CHECK LIST

TESTING & COMMISSIONING OF


FM 200 SYSTEM- FUNCTIONAL TEST

NOT
SL. NO. ACTIVITY OK N/A REMARKS
OK

IF FM 200 PANEL IS IN AUTO MODE

WHEN ONE OF THE TWO DETECTOR ZONES OPERATED


1
WITHIN FM200 PROTECTED AREA
a CHECK THE FIRST STAGE ALARM BELL/ STROBE HAS OPERATED
b CHECK SMOKE DETECTOR SIGNAL LED HAS OPERATED
c CHECK INTERNAL PANEL BUZZER HAS OPERATED

WHEN SECOND DETECTOR ZONES OPERATED WITHIN


2
FM200 PROTECTED AREA
CHECK THE PANEL INITIATES A PRE-DISCHARGE AUDIABLE/ VISUAL
a ALARM (INTERMITTENT TONE ALARM)/ (DISCHARGE TIME 60 SECONDS
STARTS)
b CHECK SMOKE DETECTOR SIGNAL LED HAS OPERATED
c CHECK INTERNAL PANEL BUZZER HAS OPERATED

3 ONCE THE TIMER HAS ELAPSED

a CHECK THE PANEL SENDS A GAS RELEASE SIGNAL TO THE


ELECTRICAL ACTUATOR ON THE MASTER CYLINDER

IF GAS NOT RELEASED FROM MASTER CYLINDER WITHIN


4
10 SECONDS

a CHECK THE PANEL SENDS A GAS RELEASE SIGNAL TO THE STAND BY


CYLINDER
CHECK LIST
TESTING & COMMISSIONING OF
FM 200 SYSTEM- FUNCTIONAL TEST

NOT
SL. NO. ACTIVITY OK N/A REMARKS
OK

5 WHEN FM200 PANELS ABORT SWITCH ACTIVATED

a SIMULATE ALARM IN TWO DETECTOR ZONES

b KEEP THE ABORT SWITCH PRESSED & CHECK THE ELECTRICAL


ACTUATOR HAS NOT ENERGISED
ON RELEASE OF ABORT SWITCH, CHECK THE ELECTRICAL ACTUATOR
c
HAS ENERGISED AFTER 60 SECONDS

6 SYSTEM ACTUATED USING MANUAL RELEASE STATION

a CHECH THE MANUAL RELEASE STATION INDICATION HAS DISPLAYED IN


THE PANEL
b CHECK THE ALARM BELL/ STROBE HAS ENERGISED

c CHECK THE ELECTRICAL ACTUATOR HAS ENERGISED AFTER 30


SECONDS