You are on page 1of 8

1

Andover
Continuum Software and Firmware
Compatibility Matrix
Date: September, Version 2.01
2016

    CyberStation/web.Client Software Version


    2.01
  DB Server OS
MS Win Svr 2008 (SP2), MS Win Svr 2008 R2 (SP1)
Windows Server 2012 R2 Essentials SP1
  MS SQL2008 (SP3), MS SQL 2008 R2 (SP2)
Configuration

MS SQL 2012 (SP2), MS SQL 2014 (SP1)


SQL Version
Standard & Enterprise Editions
LAN

MS Win 7 Pro (SP1) 11, MS Win 7 Ultimate (SP1)11, M S W i n 1 0 ( P r o f e s s i o n a l o r


CyberStation
E n t e r p r i s e ) 11, MS Win Svr 2008 (SP2),
PC OS
MS Win Svr 2008 R2 (SP1), MS Win Svr 2012 R2
  MS Win 7 Pro (SP1)11, MS Win 7 Ultimate (SP1)11, M S W i n 1 0 ( P r o f e s s i o n a l o r
E n t e r p r i s e ) 11
web.Client
Win Svr 2008 (SP2), Win Svr 2008 R2 (SP1), MS Win Svr 2012 R2
Server OS
.NET v2.0 & .NET v3.5 SP1, .NET 4.0, .NET 4.5

  SQL Version MS SQL Express 2005 and 2012


Configuration
Single User

  CyberStation MS Win 7 Pro (SP1)11, MS Win 7 Ultimate (SP1)11, MS Win 10 ( P r o f e s s i o n a l o r E n t e r p r i s e ) 11


SU (Cyber / Win Svr 2008 (SP2), Win Svr 2008 R2 (SP1), MS Win Svr 2012 R2
DB Server OS) .NET v2.0 & .NET v3.0 (Video Only), .NET 4.0, .NET 4.5

  web.Client SU
MS Win 7 Pro (SP1)11, MS Win 7 Ultimate (SP1)11, MS Win 10 ( P r o f e s s i o n a l o r E n t e r p r i s e ) 11
(CyberStation,
Win Svr 2008 (SP2), Win Svr 2008 R2 (SP1), MS Win Svr 2012 R2 Essentials
web.Client
.NET v2.0 & .NET v3.5 SP1, .NET 4.0
Server, &
DB Server OS)

  web.Client: MS Win 7 Pro (SP1)11, MS Win 7 Ultimate (SP1)11, MS Win 10 ( P r o f e s s i o n a l o r E n t e r p r i s e ) 11


Browser PC Win Svr 2008 (SP2), Win Svr 2008 R2 (SP1), MS Win Svr 2012 R2 Essentials
OS .NET v2.0 & .NET v3.0 (Video Only), .NET 4.0, .NET 4.5
  web.Client:
IE 10 and IE 11 (32 bit only)
Browser
Virtual CyberStation VSphere 5.5, 6.0
Machine
Support and web.Client Note: requires software license, must comply to minimum system requirements.

Note: ALL Andover Continuum workstations and web.Client Application Servers must be at the exact same software rev.

For all machines with CyberStation or web.Client software installed, both 32 bit and 64 bit environments are supported.

SQL Express 2012 support requires Windows 7 SP1, Windows Server 2008 R2 SP1 and Windows Server 2008 SP2

PA-00501 Software and Firmware Compatibility Matrix


 
2

Andover Versions 2.01


Continuum
(cont’d)

  Compatible Firmware Versions


NetController II 2.18, 9
ACX Series (5720/5740) 1.18, 17
CX Controllers 1.5x
CX 9702 1.x
bCX1-CR-INF (Infinet) 1.0, 1.1, 1.24
i2 Controllers (Infinet) 3.x (3.3 to use xPUI4 Expansion module)
i2 Controllers-WL (Wireless Only Infinet) 3.5
Exceptions
i2608, i2624, i2804, i2814,
3.x
i2885, i2887
i2865-V, i2866-V, i2885-V 3.5
i2 Controllers-WL
3.5
(Wireless Only Infinet)
Infinet Controllers 1.4 or greater
Exceptions
ACX 700 1.5x
ACX 780 1.5x
DCX 250 2.16
LSX 280 Not supported
bCX1-R, bCX1-CR (BACnet) 4.3, 4.4, 4.5 5,10
b4920 4.2
b3 Controllers (BACnet) 4.3, 4.4, 4.5
Exceptions
b3865-V, b3866-V, b3885-V 4.5
b3 Controllers-WL
4.5
(Wireless Only BACnet)

1. Not applicable 10. Minimum v4.500047 required for XDriver Support on the
BACnet bCX1-4040, & minimum v1.82.
2. Not applicable
3. Not applicable 11. Remote Access Service (RAS) not supported on MS
Windows machines.
4. v1.2 required on bCX1-CR-INF to set comm. port
for Wireless. 12. Not applicable
13. Not applicable
5. v4.5 required on bCX1-R/bCX1-CR to set comm.
port for Wireless. 14. Not applicable
6. Not applicable 15. Not applicable
7. Not applicable 16. SQL Native Client version 10 and above are not supported.

8. v1.74 SP2 required for hardware support. 17. v1.100041 required on ACX-2 series (5740 and 5720) to
support Extended Custom card format
Does not support v1.8x features.
9. Special IOU module firmware versions required for FIPS
support: AC-1 and AC-1A: Minimum v25; AC-1 Plus:
Minimum v29.

Note: Only the bCX1 supports xPBA4 and xPBD4 Expansion Modules. For xPUI4 support, i2 controllers must be at v3.3 and b3 controllers
must be at least at v4.3.

The information on this chart is furnished for informational purposes only, is subject to change without notice, and should not be
construed as a commitment by Schneider Electric.

PA-00501 Software and Firmware Compatibility Matrix


 
1
Andover
Continuum Software and Firmware
Compatibility Matrix
Versions 2.0/2.0 SP1

    CyberStation/web.Client Software Version


    2.0/ 2.0 SP1
  DB Server OS
Win Svr 2003 (SP2), Win Svr 2003 R2,
MS Win Svr 2008 (SP2)12,, MS Win Svr 2008 R2 (SP1), Windows Server 2012 (SP1)
  MS SQL 2005 (SP4),
SQL Version MS SQL 2008 (SP3)16, MS SQL 2008 R2 (SP2)16, MS SQL 2012 (SP2)
Configuration

Standard & Enterprise Editions


LAN

MS Win 7 Pro (SP1) 11, MS Win 7 Ultimate (SP1)11,


CyberStation
MS Win Svr 2008 (SP2), MS Win Svr 2008 R2 (SP1)
PC OS
.NET v2.0 & .NET v3.5 SP1, .NET 4.0

  MS Win 7 Pro (SP1)11, MS Win 7 Ultimate (SP1)11,


(up to 2 connections)
web.Client
Win Svr 2003 (SP2), Win Svr 2003 R2 (SP2), Win Svr 2008 (SP2), Win Svr 2008 R2 (SP1)
Server OS
(up to 25 connections)
.NET v2.0 & .NET v3.5 SP1, .NET 4.0

  SQL Version MS SQL Express 2005 and 2012


  CyberStation MS Win 7 Pro (SP1)11, MS Win 7 Ultimate (SP1)11,
Configuration
Single User

SU (Cyber / Win Svr 2003 (SP2), Win Svr 2003 R2 (SP2), Win Svr 2008 (SP2), Win Svr 2008 R2 (SP1)
DB Server OS) .NET v2.0 & .NET v3.0 (Video Only), .NET 4.0

  web.Client SU
MS Win 7 Pro (SP1)11, MS Win 7 Ultimate (SP1)11,
(CyberStation,
Win Svr 2003 (SP2), Win Svr 2003 R2 (SP2), Win Svr 2008 (SP2), Win Svr 2008 R2 (SP1)
web.Client
(up to 2 connections)
Server, &
.NET v2.0 & .NET v3.5 SP1, .NET 4.0
DB Server OS)

  web.Client: MS Win 7 Pro (SP1)11, MS Win 7 Ultimate (SP1)11,


Browser PC Win Svr 2003 (SP2), Win Svr 2003 R2 (SP2), Win Svr 2008 (SP2), Win Svr 2008 R2 (SP1)
OS .NET v2.0 & .NET v3.0 (Video Only), .NET 4.0
  web.Client:
IE 9.0, IE 10, and IE 11 (32 bit only)
Browser
Virtual CyberStation VSphere 5.5, 6.0
Machine
Support and web.Client Note: requires software license, must comply to minimum system requirements.

Note: ALL Andover Continuum workstations and web.Client Application Servers must be at the exact same software rev.

For all machines with CyberStation or web.Client software installed, both 32 bit and 64 bit environments are supported.

SQL Express 2012 support requires Windows 7 SP1, Windows Server 2008 R2 SP1 and Windows Server 2008 SP2

PA-00501 Software and Firmware Compatibility Matrix


 
2

Andover Versions 2.0


Continuum
(cont’d)

  Compatible Firmware Versions


NetController II 2.18, 9
ACX Series (5720/5740) 1.18, 17
CX Controllers 1.5x
CX 9702 1.x
bCX1-CR-INF (Infinet) 1.0, 1.1, 1.24
i2 Controllers (Infinet) 3.x (3.3 to use xPUI4 Expansion module)
i2 Controllers-WL (Wireless Only Infinet) 3.5
Exceptions
i2608, i2624, i2804, i2814,
3.x
i2885, i2887
i2865-V, i2866-V, i2885-V 3.5
i2 Controllers-WL
3.5
(Wireless Only Infinet)
Infinet Controllers 1.4 or greater
Exceptions
ACX 700 1.5x
ACX 780 1.5x
DCX 250 2.16
LSX 280 Not supported
bCX1-R, bCX1-CR (BACnet) 4.3, 4.4, 4.5 5,10
b4920 4.2
b3 Controllers (BACnet) 4.3, 4.4, 4.5
Exceptions
b3865-V, b3866-V, b3885-V 4.5
b3 Controllers-WL
4.5
(Wireless Only BACnet)

9. Not applicable 16. Minimum v4.500047 required for XDriver Support on the
10. Not applicable BACnet bCX1-4040, & minimum v1.82.

11. Not applicable 17. Remote Access Service (RAS) not supported on MS
Windows 7 machines.
12. v1.2 required on bCX1-CR-INF to set
comm. port for Wireless. 18. Not applicable
19. Not applicable
13. v4.5 required on bCX1-R/bCX1-CR to set
comm. port for Wireless. 20. Not applicable
14. Not applicable 21. Not applicable
15. Not applicable 22. SQL Native Client version 10 and above are
16. v1.74 SP2 required for hardware not supported.
18. SQL Native Client version 10 and above are not supported.
support. Does not support v1.8x
19. v1.100041 required on ACX-2 series (5740 and 5720) to
features.
support Extended Custom card format
9. Special IOU module firmware versions required for FIPS
support: AC-1 and AC-1A: Minimum v25; AC-1 Plus:
Minimum v29.

Note: Only the bCX1 supports xPBA4 and xPBD4 Expansion Modules. For xPUI4 support, i2 controllers must be at v3.3 and b3 controllers
must be at least at v4.3.

The information on this chart is furnished for informational purposes only, is subject to change without notice, and should not be
construed as a commitment by Schneider Electric.
PA-00501 Software and Firmware Compatibility Matrix
 
3

Andover
Continuum Software and Firmware
Compatibility Matrix
Versions 1.94 SP1

    CyberStation/web.Client Software Version


    1.94 SP1
  DB Server OS
Win Svr 2003 (SP2), Win Svr 2003 R2,
MS Win Svr 2008 (SP2)12,, MS Win Svr 2008 R2 (SP1)
  MS SQL 2005 (SP4),
SQL Version MS SQL 2008 (SP3)16, MS SQL 2008 R2 (SP2)16, MS SQL 2012 (SP1)
Configuration

Standard & Enterprise Editions


LAN

Win XP Pro (SP3), MS Win 7 Pro (SP1) 11, MS Win 7 Ultimate (SP1)11,
CyberStation
MS Win Svr 2008 (SP2), MS Win Svr 2008 R2 (SP1)
PC OS
.NET v2.0 & .NET v3.5 SP1, .NET 4.0

  Win XP Pro (SP3), MS Win 7 Pro (SP1)11, MS Win 7 Ultimate (SP1)11,


(up to 2 connections)
web.Client
Win Svr 2003 (SP2), Win Svr 2003 R2 (SP2), Win Svr 2008 (SP2), Win Svr 2008 R2 (SP1)
Server OS
(both up to 25 connections)
.NET v2.0 & .NET v3.5 SP1, .NET 4.0

  SQL Version MS SQL Express


  Win XP Pro (SP3),
Configuration

CyberStation
Single User

MS Win 7 Pro (SP1)11, MS Win 7 Ultimate (SP1)11,


SU (Cyber /
Win Svr 2003 (SP2), Win Svr 2003 R2 (SP2), Win Svr 2008 (SP2), Win Svr 2008 R2 (SP1)
DB Server OS)
.NET v2.0 & .NET v3.0 (Video Only), .NET 4.0

web.Client SU Win XP Pro (SP3),


(CyberStation, MS Win 7 Pro (SP1)11, MS Win 7 Ultimate (SP1)11,
web.Client Win Svr 2003 (SP2), Win Svr 2003 R2 (SP2), Win Svr 2008 (SP2), Win Svr 2008 R2 (SP1)
Server, & (up to 2 connections)
DB Server OS) .NET v2.0 & .NET v3.5 SP1, .NET 4.0

  web.Client:
Win XP Pro (SP3),
MS Win 7 Pro (SP1)11, MS Win 7 Ultimate (SP1)11,
Browser PC
Win Svr 2003 (SP2), Win Svr 2003 R2 (SP2), Win Svr 2008 (SP2), Win Svr 2008 R2 (SP1)
OS
.NET v2.0 & .NET v3.0 (Video Only), .NET 4.0

  web.Client:
MS IE 8.0, IE 9.0
Browser

Note: ALL Andover Continuum workstations and web.Client Application Servers must be at the exact same software rev.

For all machines with CyberStation or web.Client software installed, both 32 bit and 64 bit environments are supported.

PA-00501 Software and Firmware Compatibility Matrix


4

Andover Versions 1.94 SP1


Continuum
(cont’d)

  Compatible Firmware Versions


NetController II 2.18, 9
ACX Series (5720/5740) 1.18, 17
CX Controllers 1.5x
CX 9702 1.x
bCX1-CR-INF (Infinet) 1.0, 1.1, 1.24
i2 Controllers (Infinet) 3.x (3.3 to use xPUI4 Expansion module)
i2 Controllers-WL (Wireless Only Infinet) 3.5
Exceptions
i2608, i2624, i2804, i2814,
3.x
i2885, i2887
i2865-V, i2866-V, i2885-V 3.5
i2 Controllers-WL
3.5
(Wireless Only Infinet)
Infinet Controllers 1.4 or greater
Exceptions
ACX 700 1.5x
ACX 780 1.5x
DCX 250 2.16
LSX 280 Not supported
bCX1-R, bCX1-CR (BACnet) 4.3, 4.4, 4.5 5,10
b4920 4.2
b3 Controllers (BACnet) 4.3, 4.4, 4.5
Exceptions
b3865-V, b3866-V, b3885-V 4.5
b3 Controllers-WL
4.5
(Wireless Only BACnet)

1. Not applicable 10. Minimum v4.500047 required for XDriver Support on the
BACnet bCX1-4040, & minimum v1.82.
2. Not applicable
3. Not applicable 11. Remote Access Service (RAS) not supported on MS
Windows 7 machines.
4. v1.2 required on bCX1-CR-INF to set comm. port
for Wireless. 12. Not applicable
13. Not applicable
5. v4.5 required on bCX1-R/bCX1-CR to set comm.
port for Wireless. 14. Not applicable
6. Not applicable 15. Not applicable
7. Not applicable 16. SQL Native Client version 10 and above are
not supported.
8. v1.74 SP2 required for hardware support.
Does not support v1.8x features. 17. v1.100041 required on ACX-2 series (5740 and 5720) to
support Extended Custom Card format
9. Special IOU module firmware versions required for FIPS
support: AC-1 and AC-1A: Minimum v25; AC-1 Plus:
Minimum v29.

Note: Only the bCX1 supports xPBA4 and xPBD4 Expansion Modules. For xPUI4 support, i2 controllers must be at v3.3 and b3 controllers
must be at least at v4.3.

The information on this chart is furnished for informational purposes only, is subject to change without notice, and should not be
construed as a commitment by Schneider Electric.

PA-00501 Software and Firmware Compatibility Matrix


 
5

Andover
Continuum Software and Firmware
Compatibility Matrix
Versions 1.94

    CyberStation/web.Client Software Version


    1.94
  DB Server OS
Win Svr 2003 (SP2), Win Svr 2003 R2,
MS Win Svr 2008 (SP2)12,, MS Win Svr 2008 R2 (SP1)
  MS SQL 2005 (SP4),
SQL Version MS SQL 2008 (SP3)16, MS SQL 2008 R2 (SP2)16
Configuration

Standard & Enterprise Editions


LAN

Win XP Pro (SP3), MS Win 7 Pro (SP1) 11, MS Win 7 Ultimate (SP1)11,
CyberStation
MS Win Svr 2008 (SP2), MS Win Svr 2008 R2 (SP1)
PC OS
.NET v2.0 & .NET v3.5 SP1

  Win XP Pro (SP3), MS Win 7 Pro (SP1)11, MS Win 7 Ultimate (SP1)11,


(up to 2 connections)
web.Client
Win Svr 2003 (SP2), Win Svr 2003 R2 (SP2), Win Svr 2008 (SP2) , Win Svr 2008 R2 (SP1)
Server OS
(both up to 25 connections)
.NET v2.0 & .NET v3.5 SP1

  SQL Version MS SQL Express


  Win XP Pro (SP3),
Configuration

CyberStation
Single User

MS Win 7 Pro (SP1)11, MS Win 7 Ultimate (SP1)11,


SU (Cyber /
Win Svr 2003 (SP2), Win Svr 2003 R2 (SP2), Win Svr 2008 (SP2), Win Svr 2008 R2 (SP1)
DB Server OS)
.NET v2.0 & .NET v3.0 (Video Only)

web.Client SU Win XP Pro (SP3),


(CyberStation, MS Win 7 Pro (SP1)11, MS Win 7 Ultimate (SP1)11,
web.Client Win Svr 2003 (SP2), Win Svr 2003 R2 (SP2), Win Svr 2008 (SP2), Win Svr 2008 R2 (SP1)
Server, & (up to 2 connections)
DB Server OS) .NET v2.0 & .NET v3.5 SP1

  web.Client:
Win XP Pro (SP3),
MS Win 7 Pro (SP1)11, MS Win 7 Ultimate (SP1)11,
Browser PC
Win Svr 2003 (SP2), Win Svr 2003 R2 (SP2), Win Svr 2008 (SP2), Win Svr 2008 R2 (SP1)
OS
.NET v2.0 & .NET v3.0 (Video Only)

  web.Client:
MS IE 8.0
Browser

Note: ALL Andover Continuum workstations and web.Client Application Servers must be at the exact same software rev.

For all machines with CyberStation or web.Client software installed, both 32 bit and 64 bit environments are supported.

PA-00501 Software and Firmware Compatibility Matrix


6

Andover Versions 1.94


Continuum
(cont’d)

  Compatible Firmware Versions


NetController II 2.18, 9
ACX Series (5720/5740) 1.18, 17
CX Controllers 1.5x
CX 9702 1.x
bCX1-CR-INF (Infinet) 1.0, 1.1, 1.24
i2 Controllers (Infinet) 3.x (3.3 to use xPUI4 Expansion module)
i2 Controllers-WL (Wireless Only Infinet) 3.5
Exceptions
i2608, i2624, i2804, i2814,
3.x
i2885, i2887
i2865-V, i2866-V, i2885-V 3.5
i2 Controllers-WL
3.5
(Wireless Only Infinet)
Infinet Controllers 1.4 or greater
Exceptions
ACX 700 1.5x
ACX 780 1.5x
DCX 250 2.16
LSX 280 Not supported
bCX1-R, bCX1-CR (BACnet) 4.3, 4.4, 4.5 5,10
b4920 4.2
b3 Controllers (BACnet) 4.3, 4.4, 4.5
Exceptions
b3865-V, b3866-V, b3885-V 4.5
b3 Controllers-WL
4.5
(Wireless Only BACnet)

1. Not applicable 10. Minimum v4.500047 required for XDriver Support on the
BACnet bCX1-4040, & minimum v1.82.
2. Not applicable
3. Not applicable 11. Remote Access Service (RAS) not supported on MS
Windows 7 machines.
4. v1.2 required on bCX1-CR-INF to set comm. port
for Wireless. 12. Not applicable
13. Not applicable
5. v4.5 required on bCX1-R/bCX1-CR to set comm.
port for Wireless. 14. Not applicable
6. Not applicable 15. Not applicable
7. Not applicable 16. SQL Native Client version 10 and above are
not supported.
8. v1.74 SP2 required for hardware support.
Does not support v1.8x features. 16. SQL Native Client version 10 and above are not
supported.
9. Special IOU module firmware versions required for FIPS
support: AC-1 and AC-1A: Minimum v25; AC-1 Plus: 17. v1.100041 required on ACX-2 series (5740 and 5720) to
Minimum v29. support Extended Custom Card format

Note: Only the bCX1 supports xPBA4 and xPBD4 Expansion Modules. For xPUI4 support, i2 controllers must be at v3.3 and b3 controllers
must be at least at v4.3.

The information on this chart is furnished for informational purposes only, is subject to change without notice, and should not be
construed as a commitment by Schneider Electric

PA-00501 Software and Firmware Compatibility Matrix


 