperature
difference G0.1 K). The tested charges and capillary tube
capacities are provided in Table 1. The energy consump-
tion, measured over one on/off cycle, was recalculated to
energy consumption in kW h per 24 h. The estimated
uncertainties (UZ95%) in the presented results are:
energy consumption G5%, EDC G5%, charge G0.5 g
and temperatures G1 8C.

Table 1
Experimental condition

Experimental run 1 2 3
Ambient temperature (8C) 16 25 31
EDC (l N2/min) 0.15–3.1 0.15–3.1 0.15–3.1
Charge (g) 22–50 23–40 22–42
Fig. 3. Energy consumption at ambient temperature 25 8C.
794 E. Björk, B. Palm / International Journal of Refrigeration 29 (2006) 789–798

50 charge is higher in the 16 8C experiment (z38 g) compared to


16°C 48 the 25 and 31 8C experiment (z31 g). In other words, the
46 optimum charge increases with lower ambient temperatures.
44 Tables 2–4 show relevant cycle data, representing the
42
42 corners, the centre and the centre of the sides of the contour
40 31 °C 40
maps from the 16, 25 and 31 8C experiments. Reading from
38
Table 2’s first line, for instance, it is seen that a 22 g charge
charge (g)
0.25-0.30 kWh/24h 38
36
36 and a 3.06 l N2/min EDC give an energy consumption of

charge (g)
34 34 0.39 kW h/24 h, a relative compressor on-time of 23% and a
32 32 total cycle length of 2918 s. The next column (evaporator
1.00-1.05 kWh/24h
0.30-0.35 30 30 activation time) shows the time for the dry-out point to reach
28 28 the accumulator inlet after a compressor start. In this case it
26 26 was not available, meaning that the dry-out point never
0.35-0.40
24 24 reached the accumulator. The six last columns show
22 22 temperatures averaged over the compressor on-period. The
2.4 [9.2
2.7
2.9 [15.2
3.0 [18.2
0.1
0.8 [0.25
1.4 [3.25
2.0 [6.25

2.4 [9.25
2.7 12.2
2.9 [15.2
3.0 [18.2
0.1
0.8 [0.25
1.4 [3.25
2.0 [6.25

temperature drop over the needle valve, which in this case is


1/
3 / .25]
5/
6/
5/
7/
8/
0/

1/
3/
5/
6/
5/
7/
8/
0/

2.6 K, enables future validation by simulation models. The


[

[21 ]

[21
[
1 2

.25

.25
evaporator, the condenser and the suction line temperatures
5]

5]
5
]
]
]

5]
5]
5]
]
]
]
]
]

EDC (l N2/min) / EDC (l N2/min) / are K18.2, 29.6 and 21.9 8C, respectively. The superheat
[Valveopening (-)] [Valveopening (-)] and subcooling (calculated for the evaporator as the
difference between evaporator out and evaporator in and
Fig. 4. Energy consumption at ambient temperatures 16 and 31 8C.
for the condenser as the temperature difference between
of a turn from a fully closed valve. The irregularities in the condenser high and condenser out, see Fig. 2 for
maps stem from random variations in the ambient thermocouple positions) are 7.5 and 1.1 K, respectively.
temperature and in the cycle lengths.
For some of the measurements, representing the corners,
4. Analysis
the centre and the centre of the sides of the contour maps
more detailed data is provided in Tables 2–4; one for each
4.1. Expansion device capacity (EDC)
ambient temperature.
As can be seen in Fig. 3, a wide but flat energy minimum
Tables 2–4 show that a lower EDC in general gives
(0.60–0.65 kW h/24 h) exists, stretching over a range of
longer evaporator activation time, increased superheat,
EDC and charges. This minimum is however open (no subcooling and relative on time and decreased evaporator
energy increase) for the highest EDC. For higher EDC it and condenser temperatures.
appears that an over- and undercharge is equally detrimental With lower EDC the refrigerant tends to accumulate in
to the energy consumption. With lower EDC, the minimum the condenser, which starves the evaporator. As a result, the
tends to move towards higher charges. evaporation temperature decreases. With a lower evapor-
In Fig. 4 the results from the 16 and 31 8C experiments are ation temperature the compressor mass flow (and cooling
shown. As can be seen, energy minima similar to the 25 8C capacity) decreases and so the condensation temperature.
experiment exist—flat over a wide range of charges and EDC However, the total temperature lift always increases with
and open towards the highest EDC. However, the optimum increased superheat. As a result of lower cooling capacity

Table 2
Experimental data at 16 8C
Charge EDC Energy Relative Cycle Activation Averaged over on-period
(g) (l N2/min) (kW h/24 h) on (–) length (s) time (s) Valve Dt Evap. Cond. Suction Superheat Sub-cooling
(K) (8C) (8C) (8C) (K) (K)
22 3.06 0.39 0.23 2918 n.a. 2.6 K18.2 29.6 21.9 7.5 1.1
22 2.00 0.39 0.24 3007 n.a. 4.6 K18.7 29.6 20.6 7.6 1.2
22 0.15 0.48 0.33 3252 n.a. 7.8 K22.8 28.2 17.2 9.0 2.2
36 3.06 0.27 0.13 2636 142 4.8 K10.6 32.9 19.1 3.4 2.0
36 2.00 0.28 0.14 2667 198 6.4 K11.9 32.4 17.5 4.4 2.5
36 0.15 0.40 0.24 3035 n.a. 3.3 K20.6 31.2 14.5 8.5 11.2
50 3.06 0.32 0.15 2537 112 5.9 K9.5 34.7 4.0 1.4 3.5
50 2.00 0.32 0.15 2615 136 6.5 K10.2 34.8 6.1 2.0 4.7
50 0.15 0.31 0.16 2554 215 3.7 K12.2 34.4 14.6 3.8 11.6
E. Björk, B. Palm / International Journal of Refrigeration 29 (2006) 789–798 795

Table 3
Experimental data at 25 8C
Charge EDC Energy Relative Cycle Activation Averaged over on-period
(g) (l N2/min) (kW h/24 h) on (–) length (s) time (s) Valve Dt Evap. Cond. Suction Superheat Sub-cooling
(K) (8C) (8C) (8C) (K) (K)
23 3.06 0.76 0.41 1627 n.a. 2.4 K16.3 41.9 33.7 6.3 1.0
23 2.28 0.78 0.43 1683 n.a. 4.4 K17.2 42.0 32.4 6.5 1.0
23 0.15 0.87 0.54 2060 n.a. 9.6 K21.2 41.5 28.6 7.8 1.2
31 3.06 0.62 0.28 1453 68 3.5 K10.6 44.8 30.8 0.6 1.5
31 2.28 0.61 0.28 1494 92 5.3 K10.9 44.7 29.4 1.3 1.6
31 0.15 0.76 0.42 1830 479 5.5 K17.7 43.3 24.6 6.7 9.4
40 3.06 0.87 0.36 1571 47 6.5 K9.6 48.5 7.9 0.0 2.3
40 2.28 0.80 0.34 1554 88 9.3 K9.9 48.2 10.6 0.1 2.6
40 0.15 0.71 0.36 1672 272 3.6 K14.6 46.8 23.7 5.2 15.2

and larger temperature lift, the relative on-time and the condition remains at a nearly saturated liquid condition.
energy consumption increase. This explains the energy In fact, the experimental method (Section 1.3) on how to
increase seen in Figs. 3 and 4 at lower EDC. determine the capillary tube length and quantity of charge
The flat or unchanged energy consumption that is seen gave no recommendation for the minimum length of the
for higher EDC may be explained by a shorter evaporator capillary tube. It may be that within certain limits of the
activation time (faster evaporator refilling) that counter- capillary tube length and condenser pressure the capillary
balances a throttling loss from increasing vapour quality at tube inlet conditions remains at a nearly saturated liquid
the condenser outlet (little or no subcooling was observed condition. Further research in this area may be needed. It
during the later on-period). However, it is also possible that should, however, be kept in mind that the 2.04 m long
the condenser outlet condition is more or less unchanged capillary tube, which was not removed for the experiments,
(nearly constant throttling loss) and that the losses due to limited the highest EDC. Hence, if an even higher EDC had
varied activation time are small at wider valve openings. been possible an energy increase from a throttling loss
The fact that the energy consumption is unchanged at higher seems likely. This throttling loss stems from gas being
EDC for all tested ambient temperatures, each with different passively transported around the system without contribut-
compressor on-time, indeed indicates this. At the lowest ing to the cooling capacity thus reducing the system
ambient temperature the compressor on-time is short and efficiency.
a relatively large influence of a changed activation time
would have been expected. On the other hand, at the highest 4.2. Quantity of charge
ambient temperature the compressor on-time is longer,
which makes the influence of a varied activation time small. Tables 2–4 show that increased charge in general gives
As a result, a relatively large influence of a throttling loss shorter activation time, lower superheat, lower suction line
would have been expected. It is possible that the EDC is temperature, increased subcooling and higher evaporator
extremely sensitive to the inlet vapour quality so that an and condenser temperatures.
increased inlet quality sharply reduces the mass flow, which The evaporator activation time is shortened with
results in more condensate. As a result the condenser outlet increased charge due to increased subcooling soon after

Table 4
Experimental data at 31 8C
Charge EDC Energy Relative Cycle Activation Averaged over on-period
(g) (l N2/min) (kW h/24 h) on (–) length (s) time (s) Valve Evap. Cond. Suction Superheat Sub-cooling
Dt (K) (8C) (8C) (8C) (K) (K)
22 3.06 1.13 0.58 1644 n.a. 2.5 K15.4 50.2 41.9 6.1 0.8
22 2.00 1.18 0.66 1809 n.a. 5.8 K17.0 50.3 39.7 6.4 0.9
22 0.15 1.33 0.88 5518 n.a. 12.4 K24.7 48.4 33.5 9.6 1.9
32 3.06 1.02 0.45 1375 51 3.1 K11.6 53.0 39.9 K0.4 1.3
32 2.00 1.01 0.46 1375 74 5.8 K11.8 53.2 37.8 0.2 1.5
32 0.15 1.09 0.56 1688 699 7.8 K15.8 51.9 33.0 5.9 6.8
42 3.06 1.51 0.60 1742 35 3.1 K10.4 56.2 16.4 0.1 1.8
42 2.00 1.35 0.55 1534 33 5.8 K10.9 56.1 17.5 0.1 1.9
42 0.15 1.09 0.48 1491 299 7.8 K13.8 54.7 31.4 2.3 12.3
796 E. Björk, B. Palm / International Journal of Refrigeration 29 (2006) 789–798

compressor start-up (as the low side charge is displaced cold suction line is significantly reduced, as the refrigerant is
towards the condenser). This start up subcooling increases held up in the condenser (15.2 K subcooling). Apparently,
the capillary tube mass flow, which accelerates the the cold suction line is more detrimental to the energy
redistribution process. As a result, the on-period averaged consumption than a liquid level in the condenser reducing
evaporation temperature increases whereas the averaged the condensation area.
superheat and suction line temperatures decrease. However,
with a too large charge, the evaporator overflows, which
gives a cold suction line (cooling capacity outside the
cabinet). The result is higher energy consumption. With a 5. Discussion
too low charge, the explanation for increased energy
consumption is similar as for lower EDC; an undercharged
5.1. Comparison to earlier results
evaporator gives a large superheat, a low evaporation
temperature and so a large temperature lift, which reduces
With one exception the results qualitatively are in
the system efficiency. The evaporator accumulator explains
agreement with the steady state simulations carried out by
the rather flat energy minimum in between these two
Jakobsen [13]. For higher charges his model did not indicate
extremes. For a range of charges, this device acts as a buffer
an efficiency drop due to a cold suction line. The reason for
that protects the system from either superheat or a cold
this is not clear. Since his model did not include a low side
suction line.
accumulator the effect of a cold suction line would have
been expected.
4.3. Ambient temperature
The simple charge correlation proposed by Dmitriyev
and Pisarenko [32] based only upon the evaporator and
With increased ambient temperature (Tables 2–4), the
condenser volume is:
energy consumption, the condenser temperature and the
compressor running time increase whereas the activation
Gr Z 0:41Ve C 0:62Vc K38 (1)
time decreases. While most of these effects seem plausible,
the decreased activation time is not obvious. Two factors
In which Gr is the charge in grams, Ve the evaporator
may explain this. First, the increased condenser pressure at
internal volume in ml and Vc the condenser internal volume
increased ambient temperature most likely accelerates the
in ml. The correlation was originally designed for
evaporator refilling. Second, at increased ambient tempera-
refrigerant R12. However, using the input data from the
ture the compressor and its oil sump are at a higher
current system and multiplying the result with the density
temperature, which means that less refrigerant is dissolved
ratio of Isobutane to R12 (0.41 liquid/liquid), the correlation
into the compressor oil [11].
suggests 38 g as optimum charge. This is an overcharge of
This may also explain the result of increased optimum
only 15% to the nominal 33 g charge.
charge at lower ambient temperature. For lower ambient
The findings by Dmitriyev and Pisarenko [32] and
temperature, more refrigerant is dissolved into the
Kuijpers et al. [12] that the optimal charge was nearly
compressor oil and the activation time increases. As a
independent of the ambient temperature could only partly be
result, a higher charge is promoted. The short compressor
verified: At the two higher ambient temperatures tested (25
running time (to reach the cut-out temperature) at a low
and 31 8C) the optimum charge was approximately constant.
ambient temperature prevents an overflowed evaporator and
However, at the low (16 8C) ambient temperature the
a cold suction line even at higher quantities of charge. That
optimum charge increased. This difference can be explained
is, the redistribution process is uncompleted. However, with
by the solubility of the refrigerants. While this study uses
a larger thermal mass (food stored in the cabinet), the
Isobutane, which is a highly soluble refrigerant, previous
compressor running time will increase, the compressor will
studies used other refrigerants.
be warmer and an overflowed evaporator seems likely.
Another, but minor factor contributing to the increased
optimum charge at lower ambient is the increasing liquid 5.2. Comparison to original configuration
density.
The nominal 33 g charge in the investigated refrigerator
4.4. Combined effect of low EDC and high charge is apparently close to optimal (Figs. 3 and 4). At the 25 and
31 8C ambient temperatures it is, according to this study,
In Fig. 3 it was seen that the energy minimum tends to approximately a 2 g overcharge. At the 16 8C ambient
move towards higher charges with lower EDC. Table 3 temperature it is approximately an undercharge of 5 g.
explains this. For the highest charge (40 g), the suction line For the capillary tube length, the experimental results
temperature is colder than the ambient temperature for (Figs. 3 and 4) suggest that the 0.5 m long capillary tube that
higher EDC (2.28 and 3.06 l N2/min), in other words a loss was removed for the experiments could be removed at the
of cooling capacity. With lower EDC, the energy loss of a original configuration without any loss of efficiency.
E. Björk, B. Palm / International Journal of Refrigeration 29 (2006) 789–798 797

5.3. Influence from suction line heat exchanger offsets an increased throttling loss or a capillary tube inlet
condition that was nearly constant in spite of increased valve
Suction line heat exchangers (SLHX) are typically used opening.
in domestic refrigeration. They increase the total efficiency For an altered ambient temperature, it was found that
and prevent external condensation on the suction line the optimum charge increased at a low ambient
between the slhx and the compressor. The overall influence temperature. This was explained by a slower redistribu-
from slhx is that it increases the capillary tube capacity, tion process and by more refrigerant held up in the
lowers the evaporator inlet quality and increases the suction compressor oil at lower ambient temperature, both
line temperature (at compressor inlet). As a result the increasing the optimum charge.
optimum capillary tube length needs to be longer and the The method outlined in the introduction (Section 1.3) on
charge possibly a little higher (the slhx allows the dry-out how to determine the capillary tube length and quantity of
point closer to the evaporator outlet.) charge can be recommended as it takes different thermal
loads and thermal masses (food in cabinet) into consider-
5.4. Limitations ation. The possible energy saving with a more sophisticated
method appears to be limited. The empirical charging
It should be noted that this study has examined only correlation from Dmitriyev and Pisarenko [32], corrected by
one type of domestic refrigerator with its highest EDC a density conversion may be used as a first estimation of the
limited by the capillary tube length of the suction line optimum charge.
heat exchanger. Furthermore, the experiments were In order to make the optimisation procedure faster more
conducted with an empty (low thermal mass) cabinet, accurate correlations for void fraction are needed (appli-
as stipulated by the ISO7371 standard [30], which gives cable at the internal geometries that are common in
relatively short cycle lengths. With higher thermal mass domestic refrigerators and freezers; vertical bends, odd
(i.e. food stored in cabinet) the cycle length and so the cross section shapes and low side accumulator). Also there
compressor on-time will be longer. With longer com- may be a need for more accurate capillary tube capacity
pressor on-time the evaporator will contain more correlations (applicable at two-phase inlet conditions).
refrigerant at the end of the on-period [10,11]. In fact,
in order to ensure that the system not will be over
charged it appears wise to select the system charge at
steady state conditions as was described in the Acknowledgements
experimental procedure outlined in the introduction
(Section 1.3). The Swedish National Energy Administration and
Electrolux AB provided support for this work.

6. Conclusions

This study offers some insight into the question of References


optimum capillary tube capacity and quantity of charge for
small, capillary tube throttled, on/off cycling vapour [1] M.J.P. Janssen, L.J.M. Kuijpers, J.A. de Wit, Theoretical and
compression systems. It was found that the energy Experimental Investigation of a Dynamic Model for Small
Refrigerating Systems, Proceedings of the Purdue IIR
consumption had a minimum for certain combinations of
Conference, 18–21 July, 1988.
EDC and charges and that this minimum was flat and wide.
[2] J. Wang, Y. Wu, Start up and shut down operation in a
Overall, the lowest energy consumption was obtained with reciprocating compressor refrigeration system with capillary
charge and EDC selected in such a way that properly tubes, Int J Refrigeration 13 (1989) 187–190.
charged heat exchangers, without superheat or subcooling, [3] M.J.P. Janssen, Cycling losses in cooling circuits, MSc Thesis,
was reached within a short time after a compressor start in WOP-WET 89.002, Eindhoven University of Technology,
the regular on/off cycle. 1989.
With a too low charge, the evaporator superheat [4] M.J.P. Janssen, J.A. de Witt, L.J.M. Kuijpers, Cycling losses
increased. With a too high charge, the suction line became in domestic appliances: an experimental and theoretical
cold. Both cases leading to increased energy consumption. analysis, Int J Refrigeration 15 (3) (1992).
In between these extremes, the evaporator accumulator [5] P.J. Rubas, C.W. Bullard, Factors contributing to refrigerator
cycling losses, Int J Refrigeration 18 (3) (1995) 168–176.
buffered the charge, giving as a result a flat energy
[6] P.E. Krause, C.W. Bullard, Cycling and quasi-steady
minimum. behaviour of a refrigerator, ASHRAE Trans: Symp 19 (Part
With a too low EDC the evaporator superheat increased; 1) (1996) 1061–1069.
as a result, increasing the energy consumption. However, [7] W.H. Coulter, C.W. Bullard, An experimental analysis of
with a high EDC the energy consumption was unchanged. cycling losses in domestic refrigerator–freezers, ASHRAE
This was explained by a quicker redistribution process that Trans 103 (1) (1997) 587–596.
798 E. Björk, B. Palm / International Journal of Refrigeration 29 (2006) 789–798

[8] J. Nordenberg, Redistribution of migrated refrigerant. Master [21] M.B. Pate, D.R. Tree, A linear quality model for capillary
of Science Thesis, Department of Energy Technology, Royal tube-suction line heat exchangers, ASHRAE Trans 90 (1984)
Institute of Technology, Stockholm, Sweden 2001. 3–17.
[9] C. Inan, T. Gonul, M. Tanes, X-ray investigation of a domestic [22] K.C. Mezavila, C. Melo, An homogeneous model to simulate
refrigerator. Observations at 25 8C ambient temperature, Int J refrigerant flow through non-adiabatic capillary tubes,
Refrigeration 26 (2003) 205–213. Proceedings of the International Refrigeration Conference at
[10] E. Björk, B. Palm, Refrigerant mass charge distribution in a Purdue University, USA, 1996.
domestic refrigerator. Part I. Transient conditions, Appl [23] B. Xu, P.K. Bansal, Non-adiabatic capillary tube flow: a
Therm Eng 26 (2006) 829–837. homogeneous model and process description, Appl Therm
[11] E. Björk, B. Palm, Refrigerant mass charge distribution in a Eng 22 (2002) 1801–1819.
domestic refrigerator. Part II. Steady state conditions, Appl [24] J. Sinpiboon, S. Wongwises, Numerical investigation of
Therm Eng 26 (2006) 866–871. refrigerant flow through non-adiabatic capillary tubes, Appl
[12] L.J.M. Kuijpers, M.J.P. Janssen, P.J.M. Verboven, The influence Therm Eng 22 (2002) 2015–2032.
of the refrigerant charge on the functioning of small refrigerating [25] C. Melo, L.A.T. Viera, R.H. Pereira, Non-adiabatic
appliances, ASHRAE Trans 94 (1988) 813–828. capillary tube flow with isobutane, Appl Therm Eng 22
[13] A. Jakobsen, Energy optimisation of refrigeration systems. (2002) 1661–1672.
The domestic refrigerator—a case study, PhD Thesis,
[26] P.K. Bansal, B. Xu, A parametric study of refrigerant flow in
Refrigeration Laboratory, The Technical University of Den-
non-adiabatic capillary tubes, Appl Therm Eng 23 (2003)
mark, 1995.
397–408.
[14] N. Vjacheslav, A. Rozhentsev, C. Wang, Rationally based model
[27] W.J. Mulroy, D.A. Didion, Refrigerant migration in a split-
for evaluating the optimal refrigerant mass charge in refrigerat-
unit air conditioner, ASHRAE Trans 91 (Part 1A) (1985)
ing machines, Energy Convers Manage 42 (2001) 2083–2095.
193–206.
[15] G. Ding, C. Zhang, Z. Lu, Dynamic simulation of natural
[28] L.J.M. Kuijpers, M.J.P. Janssen, J.A. de Wit, Experimental
convection bypass two-circuit cycle refrigerator–freezer and
verification of liquid hold-up predictions in small refrigeration
its application. Part 1: component models, Appl Therm Eng 24
(2004) 1513–1524. heat exchangers, Proceedings of the XVIIth International IIR-
[16] Z. Lu, G. Ding, C. Zhang, Dynamic simulation of natural Congress Refrigeration, Vienna, 1987.
convection bypass two-circuit cycle refrigerator–freezer and [29] Personal communication with B. Andersson, Electrolux AB,
its application. Part 2: system simulation and application, Appl AB-CD, R&D, domestic refrigeration.
Therm Eng 24 (2004) 1525–1533. [30] International standard, ISO 7371, Reference number
[17] P.K. Bansal, A.S. Rupasinghe, An empirical model for sizing ISO7371:1995(E).
capillary tubes, Int. J. Refrigeration 19 (1996) 497–505. [31] ASHRAE handbook, equipment volume, ISBN: 0-910110-52-
[18] O. Garcia-Valladares, Review of numerical simulation of a 2, p. 19:21–19:30, 1988.
capillary tube using refrigerant mixtures, Appl Therm Eng 24 [32] V.I. Dmitriyev, V.E. Pisarenko, Determination of optimum
(2004) 949–966. refrigerant charge for domestic refrigerator units, Int J
[19] C. Zhang, G. Ding, Approximate analytic solutions of Refrigeration 7 (3) (1984) 178–180.
adiabatic capillary tube, Int J Refrigeration 27 (2004) 17–24. [33] N. Vjacheslav, A. Rozhentsev, C. Wang, Rationally based
[20] P.K. Bansal, G. Wang, Numerical analysis of choked model for evaluating the optimal refrigerant mass charge in
refrigerant flow in adiabatic capillary tubes, Appl Therm refrigerating machines, Energy Convers Manag 42 (2001)
Eng 24 (2004) 851–863. 2083–2095.

You might also like