*** Steel pipe used in manual and open systems shall be galvanized on its internal and external
surfaces.
**** all pipe greater than 50 DN Will not use screw union .
*** only one-piece reducing fitting shall be used wherever a change is made in the size of pipe.
*** Hexagonal or face bushings shall be permitted for use in reducing the size of openings of fittings
**** Rubber-gasketed fittings shall be permitted to be used to connect pipe in fire-exposed areas where
the water spray system is automatically controlled.
Control valves shall not close in less than 5 seconds when operated at maximum possible speed from
the fully open position.
Quantity of the spray nozzle depend on the flow rate and k factor of each type as below
MINIMAX
RD
Vinking