You are on page 1of 8

BOQ FOR AIR CONDITIONING WORKS

Description Rate Amount


S.No Qty Unit
In words In figures Rs
1 Refrigeration Machines
Supply transporting to site ,installation, testing
and commissioning of AIR COOLED SCREW
CHILLERS complete with multiple heremetic
/semiheremetic screw compressors, air cooled
condenser with corrosion protective coat on
condenser coils /fins , chillers with inlet and
outlet Victaulic coupling assembly ,refrigerant,oil,
microprocessor control panel compatible for hook
up to Building Management system with weather
proof electrical panel ,Power isolators and
capacitors, flow switches ,transformer for control
circuit, service modem connectivity and all
electricals to be of IP55 .The
equipmentmanufactured shall be suitable Seismic
zone 5 and installation shall be done in
accordance for the Seismic requirements.
80 TR capacity at Entering airto condenser at 35
˚C 2 No.
Entering water to Chiller at 12 ˚C and
Leaving water from chiller at 7 ˚C

2 Vibration Isolators
For pumps- Rectangular structural beam or
channel concretew form for floating
foundations,concrete reinforcement bars, spring
isolators on 1/4 inch neoprene rubber acostical
pads etc 3 Sets

3 Double sphere flexible connector with GI flanges


and bolts etc.
a On Chillers 4 nos
b On Pumps 6 nos

45
Description Rate Amount
S.No Qty Unit
In words In figures Rs
4 Chilled Water Pumps
Supply transporting to site ,installation, testing
and commissioning of Centrifugal Chilled water
pumps monoblock type with IP 55 TEFC motor
suitable for outdoor installation mounted on
common base frame FRP coated for corrosion
prevention,for recirculation of chilled water for air
conditioning system.The pump motor shall be
suitable for 415 + / - 10 % volts,50 cycles, 3 phase
power supply.The pumps shall have bronze
impeller ,stainless steel shaft and electrical power
on /off push button or Power isolator near the
pumps.All electricals and motor to be IP 55. 3 Nos
Water flow 48 M³ per hour
Head 25 Meters of water column
Motor 5.5 KW
5 AIR HANDLING UNITS
Double skin cabinet type AHU with backward
curve Centrifugal fan, insulated sandwich type SS
drain tray, Coil section with six row deep cooling
coil, door limit switch, nonflammable filters, floor
mounted vibration isolators for the fan motor
assembly, outlet dampers all accessories
etc.Electrical panel with necessary control, MCCB
single phase preventor, phase indicating lamps,
ON/OFF status, non polarised NO / NC contacts
for tripping on signal from fire dampers / fire
alarm panel starter Copper PVC armoured power
& Control cabling within the AHU room upto
thermostat /sensor etc. two AHU rooms
a 12000 cfm against 40 mm static 6 R (rows) Deep
cooling coil. 2 Nos
6 Drain Piping
Hard PVC drain piping with elbows, tees, clean

outs etc without insulation within the AHU room


a 50 mm dia 30 RMT
b 40 mm dia 12 RMT
c 32 mm dia 12 RMT

46
Description Rate Amount
S.No Qty Unit
In words In figures Rs
7 Chilled Water Cassette Type Fan Coil unit
Ceiling suspended complete with Four walls
chilled water copper tube aluminum finned
coil,Fan with four directional flow aerofoil blade
quiet high efficiency centrifugal fan ,easily
cleanable synthetic filter, Auto water pump- for
auto drain water detection and pump out of drain
pan. Two way or three way vavle with actuator,
and cordless remote for the opreration of the fan.
Attractive Grill as integral part of the unit.
Provision for the fresh air intake. The unit shall be
suitable for operation on Single phase 230 volts
50- cycles, the fan shall have three speeds.
additional box for housing the two way /three
way valve and other isolating valves with drain
provision connected to drain section of cassette.
Only 5 Amps plug point/MCB will be given
within 3 M from cassette unit and from there all
wiring to be included.
a 10000 Kcal per hour 6 Nos.

8 Supply and fixing of Brass ball valve with


strainer and ball valve without strainer for the fan
coil units with flare nuts teflon tape etc.
a 20 mm dia 6 set
9 Copper piping from the cassette unit to the
nearest M S chilled water piping with tee elbow
bends fittings etc 6 sets
10 Kitec aluminum commpsite pipe with
compression type kitec fittings with Nitrile rubber
insualtion as drain pipe for the Chilled water
cassette fan coil units.
a 32 mm dia 10 RMT
b 25 mm dia 10 RMT
c 20 mm dia 10 RMT

47
Description Rate Amount
S.No Qty Unit
In words In figures Rs
11 Chilled water piping
Insulated chilled water piping, MS heavy duty 'C'
Class complete with with bends, elbows tees,
vibration isolators, hangers, fullround high
density PU supports finished, 50 mm thick
expanded polystyrene pipe sections fixed with hot
bitumen as adhesive, finished with plasticised tar
felt as vapour barrier with over lap and clad with
Pre painted /Pre coated steel sheet of approved
color.
a 150 mm dia 10 RMT
b 125 mm dia 36 RMT
d 100 mm dia 60 RMT
e 80 mm dia 50 RMT
f 65 mm dia 10 RMT
g 50 mm dia 10 RMT
h 40 mm dia 54 RMT
I 32 mm dia 30 RMT
12 National Interfit make - Grooved Mechanical
Joining System with EPDM rubber gasket.
I) Elbow
a 125 mm dia 6 Nos.
b 100 mm dia 12 Nos.
c 80 mm dia 12 Nos.
d 65 mm dia 4 Nos.
e 50 mm dia 4 Nos.
f 40mm dia 6 Nos.
g 32 mm dia 12 Nos.
h 25 mm dia 2 Nos.
ii) Rigid Coupling Style 5
a 125 mm dia 12 Nos.
b 100 mm dia 12 Nos.
c 80 mm dia 12 Nos.
d 65 mm dia 4 Nos.
e 50 mm dia 3 Nos.
f 40 mm dia 6 Nos.

48
Description Rate Amount
S.No Qty Unit
In words In figures Rs
g 32 mm dia 12 Nos.
h 25 mm dia 4 Nos.
III) Gruv Flange Style 14
a 125 mm dia 12 Nos.
b 100 mm dia 12 Nos.
c 80 mm dia 12 Nos.
d 50 mm dia 4 Nos.
iv) Reducing Coupling style25  
a 125 mm to 100 12 Nos.
b 100 mm to 80 mm 6 Nos.
c 80 mm to 80 mm 6 Nos.
d 80 mm to 65 mm 3 Nos.
e 80 mm to 50mm 3 Nos.
f 80 mm to 40 mm 5 Nos.
g 40 mm to 32 mm 2 Nos.

13 Insulated Butter fly valves with flanges gaskets


bolts and Nuts etc
a 100 mm dia 7 Nos
b 80 mm dia 4 Nos
c 50 mm dia 2 Nos

14 Insulated balancing type control cum balancing


valves complete with measuring ports with
fanges / screwed fittiings with GI fasteners of bolt
and Nuts washers etc
a 100 mm dia 2 Nos
b 80 mm dia 2 Nos

15 Insulated ANERGY flow starightener cum


strainer at the inlet of the pumps complete with
flanges, bolts nuts gaskets etc.
a 100 mm dia 3 Nos
16 Insualted Plate typ swing Check valves with
flanges, bolts nuts gaskets etc.
a 65 mm dia 3 Nos
17 Insulated Y stariners at the inlet of the AHU with
flanges , gaskets GI nuts and bolts etc
a 80 mm dia 2 Nos.

18 Supply and fixing of four inch Pessure gauge with


0 to 7 Kg / cm² range with isolating ball vave and
nipple. 14 nos
19 Supply and fixing of Thermometers with a range
14 nos
of 0 to 50°C

20 Supply and installation of Auto air purge at the


top most level of the chilled water circuit Anergy
or equivalent make 6 Nos

49
Description Rate Amount
S.No Qty Unit
In words In figures Rs
21 Small Single phase pump to pump the water from
the storage tank to the expansion Tank with level
controller and auto on / off. 1 set
Sheet Metal Ducting
22 SupplyTransport to site Fabricate erect ducting
out of Galvanized Steel Sheet complete with
elbows,turning vanes, volume control duct
dampers, neoprene gaskets Galvanized supports
hangers etc.
a 18 G GI 40 Sq.M
b 20 G GI 40 Sq.M
c 22 G GI 150 Sq.M
d 24 G GI 200 Sq.M
23 Supply and installation of Aluminum powder
coated Louvers with bird screen, adjustable
damper for fresh air and without damper for
exhaust air etc.
a For Fresh Air 1 Sq.M
b For Exhaust Air 2 Sq.M
24 Acoustic insulation
a AHU room acoustic insulation with 2 inch 48 Kg
/ M ³ Fiberglass insuation, fnised with prepainted
perforated GI sheet. 200 Sq.M
b Duct inside lining with 1 inch 48 Kg / M ³ Fiber
glass and fished with perforated pre painted Gi
sheet with aid of washers and GI bolts and nuts 100 Sq.M
25 Thermal insualtion of ducts with Factory
laminated aluminum fiberglass covered with GI
wire netting and PVC strapping every 300 mm
a 50 mm thick 24 Kg / M ³ 100 Sq.M
b 25 mm thick 24 Kg / M ³ 400 Sq.M
26 Fire Dampers with fusible link to cosle the
damper by melting the fusible link when the
temperature exceeds 50°C in the supply air and
return air path. 6 Sq.M
27 GRILLES /DIFFUSERS
Square / rectangular diffusers extruded
aluminum removable core type with or without
aluminum volume control dampers.
a Supply air diffuser with VCD 1 Sq.M
b Return air diffuser without VCD 2 Sq.M

28 Linear Grilles( EP- 00, EP-15, EP-30 , EP 45)


continous or with four side flange , including
mittered corners or shape as required to suit
interiors etc
a 200 mm wide 300 RMT
b 150 mm wide 20 RMT

50
Description Rate Amount
S.No Qty Unit
In words In figures Rs
29 Aluminum opposed blade dampers, nylon geared
with aerofoil blades Matt black colored powder
coat finish. 7 Sq.M
30 VENTILATION & EXHAUST FANS
Cabinet type GI construction fan section, TEFC
motor electrical panel, isolators power cabling
dampers mounting arrangements spring isolators
etc all electricals to be IP 55
a 2200 cfm 2 Nos.
31 Propeller fans
a 24 inches dia 6 Nos
ELECTRICAL EQUIPMENT
Floor mounted cubicle type compartmentalized
dust & vermin proofelectrical main air
coinditioning central panel duly painted with
seven tank painting process in 14 / 16 G with
ACB / MCCB and SFU required to cater to
complete Air conditioning equipment in the
Terrace level of Seminar Hall complete with
electolytic tinned copper busbars, incoming ,out
going feeders starters indiacting lamps, selector
switch ,internal copper control & power cabling ,
run hour meter, KW hour meter, Ammeter,
Voltmeter, as detailed below:
a Main panel with Incomer of 400 A and 200 Amps
out going feeders for the two chillers with MCCB
/ SFU , 3 numbers 32 ampheres Chilled water
pumps with SFU with ammeter , DOL Starter 32
Amps feeder for the make up water pump and a
spare feeder of 32 Amphers. 1 Nos
b Panel for AHU uded in AHU
c Power cabling 3 1/2 C 185 Sq mm PVC
armoured Aluminium cable between the panel to
Chiller isolator & or Chiller 100 RMT
d Power cabling 4 C 6 sq mm PVC armoured
Aluminium conductor between the panel to
Chilled water pumps 300 RMT
e Control wiring 7 C 2.5 Sq.mm copper 400 RMT
f Earthing out of 8 swg copper conductor 400 RMT

51
Description Rate Amount
S.No Qty Unit
In words In figures Rs
Building Management System
32 Portable Operator Terminal 1 Set

33 Software 1 Set

34 System interface unit 1 Set

35 DDC Controllers
a CHILLER Controller 1 Set
b AHU's Controller 2 Set

36 Field Devices
a Outside air temperature & Rh sensor 1 No.
b Immersion temperature sensor [CHW
temperatures] 4 Nos.
c Duct type temperature sensor 2 Nos.
d DP Switch to monitor fan run status 2 Nos.
e DP Switch to monitor filter status 2 Nos.
f DP sensor across Supply and Return Header 1 Nos.

37 VALVE & ACTUATORS


2 WAY Valve
a 2 way modulating valve 100mm dia for Bypass
Line 1 Nos.
b 80 mm 2 way modulating valve for AHU 2 Nos.
Butterfly Valve
d 100 mm dia with on/off actuator with position
feedback 2 Nos.

38 Cables and conduits


Supply installation testing and commissioning of
following
a 2 core cable 1.0 sq.mm multistandard unscreened
cable 1200 Rmt
b 2 core cable 1.0 sq.mm multistandard screened
cable 500 Rmt

c 1" MS Conduit 800 Rmt

Grand Total

52

You might also like