AFLEX 3000
Users Manual
Global Representative
PROVA INSTRUMENTS INC
EN 61010-2-032
CAT III 600V
Pollution Degree 2
Definition of Symbols:
Caution: Refer to Accompanying Documents
Double Insulation
6. MAINTENANCE .............................................................11
1
2. PANEL AND PARTS DESCRIPTION
1. Coupling Assembly
2. Flexible Loop
3. Banana Plugs for Output
4. Output Range Select Switch
5. Power on LED
6. Low Battery Voltage LED
7. Current Range Select Switch
8. Battery Cover
2
3. OPERATING INSTRUCTION
3
1. Connect the banana plugs to the measuring instrument. Select
the corresponding sensitivity on your instrument. Select AC
range if a multi-meter is used.
2. On the flexible current probe, select the desired range (300A or
3000A) and output (300mV or 1V).
3. Connect the flexible probe around the conductor.
4. Make sure the current flowing direction is in consistent with the
arrow marked on the probe coupling. If the flexible current
probe is connected in the right orientation, the correct phase will
be displayed in the oscilloscope.
5. Keep the probe coupling more than 25mm away from the
conductor.
WARNING: Always wear appropriate gloves in operation.
4
Example 1: Current range 300A and Output 300mV. The AC voltage
reading is 100mV
The actual AC current = 300A / 300mV * 100mV = 100A
5
Example 2: Current range 3000A and Output 300mV. The AC
voltage reading is 100mV
The actual AC current = 3000A / 300mV * 100.0mV = 1000A
6
Example 3: Current range 300A and Output 1V. The AC voltage
reading is 333.3mV
The actual AC current = 300A / 1V * 333.3mV = 100A
7
Example 4: Current range 3000A output 1V. The AC voltage reading
is 333.3mV
The actual AC current = 3000A / 1V * 333.3mV = 1000A
8
4. ELECTRICAL SPECIFICATIONS
(23˚ ±3˚, 50/60Hz, conductor located at the center of the flexible loop)
Range
300A AC 3000A AC
Output Select 300mV 1V 300mV 1V
Output Signal 1mV/A 3.33mV/A 0.1mV/A 0.333mV/A
Accuracy 1% of full scale 1% of full scale
Linearity (10 to 100%) 0.2% of reading 0.2% of reading
Position Sensitivity 2% of range 2% of range
External Field (200 mm
1% of range 1% of range
from the head, < 40A/m)
Phase Error < ± 1˚ < ±1˚
Temperature Coefficient
0.02% of reading / ˚C 0.02% of reading / ˚C
( 0 to 70˚C)
9
5. GENERAL SPECIFICATION
Indoors use
Altitude: 2000m
Probe Length: 3000-24 24 in / 610 mm
3000-36 36 in / 915 mm
3000-48 48 in / 1220 mm
Minimum Bending Diameter: 35mm
Connector Diameter: 23mm
Cable Diameter: 14mm
Cable Length from Probe to Box: 170mm
Cable Length from Box to Output: 170mm
Battery: two 1.5 SUM-3
Dimension (Box): 130mm(L) x 80mm(W)x 43mm(H)
5.1”(L) x 3.1”(W) x 1.7”(H)
Operating Temperature: -10 to 85˚C
Operating Humidity: 15% to 85% RH
Storage Temperature: -20 to 85˚C
Storage Humidity: 15% to 85% RH
Weight: 430g
Accessory: users manual x 1
1.5V battery x 2
10
6. MAINTENANCE
11
7. BATTERY REPLACEMENT
1. Remove the flexible current probe from any circuit to be
measured.
2. Disconnect the flexible current probe from any measuring
instrument.
3. Turn the power off
4. Remove screw and then the battery cover.
5. Replace the old batteries with new batteries.
6. Replace the battery cover and fasten the screw.
12