BASE DE DATOS DE AJUSTE DE PROTECCIONES

Tipo: DISTANCIA Subestación: CACHIMAYO Región: SIERRA SUR


Fabricante: ABB Línea: L-1001 Dpto: CUZCO
Modelo: REL670 E.T. Origen: CACHIMAYO Empresa: EGEMSA
Versión: E.T. Destino: MACHUPICHU Diag.Unif.N°:
Tecnología: NUMÉRICA Uprim[kV]: 138 Man.Serv.N°:
Año instal.: Fases: RSTN Fecha: 14-Feb-14
Código: Ucc [V]: Respons.: JCA
N° Serie: Uca [V]: 100 Revisión: 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 (AS BUILT) GRUPO 1 (AECP 2014) OBSERVACIONES
ACTUAL PROPUESTO
COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

DATOS GENERALES
DATOS DE LA LINEA TRANSFORMADORES DE CORRIENTE
TRANSFORMADOR DE TENSION RELACIONES DE IMPEDANCIA
DATOS DE LA CARGA

VALORES DE AJUSTE
@ SYSTEM SETUP @ ANALOG INPUTS
21 PROTECCION DE DISTANCIA @ ZONA 1 ( ZM1 )
21 ZONA 2 ( ZM2 ) 21 ZONA 3 ( ZM3 )
21 ZONA 4 ( ZM4 ) 21 ZONA 5 ( ZM5 )
21 PHASE SELECTION WITH LOAD ENCROACHMENT 68 POWER SWING DETECTION
21 Automatic switch onto fault logic (PSOF) 50 Instantaneous phase overcurrent protection (PIOC, 50)
51/67 Four step phase overcurrent protection (POCM, 51/67)50N Instantaneous residual overcurrent protection (PIOC, 50N)
51N/67N
Four step residual overcurrent protection (PEFM, 51N/67N)
26 Thermal overload protection, one time constant (PTTR, 26)

50BF Breaker failure protection (RBRF, 50BF) 50STBStub protection (PTOC, 50STB)

52PD Pole discordance protection (RPLD, 52PD) 27/59 VOLTAGE PROTECTION

27 Two step undervoltage protection (PUVM, 27) 59 Two step overvoltage protection (POVM, 59)
59N Two step residual overvoltage protection (POVM, 59N)RDIF Current circuit supervision (RDIF)
RFUF Fuse failure supervision (RFUF) 25 Synchrocheck and energizing check (RSYN, 25)

79 Autorecloser (RREC, 79) 85 Scheme communication logic for distance protection (PSCH, 85)
85 Current reversal and weak-end infeed logic for distance
PLAL
protection
Local acceleration
(PSCH, 85) logic (PLAL)

85 Scheme communication logic for residual overcurrent protection


85 Current(PSCH,
reversal
85) and weak-end infeed logic for residual overcurrent protection (PSCH, 85)

DATOS GENERALES
DATOS DE LA LINEA
Generales
Código de la línea - L-1001
E.T. Origen - CACHIMAYO
E.T. Destino - MACHUPICHU
Longitud total km 99.52
Parámetros por km tot.s/corregir tot.corregidos
Resistencia de secuencia positiva ohm/km 0.157 ohm 15.62 ohm 15.54
Reactancia de secuencia positiva ohm/km 0.5012 ohm 49.88 ohm 49.76
Conductancia de secuencia positiva us/km 0 us 0.00 us 0.57
Susceptancia de secuencia positiva us/km 3.2984 us 328.26 us 330.06
Resistencia de secuencia cero ohm/km 0.41 ohm 40.80 ohm 40.35
Reactancia de secuencia cero ohm/km 1.62 ohm 161.22 ohm 160.38
Conductancia de secuencia cero us/km 0 us 0.00 us 0.61
Susceptancia de secuencia cero us/km 2.0945 us 208.44 us 210.81
Resistencia mutua de secuencia cero ohm/km 0 ohm 0.00 ohm -
Reactancia mutua de secuencia cero ohm/km 0 ohm 0.00 ohm -
Datos característicos Módulo Angulo
Secuencia positiva
Impedancia de secuencia positiva (Z) ohm/km 0.5252 rad/km 1.2672
Admitancia de secuencia positiva (Y) us/km 3.2984 rad/km 1.5708
Impedancia característica ([Z/Y]) ohm/km 399.04 rad/km -0.1518
Coef. de atenuación (Re[ZY]^0.5) 0.02 0.13 0.13 1.42 0 1.4 neper/km 0.000199 -
Coef. de fase (Im[ZY]^0.5) 1 0 1 0.003 rad/km 0.001301 -
Velocidad de propagación 0.13 1.417 km/seg 289756 -
Impedancia de secuencia positiva total corregida por longitud 99 0.0 ohm 52.13 rad 1.2681
Admitancia de secuencia positiva total corregida por longitud 100 0.0 ohm 330.06 rad 1.5691
Potencia natural MW 47.72 -
Secuencia cero
Impedancia de secuencia cero (Z0) ohm/km 1.6711 rad/km 1.3229
Admitancia de secuencia cero (Y0) us/km 2.0945 rad/km 1.5708
Impedancia característica ([Z0/Y0]) ohm/km 893.22 rad/km -0.1239
Coef. de atenuación (Re[Z0Y0]^0.5) 0.02 0.18 0.19 1.448 0 1.4 neper/km 0.000231 -
Coef. de fase (Im[Z0Y0]^0.5) 1 0 1 0.004 rad/km 0.001856 -
Velocidad de propagación 0.19 1.444 km/seg 203066 -
Impedancia total de secuencia cero corregida por longitud 99 0.0 ohm 165.38 rad 1.3243
Admitancia total de secuencia cero corregida por longitud 101 0.0 ohm 210.81 rad 1.5679
Relaciones tierra-conductor Módulo Angulo
Relación ZN/ZL sistema europeo (k0=[Z0-Z1]/3Z1) - 0.73 grados 4.6508
Relación RN/R1 ([R0-R1]/3R1) - 0.54 -
Relación XN/X1 ([X0-X1]/3X1) - 0.74 -
Relación ZN/ZL sistema americano (k0=[Z0-Z1]/Z1) - 2.18 grados 4.6508
TRANSFORMADORES DE CORRIENTE
Marca - -
Tipo -
Modelo - -
Cantidad de núcleos - - 3 3
Corriente nominal A - 1 350 1 350
Relación de transformación - - 350.00 350.00
Clase - - 5P20 5P20
Prestación VA - 40 40
TRANSFORMADOR DE TENSION
Marca - -
Tipo - -
Modelo - -
Cantidad de arrollamientos - - 2 2
Tensión nominal entre fases V - 100 138000 100 138000
Relación de transformación - - 1380.00 1380.00
Clase - - 3P 3P
Prestación VA - 30 30
RELACIONES DE IMPEDANCIA
Relación secundario/primario (Zs/Zp = Us/Is:Up/Ip) - - 0.25 0.25
Relación primario/secundario (Zp/Zs = Up/Ip:Us/Is) - - 3.94 3.94
DATOS DE LA CARGA
Potencia máxima permanente MVA - 93.2 93.2
Resistencia mínima de carga a Unom ohm - 147.63 147.63
VALORES DE AJUSTE
SYSTEM SETUP Disp.s/interr.:
ANALOG INPUTS
Current
CT Star Point 1 - From Object - To Object To Object - To Object -
CT sec 1 A 1 10 1 1 - 1 -
CT prim 1 A 1 99999 1 1000 - 1000 -
CT Star Point 2 - From Object - To Object To Object - To Object -
CT sec 2 A 1 10 1 1 - 1 -
CT prim 2 A 1 99999 1 1000 - 1000 -
CT Star Point 3 - From Object - To Object To Object - To Object -
CT sec 3 A 1 10 1 1 - 1 -
CT prim 3 A 1 99999 1 1000 - 1000 -
Voltage
VT sec 7 V 0.0 999.999 0.001 100.000 - 100.000 -
VT prim 7 kV 0.05 2000.00 0.05 220.00 - 220.00 -
VT sec 8 V 0.0 999.999 0.001 100.000 - 100.000 -
VT prim 8 kV 0.05 2000.00 0.05 220.00 - 220.00 -
VT sec 9 V 0.0 999.999 0.001 100.000 - 100.000 -
VT prim 9 kV 0.05 2000.00 0.05 220.00 - 220.00 -
Line -Fault Locator
R1A Source resistance A (near end) ohm 0.001 1500.000 0.001 5.11 - 5.11 -
X1A Source reactance A (near end) ohm 0.001 1500.000 0.001 28.11 - 28.11 -
R1B Source resistance B (far end) ohm 0.001 1500.000 0.001 5.68 - 5.68 -
X1B Source reactance B (far end) ohm 0.001 1500.000 0.001 24.65 - 24.65 -
R1L Pos seq line resistance ohm 0.001 1500.000 0.001 5.72 - 5.72 -
X1L Pos seq line reactance ohm 0.001 1500.000 0.001 50.26 - 50.26 -
R0L Zero seq line resistance ohm 0.001 1500.000 0.001 27.42 - 27.42 -
X0L Zero seq line reactance ohm 0.001 1500.000 0.001 146.49 - 146.49 -
R0M Zero seq mutual resistance ohm 0.001 1500.000 0.001 0.001 - 0.001 -
X0M Zero seq mutual reactance ohm 0.001 1500.000 0.001 0.001 - 0.001 -
LineLength Length of line km 0.0 10000.0 0.1 99.52 - 99.52 -
21 PROTECCION DE DISTANCIA Disp.s/interr.:
ZONA 1 ( ZM1 )
ZMQPDIS
Operat Operation on/off - ON - OFF ON - ON -
Ibase Base current, i,e. rated current A 1 99999 1 1.00 350 1.00 350
Ubase Base voltage, i.e. rated voltage kV 0.05 2000.00 0.05 100.00 138 100.00 138
Off
Non-directional
OperationDir Operation mode of directionality - Forward - Forward -
Forward
Reverse
X1 Positive sequence reactance reach ohm 0.10 3000.00 0.01 8.15 32.13 8.15 32.13
R1 Positive seq. resistance for zone characteristic angle ohm 0.10 1000.00 0.01 2.55 10.06 2.55 10.06
X0 Zero sequence reactance reach ohm 0.10 9000.00 0.01 26.26 103.55 26.26 103.55
R0 Zero seq. resistance for zone characteristic angle ohm 0.50 3000.00 0.01 6.66 26.25 6.66 26.25
RFPP Fault resistance reach in ohm/loop, Ph-Ph ohm 1.00 3000.00 0.01 13.12 51.73 13.12 51.73
RFPE Fault resistance reach in ohm/loop, Ph-E ohm 0.01 9000.00 0.01 17.80 70.18 17.80 70.18
OperationPP Operation mode Off/On of Phase-Phase loops - ON - OFF ON - ON -
Timer tPP Operation mode Off/On of zoner timer, Ph-Ph - ON - OFF ON - ON -
tPP Time delay of trip, Ph-Ph s 0.000 60.000 0.001 0.000 - 0.000 -
OperationPE Operation mode Off/On of Phase-Earth loops - ON - OFF ON - ON -
Timer tPE Operation mode Off/On of zoner timer, Ph-E - ON - OFF ON - ON -
tPE Time delay of trip, Ph-E s 0.000 60.000 0.001 0.000 - 0.000 -
IMinOpPP Minimum operate delta current for Phase-Phase loops %IB 10 30 1 20 - 20 -
IMinOpPE Minimum operate phase current for Phase-Earth loops %IB 10 30 1 20 - 20 -
IMinOpIN Minimum operate residual current for Phase-Earth loops %IB 5 30 1 5 - 5 -
21 ZONA 2 ( ZM2 )
ZMQPDIS
Operat Operation on/off - ON - OFF ON - ON -
Ibase Base current, i,e. rated current A 1 99999 1 1.00 350 1.00 350
Ubase Base voltage, i.e. rated voltage kV 0.05 2000.00 0.05 100.00 138 100.00 138
Off
Non-directional
OperationDir Operation mode of directionality - Forward - Forward -
Forward
Reverse
X1 Positive sequence reactance reach ohm 0.10 3000.00 0.01 15.74 62.05 15.74 62.05
R1 Positive seq. resistance for zone characteristic angle ohm 0.10 1000.00 0.01 4.93 19.43 4.93 19.43
X0 Zero sequence reactance reach ohm 0.10 9000.00 0.01 50.72 199.97 50.72 199.97
R0 Zero seq. resistance for zone characteristic angle ohm 0.50 3000.00 0.01 12.86 50.69 12.86 50.69
RFPP Fault resistance reach in ohm/loop, Ph-Ph ohm 1.00 3000.00 0.01 13.12 51.73 13.12 51.73
RFPE Fault resistance reach in ohm/loop, Ph-E ohm 0.01 9000.00 0.01 17.80 70.18 17.80 70.18
OperationPP Operation mode Off/On of Phase-Phase loops - ON - OFF ON - ON -
Timer tPP Operation mode Off/On of zoner timer, Ph-Ph - ON - OFF ON - ON -
tPP Time delay of trip, Ph-Ph s 0.000 60.000 0.001 0.40 - 0.40 -
OperationPE Operation mode Off/On of Phase-Earth loops - ON - OFF ON - ON -
Timer tPE Operation mode Off/On of zoner timer, Ph-E - ON - OFF ON - ON -
tPE Time delay of trip, Ph-E s 0.000 60.000 0.001 0.40 - 0.40 -
IMinOpPP Minimum operate delta current for Phase-Phase loops %IB 10 30 1 20 - 20 -
IMinOpPE Minimum operate phase current for Phase-Earth loops %IB 10 30 1 20 - 20 -
IMinOpIN Minimum operate residual current for Phase-Earth loops %IB 5 30 1 - - - -
21 ZONA 3 ( ZM3 )
ZMQPDIS
Operat Operation on/off - ON - OFF ON - ON -
Ibase Base current, i,e. rated current A 1 99999 1 1.00 350 1.00 350
Ubase Base voltage, i.e. rated voltage kV 0.05 2000.00 0.05 100.00 138 100.00 138
Off
Non-directional
OperationDir Operation mode of directionality - Forward - Forward -
Forward
Reverse
X1 Positive sequence reactance reach ohm 0.10 3000.00 0.01 22.04 86.92 22.04 86.92
R1 Positive seq. resistance for zone characteristic angle ohm 0.10 1000.00 0.01 6.90 27.22 6.90 27.22
X0 Zero sequence reactance reach ohm 0.10 9000.00 0.01 71.04 280.11 71.04 280.11
R0 Zero seq. resistance for zone characteristic angle ohm 0.50 3000.00 0.01 18.01 71.00 18.01 71.00
RFPP Fault resistance reach in ohm/loop, Ph-Ph ohm 1.00 3000.00 0.01 13.12 51.73 13.12 51.73
RFPE Fault resistance reach in ohm/loop, Ph-E ohm 0.01 9000.00 0.01 17.80 70.18 17.80 70.18
OperationPP Operation mode Off/On of Phase-Phase loops - ON - OFF ON - ON -
Timer tPP Operation mode Off/On of zoner timer, Ph-Ph - ON - OFF ON - ON -
tPP Time delay of trip, Ph-Ph s 0.000 60.000 0.001 0.800 - 0.800 -
OperationPE Operation mode Off/On of Phase-Earth loops - ON - OFF ON - ON -
Timer tPE Operation mode Off/On of zoner timer, Ph-E - ON - OFF ON - ON -
tPE Time delay of trip, Ph-E s 0.000 60.000 0.001 0.800 - 0.800 -
IMinOpPP Minimum operate delta current for Phase-Phase loops %IB 10 30 1 20 - 20 -
IMinOpPE Minimum operate phase current for Phase-Earth loops %IB 10 30 1 20 - 20 -
IMinOpIN Minimum operate residual current for Phase-Earth loops %IB 5 30 1 - - - -
21 ZONA 4 ( ZM4 )
ZMQPDIS
Operat Operation on/off - ON - OFF OFF - OFF -
Ibase Base current, i,e. rated current A 1 99999 1 0.00 0.00
Ubase Base voltage, i.e. rated voltage kV 0.05 2000.00 0.05 0.00 0.00
Off
Non-directional
OperationDir Operation mode of directionality - - -
Forward
Reverse
X1 Positive sequence reactance reach ohm 0.10 3000.00 0.01 0.00 0.00
R1 Positive seq. resistance for zone characteristic angle ohm 0.10 1000.00 0.01 0.00 0.00
X0 Zero sequence reactance reach ohm 0.10 9000.00 0.01 0.00 0.00
R0 Zero seq. resistance for zone characteristic angle ohm 0.50 3000.00 0.01 0.00 0.00
RFPP Fault resistance reach in ohm/loop, Ph-Ph ohm 1.00 3000.00 0.01 0.00 0.00
RFPE Fault resistance reach in ohm/loop, Ph-E ohm 0.01 9000.00 0.01 0.00 0.00
OperationPP Operation mode Off/On of Phase-Phase loops - ON - OFF - -
Timer tPP Operation mode Off/On of zoner timer, Ph-Ph - ON - OFF - -
tPP Time delay of trip, Ph-Ph s 0.000 60.000 0.001 - -
OperationPE Operation mode Off/On of Phase-Earth loops - ON - OFF - -
Timer tPE Operation mode Off/On of zoner timer, Ph-E - ON - OFF - -
tPE Time delay of trip, Ph-E s 0.000 60.000 0.001 - -
IMinOpPP Minimum operate delta current for Phase-Phase loops %IB 10 30 1 - -
IMinOpPE Minimum operate phase current for Phase-Earth loops %IB 10 30 1 - -
IMinOpIN Minimum operate residual current for Phase-Earth loops %IB 5 30 1 - -
21 ZONA 5 ( ZM5 )
ZMQPDIS
Operat Operation on/off - ON - OFF ON - ON
Ibase Base current, i,e. rated current A 1 99999 1 1.00 350 1.00 350
Ubase Base voltage, i.e. rated voltage kV 0.05 2000.00 0.05 100.00 138 100.00 138
Off
Non-directional
OperationDir Operation mode of directionality - Reverse - Reverse -
Forward
Reverse
X1 Positive sequence reactance reach ohm 0.10 3000.00 0.01 0.38 1.48 2.90 11.43
R1 Positive seq. resistance for zone characteristic angle ohm 0.10 1000.00 0.01 0.12 0.46 0.91 3.58
X0 Zero sequence reactance reach ohm 0.10 9000.00 0.01 1.21 4.77 9.35 36.86
R0 Zero seq. resistance for zone characteristic angle ohm 0.50 3000.00 0.01 0.31 1.21 2.37 9.34
RFPP Fault resistance reach in ohm/loop, Ph-Ph ohm 1.00 3000.00 0.01 1.27 5.00 13.12 51.73
RFPE Fault resistance reach in ohm/loop, Ph-E ohm 0.01 9000.00 0.01 1.90 7.50 17.80 70.18
OperationPP Operation mode Off/On of Phase-Phase loops - ON - OFF ON - ON -
Timer tPP Operation mode Off/On of zoner timer, Ph-Ph - ON - OFF ON - ON -
tPP Time delay of trip, Ph-Ph s 0.000 60.000 0.001 1.20 - 1.50 -
OperationPE Operation mode Off/On of Phase-Earth loops - ON - OFF ON - ON -
Timer tPE Operation mode Off/On of zoner timer, Ph-E - ON - OFF ON - ON -
tPE Time delay of trip, Ph-E s 0.000 60.000 0.001 1.20 - 1.50 -
IMinOpPP Minimum operate delta current for Phase-Phase loops %IB 10 30 1 20 - 20 -
IMinOpPE Minimum operate phase current for Phase-Earth loops %IB 10 30 1 20 - 20 -
IMinOpIN Minimum operate residual current for Phase-Earth loops %IB 5 30 1 - - - -
ZDRDIR
ArgNegRes Angle to blinder in second quadrant for forward direction Deg 90 175 1 115 - 115 -
ArgDir Angle to blinder in fourth quadrant for forward direction Deg 5 45 1 15 - 15 -
IMinOpPP Minimum operate delta current for Phase-Phase loops %IB 5 30 1 10 - 10 -
IMinOpPE Minimum operate phase current for Phase-Earth loops %IB 5 30 1 5 - 5 -
IBase Base current A 1 99999 1 1.00 350 1.00 350
UBase Base Voltage kV 0.05 2000.00 0.05 100.00 138 100.00 138
21 PHASE SELECTION WITH LOAD ENCROACHMENT
FDPSPDIS(Bas.par.gro.sett.for the PHS--)
IBase Base current, i,e. rated current A 1 99999 1 1.00 350.00 1.00 350.00
INBlockPP 3I0 limit for blocking phase-to-phase measuring loops %IPh 10 100 1 40 - -
INReleasePE 3I0 limit for releasing phase-to-earth measuring loops %IPh 10 100 1 20 - 40 -
RLdFw Forward resistive reach within the load impedance area ohm 1.00 3000.00 0.01 25.36 100.00 20.00
RLdRv Reverse resistive reach within the load impedance area ohm 1.00 3000.00 0.01 25.36 100.00 0.00
ArgLd Load angle determining the load impedance area Deg 5 70 1 30 - -
X1 Positive sequence reactance reach ohm 0.50 3000.00 0.01 26.45 104.30 26.45 104.30
X0 Zero sequence reactance reach ohm 0.50 9000.00 0.01 85.25 336.13 85.25 336.13
RFFwPP Fault resistance reach, Ph-Ph, forward ohm 0.50 3000.00 0.01 15.72 62.00 30.43 120.00
RFRvPP Fault resistance reach, Ph-Ph, reverse ohm 0.50 3000.00 0.01 15.72 62.00 30.43 120.00
RFFwPE Fault resistance reach, Ph-E, forward ohm 1.00 9000.00 0.01 21.30 84.00 21.30 84.00
RFRvPE Fault resistance reach, Ph-E, reverse ohm 1.00 9000.00 0.01 21.30 84.00 21.30 84.00
IMinOpPP Minimum operate delta current for Phase-Phase loops %IB 5 30 1 10 - 10 -
IMinOpPE Minimum operate phase current for Phase-Earth loops %IB 5 30 1 5 - 5 -
68 POWER SWING DETECTION
ZMRPSB_78
Operat Operation mode on/off - ON - OFF ON - -
X1InFw Inner reactive boundary, forward ohm 0.10 3000.00 0.01 25.36 100.00 25.36 100.00
R1LIn Line resistance for inner characteristic angle ohm 0.10 1000.00 0.01 5.07 20.00 5.07 20.00
R1FInFw Fault resist coverage to inner resistive line forward ohm 0.10 1000.00 0.01 25.36 100.00 25.36 100.00
X1InRv Inner reactive boundary, reverse ohm 0.10 3000.00 0.01 25.36 100.00 25.36 100.00
R1FInRv Fault resist line to inner resistive boundary, reverse ohm 0.10 1000.00 0.01 25.36 100.00 25.36 100.00
Oper.LdCh Operation of load discrimination characteristic - ON - OFF ON - -
RLdOutFw Outer resistive load boundary, forward ohm 0.10 3000.00 0.01 27.10 106.87 36.52 144.00
ArgLd Load angle determining the load impedance area Deg 5 70 1 30 - 30 -
RLdOutRv Outer resistive load boundary, reverse ohm 0.10 3000.00 0.01 27.10 106.87 36.52 144.00
kLdRFw Mult factor for inner resistive load boundary, forward mult 0.50 0.90 0.01 0.78 - 0.65 -
kLdRRv Mult factor for inner resistive load boundary, reverse mult 0.50 0.90 0.01 0.78 - 0.65 -
tP1 Timer for detection of initial power swing s 0.000 60.000 0.001 0.045 - 0.024 -
tP2 Timer for detection of subsequent power swing s 0.000 60.000 0.001 0.015 - 0.012 -
tW Waiting timer for activation of tP2 timer s 0.000 60.000 0.001 0.250 - 0.250 -
tH Timer for holding power swing START output s 0.000 60.000 0.001 0.500 - 0.500 -
tEF Timer for overcoming single-pole reclosing dead time s 0.000 60.000 0.001 3.000 - 3.000 -
tR1 Timer giving delay to inhibit by the residual current s 0.000 60.000 0.001 0.300 - 0.300 -
tR2 Timer giving delay to inhibit at very slow swing s 0.000 60.000 0.001 2.000 - 2.000 -
IMinOpPE Minimum operate current in % of IBase %IB 5 30 1 10 - 10 -
IBase Base setting for current level settings A 1 99999 1 1.00 350.00 1.00 350.00
21 Automatic switch onto fault logic (PSOF)
Operat Operation on/off - ON - OFF - -
Ibase Base current, i,e. rated current A 1 99999 1 0.00 0.00
Ubase Base voltage, i.e. rated voltage kV 0.05 2000.00 0.05 0.00 0.00
Impedance
Mode Mode of operation of SOFT Function - UI Level - -
UILvI&Imp
AutoInit Automatic switchonto fault initialization - ON - OFF - -
IPh< Current level for detection of dead line in % of Ibase %IB 1 100 1 0.00 0.00
UPh< Voltage level for detection of dead line in % of Ubase %UB 1 100 1 0.00 0.00
tDuration Time delay for UI detection s 0.000 60.000 0.001 - -
tSOFT Drop off delay time of switch onto fault function s 0.000 60.000 0.001 - -
tDLD Delay time for activation of dead line detection s 0.000 60.000 0.001 - -
51/67 Four step phase overcurrent protection (POCM, 51/67)
Bas.Gen.sett.for the TOC1-
- MeasType - DFT ; RMS RMS - RMS -
Bas.par.gr.sett.for the TOC1-
Operation Operation on/off - ON - OFF OFF - OFF -
51/67 _ 1
Off
Non-directional
DirMode1 Directional mode of step 1 - OFF - OFF -
Forward
Reverse
51N/6
Four step residual overcurrent protection (PEFM, 51N/67N)
7N
Bas.para.gr.set.for the TEF1-
Operation Operation on/off - ON - OFF ON - ON -
IBase Base setting for current values A 1 99999 1 1.00 350 1.00 350
UBase Base setting for voltage levels in kV kV 0.05 2000.00 0.01 100.00 138 100.00 138
IMinOpFund Min. fundamental frequency current level in % IBase %IB 1 2500 1 - - -
AngleRCA Relay Characteristic angle (RCA) Deg -180 180 1 65 - 65 -
polMethod polMethod - Voltage; Current; Dual Voltaje - Voltaje -
UPolMin UPolMin %UB 1 100 1 3 - 3 -
IPolMin IPolMin %IB 2 100 1 5 - 5 -
RNPol RNPol ohm 0.50 1000.00 0.01 5.00 - 5.00 -
XNPol XNPol ohm 0.50 3000.00 0.01 40.00 - 40.00 -
IN>Dir Operate residual current level for DirComp in % IBase %IB 1 100 1 10 - 10 -
2ndHarmStab 2nd harmonic restrain operation in % of INAMPL % 5 100 1 20 - 20 -
UseStartValue Current level blk at parallel transf (Step1,2,3 or 4) - IN1>, IN2>, IN3>, IN4> IN1> - IN1> -
BlkParTransf Enable blocking at parallel transformers - ON - OFF OFF - OFF -
Off
SOTF
SOTF SOTF operation mode - OFF - OFF -
UnderTime
SOTF+UnderTime
51N/67N _ 1
Off
Non-directional
DirMode1 Directional mode of step 1 - Forward - Forward -
Forward
Reverse

ANSI EI, VI, NI, MI, DT


L.T.E. inv
L.T.V. inv
L.T. inv
IEC Norm. IEC Norm.
Characteristic 1 Selection of time delay curve type for step 1 - IEC NI, VI, EI, S.T.I, L.T.I, DT - -
Invr. Invr.
Reserved
Programmable
RI type
RD type
IN1> Operate residual current level for step 1 in % of IBase %IB 1 2500 1 23 80.50 23 80.50
t1 Independent (definitive) time delay of step 1 s 0.000 60.000 0.001 0.00 - 0.00 -
k1 Time multiplier for the dependent time delay for step 1 - 0.05 999.00 0.01 0.13 - 0.13 -
IN1Mult Multiplier for operate current level for step 1 - 1.0 10.0 0.1 1.00 - 1.00 -
t1Min Minimum operate time for IEC IDMT curves for step 1 s 0.000 60.000 0.001 0.00 - 0.00 -
51/67 _ 2
Off
Non-directional
DirMode2 Directional mode of step 2 - OFF - OFF - Se usa para comparación direccional
Forward
Reverse

ANSI EI, VI, NI, MI, DT


L.T.E. inv
L.T.V. inv
L.T. inv
Characteristic 2 Selection of time delay curve type for step 2 - IEC NI, VI, EI, S.T.I, L.T.I, DT IEC DT - -
Reserved
Programmable
RI type
RD type
IN2> Operate residual current level for step 2 in % of IBase %IB 1 2500 1 12.00 42.00 0.00
t2 Independent (definitive) time delay of step 2 s 0.000 60.000 0.001 0.20 - -
k2 Time multiplier for the dependent time delay for step 2 - 0.05 999.00 0.01 0.05 - -
IN2Mult Multiplier for operate current level for step 2 - 1.0 10.0 0.1 1.00 - -
t2Min Minimum operate time for IEC IDMT curves for step 2 s 0.000 60.000 0.001 0.00 - -
50BF Breaker failure protection (RBRF, 50BF)
Operat Operation Off/On - On - Off OFF - OFF -
27/59 VOLTAGE PROTECTION
27 Two step undervoltage protection (PUVM, 27)
Bas.para.gr.set.for the TUV1-
Operat Operation - On - Off OFF - OFF -
27 - 1
Operat Operation STEP 1 - On - Off OFF - OFF -
59 Two step overvoltage protection (POVM, 59)
Basic.gene.set.for the TOV1-
- ConnType - PhG DFT; PhPh RMS; PhG RMS - -
Bas.para.gr.set.for the TOV1-
Operation Operation - On - Off - -
UBase Base setting for voltage levels in kV kV 0.05 2000.00 0.01 - -
59 - 1
Operat Operation STEP 1 - On - Off - -
Definite time
Inverse curve A
Characterist1 Operation characteristic selection, step 1 - Inverse curve B - -
Inverse curve C
Prog. inv. Curve
1 out of 3
OpMode1 Operation Mode - 2 out of 3 - -
3 out of 3
U1> U setting/start val (DT & IDMT) in % of UBase, step 1 %UB 1 200 1 - -
t1 Operate time delay in DT mode, step 1. s 0.000 60.000 0.001 - -
tReset1 Time delay in DT reset (s), step 1 s 0.000 60.000 0.001 - -
25 Synchrocheck and energizing check (RSYN, 25)
Operation Operation - On - Off - - Sincronismo lo realiza el UPD2
phase1, phase2, phase3
phase1-phase2
SelPhaseBus1 Select phase for bus1 - - -
phase2-phase3
phase3-phase1
phase1, phase2, phase3
phase1-phase2
SelPhaseBus2 Select phase for bus2 - - -
phase2-phase3
phase3-phase1
phase1, phase2, phase3
phase1-phase2
SelPhaseLine1 Select phase for line1 - - -
phase2-phase3
phase3-phase1
phase1, phase2, phase3
phase1-phase2
SelPhaseLine2 Select phase for line2 - - -
phase2-phase3
phase3-phase1
No voltage sel.
Double bus
CBConfig Select CB configuration - 1 1/2 bus CB - -
1 1/2 bus alt. CB
Tie CB
UBase Base voltage in kV kV 0.001 9999.999 0.001 0.00
PhaseShift Phase Shift Deg -180 180 5 - -
URatio Voltage Ratio - 0.20 5.00 0.01 - -
OperationSC Operation for synchronism check function Off/On - On - Off - -
UHighBusSC Voltage high limit bus for synchrocheck in % of UBase %UB 50.0 120.0 1.0 - -
UHighLineSC Voltage high limit line for synchrocheck in % of UBase %UB 50.0 120.0 1.0 - -
UDiffSC U difference limit between bus and line in % of UBase %UB 2.0 50.0 1.0 - -
FreqDiffA Freq. Difference limit between bus and line Auto Hz 0.003 1.000 0.001 - -
FreqDiffM Freq. difference limit between bus and line Manual Hz 0.003 1.000 0.001 - -
PhaseDiffA F angle difference limit between bus and line Auto Deg 5 90 1 - -
PhaseDiffM F angle difference limit between bus and line Manual Deg 5 90 1 - -
tSCA Time delay output for synchrocheck for Auto operation s 0.000 60.000 0.001 - -
tSCM Time delay output for synchrocheck for Manual operation s 0.000 60.000 0.001 - -
AutoEnerg Automatic energizing check mode - Off, DLLB, DBLL, Both - -
ManEnerg Manual energizing check mode - Off, DLLB, DBLL, Both - -
ManEnerDBDL Manual dead bus, dead line energizing - On - Off - -
UHighBusEnerg Voltage high limit bus for energ. check in % of UBase %UB 50.0 120.0 1.0 - -
UHighLineEnerg Voltage high limit line for energ. check in % of UBase %UB 50.0 120.0 1.0 - -
ULowBusEnerg Voltage low limit bus for energ check in % of UBase %UB 50.0 120.0 1.0 - -
ULowLineEnerg Voltage low limit line for energ check in % of UBase %UB 50.0 120.0 1.0 - -
UMaxEnerg Maximum voltage for energizing in % of UBase %UB 80.0 140.0 1.0 - -
tAutoEnerg Time delay for automatic energizing check s 0.000 60.000 0.001 - -
tManEnerg Time delay for manual energizing check s 0.000 60.000 0.001 - -
79 Autorecloser (RREC, 79)
OFF
Operation Operation - External ctrl - -
ON
NoOfShots Max number of reclosing shots 1-5 - 1, 2, 3, 4, 5 - -
3 phase, 1/2/3ph
Restriction of fault type 1/2ph, 1ph+1*2ph
ARMode - - -
for shot 1 1/2ph+1*3ph
1ph+1*2/3ph
StartBy To be set ON if AR is to be started by CB open OFF
- - -
CBOpen position ON
CBAux Select the CB aux contact type NC/NO for NormClosed
- - -
ContType CBPOS input NormOpen
CBReadyType Select type of circuit breaker ready signal - CO, OCO - -
t1 1Ph Open time for shot 1, single-phase s 0.000 60.000 0.001 - -
t1 2Ph Open time for shot 1, two-phase s 0.000 60.000 0.001 - -
t1 3Ph Open time for shot 1, delayed reclosing 3ph s 0.000 60.000 0.001 - -
t1 3PhHS Open time for shot 1, high speed reclosing 3ph s 0.000 60.000 0.001 - -
t2 3Ph Open time for shot 2, three-phase s 0.00 60.00 0.01 - -
t3 3Ph Open time for shot 3, three-phase s 0.00 60.00 0.01 - -
t4 3Ph Open time for shot 4, three-phase s 0.00 60.00 0.01 - -
t5 3Ph Open time for shot 5, three-phase s 0.00 60.00 0.01 - -
tReclaim Duration of the reclaim time s 0.00 60.00 0.01 - -
tSync Maximum wait time for synchrocheck OK s 0.00 60.00 0.01 - -
Extended t1 Extended open time for loss of permissive channel - On - Off - -
tExtended t1 Open time extended by this value if Extended t1 is true s 0.000 60.000 0.001 - -
tInhibit Inhibit reclosing reset time s 0.000 60.000 0.001 - -
tTrip Maximum trip pulse duration s 0.000 60.000 0.001 - -
CutPulse Shorten closing pulse at a new trip - On - Off - -
tPulse Duration of the circuit breaker closing pulse s 0.000 60.000 0.001 - -
OFF
Follow CB Advance to next shot if CB has been closed during dead time - - -
ON
tCBClosedMin Min time that CB must be closed before newseq allows s 0.00 60.00 0.01 - -
AutoCont Continue with next recl-shot if breaker did not close - On - Off - -
tAutoContWait Wait time after CloseCom before proc to next shot s 0.000 60.000 0.001 - -
Unsuc Unsuccessful closing signal obtained by checking NoCBCheck
- - -
ClByCBChk CB position CB check
BlockBy OFF
Block AR at unsuccessful reclosing - - -
UnsucCl ON
tUnsucCl Wait time for CB before ind unsuccessful/successful s 0.00 60.00 0.01 - -
Priority Priority selection between adjacent terminals - None, Low, High - -
tWaitForMaster Maximum wait time for release from Master s 0.00 60.00 0.01 - -
85 Scheme communication logic for distance protection (PSCH, 85)
Operation Operation - On - Off - -

Off, Intertrip, Permissive UR, Permissive


SchemeType Scheme Type - - -
OR, Blocking

tCoord Co-ordination time for blocking communication scheme s 0.000 60.000 0.001 - -
tSendMin Minimum duration of a carrier send signal s 0.000 60.000 0.001 - -
Unblock Operation mode of unblocking logic - Off, NoRestart, Restart - -
tSecurity Security timer for loss of carrier guard detection s 0.000 60.000 0.001 - -
85 Scheme communication logic for residual overcurrent protection (PSCH, 85)
Operation Operation - On - Off - -

Off, Intertrip, Permissive UR, Permissive


SchemeType Scheme Type - - -
OR, Blocking

tCoord Communication scheme coordination time s 0.000 60.000 0.001 - -


tSendMin Minimum duration of a carrier send signal s 0.000 60.000 0.001 - -
Unblock Operation mode of unblocking logic - Off, NoRestart, Restart - -
tSecurity Security timer for loss of carrier guard detection s 0.000 60.000 0.001 - -
OBSERVACIONES
Se usa para comparación direccional

Sincronismo lo realiza el UPD2