BFM136 Branch-Feeder-MonitorTM

‰ Class1 Accuracy - including CTs


‰ 64
samples per cycle
‰ 3 Voltage Inputs (up to
480VAC panels)
‰ 36 Current Inputs
‰ Measuring range up to 400A
‰ Split Core CT (100A & 400A)
‰ Time-of-Use(TOU) metering
BFM 136
‰ Harmonics and Vectors
SATEC’s Branch-Feeder-MonitorTM (BFM) is our ‰ Integrates with eXpertManager
new generation energy management meter
designed for energy and demand monitoring, system and eXpertPower service
load profiling, and multi-tariff (TOU), multi- ‰ Multi-circuit energy reading
client billing applications. Each BFM monitors
‰ 8 MB Flash data storage
up to 12 three-phase circuits, 18 two-phase
circuits, 36 single-phase circuits, or any ‰ Event Log
combination thereof. This flexibility makes the ‰ 120-day daily load profile
BFM especially suitable for multi-tenant
facilities such as residential and office ‰ Real-time Clock
buildings, shopping malls, hotels, hospitals, ‰ Built-in RS485 (COM 1)
universities, supermarkets and data centers.
‰ Optional COM 2 Ethernet,
Ideal for both new and retrofit projects, the modem, RS485, external 900
BFM’s compact size is designed to easily fit into
existing panel boards, thus eliminating
MHz or 2.4 GHz RF wireless
expensive retrofitting costs or allocating extra ‰ Compact Design FEATURES & BENEFITS
space for the instrument. The BFM provides ƒ ANSI C12.16 and IEC 62053-21 compliance
the ideal solution for sub-metering applications ƒ Provides the complete set of energy and
and is designed to answer the monitoring and demand data for billing purposes
billing needs of multi-tenant facilities. ƒ Easy installation into existing electric panel
boards thanks to its compact design
The BFM monitors up to 36 current inputs via ƒ Multi-point energy and demand load profiling
external sensors. Each sensor measures and ƒ Communications Ports: standard RS485,
reports the current and power consumed by optional second RS232, RS485, Ethernet,
each of the branch circuits at the panel board. wireless RF Modem (ZIGBEE) or 56K Modem
For billing purposes, one can define single or ƒ Communications Protocols: Modbus
multiple circuits for each customer. This TCP/RTU/ASCII
flexibility allows one to simply reassign circuit ƒ Flash memory data storage requires no
groups to changing customers without battery backup
complicated wiring changes. Further, the ƒ Interval data and Time-of-Use (TOU)
building owner saves time and effort by capability
monitoring up to 36 circuits directly at the main ƒ Advanced and user friendly options for data
panel board or load center. access:
♦ Optional LCD display for local data access
The BFM’s programmable alarm system enables ♦ PAS: free configuration software support
one to take preventive maintenance steps to ♦ eXpertManager PQ SCADA system access, or
avoid unnecessary outages. SATEC also provides eXpertPowerTM: Internet access to data,
split-core current transformers and wireless from anywhere, anytime, featuring highly
communication options to simplify installation. advanced features for total energy
management and billing
ƒ Real-time waveform monitor feature allows
for quick and easy installation verification

Model CT126 Model CT236 Model CT4A6 Model CT3CT


Single CT 100A, 600V Single CT 100A, 600V Large Hole Single CT 400A, 600 V 3CT Strip 100A, 600V
Inner Diameter 12 mm Inner Diameter 23 mm Inner Diameter 26 mm Up to 12 units per BFM
Cable length 2.5 meters Cable length 2.5 meters Cable length 2.5 meters Cable length 2.5 meters
TM
BFM136 Branch-Feeder-Monitor

The BFM provides a variety of electrical data


such as per phase voltage and current, kW
total, kVAR total, kVA total, PF total, Freq,
kWH, kVARH, kVAH, demands and maximum
demands. It also captures billing usage data in
two formats, fixed rate or TOU based. The
data can be viewed on the BFM’s LCD display Sub-meter Configuration
(BFM136) or transferred via communication to
software applications for more sophisticated
analysis. The BFM allows easy integration with
Energy Management or SCADA systems via the
industry standard Modbus RTU/ASCII protocols.
Through communications, one can access all
measured parameters remotely and perform
device configuration.

Billing
Tariffs vary according to the type of consumers
- residential, commercial or industrial, and the
amount of electricity consumed. The BFM’s
TOU feature provides data in compliance with
the rates set by the local electricity supplier The BFM can be configured to monitor 12 3-
and in accordance with the specified voltage phase circuits, 18 2-phase circuits, 36 single-
level – high, medium, or low. The BFM phase circuits or any combination thereof. The
sub-meter configuration is performed through TOU Calendar
provides information on peak demands and
allows for the assessment of penalty if the an intuitive interface with the PAS software.
power factor falls below a level defined by the
local authority. Virtual totalization sub-meters
ƒ A minimum of 4 totalization sub-meters
TM
PAS Software, eXpertPower e-Service, ƒ Allows for automatic totalization of multiple
and eXpertManagerTM system sub-meters that belong to the same tenant
The BFM is bundled with PAS, our easy to use
software designed for configuring, viewing and BFM Measurement Parameters
analyzing data from our instruments. For more Once the sub-meters have been properly
advanced options, eXpertPowerTM, SATEC’s configured, each sub-meter provides the
web-based energy management e-service, and following measurement parameters:
eXpertManager provides real-time visibility and ƒ Real-time
reporting capability for the entire power systems ♦ Voltage and Current per sub-meter
over the Internet. ♦ Watts per phase and total sub-meter
♦ VARs per phase and total sub-meter
PAS Features ♦ VA per phase and total per sub-meter
ƒ Included with every BFM ♦ PF per phase and total per sub-meter TOU Daily Profiles
ƒ Easy to use remote configuration software ♦ Frequency
ƒ Supports off-line programming to allow easy ƒ Demands and Max. Demands
downloading of a standard configuration to ♦ V and I per phase
multiple instruments ♦ Total Watts per sub-meter
ƒ Supports scheduled polling, viewing of real- ♦ Total VARs per sub-meter
time data, and the automatic retrieval of ♦ Total VAs per sub-meter
load profile. ƒ Energy Measurements
♦ Wh Import per sub-meter
Bill Comparison via eXpertPowerTM ♦ VARh Import per sub-meter
The BFM provides eXpertPowerTM all the ♦ VAh per sub-meter
necessary data to perform bill comparisons. ƒ TOU Daily Load Profile
Facilities with several utility meters can utilize ♦ 8MB of Flash memory
eXpertPowerTM to combine meters for billing, ♦ Energy and Demand Tariff Profile
resulting in significant cost savings. ♦ 120-day capacity

Data Management with eXpertManager Time-of-Use (TOU)


The BFM136 integrates with SATEC's ƒ User-friendly programmable TOU schedule
eXpertManager system to provide a real time ƒ 4 energy / demand registers x 4 tariffs
data acquisition and control system that allows ƒ 4 seasons x 4 types of days
facility operators to manage data. ƒ 8 tariff changes per day
BFM136 Branch-Feeder-MonitorTM

Load Profile and Event Log


ƒ 8MB of non-volatile memory
ƒ 1 Event Log
ƒ 120-day daily load profile Communications INPUT SPECIFICATIONS
ƒ Daily energy profile for each tariff and total 2 independent and simultaneous connections Voltage:
ƒ Daily maximum demand profile for each ƒ Unique “Assignable Register Map” Direct Input: 120 / 240 /480 VAC
tariff and total ƒ Firmware upgrade via communications, Max. Voltage: 320 VLN / 544 VLL
ƒ Daily summary profile of all tariffs eliminating chip replacement PT Ratio: 1.0
ƒ Separate for each sub-meter COM1 Range: 0-600 VAC
ƒ Optically isolated RS485 port Burden: < 1.5W per phase
User Defined Setpoint Alarms ƒ Isolation: 2000VAC (IEC1010-1) Overload: 1000 VAC continuous
ƒ 4 setpoints per sub-meter ƒ Selectable baud rate to max. 115,200 2000 VAC for 1 second
♦ Over / Under Voltage ƒ Protocols supported: Modbus RTU/ASCII Isolation: 2.5kV RMS, 60Hz, 1 min.
♦ Over / Under Current COM2 Leakage current: < 0.005A per circuit
♦ Over / Under Frequency ƒ Optional RS232 port Impulse: 1.2/50uS 6kV
♦ Over kW Imp ƒ Isolation: 2000V RMS Wire size: 10 AWG max.
♦ Over kVA ƒ Selectable baud rate to max. 115,200 Current:
ƒ Protocol supported: Modbus RTU/ASCII Input ratings: 50A nominal/100A max.
ƒ Optional RS485 port Test current: 15A
ƒ Isolation: 2000V RMS Overload: 3000A for ½ cycle @ 60Hz
ƒ Selectable baud rate to max. 115,200 Burden: < 1VA per phase
ƒ Protocol supported: Modbus RTU/ASCII Isolation: 2.5kV RMS, 60 Hz, 1 min.
ƒ Optional Ethernet CT Ratio: 1-100
ƒ Transformer-isolated 10/100BaseT Range: 0-10000A
ƒ Connector: RJ45
ƒ Protocol supported: Modbus TCP
ƒ Optional Dial-up Modem Standards of Compliance:
ƒ Transformer-isolated 56KB modem UL Approved
ƒ Connector: RJ11 CE EMC: 89/336/EEC as amended by
ƒ Protocol supported: Modbus RTU/ASCII 92/31/EEC and 93/68/EEC
ƒ Optional RS485 port with eXternal Trio unit LVD: 73/23/EEC as amended by
ƒ 900 MHz, 1 Watt RF 93/68/EEC and 93/465/EEC
ƒ Protocol supported: Modbus RTU EN Harmonized standards to which
Setpoints System conformity is declared:
EN55011: 1991; EN 50082-1: 1992;
Power Quality Real-time clock EN61010-1: 1993; A2/1995
ƒ Real-time waveform monitor ƒ Accuracy: 1 minute per month @ 25°C EN50081-2: 1994 Generic Emission
ƒ Installation and wiring verification ƒ Time retained for a minimum of 24 hours, Standard – Industrial Environment
ƒ Harmonics and Phasor analysis for V, I and 1 week typical upon loss of power EN50082-2: 1995 Generic Immunity
Power via PAS Standard – Industrial Environment
ƒ Separate for each sub-meter EN55022:1994 Class A
Accuracy EN61000-4-2: 1995 Electrostatic
Voltage: 0.3% reading + 0.05% F.S. Discharge
Range: 0 to 600V EN61000-4-4: 1995 Electrical Fast
Current: 0.5% reading + 0.05% F.S. Transient
(1% to 100% F.S.) EN61000-4-8: 1993 Radio Frequency
Range: 0 to CT Primary Electromagnetic Field, Amplitude
Starting Current: 0.1% F.S. Modulated.
Frequency: 0.02% reading (50 or 60 Hz) ENV50140: 1995 (200Hz) Radio
PF: 1.0% F.S. (|PF| ≥ 0.5) Frequency Electromagnetic Field, Pulse
Watts: 1.0% reading + 0.02% F.S. Modulated
(|PF| ≥ 0.5) ENV50204: 1995 (900MHz)
-120.00 to +120.00 kW ENV50141: 1993 Radio Frequency
VARs: 1.0% reading + 0.02% F.S. Common Mode, Amplitude Modulated
Real-time Waveform Monitor (|PF| ≤ 0.9) ANSI C12.2 1998
-120.00 to +120.00 kVAR IEC 62053-21 Class 1S
Front Panel Display (BFM136) VAs: 1.0% reading + 0.02% F.S.
ƒ 2 x 16 character backlit LCD display (|PF| ≥ 0.5) MISCELLANEOUS
ƒ Auto-scroll feature 0 to 120.00 kVA Warranty:
ƒ 4 push buttons Wh: Class 1S as per IEC 62053-21: 2003 3-Year limited warranty
0 to +99,999,999.9 kWh
VARh: Class 1S as per IEC 62053-21:2003 Environmental Conditions
0 to +99,999,999.9 kVARh Operating Temp.: -20 to +60°C (-4 to 140°F)
VAh: Class 1S as per IEC 62053-21: 2003 Storage Temp.: -25 to +80°C (-13 to 176°F)
0 to 99,999,999.9 kVAh Humidity: 0 to 95% non-condensing

Model CTSC400 Model TRIO JR900-00-001-E00


Model CTSC100
400A Split core CT, 600V 900 MHz ISM Band
100A Split core CT, 600V
Up to 36 units per BFM 1 Watt, Half Duplex
Up to 36 units per BFM
Cable length 6 feet - JAN 09
Cable length 6 feet
TM
BFM
M136 B
Branch--Feeder--Monito
or
Optional COM 2 Com
mmunicatiion add on port
+
RS485 RS485 RS485

Tx Rx

RF RS232 NONE

Future 900MHz Model R2 M2


No COM
RS232 n
option

RS485 RS485 RS485

DIAL-UP
MODEM
TELEPHON ETHE
ERNET RS485/422

Model MOD
M Model ETH R4
Model R
dem
56K Mod Ethernet RS4855

TM
M
BFM Branch-Fee
eder-Monitor

6
BFM136

Options:

RATION
CALIBR
50 50Hz
60 60Hz
COM2 – second COM porrt
0 None
R2 RS232
R4 RS485
MODD 56K modem
ETH Ethernet
RFM RF Modem (future)
MOUNTTING
0 Wall mount
D DIN
ACCESSSORIES*
CT12
26 Single CT 100A A, 12 mm; QTY: 1-336
CT23
36T Single CT 100A A, 23 mm; QTY: 1-336
CT4A
A6 Single CT 400A A, 26 mm; QTY: 1-336
CTSC
C100 Single Split Core CT 100A, 0.6 in.; Qty: 1-36
CT3C
CT 3 CT Strip 1” (25mm) between CT T centers. QTY 1-12
2
CTSC400 Single Split Core CT 400A, 1 x 1.85 inches; Qty: 1-36

*The CTT assembly includes s) long color-coded wire cables with sn


s a 6-foot (2 meters nap
connecttor on one end for easy
e connection.

EXAMPLES:
60Hz-ETH-D
BFM136-6

SATEC Integrated Solutions


10 Millto on, NJ, 07083
own Court, Unio
US Toll Free:
F 1-888-657-2832
Tel: +1 (
(908) 686-9510 0
Fax: +1 (908) 686-952 20
Email: sa
ales@satecis.com
http://wwww.satecis.com

Revisio
on Date: Octobe
er 2008

You might also like