Models:
5E/4EF
7.3E/6EF
TP-5985 10/02d
California Proposition 65
WARNING
Engine exhaust from this product contains chemicals
known to the State of California to cause cancer, birth
defects, or other reproductive harm.
NOTICE
Airborne particles. Notice Fuse replacement. Replace fuses
Can cause severe injury or with fuses of the same ampere rating
and type (for example: 3AB or 314,
blindness. NOTICE
ceramic). Do not substitute clear
Wear protective goggles and clothing glass-type fuses for ceramic fuses.
when using power tools, hand tools, This generator set has been
Refer to the wiring diagram when the
or compressed air. rewired from its nameplate voltage
ampere rating is unknown or
to
questionable.
Tightening the hardware. Flying
projectiles can cause severe injury NOTICE
or death. Loose hardware can cause Saltwater damage. Saltwater quickly
the hardware or pulley to release from 246242 deteriorates metals. Wipe up saltwater
the generator set engine and can cause on and around the generator set and
personal injury. Retorque all remove salt deposits from metal
crankshaft and rotor hardware after NOTICE
surfaces.
servicing. Do not loosen the crankshaft Voltage reconnection. Affix a notice
hardware or rotor thrubolt when making to the generator set after reconnecting
adjustments or servicing the generator the set to a voltage different from the
set. Rotate the crankshaft manually in voltage on the nameplate. Order
a clockwise direction only. Turning the voltage reconnection decal 246242
crankshaft bolt or rotor thrubolt from an authorized service
counterclockwise can loosen the distributor/dealer.
hardware.
This manual provides operation instructions for 5/7.3E The equipment service requirements are very important
and 4/6EF model generator sets. to safe and efficient operation. Inspect the parts often
and perform required service at the prescribed intervals.
Refer to the engine operation manual for generator set
Obtain service from an authorized service
engine scheduled maintenance information.
distributor/dealer to keep equipment in top condition.
This manual may be used for models not listed on the
front cover.
Before installing a marine generator set, obtain the
Information in this publication represents data available most current installation manual from your local
at the time of print. Kohler Co. reserves the right to distributor/dealer. Only qualified persons should
change this publication and the products represented install the generator set.
without notice and without any obligation or liability
whatsoever. x:in:001:002:a
Service Assistance
D Visit the Kohler Power Systems website at East China Regional Office, Shanghai
KohlerPowerSystems.com Phone: (86) 21 6288 0500
Fax: (86) 21 6288 0550
D Look at the labels and stickers on your Kohler product India, Bangladesh, Sri Lanka
or review the appropriate literature or documents India Regional Office
included with the product Bangalore, India
Phone: (91) 80 3366208
D Call toll free in the US and Canada 1-800-544-2444 (91) 80 3366231
Fax: (91) 80 3315972
D Outside the US and Canada, call the nearest regional
office Japan, Korea
North Asia Regional Office
Africa, Europe, Middle East Tokyo, Japan
London Regional Office Phone: (813) 3440-4515
Langley, Slough, England Fax: (813) 3440-2727
Phone: (44) 1753-580-771
Latin America
Fax: (44) 1753-580-036
Latin America Regional Office
Asia Pacific Lakeland, Florida, USA
Power Systems Asia Pacific Regional Office Phone: (863) 619-7568
Singapore, Republic of Singapore Fax: (863) 701-7131
Phone: (65) 264-6422 X:in:008:001a
2 3 7 10
4 8 11
1 6 9 12
5
13
14
29
15
16
17
28 18
20
19
21
SERVICE VIEW 23
27 26 25 24 22
30
ENGINE-END VIEW
ADV-6395-A
GY-250000-A
1. Electric choke (on carburetor) 18. Anticorrosion zinc anode
2. Carburetor/choke linkage 19. Seawater drain (remove plate)
3. Spark plugs (also one on nonservice side) 20. Seawater pump (water inlet)
4. Oil fill 21. Cooling air inlet
5. Overflow tube 22. Mixing elbow, water outlet/exhaust outlet (nonservice side)
6. Pressure cap (coolant fill location after draining coolant) 23. Fuel feed pump (fuel inlet)
7. Controller 24. Oil check
8. Start/Stop switch 25. Coolant drain (remove hose clamp to drain coolant)
9. Nameplate (top) 26. Oil drain valve
10. AC load lead connector (nonservice side) 27. Lube oil filter
11. Input fuse 28. Antidieseling solenoid (on carburetor)
12. Battery charging fuse 29. Air intake silencer/backfire flame arrestor
30. Coolant overflow bottle (daily coolant check/fill location)
13. AC circuit breaker
14. Remote start connector (nonservice side) Note: Consult installation drawings in Spec Sheet or Installation
15. Voltage regulator fuse Manual for fuel- and battery-connection points.
16. Hourmeter Note: Consult distributor/dealer or Service Manual for items
17. Heat exchanger not shown.
2.1 Prestart Checklist Fuel Level. Check the fuel level and keep the tank(s)
full to ensure adequate fuel supply.
To ensure continued satisfactory operation perform the
following checks or inspections before or at each Oil Level. Maintain the oil level at or near, not over, the
startup, as designated, and at the intervals specified in full mark on the dipstick.
the service schedule. In addition, some checks require
verification after the unit starts. Operating Area. Check for obstructions that could
block the flow of cooling air. Keep the air intake area
Air Inlets. Check for clean and unobstructed air inlets. clean. Do not leave rags, tools, or debris on or near the
generator set.
Air Shrouding. Check for securely installed and
positioned air shrouding. Seawater Pump Priming. Prime the seawater pump
before initial startup. To prime the pump: (1) close the
Backfire Flame Arrester. Check for a clean and seacock, (2) remove the hose from the water-filter
installed backfire flame arrester to prevent unfiltered air outlet, (3) fill the hose and seawater pump with clean
from entering the engine. water, (4) reconnect the hose to the water filter outlet,
and (5) open the seacock. Confirm seawater pump
Battery. Check for tight battery connections. Consult operation on startup as indicated by water discharge
the battery manufacturer’s instructions regarding from the exhaust outlet.
battery care and maintenance.
Coolant Level. Check the coolant level according to 2.2 Marine Inspection
the cooling system maintenance information.
Kohler Co. recommends that all boat owners have their
Exhaust System. Check for exhaust leaks and vessels—especially the exhaust system attached to the
blockages. Check the silencer and piping condition and generator set—inspected at the start of each boating
check for tight exhaust system connections. season by the local Coast Guard Auxiliary. If there is no
Coast Guard Auxiliary in the area, contact an authorized
Inspect the exhaust system components (exhaust Kohler distributor/dealer for the inspection.
manifold, mixing elbow, exhaust line, hose clamps,
m:op:001:003
silencer, and outlet flapper) for cracks, leaks, and
corrosion.
2.3 Angular Operation
D Check the hoses for softness, cracks, leaks, or dents.
See Figure 2-1 for angular operation limits for units
Replace the hoses as needed.
covered in this manual.
D Check for corroded or broken metal parts and replace
them as needed. Intermittent—
Continuous 3 minutes or less
D Check for loose, corroded, or missing clamps. 25_ 30_
Tighten or replace the hose clamps and/or hangers
as needed. Maximum value for all directions
Note: Close seacock if water enters the exhaust Hourmeter Meter records total generator set
operating hours for reference in
system. If water enters the exhaust system, maintenance scheduling.
close the seacock and drain the water from the
exhaust system at the silencer’s drain plug before
attempting to start the generator set. If excessive
cranking is a chronic problem, have the unit,
including the exhaust system, serviced by an
authorized Kohlerr distributor/dealer.
Before starting the generator set, 2.6.4 Stopping the Generator Set
operate the blower 4 minutes and
check the engine compartment for The following table describes the actions required to
gasoline vapors. stop the generator set.
WARNING
Rotating parts.
Can cause severe injury or death.
Accidental starting. Operate the generator set only when
Can cause severe injury or death. all guards, screens, and covers are in
place.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first Servicing the generator set when it is operating. Exposed
when disconnecting the battery. moving parts can cause severe injury or death. Keep
Reconnect the negative (--) lead last hands, feet, hair, clothing, and test leads away from the belts
when reconnecting the battery. and pulleys when the generator set is running. Replace
guards, screens, and covers before operating the generator
set.
Disabling the generator set. Accidental starting can
cause severe injury or death. Before working on the Sound shield removal. Exposed moving parts can cause
generator set or equipment connected to the set, disable the severe injury or death. The generator set must be operating
generator set as follows: (1) Place the generator set start/stop in order to perform some scheduled maintenance procedures.
switch in the STOP position. (2) Disconnect the power to the Be especially careful if the sound shield has been removed,
battery charger, if equipped. (3) Remove the battery cables, leaving the belts and pulleys exposed.
negative (--) lead first. Reconnect the negative (--) lead last (Sound-shield-equipped models only)
when reconnecting the battery. Follow these precautions to
prevent the starting of the generator set by the remote NOTICE
start/stop switch. Saltwater damage. Saltwater quickly deteriorates metals.
Wipe up saltwater on and around the generator set and
WARNING remove salt deposits from metal surfaces.
NOTICE
Hardware damage. The engine and generator set may use
both American Standard and metric hardware. Use the correct
size tools to prevent rounding of the bolt heads and nuts.
Hot engine and exhaust system.
Can cause severe injury or death. Annual Inspection. Kohler Co. recommends that all
Do not work on the generator set until boat owners have their vessels—especially the exhaust
it cools. system attached to the generator set—inspected at the
start of each boating season by their local Coast Guard
Servicing the exhaust system. Hot parts can cause Auxiliary. If there is no Coast Guard Auxiliary in the area,
severe injury or death. Do not touch hot engine parts. The contact an authorized Kohler distributor/dealer for the
engine and exhaust system components become extremely inspection.
hot during operation.
See the Safety Precautions and Instructions at the
beginning of this manual before attempting to service,
repair, or operate the generator set. Have an authorized
distributor/dealer perform generator set service.
Do not mix different oil brands. Incompatibility could Note: Do not operate the set if the oil level is below the
cause a breakdown of lubricating ingredients and Add mark on the dipstick or above the Full mark
reduce engine protection. on the dipstick.
4. Allow ample time for all oil to drain. Oil Filter Change Procedure
5. Close the oil-drain valve. 1. Loosen the oil filter by turning it counterclockwise.
Remove the oil filter and use rags to clean up
6. Remove the oil-fill cap. spilled oil. Dispose of the oil filter in an approved
manner.
7. Replace the engine oil filter according to the
service schedule and the procedure in 2. Clean the contact surface of the oil filter adapter.
Section 3.3.5.
3. Lightly lubricate the gasket surface of the new filter
8. Fill crankcase with oil. Section 1 shows the oil fill with fresh engine oil. Thread the filter on the
location. See Figure 3-1 for oil selection and adapter until the gasket makes contact and
Figure 3-3 for oil capacity. Replace the oil-fill cap. hand-tighten the filter an additional one-half turn.
Wash hands after any contact with engine oil.
9. Start the generator set and check for oil leaks.
Note: If also performing an oil change, skip steps 4
10. Stop the generator set. Check the oil level. Add oil, and 5 and go back to oil change procedure.
as necessary, to bring the level up to the Full mark.
4. Start the generator set and check for oil leaks.
Note: Too high an oil level causes high oil
consumption and engine carbonizing. Too 5. Stop the generator set. Check oil level. Add oil, as
low a level damages the engine. necessary, to bring level up to Full mark.
1. Loosen the hose clamp at the breather hose at the Inspecting the exhaust system. Carbon monoxide can
air silencer fitting and remove the hose. cause severe nausea, fainting, or death. For the safety of
the craft’s occupants, install a carbon monoxide detector.
2. Loosen the hose clamp attaching the air silencer Consult the boat builder or dealer for approved detector
assembly to the carburetor. location and installation. Inspect the detector before each
generator set use. In addition to routine exhaust system
3. Lift off the air silencer assembly. inspection, test the carbon monoxide detector per the
manufacturer’s instructions and keep the detector operational
4. Clean the assembly in evaporative solvent and at all times.
wipe clean. Allow to dry.
At the interval specified in the service schedule, inspect
5. Reassemble using the reverse sequence. the exhaust system components (exhaust manifold,
mixing elbow, exhaust line, hose clamps, silencer, and
outlet flapper) for cracks, leaks, and corrosion.
Maintain the coolant level in coolant recovery tank at 6. Fill the system with the recommended coolant.
approximately 1/4 full. Before filling the cooling system,
close all petcocks and tighten all hose clamps. Use a 7. Replace the pressure cap.
solution of 50% ethylene glycol and 50% clean,
softened water to inhibit rust/corrosion and prevent 3.7.2 Pressure Cap
freezing. Add additional coolant, as necessary, to the
coolant recovery tank. Periodically check the coolant Closed heat exchanger systems utilize a pressure cap
level on closed systems by removing the pressure cap. to raise the boiling point of the coolant, enabling higher
Do not rely solely on level in coolant recovery tank. Add operating temperatures. If the cap leaks, replace it with
fresh coolant until the level is just below the overflow a cap of the same rating. Find the pressure cap rating in
tube opening. Figure 3-5.
2. Remove the retaining cap and remove the reed 1. Mounting base TP-5856-3
2. Retaining cap
valve for inspection. See Figure 3-8. 3. Reed valve
3. Use a mild detergent to remove residue and Figure 3-8 Siphon Break
oxidation from the reed valve. m:sm:003:007
7 8
9
1 10
22
6
4 11
Waterline 20
21
16 12
19
15
17
13
18
14 TP-5586-3
2. Use a wire brush to remove the loose corrosion on 5. Start the generator set and check for leaks at the
the anticorrosion zinc anode. Replace the anode anticorrosion zinc anode location. The pump is
according to Figure 3-10 and Figure 3-11. operating if cooling water flows from the exhaust
outlet. If water is not discharging at the exhaust
outlet, see Prestart Checklist—Seawater Pump
Anticorrosion Zinc Anode Replacement
Priming.
Replace When
New Anode Percent of Zinc
Models Dimensions mm (in.) Remaining Is: 3.7.6 Seawater Outlet
5/7.3E and <50% of
9 (0.34) x 43 (1.7) Check the seawater outlet at the interval specified in the
4/6EF length/diameter
service schedule. See Figure 3-9 for location. Remove
Figure 3-10 Anticorrosion Zinc Anode (Plug) any obstructions to keep the outlet clear.
Measurements
3. Change the oil and oil filter; see Section 3.3.4—Oil 11. Keep spark plugs in their holes or seal spark plug
Change and Section 3.3.5—Oil Filter Change. holes with suitable threaded metal plugs.
4. Close the seacock and remove the hose at the 12. Seal the air inlet, exhaust pipe, and fuel tank cap
seacock. Place the hose in a container having with tape.
approximately 3.7-7.5 L (1-2 U.S. gallons) of
13. Disconnect and remove the battery. Place the
coolant/antifreeze. Kohler Co. recommends using
battery in a warm, dry location for the storage
an environmentally friendly potable antifreeze
period. Recharge the battery once a month to
such as PeakR RV/marine propylene glycol/water
maintain a full charge.
mix or equivalent.
14. Select a well-ventilated (not humid or dusty)
5. With a suitable container at the exhaust outlet, run
location to store the generator.
the generator set until coolant discharges at the
exhaust outlet or until depleting the coolant 15. Cover the entire unit with a dust cover.
mixture. Do not allow coolant mixture to flow into
waterways. Note: Run the generator set once a month
whenever possible.
6. Stop the generator set.
Section or
Publication
Starts hard
Excessive or
abnormal noise
Cranks but
does not start
No or low
output voltage
Stops
suddenly
Lacks power
Overheats
Low oil
pressure
High fuel
consumption
Does not
crank
Probable Causes Recommended Actions Reference*
Controller
Controller start/stop switch in the Move the controller start/stop switch to the START position. Section 2
x
STOP position
Section 4 Troubleshooting
Controller fuse blown Replace the blown controller fuse. If the fuse blows again, Section 2, W/D
x x x
troubleshoot the controller.[
x x Controller circuit breaker tripped Reset the controller circuit breaker. Section 2
Controller master or start/stop switch Replace the controller master or start/stop switch. —
x
inoperative
x Controller fault Troubleshoot the controller.[ Gen. S/M
x x Controller circuit board(s) inoperative Replace the controller circuit board. Gen. S/M
Cooling System
x x Air openings clogged Clean the air openings. —
x Impeller inoperative Replace the impeller Section 3
x x Seawater strainer clogged or restricted Clean the strainer. Section 3
High temperature shutdown Allow the engine to cool down. Then troubleshoot the cooling Sec. 3, Eng. O/M
x
system.
Low coolant level shutdown, if Restore the coolant to normal operating level. Section 3
x
equipped
x Coolant level low Restore the coolant to normal operating level. Section 3
x Thermostat inoperative Replace the thermostat. Eng. S/M
* Sec./Section—numbered section of this manual; ATS—Automatic Transfer Switch; Eng.—Engine; Gen.—Generator Set; I/M—Installation Manual; O/M—Operation Manual; S/M—Service Manual;
S/S—Spec Sheet; W/D—Wiring Diagram
[ Have an authorized service distributor/dealer perform this service.
TP-5985 10/02
Trouble Symptoms
TP-5985 10/02
Section or
Publication
Starts hard
Excessive or
abnormal noise
Cranks but
does not start
No or low
output voltage
Stops
suddenly
Lacks power
Overheats
Low oil
pressure
High fuel
consumption
Does not
crank
Probable Causes Recommended Actions Reference*
Electrical System (DC circuits)
Battery connections loose, corroded, Verify that the battery connections are correct, clean, and tight. Section 3
x x
or incorrect
Battery weak or dead Recharge or replace the battery. The spec sheet provides Section 3, S/S
x x
recommended battery CCA rating.
Engine harness connector(s) not Disconnect the engine harness connector(s) then reconnect it to W/D
x x
TP-5985 tight
locked10/02 the controller.
x Fault shutdown Reset the fault switches and troubleshoot the controller. Section 2
High exhaust temperature switch Replace the inoperative switch. Gen. S/M or W/D
x
inoperative
x x Starter/starter solenoid inoperative Replace the starter or starter solenoid. Eng. S/M
High water temperature switch Replace the inoperative switch. Gen. S/M or W/D
x
inoperative
x Faulty ground connection Clean and retighten the connection. —
Engine
Air cleaner/backfire flame arrestor Clean or replace the filter element. Section 2
x x x x
clogged
x x x x x Compression weak Check the compression.[ Eng. S/M
Engine overload Reduce the electrical load. See the generator set installation I/M
x x x x x
manual for wattage specifications.
Exhaust system leak Inspect the exhaust system. Replace the inoperative exhaust Section 3, I/M
x
system components.[
Exhaust system not securely installed Inspect the exhaust system. Tighten the loose exhaust system Section 3, I/M
x
components.[
x x Valve clearance incorrect Adjust the valves.[ Eng. S/M
x Vibration excessive Tighten all loose hardware. —
Ignition system inoperative Check the ignition system (ignition module, spark plugs, spark Eng. O/M
x x x
(gas/gasoline only) plug wires, etc.).
* Sec./Section—numbered section of this manual; ATS—Automatic Transfer Switch; Eng.—Engine; Gen.—Generator Set; I/M—Installation Manual; O/M—Operation Manual; S/M—Service Manual;
S/S—Spec Sheet; W/D—Wiring Diagram
[ Have an authorized service distributor/dealer perform this service.
Section 4 Troubleshooting
25
26
Trouble Symptoms
Section or
Publication
Starts hard
Excessive or
abnormal noise
Cranks but
does not start
No or low
output voltage
Stops
suddenly
Lacks power
Overheats
Low oil
pressure
High fuel
consumption
Does not
crank
Probable Causes Recommended Actions Reference*
Fuel System
x x Fuel tank empty or fuel valve shut off Add fuel and move the fuel valve to the ON position. —
Section 4 Troubleshooting
x x Fuel pressure insufficient (gas only) Check the fuel supply and valves.[ S/S, Gen. O/M
x x x x Fuel line restriction Check the fuel lines and fuel tank. Eng. O/M
x Antidieseling solenoid inoperative Replace the solenoid.[ Eng. S/M
x x x Stale or bad fuel. Incorrect type of fuel Replace fuel. Clean the carburetor. Sec. 3, Eng S/M
x x x Fuel feed pump inoperative Replace the fuel feed pump.[ Eng. S/M
Generator
AC output circuit breaker open Reset the breaker and check for AC voltage at the generator —
x
side of the circuit breaker.
Transfer switch test switch in the OFF Move the transfer switch test switch to the AUTO position. ATS O/M
x
position
Wiring, terminals, or pin in the exciter Check for continuity. Gen. S/M, W/D
x
field open
Main field (rotor) inoperative (open or Test and/or replace the rotor.[ Gen. S/M
x
grounded)
x Stator inoperative (open or grounded) Test and/or replace the stator.[ Gen. S/M
x Vibration excessive Tighten loose components.[ —
x x Voltage regulator out of adjustment Adjust the voltage regulator. Gen. S/M
Voltage regulator inoperative Replace the voltage regulator fuse, If the fuse blows again, Gen. S/M
x x
troubleshoot the voltage regulator.
Lube System
x x x Oil level low Restore the oil level. Inspect the generator set for oil leaks. Eng. O/M
x Low oil pressure shutdown Check the oil level. Eng. O/M
Low oil pressure (LOP) switch Replace the LOP switch. W/D
x
inoperative
Crankcase oil type incorrect for Change the oil. Use oil with a viscosity suitable for the operating Eng. O/M
x x x x
ambient temperature climate.
* Sec./Section—numbered section of this manual; ATS—Automatic Transfer Switch; Eng.—Engine; Gen.—Generator Set; I/M—Installation Manual; O/M—Operation Manual; S/M—Service Manual;
S/S—Spec Sheet; W/D—Wiring Diagram
[ Have an authorized service distributor/dealer perform this service.
TP-5985 10/02
Section 5 Wiring Diagrams
WARNING WARNING
The following list contains abbreviations that may appear in this publication.
A, amp ampere CG center of gravity fglass. fiberglass
ABDC after bottom dead center CID cubic inch displacement FHM flat head machine (screw)
AC alternating current CL centerline fl. oz. fluid ounce
A/D analog to digital cm centimeter flex. flexible
ADC analog to digital converter CMOS complementary metal oxide freq. frequency
adj. adjust, adjustment substrate (semiconductor) FS full scale
ADV advertising dimensional cogen. cogeneration ft. foot, feet
drawing Com communications (port) ft. lbs. foot pounds (torque)
AHWT anticipatory high water conn. connection ft./min. feet per minute
temperature cont. continued g gram
AISI American Iron and Steel CPVC chlorinated polyvinyl chloride ga. gauge (meters, wire size)
Institute crit. critical
ALOP anticipatory low oil pressure gal. gallon
CRT cathode ray tube gen. generator
alt. alternator CSA Canadian Standards
Al aluminum genset generator set
Association GFI ground fault interrupter
ANSI American National Standards CT current transformer
Institute Cu copper GND, ground
(formerly American Standards gov. governor
Association, ASA) cu. in. cubic inch
cw. clockwise gph gallons per hour
AO anticipatory only
CWC city water-cooled gpm gallons per minute
API American Petroleum Institute
cyl. cylinder gr. grade, gross
approx. approximate, approximately
D/A digital to analog GRD equipment ground
AR as required, as requested
DAC digital to analog converter gr. wt. gross weight
AS as supplied, as stated, as
suggested dB decibel HxWxD height by width by depth
ASE American Society of Engineers dBA decibel (A weighted) HC hex cap
ASME American Society of DC direct current HCHT high cylinder head temperature
Mechanical Engineers DCR direct current resistance HD heavy duty
assy. assembly deg., ° degree HET high exhaust temperature
ASTM American Society for Testing dept. department hex hexagon
Materials dia. diameter Hg mercury (element)
ATDC after top dead center DI/EO dual inlet/end outlet HH hex head
ATS automatic transfer switch DIN Deutsches Institut fur Normung HHC hex head cap
auto. automatic e. V. HP horsepower
aux. auxiliary (also Deutsche Industrie hr. hour
A/V audiovisual Normenausschuss) HS heat shrink
avg. average DIP dual inline package hsg. housing
AVR automatic voltage regulator DPDT double-pole, double-throw HVAC heating, ventilation, and air
AWG American Wire Gauge DPST double-pole, single-throw conditioning
AWM appliance wiring material DS disconnect switch HWT high water temperature
bat. battery DVR digital voltage regulator Hz hertz (cycles per second)
BBDC before bottom dead center E, emer. emergency (power source) IC integrated circuit
BC battery charger, battery EDI electronic data interchange ID inside diameter, identification
charging EFR emergency frequency relay IEC International Electrotechnical
BCA battery charging alternator e.g. for example (exempli gratia) Commission
BCI Battery Council International EG electronic governor IEEE Institute of Electrical and
BDC before dead center EGSA Electrical Generating Systems Electronics Engineers
BHP brake horsepower Association IMS improved motor starting
blk. black (paint color), block EIA Electronic Industries in. inch
(engine) Association in. H2O inches of water
blk. htr. block heater EI/EO end inlet/end outlet in. Hg inches of mercury
BMEP brake mean effective pressure EMI electromagnetic interference in. lbs. inch pounds
bps bits per second emiss. emission Inc. incorporated
br. brass eng. engine ind. industrial
BTDC before top dead center EPA Environmental Protection int. internal
Agency int./ext. internal/external
Btu British thermal unit
EPS emergency power system I/O input/output
Btu/min. British thermal units per minute
ER emergency relay IP iron pipe
C Celsius, centigrade
ES engineering special, ISO International Organization for
cal. calorie engineered special
CARB California Air Resources Board Standardization
ESD electrostatic discharge J joule
CB circuit breaker est. estimated
cc cubic centimeter JIS Japanese Industry Standard
E-Stop emergency stop k kilo (1000)
CCA cold cranking amps etc. et cetera (and so forth)
ccw. counterclockwise K kelvin
exh. exhaust kA kiloampere
CEC Canadian Electrical Code
cfh cubic feet per hour
ext. external KB kilobyte (210 bytes)
F Fahrenheit, female
cfm cubic feet per minute
Use the log below to keep a cumulative record of required services were performed. Enter hours to the
operating hours on your generator set and the dates nearest quarter hour.