Abu Dhabi Airports Company PJSC Specification, Section 265120

NOTE
THIS ISSUE INCLUDES AN UPDATE OF A FULL SET OF
LUMINAIRE DATA SHEETS REQUIRED FOR THE FRONT OF
HOUSE LIGHTING, INCLUDING REVISED SPECIFICATIONS FOR
SIX LUMINAIRE TYPES AND UPDATE ON FINISHES. THESE
SHEETS WILL BE SUBJECT TO FURTHER UPDATE IN JANUARY
2015 AS PART OF BULLETIN 120.3 BUT ONLY TO COMPLETE THE
LUMINAIRE INSTALLATION DETAILS AND CROSS REFERENCES
WITH THE RESPECTIVE ARCHITECTURAL INFORMATION AND
SPECIFICATIONS.

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 1 of 231


Bulletin No. 145: Volume 3 of 4 (Rev.07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

SECTION 265120
ARCHITECTURAL FRONT OF HOUSE LIGHTING SPECIFICATION

1. GENERAL
1.1 RELATED DOCUMENTS DRAWINGS AND GENERAL PROVISIONS OF
THE CONTRACT, INCLUDING GENERAL AND SUPPLEMENTARY
CONDITIONS AND DIVISION 01 SPECIFICATION SECTIONS, APPLY TO
THIS SECTION.

A. These documents outline the design intent for the electric lighting. Where
design intent is unclear, the Contractor shall contact the Engineer in
writing prior to proceeding with the specific item that requires
clarification.

B. This specification supersedes all previous issues and shall be read in


conjunction with the following:-

 Section 260500: Common Works for Electrical Systems

 Section 262726: Wiring Devices

 Section 260519: Low-voltage Electrical Power Conductors and


Cables

 Section 265100: Interior Lighting

 Section 265150: Lighting and Electrical Insstallations in Utility


Areas

 Section 265600 Exterior Lighting for Curbs and Service Roads

 Section 265610 Exterior Lighting

 REP_LCS_0001 Lighting Control and Estidama Requirements

 Specification sections 92900, 95134, 95135 and 95400

1.2 STANDARDS COMPLIANCE

A. The Lighting and association Electrical installation shall comply with the
latest revised versions of all applicable laws, rules, regulations, standards,
codes and ordinances of the local Authorities Having Jurisdiction and
other requirements specified in other Specifications and Contract
Drawings.

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 2 of 231


Bulletin No. 145: Volume 3 of 4 (Rev.07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

B. Standards requirements particular to individual luminaire types are


indicated on the relevant luminaire specification sheet.

C. All equipment supplied shall also comply with the relevant manufacturing
standards inclusive of Requirements of Estidama.

D. Obtain the required permits from the local authorities, where applicable for
this work and pay for all fees required by the local for permits, inspections
and review, including special agency construction and operating permits, if
any. Make corrections in the work as required by the Engineer or
Authorities Having Jurisdiction to pass all such regulations.

E. All equipment and components shall be subject to the warranty terms and
conditions as set out in these specifications.

F. If any variants of standard luminaires are required, these shall be


developed by the manufacturer of the standard luminaire, unless otherwise
specifically stated and approved by the Engineer, and shall be
manufactured to the same standards as the equivalent standard luminaire.

G. Two copies of all working drawings of proposed variants dimensioned in


mm, shall be supplied to the Engineer for approval prior to fabrication.

H. Notwithstanding the above, the manufacturer shall remain responsible for


ensuring compliance with relevant standards, the accuracy of the
information shown on his drawings at all times and for ensuring that the
equipment shown fulfils the requirements of this specification.

I. The Engineer shall not accept the installation of non-approved luminaires.

1.3 WORK INCLUDED

A. Contractor shall provide all Labour, Materials, Contractor’s Equipment


and Plant to fully execute the requirements to furnish, deliver, and install
the Works as expressly described in the Drawings and Specification, or
implied therefrom, and in accordance with the Contract. It is the intent of
this Specification section that the work performed pursuant hereto be
complete and acceptable in every respect for its intended purpose. It is
further required that the provisions of this Specification section shall be
complementary to, and shall be correlated with, the requirements of the
Contract. Nothing in this specification section shall limit the scope of work
as required by the Contract.

1.4 SUBMITTALS

A. The Contractor shall submit shop drawings, technical data, samples and
prototypes as specifically instructed below. Submittals shall include but
not limited to:

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 3 of 231


Bulletin No. 145: Volume 3 of 4 (Rev.07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

1. Manufacturer’s dimensioned scale drawings showing in complete


detail the fabrication of all lighting luminaires including overall
and detail dimensions, finishes, metal thickness, glass thickness,
type, fabrication methods, support method, ballasts, transformers,
sockets, type of shielding, reflectors, trims, hinges, gaskets,
provisions for re-lamping and all other information to show
compliance with the contract documents.
2. Certified laboratory test data and reports including photometric
data measured in accordance with BS EN 13032-1. Refer to
Section 2.3 for additional requirements for LED products.
3. Technical datasheets for all luminaire components:
a. Luminaire
b. Lamps
c. Control gear / drivers / ballasts
4. Installation instructions.
5. Maintenance and operating instructions, including tools required,
details of cleaning methods and types / specification of appropriate
materials, replacement parts identification list, and final as-built
shop drawing in accordance to Division 01 Specifications
6. All drawings shall clearly indicate the contract drawing number
used as a reference in the development of the shop drawings, the
name of the project, Employer, Contractor, Sub-contractor,
Architect and Engineer .
B. Project Lighting Calculations

1. The Contractor shall submit lighting calculations for review and


approval by the Engineer. These calculations shall include:
a. Illuminance plots at floor level in tabular and lux contour
lines.
b. Average, maximum, minimum illuminance and uniformity
for each calculated area.
c. Day 1 calculations, defined as the initial illuminance
without maintenance factors.
d. Future date calculations, defined as the maintained
illuminance with maintained factors applied.
e. Details of the maintenance factors used and the
methodology of their calculation. For LED products
reference to luminaire lifetime should be made.
2. Calculations shall be produced using Dialux 4.12 or later, or other
software approved by the Engineer.

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 4 of 231


Bulletin No. 145: Volume 3 of 4 (Rev.07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

3. Photometric data files shall be provided to the Engineer for


verification.
4. Spacing between calculation points shall be as per IESNA
standards or equivalent European or International Standards.
C. The above submittal requirements apply to all luminaires. Additional
submittal requirements for LED products are set out in Section 2.3.

1.5 SAMPLES

A. The Contractor is to provide working samples, with a cord and plug and
specified lamp(s), of all luminaires for approval and/or installation in
mock-ups as required and coordinated with Division 01 requirements for
mock-ups.

B. Manufacturers of custom luminaires shall submit a prototype sample(s) of


each luminaire for review by the Engineer. Prototype samples shall be
sufficiently detailed and operational to allow evaluation of compliance
with the salient features of the specification. Preliminary designs or shop
drawings shall not be accepted in place of prototype samples. The
Contractor shall allow for a minimum of 2 prototype iterations for the
development of custom luminaires.

C. Where required, the Contractor shall allow for all necessary installation,
access, provision of temporary power supply and attendance for on-site
mock-ups of luminaires and coordinate with Division 01 requirements for
mock-ups.

D. Luminaires under the contract shall be identical with the approved sample.
No luminaire used as a sample shall be allowed to be installed on the
project.

E. All charges for sample shipments, including returns, are to be prepaid by


the Contractor.

1.6 QUALITY ASSURANCE

A. Materials, equipment and accessories, as well as workmanship, provided


under this section shall conform to the highest commercial standards, as
specified and indicated on drawings. Luminaire parts and components not
specifically identified or indicated shall be made of materials most
appropriate to their use or function and as such resistant to corrosion,
thermal and mechanical stresses encountered in the normal application and
function of the luminaires.

B. All luminaires shall be manufactured to a consistent level of quality. Size,


colour and components parts shall be identical for all luminaires of the
same type.

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 5 of 231


Bulletin No. 145: Volume 3 of 4 (Rev.07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

C. All luminaires and related materials shall be new. Recycled materials are
permissible only with the approval of the Engineer.

D. Testing & Submittals

1. The following reports, listings and information shall be completed


by the manufacturer and submitted for review and approval by the
Engineer prior to order.
a. LM-79-08 Approved Method: Electrical and Photometric
Measurements of Solid-State Lighting Products. Provide
test report and certificate.
b. LM-80-08 Approved Method: Measuring Lumen
Maintenance of LED Light Sources. Provide test report and
certificate.
c. IESNA TM-21-11, IES Approved Method: Making Useful
LED Lifetime Projections. Provide test report and
certificate.
d. Lumen depreciation curve of the LED luminaire.
e. Photometric Intensity Distribution using absolute
photometry.
f. Datasheets for LED light source, detailing manufacturer
and product reference.
g. Datasheets for LED driver, detailing manufacturer and
product reference, power factor, efficiency and dimming
type (PWM or CCR or hybrid). Where PWM is used the
frequency of operation shall be clearly noted.
h. Light source spectral power distribution data at 10nm
increments from 380nm to 780nm.
i. Color rendering index data Ra, and R1 to R15.
j. Color variation test data, identifying color temperature and
chromaticity coordinates at start of life (initial) and at 6,000
hours.
k. Total luminaire wattage, including driver.
l. Ambient temperature at which the LED luminaire
performance is rated. Submit information on how at least
three ambient temperatures will affect the performance and
lifetime of the LED luminaire.
m. LED luminaire warranty documentation.

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 6 of 231


Bulletin No. 145: Volume 3 of 4 (Rev.07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

1.7 WARRANTY

A. Refer to Division 1 Section 017836 – Warranties.

B. Unless otherwise stated in this specification section all materials,


assemblies, component parts, and workmanship shall be guaranteed
against defect, damage, or non-conformity for a period of one (1) year.

C. During the guarantee period the manufacturer shall make all necessary
repairs or replacement to achieve conformity to the requirements of the
Contract Documents.

D. Ballasts shall be warranted for five years. LED luminaires, including LED
drivers, shall be warranted as described in Section 2.0.

E. An LED Luminaire is deemed to be faulty should any of the following


conditions apply. These conditions are based the 5 year warranty period
required.

F. An LED luminaire, including all associated components and drivers, has


catastrophically failed resulting full loss of light output at any time prior to
the end of the warranty period.

G. More than 0.2% per 1000 burning hours of individual LED devices within
an LED luminaire have catastrophically failed at any time prior to the end
of the warranty period.

H. An LED luminaire has experienced lumen depreciation in excess of 0.6%


per 1,000 burning hours at any time prior to the end of the warranty period.

I. Color variation, from results recorded initially and submitted, at any time
before the end of the warranty period in excess of n-step MacAdam
ellipse, where n is defined within the luminaire specification sheets for
each luminaire. If not specified, this shall be 3-step MacAdam ellipse.

J. An LED luminaire experiences visible flicker or blinking at any time prior


to the end of the warranty period.

K. An LED luminaire produces audible noise at any time prior to the end of
the warranty period. This applies at full output and at any dimming level
should dimming be specified.

2. PRODUCTS
2.1 GENERAL

A. The following requirements apply to all luminaires (including LED


luminaires):

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 7 of 231


Bulletin No. 145: Volume 3 of 4 (Rev.07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

1. Contractor shall provide all accessories and design features


described in this document, or necessary in order to provide a
complete installation including mounting hardware, louvers, lenses
filters, transformers, drivers, control gear etc.
2. Luminaires shall be manufactured in strict conformance with the
contract drawings and specifications. Specifications and scale
drawings are intended to convey the salient features, function and
character of the luminaires only, and do not undertake to illustrate
or set forth every item or detail necessary for the work. Minor
details, not usually indicated on the drawings, or specified, but that
are necessary for the proper installation, manufacture and
completion of the luminaires, shall be included, the same as if they
were herein specified or indicated on the drawings.
3. The Employer shall not be held responsible for the omission or
absence of any detail which may be required in the manufacture
and installation of the luminaires. The responsibility of accurately
fabricating and installing the luminaires to the fulfilment of this
specification rests with the Contractor.
4. It is the responsibility of the Contractor to bring to the attention of
the Engineer any discrepancies or installation issues before
proceeding with work.
5. All special tools required for the operation, maintenance and repair
of the equipment shall be identified, included in the Tender and
handed over to the Employer upon completion of the
commissioning
6. All luminaires shall be CE certified and shall carry a CE Marking.
7. Operating temperature rating for all interior luminaires and
associated control gear shall be between 0°C and minimum +40°C
at a minimum 95% Relative Humidity (RH).
a. All luminaires and associated control gear shall operate
within the above ambient temperature limits without forced
/ active cooling and with no degradation in performance.
8. Operating temperature rating for all exterior luminaires and
associated control gear shall be between -40°C and minimum
+60°C at a minimum 95% Relative Humidity (RH).
9. Storage (i.e. non-operating) temperature of all luminaire
components to be designed to tolerate between -40°C and a
minimum +80°C at a minimum 95% Relative Humidity (RH).
2.2 LED PRODUCTS

A. General

1. All LED luminaires shall be subject to EMC emission and


immunity testing and provided with EMC compliance certification.

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 8 of 231


Bulletin No. 145: Volume 3 of 4 (Rev.07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

2. Light output power at 400nm and below shall be 0 (zero).


3. Unless specified otherwise, white LED luminaires shall have a
power factor > 0.9.
4. Unless specified otherwise, RGB LED luminaires shall have a
power factor > 0.5.
5. All LED luminaires shall undergo a minimum 24-hour burn-in test
during manufacturing. All LED luminaires shall undergo a further
100-hour burn-in test on site prior to hand over. Documentation
confirming both manufacturing and on site burn-in shall be
provided for review by the Engineer.
6. Unless specified otherwise, minimum luminaire lifetime shall be
50,000 hours at L70F10. Note this is the complete luminaire, not
the LED source.
7. Unless specified otherwise, the maximum failure fraction of LED
luminaires at the end of luminaire lifetime shall be 10%, F10.
8. All LED luminaires shall have lumen maintenance code 9
according to IEC/PAS 62717, where maintained luminous flux at
6,000 hours shall be in excess of 90% of initial luminaire lumens.
9. All hardwired connections to LED luminaires and drivers shall be
reverse polarity protected.
10. All LED luminaires shall provide a cover or other suitable
protection of LED chips to allow for cleaning. LED luminaires
with exposed LED chips are not acceptable.
11. All LED luminaires and / or associated driver(s) shall have a means
of thermal protection in the form of an automatic dimming or
stepping/holding down the output where temperature exceeds
operational limits. Thermal cut-out devices which turn off the
fixture completely are not acceptable for luminaires within spaces
occupied by the public.
12. Audible noise from luminaire and / or drivers when at full lumen
output or at any dimming level shall not be acceptable.
B. LED Drivers

1. Read this section in conjunction with section 8.2 of


REP_LCS_0001.
2. LED drivers shall be RoHS compliant.
3. LED drivers shall have a minimum efficiency of 85%.
4. LED drivers shall have a total individual luminaire Harmonic
Distortion (THD) of < 10%.
5. Visible blinking, flickering or strobing shall not be acceptable at
full lumen output, nor at any dimming level should dimming be
specified.

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 9 of 231


Bulletin No. 145: Volume 3 of 4 (Rev.07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

6. Dimmable LED drivers shall dim via Pulse Width Modulation


(PWM) or using a hybrid combination of PWM and Constant
Current Reduction (CCR). Dimmable drivers using CCR only are
not acceptable.
7. Unless specified otherwise, PWM frequency shall be a minimum of
400Hz.
C. Colour and Colour Consistency (white light)

1. Refer to luminaire specification sheets for colour temperature and


colour consistency requirements for LED luminaire types.
2. The specified colour temperature variation applies to the initial
color temperature variation and at any time prior to the end of the
warranty period.
2.3 SUPPLEMENTARY LIGHTING CONTROL INFORMATION

A. This section should be read in conjunction with the lighting control


performance specification “REP_LCS_0001 Lighting Control - Issue 2”.

B. The lighting control system shall provide dimming and switching control
for the interior and exterior lighting within the following areas of the
Midfield Terminal Complex, Abu Dhabi;

1. L2.0 Departures Kerb and L2.0 Kerbs and Forecourts


2. L2.0 Well Wisher’s Hall and adjoining Check-In Hall
3. L2.0 Check-In
4. L2.0 Pre Check-In Security and Airside Security / Emigration
Areas
5. L2.0 Airside Lounge
6. L2.0 – L1.0 Airside Garden
7. L2.0 Departures Concourse and L3.0 Sterile Corridor
8. L2.0 Departures Holdrooms and Holdroom Pier Ends
9. L2.0 and L3.0 Gatehouses
10. L3.0 - L2.0 Bus Departure Lounges
11. L3.0 – L0.0 Arrivals Escalators (O/D PAX) and Elevators
12. L1.0 and L0.0 Arrivals Lobbies including Bus Arrivals Lobbies
13. L0.0 Arrivals Hall: Immigration and Customs Security Screening
Lobbies
14. L0.0 Baggage Reclaim Hall
15. L2.0 - L0.0 Arrivals Internal Water Garden
16. L0.0 Arrivals / Meeters’ & Greeters’ Hall

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 10 of 231


Bulletin No. 145: Volume 3 of 4 (Rev.07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

17. L0.0 Arrivals Forecourt


18. L0.1 Pedestrian Bridges to Car Park
C. Lighting control shall be based on the concept of lighting scene control,
where a lighting scene can comprise all or any of the independently
controlled lighting zones or channels.

D. Each area of the building is divided into a series of lighting zones based on
anticipated usage. Each zone comprises a series of lighting channels and
these zones can be selected individually to form a lighting scene.

1. For example, each Hold room constituting all lights within the
ceiling and floor will constitute a single lighting zone.
2. Each Pier Sterile Corridor will also constitute a single lighting zone
across the entire length of the Pier.
3. The Central Terminal Building has a number of horizontal Lighting
zones which breakdown as follows:
a. Departures Roof
b. Departures Landside Pavilion Buildings
c. Departures Airside Pavilion Buildings
d. Arrivals Landside
e. Arrivals Airside
E. Each lighting channel shall comprise one or more lighting circuits.
Lighting channels can be selected individually and represent a method of
controlling large quantities of light fixtures, spread across multiple
electrical circuits, simultaneously such that they appear to be powered via
a single circuit. Selection of the lighting control channels shall allow
SCADA, BMS and Emergency lighting monitoring operations.

F. The lighting control system shall incorporate a comprehensive scheduler to


automate time-based events. It shall be possible to trigger scheduled events
as a ‘One Off’ timed event or a recurring event. ‘One Off’ Events are
scheduled for a specific date and time. Once the event has occurred, the
scheduled event should be deleted from the timed control database.

G. The scheduler shall be capable of initiating events or sequences of events


on a specific time or time difference from sunrise or sunset on a:

1. Day of Week
2. Day of Month
3. Specific Calendar Date
H. Sunrise and sunset information may be determined by latitude and
longitude, and the system shall automatically keep track of daylight

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 11 of 231


Bulletin No. 145: Volume 3 of 4 (Rev.07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

saving, and leap years. It shall be possible to schedule the date of recurring
events in several ways:

1. At a specific day and time each week i.e. : every Monday,


Wednesday and Friday at 3:00 PM
2. On a specific day of the month i.e. On the 15th of every month at
3:00PM
3. On a specific day of the week each month i.e. on the 1st Monday in
every month at 3:00 PM
4.I. Similarly, the time of recurring events can be scheduled in several ways:

5.1. At a specific time i.e. Every day at 3:00 PM


6.2. At a specific time before or after Sunrise/ Sunset i.e. Every day at 1
hour before Sunrise
7.3. At a recurring time i.e. Every 15 minutes
I.J. For recurring events provision must also be included for the end-user to
schedule exceptions. For example “Every day at 3:00 except for December
24th and January 1st”.

J.K. The system management software shall also incorporate a macro based
logic control builder that utilizes a plain language function editor. The
macro builder must be capable of handling sequential and conditional
control routines.

K.L. Daylight sensitive photocells shall be provided and located at designated


positions (as shown on electrical drawings and defined in the
Specification REP/LCS/001) within:

1. Each Pier (4no)


2. Central Departures Hall
3. Welcomers Hall and Forecourt
L.M. These devices shall provide daylight sensitive control for designated
lighting channels and scenes according to daylight availability within the
space. The system shall incorporate a time delay or similar device to
satisfactorily cater for rapid changes in ambient lighting conditions (for
example due to passing clouds). These devices shall provide operational
signals for the localised areas of the project within which they are
mounted.

M.

2.4 SCHEDULES

A. LIGHTING CONTROL PANEL SCHEDULE

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 12 of 231


Bulletin No. 145: Volume 3 of 4 (Rev.07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Control Zone Control Panel Operation Location


All Areas +
MCP Security
access to master
All Areas Programmable Operations
time-clock and
Touch Screen Centre
photocells

B. LIGHTING SCENE SCHEDULE

1. The following lighting scenes are proposed. Final settings to be


set and agreed on site with the Employer.

Scene Description Proposed Time

Scene 1 Morning 1 hour post-sunrise - 1000

Scene 2 Daytime 1000 – 1 hour pre sunset

Scene 3 Evening 1 hour pre – 2 hour post sunset

Scene 4 Night 2 hour post sunset - 2400

Scene 5 Early Hours 2400 – 1 hour pre-sunrise


1 hour pre-sunrise – 1 hour post-
Scene 6 Early Morning
sunrise

2. Special scenes relating to individual rooms are not included on this


schedule.
C. LIGHTING CONTROL LOAD SCHEDULE

1. Lighting control channel schedules are provided following the


luminaire specification sheets.
2. Please refer to electrical circuiting schedule design requirements
for actual circuit breakdowns of stated control zones.
3. The lighting control schedules provide quantities of fixtures and
load per lighting control channel. Where continuous row
luminaires are specified, such as luminaire type XL2c, the control
schedules indicate a single luminaire length to allow total load to
be calculated. The contractor shall not use this information to
procure these fixtures. As specified within the luminaire datasheets,
the actual fixture length shall be determined based on site
measurements and the appropriate length selected from the range
of lengths specified.

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 13 of 231


Bulletin No. 145: Volume 3 of 4 (Rev.07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

3. EXECUTION
3.1 INSTALLATION

A. The Contractor is to ensure the correct supply voltage at the luminaire and
lamp. All wiring is to be carried out in accordance with the applicable
building and ADM-IBC electrical codes and relevant national standards.

B. The Contractor shall coordinate exact quantities and critical dimensions


with site conditions. All linear and continuous linear luminaire dimensions
are to be verified by the Contractor and submitted to the Engineer for
approval prior to order.

C. The Contractor shall verify and coordinate the provision of appropriate


framing, support structures, mounting brackets and other required
structural connections by the General Contractor or other trades to ensure a
timely, neat installation of all luminaires.

D. The Contractor shall coordinate and provide any associated mounting


hardware, conduit connections, or associated appurtenances for the
effective installation of the luminaires. Provide each luminaire with
complete installation instructions. All luminaires shall be installed in strict
conformance with manufacturer’s recommendations and instructions.

E. All transformers, control gear and emergency battery packs for ceiling
recessed luminaires are to be coordinated with the architectural details to
comply with access requirements.

F. The Contractor is to ensure the co-ordination and compatibility of all


luminaire control gear/transformer types with the lighting control system.

G. Exact locations of all luminaires including mounting heights and plan


dimensions are shown on the architectural drawings. Any ambiguities or
conflicts in this dimensional information shall be identified to the Engineer
prior to ordering and installation.

H. All fixing detail/cut-out and recess dimensions are to be confirmed with


manufacturers by the Contractor.

I. The Contractor shall not install exposed luminaires, reflectors or trims


until all plastering and painting that may mar the luminaire finishes is
completed. Replace blemished, dented, damaged or unsatisfactory
luminaires as directed.

J. Luminaires shall not be suspended from any duct-work or pipework.

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 14 of 231


Bulletin No. 145: Volume 3 of 4 (Rev.07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

K. The Contractor shall rigidly align all continuous row luminaires for true
in-line appearance.

L. Luminaires shall not be operated for work light at any time during
construction, nor shall it be illuminated for any other reason apart from
necessary testing and commissioning of the installation. Failure to comply
with this requirement will make it necessary for the Contractor to re-lamp
at no additional cost to Employer just prior to turnover of area to
Employer.

3.2 COMMISSIONING, FOCUS AND ADJUSTMENT

A. The Contractor shall supply one single volume to the Employer’s resident
team within twenty (20) days of commissioning (before training)
incorporating a full system operational description, all component
specifications, scaled drawings for all devices, wiring schematics for
installed cabling, manuals for each device, installation details,
programming instructions and all safety advisories required under law or
specified by the manufacturer or installer.

B. The manufacturer shall fully electrical test and commission the lighting
control system with the sub-contractor and demonstrate its correct
operation, in accordance with this specification, through the independent
flashing of each Logical Control Channel prior to commencement of final
programming.

C. The Contractor shall allow sufficient time for programming and re-
adjustments, post commissioning of the lighting control system with the
Engineer.

D. All adjustable luminaires shall be aimed, focused, and locked by the


Contractor under the supervision of the Engineer.

E. All focusing and adjusting shall be carried out after the entire installation
is complete. All ladders, scaffolds etc required, shall be furnished by the
Contractor, at the direction of the Engineer. As aiming and adjusting is
completed, locking set screws, nuts and bolts, shall be securely tightened.
Where possible, units shall be focused during the normal working day.
Where daylight prevents this, focusing shall be carried out during the night
at a time mutually agreeable to Contractor, Engineer, and Employer.
Adjustments shall be made in accordance with the Engineer’s stated intent,
under their supervision.

F. The final focussing and scene setting of the installation must be


undertaken with the Engineer and a lighting control technician in
attendance. The programming of a lighting control system from a written
lighting scene schedule shall not constitute completion.

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 15 of 231


Bulletin No. 145: Volume 3 of 4 (Rev.07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

3.3 CLEAN-UP

A. At the time of final acceptance by the Engineer, all luminaires shall have
been thoroughly cleaned with materials and methods recommended by the
manufacturers, all broken parts shall have been replaced and all lamps
shall be operative.

3.4 TRAINING

A. A manufacturer shall allow five days and five nights for assistance to the
resident Employer team in training designated staff members in use of the
lighting control system. This shall include programming, setting levels, use
of all devices and resetting electrical items such as circuit breakers etc.

B. If required, additional training shall be provided as requested as an


additional cost item.

3.5 MAINTENANCE

Where components of a luminaire are replaceable, including but not limited to and
control gear, LED modules and drivers, it should be clearly noted within the
Operation and Maintenance manuals that exact replacements should be used in
accordance to the Division 01 requirements. Should alternative components be
used, it should be clearly noted that additional EMC and CE certifications may be
required. In the case of LED luminaires, the compatibility of LED and driver
should be confirmed prior to any additional EMC and CE certifications.

END OF SECTION

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 16 of 231


Bulletin No. 145: Volume 3 of 4 (Rev.07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

SCHEDULES FOLLOW:

1 - LUMINAIRE SPECIFICATION SHEETS

2 - LIGHTING CONTROL LOAD SCHEDULES

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 17 of 231


Bulletin No. 145: Volume 3 of 4 (Rev.07) January 31, 2015
Bollard IP 65 · D - 58708 Menden
BEGA Lichttechnische Spezialfabrik
Hennenbusch 8563
BEGA
Bollard
Abu Dhabi Airports Company PJSC
IP 65
Date 8563 Specification, Section 265120
Date

Luminaire Description: Bollard


ctor
Manufacturing standard: EN 60 598 Total luminaire wattage (max): 28W
ctor Primary luminaire Aluminium alloy Power factor: > 0.9
nd
construction material: Rated luminous flux (lm): 1,480lm
es and Finish: Stainless steel Luminaire efficacy: 53lm/W
nd
BEGA Lichttechnische Spezialfabrik
Accessories: N/A
Hennenbusch · D - 58708 Menden BEGA Beam / distribution: Symmetric, see LDC
es and
inium Light source type: IP 65
Bollard LED 8563 CRI / Colour temperature: > 80 / 3,000K
Project 1
Driver type: Date Constant current Colour Variation: 20.08.2014
≤ 3 SDCM
BEGA Lichttechnische Spezialfabrik
inium Drive current or voltage: 700mA
Hennenbusch · D - 58708 Menden BEGA Operator Luminaire Lifetime: ≥ 50,000 hours
Telephone
um Dimming & type:
Bollard IP 65 DALI, integral 8563 Fax
e-Mail
Lifetime Basis: L70 / F10 @ Ta 600C
onto a
ector IP: Date IP65
um BEGA 8563 K4 LED 24,3W / Luminaire Data Sheet
onto
and
e a
eces and
Luminaire distribution curve (LDC)
Luminous emittance 1: Location:
ector
e Arrivals drop off
x 4@
minium
e
and

ces and
x 4@
nium
g onto a

minium
de
de
Weight: 10.0 kg
c – Conformity mark
Dust tight and protection against water jets
Protection class IP 65
Safety class I
DC 170-240 V
220-240 V x 0/50-60 Hz
LED-Power supply unit
with fuse Neozed D 01 · 6 A
for through-wiring – for 2 cables up to 5 x 4@
Weight:
Access door
c
ø 132
Dust
ø
Protection
Mounting plate
Safety
foundation
DC
Luminaire with
Reflector Vmade
220-240
LED-Power
Silicone
with
Borosilicate
andthrough-wiring
for
Access
Luminaire
ø
Product
ø 100 mm, 3 elongated holes 9 mm wide
access
Mounting
For
foundation
uniform.
Luminaire with mounting plate for bolting onto a
rotationally
Reflector made
Illumination
Silicone gasket
onto
Borosilicate
and light
The
symmetrical
Luminaire made
Product LED
Shielded
Application
access roads.
For the illumination of walkways, entrances and
uniform.
rotationally
Illumination on the illuminated surface is
onto
The light of the LED is directed by a reflector
symmetrical light output.
Shielded LED bollard with rotationally
Application
06.14 · Technical amendments reserved
Project · Reference

Product

Project · Reference number


ets Notes:
100tight

nium
x 4@ 132 mm,
– Conformity

170-240

the illumination
stainless steel– for 2 cables up to 5 x 4@

stainless
fuse Neozed

g onto a

a conical

a conical data
mm, 3 elongated
mm,and

classorI an anchorage unit

roads. 1. Refer to Section ‘2.0 Products’ of this


door
10.0 and

gasket

ets

of the
description

description
plate with two pitch circles:
made

de specification for additional requirements.


classwith

or an anchorage
x 0/50-60

symmetrical,

symmetrical,
3 elongated

3 elongated holes 9 mm wide

on the illuminated surface is


supply unit

de
glass D 01 · 6 A

glass
www.bega.com

lightof
V mounting plate for bolting onto a

andofconnection
kg connection box 632

steel

bollard with rotationally


2. Luminaire to be passively cooled.

reflector.

reflector.
protectionholes

LED is directed by a reflector


x 4@
of anodised

of anodised
jets
IP 65
mark holes 9 mm wide

output.
aluminium box

aluminium alloy, aluminium


of walkways,

www.bega.com
two pitch circles:

number

sheet
www.bega.com
Hz pure aluminium

broad

broad spread and


against

Luminaire classification according to CIE: 100 Luminous emittance 1:


Montageplatte
CIE flux code: 23 71 97 100 100 Mounting plate
pure
unit entrances and

jets
alloy,632
9 mm

Contre-plaque
spread

BEGA-8563K4 Bollard with shielded light source.


Montageplatte
water

aluminium

With LED 24,3 W, 2.490 lumen,


Mounting plate
Contre-plaque
colour temperature 4.000 K. Montageplatte
www.bega.com
aluminium

Colour rendering index (Ra) 80. Mounting plate


wide

With exchangeable BEGA LED module with excess Contre-plaque 3 x 120°


and

3 x 120°
temperature protection and a service life of
jets
3x

at least 50.000 operating hours. 20 years warranty


1100

3x

12
1100

1050mm

12

of availability of LED module and wear parts.



With LED power supply unit 220-240 V, 50-60 Hz.


Protection class IP 65.
Montageplatte 3 x 120°
Mounting plate
Cast aluminium, aluminium and stainless steel.
Contre-plaque
3x

With borosilicate glass and reflector made of


1100

12

pure anodised aluminium.


Luminaire luminous flux
Lamp luminous flux
Connected wattage
LED 3000 K
Lamp

Bollard

Luminaire with door and 3 x 1built-in


20° connection box 632
and mounting plate forØbolting
100 onto a foundation or
3x

anchorage unit 896. Ø 132


1100

Ø 190
12

Height above ground: 1.100 mm.


Colour: graphite.
Ø 100
Lamp 1100 Ø 190 Article
1100 No. 8563 Ø 132
LED 3000 K 24.3 W Colour temperature 3000 K.
Connected wattage 350mm 27.3 W Also available with 4000 K on request.
Lamp luminous flux 2380 lm 3000 K – article number
Ø 100
Ø 100
Ø 190

Luminaire luminousØ 190


flux Ø 190
1416 lm 4000 K – article number + K4
Ø 132
Ø 132
Lamp
Colour rendering index Ra > 80
Accessory Article No. 8563
BEGA Article No. LED-0382/830
LampLED 3000 K 896 Anchorage
Article No. 856324.3unit W Colour temperature 3000 K.
LEDConnected Anchorage unit with 3000
mounting
K. flange made of
3000
4000 K wattage 24.3 W Colour
hot-dip 27.3
temperature
galvanised W
steel. Total Also500
length available
mm. with 4000 K on request.
Lamp
Lamp
Connected
Lamp
wattage
luminous luminous
flux flux
27.3 W
2380 3 stainless 2380
steel lm MArticle
Also available with 4000 K on request.
fixing screws 3000
8. K No. 8563number
– article
2490 lm 3000 K – article number
LED
Luminaire 3000
luminous K
flux
Luminaire luminous fluxR > 80 1416
1481 lm 4000 K – article24.3
Pitch circle ø 132 numberW
mm. + K4 Colour temperature 3000 K.
4000 K – article number + K4
1416 lm
Colour rendering index
Connected
Colour rendering wattage
index
a
a
LED-0382/830
A
Accessory
R27.3
separate instructions
> 80W
for use Also
can be available
provided with 4000 K on request.
BEGA Article No. LED-0382/840 upon
896 request.
Anchorage aunit
Lamp
BEGA luminous flux
Article No. LED-0382/830
Anchorage
2380 lm Accessory 3000 K – article number
unit with mounting flange made of
LED 4000 K
Luminaire luminous flux 24.3 W
1416
hot-dip galvanised 896 500Anchorage
lmTotal length
steel. 4000 Kmm. unit
– article number + K4 The drawings on this page are
Connected wattage 27.3 W
3 stainless steel fixing screws MAnchorage unit with mounting flange made of indicative. Refer to the architectural
1416 lm
2380 lm

8.
Colour
luminousrendering index R > 80
27.3 W
24.3 W

Lamp flux 2490 lm


LED 4000 K Pitch circle ø 13224.3
amm. W Accessory
Luminaire luminous flux
BEGA Article No. 1481 lm
LED-0382/830 hot-dip galvanised steel. Total length 500 mm. drawings for correct setting out,
Connected
Colour rendering indexwattage Ra > 80 A separate 27.3 W
instructions for use 896 Anchorage
can be provided unit screws M 8.
BEGA Article No. LED-0382/840 upon request. 3 stainless steel fixing mounting details and final dimensions.
Lamp luminous flux 2490 lm Anchorage unit with mounting flange made of
Mounting plate

Mounting plate
Montageplatte

Montageplatte
Contre-plaque

Contre-plaque

Page 1
LED 4000 luminous
K 24.3 lm W Pitch circle ø 132 mm.
3 x 120°

3 x 120°
Ø 132
Ø 100

Luminaire flux 1481 hot-dip galvanised steel. Total length 500 mm.
4000 K – article number + K4
3000 K – article number
Also available with 4000 K on request.
Colour temperature 3000 K.
Article No. 8563

Connected wattage 27.3 W


Date

IP 65
Hennenbusch · D - 58708 Menden
BEGA Lichttechnische Spezialfabrik

Date

Colour rendering index Ra > 80 3 A stainless


separate steel
instructions for useMcan
fixing screws 8. be provided
Lamp
BEGA luminous flux
Article No. LED-0382/8402490 lm upon request. Type:
Pitch circle ø 132 mm.
Luminaire luminous flux
3x 3x 1481 lm
Colour rendering index Ra > 80 A separate instructions for use can be provided
12 12
0° 0°

BEGA Article No. LED-0382/840 upon request.


B1

Page 18 of 231
www.bega.com

www.bega.com

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
BEGA
8563
NIVERSAL OPEN
SFDFTTFEEPXOMJHIUXJUIEFFQTFUSFnFDUPS
t 'JYFESFDFTTFEEPXOMJHIUXJUIEFFQTFUSFnFDUP
Abu Dhabi Airports Company PJSC Specification, Section 265120

TUDPOTUSVDUJPO
t %JFDBTUDPOTUSVDUJPO
Luminaire Description: Recessed fixed downlight
FDFTTFEEPXOMJHIUXJUIEFFQTFUSFnFDUPS
Manufacturing standard: EN 60 598 Total luminaire wattage (max): 19W

DPOUSPMTFDPOEBSZSFnFDUPS
t (MBSFDPOUSPMTFDPOEBSZSFnFDUPS
Primary luminaire Die-cast aluminium Power factor: > 0.9
TUDPOTUSVDUJPO
construction material: Rated luminous flux (lm): 1,720lm
Finish: See Notes Luminaire efficacy: 91lm/W

DPOUSPMTFDPOEBSZSFnFDUPS
Accessories:
FEXJUIQSFXJSFESFNPUFOPOEJNNJOHESJWFS
N/A
t 4VQQMJFEXJUIQSFXJSFESFNPUFOPOEJNNJOHE
Light source type: LED
Beam D9b/ distribution:
D9b D9b D9b
Symmetric,
D9b

CRI / Colour temperature: > 80 / 3,000K


see LDC

Driver type: Security booth Constant current Colour Variation: ≤ 3 SDCM

FEXJUIQSFXJSFESFNPUFOPOEJNNJOHESJWFS
06.08.2014
Drive current or voltage: 700mA Luminaire Lifetime: ≥ 50,000 hours
BUJWFSBOHFPGBDDFTTPSJFT
t %FDPSBUJWFSBOHFPGBDDFTTPSJFT
Dimming & type: DALI, remote
Operator
Telephone
Fax
e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: IP20
BUJWFSBOHFPGBDDFTTPSJFT Projection Lighting UO20**8W* Universal / Luminaire Data Sheet
Luminaire distribution curve (LDC) Location:
Luminous emittance 1:

See our luminaire catalog for an image of the Circulation Transfer Building
luminaire.
Recessed in tray to illuminate columns in
Welcomers Hall, Baggage Reclaim and
Arrival Lobby
Arrivals Tunnel
Arrivals Bussing Corridor
D9b Notes:
Janitor’s closet
D9b
Notes:
D9b
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
80+ 2000lm CRI 80+CRI 80+ 3000lm
m CRI400/700/1000/1300lm 2000lm CRI
CRI 80+
80+ 3000lm CRI 80+
2. Luminaire to be passively cooled.
mI CRI 400/700lm
98 80+ 2000lm
1000lm CRI
CRICRI
80+9898 1300lm
1000lm
3000lm CRI 98
CRI 98
CRI 80+ 1300lm CRI 98
Luminaire classification according to CIE: 100 Luminous emittance 1: 3. Fixture to be powder coated (RAL
98 1000lm CRI 98code: 96
CIE flux 99 100 1300lm
100 86 CRI 98
9016).

115mm 127mm
115mm 127mm
96mm 96mm
115mm 127mm
96mm

108mm
Cut Out: Ø95mm Cut Out: Ø95mm
Cut Out: Ø95mm

ee by
by
Available
specialorder
special order
by special order
The drawings on this page are
L5 L5 indicative. Refer to the architectural
L5 L5
D1
D6 D6 D6
D1 drawings for correct setting out,

tt
/JDLFM4BUJOPQUJPO
D6 D6 D6

/JDLFM4BUJOPQUJPO
t /JDLFM4BUJOPQUJPO
Page 1 mounting details and final dimensions.

Type:
fix
pa

Detail 6
D1
Sheet 1/2
Detail section of light tray from MTC-A-94-TB-L_-_-0-00-09-034 034

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 19 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
S.O.P

Abu Dhabi Airports Company PJSC Specification, Section 265120

Glass smoke downstand GFF


with glass fin support 04
Light fitting

Smoke detector Clear laminated glass GLZ


01 04 30.11.14 BULLETIN 134

910
03 31.10.14 BULLETIN 120
Provide embedment in column 02 25.08.14 BULLETIN 107
to recieve steel framing
01 01.07.14 BULLETIN 85
ontainment DFR 00 15.07.12 ISSUED FOR CONSTRUCTION
urtain type 1 02
Side wall sprinkler
12° (if applicable) 163
152 L5 L5 ISSUED FOR CONSTRUCTION
R9

16°
1

ed cladding MPC

80 92
80 80

ghting tray 04B ABU DHABI


R1 AIRPORTS COMPANY
360

38
Steel Framing ABU DHABI AIRPORTS COMPANY
200

200
38
R1 L. +16.85
50 Kohn Pedersen Fox Associates
D1 D1
(International) PA
R1669

Architects and Planning Consultants


7a Langley Street
55 London WC2H 9JA
England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com

Light fitting Smoke Containment DFR


Curtain type 1 02

Sprinkler
Detail 3 Sprinkler (typ)

Detail through Processor Arrival ceiling lighting tray typical from MTC-A-41-TB-L0-1-5-00-00-872
ABU DHABI INTERNATIONAL AIRPORT
04 MIDFIELD TERMINAL COMPLEX

100 540 485 1780 PROCESSOR ARRIVAL CEILING


2905 COMPONENTS - LIGHTING TRAY AND
Metal unperforated cladding MPC SMOKE CURTAIN AT WATER GARDEN
lighting tray 04B
MTC A 41 TB __ L0.1 5.00 00.872 04

3 SECTION OF LIGHTING TRAY KPF MC KF JH 25.09.2009


SCALE 1:10
SEE G04310 AND G04312 FOR LOCATIONS OF GFF 04 AND DFR 02. WBS AUH.06.10.0401

2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights reserved. Do not scale.

D1

Detail
2
2 AT TRANSFER CEILING SECTIONAL DETAIL
CEILING 3 METAL PANELING - GYPSUM CEILING
SCALE 1:5 SCALE 1:5

Detail of ceiling at Transfer ceiling from MTC-A-94-TB-L_-_-0-00-09-051

00 05.01.15 BULLETIN 137

ISSUED FOR CONSTRUCTION

ABU DHABI
AIRPORTS COMPANY
ABU DHABI AIRPORTS COMPANY

Kohn Pedersen Fox Associates


(International) PA
Architects and Planning Consultants
7a Langley Street
London WC2H 9JA
England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com

ABU DHABI INTERNATIONAL AIRPORT


MIDFIELD TERMINAL COMPLEX

CENTRE SPACE LEVEL 3


TYPICAL DETAILS
SECTIONS AND DETAILS

MTC A 94 TB __ L_._ 0.00 09.051 00

JS ISO KF CB 05.01.15 The drawings on this page are


WBS AUH.06.10.0401
indicative. Refer to the architectural
drawings for correct setting
2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights reserved. Do not scale.

out, mounting details and final


dimensions.

Type:

D1
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 20 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
NIVERSAL OPEN
PXOMJHIUXJUIEFFQTFUSFnFDUPS
t 'JYFESFDFTTFEEPXOMJHIUXJUIEFFQTFUSFnFDUP
Abu Dhabi Airports Company PJSC Specification, Section 265120

DUJPO
t %JFDBTUDPOTUSVDUJPO
Luminaire Description: Recessed fixed downlight
FDFTTFEEPXOMJHIUXJUIEFFQTFUSFnFDUPS
Manufacturing standard: EN 60 598 Total luminaire wattage (max): 47W

POEBSZSFnFDUPS
t (MBSFDPOUSPMTFDPOEBSZSFnFDUPS
Primary luminaire Die-cast aluminium Power factor: > 0.9
TUDPOTUSVDUJPO
construction material: Rated luminous flux (lm): 2,580lm
Finish: See Notes Luminaire efficacy: 83lm/W

DPOUSPMTFDPOEBSZSFnFDUPS
Accessories:
FXJSFESFNPUFOPOEJNNJOHESJWFS
N/A
t 4VQQMJFEXJUIQSFXJSFESFNPUFOPOEJNNJOHE
Light source type: LED
Beam / distribution: Symmetric, see LDC
CRI / Colour temperature: > 80 / 3,000K
Driver type: Project 1 Constant current Colour Variation: ≤ 3 SDCM

FEXJUIQSFXJSFESFNPUFOPOEJNNJOHESJWFS
06.08.2014
Drive current or voltage: 1,050mA Luminaire Lifetime: ≥ 50,000 hours
FPGBDDFTTPSJFT
t %FDPSBUJWFSBOHFPGBDDFTTPSJFT
Dimming & type: DALI, remote
Operator
Telephone
Fax
e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: IP20
BUJWFSBOHFPGBDDFTTPSJFT Projection Lighting UO20**8W* Universal / Luminaire Data Sheet
Luminaire distribution curve (LDC) Location:
Luminous emittance 1:

See our luminaire catalog for an image of the Pier bridges


luminaire.
Gatehouses

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Luminaire to be passively cooled.
3000lm CRI 80+CRI 80+ 2000lm CRI 80+
0+ 400/700/1000/1300lm 3000lm CRI 80+ 3. Fixture to be powder coated (RAL

m98 1300lm
CRI 80+ 2000lm CRI
400/700lm
CRI 98 98
CRI
80+ 1000lm
3000lm CRI 98
CRI 80+ 1300lm CRI 98 9016).
Luminaire classification according to CIE: 100 Luminous emittance 1:
98 1000lm CRI 98code: 96
CIE flux 99 100 1300lm
100 86 CRI 98

115mm 127mm 115mm 127mm


96mm
115mm 127mm
96mm

108mm
mm Cut Out: Ø95mm
Cut Out: Ø95mm

elby
order
Available by special order
special order
The drawings on this page are
indicative. Refer to the architectural
drawings for correct setting out,

t /JDLFM4BUJOPQUJPO
t /JDLFM4BUJOPQUJPO t /JDLFM4BUJOPQUJPO
D1c
Page 1 mounting details and final dimensions.

Type:
L2c L2c

Detail 4
D1c
Detail section of underside of Link Bridge from MTC-A-94-TB-L_-_-0-00-09-040

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 21 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
ADJUSTABLE
NIVERSAL
DJUSTABLE
adjustable downlighter
• High output fully adjustable downlighter
Abu Dhabi Airports Company PJSC

Luminaire Description:
ction with protective clear glass
Recessed adjustable downlight
Specification, Section 265120

• Die-cast construction with protective clear glas


utput fully adjustable downlighter
Manufacturing standard: EN 60 598 Total luminaire wattage (max): 47W
Primary luminaire Die-cast aluminium Power factor: > 0.9
e-wired non dimmable driver
• Supplied with pre-wired non dimmable driver
construction material: Rated luminous flux (lm): 2,670lm
st construction with protective clear glass
Finish:
See Notes Luminaire efficacy: 86lm/W
Accessories: N/A Beam / distribution: Symmetric, see LDC
f beam angles
• Versatile range of beam angles
ed with pre-wired non dimmable driver
Light source type:
Driver type: Project 1
LED
Constant current
CRI / Colour temperature: > 80 / 3,000K
Colour Variation: ≤ 3 SDCM
10.08.2014
Drive current or voltage: 1,050mA Operator
Luminaire Lifetime: ≥ 50,000 hours

le range of beam angles


Dimming & type: DALI, remote Lifetime Basis: L70 / F10 @ Ta 250C
Telephone
Fax
e-Mail
IP: IP20
Projection Lighting UA30**8M* Universal Adjustable / Luminaire Data Sheet
Luminaire distribution curve (LDC)
Luminous emittance 1:
Location:
See our luminaire catalog for an image of the Gatehouses
luminaire.
Arrivals Bussing corridor

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Luminaire to be passively cooled.
80+ 3000lm CRI 80+CRI 80+
400/700/1000/1300lm 2000lm CRI 80+ 3000lm CRI 80+ 3. Fixture to be powder coated (RAL
RI 98 1300lm
700lmCRI
CRI98
98 1000lm CRI 98 1300lm CRI 98 9016).
Luminaire classification according to CIE: 100 Luminous emittance 1:
CRI 80+ 2000lm CRI
CIE flux80+
code: 99 100 1003000lm
100 89 CRI 80+
8 1000lm CRI 98
142mm
1300lm CRI 98
Rotate: 355°
142mm
104mm
86mm
142mm
104mm Rotate: 355°
86mm 104mm Tilt: 20° Tilt: Tilt:
28˚ 20°
28° Gy
02mm 108mm
Cut Out: Tilt:
Ø102mm20° Tilt: 28˚
Cut Out: Ø102mm

The drawings on this page are


indicative. Refer to the architectural

• Satin Nickel option


L3 L3

• Satin Nickel option


• Satin Nickel option
L3 L3
Page 1
drawings for correct setting out,
mounting details and final dimensions.

Type:
D1d D1d

Detail 3
D1d
Sheet 1/2
Detail section from MTC-A-07-TB-L_-_-_-__-00-475

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 22 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
TION

D1d D1d D1d D1d D1d D1d D1d D1d


C C C C C C C

C C C C C C C

D1d D1d D1d D1d D1d D1d D1d D1d

G PLAN M

Detail 2
Reflected ceiling plans of lower Arrivals Bussing Corridor vertical circulation from MTC-A-07-TB-L_-_-_-__-00-476
OHL Revision Notes\Rev 1_Bulletin 134.dwg

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

D1d
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 23 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
ADJUSTABLE
NIVERSAL
DJUSTABLE
adjustable downlighter
• High output fully adjustable downlighter
Abu Dhabi Airports Company PJSC

Luminaire Description:
ction with protective clear glass
Recessed adjustable downlight
Specification, Section 265120

• Die-cast construction with protective clear glas


utput fully adjustable downlighter
Manufacturing standard: EN 60 598 Total luminaire wattage (max): 47W
Primary luminaire Die-cast aluminium Power factor: > 0.9
e-wired non dimmable driver
• Supplied with pre-wired non dimmable driver
construction material: Rated luminous flux (lm): 2,700lm
st construction with protective clear glass
Finish:
See Notes Luminaire efficacy: 87lm/W
Accessories: N/A Beam / distribution: Symmetric, see LDC
f beam angles
• Versatile range of beam angles
ed with pre-wired non dimmable driver
Light source type:
Driver type: Project 1
LED
Constant current
CRI / Colour temperature: > 80 / 3,000K
Colour Variation: ≤ 3 SDCM
10.08.2014
Drive current or voltage: 1,050mA Operator
Luminaire Lifetime: ≥ 50,000 hours

le range of beam angles


Dimming & type: DALI, remote Lifetime Basis: L70 / F10 @ Ta 250C
Telephone
Fax
e-Mail
IP: IP20
Projection Lighting UA30**8N* Universal Adjustable / Luminaire Data Sheet
Luminaire distribution curve (LDC)
Luminous emittance 1:
Location:
See our luminaire catalog for an image of the Gatehouses
luminaire.

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Luminaire to be passively cooled.
80+ 3000lm CRI 80+CRI 80+
400/700/1000/1300lm 2000lm CRI 80+ 3000lm CRI 80+ 3. Fixture to be powder coated (RAL
RI 98 1300lm
700lmCRI
CRI98
98 1000lm CRI 98 1300lm CRI 98 9016).
Luminaire classification according to CIE: 100 Luminous emittance 1:
CRI 80+ 2000lm CRI
CIE flux80+
code: 99 100 1003000lm
100 90 CRI 80+
8 1000lm CRI 98
142mm
1300lm CRI 98
Rotate: 355°
142mm
104mm
86mm
142mm
104mm Rotate: 355°
86mm 104mm Tilt: 20° Tilt: Tilt:
28˚ 20°
28° Gy
02mm 108mm
Cut Out: Tilt:
Ø102mm20° Tilt: 28˚
Cut Out: Ø102mm

The drawings on this page are


indicative. Refer to the architectural

• Satin Nickel option • Satin Nickel option


• Satin Nickel option Page 1
drawings for correct setting out,
mounting details and final dimensions.

Type:

D1e

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 24 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
EBLE
PIN HOLE
HOLE
mal glare
Abu Dhabi Airports Company PJSC

• Fixed downlight with minimal glare


Luminaire Description: Recessed fixed downlight
Specification, Section 265120

n options
• Various reflector and lumen options
light with minimal glare
Manufacturing standard: EN 60 598 Total luminaire wattage (max): 54W
Primary luminaire Die-cast aluminium Power factor: > 0.9

n dimming driver
• Supplied with pre-wired non dimming driver
construction material:
ector and lumen options
Finish:
See Notes
Rated luminous flux (lm): 3,560lm
Luminaire efficacy: 66lm/W
Accessories: N/A Beam / distribution: Symmetric, see LDC

sm• AlphaLED Fast Fix mechanism


th pre-wired non dimming driver
Light source type:
Driver type: Project 1
LED
Constant current
CRI / Colour temperature: > 80 / 3,000K
Colour Variation: ≤ 3 SDCM
14.08.2014
Drive current or voltage: 1,050mA Luminaire Lifetime: ≥ 50,000 hours
ast Fix mechanism
gen and metal halide
• Ideal replacement for halogen and metal halide
Dimming & type: DALI, remote
Operator
Telephone
Fax
e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: IP20

ement for halogen and metal halide


are reduction baffle
• Supplied with extended glare reduction baffle
Location:
Projection Lighting N240**8MW Nimble Pin Hole / Luminaire Data Sheet
Luminaire distribution curve (LDC)
Luminous emittance 1:

th extended glare reduction baffle


See our luminaire catalog for an image of the Security
luminaire.
Circulation
Holdrooms
Transfer Building
r

ide
fle Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
0+ 700/1000/1300lm
4000lm CRI CRI
80+ 80+ 2000lm CRI 80+ 3000lm CRI 80+ 4000lm CRI
2. Luminaire to be 80+
passively cooled.
8 700lm CRI
2000lm CRI98
98 1000lm CRI 98 1300lm CRI 98 2000lmto CRI
3. Fixture 98 coated (RAL
be powder
00lm CRI 80+ 3000lm CRI 80+ 4000lm CRI 80+
9016).
000lm CRI 98 1300lm CRI 98 2000lm CRI 98
Luminaire classification according to CIE: 100 Luminous emittance 1:
CIE flux code: 99 100 100 100 89

157mm 157mm
27mm 107mm 125mm 157mm 127mm
125mm 127mm
PRODUCT CODE
Lumen Output:
(07) 700 lm
(10) 1000 lm
(13) 1300 lm

132mm
(20) 2000 lm
(30) 3000 lm
(40) 4000 lm
Colour Temps: Cut Out: Ø122mm
Cut Out: Ø122mm (27)
(30)
2700K
3000K
(35) 3500K
(40) 4000K
Colour Rendering:
(7) Vibrancy
(8) CRI 80+
(9) CRI 98
(CRI 98 up to 2000 Lumens)

Beam Angles:
(N) Narrow: 20°
(M) Medium: 40°
(W) Wide: 60°
Colour:
(W) White

The drawings on this page are


indicative. Refer to the architectural
N2 _ _ _ _ _ _ _ /**/ **
drawings for correct setting out,
Page 1 mounting details and final dimensions.
Options:
Dimming: / M3 Emergency
/ DT Trailing EdgeL4
/ DL Leading Edge L4
/ DD DALI
/ DA Analogue (1-10V)
(Other dimming options available by special order) 91
Type:
D2

D2
20/03/2014 12:55

Detail 5
Ceiling interface at Transfer Building north section from MTC-A-41-TB-L2-0-_-__-00-654

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 25 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
iRoll

Design iGuzzini iGuzzini


Luminaire Description: Surface mounted downlight
july 2014
Manufacturing standard: EN 60 598 Total luminaire wattage (max): 13W
Primary luminaire Die-cast aluminium Power factor: > 0.9
construction material: iRollRated luminous flux (lm): 1,030lm
Finish: Anodised aluminium silver Luminaire efficacy: 79lm/W
Accessories: See Notes code Beam / distribution: Symmetric, see LDC
MQ09
Light sourceProject
type: 1
LED CRI / Colour temperature: > 80 / 3000K
Driver type: Constant current Colour Variation: 15.08.2014 ≤ 3 SDCM

Technical description
Drive current or voltage: 300mA Operator
LED
Telephone Luminaire Lifetime:luminaire;≥integrated
lamp, ceiling-mounted 50,000 hours
DALI dimmable control gear. Die-cast
Fax
Dimming & type: DALI, integral shaped
e-Mail Lifetime Basis:
aluminium cylindrical body with L70 / F10element
diffuser @ Ta 25 and0
Cintegrated lamp and optic
IP: IP20 aluminium vapours and finished with a protective, anti-scratch layer; safety glass cover
D3 D3 iGuzzini illuminazione S.p.A MQ09_LY28 iRoll: Ceiling-mounted luminaire - warm LED -
General light - DALI dimmable... / Luminaire Data Sheet
Installation
Luminaire distribution curve (LDC) Location:
D3 D3
D3
Plateemittance
Luminous fixed to
ceiling using screws and screw anchors (not included); cylindrical body fi
1:
D3
See our luminaire catalog for an image of the
bayonet assembly systems ensuring simple installation
Bussing and maintenance. Wall or pend
Area lit disk
luminaire. special accessory kits with a separate code.
Circulation lit disks
L2c
L2c
L2c

L2c
L2c

D3
D3
Size (mm)
L2c D3 D3
D3 ø140x200

D3 Colour Notes:
White (01) | Grey (15)
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
Weight (kg) 2. Luminaire to be passively cooled.
1.18
3. Luminaire to be positioned in line with
all L2c fixtures are recommended to
be to be spaced equally apart the disc fabric.
a mock-up is recommended to
Luminaire classification
ensureaccording
desired effectto
is CIE: 100
achieved Mounting
Luminous emittance 1: 4. Refer to architectural details for fixing
CIE flux code: 98 99 100 100 86
wall surface | ceiling surface | ceiling pendant
details.

L2c
D3
Wiring info
Control gear integrated in luminaire; mains and optic unit connections made with quick
D3
L2c

Notes
L2c
L2c

D3
L2c

D3
Kit for wall-mounting: code no. 9439
D3

D3

Com

D3
D3

Detail 9
Detail plan of circulation lit disk from MTC-A-93-TB-L_-_-_-__-00-135 ARUP LIGHTING D3 D3

Product configuration: MQ09+LED


MARK_UPS
D3
D3

LED: LED WARM


L2c L2c L2c L2c L2c
L2c
D3

Product characteristics
D3
D3
D3

Total lighting output [Lm]: 1031.64 Total luminous flux a


D3
D3
D3 The drawings on this page are
L2c ARUP LIGHTIN
Total power [W]: 12.7 EmergencyMARK_UPS
indicative. Refer to the architectural luminou D3

Luminous efficacy [Lm/W]: 81.23 Voltage [V]: -


drawings for correct setting out,
D3 D3
D3 Page 1
D3

Number of optical assemblies: 1 mounting details and final dimensions.


L2c

L2c L2c L2c L2c L2c


L2c L2c L2c L2c
L2c

Optical assembly Characteristics 1


D3

Type:
D3
D3
D3
D3 Light Output Ratio (L.O.R.) [%]: 86 Number of lamps for
ARUP LIGHTING
Lamp code: LED Socket: /
L2c
MARK_UPS
D3

ZVEI Code: LED Ballast losses [W]: 2


D3

Nominal power [W]: 10


Nominal luminous [Lm]: 1200
D3
Colour temperature [
CRI: 80
Sheet 1/2
2c L2c
Lamp maximum intensity [cd]: /
Detail section of Bussing Area lit disk from MTC-A-93-TB-L_-0-_-__-00-536 Wavelength [Nm]: /
Beam angle [°]: 58° MacAdam Step: <3
Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 26 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) Polar January 31, 2015
Recommended fixture spacings as indicated above
ARM
01
D3
D3
D3
ARM

Abu Dhabi Airports Company PJSC


01

Specification, Section 265120

L2c
ARM L2c L2c L2c L2c L2c L2c
01

D3
D3 D3 D3
D3 D3

D3

02
ARM
01
D3
D3
D3
SFS ARM
01 01 D3

SFS
01

L2c
2 TOP VIEW OF FRAMING
L2c
SFS L2c L2c L2c L2c SCALEL2c
L2c 1:20
01

L2c L2c L2c L2c

D3 D3
D3 D3

D3 02 31.01.15 BULLETIN 145


01 31.10.14 BULLETIN 120
00 15.07.12 ISSUED FOR CONSTRUCTION
02

D3 ARM
01 ISSUED FOR CONSTRUCTION

SFS
D3
01 ABU DHA
AIRPORTS COM
ABU DHABI AIRPORTS COMPANY
SFS
01 8,9
93535 Kohn Pedersen Fox Associates
(International) PA
Architects and Planning Consultants

1 DETAILS
L2c 7a Langley Street
London WC2H 9JA

SCALE 1:5 2 TOP VIEW OF FRAMING England


T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com

SFS SCALE 1:20


01
Detail 1 Detail 2 ARM
01
L2c L2c L2c L2c 02
SFS
Detail section of Bussing Area lit disk from MTC-A-93-TB-L_-0-_-__-00-536 01

SFS ABU DHABI INTERNATIONAL AI


01 02 31.01.15 BULLETIN 145 MIDFIELD TERMINAL COMPL
SFS 01 31.10.14 BULLETIN 120
01 00 15.07.12 ISSUED FOR CONSTRUCTION
BUSSING AREA LIGHTING
DETAILS - LIT DISC
D3 ARM
01 ISSUED FOR CONSTRUCTION

3 SECTION MTC A 93 TB __ L_.0 _.__ 0


SCALE 1:20
ABU DHABI
AIRPORTS
KPF COMPANY
MC KF JH

ABU DHABI AIRPORTS COMPANY


8,9 WBS A
93535 2014 KOHN
KohnPEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights rese
Pedersen Fox Associates
(International) PA
Architects and Planning Consultants

1 DETAILS 7a Langley Street


London WC2H 9JA
England
T: +44 (0)207 319 5300
SCALE 1:5 F: +44 (0)207 497 1175
www.kpf.com

ARM
01
02
SFS
01

SFS ABU DHABI INTERNATIONAL AIRPORT


01 MIDFIELD TERMINAL COMPLEX
SFS
01
BUSSING AREA LIGHTING
DETAILS - LIT DISC

3 SECTION MTC A 93 TB __ L_.0 _.__ 00.536 02


SCALE 1:20

KPF MC KF JH 30.06.2010

WBS AUH.06.10.0401

2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights reserved. Do not scale.

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

D3
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 27 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
NIVERSAL OPEN
SFDFTTFEEPXOMJHIUXJUIEFFQTFUSFnFDUPS
t 'JYFESFDFTTFEEPXOMJHIUXJUIEFFQTFUSFnFDUP
Abu Dhabi Airports Company PJSC Specification, Section 265120

TUDPOTUSVDUJPO
t %JFDBTUDPOTUSVDUJPO
Luminaire Description: Recessed fixed downlight
FDFTTFEEPXOMJHIUXJUIEFFQTFUSFnFDUPS
Manufacturing standard: EN 60 598 Total luminaire wattage (max): 19W

DPOUSPMTFDPOEBSZSFnFDUPS
t (MBSFDPOUSPMTFDPOEBSZSFnFDUPS
Primary luminaire Die-cast aluminium Power factor: > 0.9
TUDPOTUSVDUJPO
construction material: Rated luminous flux (lm): 1,640lm
Finish: See Notes Luminaire efficacy: > 86lm/W

DPOUSPMTFDPOEBSZSFnFDUPS
Accessories:
FEXJUIQSFXJSFESFNPUFOPOEJNNJOHESJWFS
N/A
t 4VQQMJFEXJUIQSFXJSFESFNPUFOPOEJNNJOHE
Light source type: LED
Beam / distribution: Symmetric, see LDC
CRI / Colour temperature: > 80 / 3,000K
Driver type: Project 1 Constant current Colour Variation: ≤ 3 SDCM

FEXJUIQSFXJSFESFNPUFOPOEJNNJOHESJWFS
10.08.2014
Drive current or voltage: 700mA Luminaire Lifetime: ≥ 50,000 hours
BUJWFSBOHFPGBDDFTTPSJFT
t %FDPSBUJWFSBOHFPGBDDFTTPSJFT
Dimming & type: DALI, remote
Operator
Telephone
Fax
e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: IP20
BUJWFSBOHFPGBDDFTTPSJFT Projection Lighting UO20**8M* Universal / Luminaire Data Sheet
Luminaire distribution curve (LDC) Location:
Luminous emittance 1:

See our luminaire catalog for an image of the Circulation


luminaire.
Janitor’s closet

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Luminaire to be passively cooled.
80+ 2000lm CRI 80+CRI 80+ 3000lm
m CRI400/700/1000/1300lm 2000lm CRI
CRI 80+
80+ 3000lm CRI 80+ 3. Fixture to be powder coated (RAL

mI CRI 400/700lm
98 80+ 2000lm
1000lm CRI
CRICRI
80+9898 1300lm
1000lm
3000lm CRI 98
CRI 98
CRI 80+ 1300lm CRI 98 9016).
Luminaire classification according to CIE: 100 Luminous emittance 1:
98 1000lm CRI 98code: 99
CIE flux 100 1001300lm
100 82 CRI 98

115mm 127mm
115mm 127mm
96mm 96mm
115mm 127mm
96mm

108mm
Cut Out: Ø95mm Cut Out: Ø95mm
Cut Out: Ø95mm

ee by
by
Available
specialorder
special order
by special order
The drawings on this page are
indicative. Refer to the architectural
drawings for correct setting out,

tt
/JDLFM4BUJOPQUJPO
/JDLFM4BUJOPQUJPO
t /JDLFM4BUJOPQUJPO
Page 1 mounting details and final dimensions.

Type:

D6

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 28 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Suspended fixed downlight

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 62W


Primary luminaire Die-cast aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 4,750lm
Finish: Anodised aluminium silver Luminaire efficacy: 77lm/W
Accessories: See Notes Beam / distribution: Symmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 3,000K
Driver type: Project 1 Constant current Colour Variation: ≤ 3 SDCM
07.03.2014
Drive current or voltage: 1,050mA
iRoll Operator
Luminaire Lifetime: ≥ 50,000 hours
Dimming & type: DALI, remote Telephone
Fax Lifetime Basis: L70 / F10 @ Ta 250C
e-Mail
Design iGuzzini
IP: IP20 iGuzzini

iGuzzini illuminazione S.p.A TG65 iRoll TG65 / Luminaire Data Sheet


july 2014
Luminaire distribution curve (LDC)
Luminous emittance 1:
Location:
See our luminaire catalog for an image of the Baggage Reclaim
luminaire. iRoll

code
MQ09

L5

Technical description Notes:


LED lamp, ceiling-mounted luminaire; integrated DALI dimmable1. Refer
controltogear. Die-cast
Section aluminium
‘2.0 Products’ plate for surfa
of this
shaped aluminium cylindrical body with diffuser element and integrated lampforand
specification optic units;
additional reflector vacuum-m
requirements.
aluminium vapours and finished with a protective, anti-scratch layer; safety glass cover over LED lamp. General
2. Luminaire to be passively cooled.
3. Suspension rod and mounting plate to
Installation be provided.
Plate fixed to ceiling Luminous
Luminaire classification according to CIE: 100
using screws and screw anchors (not included); cylindrical body fitted with a mechanical s
emittance 1: 4. Luminaire to be suspended in line with
CIE flux code: 99 100 100 100 bayonet
80 assembly systems ensuring simple installation and maintenance. Wall or pendant application option av
panels.
special
L4d
accessory kits with a separate code.

Size (mm)
ø140x200

Colour
White (01) | Grey (15)

Weight (kg)
1.18

Mounting
D8
wall surface | ceiling surface | ceiling pendant

ARUP LIGHTING
Wiring info
MARK_UPS
Control gear integrated in luminaire; mains and optic unit connections made with quick coupling terminal blocks
The drawings on this page are
indicative. Refer to the architectural
drawings for correct setting out,
Notes Page 1 mounting details and final dimensions.
Kit for wall-mounting: code no. 9439
L5 L5

Type: Complies with EN60598-1 an

Product configuration: MQ09+LED


D8
Section detail of Baggage Reclaim light shelf from MTC-A-94-TB-L_-_-0-00-09-033
LED: LED WARM Sheet 1/2

Contract: Midfield Terminal BuildingProduct


– General Contractor, AUH.06.10.0401
characteristics Page 29 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07)lighting output [Lm]: 1031.64
Total January 31, 2015
Total luminous flux at or above an angle of 90
Total power [W]: 12.7 Emergency luminous flux [Lm]: /
Luminous efficacy [Lm/W]: 81.23 Voltage [V]: -
Number of optical assemblies: 1
Abu Dhabi Airports Company PJSC Specification, Section 265120

D8

L5 L5

L8

Detail 3
Section detail through Baggage Reclaim light shelf from MTC-A-94-TB-L_-_-0-00-09-033

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

D8
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 30 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Suspended adjustable and lockable projector

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 62W


Primary luminaire Die-cast aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 4,750lm
Finish: Anodised aluminium silver Luminaire efficacy: 77lm/W
Accessories: See Notes Beam / distribution: Symmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 3,000K
Driver type: Project 1 Constant current Colour Variation: ≤ 3 SDCM
07.03.2014
Drive current or voltage: 1,050mA Operator
Luminaire Lifetime: ≥ 50,000 hours
Dimming & type: DALI, remote Telephone
Fax Lifetime Basis: L70 / F10 @ Ta 250C
e-Mail
IP: IP20
iGuzzini illuminazione S.p.A TG65 iRoll TG65 / Luminaire Data Sheet
Luminaire distribution curve (LDC)
Luminous emittance 1:
Location:
See our luminaire catalog for an image of the Baggage Reclaim
luminaire.
Processor Security

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Luminaire to be passively cooled.
3. Luminaire to be suspended between
panels.
168
Luminaire classification according to CIE: 100 Luminous emittance 1: 4. Suspension rod and mounting plate to
CIE flux code: 99 100 100 100 80
be provided.
5. At Baggage Reclaim Lluminaire
to be suspended in line with panels.
Fixture to be fixed to the substrate,
at an elevation that matches adjacent
ceiling panels.
6. Luminaire with adjustable and
lockable mechanism for aiming.

240
Ø1
40

199

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
Page 1 mounting details and final dimensions.

Type:

D8c
Sheet 1/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 31 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

L2c L2c

D8c

L3.0 PUBLIC GALLERY - CLEAR INFILL GLASS


3 L3.0 OFFICE GLA
Detail 1 SCALE 1:20
SCALE 1:50
Detail through Public Gallery clear infill glass from MTC-A-52-TB-L_-_-_-__-00-630

4
-

8
-

2 L3.0 PUBLIC GALLERY INFILL GLASS WITH FIRE RATED SOFFIT


SCALE 1:20

4 DETAIL @ SLA
SCALE 1:5
MILD STEEL SUPPORT BRACKET GLAZED NON-FIRE RATED FLOORING/BRIDGE GLZ
12B
STAINLESS STEEL TRIM DCM S
4MM THICK 03
4
B

02 G
C
4
C

TYPE L2c LIGHT The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

SUPPORT BRACKET SUPPORT BRACKET


Type:

STAINLESS STEEL TRIM DCM


03
DCM STAINLESS STEEL TRIM
03
D8c
Sheet 2/2 R
D
B

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 32 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) GRC UNIT GRC GRC GRC UNIT January 31, 2015
01 01
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Wall mounted adjustable and lockable projector

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 62W


Primary luminaire Die-cast aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 4,750lm
Finish: Anodised aluminium silver Luminaire efficacy: 77lm/W
Accessories: See Notes Beam / distribution: Symmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 3,000K
Driver type: Project 1 Constant current Colour Variation: ≤ 3 SDCM
07.03.2014
Drive current or voltage: 1,050mA Operator
Luminaire Lifetime: ≥ 50,000 hours
Dimming & type: DALI, remote Telephone
Fax Lifetime Basis: L70 / F10 @ Ta 250C
e-Mail
IP: IP20
iGuzzini illuminazione S.p.A TG65 iRoll TG65 / Luminaire Data Sheet
Luminaire distribution curve (LDC)
Luminous emittance 1:
Location:
See our luminaire catalog for an image of the Baggage Reclaim
luminaire.

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Luminaire to be passively cooled.
3. Luminaire with adjustable and
lockable mechanism for aiming.
168
Luminaire classification according to CIE: 100 Luminous emittance 1: 4. To be supplied with all necessary
CIE flux code: 99 100 100 100 80
mounting accessories.

240
Ø1
40

199

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
Page 1 mounting details and final dimensions.

Type:

D8d
Sheet 1/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 33 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

L5

L2c L18 L18 L2c


D8d

Detail 1
Terminal Building section at CIP Lounge/ Garden from MTC-A-03-TB-L_-_-5-00-00-611

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

D8d
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 34 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Recessed adjustable downlight

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 100W


Primary luminaire Die-cast aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 7,300lm
Finish: See Notes Luminaire efficacy: 73lm/W
Accessories: N/A Beam / distribution: Symmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 3,000K
Driver type: Project 1 Constant current Colour Variation: ≤ 3 SDCM
07.03.2014
Drive current or voltage: 1,500mA Operator
Luminaire Lifetime: ≥ 50,000 hours
Dimming & type: DALI, remote Telephone
Fax Lifetime Basis: L70 / F10 @ Ta 250C
e-Mail
IP: IP20
iGuzzini illuminazione S.p.A TG65 iRoll TG65 / Luminaire Data Sheet
Luminaire distribution curve (LDC)
Luminous emittance 1:
Location:
See our luminaire catalog for an image of the Departures Hall skylights
luminaire.
Departures Hall perimeter
Centre Space skylights

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Luminaire to be passively cooled.
3. Luminaire capable to be rotated 30°
relative to the horizontal plane and 358°
Luminaire classification according to CIE: 100 Luminous emittance 1: about the vertical axis.
CIE flux code: 99 100 100 100 80
226 4. Luminaire with adjustable and
lockable mechanism for aiming.
5. Fixture to be powder coated (RAL
17

860M).
0
119

30° 0
14

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
Page 1 mounting details and final dimensions.

Type:

D8e
Sheet 1/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 35 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
01 07.07.14 BULLETIN 92
00 15.07.12 ISSUED FOR CONSTRUCTION

ISSUED FOR CONSTRUCTION


Abu Dhabi Airports Company PJSC Specification, Section 265120
ABU DHABI
AIRPORTS COMPANY
ABU DHABI AIRPORTS COMPANY

Kohn Pedersen Fox Associates


(International) PA
Architects and Planning Consultants
7a Langley Street
London WC2H 9JA
England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com

ABU DHABI INTERNATIONAL AIRPORT


MIDFIELD TERMINAL COMPLEX

CENTRE ROOF CEILING


AXONOMETRIC
140

D8e MTC A 41 TB __ L4.0 _.__ 00.030 03


170

230
KPF MC KF JH 25.09.2009

800 500 WBS AUH.06.10.0401

2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights reserved. Do not scale.

Detail 3
Section detail of Centre Roof skylight from MTC-A-41-TB-L4-0-_-__-00-030

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

D8e
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 36 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Recessed adjustable downlight

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 100W


Primary luminaire Die-cast aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 7,300lm
Finish: See Notes Luminaire efficacy: 73lm/W
Accessories: N/A Beam / distribution: Symmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 3,000K
Driver type: Project 1 Constant current Colour Variation: 27.03.2014
≤ 3 SDCM
Drive current or voltage: 1,500mA Operator Luminaire Lifetime: ≥ 50,000 hours
Telephone
Dimming & type: DALI, remote Fax
e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: IP20
IGUZZINI MK22 Palco 63.3W / Luminaire Data Sheet

Luminaire distribution curve (LDC)


Luminous emittance 1: Location:
Departures Hall skylights

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Luminaire to be passively cooled.
3. Luminaire capable to be rotated 30°
relative to the horizontal plane and 358°
Luminaire classification according to CIE: 100 Luminous emittance 1: about the vertical axis.
CIE flux code: 100 100 100 100 86

Adjustable spotlight with adapter for installation on electrified track for high
4. Luminaire with adjustable and
output LED lamp with 226 monochrome emission in a warm White (3000K) tone.
Medium optic (15-20°). Electronic ballast integrated in the product. Luminaire
lockable mechanism for aiming.
made of die-cast aluminium and thermoplastic material, allows 360° rotation
about the vertical axis and 90° tilting relative to the horizontal plane. The 5. Fixture to be powder coated (RAL
luminaire has mechanical aiming locks for both movements, operated using
the same tool on two screws, one at the side of the rod and one on the 860M).
adapter for the track. Passive heat dissipation. Spotlight designed to contain
17

up to two flat accessories simultaneously. Another external component can


0

also be applied, selected from directional flaps and an anti-glare screen. All
external accessories rotate 360° about the spotlight longitudinal axis. LED
lifetime with residual flow at 80% (L80): 50,000 h at Ta 25°

MK22.001 - Large body spotlight - 55W - LED 4800 lm - warm white - CRI
(Ra) 80 - electronic ballast - medium optic - Bianco
LM31 - Lamp LED Warm White
119

30° 0
14

The drawings on this page are


indicative. Refer to the architectural
Page 1
drawings for correct setting out,
mounting details and final dimensions.

Type:

D8f

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 37 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Recessed adjustable downlight

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 100W


Primary luminaire Die-cast aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 7,300lm
Finish: See Notes Luminaire efficacy: 73lm/W
Accessories: N/A Beam / distribution: Symmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 6,500K
Driver type: Project 1 Constant current Colour Variation: 27.03.2014
≤ 3 SDCM
Drive current or voltage: 1,500mA Operator Luminaire Lifetime: ≥ 50,000 hours
Telephone
Dimming & type: DALI, remote Fax
e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: IP20
IGUZZINI MK22 Palco 63.3W / Luminaire Data Sheet

Luminaire distribution curve (LDC)


Luminous emittance 1: Location:
Departures Hall skylights

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Luminaire to be passively cooled.
3. Luminaire capable to be rotated 30°
relative to the horizontal plane and 358°
Luminaire classification according to CIE: 100 Luminous emittance 1: about the vertical axis.
CIE flux code: 100 100 100 100 86

Adjustable spotlight with adapter for installation on electrified track for high
4. Luminaire with adjustable and
output LED lamp with 226 monochrome emission in a warm White (3000K) tone.
Medium optic (15-20°). Electronic ballast integrated in the product. Luminaire
lockable mechanism for aiming.
made of die-cast aluminium and thermoplastic material, allows 360° rotation
about the vertical axis and 90° tilting relative to the horizontal plane. The 5. Fixture to be powder coated (RAL
luminaire has mechanical aiming locks for both movements, operated using
the same tool on two screws, one at the side of the rod and one on the 860M).
adapter for the track. Passive heat dissipation. Spotlight designed to contain
17

up to two flat accessories simultaneously. Another external component can


0

also be applied, selected from directional flaps and an anti-glare screen. All
external accessories rotate 360° about the spotlight longitudinal axis. LED
lifetime with residual flow at 80% (L80): 50,000 h at Ta 25°

MK22.001 - Large body spotlight - 55W - LED 4800 lm - warm white - CRI
(Ra) 80 - electronic ballast - medium optic - Bianco
LM31 - Lamp LED Warm White
119

30° 0
14

The drawings on this page are


indicative. Refer to the architectural
Page 1
drawings for correct setting out,
mounting details and final dimensions.

Type:

D8g

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 38 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
February 2014

Adjustable downlight – 56,4W LED warm white 3000K – 6000 lm – electronic driver – medium optic
Abu Dhabi Airports Company PJSC Reference: A_D9b Specification, Section 265120
Product code:
TX65
Luminaire Description: Recessed fixed downlight
Technical description:
Manufacturing standard: EN 60 598Adjustable recessed roundTotalluminaire designed
luminaire to use a(max):
wattage LED lamp. Version with rim for surface-mounting. Ref
65W
vacuum-metalized with aluminum vapors with an anti-scratch protective layer. Die-cast aluminum body and pa
Primary luminaire Die-cast system.
aluminium Power factor: > 0.9
Product complete with LED unit in a warm white tone 3000K and DALI driver separate from the lumin
construction material: Rated
can be rotated 30° relative to theluminous fluxand
horizontal plane (lm):
358°4,750lm
about the vertical axis. Screw-operated mechanic
Finish: See Notesluminaires to be aimed onLuminaire
the vertical efficacy:
axis and horizontal plane.
73lm/WLED lifetime with residual flow at 80% (L80) 5
Ta 25°. Medium optic (30°).
Accessories: N/A Beam / distribution: Symmetric, see LDC
Light source type: LED Installation:
CRI / Colour temperature: > 80 / 3,000K
Driver type: Project 1 ConstantInstalled Colour
currentusing torsion springs Variation:
which allow easy recessing ≤ in 3 SDCM
false ceilings with thickness from 1 mm to 25 mm
07.03.2014
Drive current or voltage: 1,050mA Operator
Luminaire Lifetime: ≥ 50,000 hours
Dimming & type: Dimension:
DALI, remote Fax Lifetime Basis:
Telephone
L70 / F10 @ Ta 250C
Ø 226 mm - H 255 e-Mail
mm
IP: IP20
Colour: S.p.A TG65 iRoll TG65 / Luminaire Data Sheet
iGuzzini illuminazione
RAL 9016 /Aluminium
Luminaire distribution curve (LDC)
Luminous emittance 1:
Location:
Weight [Kg]: Welcomers Hall
See our luminaire catalog for an image of the
luminaire. 2,4
Baggage Reclaim
Mounting: Arrival Lobby
Ø212 ceiling hole
Processor Departure Public Gallery
Wiring:
Product complete with electronic components
Notes:
Product configuration: TX65+LED
1. Refer to Section ‘2.0 Products’ of this
TX65: Round adjustable luminaire D = 226 mm H=255mm warm white 56,4W
specification LED 6000lm
for additional with DALI ballast -
requirements.
2. Luminaire to be passively cooled.
LED: LED Neutral White
3. Detail to be coordinated with Architect
Engineer.
Product
Luminaire classification according to CIE: 100 Characteristics:
Luminous emittance 1: 4. Fixture to be powder coated (RAL
CIE flux code: 99 100 100 100 80 Total lighting Output [Lm]: 4750 Total luminous Flux at or above an angle of 9
9016).
Total power [W]: 65 Emergency Luminous Flux [Lm]: /
Luminous Efficacy [Lm/W]: 73.1 Cut off angle: 48°
Number of optical assemblies: 1 Power factor: 0.96

Optical assembly Characteristics 1:


Light Output Ratio (L.O.R.) [%]: 78 Number of lamps for vano: 1
Lamp code: LED Socket: /
ZVEI Code: LED Ballast Losses [W]: 10
Nominal power [W]: 55 Colour temperature [K]: 4000
Nominal luminous [Lm]: 5800 CRI: 80
Lamp maximum intensity [cd]: / Wavelength [Nm]: /
Beam Angle [°]: 38° MacAdam Step: <3

Complies with EN
D9

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
Page 1 mounting details and final dimensions.
L2c

Type:

Detail 10
D9
Detail section of Processor Departure Public Gallery ceiling from MTC-A-41-TB-L2-0-5-00-00-493

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 39 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
February 2014

Adjustable downlight – 56,4W LED warm white 3000K – 6000 lm – electronic driver – medium optic
Abu Dhabi Airports Company PJSC Reference: A_D9b Specification, Section 265120
Product code:
TX65
Luminaire Description: Recessed adjustable downlight
Technical description:
Manufacturing standard: EN 60 598Adjustable recessed roundTotalluminaire designed
luminaire to use a(max):
wattage LED lamp. Version with rim for surface-mounting. Ref
80W
vacuum-metalized with aluminum vapors with an anti-scratch protective layer. Die-cast aluminum body and pa
Primary luminaire Die-cast system.
aluminium Power factor: > 0.9
Product complete with LED unit in a warm white tone 3000K and DALI driver separate from the lumin
construction material: Rated
can be rotated 30° relative to theluminous fluxand
horizontal plane (lm):
358°4,750lm
about the vertical axis. Screw-operated mechanic
Finish: See Notesluminaires to be aimed onLuminaire
the vertical efficacy:
axis and horizontal plane.
59lm/WLED lifetime with residual flow at 80% (L80) 5
Ta 25°. Medium optic (30°).
Accessories: N/A Beam / distribution: Symmetric, see LDC
Light source type: LED Installation:
CRI / Colour temperature: > 80 / 3,000K
Driver type: Project 1 ConstantInstalled Colour
currentusing torsion springs Variation:
which allow easy recessing ≤ in 3 SDCM
false ceilings with thickness from 1 mm to 25 mm
07.03.2014
Drive current or voltage: 1,350mA Operator
Luminaire Lifetime: ≥ 50,000 hours
Dimming & type: Dimension:
DALI, remote Fax Lifetime Basis:
Telephone
L70 / F10 @ Ta 250C
Ø 226 mm - H 255 e-Mail
mm
IP: IP20
Colour: S.p.A TG65 iRoll TG65 / Luminaire Data Sheet
iGuzzini illuminazione
RAL 9016 /Aluminium
Luminaire distribution curve (LDC)
Luminous emittance 1:
Location:
Weight [Kg]: Welcomers Hall
See our luminaire catalog for an image of the
luminaire. 2,4
Baggage Reclaim
Mounting: L14 Arrival Lobby
b D9b D9b D9b
Ø212 ceiling hole
Transit Area infill ceiling
Wiring:
Product complete with electronic components
Notes:
Product configuration: TX65+LED
1. Refer to Section ‘2.0 Products’ of this
TX65: Round adjustable luminaire D = 226 mm H=255mm warm white 56,4W
specification LED 6000lm
for additional with DALI ballast -
requirements.
2. Luminaire to be passively cooled.
LED: LED Neutral White
ARUP LIGHTING 3. Luminaire capable to be rotated 30°
MARK_UPS
Rev1
relative to the horizontal plane and 358°
Product Characteristics: about the vertical axis.
L14
D9b
D9b D9b D9b
Luminaire classification according to CIE: 100 Luminous emittance 1:
CIE flux code: 99 100 100 100 80 Total lighting Output [Lm]: 4750 Total
Adjustable aiming 4. Detail to luminous Flux atwith
be coordinated or above an angle of 9
Architect
Total power [W]: 65 Engineer.
Emergency Luminous Flux [Lm]: /
Luminous Efficacy [Lm/W]: 73.1 Cut off
5. Fixture angle:
to be 48° coated (RAL
powder
Number of optical assemblies: 1 9016).Power factor: 0.96
D9b D9b D9b D9b D9b

Optical assembly Characteristics 1:


Light Output Ratio (L.O.R.) [%]: 78 Number of lamps for vano: 1
L14
Lamp code: LED Socket: /
ZVEI Code: LED Ballast Losses [W]: 10
L14 L14

L14

L14 Nominal power [W]: 55 Colour temperature [K]: 4000


solid in order

Nominal luminous
shadow [Lm]: 5800
not to cast
CRI: 80
er
D9
D9b
Lamp maximum intensity [cd]: / Wavelength [Nm]: /
L14 Beam Angle [°]: 38° MacAdam Step: <3

Complies with EN

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
Page 1 mounting details and final dimensions.

D9b D9b D9b


D9b D9b
L14
Type:

D9b
Detail sections of Lighting Lozenge in Arrival Lobby from MTC-A-93-TB-L_-_-_-__-00-531 Sheet 1/3

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 40 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
03

L14 L14 L14

3,4
L14

D9b
9b D9b D9b 6 SECTION - PROCESSOR ARRIVALS, L0.0

Abu Dhabi Airports Company PJSC


SCALE 1:20

Specification, Section 265120


ARM
01

SFS
10
A93530
03
02
31.01.15
31.10.14
BULLETIN 145
BULLETIN 120
01
01 25.07.14 BULLETIN 101
ARM 00 15.07.12 ISSUED FOR CONSTRUCTION SFS
01
03 01
ISSUED FOR CONSTRUCTION
SFS
ABU DHABI 01
AIRPORTS COMPANY
2 ABU DHABI AIRPORTS COMPANY

12,13
Kohn Pedersen Fox Associates
(International) PA

D9b D9b D9b D9b D9b


Architects and Planning Consultants
L14 L14 7a Langley Street
London WC2H 9JA

A93530
England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com
L14
L14

D9b

L14 7 SECTION - PROCESSOR ARRIVALS, L0.0 ABU DHABI INTERNATIONAL AIRPORT


SFS
SCALE 1:10
MIDFIELD TERMINAL COMPLEX
01

LIGHTING LOZENGE
L14 DETAILS (2 OF 2)

MTC A 93 TB __ L_._ _.__ 00.531 03


1 PLAN & RCP - ARRIVALS IMMIGRATION HALL, L0.1 SFS
SCALE 1:20 4 SECTION - ARRIVALS IMMIGRATION HALL, L0.1 SLOPED CEILING 01 KPF MC KF JH 30.06.2010

SCALE 1:10

Detail 4
WBS AUH.06.10.0401

2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights reserved. Do not scale.

L14

D9b D9b
D9b D9b D9b

2 Detail 2 - ARRIVALS IMMIGRATION HALL, L0.1


SECTION
SCALE 1:20
Detail sections of Lighting Lozenge in Arrival Lobby from MTC-A-93-TB-L_-_-_-__-00-531

ARM
10
01 A93530
ARM
01

L15
SFS
01 L15 SFS L15
01
L15 L15
D9b
L15
D9b L14
Detail 1L14 L14
D9b D9b
Detail section of Transit Area infill ceiling from MTC-A-94-TB-L4-0-0-00-09-029
D9b 1
3

SFS
01
4
A93530
L14
SIM 03

3 SECTION - ARRIVALS IMMIGRATION HALL, L0.1 FLAT CEILING


SCALE 1:10
The drawings on this page are
indicative. Refer to the architectural
L15 4 SECTION - ARRIVALS IMMIGRATION HALL, L0.1 SLOPED CEILING
L15 SCALE 1:10
drawings for correct setting out,
L15 mounting details and final dimensions.
L15

D9b

Type:

D9b

Beam beyond

Detail 2 SECTION
INFILL ROOF NORTH
D9b
2 Sheet 2/3
Detail section
SCALEof Transit Area infill ceiling from MTC-A-41-TB-L4-0-5-12-00-510
1:50

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 41 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015

20
30
Sprinkler cap
Metal acoustic ceiling MPC
ABU DH
concealed grid 03A
AIRPORTS CO
Abu Dhabi
6 Airports Company
EDGE SECTION OF PJSC
ACOUSTIC
CEILING PANEL-SIDE ABOVE SERVICE BOOM Specification, Section
ABU DHABI AIRPORTS 265120
COMPANY

SCALE 1:10
Kohn Pedersen Fox Associates
(International) PA
Architects and Planning Consultants
7a Langley Street
London WC2H 9JA
England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com

D9b

ABU DHABI INTERNATIONAL A


MIDFIELD TERMINAL COMP
L4
PROCESSOR ARRIVAL
CEILING COMPONENTS
- ACOUSTIC PANEL

MTC A 41 TB __ L0.1 5.00

7 EDGE SECTION OF ACOUSTIC CEILING PANEL-SIDE ABOVE SERVICE BOOM KPF MC KF JH


Detail 7 SCALE 1:10
Edge section of acoustic ceiling panel at Arrival Lobby from MTC-A-41-TB-L0-1-5-00-00-871 WBS

2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights r

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

D9b
Sheet 3/3

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 42 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
February 2014

Adjustable downlight – 56,4W LED warm white 3000K – 6000 lm – electronic driver – medium optic
Abu Dhabi Airports Company PJSC Reference: A_D9b Specification, Section 265120
Product code:
TX65
Luminaire Description: Recessed adjustable downlight
Technical description:
Manufacturing standard: EN 60 598Adjustable recessed roundTotalluminaire designed
luminaire to use a(max):
wattage LED lamp. Version with rim for surface-mounting. Ref
55W
vacuum-metalized with aluminum vapors with an anti-scratch protective layer. Die-cast aluminum body and pa
Primary luminaire Die-cast system.
aluminium Power factor: > 0.9
Product complete with LED unit in a warm white tone 3000K and DALI driver separate from the lumin
construction material: Rated
can be rotated 30° relative to theluminous fluxand
horizontal plane (lm):
358°3,000lm
about the vertical axis. Screw-operated mechanic
Finish: See Notesluminaires to be aimed onLuminaire
the vertical efficacy:
axis and horizontal plane.
55lm/WLED lifetime with residual flow at 80% (L80) 5
Ta 25°. Medium optic (30°).
Accessories: N/A Beam / distribution: Symmetric, see LDC
Light source type: LED Installation:
CRI / Colour temperature: > 80 / 3,000K
Driver type: Project 1 ConstantInstalled Colour
currentusing torsion springs Variation:
which allow easy recessing ≤ in 3 SDCM
false ceilings with thickness from 1 mm to 25 mm
13.03.2014
Drive current or voltage: 700mA Operator
Luminaire Lifetime: ≥ 50,000 hours
Dimming & type: Dimension:
DALI, remote Fax Lifetime Basis:
Telephone
L70 / F10 @ Ta 250C
Ø 226 mm - H 255 e-Mail
mm
IP: IP20
Colour:MB89 Reflex Easy 39W / Luminaire Data Sheet
IGUZZINI
RAL 9016 /Aluminium
Luminaire distribution curve (LDC)
Luminous emittance 1:
Location:
Weight [Kg]: Arrival Lobby
2,4

Mounting:
Ø212 ceiling hole

Wiring:
Product complete with electronic components
Notes:
Product configuration: TX65+LED
1. Refer to Section ‘2.0 Products’ of this
TX65: Round adjustable luminaire D = 226 mm H=255mm warm white 56,4W
specification LED 6000lm
for additional with DALI ballast -
requirements.
2. Luminaire to be passively cooled.
LED: LED Neutral White
3. Luminaire capable to be rotated 30°
relative to the horizontal plane and 358°
Product
Luminaire classification according to CIE: 100 Characteristics:
Luminous emittance 1: about the vertical axis.
CIE flux code: 92 100 100 100 95 Total lighting Output [Lm]: 4750 Totaltoluminous Flux at or(RAL
above an angle of 9
Adjustable aiming 4. Fixture be powder coated
Photo Total power [W]: 65 9016).Emergency Luminous Flux [Lm]: /
MB89.039 - Round recessed luminaire - D=226 mm H=146 mm - LED 3000
Luminous
lm warm white - DALI ballast - general light optic with controlled luminanceEfficacy [Lm/W]: 73.1 Cut off angle: 48°
UGR<19 - Bianco alluminio
LI30 - Lamp LED warm white Number of optical assemblies: 1 Power factor: 0.96

Optical assembly Characteristics 1:


Light Output Ratio (L.O.R.) [%]: 78 Number of lamps for vano: 1
Lamp code: LED Socket: /
ZVEI Code: LED Ballast Losses [W]: 10
Nominal power [W]: 55 Colour temperature [K]: 4000
Nominal luminous [Lm]: 5800 CRI: 80
Lamp maximum intensity [cd]: / Wavelength [Nm]: /
Beam Angle [°]: 38° MacAdam Step: <3
Components:
•1 x
•1 x Source 1
Complies with EN

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
Page 1 mounting details and final dimensions.

Type:

D9d

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 43 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
February 2014

Adjustable downlight – 56,4W LED warm white 3000K – 6000 lm – electronic driver – medium optic
Abu Dhabi Airports Company PJSC Reference: A_D9b Specification, Section 265120
Product code:
TX65
Luminaire Description: Concrete recessed adjustable downlight
Technical description:
Manufacturing standard: EN 60 598Adjustable recessed roundTotalluminaire designed
luminaire to use a(max):
wattage LED lamp. Version with rim for surface-mounting. Ref
80W
vacuum-metalized with aluminum vapors with an anti-scratch protective layer. Die-cast aluminum body and pa
Primary luminaire Die-cast system.
aluminium Power factor: > 0.9
Product complete with LED unit in a warm white tone 3000K and DALI driver separate from the lumin
construction material: Rated
can be rotated 30° relative to theluminous fluxand
horizontal plane (lm):
358°4,750lm
about the vertical axis. Screw-operated mechanic
Finish: See Notesluminaires to be aimed onLuminaire
the vertical efficacy:
axis and horizontal plane.
59lm/WLED lifetime with residual flow at 80% (L80) 5
Ta 25°. Medium optic (30°).
Accessories: Concrete housing Beam / distribution: Symmetric, see LDC
Light source type: LED Installation:
CRI / Colour temperature: > 80 / 3,000K
Driver type: Project 1 ConstantInstalled Colour
currentusing torsion springs Variation:
which allow easy recessing ≤ in 3 SDCM
false ceilings with thickness from 1 mm to 25 mm
07.03.2014
Drive current or voltage: 1,350mA Operator
Luminaire Lifetime: ≥ 50,000 hours
Dimming & type: Dimension:
DALI, remote Fax Lifetime Basis:
Telephone
L70 / F10 @ Ta 250C
Ø 226 mm - H 255 e-Mail
mm
IP: IP20
Colour: S.p.A TG65 iRoll TG65 / Luminaire Data Sheet
iGuzzini illuminazione
RAL 9016 /Aluminium
Luminaire distribution curve (LDC)
Luminous emittance 1:
Location:
Weight [Kg]: Baggage reclaim
See our luminaire catalog for an image of the
luminaire. 2,4

Mounting:
Ø212 ceiling hole

Wiring:
Product complete with electronic components
Notes:
Product configuration: TX65+LED
1. Refer to Section ‘2.0 Products’ of this
TX65: Round adjustable luminaire D = 226 mm H=255mm warm white 56,4W
specification LED 6000lm
for additional with DALI ballast -
requirements.
2. Luminaire to be passively cooled.
LED: LED Neutral White
3. Luminaire capable to be rotated 30°
relative to the horizontal plane and 358°
Product
Luminaire classification according to CIE: 100 Characteristics:
Luminous emittance 1: about the vertical axis.
CIE flux code: 99 100 100 100 80 Total lighting Output [Lm]: 4750 Total luminous Flux at or above
Adjustable aiming 4. Concrete housing to be provided for an angle of 9
Total power [W]: 65 cast inEmergency Luminous Flux [Lm]: /
concrete installation.
Design iGuzzini iGuzzini
Luminous Efficacy [Lm/W]: 73.1 Cuttooffbeangle:
5. Driver 48°within concrete
located
Number of optical assemblies: 1 Power factor: 0.96
housing.
june 2014
Concrete housing and dimensions
6. Fixture to be powder coated (RAL
Optical assembly Characteristics 1: 9016).
ContainerLight Output Ratio
for concrete (L.O.R.)
ceilings [%]: 78Easy round version (HAL)
for Sistema Number of lamps for vano: 1
Lamp code: LED Socket: /
code ZVEI Code: LED Ballast Losses [W]: 10
6030 Nominal power [W]: 55 Colour temperature [K]: 4000
Nominal luminous [Lm]: 5800 CRI: 80
350

Colour Lamp maximum intensity [cd]: / Wavelength [Nm]: /


Trasparente Incolore
Beam (24)[°]: 38°
Angle MacAdam Step: <3

Weight (kg) 590 x 450 min.


2.65 Complies with EN

Complies
The drawings on with
this EN60598-1
page are and pertinent regula
indicative. Refer to the architectural
drawings for correct setting out,
Page 1 mounting details and final dimensions.

Type:

D9f

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 44 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Recessed adjustable downlight

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 11W


Primary luminaire Die-cast aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 575lm
Pixel Pro
Finish: Stainless steel Luminaire efficacy: 52lm/W
Design Iosa Ghini iGuzzini
Accessories: N/A Concrete housing Beam / distribution: Symmetric, see LDC
august 2014
Light sourceProjecttype:
1
LED CRI / Colour temperature: > 80 / 3,000K
Pixel
Pixel
Pixel Pro
Pro
Pro
Driver type: Constant current Colour Variation: 15.08.2014
≤ 3 SDCM
Pixel Pro
Drive current or voltage:Design 350mA
Design
Design
Iosa
Iosa
Iosa
Ghini
Pixel Pro
Ghini
Ghini Operator
Telephone Luminaire
iGuzzini Lifetime:
iGuzzini
iGuzzini ≥ 50,000 hours
Fax
Dimming & type: DALI, remote code
august
august
august
MN61
2014Lifetime Basis:
e-Mail
2014
2014 L70 / F10 @ Ta 250C
IP:Design Iosa GhiniiGuzzini illuminazione iGuzzini
IP20 S.p.A MN61_LP31 Pixel Pro: recessed luminaire Ø 110 - warm
Technical description
white
august
Pixel
Pixel
Pixel
Pro
2014passive dissipation LED 10... / Luminaire Data Sheet
Pro
Pro
recessed adjustable removable luminaire for LED lamp with passive heat dissipation system. Structure with die-cast aluminium
frame and maindistribution
body; shaped surface
curve with high level radiant effect for effectively reducing the temperature and keeping the long-ter
code
Luminaire
code
code
LED lamp performance
Luminous
(LDC) Location:
emittance 1:unchanged. Steel rotation hinge, chrome-plated aluminium body closing ring. Plastic reflector with high
MN61
MN61
MN61
definition treatment ­ medium beam angle. Body adjusted using manually operated device: internal 45° ­ external 75° ­ rotation abo
See our luminaire catalog for an image Arrivals Feature Stair
axis 355°. Supplied with DALI dimmable control gear connected to the luminaire. Warm white high efficiency LED ­ lifetime with
Pixel Pro of the residual flow at 80% (L80): 50,000 h ­ Ta 25°.
luminaire. Technical
Technical
Technical description
description
description
recessed
recessed
recessed adjustable
adjustable
adjustable
removable
removable
removable
luminaire
luminaire
luminaire
forfor
for
LEDLED
LEDlamp
lamp
lampwith
with
with
passive
passive
passiveheat
heat
heatdissipation
dissipation
dissipation
system.
system.
system. Structure
Structure
Structure with
with
with
die-cast
die-cast
die-castaluminium
aluminium
aluminium
code frame
frame
frameand and
and
main
Installation main
main
body;
body;
body;
shaped
shaped
shaped
surface
surface
surfacewith
with
with
highhigh
high
level
level
level
radiant
radiant
radiant
effect
effect
effect
forfor
for
effectively
effectively
effectively
reducing
reducing
reducing
thethe
the
temperature
temperature
temperature and
and
and
keeping
keeping
keeping
thethe
the
long-term
long-term
long-ter
LEDLED
LEDlamp
lamp
lampperformance
performance
performance unchanged.
unchanged.
unchanged. Steel
Steel
Steel
rotation
rotation
rotation
hinge,
hinge,
hinge,chrome-plated
chrome-plated
chrome-plated aluminium
aluminium
aluminium body
body
body
recessed using steel springs in false ceilings with thicknesses starting at 1 mm; preparation hole Ø 100closing
closing
closing ring.
ring.
ring.
Plastic
Plastic
Plastic
reflector
reflector
reflector
with
with
with
high
high
high
MN61 definition treatment ­ medium beam angle. Body adjusted using manually operated device: internal 45° ­ external 75° ­ rotation about
definition treatment ­ medium beam angle. Body adjusted using manually operated device: internal 45° ­ external 75° ­ rotation abou
definition treatment ­ medium beam angle. Body adjusted using manually operated device: internal 45° ­ external 75° ­ rotation abo
axis 355°. Supplied with DALI dimmable control gear connected to the luminaire. Warm white high efficiency LED ­ lifetime with
axis 355°. Supplied with DALI dimmable control gear connected to the luminaire. Warm white high efficiency LED ­ lifetime with
axis 355°. Supplied with DALI dimmable control gear connected to the luminaire. Warm white high efficiency LED ­ lifetime with
Size (mm)
residual flow at 80% (L80): 50,000 h ­ Ta 25°.
residual flow at 80% (L80): 50,000 h ­ Ta 25°.
residual flow at 80% (L80): 50,000 h ­ Ta 25°.
Technical description ø110x67
recessed adjustable removable luminaire for LED lamp with passive heat dissipation
Installation
Installation
Installation Notes: system. Structure with die-cast aluminium
frame and main body; shaped surface with high level radiant effect for effectively reducing the temperature and keeping the long-te
Colour
recessed using steel springs in false ceilings with thicknesses starting at 1 mm; preparation hole Ø 100
recessed using steel springs in false ceilings with thicknesses starting at 1 mm; preparation hole Ø 100
recessed using steel springs in false ceilings with thicknesses starting at 1 mm; preparation hole Ø 100
White/Aluminium
LED lamp performance unchanged. (39)
Steel | Grey/aluminium
rotation (78)
hinge, chrome-plated aluminium
1. Referbody closing‘2.0
to Section ring.Products’
Plastic reflector
of this with high
definition treatment ­ medium beam angle. Body adjusted using manually operated device: internal 45° ­ external 75° ­ rotation ab
Size
Size
Size
(mm)
(mm)
(mm) specification for additional requirements.
Weight
ø110x67(kg)
axis 355°. Supplied with DALI dimmable control gear connected to the luminaire. Warm white high efficiency LED ­ lifetime with
ø110x67
ø110x67
0.52
residual flow at 80% (L80): 50,000 h ­ Ta 25°. 2. Luminaire to be passively cooled.
Colour
Colour
Colour
Mounting
3. Luminaire capable to be rotated 20°
White/Aluminium
White/Aluminium
White/Aluminium(39)
(39)
(39)
| Grey/aluminium
|| Grey/aluminium
Grey/aluminium
(78)
(78)
(78)
Installation ceiling recessed relative to the horizontal and 355° about
Luminaire classification according to CIE: 100 Luminous emittance 1: the vertical axis.
recessed using steel springs in false ceilings with thicknesses starting at 1 mm; preparation hole Ø 100
Weight
Weight
Weight
(kg)
(kg)
(kg)
CIE flux code: 100 100 100 100 80 Wiring info
0.52
0.52
0.52
on control gear box with quick-coupling connections

Concrete housing dimensions Size (mm)


Mounting
Mounting
Mounting
ø110x67 ceiling
ceiling
ceiling
recessed
recessed
recessed Complies with EN60598-1 and pertinent regulatio

Colour Wiring
Wiring
Wiringinfo
info
info
onon
on
control
control
controlgear
gear
gear
boxbox
box
with
with
with
quick-coupling
quick-coupling
quick-coupling
connections
connections
connections
White/Aluminium (39) | Grey/aluminium (78)
Product configuration: MN61+LED Complies
Complies
Complies
with
with
with
EN60598-1
EN60598-1
EN60598-1
and
and
and
pertinent
pertinent
pertinent
regulations
regulatio
regulatio
LED: n.1 led warm
Weight (kg)
0.52
Product characteristics
Total lighting output [Lm]: 622.99 Total luminous flux at or above an angle of 90° [Lm]: 0
Total power [W]: 11.2 Emergency luminous flux [Lm]: /
Mounting Product
Product
Product
Luminousconfiguration:
configuration:
configuration:MN61+LED
MN61+LED
MN61+LED
efficacy [Lm/W]: 55.62 Voltage [V]: -
ceiling recessed LED:
LED:
LED:
n.1n.1
Numbern.1
led
led
led
ofwarm
warm
warmassemblies: 1
optical

Product
Product
Product
Opticalcharacteristics
characteristics
characteristics
assembly Characteristics 1
Wiring info Total
Total
Total
lighting
Light lighting
lighting
Outputoutput
output
output
Ratio[Lm]:
[Lm]:
[Lm]:
622.99
(L.O.R.)622.99
622.99
[%]: 80 Total luminous flux at or above an angle of 90° [Lm]: 0
Total luminous flux at or above an angle of 90° [Lm]: 0
Total luminous flux at or above an angle of 90° [Lm]: 0
Number of lamps for optical assembly: 1
on control gear box with Total
quick-coupling
Total
Total
Lamppower
power
power[W]:
code: [W]:
[W]:
LED connections
11.2
11.2
11.2 Emergency
Emergency
Emergency
Socket: / luminous
luminous
luminous flux
flux
flux
[Lm]:
[Lm]:
[Lm]:
/ //
Luminous
Luminous
Luminous efficacy
ZVEI Code: efficacy
efficacy
LED[Lm/W]:[Lm/W]:
[Lm/W]: 55.62
55.62
55.62 Voltage
Voltage
Voltage
Ballast [V]:[V]:
[V]:
- -- [W]: 2.2
losses
Number
Number
Number
Nominalof of
of
optical
optical
optical
power assemblies:
[W]:assemblies:
assemblies:
9 1 11 Colour temperature [K]: 3000
Nominal luminous [Lm]: 780 CRI: 85 Complies with EN60598-1 and pertinent regulat
Lamp maximum intensity [cd]: / Wavelength [Nm]: /
Optical
Optical
Optical
assembly
assembly
assembly Characteristics
Characteristics
Characteristics 1 11
Beam angle [°]: 26° MacAdam Step: <3
Light
Light
Light
Output
Output
Output Ratio
Ratio
Ratio(L.O.R.)
(L.O.R.)
(L.O.R.)[%]:
[%]:
[%]:
808080 The drawings
Number
Number
Number of oflamps
of lamps
lamps on
forforthis
for
optical page
optical
optical are1 11
assembly:
assembly:
assembly:
Lamp
Lamp
Lampcode:
code:
code:LEDLED
LED Socket:
Socket:
Socket:
indicative./ // Refer to the architectural
ZVEI
ZVEI
ZVEI
Code:
Polar Code:
Code: LEDLED
LED Ballast
Ballast
Ballastlosses
losses
losses [W]:
[W]:
[W]:
2.22.2
2.2
Nominal
Nominal
Nominalpower
power
power [W]:
[W]:
[W]:9 99 Page 1 drawings
Colour
Colour
Colour for correct
temperature
temperature
temperature [K]:
[K]:
[K]: setting
3000
3000
3000 out,
Nominal
Nominal
Nominalluminous
luminous
luminous [Lm]:
[Lm]:
[Lm]:780
780
780 mounting
CRI:
CRI:
CRI: 85 details and final dimensions.
8585
Product configuration:Lamp
Lamp
Lampmaximum
MN61+LED maximum
maximum intensity
intensity
intensity [cd]:
[cd]:
[cd]:
/ // Wavelength
Wavelength
Wavelength [Nm]:
[Nm]:
[Nm]:
/ //
Beam angle [°]: 26°
Beam angle [°]: 26°
Beam angle [°]: 26° MacAdam
MacAdam
MacAdam Step:
Step:
Step:<3<3
<3
LED: n.1 led warm
Polar
Polar
Polar Type:
Product characteristics
Total lighting output [Lm]: 622.99 Total luminous flux at or above an angle of 90° [Lm]: 0
Total power [W]: 11.2
Luminous efficacy [Lm/W]: 55.62
Emergency luminous flux [Lm]: /
Voltage [V]: - D10
Number of optical assemblies: 1
Sheet 1/3 MN61_EN 1

Optical assembly Characteristics 1


Light–Output
Contract: Midfield Terminal Building Ratio
General (L.O.R.) [%]:AUH.06.10.0401
Contractor, 80 Page145 of 231
Number of lamps for optical assembly:
Lamp07)
Bulletin No. 145: Volume 3 of 4 (Rev code: LED Socket: / January 31, 2015
ZVEI Code: LED Ballast losses [W]: 2.2 MN61_EN
MN61_EN
MN61_EN
1 /112
Nominal power [W]: 9 Colour temperature [K]: 3000
Nominal luminous [Lm]: 780 CRI: 85
Lamp maximum intensity [cd]: / Wavelength [Nm]: /
Abu Dhabi Airports Company PJSC Specification, Section 265120

D10 D10

D10 D10

D10

D10

D10 D10

D10 D10
W1 W1 W1 W1 W1
W1
W1
D10 W1
W1
W1
W1
W1
W1
D10 W1 D10
W1
D10 W1 D10
W1
W1 D10
W1
W1
W1 D10
W1
W1
D10 D10
W1
W1
W1 D10 D10
W1 W1 W1 W1 W1 W1 W1 W1
W1
W1
D10 W1
W1
W1
W1
W1
W1
D10 W1 D10
W1
D10 W1 D10
W1
W1 D10
W1
W1
W1 D10
W1
W1 D10 D10
W1
W1
W1 D10 D10
W1 W1 W1 W1 W1 W1 W1 W1
W1
D10 W1
W1
W1
W1
W1
W1
W1
W1

ARUP LIGHTING
W1
W1
W1

MARK_UPS
W1
W1
W1
W1

W1
W1
W1
Rev1
W1
W1
W1 W1 W1

Section of Arrivals Feature Stair from MTC-A-94-TB-L_-_-0-00-07-009

D10
D10 D10
D10
D10
D10 D10
D10

D10
D10

D10
D10

D10
D10 D10
D10
W1
W1 W1
W1 W1
W1
D10
D10 D10
D10
W1
W1
W1
W1
D10
D10 D10
D10
W1
W1
W1
W1
W1
W1
D10
D10 D10
D10
W1
W1
D10
D10 D10
D10
W1
W1 1. FOR LIGHT FITTING INTEGRATION AND FIXING DETAILS
REFER TO A-94 & A-93 ARCHITECTURAL DRAWINGS AND
W1 D10
D10
LIGHTING SPECIFICATIONS 265120
1 W1
W1
W1 W1
W1 D10
D10 2. ARCHITECTURAL BACKGROUNDS ADDED FOR CLARITY

W1 W1
W1 D10
D10 D10
D10
W1 W1
W1 W1
W1 W1
W1 W1
W1 W1
W1
W1
D10
D10 D10
D10
W1
W1 W1
W1 W1
W1
D10
D10
W1
W1 W1
W1
W1
1
W1 W1
W1
W1
W1
D10
D10 D10
D10
W1
W1
D10
D10 D10
D10
W1
W1
D10
D10
W1
W1
W1 D10
D10
W1
W1
W1 D10
D10 D10
D10
W1
W1 W1
W1 W1 W1 W1
The drawings on this page are
W1 W1 W1
D10
D10 D10
D10 W1
W1

D10
D10
W1
W1 indicative. Refer to the architectural
W1
W1
W1
drawings for correct setting
W1
W1
W1
out, mounting details and final
W1
W1 dimensions.
W1
W1
W1
W1

W1
W1
W1
W1
Type:
W1
W1 W1
W1

LONG ELEVATION
SCALE 1:50 Detail 2
D10
Sheet 2/3
Section of Arrivals Feature Stair from MTC-A-94-TB-L_-_-0-00-07-009

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 46 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January
02 31.01.1531, 2015
BULLETIN 145
01 31.10.14 BULLETIN 120
00 15.07.12 ISSUED FOR CONSTRUCTION

ISSUED FOR CONSTRUCT


Abu Dhabi Airports Company PJSC Specification, Section 265120

1. Fo
MT

W1

D10

A D

1 CROSS SECTION
02 3
SCALE 1:5
01 1
Detail 1 STAINLESS STEEL INSERT STA
01
00 1

Cross section of Arrivals Feature Stair from MTC-A-07-TB-L_-_-_-__-00-902

ABU

B
E

1
A07902

VER
AR
SEC

MTC
C F
KPF

2 PLAN
3 TREAD SECTIONS
SCALE 1:5
SCALE 1:10
2014 KOHN PED

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

D10
Sheet 3/3

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 47 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Suspended fixed downlight

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 25W


Primary luminaire Die-cast aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 1,880lm
Finish: Anodised aluminium silver Luminaire efficacy: 75lm/W
Accessories: See Notes Beam / distribution: Symmetric, see LDC
Project 1
Light source type: LED CRI / Colour temperature: 19.03.2014 > 80 / 3,000K

Driver type: Constant current Operator


Telephone
Colour Variation: ≤ 3 SDCM
Fax
Drive current or voltage: 600mA iRoll e-Mail Luminaire Lifetime: ≥ 50,000 hours
Dimming & type: DALI, integral Lifetime Basis: L70 / F10 @ Ta 250C
iGuzzini illuminazione S.p.A MK24_LM31 Palco: Large body spotlight - 55W - LED 4800
Design iGuzzini
IP: iGuzzini
lm - warm whiteIP20
- CRI (Ra) 80 - electronic ballast and - wide flood optic / Luminaire
Data Sheet
july 2014
Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
See our luminaire catalog for an image of the Suspended between panels at
luminaire.
iRoll Immigration in Level 0.0

code
MQ09

Technical description Notes:


LED lamp, ceiling-mounted luminaire; integrated DALI dimmable1. Refer
controltogear. Die-cast
Section aluminium
‘2.0 Products’ plate for surfa
of this
shaped aluminium cylindrical body with diffuser element and integrated lampforand
specification optic units;
additional reflector vacuum-m
requirements.
aluminium vapours and finished with a protective, anti-scratch layer; safety glass cover over LED lamp. General
2. Luminaire to be passively cooled.
3. Suspension rod and mounting plate to
Installation be provided.
Plate
Luminaire classification according fixed
to CIE: 100to ceiling Luminous
using screws and
emittance 1: screw anchors (not included); cylindrical body fitted with a mechanical s
CIE flux code: 99 100 100 100 103 4. Fixture to be fixed to the substrate,
bayonet assembly systems ensuring simple installation and maintenance. Wall or pendant application option av
at an elevation that matches adjacent
special accessory kits with a separate code.
ceiling panels.
5. Luminaire to be suspended in line with
Size (mm) panels.
ø140x200

Colour
White (01) | Grey (15)

Weight (kg)
1.18

Mounting
wall surface | ceiling surface | ceiling pendant

Wiring info
Control gear integrated in luminaire; mains and optic unit connections made with
The drawings quick
on this coupling
page are terminal blocks
Page 1
indicative. Refer to the architectural
drawings for correct setting out,
Notes mounting details and final dimensions.
Kit for wall-mounting: code no. 9439

Type: Complies with EN60598-1 an

Product configuration: MQ09+LED


D11
LED: LED WARM

Contract: Midfield Terminal BuildingProduct


– General Contractor, AUH.06.10.0401
characteristics Page 48 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07)lighting output [Lm]: 1031.64
Total January 31, 2015
Total luminous flux at or above an angle of 90
Total power [W]: 12.7 Emergency luminous flux [Lm]: /
Luminous efficacy [Lm/W]: 81.23 Voltage [V]: -
Number of optical assemblies: 1
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Recessed fixed downlight

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 39W


Primary luminaire Die-cast aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 2,820lm
Finish: See Notes Luminaire efficacy: 72lm/W
Accessories: N/A Beam / distribution: Symmetric, see LDC
Project 1
Light source type: Reflex Easy
LED CRI / Colour temperature: 19.03.2014 > 80 / 3,000K

Driver type:
Design iGuzzini Constant current Operator Colour Variation:
iGuzzini ≤ 3 SDCM
Reflex Easy Telephone
Drive current or voltage: 700mA Fax
e-Mail Luminaire Lifetime: ≥ 50,000 hours
March 2014
Dimming & type:
Design iGuzzini DALI, integral Lifetime Basis:
iGuzzini L70 / F10 @ Ta 250C
iGuzzini illuminazione S.p.A MB81_LI30 Reflex Easy: Round recessed luminaire -
IP: D=226 mm H=103 mm IP20- LED
March 3000 lm warm white - DALI ballast - general light optic with
2014
Reflex Easycontrolled
- Round recessed luminaire
luminance UGR<19 / Luminaire
- D=226 Data
mm H=103 mmSheet
- LED 3000 lm warm white - DALI ballast - general light optic
with controlled luminance UGR<19
Reference: A_D11b Luminaire distribution curve (LDC)
Luminous emittance 1: Location:
Reflex Easy - Round recessed luminaire - D=226 mm H=103 mm - LED 3000 lm warm white - DALI ballast - general light optic
with
for ancontrolled
See our luminaire catalogProduct image of theluminance UGR<19
code: Arrival Lobby
luminaire. Reference: A_D11b
MB81
Product code:
Technical description:
MB81
Recessed fixed round luminaire designed to use a LED lamp. Version with rim for surface-mounting. Reflector vacuum-metallised
with aluminium vapours with an anti-scratch protective layer. Die-cast aluminium body and passive dissipation system. Product
Technical description:
complete with 3000 lm DALI LED unit in a warm white tone 3000K and driver separate from the luminaire. Light distribution
Recessed fixed round luminaire designed to use a LED lamp. Version with rim for surface-mounting. Reflector vacuum-metallised
UGR<19 with controlled luminance.
with aluminium vapours with an anti-scratch protective layer. Die-cast aluminium body and passive dissipation system. Product
Notes:
complete with 3000 lm DALI LED unit in a warm white tone 3000K and driver separate from the luminaire. Light distribution
Installation:
UGR<19 with
Recessed controlled
using luminance.
torsion springs 1. Refer
which allow easy installation in false ceilings with to ranging
thickness Sectionfrom
‘2.01Products’ of this
mm to 25 mm.
specification for additional requirements.
Installation:
Dimension: 2. Luminaire to be from
passively cooled.
Recessed using torsion springs which allow easy installation in false ceilings with thickness ranging 1 mm to 25 mm.
Ø 226 mm - H 103 mm
3. Fixture to be powder coated (RAL
Dimension:
Colour: 9016).
Luminaire classification according
Ø 226 mm to CIE:
- H 100
White/Aluminium 103(39)
mm Luminous emittance 1:
CIE flux code: 85 100 100 100 100
Colour: [Kg]:
Weight
White/Aluminium
1,88 (39)

Weight [Kg]:
Mounting:
1,88 recessed
Ceiling
Mounting:
Wiring:
Ceiling recessed
Product complete with DALI electronic components
Wiring:
Notes:
Product complete
L80 at 50,000 with
hours DALI
L70 electronic
at 65,000 components
hours
Notes:
Product configuration: MB81+LED
L80 at 50,000
MB81: hours L70luminaire
Round recessed at 65,000- hours
D=226 mm H=103 mm - LED 3000 lm warm white - DALI ballast - general light optic with controlled
luminance UGR<19
Product configuration: MB81+LED
LED:
MB81:LED warm
Round white luminaire - D=226 mm H=103 mm - LED 3000 lm warm white - DALI ballast - general light optic with controlled
recessed
luminance
Product UGR<19
characteristics:
LED: lighting
Total LED warm white
output [Lm]: 2817.6 Total luminous flux at or above an angle of 90° [Lm]: 0
Total power [W]: 39 Emergency luminous flux [Lm]: /
Product characteristics:
Luminous efficacy [Lm/W]: 72.25 Voltage [V]: -
Total lighting output [Lm]: 2817.6 Total luminous flux at or above an angle of 90° [Lm]: 0
Number of optical assemblies: 1
Total power [W]: 39 Emergency luminous flux [Lm]: /
The drawings on this page are
Luminous
Optical efficacy [Lm/W]:
assembly 72.25
Characteristics 1: Voltage [V]:
Page 1 -
indicative. Refer to the architectural
Number
Light of optical
Output Ratio assemblies:
(L.O.R.) [%]:194 Number of lamps for opticalfor
drawings assembly: 1
correct setting out,
Lamp code: LED Socket: / mounting details and final dimensions.
Optical assembly Characteristics 1:
ZVEI Code: LED Ballast losses [W]: 5
Light Output Ratio (L.O.R.) [%]: 94 Number of lamps for optical assembly: 1
Nominal power [W]: 34 Colour temperature [K]: 3000
Lamp code: LED Socket: /
Nominal luminous [Lm]: 3000 CRI: 80
ZVEI Code: LED Type:
Ballast losses [W]: 5
Lamp maximum intensity [cd]: / Wavelength [Nm]: /
Nominal power [W]: 34 Colour temperature [K]: 3000
Beam angle [°]: 68° MacAdam Step: <3
Nominal luminous [Lm]: 3000 CRI: 80
Lamp maximum intensity [cd]: /
Beam angle [°]: 68°
Wavelength [Nm]: /
MacAdam Step: <3 D11b
Complies with EN60598-1 and pertinent regu

Complies with EN60598-1 and pertinent regu

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 49 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Recessed fixed downlight

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 11W


Primary luminaire Die-cast aluminium Power factor: > 0.9
construction material: ARCHITECTURAL DOWNLIGHTS
Rated luminous flux (lm): 610lm
Finish: See Notes Luminaire efficacy: 55lm/W
ARCHITECTURAL DOWNLIGHTS
HURRICANE 35
Accessories: N/A Beam / distribution: Symmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 3,000K

HURRICANE 35
Driver type: Project 1 Constant current Colour Variation: 13.03.2014
≤ 3 SDCM
Drive current or voltage: 350mA Operator Luminaire Lifetime: ≥ 50,000 hours
Telephone
Dimming & type: DALI, remote Fax
e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: IP20
ACDC 1138/FX/30/45R/WHI/N 1138/FX/30/45R/WHI/N / Luminaire Data Sheet

Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
See our luminaire catalog for an image of the Washrooms Arrivals Tunnel
luminaire.
Ablutions
Bus Holdroom
Welcomers Hall entrance doors
Departures Hall entrance doors

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
Hurricane 35 Devil Fixed Hurricane 35 Xicato Fixed Hurricane 35 Demon Fixed
2. Luminaire to be passively cooled.
3. Fixture to be powder coated (RAL
Hurricane 35 Devil Fixed Hurricane 35 Xicato Fixed Hurricane
9016). 35 Demon Fixed
Luminaire classification according to CIE: 100 Luminous emittance 1:
CIE flux code: 94 98 100 100 100
Height 87mm
Height 115mm
83

Height 87mm 83mm 83


Height 115mm
83

83mm

Cutout
Cut-Out 74mm
83mm 74mm 83

83mm Cut-Out
74mm
Cutout
Cut-Out 74mm
74mm

Cut-Out
74mm

Hurricane 35 Devil Fixed Hurricane 35 Xicato Fixed Hurricane Demon Fixed


Low glare deep recessed for 40° visual cutoff
Hurricane 35 Devil Fixed Compatible with the following 35
Hurricane LEDXicato
engines:Fixed
Demon, Devil, Xicato Hurricane Demon Fixed
Please note that product heights will vary between engines
Low glare deep recessed for 40° visual cutoff
Devil optic options - 18°, 24°, 30°, 45°Compatible with the following
Xicato 40° optic
LED only Demon, Devil, XicatoDemon optic options - 18°, 24°, 40°
engines:
Please note that product heights will vary between engines
Suitable temperature
Devil optic range:
options - 18°, 24°, 30°, 45°-10°C to 40°C Xicato 40° optic only Demon optic options - 18°, 24°, 40°
The drawings on this page are
Suitable temperature range: -10°C to 40°C indicative. Refer to the architectural
Page 1 drawings for correct setting out,
mounting details and final dimensions.

Type:

D12
Sheet 1/3

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 50 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015

Hurricane 35 Devil Adj Hurricane 35 Xicato Adj Hurricane 35 Demon Adj


Abu Dhabi Airports Company PJSC Specification, Section 265120

XD1d XD1d XD1d


XD1d

L17 D12 D12


L17
L17 L17 L17

U3
U3 U3 U3 U3
U3

Section detail of entrance doors from MTC-A-94-TB-L_-_-0-00-09-038

L4 L4 L4 L4 L

D12 D12

Detail 2
Detail section of Bus Holdroom from MTC-A-41-TB-L1-0-5-00-00-610

L17b
D12
D12

D12

D12
L17b
D12
D12 D12
D12

D12
L17b
D12
D12
U3 U3 D12
The drawings on this page are
U3 indicative. Refer to the architectural
L17b

drawings for correct setting out,


U3
mounting details and final dimensions.
U3

U3

Type:

Detail 1
D12
Plan of entrance doors from MTC-A-94-TB-L_-_-0-00-09-038 Sheet 2/3

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401


XD1d XD1d XD1d
XD1d
Page 51 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015

L17 D12 D12


L17
L17 L17 L17
Abu Dhabi Airports Company PJSC Specification, Section 265120

D12

L4

Detail 4
Detail section of Bus Holdroom from MTC-A-41-TB-L_-_-_-__-00-945

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

D12
Sheet 3/3

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 52 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Recessed fixed downlight

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 1W


Primary luminaire Anodised aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 70lm
Finish: See Notes Luminaire efficacy: 70lm/W
Accessories: N/A Beam / distribution: Symmetric, see LDC
Light sourceProject
type: 1 LED CRI / Colour temperature: > 80 / 3,000K
13.03.2014
Driver type: Constant current Colour Variation: ≤ 3 SDCM
Operator
Drive current or voltage: 350mA Telephone
Fax Luminaire Lifetime: ≥ 50,000 hours
e-Mail
Dimming & type: DALI, remote Lifetime Basis: L70 / F10 @ Ta 250C
IP: IP40
Lightgraphix Ltd. LD72/350/NB Miniature Low Glare LED Downlight / Luminaire Data
Sheet
Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
See our luminaire catalog for an image of the Washrooms above vanities
luminaire.

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Luminaire to be passively cooled.
3. Fixture to be powder coated (RAL
9016).
Luminaire classification according to CIE: 100 Luminous emittance 1:
CIE flux code: 99 100 100 100 104

The drawings on this page are


Page 1 indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.

Type:

D12b

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 53 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Reflex easy
Abu Dhabi Airports Company PJSC Specification, Section 265120
Design iGuzzini iGuzzini

Luminaire Description: Recessed adjustable downlight


Adjustable downlight – 60W LED warm white 3000K – 5700 lm – medium optic
Ref. Green Wall Lights
Manufacturing standard: EN 60 598 Total luminaire wattage (max): 90W
Primary luminaire Die-cast Product
aluminium
code: Power factor: > 0.9
construction material: TCR4 Rated luminous flux (lm): 4,000lm
Finish: See Notes Technical description:Luminaire efficacy: 81lm/W
Accessories: N/A Adjustable recessed roundBeam / distribution:
luminaire designed to use a LEDSymmetric, seewith
lamp. Version LDCrim for surface-mounting. Re
Light sourceProject
type:1 LED vacuum-metalized with aluminum
CRI / vapors
Colour with an anti-scratch
temperature: > 90protective
/ 3,000K layer. Die-cast aluminum body and p
system. Product complete with LED unit in a warm13.08.2014
white tone 7000K and DALI driver separate from the lumin
Driver type: Constant current Colour Variation: ≤ 3 SDCM
can be rotated 30° relative to the horizontal plane and 358° about the vertical axis. Screw-operated mechanic
Operator
Drive current or voltage: 1,400mAluminaires to beTelephoneaimed Luminaire Lifetime: ≥ 50,000 hours
Fax on the vertical axis and horizontal plane. LED lifetime with residual flow at 80% (L80)
Dimming & type: DALI, remote e-Mail
Lifetime Basis:
Ta 25°. Medium optic (30°). L70 / F10 @ Ta 250C
IP: IP20
iGuzzini illuminazione S.p.A MK22_LM31 Palco: Large body spotlight - 55W - LED 4800
Installation:
lm - warm white - CRI (Ra) 80 ... / Luminaire Data Sheet
Installed using torsion springs which allow easy recessing in false ceilings with thickness from 1 mm to 25 mm
Luminaire distribution curve (LDC)
Luminous emittance 1: Location:
See our luminaire catalog for an imageDimension:
of the Arrival Lobby green wall
luminaire.
Ø 242 mm - H 280 mm Centre Space green walls
Colour:
RAL 9016 /Aluminium L8

Weight [Kg]:
2,4
Notes:
Mounting:
1. Refer to Section ‘2.0 Products’ of this
Ø212 ceiling hole specification for additional requirements.

Wiring: 2. Luminaire to be passively cooled.


Product complete with electronic components 3. Luminaire capable to be rotated 30°
relative to the horizontal plane and 358°
Product
Luminaire classification according to CIE:configuration:
100 TCR3+LED
Luminous emittance 1: about the vertical axis.
CIE flux code: 99 100 100 100 78
Adjustable aiming TCR3: Round adjustable luminaire warm white 60W LED 5800lm withtoDALI
4. Fixture ballastcoated
be powder - 30° medium
(RAL optic
9016).
LED: LED Warm White

Product Characteristics:
Total lighting Output [Lm]: 4750 Total luminous Flux at or above an angle of
Total power [W]: 65 Emergency Luminous Flux [Lm]: /
Luminous Efficacy [Lm/W]: / Cut off angle: 48°
Number of optical assemblies: 1 Power factor: 0.96

Optical assembly Characteristics 1:


Light Output Ratio (L.O.R.) [%]: 78 Number of lamps for vano: 1
Lamp code: LED Socket: /
ZVEI Code: LED Ballast Losses [W]: 10
Nominal power [W]: 60 Colour temperature [K]: 4000
Nominal luminous [Lm]: 5800 CRI: 90
Lamp maximum intensity [cd]: / Wavelength [Nm]: /
The drawings on this page are
Beam Angle [°]: 48° MacAdam Step: <3
indicative. Refer to the architectural
D13 D13 D13 D13
Page 1 drawings for correct setting out,
mounting details and final dimensions.
Complies with EN

Type:

Detail 3
D13
Section through Green Wall at Arrival Lobby from MTC-A-94-TB-L_-_-0-00-09-031

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 54 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
February 2014

Adjustable downlight – 56,4W LED warm white 3000K – 6000 lm – electronic driver – medium optic
Abu Dhabi Airports Company PJSC Reference: A_D9b Specification, Section 265120
Product code:
TX65
Luminaire Description: Recessed adjustable downlight
Technical description:
Manufacturing standard: EN 60 598Adjustable recessed roundTotalluminaire designed
luminaire to use a(max):
wattage LED lamp. Version with rim for surface-mounting. Ref
80W
vacuum-metalized with aluminum vapors with an anti-scratch protective layer. Die-cast aluminum body and pa
Primary luminaire Die-cast system.
aluminium Power factor: > 0.9
Product complete with LED unit in a warm white tone 3000K and DALI driver separate from the lumin
construction material: Rated
can be rotated 30° relative to theluminous fluxand
horizontal plane (lm):
358°4,750lm
about the vertical axis. Screw-operated mechanic
Finish: See Notesluminaires to be aimed onLuminaire
the vertical efficacy:
axis and horizontal plane.
59lm/WLED lifetime with residual flow at 80% (L80) 5
Ta 25°. Medium optic (30°).
Accessories: N/A Beam / distribution: Symmetric, see LDC
Light source type: LED Installation:
CRI / Colour temperature: > 80 / 3,000K
Driver type: Project 1 ConstantInstalled Colour
currentusing torsion springs Variation:
which allow easy recessing
27.03.2014

in 3 SDCM
false ceilings with thickness from 1 mm to 25 mm
Drive current or voltage: 1,350mA Operator Luminaire Lifetime: ≥ 50,000 hours
Dimming & type: Dimension:
DALI, remote
Telephone
Fax Lifetime Basis: L70 / F10 @ Ta 250C
Ø 226 mm - H 255 e-Mail
mm
IP: IP20
IGUZZINI MK22 Palco 63.3W / Luminaire Data Sheet
Colour:
RAL 9016 /Aluminium
Luminaire distribution curve (LDC)
Luminous emittance 1: Location:
Weight [Kg]: Arrival Lobby
2,4
Arrivals Bussing corridor
Mounting:
Ø212 ceiling hole

Wiring:
Product complete with electronic components
Notes:
Product configuration: TX65+LED
1. Refer to Section ‘2.0 Products’ of this
TX65: Round adjustable luminaire D = 226 mm H=255mm warm white 56,4W
specification LED 6000lm
for additional with DALI ballast -
requirements.
2. Luminaire to be passively cooled.
LED: LED Neutral White
3. Luminaire capable to be rotated 30°
relative to the horizontal plane and 358°
Product
Luminaire classification according to CIE: 100 Characteristics:
Luminous emittance 1: about the vertical axis.
CIE flux code: 100 100 100 100 86
Adjustable aiming Total lighting Output [Lm]: 4750 Totaltoluminous
4. Fixture Flux
be powder at or(RAL
coated above an angle of 9
Adjustable spotlight with adapter for installation on electrified track for high
output LED lamp with monochrome emission in a warmTotal power
White (3000K) tone. [W]: 65 9016).Emergency Luminous Flux [Lm]: /
Medium optic (15-20°). Electronic ballast integrated in the product. Luminaire
Luminousplane. The Efficacy [Lm/W]: 73.1
made of die-cast aluminium and thermoplastic material, allows 360° rotation
about the vertical axis and 90° tilting relative to the horizontal Cut off angle: 48°
luminaire has mechanical aiming locks for both movements, operated using
the same tool on two screws, one at the side of the rodNumberand one on the of optical assemblies: 1 Power factor: 0.96
adapter for the track. Passive heat dissipation. Spotlight designed to contain
up to two flat accessories simultaneously. Another external component can
also be applied, selected from directional flaps and an anti-glare screen. All

Optical assembly Characteristics 1:


external accessories rotate 360° about the spotlight longitudinal axis. LED
lifetime with residual flow at 80% (L80): 50,000 h at Ta 25°

Light Output Ratio (L.O.R.) [%]: 78


MK22.001 - Large body spotlight - 55W - LED 4800 lm - warm white - CRI
(Ra) 80 - electronic ballast - medium optic - Bianco
Number of lamps for vano: 1
LM31 - Lamp LED Warm White
Lamp code: LED Socket: /
ZVEI Code: LED Ballast Losses [W]: 10
Nominal power [W]: 55 Colour temperature [K]: 4000
Nominal luminous [Lm]: 5800 CRI: 80
Lamp maximum intensity [cd]: / Wavelength [Nm]: /
Beam Angle [°]: 38° MacAdam Step: <3

Complies with EN

The drawings on this page are


indicative. Refer to the architectural
Page 1
drawings for correct setting out,
mounting details and final dimensions.

Type:

D16

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 55 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Recessed IP44 fixed downlight

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 11W


Primary luminaire Die-cast aluminium Power factor: > 0.9
construction material: ARCHITECTURAL DOWNLIGHTS
Rated luminous flux (lm): 580lm
Finish: See Notes Luminaire efficacy: 53lm/W
ARCHITECTURAL DOWNLIGHTS
HURRICANE 35
Accessories: N/A Beam / distribution: Symmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 3,000K

HURRICANE 35
Driver type: Project 1 Constant current Colour Variation: 13.03.2014
≤ 3 SDCM
Drive current or voltage: 350mA Operator Luminaire Lifetime: ≥ 50,000 hours
Telephone
Dimming & type: DALI, remote Fax
e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: IP44
ACDC 1138/FX/30/45R/WHI/N 1138/FX/30/45R/WHI/N / Luminaire Data Sheet

Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
See our luminaire catalog for an image of the Transfer Building showers
luminaire.

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
Hurricane 35 Devil Fixed Hurricane 35 Xicato Fixed Hurricane 35 Demon Fixed
2. Luminaire to be passively cooled.
3. Fixture to be powder coated (RAL
Hurricane 35 Devil Fixed Hurricane 35 Xicato Fixed Hurricane
9016). 35 Demon Fixed
Luminaire classification according to CIE: 100 Luminous emittance 1:
CIE flux code: 94 98 100 100 100
Height 87mm
Height 115mm
83

Height 87mm 83mm 83


Height 115mm
83

83mm

Cutout
Cut-Out 74mm
83mm 74mm 83

83mm Cut-Out
74mm
Cutout
Cut-Out 74mm
74mm

Cut-Out
74mm

Hurricane 35 Devil Fixed Hurricane 35 Xicato Fixed Hurricane Demon Fixed


Low glare deep recessed for 40° visual cutoff
Hurricane 35 Devil Fixed Compatible with Hurricane
the following35
LEDXicato
engines: Demon, Devil, Xicato
Fixed Hurricane Demon Fixed
Please note that product heights will vary between engines
Low glare deep recessed for 40° visual cutoff
Devil optic options - 18°, 24°, 30°, 45°Compatible with the following
Xicato 40°
LEDoptic only Demon, Devil, Xicato Demon optic options - 18°, 24°, 40°
engines:
Please note that product heights will vary between engines
Suitable temperature
Devil optic range:
options - 18°, 24°, 30°, 45°-10°C to 40°CXicato 40° optic only Demon optic options - 18°, 24°, 40°
The drawings on this page are
Suitable temperature range: -10°C to 40°C indicative. Refer to the architectural
Page 1 drawings for correct setting out,
mounting details and final dimensions.

Type:

D18

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 56 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015

Hurricane 35 Devil Adj Hurricane 35 Xicato Adj Hurricane 35 Demon Adj


Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Continuous integrated linear profile

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 25W/m


Primary luminaire LED strip mounted on Power factor: > 0.9
construction material: extruded aluminium profile Rated luminous flux (lm): 2,800lm/m
Finish: N/A Luminaire efficacy: 112lm/W
Accessories: See Notes Beam / distribution: Symmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 3,000K
ghting solutions
Driver type: Project 1
Constant Voltage Colour Variation: 10.08.2014
≤ 3 SDCM
Drive current or voltage: 24V Operator Luminaire Lifetime: ≥ 50,000 hours
Telephone
Dimming & type: DALI, remote Fax
e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: LED Linear ™ – linear lighting
IP20solutions
ex HYDRA LD25 LED Linear / Luminaire Data Sheet

W824
2.400 K
W827
2.700 K
W830
3.000 K
W835
3.500 K
W840
4.000 K

W850
5.000 K
Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
VarioLED™ Flex HYDRA LD25

W824
2.400 K
W827
2.700 K
W830
3.000 K
W835
3.500 K
W840
4.000 K

W850
5.000 K
See our luminaire catalog for an image of the Bussing Area lit wall
luminaire.
Binnacles
Car Park bridges
Gatehouses

25 Watt/meter Circulation
25 Watt/meter
Arrivals Tunnel circular cove
3.168 lumen/meter (lm/m) Notes:
3.168 lumen/meter (lm/m)
Centre Space circular coves
! One Bin Only: 3 MacAdam
Watt
! One Bin Only: 3 85
Ra/CRI MacAdam
Transfer Building circular coves

! 127 Lumen/ Ra/CRI 85


Notes:
/Watt
! en & measurement 1. Refer to Section ‘2.0 Products’ of this
AufbauLuminaire
& Maße 12
CIE flux code:
Lumaccording
7Assembly
classification
47 79 96 100 95
to CIE: 100 Due to missing symmetry properties, no UGR table
can be displayed for this luminaire.
specification for additional requirements.
2. Linear LED strip to be mounted on
125 mm (24 x)
a suitable profile to provide sufficient
embly & measurement heat dissipation per manufacturer’s
recommendations.
+ 24 V
9,5 mm
GND 3. Continuous profiles to be supplied
125 mm (24 x) with all necessary accessories including
mounting profiles, covers, brackets and
9 mm 17,85 mm 17,85 mm 17,85 mm 17,85 mm 17,85 mm 17,85 mm 9 mm
end caps.
2,1 mm 4. Mock-up sample to be provided
9,5 mm for each application shown. Final
selection of optical lens/cover to be
Elektrische & Optische Betriebsdaten Electrical & optical data confirmed during site mock-up.
5. Lengths required to be confirmed by
mm 17,85 mm 17,85 mm 17,85 mm 17,85 mm 9 mm site measurement prior to ordering and
Keine zusätzliche Kühlung
Abmessungen Dimensions 3.000 mm x 9,5 mm x 2,1 mm coordinated with Architect Engineer.
über AL-Profil notwendig.
Teilungsmaß Step length 125 mm/7 LED 2,1 mm No need for additional6. When
heat required, profile sections to be
Leistung Power 74,9 W/25 Watt/meter sinking on AL profile. cut to match required radius.
Effizienz Efficacy bis zu/up to 127 lumen/Watt 7. Mock-ups required to confirm design
intent.
he Betriebsdaten Electrical & optical
Anzahl LED Number LED
Spannung Voltage (V)
data
24 Volt (23 V , 25 V )
Profile sections cut to match radius
168 LED, 17,85 mm LED pitch
min max
The drawings on this page are
indicative.
The drawingsRefer
on to thepage
this architectural
are
Page 1 drawings
indicative.for correct
Refer setting
to the out,
architectural
Strom Current 3,12 A/130 mA per step L80, mounting for
details andsetting
final dimensions.
> 37.000 hrs drawings correct out,
Temperatur Temperature tcmin = –25°C, tcmax = +80°C
Keine zusätzliche Kühlung mounting details and final dimensions.
3.000 mm x 9,5 mm x 2,1 mmt
Lagertemp. Storage temp. = –30°C, tmax = +85°Cüber AL-Profil notwendig.
min

125 mm/7
Außentemperatur Ambient LED
temp. tamin = –25°C, tamax = +45°C Type:
No need for additional heat
74,9 W/25 Watt/meter sinking on AL profile.
VarioLED™ Flex Art. # Lumen/meter Ra
HYDRA LD15 bis zu/up to 127 lumen/Watt
(lm/m) CRI
R9
CRI
Farbtemperatur
Color Temperature (K) L2b
W824 Nähere Erläuterungen zu Änderungen, Grenz­ Sheet 1/5
168 LED,10377
17,85 mm1.916
LED pitch85 30 2.400
werten und Schwankungen im Herstellungs­
W827 10330 2.623 85 20 2.700 prozess finden Sie im LED Linear™ System­
24Terminal
W830Midfield
Contract: Volt10329
(23Building
Vmin, 252.800
Vmax
– ) 85Contractor,
General 20 3.000
AUH.06.10.0401 katalog, Seite 532. Page 57 of 231
BulletinW835
No. 145:3,12
Volume
A/130 3 mA
10328of 4 per
(Rev 07)
step
2.947 85 20 3.500 For more details regarding catalogue January 31, 2015
L80, changes, min and max data sheet values
W840 10327 3.018 83 20 >4.000
37.000 hrs
W850
tcmin = –25°C, tcmax = +80°C
10326 3.168 83 10 5.000
and production tolerances see the
LED Linear™ system catalogue, page 533.
Abu Dhabi Airports Company PJSC Specification, Section 265120

L2b L2e

L2o

ted handrail

Detail 4
Detail section of Binnacle from MTC-A-36-TB-L2-0-_-__-00-552

cover by others

diffuse panel, by
others

L2b

L2n inside wall edge


detail
L2b

ARUP LIGHTING
Detail section of Car Park bridge from MTC-A-81-TB-L_-_-_-__-00-702 MARK_UPS

The drawings on this page are


L2b indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.

Type:
U4

L2b
diffuse panel,
by others

Sheet 2/5
Detail section of Gatehouse wall lighting detail from MTC-A-07-TB-L_-_-_-__-00-920

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 58 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
D3 D3

8,9
Abu Dhabi Airports Company PJSCA93535
D3 Specification,
D3
D3
Section 265120
D3
2 D3 D
8 A93536
A93535

L2c
L2c
L2c

L2c
L2c
4 x L2b 4 x L2b D3 D3
D3 D3
L2c D3
D3 D3
D3

L2c
L2c
L2c
L2c
L2c
L2c
L2c
D3
4,5
to be painted matte white D3 D3
93535
D3

D3
all L2c fixtures are recommended to
be to be spaced equally apart
4 x L2b a mock-up is recommended to
4 x L2b ensure desired effect is achieved
4 x L2b

8 RCP - LIT DISC


L2c
SFS D3 SCALE 1:50
4 x L2b 4 x L2b 01

D3
4,5

L2c
L2c
D3

L2c
L2c
Detail 4 93535 D3

D3
Detail plan and section of Bussing Area lit wall from MTC-A-93-TB-L_-_-_-__-00-135 D3
D3
to be painted matte white
SFS
D3 D3
01

L2c
L2c
L2c
L2c
SFS FAB
D3
01 SFS D3
4 ELEVATION - LIT WALL TYPE 1
01 SFS
01
D3 D3
01
SCALE 1:50
4 x L2b
4 x L2b 4 x L2b

SFS
01

SFS 9 RCP - LIT DISC


01 SCALE 1:50
DCM
07A 4 x L2b 4 x L2b 4 x L2b
06
9 6 SFS
-- 01
SFS A93535
01 SFS
01 APP
TO BE PAINTED
05
MATTE WHITE

7
Detail 5 PLAN - LIT WALL TYPE 1
5
Detail
SFS
plan and section of Bussing Area lit wall from MTC-A-93-TB-L_-_-_-__-00-135
SCALE 1:50
01 APP
04

L DETAIL 3 PLAN - LIT WALL DETAIL


DCM 10 ACCESS DOOR ELEVATION
SCALE 1:5
07A 1,2,3 SCALE 1:100
FAB
SFS
01
01
5 4,5
DCM
93135 93535
07A

DCM 4 x L2b 4 x L2b 4 x L2b 4 x L2b 4 x L2b 4 x L2b


4 x L2b
07A FAB
SFS
10 01
01 10 SFS --
to be painted matte 01 ARM
L2b white 01
APP ARM
05 01
L2b The
SFS
drawings on this page are 05
04
31.01.15
31.10.14
BULLET
BULLET

SFS
indicative.
01 Refer to the architectural 03 25.07.14 BULLET

01 drawings for correct setting out, 02 25.04.14 BULLET


01 25.05.13 BULLET
mounting details and final dimensions.
4 x L2b 4 x L2b 4 x L2b 4 x L2b 4 x L2b 4 x L2b 4 x L2b ISSUE
4

Type:

4 x L2b 4 x L2b DCM ABU DHABI AIRPORTS CO

L2b
4 x L2b 4 x L2b 4 x L2b 4 x L2b 4 x L2b 4 x L2b 4 x L2b 4 x L2b
07A
8 SECTION - LIT WALL
SCALE 1:10 SFS
Detailmatte
to be painted 6 6 PLAN - LIT WALL 01
white SCALE 1:10 Sheet 3/5
Detail plan of Lit Wall from MTC-A-93-TB-L_-0-_-__-00-535 SFS
7 01
93135
Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 59 of 231
Bulletin No. 145: Volume 3 of 4 (Rev
4,5 07) 4 x L2b 4 x L2b 4 x L2b 4 x L2b 4 x L2b 4 x L2b 4January
x L2b 31, 2015 ABU
4 x L2b 4 x L2b
DHAB
93535
SFS SFS
MIDFIE
01 01
4 x L2b 4 x L2b 4 x L2b 4 x L2b 4 x L2b 4 x L2b 4 x L2b 4 x L2b 4 x L2b 4 x L2b
DCM SFS BUSSING ARE
07A
6 ELEVATION
01 - LIT WALL TYPE 2 DETAILS
01 METAL FRAMING

IXTURE
Abu Dhabi Airports Company PJSC LMF LIGHTWEIGHT Specification, Section 265120
CFM COLD FORMED
4 02 METAL CEILING 01 METAL FRAMING 4
NG SLOT FRAMING A41666
LIGHTWEIGHT LMF
400

METAL 02
L2b
L2b L2b
L2b CEILING FRAMING
AR DIFFUSER
URN)

1500
GYB

6250
01
L18 L18

GYPSUM BOARD GYB


4500

01
GBA
TRAVELATOR

3000
05

TRZ
01/02

Detail 3
Detail section at Arrivals Corridor from MTC-A-41-TB-L_-_-_-__-00-667
CA G11
1. FOR LIGHT FITTING INTEGRATION AND FIXING DETAILS
REFER TO A-94 & A-93 ARCHITECTURAL DRAWINGS AND
LIGHTING SPECIFICATIONS 265120

AT ARRIVALS CORRIDOR 2. ARCHITECTURAL BACKGROUNDS ADDED FOR CLARITY

L2b

02 31.01.15 BULLETIN 145


01 31.10.14 BULLETIN 120
00 15.07.12 ISSUED FOR CONSTRUCTION

ISSUED FOR CONSTRUCTION

XS1 ABU DHABI


AIRPORTS COMPANY
ABU DHABI AIRPORTS COMPANY

Kohn Pedersen Fox Associates


(International) PA
Architects and Planning Consultants
7a Langley Street
London WC2H 9JA
England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com

Detail 1
ABU DHABI INTERNATIONAL AIRPORT
Detail of concrete facade interface of Processor Arrival Car Park Link
MIDFIELD bridge
TERMINAL from MTC-A-94-TB-L_-_-0-00-09-020
COMPLEX

PROCESSOR ARRIVAL
CARPARK LINK BRIDGE
SECTIONS AND DETAILS
3 CONCRETE-FACADE INTERFACE- LIGHTING DETAIL
SCALE 1:5 MTC A 94 TB __ L_._ 0.00 09.020 02

KPF MC KF JH 25.09.2009

WBS AUH.06.10.0401

2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights reserved. Do not scale.

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
L2b L4
out, mounting details and final
dimensions.

Type:

Detail 4
L2b
Sheet 4/5
Detail section of perimeter of Transfer Building Arrival from MTC-A-41-TB-L3-0-_-__-00-650

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 60 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
1. Details for Gatehouses In situ Concrete Open Stairs. 3

GLZ Laminated clear glass with coloured interlayer 2. Details to apply to Code E and Code F Gatehouses S
18 3. PFT-01 Polished Floor Treatment will require different
for each pier.

GYP Decorative Plaster to


Abu Dhabi Airports Company PJSC 04 Concrete- Internal Specification, Section 265120
Propiertry Aluminium
Shadow Gap/
Stop Bead

PFT Polished Floor Treatment


01

ARM Stair Nosing


12

PFT Polished Floor Treatment


01 D1

Polished Floor Treatment PFT


L2b 01

Aluminium
Detail 1 Architectural Profile
(3mm thickness)
1 LIGHT AND CEILING PERIMETER SECTIONAL DETAIL 2 CEILING AT TRANSFER CEILING SECTIONAL DETAIL 3 METAL PANELING - GYPSUM CEILING
Mill Finish
Detail of ceiling perimeter at Transfer ceiling from MTC-A-94-TB-L_-_-0-00-09-051
SCALE 1:5

Continuous 12 mm
SCALE 1:5 SCALE 1:5

thick plates

01 31.01.15 BULLETIN 145


Decorative Plaster to GYP
00 15.07.12 ISSUED FOR CONSTRUCTION
Concrete- Internal 04

SECTION INTERMEDIATE LANDING SECTION ACROSS STAIRCASE ISSUED FOR CONSTRUCTION


2 3
SCALE 1:5 SCALE 1:5

ABU DHABI
AIRPORTS COMPAN
ABU DHABI AIRPORTS COMPANY

ED GLASS GLZ
02
Kohn Pedersen Fox Associates
00 05.01.15 BULLETIN 137 (International) PA
Architects and Planning Consultants
7a Langley Street
London WC2H 9JA
England
Balustrade BAL F: +44 (0)207 497 1175
ISSUED FOR CONSTRUCTION
T: +44 (0)207 319 5300

L2o
www.kpf.com

h SS Handrail 05

ABU DHABI
AIRPORTS COMPANY
ABU DHABI AIRPORTS COMPANY

L2b
Kohn Pedersen Fox Associates
(International) PA

ABU DHABI INTERNATIONAL AIRPO


Architects and Planning Consultants
7a Langley Street
London WC2H 9JA
England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175

MIDFIELD TERMINAL COMPLEX


www.kpf.com

VERTICAL CIRCULATION
TYPICAL IN SITU CONCRETE STAIR
ABU DHABI INTERNATIONAL AIRPORT
DETAILS
MIDFIELD TERMINAL COMPLEX

MTC
CENTREA 07LEVEL
SPACE TB 3__ L_._ _.__ 00.92
TYPICAL DETAILS
SECTIONS AND DETAILS

KPF A
MTC 94 TBMC
__ KF 09.051 00
L_._ 0.00 JH 25.
5 WALL-LIGHTING DETAIL. PLAN 6 BAL 02 HANDRAIL DETAIL
Detail 5SCALE 1:5 SCALE 1:2 JS ISO KF CB 05.01.15 WBS AUH.06.

Detail of typical Gatehouse wall lighting detail from MTC-A-07-TB-L_-_-__-00-920 2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights reserved.
WBS AUH.06.10.0401

2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights reserved. Do not scale.
D

Stone Type 01 STN


01

Stone Type 8 STN


08

The drawings on this page are


L2b indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

1. For technical detail in drawing n.1, refer to structural


engineers drawing MTC-S-08-TB-__-L0.2-0.00-55.501 Type:
2. For technical detail in drawing n.3, refer to structural
engineers drawing B1 in MTC-S-08-TB-__-L0.2-0.00-55.502

3. For lighting details, refer to series MTC-A-94

Detail 4
L2b
Sheet 5/5
Detail section of Car Park bridge from MTC-A-81-TB-L_-_-_-__-00-702
Decorative Plaster to GYP
Concrete (external) 04
4 CROSS SECTION - PUBLIC MEZZANINE ARRIVALS OPEN AREA
Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401
SCALE 1:10 Page 61 of 231
3
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Custom stainless steel bumper rails & trolley guards DCM
02

Stone Type 14 STN


14
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Continuous integrated linear profile

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 15W/m


Primary luminaire LED strip mounted on Power factor: > 0.9
construction material: extruded aluminium profile Rated luminous flux (lm): 1,930lm/m
Finish: N/A Luminaire efficacy: 129lm/W
Accessories: See Notes Beam / distribution: Symmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 3,000K
ghting solutions
Driver type: Project 1
Constant Voltage Colour Variation: 10.08.2014
≤ 3 SDCM
Drive current or voltage: 24V Operator Luminaire Lifetime: ≥ 50,000 hours
Telephone
Dimming & type: DALI, remote Fax
e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: LED Linear ™ – linear lighting
IP20solutions
ex HYDRA HD15 LED Linear GmbH / Luminaire Data Sheet

W824
2.400 K
W827
2.700 K
W830
3.000 K
W835
3.500 K
W840
4.000 K

W850
5.000 K
Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
VarioLED™ Flex HYDRA HD15

W824
2.400 K
W827
2.700 K
W830
3.000 K
W835
3.500 K
W840
4.000 K

W850
5.000 K
See our luminaire catalog for an image of the Lit disk Gatehouses cove
luminaire.
Public Gallery Pier Pavilions
Glazed wall detail Stairs
Baggage Reclaim Arrivals Tunnel

15,4 Watt/meter Welcomers Hall


15,4 Watt/meter
Vertical Circulation
Processor Departure Public Gallery
2.182 lumen/meter (lm/m) Notes:
2.182 lumen/meter (lm/m)
! One Bin Only: 3 MacAdam
en/Watt
! One Bin Only: 3 85
Ra/CRI MacAdam
! 142 Lum
Ra/CRI 85
Notes:

n/Watt
! e & measurement 1. Refer to Section ‘2.0 Products’ of this
AufbauLuminaire
& Maße
CIE flux code:
Lumaccording
2Assembly
14classification
46 78 96 100 115
to CIE: 100 Due to missing symmetry properties, no UGR table
can be displayed for this luminaire.
specification for additional requirements.
2. Linear LED strip to be mounted on
62,5 mm (64 x)
a suitable profile to provide sufficient
embly & measurement heat dissipation per manufacturer’s
recommendations.
+ 24 V 9,5 mm 3. Continuous profiles to be supplied
x) GND
with all necessary accessories including
mounting profiles, covers, brackets and
4,45 mm 8,9 mm 8,9 mm 8,9 mm 8,9 mm 8,9 mm 8,9 mm 4,45 mm end caps.

2,1 mm
4. Mock-up sample to be provided
9,5 mm for each application shown. Final
selection of optical lens/cover to be
Elektrische & Optische Betriebsdaten Electrical & optical data confirmed during site mock-up.
5. Lengths required to be confirmed by
mm 8,9 mm 8,9 mm 4,45 mm site measurement prior to ordering and
Keine zusätzliche Kühlung
Abmessungen Dimensions 4.000 mm x 9,5 mm x 2,1 mm coordinated with Architect Engineer.
über AL-Profil notwendig.
Teilungsmaß Step length 62,5 mm/7 LED
2,1 mm No need for additional6. When
heat required, profile sections to be
Leistung Power 61,44 W/15,4 Watt/meter sinking on AL profile. cut to match required radius.
Effizienz Efficacy bis zu/up to 142 lumen/Watt 7. Mock-ups required to confirm design
intent.
he Betriebsdaten Electrical & optical
Anzahl LED Number LED
Spannung Voltage (V)
data
24 Volt (23 V , 25 V )
Profile sections cut to match radius
448 LED, 8,9 mm LED pitch
min max
The drawings on this page are
indicative.
The drawingsRefer
on to thepage
this architectural
are
Page 1 drawings
indicative.for correct
Refer setting
to the out,
architectural
Strom Current 2,56 A/40 mA per step L80, mounting for
details andsetting
final dimensions.
> 37.000 hrs drawings correct out,
Temperatur Temperature tcmin = –25°C, tcmax = +85°C
Keine zusätzliche Kühlung mounting details and final dimensions.
4.000 mm x 9,5 mm x 2,1 mmt
Lagertemp. Storage temp. = –30°C, tmax = +85°Cüber AL-Profil notwendig.
min

62,5Ambient
Außentemperatur mm/7temp.
LED tamin = –25°C, tamax = +45°C Type:
No need for additional heat
61,44 W/15,4 Watt/meter sinking on AL profile.
VarioLED™ Flex Art. # Lumen/meter Ra
HYDRA HD15 bis zu/up to 142 lumen/Watt
(lm/m) CRI
R9
CRI
Farbtemperatur
Color Temperature (K) L2c
W824 10385 Nähere Erläuterungen zu Änderungen, Grenz­ Sheet 1/7
448 LED, 8,9 mm 1.320
LED pitch 85 30 2.400
werten und Schwankungen im Herstellungs­
W827 10384 1.807 85 20 2.700 prozess finden Sie im LED Linear™ System­
24Terminal
W830Midfield
Contract: Volt10383
(23Building
Vmin, 251.929
–Vmax) 85Contractor,
General 20 3.000
AUH.06.10.0401 katalog, Seite 532. Page 62 of 231
BulletinW835
No. 145:2,56
Volume
A/40 3 mA
10382of 4per
(Rev 07)
step
2.030 85 20 3.500 For more details regarding catalogue January 31, 2015
L80, changes, min and max data sheet values
W840 10381 2.079 83 20 >4.000
37.000 hrs
W850
tcmin = –25°C, tcmax = +85°C
10380 2.182 83 10 5.000
and production tolerances see the
LED Linear™ system catalogue, page 533.
325

L4
CONTINUOUS LINEAR GRILLE.
SEE MECH. DWG'S

125
Abu Dhabi Airports Company PJSC Specification, Section 265120
200 500 30 200 30

Superseded
Refer to MTC-A-41-TB-L_-_-_-__-00-667 SFS STRETCHED FABRIC
ARRIVALS TUNNEL
detail 4 in Arup mark-ups for new detail
L2c 3 DETAIL 01
SCALE 1:5
7
09
-

GLZ TRANSLUCENT
CA 11 INTERLAYER
L2c

ARUP LIGHTING
LED STRIP GRAZING
TRANSLUCENT GLASS

L2c
matte white MARK_UPS
GALVINISED MILD STEEL
BRACKET INTERVAL PER
L20 PANEL JOINT. SIZE TBD
L20 L2c
L18f METAL FRAME
2040
1800
2040

L20
L18 L18 GYB GYPSUM BOARD
90

01
210

L2c L2c
300 120 15
B9
20 180
TYPE L20 - LINEAR LED RGB DCM ST. STEEL TRIM (REMOVABLE TO
STRIP LIGHT MOUNTED IN
03 ACCESS LIGHT FIXTURE)
ARCHITECTURAL DETAILS
SFS STRETCHED FABRIC 09 30.11.14
DCM CONTINUOUS SSTL
01 08 31.10.14
03 SHOP BONDED TO GLASS
SPRINKLER 07 25.08.14
06 25.06.14
Detail section of boom
SOUNDedge from FAB
ABSORBING MTC-A-03-TB-L_-_-5-00-00-601
ARRIVALS TUNNEL ARRIVALS TUNNEL 05 25.05.14
PANEL 01 4 DETAIL 6 DETAIL
SCALE 1:5 SCALE 1:5
GYB GLZ IS
01 11

12 L2c
41664
L18g
1600

back painted ABU DHABI AIR

GLZ BACK PAINTED laminated glass


2800

16 LAMINATED GLASS
6
- translucent
translucent glass GLZ BACK PAINTED
diffuserL2c
(by others) 16 LAMINATED GLASS
GLZ
TRANSLUCENT GLASS
16 DIFFUSER (BY OTHERS) 150

TYPE 2c LIGHT FIXTURE


L2c
GALVINISED MILD STEEL L2h
150 L2c ABU D
3000

BRACKET INTERVAL PER


PANEL JOINT. SIZE TBD
5 L2c
L2h M
400

-
CONTINUOUS LINEAR GRILLE.
L2c
SEE MECH. DWG'S
ARRIVAL
200

ALUM. EXTRUDED PROFILE RCP & SE


L2c translucent Detail updated.
L2c
SFS STRETCHED FABRIC To be coordinated
30 with
200 architect MTC A
01
21
ESCALATOR WELL DCM
5 DETAIL 03 ST. STEEL TRIM
KPF

Detail 5 SCALE 1:5


Detail 7
Detail section of escalator well in Arrivals Tunnel from MTC-A-41-TB-L_-_-_-__-00-665 2014 KOHN PEDERSEN FO

ARUP LIGHTING
matte white MARK_UPS
The drawings on this page are
indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.

L2c
Type:

Detail 6
L2c
Sheet 2/7
Detail section of Arrivals Tunnel from MTC-A-41-TB-L_-_-_-__-00-665

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 63 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

L2c
DIFFUSING PANEL

L2c

Detail 3
Detail section of Pier Pavilions bullnose from MTC-A-35-TB-L_-_-_-__-00-700

L2c

Detail section of Public Gallery cove from MTC-A-41-TB-L2-0-5-00-00-596

D1c

L2c L2c

ARU
MAR
The drawings on this page are
indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.

Type:

L2c
Sheet 3/7
Detail section of Gatehouses cove from MTC-A-03-TB-L_-_-_-__-00-512

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 64 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
L13

L13

Abu Dhabi Airports Company PJSC Specification, Section 265120


L2c

L2c
L13b

Detail 6
Detail section of stone stair balustrade from MTC-A-07-TB-L_-_-_-__-00-551

L2c

Detail 2
Detail section of stone stair from MTC-A-94-TB-L_-_-0-00-07-031

D3 D3

L5
D3 D3 L5
D3 D3
L2c
L2c
L2c

L2c
L2c

D3
L2c D3
D3 D3
D3

L2c L2c

D3

Detail section through typical boom from MTC-A-94-TB-L_-_-0-00-09-033 033

all L2c fixtures are recommended to


be to be spaced equally apart
a mock-up is recommended to
D3 D3 ensure desired effect is achieved

D3 D8
D3

The drawings on thisARUP


page areLIGHTING
D3 D3 L2c
D3
MARK_UPS
indicative. Refer to the architectural
drawings for correct setting out,
L2c
L2c
L2c

L2c
L2c

D3
D3 mounting details and final dimensions.
L2c

L5c L5c
L2c
L2c

L2c D3 D3
L2c

D3 D3
D3 L5c L5c
D3
D8 to be in-line
D3with
panel
D3 Type:
D3

L2c
Detail 8 Detail 9
Detail plan Bussing Area lit disk and circulation lit disk from MTC-A-93-TB-L_-_-_-__-00-135
ARUP LIGHTING
Sheet 4/7
all L2c fixtures are recommended to
be to be spaced equally apart
a mock-up is recommended to
MARK_UPS
ensure desired effect is achieved
Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 65 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
L2c
D3
Abu Dhabi Airports Company PJSC Specification, Section 265120

L5 L5

L2c L2c
L18 L18

Detail 1
Detail section through typical boom from MTC-A-94-TB-L_-_-0-00-09-033

L5 L5

L2c

translucent
diffuser

Detail 5
Detail section through handrail from MTC-A-94-TB-L_-_-_-__-09-042
L17
L8

D9

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.
L2c

Type:

Detail 10
L2c
Detail section of Processor Departure Public Gallery ceiling from MTC-A-41-TB-L2-0-5-00-00-493 Sheet 5/7

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 66 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

D1c

L2c L2c

Detail 4
Detail section of underside of Link Bridge from MTC-A-94-TB-L_-_-0-00-09-040

L2c L2c

D8c

L16

L3.0 PUBLIC GALLERY - CLEAR INFILL GLASS


Detail 1 SCALE 1:20 3 L3.0 OFFICE GLA
Detail through Public Gallery clear infill glass from MTC-A-52-TB-L_-_-_-__-00-630 SCALE 1:50

4
-

8
-
L2c

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

2 L3.0 PUBLIC GALLERY INFILL GLASS WITH FIRE RATED SOFFIT Type:
SCALE 1:20

Detail 2 L2c4 DETAIL @ SLA


SCALE 1:5
Detail section of Pier Pavilions bullnose
MILD STEEL from
SUPPORT MTC-A-94-TB-L_-_-0-00-09-043
BRACKET GLAZED NON-FIRE RATED FLOORING/BRIDGE GLZ
Sheet 6/7
12B
STAINLESS STEEL TRIM DCM S
4MM THICK 03
4
Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 67 of 231 B
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
02 G
C
4
C
Abu Dhabi Airports Company PJSC Specification, Section 265120

L2c L2c

L18d L18d L18d

Detail 1
Side Elevation of vertical circulation Glazed Passenger Lift ELV-05-09, 10, 11, 63 from MTC-A-07-TB-L_-_-_-__-00-105

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

L2c
Sheet 7/7

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 68 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Illuminated LED handrail

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 12W/m


Primary luminaire Stainless steel Power factor: > 0.9
construction material: Rated luminous flux (lm): 580lm/m
Finish: Stainless steel Luminaire efficacy: 48lm/W
Accessories: N/A See Notes Beam / distribution: Symmetric, see LDC
Light sourceProject
type: 1 LED CRI / Colour temperature: > 80 / 3,000K
Driver type: Constant Voltage Colour Variation: 04.04.2014
≤ 3 SDCM
Operator
Drive current or voltage: 24V Telephone Luminaire Lifetime:
Fax
≥ 50,000 hours
Dimming & type: DALI, integral e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: IP66
DW Windsor Z GARDA HANDRAIL :- ASYMMETRIC LINEAR MODULE 900mm /
Luminaire Data Sheet
Luminaire distribution curve (LDC)
Luminous emittance 1: Location:
See our luminaire catalog for an image of the Gatehouses
luminaire.
Museum Landscaping

FLEXIBLE INSTALLATION
Notes:
1. Refer to Section ‘2.0 Products’ of this
Garda scheme performance is optimised by developing
specification for additional requirements. Stanch
mounting centres in unison with the spacing of modules.
2. Luminaire to be passively cooled. Wiring
3. In the Gatehouses to be supplied Fixing a
Mounting with a round section bracket to allow
Luminaire classification according to CIE: 100 Due to missing symmetry properties, no UGR table
overco
for mounting to the concrete wall.
CIE flux code: 36 76 95 100 100 Fixing
can becan be via
displayed for brackets,
this luminaire.stanchions or onto existing structures mount
with typical spacings every 1-1.5m. A variety of profiles
FOR GLASS SCREENScan
REFERbe
TO DRAWINGS,
include
8 A51-116, 117, 140-143.
D1d D1d designed and manufactured1depending onFOR
the look
MARS andSCREEN CONFIGURATION REFER TO
SECURE
A51-114, 115, 151 TO 153
D1d A31452
functionality required, as illustrated in the case studies within
D1d
Round section bracket FOR PLANT ROOM LAYOUTS REFER TO DRAWINGS M03019,
L2c this publication. M07001-003 & M07010-011, MTC-M-08-AS-L1.0-6.00-21.010-011

L2b FOR INTERNAL ELEVATIONS REFER TO A-51 DRAWINGS

1
A07881

PFT
01 ARUP LIGHTING
L2o +28.92
ARRIVALS
LEVEL FFL
MARK_UPS
18 Rev1
L2b 2
A07920
Round wall bracket Square wall bracket
PFT L2o 3 Buried
01 A07920
Where curved handrails are required, diameters as small as one
L2b The drawings on this page are
L2o metre can be accomplished with our flexible LED modules.
indicative. Refer to the architectural
WP Page 1
+25.80 drawings for correct setting out,
UPPER DECK mounting details and final dimensions.
Loadings BOARDING
18 LEVEL FFL
L2b The following
L2c are taken into account when we design the
D1
structural elements of the scheme: Type:
■ Loading requirements for the scheme
L2o ■ Stanchion or bracket spacing
PFT
01 L2b
■ Profile of the stanchion L2o
Sheet 1/2
Detail
27 The robust 3mm thick profile of
section of handrail in Gatehouse Type F from MTC-A-03-TB-L_-_-_-__-00-505 the handrail is designed to
+22.35
26 DEPARTURES
25
24
withstand loadings in excess of 3kNFFL
LEVEL using fixing distances of
06 xx.xx.xx BULLETIN XX
Contract: Midfield
23
22 Terminal Building – General Contractor,
up toAUH.06.10.0401
2.1m. This is maintained when LED05modules are inserted.
25.02.14 BULLETIN
Page 69 of 231
Bulletin No. 145:21
Volume
20 3 of 4 (Rev 07) 04 25.11.13 BULLETIN 30 January 31, 2015
The combination of spacing and stanchion Flange
03 profile
25.08.13 isBULLETIN
optimised to
19
18 21
17
16
15
suit application loading requirements and aesthetics. Some
02 .25.04.13 BULLETIN 12
01 21.12.12 BULLETIN 06
14
13 sample spacings (distance achievable between LED module
12
01 31.01.15 BULLETIN 145
ster to GYP
00 15.07.12 ISSUED FOR CONSTRUCTION
nternal 04

SECTION ACROSS STAIRCASE ISSUED FOR CONSTRUCTION


3
Abu Dhabi
SCALE 1:5 Airports Company PJSC Specification, Section 265120
ABU DHABI
AIRPORTS COMPANY
ABU DHABI AIRPORTS COMPANY

Kohn Pedersen Fox Associates


(International) PA
Architects and Planning Consultants
7a Langley Street
London WC2H 9JA
England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175

L2o
www.kpf.com

ABU DHABI INTERNATIONAL AIRPORT


MIDFIELD TERMINAL COMPLEX

VERTICAL CIRCULATION
TYPICAL IN SITU CONCRETE STAIR
DETAILS

MTC A 07 TB __ L_._ _.__ 00.920 01

KPF MC KF JH 25.09.2009
6 BAL 02 HANDRAIL DETAIL
Detail SCALE
6 1:2 WBS AUH.06.10.0401

Detail of typical Gatehouse handrail from MTC-A-07-TB-L_-_-__-00-920


2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights reserved. Do not scale.

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

L2o
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 70 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Continuous integrated linear profile

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 15W/m


Primary luminaire LED strip mounted on Power factor: > 0.9
construction material: extruded aluminium profile Rated luminous flux (lm): 1,930lm/m
Finish: N/A Luminaire efficacy: 129lm/W
Accessories: See Notes Beam / distribution: Symmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 3,000K
ghting solutions
Driver type: Project 1
Constant Voltage Colour Variation: 10.08.2014
≤ 3 SDCM
Drive current or voltage: 24V Operator Luminaire Lifetime: ≥ 50,000 hours
Telephone
Dimming & type: DALI, remote Fax
e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: LED Linear ™ – linear lighting
IP20solutions
ex HYDRA HD15 LED Linear GmbH / Luminaire Data Sheet

W824
2.400 K
W827
2.700 K
W830
3.000 K
W835
3.500 K
W840
4.000 K

W850
5.000 K
Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
VarioLED™ Flex HYDRA HD15

W824
2.400 K
W827
2.700 K
W830
3.000 K
W835
3.500 K
W840
4.000 K

W850
5.000 K
See our luminaire catalog for an image of the Side Pavilions
luminaire.

15,4 Watt/meter
15,4 Watt/meter
2.182 lumen/meter (lm/m) Notes:
2.182 lumen/meter (lm/m)
! One Bin Only: 3 MacAdam
1. Refer to Section ‘2.0 Products’ of this

Watt
! One Bin Only: 3 85
Ra/CRI MacAdam
specification for additional requirements.
2. Linear LED strip to be mounted on

att
! 142 Lumen/ Ra/CRI 85
a suitable profile to provide sufficient

umen/W
heat dissipation per manufacturer’s
& Maße !
AufbauLuminaire
CIE flux code:
L according
2Assembly
14classification & measurement
46 78 96 100 115

62,5 mm (64 x)
to CIE: 100 Due to missing symmetry properties, no UGR table
can be displayed for this luminaire.
recommendations.
3. Continuous profiles to be supplied
with all necessary accessories including
embly & measurement mounting profiles, covers, brackets and
end caps.
+ 24 V 9,5 mm 4. Mock-up sample to be provided.
x) GND Final selection of optical lens/cover to be
confirmed during site mock-up.
4,45 mm 8,9 mm 8,9 mm 8,9 mm 8,9 mm 8,9 mm 8,9 mm 4,45 mm 5. Lengths required to be confirmed by
site measurement prior to ordering and
2,1 mm coordinated with Architect Engineer.
9,5 mm
6. Profile sections to be cut to match
Elektrische & Optische Betriebsdaten Electrical & optical data required radius.
7. Mock-ups required to confirm design
mm 8,9 mm 8,9 mm 4,45 mm intent.
Keine zusätzliche Kühlung
Abmessungen Dimensions 4.000 mm x 9,5 mm x 2,1 mm
über AL-Profil notwendig.
Teilungsmaß Step length 62,5 mm/7 LED
2,1 mm No need for additional heat
Leistung Power 61,44 W/15,4 Watt/meter sinking on AL profile.
Effizienz Efficacy bis zu/up to 142 lumen/Watt

he Betriebsdaten Electrical
Spannung Voltage (V)
& optical
Anzahl LED Number LED
data
448 LED, 8,9 mm LED pitch
24 Volt (23 V , 25 V )
Profile sections cut to match radius min max
The drawings on this page are
indicative. Refer to the architectural
Page 1 drawings for correct setting out,
Strom Current 2,56 A/40 mA per step L80, mounting details and final dimensions.
> 37.000 hrs
Temperatur Temperature tcmin = –25°C, tcmax = +85°C
Keine zusätzliche Kühlung
4.000 mm x 9,5 mm x 2,1 mmt
Lagertemp. Storage temp. = –30°C, tmax = +85°Cüber AL-Profil notwendig.
min

62,5Ambient
Außentemperatur mm/7temp.
LED tamin = –25°C, tamax = +45°C Type:
No need for additional heat
61,44 W/15,4 Watt/meter sinking on AL profile.
VarioLED™ Flex Art. # Lumen/meter Ra
HYDRA HD15 bis zu/up to 142 lumen/Watt
(lm/m) CRI
R9
CRI
Farbtemperatur
Color Temperature (K) L2p
W824 10385 Nähere Erläuterungen zu Änderungen, Grenz­ Sheet 1/2
448 LED, 8,9 mm 1.320
LED pitch 85 30 2.400
werten und Schwankungen im Herstellungs­
W827 10384 1.807 85 20 2.700 prozess finden Sie im LED Linear™ System­
24Terminal
W830Midfield
Contract: Volt10383
(23Building
Vmin, 251.929
–Vmax) 85Contractor,
General 20 3.000
AUH.06.10.0401 katalog, Seite 532. Page 71 of 231
BulletinW835
No. 145:2,56
Volume
A/40 3 mA
10382of 4per
(Rev 07)
step
2.030 85 20 3.500 For more details regarding catalogue January 31, 2015
L80, changes, min and max data sheet values
W840 10381 2.079 83 20 >4.000
37.000 hrs
W850
tcmin = –25°C, tcmax = +85°C
10380 2.182 83 10 5.000
and production tolerances see the
LED Linear™ system catalogue, page 533.
Abu Dhabi Airports Company PJSC Specification, Section 265120

L2p
L2p L2p L2p L2p
L2p L2p L2p L2p
L2p
L2p

00 15.07.12 ISSUED F

ISSUED

Detail 1 ABU DHABI AIRPORTS COM


Side pavilion elevation from MTC-A-35-TB-L_-_-_-__-00-597

L2p

L2p
allow for two sides
L2p
ABU DHABI
MIDFIEL

DEPARTURES
ELEVATIONS
SHEET 03
L2p
A 35 T

KPF MC

2012 KOHN PEDERSEN FOX ASSOCIA

Detail 2 Detail 3
Side pavilion details from MTC-A-94-TB-L_-_-0-00-09-047

U1c

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.

Type:

L2p
L18b Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 72 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Continuous integrated linear profile

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 25W/m


Primary luminaire LED strip mounted on Power factor: > 0.9
construction material: extruded aluminium profile Rated luminous flux (lm): 2,800lm/m
Finish: N/A Luminaire efficacy: 112lm/W
Accessories: See Notes Beam / distribution: Symmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 3,000K
ghting solutions
Driver type: Project 1
Constant Voltage Colour Variation: 10.08.2014
≤ 3 SDCM
Drive current or voltage: 24V Operator Luminaire Lifetime: ≥ 50,000 hours
Telephone
Dimming & type: DALI, remote Fax
e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: LED Linear ™ – linear lighting
IP20solutions
ex HYDRA LD25 LED Linear / Luminaire Data Sheet

W824
2.400 K
W827
2.700 K
W830
3.000 K
W835
3.500 K
W840
4.000 K

W850
5.000 K
Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
VarioLED™ Flex HYDRA LD25

W824
2.400 K
W827
2.700 K
W830
3.000 K
W835
3.500 K
W840
4.000 K

W850
5.000 K
See our luminaire catalog for an image of the Departures chandeliers
luminaire.
Centre Space chandeliers

25 Watt/meter
25 Watt/meter
3.168 lumen/meter (lm/m) Notes:
3.168 lumen/meter (lm/m)
! One Bin Only: 3 MacAdam
1. Refer to Section ‘2.0 Products’ of this

Watt
! One Bin Only: 3 85
Ra/CRI MacAdam
specification for additional requirements.
2. Linear LED strip to be mounted on

att
! 127 Lumen/ Ra/CRI 85
a suitable profile to provide sufficient

umen/W
heat dissipation per manufacturer’s
& Maße !
AufbauLuminaire12 L according
7Assembly
classification
CIE flux code:
& measurement
47 79 96 100 95
to CIE: 100

125 mm (24 x)
Due to missing symmetry properties, no UGR table
can be displayed for this luminaire.
recommendations.
3. Continuous profiles to be supplied
with all necessary accessories including
embly & measurement mounting profiles, covers, brackets and
end caps.
+ 24 V
9,5 mm 4. Mock-up sample to be provided.
GND
125 mm (24 x) Final selection of optical lens/cover to be
confirmed during site mock-up.
9 mm 17,85 mm 17,85 mm 17,85 mm 17,85 mm 17,85 mm 17,85 mm 9 mm
5. Lengths required to be confirmed by
2,1 mm site measurement prior to ordering and
9,5 mm coordinated with Architect Engineer.
6. Profile sections to be cut to match
Elektrische & Optische Betriebsdaten Electrical & optical data required radius.

mm 17,85 mm 17,85 mm 17,85 mm 17,85 mm 9 mm 7. Mock-ups required to confirm design


intent.
Keine zusätzliche Kühlung
Abmessungen Dimensions 3.000 mm x 9,5 mm x 2,1 mm
über AL-Profil notwendig.
Teilungsmaß Step length 125 mm/7 LED 2,1 mm No need for additional heat
Leistung Power 74,9 W/25 Watt/meter sinking on AL profile.
Effizienz Efficacy bis zu/up to 127 lumen/Watt

he Betriebsdaten Electrical
Spannung Voltage (V)
& optical
Anzahl LED Number LED
data
168 LED, 17,85 mm LED pitch
24 Volt (23 V , 25 V )
Profile sections cut to match radius min max
The drawings on this page are
indicative. Refer to the architectural
Page 1 drawings for correct setting out,
Strom Current 3,12 A/130 mA per step L80, mounting details and final dimensions.
> 37.000 hrs
Temperatur Temperature tcmin = –25°C, tcmax = +80°C
Keine zusätzliche Kühlung
3.000 mm x 9,5 mm x 2,1 mmt
Lagertemp. Storage temp. = –30°C, tmax = +85°Cüber AL-Profil notwendig.
min

125 mm/7
Außentemperatur Ambient LED
temp. tamin = –25°C, tamax = +45°C Type:
No need for additional heat
74,9 W/25 Watt/meter sinking on AL profile.
VarioLED™ Flex Art. # Lumen/meter Ra
HYDRA LD15 bis zu/up to 127 lumen/Watt
(lm/m) CRI
R9
CRI
Farbtemperatur
Color Temperature (K) L2q
W824 Nähere Erläuterungen zu Änderungen, Grenz­ Sheet 1/3
168 LED,10377
17,85 mm1.916
LED pitch85 30 2.400
werten und Schwankungen im Herstellungs­
W827 10330 2.623 85 20 2.700 prozess finden Sie im LED Linear™ System­
24Terminal
W830Midfield
Contract: Volt10329
(23Building
Vmin, 252.800
Vmax
– ) 85Contractor,
General 20 3.000
AUH.06.10.0401 katalog, Seite 532. Page 73 of 231
BulletinW835
No. 145:3,12
Volume
A/130 3 mA
10328of 4 per
(Rev 07)
step
2.947 85 20 3.500 For more details regarding catalogue January 31, 2015
L80, changes, min and max data sheet values
W840 10327 3.018 83 20 >4.000
37.000 hrs
W850
tcmin = –25°C, tcmax = +80°C
10326 3.168 83 10 5.000
and production tolerances see the
LED Linear™ system catalogue, page 533.
Abu Dhabi Airports Company PJSC Specification, Section 265120

Allow for 48 U1 and 8 S6

3 strips of L2q

ARUP LIGHTING
L2q
L2q L2q L2q L2q L2q L2q
L2q
MARK_UPS L2q L2q L2q

Rev1

L2q L2q L2q

Detail sections of Departures Hall and Centre Space chandeliers from MTC-A-94-TB-L3-0-0-00-09-004

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.

Type:

L2q
Sheet 2/3

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 74 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

U1 U1 U1 U1
U1 U1

S6 S6

S6

L2q L2q L2q L2q L2q L2q


L2q L2q L2q L2q L2q

Detail 3
Type A Chandelier detail and section from MTC-A-94-TB-L3-0-0-00-09-004

U1 U1

S6

L2q L2q L2q

Detail 4
Type B Chandelier detail and section from MTC-A-94-TB-L3-0-0-00-09-004

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

L2q
Sheet 3/3

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 75 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Continuous integrated linear profile

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 15W/m


Primary luminaire LED strip mounted on Power factor: > 0.9
construction material: extruded aluminium profile Rated luminous flux (lm): 1,930lm/m
Finish: TBC Luminaire efficacy: 129lm/W
Accessories: See Notes N/A Beam / distribution: Symmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 3,000K
ghting solutions
Driver type: Project 1
Constant Voltage Colour Variation: 10.08.2014
≤ 3 SDCM
Drive current or voltage: 24V Operator Luminaire Lifetime: ≥ 50,000 hours
Telephone
Dimming & type: DALI, remote Fax
e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: LED Linear ™ – linear lighting
IP20solutions
ex HYDRA HD15 LED Linear GmbH / Luminaire Data Sheet

W824
2.400 K
W827
2.700 K
W830
3.000 K
W835
3.500 K
W840
4.000 K

W850
5.000 K
Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
VarioLED™ Flex HYDRA HD15

W824
2.400 K
W827
2.700 K
W830
3.000 K
W835
3.500 K
W840
4.000 K

W850
5.000 K
See our luminaire catalog for an image of the Escalators
luminaire.
Travelators

15,4 Watt/meter
15,4 Watt/meter
2.182 lumen/meter (lm/m) Notes:
2.182 lumen/meter (lm/m)
! One Bin Only: 3 MacAdam
1. Refer to Section ‘2.0 Products’ of this

Watt
! One Bin Only: 3 85
Ra/CRI MacAdam
specification for additional requirements.
2. Linear LED strip to be mounted on

att
! 142 Lumen/ Ra/CRI 85
a suitable profile to provide sufficient

umen/W
heat dissipation per manufacturer’s
& Maße !
AufbauLuminaire
CIE flux code:
L according
2Assembly
14classification & measurement
46 78 96 100 115

62,5 mm (64 x)
to CIE: 100 Due to missing symmetry properties, no UGR table
can be displayed for this luminaire.
recommendations.
3. Continuous profiles to be supplied
with all necessary accessories including
embly & measurement
L6 mounting profiles, covers, brackets and
L6
end caps.
+ 24 V 9,5 mm 4. Final selection of optical lens/cover to
x) GND be confirmed during site mock-up.
5. Lengths required to be confirmed by
4,45 mm 8,9 mm 8,9 mm 8,9 mm 8,9 mm 8,9 mm 8,9 mm 4,45 mm site measurement prior to ordering and
coordinated with Architect Engineer.
2,1 mm
9,5 mm 6. Mock-ups required to confirm design
intent.
Elektrische & Optische Betriebsdaten Electrical & optical data 7. This luminaire type is no longer
part of the FOH package. The
mm 8,9 mm 8,9 mm 4,45 mm specification requirement for this
Keine zusätzliche Kühlung
Abmessungen Dimensions 4.000 mm x 9,5 mm x 2,1 mm luminaire is to be included in the
über AL-Profil notwendig.
Teilungsmaß Step length 62,5 mm/7 LED escalator works specification
2,1 mm No need for additionalsections
heat 143100 Escalators and
Leistung Power 61,44 W/15,4 Watt/meter sinking on AL profile.
143200 Moving Walks.
Effizienz Efficacy bis zu/up to 142 lumen/Watt

he Betriebsdaten Electrical
Anzahl LED Number LED
Spannung Voltage (V)
& optical data
448 LED, 8,9 mm LED pitch
24 Volt (23 V , 25 V ) min max
The drawings on this page are
indicative. Refer to the architectural
Page 1 drawings for correct setting out,
Strom
L3 Current L3 2,56 A/40 mA per step L80, mounting details and final dimensions.
> 37.000 hrs
Temperatur Temperature tcmin = –25°C, tcmax = +85°C
Keine zusätzliche Kühlung
4.000 mm x 9,5 mm x 2,1 mmt
Lagertemp. Storage temp. = –30°C, tmax = +85°Cüber AL-Profil notwendig.
min

62,5Ambient
Außentemperatur mm/7temp.
LED tamin = –25°C, tamax = +45°C Type:
No need for additional heat
61,44 W/15,4 Watt/meter sinking on AL profile.
VarioLED™ Flex Art. # Lumen/meter Ra
HYDRA HD15 bis zu/up to 142 lumen/Watt
(lm/m) CRI
R9
CRI
Farbtemperatur
Color Temperature (K) L3
W824 of escalators10385 Nähere Erläuterungen zu Änderungen, Grenz­
Detail section 448 LED,from mm 1.320
LED pitch 85 30
8,9MTC-A-94-TB-L_-_-0-00-07-008 2.400
werten und Schwankungen im Herstellungs­
W827 10384 1.807 85 20 2.700 prozess finden Sie im LED Linear™ System­
24Terminal
W830Midfield
Contract: Volt10383
(23Building
Vmin, 251.929
–Vmax) 85Contractor,
General 20 3.000
AUH.06.10.0401 katalog, Seite 532. Page 76 of 231
BulletinW835
No. 145:2,56
Volume
A/40 3 mA
10382of 4per
(Rev 07)
step
2.030 85 20 3.500 For more details regarding catalogue January 31, 2015
L80, changes, min and max data sheet values
W840 10381 2.079 83 20 >4.000
37.000 hrs
W850
tcmin = –25°C, tcmax = +85°C
10380 2.182 83 10 5.000
and production tolerances see the
LED Linear™ system catalogue, page 533.
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Staggered fluorescent cove luminaire


Project 1
14.03.2014

Manufacturing standard: EN 60 598 Operator Lamp Type: T5 - High Efficiency, Long Life
Telephone
Primary luminaire Sheet aluminium Fax Lamp Wattage: 13W, 19W, 25W, 32W
e-Mail
construction material: Lamp Manufacturer: -
Finish: Intralux Australia
See P KLT5114
Notes Intralux Kove T5 KLT5114 Beam pelmet illumination module Asymmetric, see LDC
/ distribution:
Luminaire mounted in Konstruct cove CAUTION. Data is based on a test which
Accessories: N/A a lower section of cove. If youCRI
included / Colour
are following temperature:
Intralux Australia's > 80 / 3,000K
recommendations for cove sizes and finish, the result should be a reasonable
IP: IP20 Ballast/Transformer:
simulation however the results will not be valid for significant departures. The DALI, integral
Luminous sizes have been changed to match the original size / Luminaire Data ≥ 48,000 hours
Kovelife:
Lamp
Sheet
Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
See our luminaire catalog for an image of the Welcomers Hall
luminaire.
Baggage Reclaim
Bus Holdroom
Circulation
Perimeter coves
Arrivals Tunnel
Transfer Building

Notes:

Luminaire classification according to CIE: 0


CIE flux code: 00 00 00 00 84
Due to missing symmetry properties, no UGR table
can be displayed for this luminaire.
KOVE T5 LUMINA
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Lamp wattages indicated (13W, INSTALLATIO
19W, 25W, 32W) refer to different types

DATE
"6 Ê/xÊ1
October 2003
, of lamps to be combined to form a
Lengths required DS-K15-EU
continuous line.CODE to be
/
 
Ê ",/"
confirmed by site measurement prior to
PROJECT ordering and coordinated with Architect.
TYPE
/ "V̜LiÀÊÓääÎ
" /x‡/‡£‡ 1
coated (RAL
3. Fixture to be powder
9016).
*,"
/
1. MODULE SET UP (IDENTICAL FOR DOUBLE
/9*
LAMP MODULES)

High side to œÛiÊ/x½ÃÊÃÌ>˜`>À`ÊÌ܈˜‡>“«Ê“œ`ՏiÃÊ


back of cove Vœ“Lˆ˜iÊÌ܈˜‡>“«ÃʜvÊ̅iÊÃ>“iÊÜ>ÌÌ>}i°Ê
œÃÌʏ>“«ÊÌÞ«iÃÊ>ÀiÊ>ۈ>>Liʈ˜ÊÌ܈˜‡>“«Ê
Vœ˜vˆ}ÕÀ>̈œ˜Ã°
45˚ MAX

Page 1

-ˆ˜}i œÛiÊ/xÊṎˆÃiÃÊ̅iʏ>ÌiÃÌʈ˜Ê/xÊvÕœÀiÃVi˜Ìʏ>“«Ê
Ensure continuity of light
ÌiV…˜œœ}ްʣȓ“ÊvÕœÀiÃVi˜ÌÊÌÕLiÃʈ˜Ê£{7Ê̜Ê
by interlocking modules
nä7ÊÛ>Àˆ>˜ÌÃÊ>ÀiÊÕÃi`ʈ˜Ê̅iÊœÛiÊ/xʈ˜`ˆÀiVÌÊ
ˆÕ“ˆ˜>̈œ˜Ê“œ`Տið
Position and Orientation. Straight Installations. Curved Installation. Corner Configurat
-ˆ˜}iÊ/܈˜ÊÊÊÊ
The drawings on this page are
L4 indicative. Refer to the architectural
drawings for correct setting out,
2. POWER CONNECTION mounting details and final dimensions.

Power Feed -Ì>˜`>À`ÊÌ܈˜‡>“«Ê“œ`ՏiÃÊ«ÀœÛˆ`iÊ̅iʓœÃÌÊ


Type: 10 Amp Max
iVœ˜œ“ˆV>Ê܏Ṏœ˜Ê>˜`ÊŜՏ`ÊLiÊÕÃi`Ê܅iÀiÛiÀÊ
«œÃÈLi°Ê/܈˜‡>“«Ê“œ`ՏiÃÊV>˜Ê>ÃœÊLiÊÌi>“i`Ê

Detail 5
܈̅ÊȘ}iʏ>“«Ê“œ`ՏiÃÊ̅iÊ>VVœ“œ`>ÌiÊ՘ÕÃÕ>Ê
i˜}̅ð
L4
Sheet 1/4
Detail section of perimeter cove from MTC-A-41-TB-L_-_-_-__-00-940
˜`ˆÛˆ`Õ>Ê/xʓœ`ՏiÃÊV>˜ÊLiÊVœ“Lˆ˜i`Ê̜Ê
«ÀœÛˆ`iÊVœ˜Ìˆ˜ÕœÕÃʈÕ“ˆ˜>̈œ˜°Ê-ˆ˜}iʏ>“«Ê
Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 77 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) “œ`ՏiÃÊV>˜Ê>ÃœÊLiÊ>˜}i`Ê̜ʫÀœÛˆ`iʈÕ“ˆ˜>̈œ˜ÊJanuary 31, 2015
̜ÊVÕÀÛi`ÊVœÛið
First Module. Consecutive Modules. Split Circuits and Long Runs.
È *…œÌœ“iÌÀˆVÊ Ý>“«i\
Abu Dhabi Airports Company PJSC Specification, Section 265120

L4 L4 L4 L4

D12 D12

L5
L5

L4
L4

superseded
superseded
Detail 2
Detail section of Bus Holdroom from MTC-A-41-TB-L1-0-5-00-00-610

S1
S1

L4 L5c
L4 L5c

Detail 3
Detail section through coffer panel end from MTC-A-94-TB-L_-_-0-00-09-033 033

D12
The drawings on this page are
indicative. Refer to the architectural
L4 drawings for correct setting out,
mounting details and final dimensions.

Type:

Detail 4
L4
Sheet 2/4
Detail section of Bus Holdroom from MTC-A-41-TB-L_-_-_-__-00-945

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 78 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
GYB GYPSUM BOARD
72 ISSUED FOR CONSTRUC

62
20
4625
01
1900
ARRIVALS TUNNEL
CLG
10 4
DETAIL, TYPE L18 CEILING SLOT LIGHTS & INTERFACE BETWEEN GYB-01 & CLG-10 ABU
Abu DhabiSCALE
Airports
1:5 Company PJSC Specification, Section 265120 AIRPORTS

3000
GYP
ABU DHABI AIRPORTS COMPANY
04

TRZ Kohn Pedersen Fox Asso


(International) PA

01/02
Architects and Planning C
7a Langley Street
London WC2H 9JA
England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com

LIGHT WEIGHT LMF


02

GYPSUM BOARD GYB


01

CEILING MOUNTED LINEAR


ABU DHABI INTERNATION
SLOT DIFFUSER MIDFIELD TERMINAL CO
(SUPPLY)
400

325

L4 ARRIVALS TUNNEL LB1 & LB


RCP & SECTIONS (SHEET 2 O

MTC A 41 TB __ L_._ _
200

KPF MC KF
ARRIVALS TUNNEL
GYPSUM BOARD GYB
5 DETAIL, LIGHT COVE
Detail 5 01
SCALE 1:5
Detail section of Arrival Tunnel from MTC-A-41-TB-L_-_-_-__-00-666 2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. A
HT
ING

07 30.11.14 BULLETIN 134


06 31.10.14 BULLETIN 120
05 25.09.14 BULLETIN 115
04 25.08.14 BULLETIN 107
03 25.06.14 BULLETIN 90

GYB
01 ISSUED FOR CONSTRUCTION

125
ABU DHABI
400

AIRPORTS COMPANY
L4 ABU DHABI AIRPORTS COMPANY

Kohn Pedersen Fox Associates


(International) PA
125

Architects and Planning Consultants


7a Langley Street
London WC2H 9JA
England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com

GYB 110 262 200


01

ARRIVALS TUNNEL
4 DETAIL
Detail 4
ABU DHABI INTERNATIONAL AIRPORT
SCALE 1:5 MIDFIELD TERMINAL COMPLEX
Detail section of Arrival Tunnel from MTC-A-41-TB-L_-_-_-__-00-667

ARRIVALS TUNNEL LB1 & LB2 CEILING


RCP & SECTIONS (SHEET 3 of 3)

MTC A 41 TB __ L_._ _.__ 00.667 07

KPF MC KF JH 31.08.2010

WBS AUH.06.10.0401

2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights reserved. Do not scale. The drawings on this page are
L4 indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

Detail 6
Detail section of perimeter of Transfer Building Arrival from MTC-A-41-TB-L3-0-_-__-00-650
L4
Sheet 3/4

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 79 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
FORMED METAL FRAMING

5 EDGE SECTION OF ACOUSTIC CEILING PANEL-SIDE PARALLEL TO RIB STRUCTURE


SCALE 1:10

08 31.01.15 BULLETIN 145


325 07 05.01.15 BULLETIN 137
Concealed
L4 06 31.10.14 BULLETIN 120
sprinkler head
CONTINUOUS LINEAR GRILLE.
SEE MECH. DWG'S 05 25.09.14 BULLETIN 115
04 25.08.14 BULLETIN 107
125

200 500 30 200 30


ISSUED FOR CONSTRUCTIO
Escutcheon
Sprinkler cap
ARRIVALS TUNNEL SFS STRETCHED FABRIC
Detail 33 DETAIL Metal acoustic ceiling MPC
01 ABU DH
concealed grid 03A
Detail of Arrivals Tunnel perimeter cove from MTC-A-41-TB-L_-_-_-__-00-665
SCALE 1:5
AIRPORTS CO
6 EDGE SECTION OF ACOUSTIC CEILING PANEL-SIDE ABOVE SERVICE BOOM ABU DHABI AIRPORTS COMPANY

SCALE 1:10 GLZ TRANSLUCENT


Kohn Pedersen Fox Associates
11 INTERLAYER (International) PA
Architects and Planning Consultants
7a Langley Street
London WC2H 9JA
LED STRIP GRAZING England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
TRANSLUCENT GLASS www.kpf.com

GALVINISED MILD STEEL


BRACKET INTERVAL PER
PANEL JOINT. SIZE TBD
METAL FRAME

D9b GYB GYPSUM BOARD


01
ABU DHABI INTERNATIONAL A
300 120 15
L2c
MIDFIELD TERMINAL COMP
L4

TYPE L20 - LINEAR LED RGB


20 180 PROCESSOR ARRIVAL
STRIP LIGHT MOUNTED IN
DCM ST. STEEL TRIM (REMOVABLE TO
CEILING COMPONENTS
03 ACCESS LIGHT FIXTURE)
ARCHITECTURAL DETAILS
SFS STRETCHED FABRIC
- 09ACOUSTIC PANEL
30.11.14 BULLETIN 134
DCM CONTINUOUS SSTL
01 08 31.10.14 BULLETIN 120
03 SHOP BONDED TO GLASS
SPRINKLER MTC A BULLETIN
07 25.08.14 41 TB 107 __ L0.1 5.00
06 25.06.14 BULLETIN 90
ARRIVALS TUNNEL ARRIVALS TUNNEL 05 25.05.14 BULLETIN 80
4 DETAIL 6 DETAIL
SCALE 1:5 7 EDGE SECTION OF ACOUSTIC CEILING PANEL-SIDE
SCALE 1:5 ABOVE SERVICE BOOM KPF MC KF JH
ISSUED FOR CONSTRUCTION
Detail 7 SCALE 1:10
WBS
Edge section of acoustic ceiling panel at Arrival Lobby from MTC-A-41-TB-L0-1-5-00-00-871
ABU DHABI
2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights r

AIRPORTS COMPA
ABU DHABI AIRPORTS COMPANY

NTED
D GLASS Kohn Pedersen Fox Associates
(International) PA
Architects and Planning Consultants
7a Langley Street
London WC2H 9JA
England
T: +44 (0)207 319 5300
NTED F: +44 (0)207 497 1175
www.kpf.com

D GLASS
CENT GLASS
(BY OTHERS) 150

GHT FIXTURE
The drawings on this page are
ED MILD STEEL indicative. Refer to the architectural
NTERVAL PER 150 L2c ABU DHABI
drawings for correct INTERNATIONAL AIRPO
setting
NT. SIZE TBD
MIDFIELD
out, mounting details TERMINAL COMPLEX
and final
400

US LINEAR GRILLE.
. DWG'S
L2c dimensions.
L4 L4 ARRIVALS TUNNEL LB1 & LB2 CEILIN
200

RUDED PROFILE RCP & SECTIONS (SHEET 1 OF 3)


Type:
D2 L2c
D FABRIC
30 200
MTC A 41 TB __ L_._ _.__ 00.6

5
ESCALATOR WELL
Detail
DETAIL 5
DCM
03 ST. STEEL TRIM
21

KPF MC KF
L4 JH 31

SCALE 1:5 Sheet 4/4


Ceiling interface at Transfer Building north section from MTC-A-41-TB-L2-0-_-__-00-654 WBS AUH.06

2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights reserved.

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 80 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Surface mounted linear luminaire

Manufacturing standard: EN 60 598 Lamp Type: T5 - High Output, Long Life


Primary luminaire Extruded aluminium Lamp Wattage: 2 x 50W
Project 1
construction material: Lamp Manufacturer:15.03.2014 -
Finish: See Notes Telephone Beam / distribution:
Operator
Asymmetric, see LDC
Fax
Accessories: N/A e-Mail CRI / Colour temperature: > 80 / 3,000K

IP: IP20 Ballast/Transformer: DALI, integral


ELLIPTIPAR F306-T155-S-00-1-000 EXTRUDED SEMI-SPECULAR METAL BALLAST
HOUSING, EXTRUDED SEMI-SPECULAR METAL REFLECTOR Lamp life:
WITH WHITE PLASTIC ≥ 48,000 hours
WIRE WAY COVER BELOW LAMP, OPEN TOP. / Luminaire Data Sheet
Style 308
Luminaire distribution curve (LDC)
Luminous emittance 1: Location:
Welcomers Hall
See our luminaire catalog for an image of the
luminaire.
Baggage Reclaim
Reflector 1
Arrival Lobby

Project 1 Circulation
15.03.2014

Operator
Telephone
Fax
e-Mail

ELLIPTIPAR F305-T155-S-00-1-000 EXTRUDED SEMI-SPECULAR METAL BALLAST


HOUSING, EXTRUDED SEMI-SPECULAR METAL REFLECTOR WITH WHITE PLASTIC
WIRE WAY COVER BELOW LAMP, OPEN TOP. / Luminaire Data Sheet
Notes:
Lighting the Ceiling Luminous emittance 1:
Dual small / xtra small concealed 1. Refer T5 Fluorescent
to Section ‘2.0 Products’ of this
Luminaire
See classification
our luminaire according
catalog to CIE:
for an image of 4
the Due to missing symmetry properties, no UGR table specification for additional requirements.
CIE flux code: 10 19 17 04 76 can be displayed for this luminaire.
Style 308 luminaire.
1:8 Scale
Reflector 2 Lamp 2. WhenLuminaire
indicated as a continuous
  Length Length , luminaires shall be
line on drawing

 1 x 2' 23-1/16"end
mounted (586mm)
to end.
 1 x 3' 34-7/8" (886mm)
 3. Mounting detail to Architect’s
  1 x 4' 46-11/16" (1186mm)
 specification.
  1 x 5' 58-1/2" (1486mm)
4. Fixture to be powder coated (RAL
 2 x 3' 69-1/2" (1765mm)
9016).
 Œ
   2 x 4' 93-1/8" (2365mm)
 
 
2 x 5' 116-5/8" (2963mm)

Cove Cove Dimensions Joint 1:4 Scale


Ceiling Dual small / xtra small concealed T5 Fluorescent (ballast compartment Style 308
versatile cove lighting for large spaces†‡ˆ not shown for clarity)
­‰
e reflector maximizes asymmetric Sightline 0° (horiz. 5° 10°
per Luminaire performance
 ‰ ƒŠ 
‰ classification according to CIE: 3 DueLamp cutoff)
to missing symmetry properties, no UGR table
­ €‚
imed lower for
longer throwsCIE flux code: 19 ‹ˆ€‰ 
41 51 02 71 C Width Length 12"
Luminaire
can be displayed for this luminaire.
Length
11" 9"
 
ntly adjustable – each row of reflectors joins
22.0 
(inside)1 x 2'(305mm)
23-1/16"(280mm)
(586mm) (230mm)


ogether; rotation
 locking screws secure position Lip 1 x 3' 5" 34-7/8" 4-1/4"
(886mm) 3-5/8" „

ectronic ballast, thru wiring for easy installation
 (inside) (127mm) (108mm) (92mm)
 
ƒ„  1 x 4' 46-11/16" (1186mm) 
…  Setback Recommended minimum:
 
ance  1 x 5' 58-1/2"
(varies)
 18" T5,(1486mm)
24" T5HO
   ∠ A* 2 x 3' 25°69-1/2" (1765mm)
22° 15° Page 1
consists   ‡    Œ
c reflector Ž„‘   ∠ B* 2 x 4' 13° 93-1/8" (2365mm)
10° 9°

 
ve light Note: Finish interior of1186mm
cove matte white for best results. 2 x 5'aiming,
*Adjustable 116-5/8"
lowest(2963mm)
angle listed. 
ing from
elliptical Cove Dimensions Joint 1:4 Scale The drawings on this pageFeatures
are
the lamp Specifications ‡  (ballast compartment
ewing†‡ˆ Ž not shown for clarity) indicative. Refer to the architectural
directs A Specular extruded Sightline 0°D(horiz.
Extruded 5° aluminum10° F Extruded aluminum J Mounting tabfor
drawings (fastener Dual T5 – versatile cov
correct settingQ out,
 ‰ ƒŠ  aluminum reflector cutoff)
ballast/wireway ballast/wireway by others)
rabola.
 ‹ˆ€‰   mounting details and final Q Larger upper reflector
dimensions.
B  Stainless steel lamp- Width 12"channel11" cover 9" compartment  K Integral electronic – can be aimed lower
zed and (inside) (305mm) (280mm)
he beam holder/support brackets E Conduit entry (230mm)
(one G Rotation locking screw ballast Q independently adjusta
esulting C Aluminum sidearm Lipwith 5" each end,
4-1/4"conduit
3-5/8"and H Joiner/alignment screw „ and aims together; rot
mounting tab (inside) (127mm)connector
(108mm) by others)
(92mm) Type:
fficiency

 Q Integral electronic ball
urface 
ƒ„ 
  Setback Recommended minimum:
ectors (varies) 18" T5, 24" T5HO Performance
ntly. Finish: Curve
Note: Electrical:
 

shown for single ∠ A*
specular finish. Sidearms
25°
13°
22°
Reflectors – extruded high purity aluminum with clear anodized
small reflector. ∠ B*and ballast/wireway
15°
10°compartment
9° –
Use 90°C wire for supply connections.
Integral electronic HPF thermallyPage 1
protected class P ballast with
L5
Each reflector consists
of two parabolic reflector
visit
cove matte whitemillforfinish
best aluminum.
results. All luminaireaiming,
*Adjustable hardware – stainless
lowest steel.
angle listed. 
end-of-life protection. Ballast/wireway compartment includes sections to drive
Sheet 1/4 light
otient.com one conduit entry at each end. Channel cover removes for across the ceiling from
Mounting: one edge. An elliptical
Lay-in installation requires only one fastener per joint (by others). access to ballast and wiring. Luminaires may be butted end-
section shields the lamp
Luminaires can be mounted individually or joined together to to-end (connectors by others) Features
for through wiring. Optional #12
from 81 normal viewing
Contract: Midfield
form a continuous row.Terminal Building – General Contractor, AUH.06.10.0401
AWG prewired modular through wiring with quick connectors. Page of 231
d D Extruded aluminum F 4 Extruded aluminum Mounting
J Optional tab (fastener Dual T5 – versatile cove lighting angles
for largeand redirects
spaces
Bulletin No.
Reflector 145: Volume 3 of (Rev 07)
aiming is adjustable andballast/wireway
is fixed in position by
Q
electronic dimming ballast; compatible dimmer January 31, 2015
its light to a parabola.
r ballast/wireway by others)
switch Q Larger
required (by others). Consult salesupper reflector maximizes
representative for asymmetric performance
rotation
channellocking
cover screws at each sidearm. When mounted in
compartment Glare is minimized and
mp- a continuous row, joiner screws lock each row of reflectors K Integral electronic
compatibility and specifications. – can be aimed lower for longer throws
asymmetry of the beam
ackets Conduitallowing
E together entry (one G Rotation locking screw
all in the row to be aimed together. Each row ballast Q independently
Optional integral emergency battery adjustable – eachisrow
operates one lamp. maximized resulting
of reflectors joins
m with ofeach end, conduit
reflectors is aimedand H Joiner/alignment screw
independently. and aims together; rotation locking
Separate unswitched supply is required. in high
screwsbeam efficiency
secure position
connector by others) and superior surface
Abu Dhabi Airports Company PJSC Specification, Section 265120

L5 L5

L5

L4d L4d

Detail 1 L2c

Detail section through typical boom from MTC-A-94-TB-L_-_-0-00-09-033 033

D8

AR
MA
L5

L5 L5

ARUP LIGHTING
D8 to be in-line with
L5c L5c

MARK_UPS
panel

L2c
L5c
L18 L5c

D8 to be in-line with
panelDetail section through Baggage Reclaim light shelf from MTC-A-94-TB-L_-_-0-00-09-033 033

The drawings on this page are


indicative. Refer to the architectural
L5 L5 drawings for correct setting out,
mounting details and final dimensions.

Type:

Detail 3
L5
Sheet 2/4
Detail section through Baggage Reclaim light shelf from MTC-A-94-TB-L_-_-0-00-09-033

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 82 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) L13c January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Lighting tray
4
A41481
3
A41481 3
A41481 Drop-down smoke curtain

L5
L18b

Details 3 and 4
Detail through typical Pier section lighting trays from MTC-A-94-TB-L_-_-0-00-09-003

S.O.P

Glass smoke downstand GFF


with glass fin support 04
Light fitting

Smoke detector Clear laminated glass GLZ


01 04 30.11.14 BULLETIN 134
910

03 31.10.14 BULLETIN 120


Provide embedment in column 02 25.08.14 BULLETIN 107
to recieve steel framing
01 01.07.14 BULLETIN 85
Containment DFR 00 15.07.12 ISSUED FOR CONSTRUCTION
Curtain type 1 02
Side wall sprinkler
12° (if applicable) 163
152 L5 L5 ISSUED FOR CONSTRUCTION
R9

16°
1

ated cladding MPC


80 92
80 80

lighting tray 04B ABU DHABI


R1 AIRPORTS COMPANY
360

38
Steel Framing ABU DHABI AIRPORTS COMPANY
200

200

38
R1 L. +16.85
50 Kohn Pedersen Fox Associates
D1 D1
(International) PA
R1669

Architects and Planning Consultants


7a Langley Street
55 London WC2H 9JA
England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com

Light fitting Smoke Containment DFR


Curtain type 1 02

Sprinkler
Detail 3 Sprinkler (typ)

Detail through Processor Arrival ceiling lighting tray typical from MTC-A-41-TB-L0-1-5-00-00-872
ABU DHABI INTERNATIONAL AIRPORT
04 MIDFIELD TERMINAL COMPLEX

100 540 485 1780 PROCESSOR ARRIVAL CEILING


2905 COMPONENTS - LIGHTING TRAY AND
Metal unperforated cladding MPC SMOKE CURTAIN AT WATER GARDEN
lighting tray 04B
MTC A 41 TB __ L0.1 5.00 00.872 04

3 SECTION OF LIGHTING TRAY KPF MC KF JH 25.09.2009


SCALE 1:10
SEE G04310 AND G04312 FOR LOCATIONS OF GFF 04 AND DFR 02. WBS AUH.06.10.0401

2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights reserved. Do not scale.

fixture to be
in-line with up
stand

L5b

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

Detail 6
L5
Sheet 3/4
Detail section from MTC-A-41-TB-L_-_-_-__-00-940

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 83 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
XL1 XL1

685
CL
METAL UNPERFORATED CLADDING MPC MPC METAL UNPERFORATED CLADDING
LIGHTING TRAY 04B 04B LIGHTING TRAY

130
1200 XD1 XD1
Abu Dhabi Airports Company PJSC
3

SECTION DETAIL 03
1000
Specification, Section 265120
CL
METAL UNPERFORATED CLADDING MPC MPC METAL UNPERFORATED CLADDING
SCALE 1:10
LIGHTING TRAY 04B 04B LIGHTING TRAY

1200

3 SECTION DETAIL 03
SCALE 1:10

L5 L5
785

L2c L2c
315

L5 L18 L18 L5
4800

3650 3650
785

7300

L2c L2c
315

CL
L18 L18 03 30.11.14 BULLETIN 134
MPC METAL PERFORATED CLADDING
4800 04A SERVICE BOOM 02 31.10.14 BULLETIN 120
01 25.02.13 BULLETIN 07
4 SECTION DETAIL 04 3650 3650
00 15.07.12 ISSUED FOR CONSTRUCTION
SCALE 1:20 7300
Detail 4
CL ISSUED FOR CONSTRUCTION
MPC METAL PERFORATED CLADDING 03 30.11.14 BULLETIN 134
04A SERVICE BOOM 02 31.10.14 BULLETIN 120

PROFILE @ 5A SHOWN DOTTED 01 25.02.13 BULLETIN 07


4 SECTION DETAIL 04 00 15.07.12 ISSUED FOR CONSTRUCTION
ABU DHABI
SCALE 1:20
AIRPORTS COMPANY
L5 L5 ABU DHABI AIRPORTS COMPANY
ISSUED FOR CONSTRUCTION
Kohn Pedersen Fox Associates
(International) PA
Architects and Planning Consultants
7a Langley Street
London WC2H 9JA
PROFILE @ 5A SHOWN DOTTED
ABU DHABI
England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com

AIRPORTS COMPANY
L5 L5
1820

ABU DHABI AIRPORTS COMPANY


1470

Kohn Pedersen Fox Associates


(International) PA
Architects and Planning Consultants
7a Langley Street
London WC2H 9JA
England

ABU DHABI INTERNATIONAL AIRPORT


T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com
135

L2c L2c MIDFIELD TERMINAL COMPLEX


275

330
1820

L18 L18
1470

4800
PROCESSOR ARRIVAL
CEILING COMPONENTS - LIGHTING TRAY/
7500 SERVICE BOOM
DING MPC
CL ABU DHABI INTERNATIONAL AIRPORT
135

TRAY 04B L2c L2c MTC A MIDFIELD


41 TB __TERMINAL
L0.1 COMPLEX
5.00 00.874 03
275

330

L18 L18
SECTION DETAIL 05/5a PROCESSOR ARRIVAL
5 4800 KPF MC KF JH 15.07.2012
SCALE 1:20
CEILING COMPONENTS - LIGHTING TRAY/
7500 SERVICE BOOM
WBS AUH.06.10.0401
CL
DDING MPC
TRAY 04B MTC A 41 TB __ L0.1 5.00 00.874 03
2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights reserved.
Do not scale.

Detail 55 SECTION DETAIL 05/5a KPF MC KF JH 15.07.2012


SCALE 1:20
WBS AUH.06.10.0401

2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights reserved. Do not scale.

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

L5
Sheet 4/4

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 84 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Surface mounted linear luminaire

Manufacturing standard: EN 60 598 Lamp Type: T5 - High Output, Long Life


Primary luminaire
Project 1 Extruded aluminium Lamp Wattage: 50W
construction material: Lamp Manufacturer: 17.03.2014
-
Operator
Finish: See Notes Telephone Beam / distribution: Asymmetric, see LDC
Fax
Accessories: N/A e-Mail
CRI / Colour temperature: > 80 / 3,000K
IP: IP20 Ballast/Transformer:
ELLIPTIPAR F305-T155-S-00-1-000 EXTRUDED SEMI-SPECULAR METAL BALLAST DALI, integral
HOUSING, EXTRUDED SEMI-SPECULAR METAL REFLECTOR Lamp life: WHITE PLASTIC ≥ 48,000 hours
WITH
escent WIRE WAY COVER BELOW LAMP, OPEN TOP. / Luminaire Data Sheet
escent Style 306
Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
See our luminaire catalog for an image of the Car Park bridges
luminaire.
Baggage Reclaim
Circulation
L0 Immigration

eight
chart)

Notes: T5 Fluorescent
Lighting the Ceiling Small concealed, integral T8 Fluorescent
1. Refer to Section ‘2.0 Products’ of this
horiz.)
Style 306Luminaire classification according to CIE: 3
1:8 Scale Due to missing symmetry properties, noCove
UGR table1:10 Scale
specificationfor additional requirements.
CIE flux code: 19 41 51 02 71 can be displayed for this luminaire.
0° 2. When indicated as a continuous
Sightline Angle
A A line
(see on drawing , luminaires shall be
chart)
3/4" B
Setback mounted
Maximumend to end.
mm) C G Candlepower
3-3/4" (see
D
chart) 3. Mounting
(adjustable) detail to Architect’s
5/8" (95mm)
E F specification.
mm)
F Lippowder
4. Fixture to be Height coated (RAL
m: J K (see chart)
9016).
O 5-7/8" Length (see chart)
1186mm
(149mm)
1-1/8" Width
hite (29mm) (see chart)

Joint 1:4 Scale Cove Dimensions


(ballast compartment Nominal Luminaire Length (max. candlepower aimed 15° above horiz.)
Features
not shown for clarity) Lamp
T5 T8 Sight- 0° (horiz.
Length 5° 10°
ner Q Choose T5 for precise optical1 control or widely utilized T8 line cutoff)
x 2' 23-1/16" (586mm) 24-3/4" (628mm)
Width 10-5/8" 8-1/4" 6-3/4"
Q Compact and flexible – effective
1 x 3'indirect cove lighting for
34-7/8" (886mm)
malls, offices, lobbies,G conference rooms and corridors
36-3/4" (932mm) C (inside) (270mm) (210mm) (171mm)
1 x 4' 46-11/16" (1186mm) 48-3/4"
Q Adjustable – all reflectors in a row join and aim together;
20.0
(1237mm) Lip 3-3/4" 3" 2-5/8"
1 x 5' 58-1/2" (1486mm) 60-1/2" (1537mm) (inside) (95mm) (76mm) (67mm)
rotation locking screwsH secure position* Setback Recommended minimum:
2 x 3' 69-1/2" (1765mm) 73-3/16" (1859mm)
Q Integral electronic ballast thru wiring for easy installation (varies) 12" T5 and T8, 18" T5HO
C 2 x 4' 93-1/8" (2365mm) 97-3/16" (2468mm) Page 1
Note: Finish interior of cove matte white
Performance J 2 x 5' 116-5/8" (2963mm) 120-7/8" (3069mm) for best results.

t Two parabolic reflector 1x55W


sections drive light T5 HO
Specifications The drawings on this page are Features
annel across the ceiling from
es oneAedge. An elliptical
Specular extruded D Extruded aluminum F Extruded aluminum J indicative.
Mounting tabRefer to the architectural
(fastener Q Choose T5 for precis
ugh sectionaluminum
shields thereflector
lamp ballast/wireway ballast/wireway bydrawings
others) for correct setting Qout,
Compact and flexible
1x32W
channel cover compartment
ng fromB normal viewing
Stainless steel lamp- T8
mounting
K Integral details and final dimensions.
electronic malls, offices, lobbie
angles holder/support
and redirectsbrackets E Conduit entry (one G Rotation locking screw ballast Q Adjustable – all refle
see its light
C Aluminum sidearm with 2200 each end, conduit and
to a parabola. H Joiner/alignment screw rotation locking scre
Glare ismounting
minimizedtab and connector by others)
t Cd Type: Q Integral electronic ba
ellite asymmetry of the beam
is maximized resulting Performance
in Finish:
high beam efficiency
and superior surfacehigh purity aluminum with clear anodized
L5b
Reflector – extruded Integral electronic HPF thermally protected class P ballast Two parabolic reflector
for specular finish. Sidearms and ballast/wireway compartment –
uniformity. (with end-of-life protection for T5 lamps). Ballast/wireway sections drive light
mill finish aluminum. All luminaire hardware – stainless steel. compartment includes one conduit entry at each end. Channel across the ceiling from
For complete photometrics, cover removes for access to ballast and wiring. Luminaires one Sheet
edge. 1/3
An elliptical
Mounting:
visit thelightingquotient.com may be butted end-to-end (connectors by others) for through section shields the lamp
Lay-in installation requires only one fastener per joint (by others). wiring. Optional #12 AWG prewired modular through wiring from normal viewing
Sidearms with mounting tabs can be base or wall mounted. with quick connectors. angles and redirects
Luminaires
Contract: can be Terminal
Midfield mounted individually
Building –orGeneral
joined together to
Contractor, AUH.06.10.0401 Page 85 ofto231
its light a parabola.
form a continuous row. Master/satellite combination is available (Configuration 3, see
Bulletin No. 145: Volume 3 of 4 (Rev 07) Ordering Information). Master supplied with 2-lamp ballast Glare
January is 2015
31, minimized and
Cradle to Cradle aiming
Reflector Certifiedis adjustable and is fixed in position by
CM
asymmetry of the beam
is a certification mark licensed (wiring, conduit and connectors between master and satellite
rotation locking screws at each sidearm. When mounted in a units by others). is maximized resulting
by the Cradle to Cradle Products
continuous
Innovation Institute.row, joiner screws lock reflectors together allowing
in high beam efficiency
all in the row to be aimed together. Optional electronic dimming ballast; compatible dimmer and superior surface
switch required (by others). Consult sales representative for uniformity.
Abu Dhabi Airports Company PJSC Specification, Section 265120

L5b L5b

L18b L18b

L2j

XL3 XL3

Detail 1 XD1c
Detail section of Car Park Bridge from MTC-A-94-TB-L_-_-0-00-09-020

L5b L5b

L18b L18b

Detail 1
Detail section from MTC-A-41-TB-L0-1-5-00-00-880
The drawings on this page are
indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.

Type:

L5b
Sheet 2/3

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 86 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015

L5b
Abu Dhabi Airports Company PJSC Specification, Section 265120

BIRD DETERRENT

L18b

L5b XL1
XL1

685

130
210

XD1 XD1
1000

CL
METAL UNPERFORATED CLADDING MPC MPC METAL UNPERFORATED CLADDING
LIGHTING TRAY 04B 04B LIGHTING TRAY
1540
1200 1200

Detail 2 2400
3 SECTION DETAIL 03
CL
Detail section of Level 2.0 ceiling at North Economy Transfer Lounge from MTC-A-41-TB-L2-0-5-13-00-433
SCALE 1:10

1 SECTION DETAIL 01
SCALE 1:10

L5 L5
785

L2c L2c
315

L18 L18
4800

3650 3650

7300

CL
MPC METAL PERFORATED CLADDING 03 30.11.1
04A SERVICE BOOM 02 31.10.1
01 25.02.1

ARU
4 SECTION DETAIL 04 00 15.07.1
SCALE 1:20

MA
Rev
PROFILE @ 5A SHOWN DOTTED

L5 L5 ABU DHABI
1820
1470

L5b L5b

ABU
135

L2c L2c
275

330

L18 L18
1500 4800
PROCE
CEILIN
CL 7500 SERVIC
CL
METAL UNPERFORATED CLADDING MPC
LIGHTING TRAY 04B MTC A

SECTION DETAIL 02 5 SECTION DETAIL 05/5a KPF


2
Detail 2
SCALE 1:10
SCALE 1:20

Details of Processor Arrival ceiling components from MTC-A-41-TB-L0-1-5-00-00-874 2014 KOHN PEDERSEN

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

L5b
Sheet 3/3

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 87 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
L7Abu Dhabi Airports Company PJSC Specification, Section 265120

Arcos Asymmetric 30W LED830


Luminaire Description: Continuous wall and glass screen mounted linear luminaire
LED Luminaire / wall mount
Manufacturing
Slender asymmetric standard: ENwasher
linear LED floor Total
60 598luminaire; with stabilised luminaire
colour wattage
temperature (max):
"Stable White"; optimised
30W/m
for Primary luminaire
the efficient and uniform lightingExtruded Slave luminairePower
aluminium
of floor areas, for DALIfactor: > 0.9
control (DALI); lamp(s): 1/30 W LED830,
construction
asymmetric material:(LED module precisely matched to this);
light distribution Rated luminous
Colour renderingflux
Ra >(lm): 1,900lm/m
80, colour temperature
Finish: Anodised aluminium silver Luminaire efficacy: 63lm/W
3000 K; Chromaticity tolerance (initial MacAdam): 3; Total luminous flux of luminaire: 1900 lm, Luminaire efficacy: 63
Accessories: Mounting bracket Beam / distribution: Asymmetric, see LDC
lm/W; UVA-free and IR-free light; service life: h for luminous flux at 70% of initial value; illuminance can be dimmed
Light source type: LED CRI / Colour temperature: > 80 / 3,000K
from 5-100 %; mains voltage: 220- 40V/ 50/60Hz; unit tilted through ±15°; housing of extruded aluminium section
Driver type: Abu Dhabi International Airport
Constant current Colour Variation: 04.04.2014
≤ 3 SDCM
withDrive
end caps of die-cast
current or aluminium;
voltage:
Zumtobel Lighting GmbH
surface:
400mA microtextured white paint
Luminairefinish;
Operator Steven Edwards
glare reduction
Lifetime: due ≥to50,000
spotlight
hours
Telephone +43 5572 390 1466
design, LED light
Dimming source not directly
& type:
Dornbirn visible;
DALI, specular reflector pure
integral Fax aluminium
Lifetime
+43 5572 390 216 silver anodised; with
Basis: L70acrylic
/ F10anti
@glare
Ta 250C
Austria e-Mail steven.edwards@zumtobel.com

lensIP:
cover; dimensions: 1000x40x212 IP20mm; note: mounting to glass wall detail to determined.
Abu Dhabi Airport - SX diffus § / Luminaire Data Sheet

Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
See our luminaire catalog for an image of the Circulation - glass screens
luminaire.

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Luminaire to be passively cooled.
3. Continuous profiles to be supplied
with all necessary accessories including
Luminaire classification according to CIE: 98 Due to missing symmetry properties, no UGR table mounting profiles, covers, brackets and
CIE flux code: 28 63 92 98 100 can be displayed for this luminaire.
40
40

end caps.

160 4. Lengths required to be confirmed by


site measurement prior to ordering and
Light Distribution STD - standard
coordinated with Architect Engineer.
5. Mounting details to be coordinated
with Architect architectural details.
160

• Light Distribution: STD - Standard


• Lamps: Tridonic LED 30.0W
• Total luminous flux of luminaire: 1900m (per 1000mm)
• Luminaire efficacy: 63 lm/W
varies • Rated life: 50000h L70 at 25°C
• Colour Rendering Index min: 80
• Colour temperature: 3000 Kelvin
• Chromaticity tolerance (initial MacAdam): 3
• Ballast: 1 x 06813232 LED CONV 32W UNI 110-240V 1-10 TCII
• Connected Load: 30.0W
• Dimming: LDE
• Maintenance category: D – Enclosed
40 IP2X
40

• Impact category: IK02


The drawings on this page are
160
indicative. Refer to the architectural
Page 1 drawings for correct setting out,
mounting details and final dimensions.
160

Type:
We reserve the right to make technical changes without prior notice. 27.11.2012 © Zumtobel - 5 year guarantee when you register at www.zumtobel.com/guarantee/registration
varies
L7
Sheet 1/3

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 88 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
4 TYPE 2A - TOP OF SLAB F
SCALE 1:20
-- NOTE: 150x150mm SSTL CONT
A51107 ANGLES SHOWN IS TYPICAL F
FINS FIXED TO TOP OF SLAB.
ARM MILD STEEL CARRIER FRAME TO
Abu Dhabi Airports Company PJSC 01 ADJUST TO CEILING HEIGHT Specification, Section 265120
CEILING VOID VARIES
LIGHT FIXTURE WHERE
OCCURING AS PER (A94)
LIGHTING PLANS

L7

GFF FRAMELESS GLASS


01 SCREENS

GLZ GLASS SCREENS


03

1 TYPE 1A 2
FACADE MULLION
SCALE 1:20
PATTERNED GLASS

BAL GLASS
05 BALUSTRADE

GLZ
23
SIMILAR 6
STN STONE A91550
6
A91550 STN STONE 10 COVER
10 COVER
DCM SSTL TROLLEY
-- DCM
02
SSTL TROLLEY
RAILING
02 RAILING A91610 ARM
ARM 01
01 SSTL FLOOR
DIFFUSER GRILL
FLOOR LIGHT TYPE U3
Detail section from MTC-A-51-TB-L_-_-_-__-00-560
7 TYPE 4 & TYPE 4C 9 TYPE 4A 10 TYPE 4D 11 TYPE 1D
SCALE 1:20 SCALE 1:20 SCALE 1:20 SCALE 1:20

NOTE: TYPE 4 HAS OPEN JOINTS BETWEEN NOTE: GLZ-11 TO BE USED WHERE TRANSLUCENCY
GLASS PANELS. TYPE 4C HAS SILICONE IS INDICATED IN SCOPING PLANS
JOINTS BETWEEN GLASS PANELS. FOR CUSTOMS GREEN CHANNEL EXIT DOORS
REFER TO A51580 L7

GFF FRAMELESS
10mm THICGLASS
L7
SSTL METAL FIN
01 SCREENS
GFF FRAMELESS GLASS
GLZ GLASS SCREENS
01 SCREENS
03
GLZ GLZ GLASS SCREENS
GLZ GLASS FINS
03 03
02

STAINLESS STEEL
POSTS AT PANEL
CENTERS

STN STONE
STN STONE
10 COVER
10 COVER
5 4
A91550 A5110
DCM SSTL
DCMTROLLEY
SSTL TROLLEY
02 RAILING. REFER
RAILING
02
TO A-90
ARM
ARM
01
01

Detail 1 Detail 7
Detail sections from MTC-A-51-TB-L_-_-_-__-00-560
The drawings on this page are
7 TYPE 4 & TYPE 4Cindicative. Refer to the architectural 9
drawings for correct setting
SCALE 1:20
out, mounting details and final
NOTE: TYPE 4 HAS OPEN JOINTS BETWEEN
dimensions. NOT
GLASS PANELS. TYPE 4C HAS SILICONE IS IN
JOINTS BETWEEN GLASS PANELS. FOR
Type: REF
L7

Detail 3
L7
Sheet 2/3
Detail section from MTC-A-51-TB-L_-_-_-__-00-566

TYPE 1A
1 Midfield TYPE 1B
Contract: Terminal Building – General Contractor, AUH.06.10.0401 2 Page 89 of 231
Bulletin No.SCALE 1:20
145: Volume 3 of 4 (Rev 07) SCALE 1:20 January 31, 2015

--
A51107
Abu Dhabi Airports Company PJSC Specification, Section 265120
L7

L7

L7

L7

L7

Detail 2
Detail section of glass screen from MTC-A-51-TB-L_-_-_-__-00-567

L7

1. FOR LIGHT FITTING INTEGRATION AND FIXING DETAILS


REFER TO A-94 & A-93 ARCHITECTURAL DRAWINGS AND
CORRIDOR SCREEN STRUCTURE LIGHTING SPECIFICATIONS 265120

2. ARCHITECTURAL BACKGROUNDS ADDED FOR CLARITY

FINISHED FLOOR LEVEL

Detail
2 2
ENLARGED SECTION OF STERILE CORRIDOR
Detail section
SCALE 1:20 of sterile corridor from MTC-A-94-TB-L_-_-0-00-09-003

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

02 31.01.15 BULLETIN 145 L7


01 31.10.14 BULLETIN 120
Sheet 3/3
00 15.07.12 ISSUED FOR CONSTRUCTION

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 ISSUED FOR CONSTRUCTION Page 90 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015

ABU DHABI
AIRPORTS COMPANY
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Canopy recessed linear profile

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 32W/m


Primary luminaire
TECTON LED continuous-row luminaire Sheet aluminium Power factor: > 0.9
construction
TECTON B L1463 material:
47W LED830 WB LDO WH Rated luminous flux (lm): 3,390lm/m
42182141
Finish:
LED continuous-row luminaire Anodised aluminium silver Luminaire efficacy: 106lm/W
Times New Roman
Accessories:
Linear TECTON LED continuous-row luminaire Seecontaining
Notes segment elements, each with Beam / distribution:
11 LEDs; Symmetric, see LDC
Slave luminaire for DALI control
(DALI only) with LED converter. Energy-efficient LED continuous-row luminaire makes environmental and financial sense. Luminaire
Light source type:
efficacy: 105 lm/W.Project 1
Total luminous LED CRI / Colour temperature:
flux of luminaire: 4950 lm. Luminaire with symmetric wide light distribution (wide beam). Colour > 80 / 3,000K
rendering Ra > 80, colour temperature 3000 K. All-in-one approach: lighting batten, lamp and reflector are combined in31.07.2014
one product
Driver
and allow type:
a 100% continuous ribbon of LED Constant gaps. High-quality look in a Colour
light withoutcurrent Variation:
design that matches ≤ 3 SDCM
the trunking. Aluminium
Operator
LED continuous-row luminaire in white, powder-coated finish. Dimming level for DC mode preset to 15%. LED service life lasts 50,000
Drive current or voltage: 700mA Telephone Luminaire Lifetime:
h before luminous flux is reduced to 80 % of the initial value. 100% flexible, tool-free ≥ 50,000 hours
Fax mechanical and electrical installation using CLIX-
technology by means of two side-mounted rotary levers on the TECTON trunking. e-MailNo ultraviolet or infrared radiation. Please order end
Dimming & type: DALI, integral Lifetime Basis:
caps separately. Luminaire wired with halogen-free leads and contains no silicone. Please note: please talk to your adviser if you
L70 / F10 @ Ta 250C
IP: ZUMTOBEL 42182141 IP20
planning to use the luminaire in environments containing chemical pollutants. Dimensions: 1463 x 60 x 70 mm. Weight: 3.25 kg
(STD - Standard) TECTON B L1463 47W LED830 WB LDO WH /
Luminaire Data Sheet
Luminaire distribution curve (LDC)
Luminous emittance 1: Location:

ARUP LIGHTING
See our luminaire catalog for an image of the Departures Hall check-in desks
luminaire.
Security Check Desks

WH 42182141
MARK_UPS
Times New Roman
g segment elements, each with 11 LEDs; Slave luminaire for DALI control
tinuous-row luminaire makes environmental and financial sense. Luminaire
lm. Luminaire with symmetric wide light distribution (wide beam). Colour
approach: lighting batten, lamp and reflector are combined in one product
Notes:
gaps. High-quality look in a design that matches the trunking. Aluminium
nish. Dimming level for DC mode preset to 15%. LED service life lasts 50,000 1. Refer to Section ‘2.0 Products’ of this
ue. 100% flexible, tool-free mechanical and electrical installation using CLIX-
n the TECTON trunking. No ultraviolet or infrared radiation. Please order end specification for additional requirements.
and contains no silicone. Please note: please talk to your adviser if you
chemical pollutants. Dimensions: 1463 x 60 x 70 mm. Weight: 3.25 kg
2. Luminaire to be passively cooled.
ZS_TEC_F_LED_front_lang.jpg 3. Continuous
ZS_TEC_M_B_LED.wmf profiles to be supplied
with all necessary accessories including
Luminaire classification according to CIE: 100 Luminous emittance 1:
Light Distribution
CIE flux code: 67 91 98 100 100
STD - standard
mounting profiles, brackets and end
caps.
h: 100% • Light Distribution: STD - standard
180°
• Light Source: 1 x LED-Z999 / 47.1W 4. To be supplied with a glare limiting
150° 150° diffuse optic.
• Total luminous flux of luminaire: 4950 lm
• Luminaire efficacy: 105 lm/W
• Rated life: 50000h L80 at 25°C 5. Lengths required to be confirmed by
120° 120° • Colour Rendering Index min.: 80 site measurement prior to ordering and
• Colour temperature: 3000 Kelvin coordinated with Architect Engineer.
• Chromaticity tolerance (initial MacAdam): 4
6. Mounting
• Ballast: 1 x 28000134 LCAI 65W 150mA-400mA ECO lp detail to be coordinated with
• Connected Load: 47.1 W Lambda = 0.98 Architect architectural details.
g 90° 450 300 150 ZS_TEC_M_B_LED.wmf 90° • Standby Power: 0.1 W
• Dimming: LDO dimmable to 1% over DALI
STD - standard • Maintenance category: D - Enclosed IP2X

% • Light Distribution: STD - standard


Source: 1 x L8
• Light60° LED-Z999 / 47.1W 60°
• Total luminous flux of luminaire: 4950 lm
• Luminaire efficacy: 105 lm/W
• Rated life: 50000h L80 at 25°C
• Colour Rendering Index min.: 80
• Colour temperature: 30°3000 Kelvin 30°
• Chromaticity tolerance (initial MacAdam): 4

• Ballast: 1 x 28000134 LCAI 65W 150mA-400mA ECO lp C180 | C0
• cd/klm
Connected Load: 47.1 W Lambda = 0.98 C270 | C90
• Standby Power: 0.1 W
D33509AA_TECTON_B_L1463_47W_LED830_WB.ldt
• Dimming: LDO dimmable to 1% over DALI
• Maintenance category: D - Enclosed IP2X

The drawings on this page are


Despite the highest quality standards and careful examination of all components, there may be isolated instances of technology-related failures of individual LEDs during the
specified product lifetime.The failure of 4 LED points causes no functional impairment to the lighting performance of the luminaire and is therefore no reason for complaint indicative. Refer to the architectural
Page 1from the
Luminous flux and connected electrical load are subject to an initial tolerance of up to + / - 10%. Color temperature is subject to a tolerance of up to +/-150 Kelvin
nominal value. drawings for correct setting out,
0
0
mounting details and final dimensions.
dt
We reserve the right to make technical changes without prior notice. 19.08.2014 © Zumtobel - 5 year guarantee when you register at
www.zumtobel.com/guarantee/registration

onents, there may be isolated instances of technology-related failures of individual LEDs during the
impairment to the lighting performance of the luminaire and is therefore no reason for complaint
Type:
nce of up to + / - 10%. Color temperature is subject to a tolerance of up to +/-150 Kelvin from the

L8
8.2014 © Zumtobel - 5 year guarantee when you register at

Detail 9
Sheet 1/2
Detail section of Info Panel from MTC-Q-04-TB-L_-_-_-__-00-508

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 91 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

L17
L8

Detail 5
Detail section through Canopy at Terminal Building from MTC-A-94-TB-L_-_-0-00-09-033

L8

Detail 7
Section through Security Desks from MTC-A-94-TB-L_-_-0-00-09-031

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
L8 dimensions.

Type:

Detail 8
L8
Sheet 2/2
Immigration desk from MTC-A-94-TB-L_-_-0-00-09-033

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 92 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Artikelnummer Art.-No. 13000038
Einheit Unit Stück/piece (pc)

Abu Dhabi Airports Company PJSC


Min. VPE Min. OQ 10 Specification, Section 265120
Halteklammer für VarioLED™ Flex VENUS/PHOBOS/SKYLLA/NIKES SV aus Edelstahl (301/1.4301) (weitere Materialien au
Mounting clip for VarioLED™ Flex VENUS/PHOBOS/SKYLLA/NIKE SV made from stainless steel (3011/1.4301) (other mate
23,5 mm x 12 mm
Luminaire Description: Continuous recessed linear flexible profile

Bezeichnung Description VarioClip TV 30 mm 316L


Manufacturing standard: EN 60 598 Total luminaire wattage (max): 6W/m
Artikelnummer Art.-No. 13000050
Primary luminaire Plastic Power factor: > 0.9
construction material: Einheit Unit
Rated Stück/piece (pc)
luminous flux (lm): 340lm/m
Finish: N/A Min. VPE Min. efficacy:
Luminaire OQ 10
57lm/W
Accessories: Mounting clips Beam / distribution:
Halteklammer Symmetric,TVsee
für VarioLED™ Flex VENUS/PHOBOS/SKYLLA/NIKE LDC(316L/1.4404/V4A) (weitere Materiali
aus Edelstahl
Mounting clip for VarioLED™ Flex VENUS/PHOBOS/SKYLLA/NIKE TV made from stainless steel (316L/1.4404/V4A) (other mat
LED Linear ™Project
Light source – linear
type:
1
lighting
LED 16,5solutions
mm x 21,5 mm CRI / Colour temperature: > 80 / 3,000K
Driver type: Constant Voltage Colour Variation: 11.08.2014
≤ 3 SDCM
Drive current or voltage: 24V Operator Luminaire Lifetime: ≥ 50,000 hours L13b
Telephone Bezeichnung Description VarioClip SV 30 mm 316L
Dimming & type: DALI, remote Fax Lifetime Basis: L70 / F10 @ Ta 25 C 0

VarioLED™ Flex VENUS TV IP67


e-Mail
LED Linear ™ – linear lighting solutions Artikelnummer Art.-No. 13000051
IP: IP67

W824
2.900 K
W827
3.200 K
W830
3.800 K

W835
4.500 K

W840
5.500 K
LED Linear Varioled Flex Venus TV IP67Einheit
W827 / Unit
Luminaire Data Sheet Stück/piece (pc)
Luminaire Min. VPE Min.curve
distribution OQ (LDC) 10Location:
VarioLED™ Flex VENUS TV IP67 Luminous emittance 1:

W824
2.900 K
W827
3.200 K
W830
3.800 K

W835
4.500 K

W840
5.500 K

W850
9.000 K
Halteklammer für VarioLED™ Flex VENUS/PHOBOS/SKYLLA/NIKE SV aus Edelstahl (316L/1.4404/V4A) (weitere Materiali
See our luminaire catalog for an image of the Stairs
luminaire. mounting clip Mounting clip for VarioLED™ Flex VENUS/PHOBOS/SKYLLA/NIKE SV made from stainless steel (316L/1.4404/V4A) (other mat
23,5 mm x 15,5 mm

Bezeichnung Description VarioClip VENUS6TV 50 mm


Watt/meter
6 Watt/meter
L13
Artikelnummer Art.-No. 13000010–01
363 lumen/meter (lm/m)
363 lumen/meter (lm/m)
Einheit L13
! Ra/CRI 85
Unit Stück/piece
Notes: (pc)
L13
Min. VPE Min.
IP67
OQ
specificationTV
AL Halteklammer für VarioLED™ Flex VENUS/PHOBOS/SKYLLA/NIKE
!
101. Refer to Section
Ra/CRI
for(L additional
85 of this
‘2.0 Products’
x H x B) 50 mmrequirements.
x 14,5 mm x 18,5 mm

Abmessungen & LängenL13Dimensions14,5& mm


available length
x 18,5 mm
Aluminum mounting clip for VarioLED™ Flex VENUS/PHOBOS/SKYLLA/NIKE
Rmin = 15 cm 2. Homogeneous, TVdot IP67
(L x Hfree
x W) 50 mm x 14.5 mm x 18.5 mm
illumination
Rmin = 5.9“ throughout the profile length.
110 mm IP67 Steckverbinder (Buchse/Stecker) an den Enden
L13
3. Lengths required to be confirmed by

Abmessungen & Längen Dimensions & available length


110 mm IP67 plug in connector (male/female) on both ends
Luminaire classification according to CIE: 100 Due to missing symmetry properties, no UGR table
L13 Bezeichnung Description
CIE flux code: 43 74 92 100 85 can be displayed for this luminaire.
Avaries
(mm) VarioClip R = 15 cm
site measurement prior to ordering and
VENUS
with SV
min
coordinated 50 mmEngineer.
Architect
16
Artikelnummer Art.-No. 13000011–01Rmin
4. Detail to be = 5.9“ with Architect
coordinated
110 mm IP67 Steckverbinder (Buchse/Stecker) an den Enden architectural details.
Einheit Unit Stück/piece (pc)
110 mm IP67 plug in connector (male/female) on both ends
15

5. Mock-up required to confirm design


Biegerichtung Bend direction Min. VPETc Min. OQ 10intent.
A (mm)
AL Halteklammer für VarioLED™ Flex VENUS/PHOBOS/SKYLLA/NIKE
+ (L x H x B) 50 mm x 19,5 mm x 12 mm
16 Aluminum mounting clip for VarioLED™ Flex VENUS/PHOBOS/SKYLLA/NIKE SV (L x H x W) 50 mm x 19.5 mm x 12 mm

Biegerichtung Bend direction 234 19,5 mm x 12 mm
Toleranz +/- 5 mm Tolerance +/- 5 mm Tc-Punkt: Rückseite des Moduls Tc-point: Rear side of module
15

A = N x 62,5 + 26; N = 1 … 80; Amin = 1 x 62,5 + 26 = 88,5; Amax = 80 x 62,5 + 26 = 5.026


L13b
Biegerichtung Bend direction
Bestellnummer Order Code: VarioLED Flex VENUS Wxxx/A TV IP67
Bestellnummer Tc

Elektrische & Optische Betriebsdaten Electrical & optical data


Biegerichtung Bend direction L13

Abmessungen Dimensions A x 16 mm x 15 mm L80,


Toleranz +/- 5 mm
Leistung Power Tolerance +/- 5 mm 6 W/meter 32.000 hrs Tc-Punkt: Rückseite des Moduls Tc-point: Rear side of module
The drawings on this page are
Spannung Voltage (V) 24 Volt (23 Vmin, 25 Vmax)
L13
indicative. Refer to the architectural
ATemperatur
= N x 62,5 + 26; N = 1 … 80; Amin = 1 x 62,5
Temperature tcmin+=26 = 88,5;
–25°C, Amax = 80 x 62,5 + 26 = 5.026
tcmax = +60°C Page 1 drawings for correct setting out,
Lagertemp. Storage temp. tmin = –30°C, tmax = +85°C mounting details and final dimensions.
Außentemperatur Ambient temp. tamin > –25°C, tamax = +45°C
Bestellnummer Order Code: VarioLED Flex VENUS Wxxx/A TV IP67
Bestellnummer
L13
Type: Nähere Erläuterungen zu Änderungen,  
VarioLED™ Flex lumen/meter Ra Farbtemperatur
VENUS TV IP67 (lm/m) CRI Color Temperature (K) Grenzwerten und Schwankungen im 
Herstellungs prozess finden Sie im LED 

L13
W824 274 80 2.900
Elektrische
W827
Detail 5
& Optische
336 Betriebsdaten
85 3.200 Electrical & optical data Linear™ Systemkatalog, Seite 532.
For more details regarding catalogue 
W830 340 85 3.800 changes, min and max data sheet values 
Detail section of stone treads from MTC-A-07-TB-L_-_-_-__-00-551 and production tolerances see the LED 
W835 340 85 4.500
Abmessungen Dimensions A x 16 mm x 15 mm Linear™ system catalogue, page 533.
L80,
W840 350 85 5.500
Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 32.000 hrs Page 93 of 231
Leistung
W850 Power 363 85
Bulletin No. 145: Volume 3 of 4 (Rev 07)
9.000 6 W/meter
January 31, 2015
Spannung Voltage (V) 24 Volt (23 Vmin, 25 Vmax)
194 Sicherheits- und Montagehinweise: LED Linear™ Systemkatalog, Seite 534 ff. Safety and assembly information: LED Linear™ system catalogue, page 536 ff.
Temperatur Temperature tcmin = –25°C, tcmax = +60°C
Abu Dhabi Airports Company PJSC Specification, Section 265120

LED Linear ™ – Vario


Luminaire Description: Continuous integrated linear profile

Manufacturing standard: VarioLED™


EN 60 598 HYDRA HD15
TotalIP67
luminaire wattage (max): 15W/m
Primary luminaire LED strip mounted on Power factor: > 0.9
construction material: extruded aluminium profile Rated luminous flux
Wasser- und(lm): 1,265lm/m
UV-geschützte Linearleuchte
Finish: N/A im Aluminiumprofil in84lm/W
Luminaire efficacy: bis zu 2 m Länge im
Polyurethanverguss mit 110 mm IP67 Steck-
Accessories: See Notes Beam / distribution:
verbinder an beidenSymmetric,
Enden. see LDC
Light source type: LED CRILED
/ Colour temperature:
Linear ™Up–toVarioLED ™> 80 / 3,000K
2 m length, water & UV resistant
Driver type: Project 1 Constant Voltage Colour Variation:
LED Luminaire ≤ 3 SDCM
10.08.2014 polyurethane en-
with LED Linear ™ – VarioL
Drive current or voltage: 24V Operator Luminaire Lifetime: ≥ 50,000
capsulation in AL profile and 110 mmhours
Telephone IP67 plug in connectors on both ends.
Dimming & type: DALI, remote Lifetime Basis: L70 / F10 @ Ta 250C
YDRA HD15 IP67
Fax
e-Mail

IP: IP67
VarioLED™ HYDRA HD15 IP67 Wasser- und UV-geschützte Linearleuchte
LED Linear GmbH / Luminaire Data Sheet

Abmessungen & Längen Dimensions & available length


Luminaire
im Aluminiumprofil in bis zu 2 m Länge im Luminous distribution
emittance 1: curve (LDC) Location:
Polyurethanverguss mit 110 mm IP67 Steck-
See our luminaire catalog for an image of the
luminaire. verbinder an beiden Enden.
18
Wasser- und UV-geschützte Linearleuchte
4,5 Under-shelf
Tc-Punkt: light for desks
Gesamte Profilrückseite
18
im Aluminiumprofil in bis zu 2 m Länge im Entire Al-profile rear side
4,5

15,5 Tc-point:
Up to 2 m length, water & UV resistant 17,5
Polyurethanverguss mit 110 mm IP67 Steck-
LED Luminaire with polyurethane en-
15,5

17,5

A mm
19 verbinder an beiden Enden.
capsulation in AL profile and 110 mm
IP67 plug in connectors on both ends.
19 Up to 2 m length, water & UV resistant
LED Luminaire with polyurethane en- Notes:
capsulation in AL profile and 110 mm 1. ReferTc to Section ‘2.0 Products’ of this
Längen Dimensions & available length IP67 plug in connectors on both ends. specification for additional requirements.
2. Linear LED strip to be mounted on +
18 a suitable profile to provide sufficient
4,5

Tc-Punkt: Gesamte Profilrückseite heat dissipation per manufacturer’s –


Tc-point:
Luminaire classification according Entire
to CIE: 100 Al-profile rear side
Due to missing symmetry properties, no UGR table recommendations.
15,5

A = 100
N x 62,5
115 + 19; N = 1 … 31; Amin = 1 can
x 62,5
be +displayed
19 = 81,5;for
Amax = luminaire.
31 x 62,5 + 19 = 1.956,5 Übersicht VarioContour IP67 ab Seite 474.
17,5

CIE flux code: 46 78 96 this


3. Continuous
Overview VarioContourprofiles
IP67 fromtopage
be 474.
supplied
Abmessungen & Längen Dimensions & available length with all necessary accessories including
17,5

A mm varies
19 mounting profiles, brackets and end
18 Bestellnummer Order Code: VarioLED HYDRA HD15 Wxxx/A IP67 caps.
4,5

Tc-Punkt: Gesamte Profilrückseite


4. Lengths required to be confirmed by
18
4,5

Tc-point: Entire Al-profile


siterear side
measurement prior to ordering and
Elektrische &TcOptische Betriebsdaten Electrical & optical data with Architect Engineer.
15,5

17,5

coordinated
5. When required, profile sections to be
VarioLED lumen/meter Farbtemperatur Es gelten die selben Daten wie für VarioLED™ Flex HYDRA HD15 mit
15,5

17,5

A mm cut to match required radius.


19 HYDRA HD15 IP67 (lm/m) Color Temperature (K) folgenden Ausnahmen: 30% Lichtverlust und Farbverschiebung im
+ 6. Mock-ups
Vergleich required toLED
zum nicht vergossenen confirm
Strip. design
W824 877 2.500 intent.
– Nähere Erläuterung zu den technischen Daten des PU-Schutzes
W827 1.201 3.300
19 im LED Linear™ Systemkatalog, Seite 584.
Amin = 1 x 62,5 + 19 = 81,5; Amax = 31 x 62,5 + 19 = 1.956,5W830 Übersicht VarioContour IP67 ab Seite 474.
1.282 4.000
Overview VarioContour IP67 from page 474. Same data as for VarioLED™ Flex HYDRA HD15 apply, except: 30%
W835 1.350 4.600 light loss and color shift compared to non encapsulated LED strip.
Tc
W840
HD15 Wxxx/A IP67 1.382
Order Code: VarioLED HYDRA W850 1.451
6.300
10.000
More details regarding the PU-protection in the LED Linear™ system
catalogue, page 584.
L13c
+
ische Betriebsdaten Electrical & optical data The drawings on this page are
Bitte sprechen Sie uns an für kundenspezifische Anpassungen,
indicative. Refer to the architectural –
wie z. drawings
B. Kabellängen und Stecker.
for correct setting out,
Page 1
lumen/meter Farbtemperatur Es gelten die selben Daten wieProfile
für VarioLED™ Flexcut
sections HYDRA HD15 mit
to match radius Pleasemounting
A = N x 62,5 + 19; N = 1 … 31; Amin = 1 x 62,5 + 19 = 81,5; Amax = 31 x 62,5 + 19 = 1.956,5 Übersicht VarioContour ask IP67forab Seite 474.
details
custom and adaptions
specific final dimensions.
like cable length and plu
(lm/m) Color Temperature (K) Zubehör Accessories
folgenden Ausnahmen: 30% Lichtverlust und Farbverschiebung im
Vergleich zum nicht vergossenen LED Strip. Overview VarioContour IP67 from page 474.
877 2.500
Nähere Erläuterung
erforderlich requiredzu den technischenoptional
Daten desoptional
PU-Schutzes Type:
1.201 3.300
Bestellnummer
1.282
Order Code: VarioLED HYDRA HD15 Wxxx/A IP67
4.000
im LED Linear™ Systemkatalog, Seite 584.

Same data as for VarioLED™ Flex HYDRA HD15 apply, except: 30%
1.350 4.600 light loss and color shift compared to non encapsulated LED strip. L13c
Details siehe Seite 456 ff. Details on page
1.382Detail 3 6.300
Elektrische & Optische Betriebsdaten Electrical & optical data
1.451
Detail section of check-in desk from
10.000
Moreund
Sicherheits-
details regarding the PU-protection in the LED Linear™ system
Montagehinweise: LED Linear™ Systemkatalog, Seite 534 ff. Safety and assembly information: LED Linear™ system catalogue,Sheet
MTC-Q-04-TB-L_-_-_-__-00-503
catalogue, page 584.
page 5361/2
ff.

Contract: Midfield Terminal


VarioLED Building – GeneralFarbtemperatur
lumen/meter Contractor, AUH.06.10.0401 Es gelten die selben Daten wie für VarioLED™Page
Flex 94 of 231
HYDRA HD15 mit
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
HYDRA HD15 IP67 (lm/m) Bitte sprechen
ColorSieTemperature (K)
uns an für kundenspezifische folgenden Ausnahmen: 30% Lichtverlust und Farbverschiebung im
Anpassungen,
wie z. B. Kabellängen und Stecker. Vergleich zum nicht vergossenen LED Strip.
W824 877 2.500
Please ask for custom specific adaptions like cable ARUP
length
Nähere LIGHTING
and plugs.
Erläuterung zu den technischen Daten des PU-Schutzes
Abu Dhabi Airports Company PJSC Specification, Section 265120

L13c

Detail 7
Detail of Staff desk at Terminal Building from MTC-A-94-TB-L_-_-0-00-09-033

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

L13c
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 95 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Continuous integrated linear profile

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 15W/m


Primary luminaire LED strip mounted on Power factor: > 0.9
construction material: extruded aluminium profile Rated luminous flux (lm): 1,930lm/m
Finish: N/A Luminaire efficacy: 129lm/W
Accessories: See Notes Beam / distribution: Symmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 3,000K
ghting solutions
Driver type: Project 1
Constant Voltage Colour Variation: 10.08.2014
≤ 3 SDCM
Drive current or voltage: 24V Operator Luminaire Lifetime: ≥ 50,000 hours
Telephone
Dimming & type: DALI, remote Fax
e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: LED Linear ™ – linear lighting
IP20solutions
ex HYDRA HD15 LED Linear GmbH / Luminaire Data Sheet

W824
2.400 K
W827
2.700 K
W830
3.000 K
W835
3.500 K
W840
4.000 K

W850
5.000 K
Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
VarioLED™ Flex HYDRA HD15

W824
2.400 K
W827
2.700 K
W830
3.000 K
W835
3.500 K
W840
4.000 K

W850
5.000 K
See our luminaire catalog for an image of the Arrival Lobby Lighting Lozenges
luminaire.
Screening Lighting Lozenges

15,4 Watt/meter
15,4 Watt/meter
2.182 lumen/meter (lm/m) Notes:
2.182 lumen/meter (lm/m)
! One Bin Only: 3 MacAdam
1. Refer to Section ‘2.0 Products’ of this

Watt
! One Bin Only: 3 85
Ra/CRI MacAdam
specification for additional requirements.
2. Linear LED strip to be mounted on

att
! 142 Lumen/ Ra/CRI 85
a suitable profile to provide sufficient

umen/W
heat dissipation per manufacturer’s
& Maße !
AufbauLuminaire
CIE flux code:
L according
2Assembly
14classification & measurement
46 78 96 100 115

62,5 mm (64 x)
to CIE: 100 Due to missing symmetry properties, no UGR table
can be displayed for this luminaire.
recommendations.
3. Continuous profiles to be supplied
with all necessary accessories including
embly & measurement mounting profiles, covers, brackets and
end caps.
+ 24 V 9,5 mm 4. Mock-up sample to be provided.
x) GND Final selection of optical lens/cover to be
confirmed during site mock-up.
4,45 mm 8,9 mm 8,9 mm 8,9 mm 8,9 mm 8,9 mm 8,9 mm 4,45 mm 5. Lengths required to be confirmed by
site measurement prior to ordering and
2,1 mm coordinated with Architect Engineer.
9,5 mm
6. When required, profile sections to be
Elektrische & Optische Betriebsdaten Electrical & optical data cut to match required radius.
7. Mock-ups required to confirm design
mm 8,9 mm 8,9 mm 4,45 mm intent.
Keine zusätzliche Kühlung
Abmessungen Dimensions 4.000 mm x 9,5 mm x 2,1 mm
über AL-Profil notwendig.
Teilungsmaß Step length 62,5 mm/7 LED
2,1 mm No need for additional heat
Leistung Power 61,44 W/15,4 Watt/meter sinking on AL profile.
Effizienz Efficacy bis zu/up to 142 lumen/Watt

he Betriebsdaten Electrical
Spannung Voltage (V)
& optical
Anzahl LED Number LED
data
448 LED, 8,9 mm LED pitch
24 Volt (23 V , 25 V )
Profile sections cut to match radius min max
The drawings on this page are
indicative. Refer to the architectural
Page 1 drawings for correct setting out,
Strom Current 2,56 A/40 mA per step L80, mounting details and final dimensions.
> 37.000 hrs
Temperatur Temperature tcmin = –25°C, tcmax = +85°C
Keine zusätzliche Kühlung
4.000 mm x 9,5 mm x 2,1 mmt
Lagertemp. Storage temp. = –30°C, tmax = +85°Cüber AL-Profil notwendig.
min

62,5Ambient
Außentemperatur mm/7temp.
LED tamin = –25°C, tamax = +45°C Type:
No need for additional heat
61,44 W/15,4 Watt/meter sinking on AL profile.
VarioLED™ Flex Art. # Lumen/meter Ra
HYDRA HD15 bis zu/up to 142 lumen/Watt
(lm/m) CRI
R9
CRI
Farbtemperatur
Color Temperature (K) L14
W824 10385 Nähere Erläuterungen zu Änderungen, Grenz­ Sheet 1/2
448 LED, 8,9 mm 1.320
LED pitch 85 30 2.400
werten und Schwankungen im Herstellungs­
W827 10384 1.807 85 20 2.700 prozess finden Sie im LED Linear™ System­
24Terminal
W830Midfield
Contract: Volt10383
(23Building
Vmin, 251.929
–Vmax) 85Contractor,
General 20 3.000
AUH.06.10.0401 katalog, Seite 532. Page 96 of 231
BulletinW835
No. 145:2,56
Volume
A/40 3 mA
10382of 4per
(Rev 07)
step
2.030 85 20 3.500 For more details regarding catalogue January 31, 2015
L80, changes, min and max data sheet values
W840 10381 2.079 83 20 >4.000
37.000 hrs
W850
tcmin = –25°C, tcmax = +85°C
10380 2.182 83 10 5.000
and production tolerances see the
LED Linear™ system catalogue, page 533.
Abu Dhabi Airports Company PJSC Specification, Section 265120

D9b D9b D9b D9b D9b

L14

L14

Detail plans of Lighting Lozenge from MTC-A-93-TB-L_-_-_-__-00-531


L14
D9b D9b D9b
D9b D9b
L14

03

ARUP LIGHTING
D9b D9b MARK_UPS
D9b D9b D9b L14

L14
L14 Rev1
SFS
01

1 PLAN & RCP - ARRIVALS IMMIGRATION HALL, L0.1 5 PLAN & RCP - PROCESSOR ARRIVAL

Detail 1
SCALE 1:20 SCALE 1:20

3,4 L14
7
L14

L14
L14
ARM
03
01 solid in orde
ARM
not to cast
01 shadow
solid in order
L14 not to cast
D9
D9b

shadow
L14 L14
L14
4
A93530
L14 SFS D9b D9b L14
D9b
4 Detail 5 01
D9b D9b
SIM
03
A93530 6 SECTION - PROCESSOR ARR
5 Detail
SIM 03
plans
PLAN & RCP of Lighting
- PROCESSOR Lozenge
ARRIVALS, L0.0 from MTC-A-93-TB-L_-_-_-__-00-531 SCALE 1:20
SCALE 1:20 03

2 SECTION - ARRIVALS IMMIGRATION HALL, L0.1


L14 L14
SCALE 1:20
7 SFS
01 ARM
01

solid in order
ARM not to cast 10
01
shadow A93530
ARM The drawings on this page are ARM
01
indicative. Refer to the architectural 01
03
drawings for correct setting out,
L14 L14 L14
mounting details and final dimensions.
0

03 SFS 4
SFS A93530
6 SECTION
01 - PROCESSOR ARRIVALS, L0.0
SCALE 1:20
01
Type: SIM 03

L14

L14
L14 L14

L14
D9b
ARM
01

10
D9b Sheet
7 2/2
SECTION - PROCESSOR A
SCALE 1:10
03 31.01.15
SFSBULLETIN 145
A93530
02 31.10.1401 BULLETIN 120
4 01 25.07.14 BULLETIN 101
A93530
ARM 00 15.07.12 ISSUED FOR CONSTRUCTION
Page 97 of 231
L14
Contract:
SIM Midfield Terminal Building – General Contractor, AUH.06.10.0401
03 01

Bulletin
3
No. 145: Volume 3 of 4 (Rev 07)
SECTION - ARRIVALS IMMIGRATION HALL, L0.1 FLAT CEILING ISSUED FOR CONSTRUCTION January 31, 2015
SCALE 1:10

ABU DHABI 4 SECTION - ARRIVALS IMMIGRATION HALL, L0.1 SLOPED CEILING


4
AIRPORTS COMPANY SCALE 1:10
A93530 ABU DHABI AIRPORTS COMPANY
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Wall recessed linear profile

Manufacturing standard: EN 60 598 Lamp Type: T5 - High Output, Long Life


Primary luminaire Extruded aluminium Lamp Wattage: 20W, 36W, 50W, 73W
Project 1
construction material: Lamp Manufacturer: 12.08.2014 -
Finish: See Notes Operator Beam / distribution: Asymmetric, see LDC
Telephone
Accessories: N/A e-Mail CRI / Colour temperature: > 80 / 4,000K
Fax

IP: IP20 Ballast/Transformer: DALI, integral


Intralux Australia P Cat. No. FWT5154. Intralux 54W Flare T5 wall washer. / Luminaire
Lamp life: ≥ 48,000 hours
Data Sheet

Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
See our luminaire catalog for an image of the Transit Area infill roof
luminaire.

UP
Notes:
1. Refer to Section ‘2.0 Products’ of this
Luminaire classification according to CIE: 100 Due to missing symmetry properties, no UGR table
CIE flux code: 37 74 96 100 61 can be displayed for this luminaire.
specification for additional requirements.
2. To be supplied with specular reflector.
3. Lamp wattages indicated (20W,
36W, 50W, 73W) refer to different types
of lamps to be combined to form a
continuous line. Lengths required to be
confirmed by site measurement prior to
56

continuous, final length


1175 to match location ordering and coordinated with Architect
466666666666666663 Engineer.
4. Mounting detail to Architect’s
specification.
5. Mock-up required to confirm design
intent.
6. Fixture to be powder coated (RAL
860M).

Page 1

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.

L15
L15 L15 Type:
L15 L15
D9b
L15

Detail 1
D9b
L15 D9b
Sheet 1/2
Detail section of Transit Area infill ceiling from MTC-A-94-TB-L4-0-0-00-09-029

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 98 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120 1
3

L15 L15

L15 L15

D9b

D9b

Beam beyond

INFILL ROOF NORTH


Detail 22 SECTION
SCALE 1:50
Detail section of Transit Area infill ceiling from MTC-A-41-TB-L4-0-5-12-00-510

20
30

40
MPC
11D

MAIN STRUCTURE
678

GYB
01

GYB
01 04 31.01.15 BULLETIN 145
03 31.10.14 BULLETIN 120
02 25.07.14 BULLETIN 101
01 26.10.12 BULLETIN 03
00 15.07.12 ISSUED FOR CONSTRUCTION

INFILL ROOF NORTH


ISSUED FOR CONSTRUCTIO
4 DETAIL
GRID
SCALE 1:5

ABU DH
2000 1000
AIRPORTS CO
ABU DHABI AIRPORTS COMPANY

Kohn Pedersen Fox Associates


(International) PA
Architects and Planning Consultants

14.75° 7a Langley Street


London WC2H 9JA
England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com

Outline
5000 2500 of ceiling
630
= = =
The drawings on this page are
3° indicative. Refer to the architectural
2 x L15
2 x L15 drawings for correctABUsetting
DHABI INTERNATIONAL
out, mounting details and final TERMINAL COMP
1100

D9b
D9b MIDFIELD
04
2850 dimensions.
04
GYB GYB
YB
1 06 GYB 01 INFILL ROOF CEILING NORTH
01 Type: TYPICAL BAY
PANEL LAYOUT
GYB - 06
L15
MTC A 41 TB __ L4.0 5.12
GYB - 01
KPF MC Sheet 2/2
KF JH

WB

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 99 of 231


2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights

Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015


Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Wall mounted adjustable linear profile


nano linernano
allegro
liner
ac allegro
xb ac xb Dimensions
Dimensions
Manufacturing standard: EN 60 598 Total luminaire wattage (max): 36W/m
Primary luminaire Extruded aluminium Power factor: > 0.9
chnical drawing
technical drawing
construction material: Rated luminous flux (lm): 2,040lm/m
Finish: Anodised aluminium silver Luminaire efficacy: 57lm/W
Accessories: Mounting bracket Beam / distribution: Asymmetric, see LDC
Light source type:
Project
309mm, 1 309mm,
611mm, 912mm, 611mm,LED
1214mm912mm,
/ 12”, 24”,
1214mm
36”, 48”
/ 12”, 24”, 36”, 48” CRI / Colour temperature: > 80 / 3,000K
Driver type: Constant current Colour Variation: 02.04.2014
≤ 3 SDCM
Operator
Drive current or voltage: 700mA Telephone Luminaire Lifetime:
Fax
≥ 50,000 hours
Dimming & type: DALI, Integral e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: IP66
Traxon Technologies Limited - Nanoliner Allegro AC XB36 120V 3000K 50x10
Nanoliner Allegro AC XB36 120V 3000K 50x10 / Luminaire Data Sheet

Luminaire distribution curve (LDC)


Luminous emittance 1: Location:
See our luminaire catalog for an image of the Internal buildings facade
luminaire.

258mm, 404mm, 258mm,


554mm, 404mm,
704mm /554mm,
10”, 16”,704mm
22”, 28”
/ 10”, 16”, 22”, 28”

16mm/0.63” 16mm/0.63”

6.2mm/0.24” 6.2mm/0.24” ARUP Notes:


LIGHTING
MARK_UPS
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Luminaire to be passively cooled.
3. Lengths required to be confirmed by
site measurement prior to ordering and
Luminaire classification according to CIE: 100 Luminous emittance 1: coordinated with Architect Engineer.
CIE flux code: 96 99 100 100 106
42mm/1.7” 42mm/1.7”
±90° ±90°

Lock screw Lock screwLock screw Lock screw


78mm/3”

78mm/3”

Pin 1: L (AC) Pin 1: L (AC)

Pin 2: N (AC) Pin 2: N (AC)

w.traxontechnologies.com
www.traxontechnologies.com
raxon technologies
©2014 traxon
all rights
technologies
reserved.all
traxon™,
rights reserved.
tx connect ®, luxiled™
traxon™, tx connect ®, luxiled™
are trademarks of traxon
are trademarks
technologies.
of traxon
u.s. patents,
technologies.
e.u. patents,
u.s. patents,
japan e.u. patents, japan
s, other patents
patents,
pending.
other
specifications
patents pending.
are subject
specifications
to change
arewithout
subject notice.
to change without notice.

01/14 v1.0 01/14 v1.0


The drawings on this page are
Page 1
indicative. Refer to the architectural
drawings for correct setting out,
L16
mounting details and final dimensions.

Type:

L16
Sheet 1/2
Detail section of internal buildings from MTC-A-72-TB-L_-_-_-__-00-651

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 100 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

L16

Detail 16
Section through Internal Building facade from MTC-A-94-TB-L_-_-0-00-09-040

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

L16
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 101 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Staggered fluorescent luminaire

Manufacturing standard: EN 60 598 Lamp Type: T5 - High Efficiency, Long Life


Primary luminaire Sheet aluminium Lamp Wattage: 13W, 19W, 25W, 32W
constructionProject
material:
1
Lamp Manufacturer: -
Finish: See Notes Beam / distribution: 13.08.2014 Symmetric, see LDC
Accessories: N/A Operator
Telephone CRI / Colour temperature: > 80 / 3,000K
Fax
IP: IP20 e-Mail Ballast/Transformer: DALI, integral
Lamp life: ≥ 48,000 hours
Thorn 96211394 ARROSLM 1x21W L840 [STD] / Luminaire Data Sheet
patent no. US 6,431,726 B1

Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
BFL281-S
patent no. US 6,431,726 B1

Welcomerstype:
Hall
Departures Hall
BFL281-S
LINEAR T5 FLUORESCENT type:
Passenger Lifts
Flip and Slide adjustable stagger T5 fluorescent
LINEAR T5 FLUORESCENT Arrivals Wallfixture
patent no. US 6,431,726 B1

Flip and Slide adjustable stagger T5 fluorescentInternal Buildings facade


SPECIFICATIONS | œ Fully assembled housing is formed fixture
and welded, 20 ga. steel,
BFL281-S
SPECIFICATIONS | œ
chemically treated to
Fully assembled housing is formed
Pier Utility
resist corrosion
type:
and
andWalls
welded,
enhance paint
20 ga. steel,
adhesion
LINEAR T5 FLUORESCENT chemically treated to resist corrosion and enhance paint T5
œ Standard finish is high reflectance white powder coat,
Flip and Slide adjustable adhesion stagger T5 fluorescent fixture
applied post production T5
SPECIFICATIONS | œ Fully assembled housing is formed and welded, 20 ga.Notes:
œ Standard finish is high reflectance white steel,powder coat,

a rc hi t ec t ur a l L I GH TI NG
œ Knock-outs accept standard electrical fittings (by others)
applied
chemically treated to post
resist production
corrosion and enhance paint
œ Rotational locking lamp holders 1. Refer to Section ‘2.0 Products’ of this
adhesion

a rc hi t ec t ur a l L I GH TI NG
Luminaire classification according to CIE: 74 Luminousœ emittance
Knock-outs 1: accept standard electrical fittings (by for
specification others)
additional requirements.
CIE flux code: 32 60 83 74 99 T5
œ Standard finish Available
œ is high for two
reflectance whiteT5 14W,coat,
powder 21W, 28W, 35 and high output
Slim section batten luminaire for 1 x 21W T16 lamp. electronic - fixed output
œ Rotational locking lamp holders
applied post production
2. Lamp wattages indicated (13W,
circuit. Three position lampholder gives maximum mounting flexibility. Body 24W, 39W, 54W, 80W linear fluorescent 19W, 25W,lamps 32W) refer to different types
steel with white finish
œ Available for two T5 14W, 21W, 28W, 35 and high output

a rchi t ect ur a l LI G H TI N G
œ Knock-outs accept standard electrical fittings (by others)
of lamps to be combined to form a
37mm
Dimensions: 872 x 38 x 65 mm œ Adjustable lamp overlap
Total power: 23 W 1 7/16" 24W, 39W,
œ Rotational locking 54W, 80W linear fluorescent
lamp holders lamps line. Lengths required to be
continuous
Weight: 0.85 kg
œ Standard Universal voltage electronic confirmed highbypower factor
site measurement prior to
œ forAdjustable
œ Available two T5 14W,lamp 21W, overlap
28W, 35 and high output
1 7/16" ballast is pre-wired
24W, 39W, 54W, 80W linear fluorescent lamps to the lamp ordering
holders and coordinated with Architect
œ Standard Universal voltage electronic Engineer.
high power factor
œ Adjustable lamp Dimming option available (consult factory for availability
œ overlap
1 7/16" ballast is pre-wired to the lamp holders 3. Fixture to be powder coated (RAL
œ Standard Universaland system
voltage compatibility)
electronic high power factor
Dimming option available (consult factory 9016). for availability
ballast œis pre-wired to the lamp holders
253mm
1/16" œ UL and ULC listed for dry and damp locations
œ Dimming optionand system
available compatibility)
(consult factory for availability
and system œ May be used in conjunction with BFL281 single lamp fixture
compatibility)
2 1/16" œ UL and ULC listed for dry and damp locations
32mm
1 1/4"
2 1/16" œ UL and ULC listedto forterminate
dry and damp runslocations
œ May be used in conjunction with BFL281 single lamp fixture
œ May be used œ IBEW manufactured
in conjunction with BFL281 singleand lamp
labeled
fixture
1 1/4" 1/4" to terminate runs
1 to terminate runsœ Made in the U.S.A.
œ IBEW NOTE:
œ IBEW manufactured manufactured
and labeled and labeled
72mm
2 13/16" Includes program rapid start ballast.
œ Made in œ theMade
U.S.A.in the U.S.A.
" " NOTE: Includes program
NOTE: rapid start
Includes ballast.
program rapid start ballast.
2213/16
13/16

overlap adjustable
overlap adjustable
overlap adjustable Page 1

fixture #1 fixture #2
fixture #1 fixture #2
The drawings on this page are
fixture #1 fixture #2 indicative. Refer to the architectural
drawings for correct setting out,
SPECIFICATION / ORDER FORMATFORMAT DIMENSIONAL INFO.
mounting details and final dimensions.
SPECIFICATION / ORDER DIMENSIONAL INFO.
model no. voltage wiring method options lamp min. - max. length
SPECIFICATION
model no. / ORDER FORMAT wiring method
voltage options DIMENSIONAL
lamp INFO. min. - max. length
BFL281-S-14 /UNV /RS Dimming - (consult factory) 2 x 14w T5 Type:
*32-3/8" - 42-1/8"
modelBFL281-S-14
no.
BFL281-S-21 /UNV
voltage wiring/RS
method Dimming
options
/CU BFL281-S
- custom - (consult factory)2 x 21w T5
finish (consult factory) 2 x 14w
lamp52-1/2" T5 min. - max.
- 64-1/2" *32-3/8"
length- 42-1/8"

Dimming BFL281-S
BFL281-S-21 /CU - custom finish (consult 2 x- 21w
88" T5 52-1/2" - 64-1/2"
L17
BFL281-S-28 2 x 28w T5
factory) 76"
BFL281-S-14 /UNV /RS - (consult factory) 2 x 14w T5 *32-3/8" - 42-1/8"
BFL281-S-35
BFL281-S-28 2 x 35w T5 100-3/4" -
2 x 28w T5112-5/8" 76" - 88"
BFL281-S-21 /CU BFL281-S
- custom finish (consult factory) 2 x 21w T5 52-1/2" - 64-1/2"
100-3/4" - 112-5/8" Sheet 1/5
BFL281-S-24 2 x 24w T5 HO *32-3/8" - 41-7/8"
BFL281-S-35 2 x 35w T5
BFL281-S-28
BFL281-S-39 2 x 39w T5 HO2 x 28w T5 - 64-1/2" 76" - 88"
52-1/2"
BFL281-S-24 2 x 24w T5 HO *32-3/8" - 41-7/8"
BFL281-S-35
BFL281-S-54 2 x 54w T5 HO2 x 35w 76" -T5
88" 100-3/4" - 112-5/8"
Contract: Midfield
BFL281-S-39
Terminal Building – General Contractor, AUH.06.10.0401 2 x 39w- T5 HO
Page 102 of 231
52-1/2" - 64-1/2"
BFL281-S-80
BFL281-S-24 2 x 80w T5 HO2 x 24w 100-7/8"
T5 HO112-7/8"*32-3/8" - 41-7/8" January 31, 2015
Bulletin No. 145: Volume 3 of 4 (Rev 07)
BFL281-S-54 2 x 54w T5 HO 76" - 88"
BFL281-S-39 2 x 39w T5 HO 52-1/2" - 64-1/2"
08.2012

BFL281-S-80 2 x 80w T5 HO 100-7/8" - 112-7/8"


BFL281-S-54 2 x 54w T5 HO 76" - 88"
*NOTE: Some ballasts affect adjustability of this fixture length. (consult factory for overlap capability)
2
Abu Dhabi Airports Company PJSC Specification, Section 265120

XD1d XD1d XD1d


XD1d

L17 D12 D12


L17
L17 L17 L17

U3
U3 U3 U3 U3
U3

Section detail of entrance doors from MTC-A-94-TB-L_-_-0-00-09-038

L17 L17 L17 L17


XD1d XD1d XD1d

L17 L17

U3 U3 U3 U3

Detail 3
Section detail of entrance doors from MTC-A-94-TB-L_-_-0-00-09-038
L2b L2b

L17

7 L17 L17
L17
L17

7 L17 L17 L17


7 L17 L17 L17

7 L17
L17
L17 L17 L17
L17 L17
L17

L2b
L2b L2b

The drawings on this page are


L17 L2b
L2b L2b L17
indicative. Refer to the architectural
drawings for correct setting out,
L2d

ARUP LIGHTING
mounting details and final dimensions.
MARK_UPS
L17 Rev2 L2b
Type:

L17
Detail 1 Detail 3 Sheet 2/5
Detail elevation and section of vertical circulation passenger lift from MTC-A-94-TB-L_-_-0-00-07-004
L17 L17 L17 L17 L2b
Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 103 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07)
L17 L2d
January 31, 2015
L17 L17
L2b
L4g

Abu Dhabi Airports Company PJSC Specification, Section 265120

GBY
01

ARUP LIGHTING
MARK_UPS
translucent
cover by others

L17
Rev1
L17
L4g

300

LEVEL 3.0 AND ABOVE


Detail 6
775

3 WINDOW - PLAN
Section of Pier Utility Wall OPAL
from MTC-A-72-TB-L_-_-_-__-00-651
DIFFUSER MTC-A-52-TB-L2-0-_-__-00-510
SCALE 1:10

GLZ

300
21
L17

CFM
300

300
01
ARM
300 18
INS
L1709 L17
BOVE LEVEL 3.0 AND ABOVE LEVEL 3.0 AND ABOVE
ECTION 2 LIGHTBOX - SECTION 5 JOINT BETWEEN WINDOWS - PLAN 6
SCALE 1:10 SCALE 1:10

Detail 2
Section of Office internal facade from MTC-A-94-TB-__-L_-_-5-31-00-025
775

300

300 300
300

LEVEL 3.0 AND ABOVE LEVEL 2.0 AND 2.1 LEVEL 3.0 AND ABOV
775

3 WINDOW - PLAN 10 WINDOW - PLAN 4 LIGHTBOX - PLA


775

FFUSER
SCALE 1:10 SCALE 1:10 SCALE 1:10
OPAL DIFFUSER

GLZ The drawings on this page are


300

indicative. Refer to the architectural


300

L17
21
L17 drawings for correct setting out,
mounting details and final dimensions.
300

300 300
Type:
300

01
300
ARM
18

Detail 2
INS
LEVEL 3.0 AND ABOVE
09
LIGHTBOX - SECTION Detail 9 5
LEVEL 3.0 AND ABOVE
JOINT BETWEEN WINDOWS - PLAN
LEVEL 3.0 AND ABOVE L17
2 6 2.1JOINT BETWEEN
LEVEL 2.0 AND LIGHTBOXES - PLAN
2.0 AND L2.1 - SECTION
Section of Internal Building courtyard 9 LIGHTBOX
Lightbox - L2.0 AND L2.1 - SECTION
from MTC-A-32-TB-L_-_-_-__-00-616 12 JOINT BETWEEN Sheet 3/5
WINDOWS - PLAN 13
SCALE 1:10 SCALE 1:10 SCALE 1:10
SCALE 1:10 SCALE 1:10

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 104 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
775
ARUP LIGHTING
MARK_UPS

Abu Dhabi Airports Company PJSC Specification, Section 265120

L5

translucent
cover, by others
L2c

L17

Detail 6
Detail section of Check-In from MTC-Q-04-TB-L_-_-_-__-00-502

L5 L5

L17

Detail 4
Detail section of Arrivals Wall from MTC-A-94-TB-__-L_-_-0-00-09-027

L13c

L17

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

Detail 6
L17
Sheet 4/5
Detail of uplight to Info Board from MTC-A-94-TB-L_-_-0-00-09-033

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 105 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

U1c
U1c U1c U1c

L17

Detail 2
Section of vertical circulation of Glazed Passenger lifts from MTC-A-94-TB-L_-_-0-00-07-018

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

L17
Sheet 5/5

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 106 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Continuous recessed linear profile

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 28W/m


Primary luminaire Extruded aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 2,085lm/m
Finish: See Notes Luminaire efficacy: 74lm/W
Accessories: See Notes Beam / distribution: Symmetric, see LDC
Project 1
Light source
SLOTLIGHT II LED single luminaires type: LED CRI / Colour temperature:
12.08.2014 > 80 / 3,000K

SLOT2 12W Driver


LED830type: L611 PM LDO IP40 Constant Current Operator Colour Variation:
42180995 ≤ 3 SDCM
single luminaires Telephone

LED light line Drive


0 L611 PM LDO IP40
current or voltage: 700mA 42180995
Fax
e-Mail Luminaire Lifetime: ≥ 50,000 hours
Times New Roman
Dimming
LED light line 12 & type:
W, Colour rendering DALI,
Ra > 80, colour temperature 3000 K,integral Lifetime
colour rendering index Ra 80; Total luminous flux of Basis: L70 / F10 @ Ta 250C
luminaire: 858 lm, Luminaire efficacy: 65 lm/W, LED service life 50,000h
ARCHITECTURAL at 70 % luminous
LIGHTING WORKSflux with LED converter. Slave luminaire for
LPL2.5-500mm-HP7-3000K-EXT 500mm HP7
Ra IP:
DALI control (DALI only) made of extruded aluminium section inIP20 Times
natural anodised finish. Opal New glass
acrylic RomanPMMA diffuser with
rdiffusely
rendering > 80,outer
patterned colour temperature
surface makes 3000 3000K
K, colour
the luminaire LED
rendering
appear LUMINAIRE
index
uniformly Ra 80;over
bright Total WITH
of itsWHITE
luminous
100% flux INTERIOR
face.ofLuminaire AND
comprises FROSTED
housing and FLAT LENS /
re efficacy: 65 lm/W, LED service life 50,000h at 70 % luminous flux with LED converter.
2 fixingSlave luminaire for wired with halogen-free
continuous
ade of Degree
opal
extruded
PMMA optic. Includes gear tray, wiring and end-cap set including screws. Luminaire Luminaire Data Sheet
leads. ofaluminium
protection:section in natural anodised
IP40. Dimensions: 611 x 72finish.
x 100Opal
mm acrylic
weight:glass PMMA diffuser with
2.1 kg
urface makes the luminaire appear uniformly bright over 100% of its face. Luminaire comprises housing and
ic. Includes gear tray, wiring and end-cap set including 2 fixing screws. Luminaire wired with halogen-free
n: IP40. Dimensions: 611 x 72 x 100 mm weight: 2.1 kg
Luminaire distribution curve (LDC)
Luminous emittance 1: Location:
per 0.5m
See our luminaire catalog for an image of the
Prayer Rooms Ablutions
luminaire.
Bus Holdroom Arrivals Tunnel
Lounges Holdrooms
Security Circulation
Toilets Smoking Rooms

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Luminaire to be passively cooled.
ZS_SLO_F_Einbau.jpg ZS_SLO_M_2_LED_alle_600.wmf 3. Continuous profiles to be supplied
with all necessary accessories including
Light Distribution
ZS_SLO_F_Einbau.jpg Luminaire classification according to CIE:ZS_SLO_M_2_LED_alle_600.wmf
100 STD - 1:
Luminous emittance standard mounting profiles, opal covers, brackets
CIE flux code: 56 85 97 100 100
and end caps.
180° h: 100% • Lamps: 1STD - standard
x LED-Z174 PM / 12W
• Total luminous flux of luminaire: 858 lm 4. Lengths required to be confirmed by
150° 150° L18
L18 65
• Luminaire efficacy: lm/W L18 L18
180° h: 100% • Lamps: 1 x LED-Z174 PM / 12WL18 site measurement prior to ordering and
• Rated life: 50000h L70 at 25°C
• Total luminous flux of luminaire:
L18 858 lm
150° • Colour Rendering Index min.: 80
• Luminaire efficacy: 65 lm/W L20
coordinated with Architect Engineer.
120° •120° L18 L70 at•25°C
Rated life: 50000h
Colour temperature: 3000 Kelvin
L20 L20
• Chromaticity tolerance (initial MacAdam): 4
• Colour Rendering Index min.: 80 5. Fixtures to be of anodised aluminium
• Ballast: 1x LED_Con LED-Converter
120° • Colour temperature: 3000 Kelvin
L20 silver finish with opal cover.
• Connected Load: 13.2 W Lambda = 0.98
• Chromaticity tolerance (initial MacAdam): 4
• Dimming: LDO dimmable to 10% over DALI
L18 1x LED_Con LED-Converter
• Ballast: L20
90° 300 200 100 90° • Maintenance category: D - Enclosed IP2X
• Connected Load: 13.2 W Lambda = 0.98
• Dimming: LDO dimmable to 10% over DALI
90° • Maintenance category: D - Enclosed IP2X

60° L4 60° L20


L18

60°
30° 30°
0° C180 | C0
cd/klm C270 | C90
L20
30°
D31068_SLOT_12W_LED830_L611_PM.ldt
C180 | C0

C270 | C90
1068_SLOT_12W_LED830_L611_PM.ldt L18

L20
Despite the highest quality standards and careful examination of all components, there may be isolated instances of technology-related failures of individual LEDs during the
The drawings on this page are
Superseded
Page 1
specified product lifetime.
Luminous flux and connected electrical load are subject to an initial tolerance of up to + / - 10%. Color temperature is subject to a tolerance of up to +/-150 Kelvin from the
indicative. Refer to the architectural
Refer to MTC-A-41-TB-L_-_-_-__-00-667
detail 4 in Arup mark-ups for new detail
nominal value. examination of all components, there may be isolated instances of technology-related failures of individual LEDs during the
ds and careful drawings for correct setting out,
L18
trical load are subject to an initial tolerance of up to + / - 10%. Color temperature is subject to a tolerance
L2c of up to +/-150 Kelvin from the mounting details and final dimensions.
We reserve the right to make technical changes without prior notice. 17.01.2014
L20© Zumtobel - 5 year guarantee when you register at
L4
www.zumtobel.com/guarantee/registration

nical changes without prior notice. 17.01.2014 © Zumtobel - 5 year guarantee when you register at
istration
L2c Type:
L2c
L20
L18

L18
L20
L2c
L20 L20
L20 L20

L18 Sheet 1/2


Arrivals Tunnel ceiling from MTC-A-41-TB-L_-_-_-__-00-665
L18
L18 L18 L18 L18

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 107 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
90
L18 L18 L20 L18 L18

210
L20

230
Abu Dhabi Airports Company PJSCL18 L18 L20
Specification, Section 265120

1800
2040

1800
1800
L20 CFM COLD FORMED METAL FRAMING

2040
2040
44
01

0
L18

18
00
20
L20

40
60

18
0

00
L18

20
40
L20 CA'
71
0 LMF CEILING SUSPENSION
33 03 STEEL ANGLE
80
L4 L18

GYB GYPSUM BOARD


L20
01
1030 325
4500
EQ

L18

125
FCL +5.800
+4.50
EQ

200 500
4500
1030 GYB GYPSUM BOARD
L20 01

ARRIVALS TUNNEL
L2c 3 DETAIL
L18 SCALE 1:5
7
0
L4 338 -

0
71
L20 CA
L2c
L18
40
20

00
18
0
60

L20
40
20

00

L18
18

2040

METAL
2040
0

1800
44

1800

L20
1800

2040

L18 L20
Detail 1 L18
230

L20 L18
90

L18 L20 L18 L20


210

L18
Arrivals Tunnel ceiling from MTC-A-41-TB-L_-_-_-__-00-665 10

C2 C1 B9
300 120 15

1 ARRIVALS TUNNEL CEILING AT LB1 & LB2 - SECTOR 5.18


SCALE 1:100 TYPE L20 - LINEAR LED RGB
STRIP LIGHT MOUNTED IN
C2 ARCHITECTURAL DETAILS
SFS STRETCHED FABRIC
01
SPRINKLER

SOUND ABSORBING FAB ARRIVALS TUNNEL


PANEL 01 4 DETAIL
SCALE 1:5
GYB GLZ
CFM COLD FORMED 01 11
01 METAL FRAMING
12 L2c
GYPSUM BOARD GYB 41664
01
1600

GLZ BACK PAINTED


2800

L20
16 LAMINATED GLASS
SFS 6
01 -
GLZ BACK PAINTED
TYPE L20 - LINEAR LED RGB L2c 16 LAMINATED GLASS
STRIP LIGHT MOUNTED IN GLZ
SFS TRANSLUCENT
ARCHITECTURAL DETAILS 16
GLASS DIFFUSER
01 10
4500

TYPE 2c LIGHT FIXTURE

4 GALVINISED MILD STEEL


- BRACKET INTERVAL PER 150
3000

5 PANEL JOINT. SIZE TBD


-
CONTINUOUS LINEAR GRILLE.
SEE MECH. DWG'S

ALUM. EXTRUDED PROFILE

L2c
SFS STRETCHED FABRIC
01 The drawings on this page are 30 200

2 SECTION ACROSS ARRIVALS TUNNEL CORRIDOR indicative. Refer


ESCALATOR WELLto the architectural
DCM
21

SCALE 1:50 drawings


5 DETAIL
for correct setting 03 ST. STEEL TRIM
SCALE 1:5
out, mounting details and final
dimensions.

Type:

L18
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 108 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Continuous surface mounted linear profile

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 28W/m


Primary luminaire Extruded aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 2,085lm/m
Finish: See Notes Luminaire efficacy: 74lm/W
Accessories: See Notes Beam / distribution: Symmetric, see LDC
Project 1
Light source type: LED CRI / Colour temperature:
12.08.2014 > 80 / 3,000K

Driver type: Constant Current Operator Colour Variation:


Telephone
≤ 3 SDCM
Drive current or voltage: 700mA Fax
e-Mail Luminaire Lifetime: ≥ 50,000 hours
Dimming & type: DALI, integral Lifetime Basis: L70 / F10 @ Ta 250C
ARCHITECTURAL LIGHTING WORKS LPL2.5-500mm-HP7-3000K-EXT 500mm HP7
IP: IP20
3000K LED LUMINAIRE WITH WHITE INTERIOR AND FROSTED FLAT LENS /
Luminaire Data Sheet
Luminaire distribution curve (LDC)
Luminous emittance 1: Location:
per 0.5m
See our luminaire catalog for an image of the Departures Hall Welcomers hall
luminaire.
Baggage Reclaim Car Park Bridges
Arrival Lobby Side Pavilions
Centre Space Arrival corridor
Circulation
le luminaires
42180995
Notes:
11 PM LDO IP40 42180995
1. Refer to Section ‘2.0 Products’ of this
Times New Roman Times New Roman specification for additional requirements.
colourRa
ering rendering index
> 80, colour Ra 80; Total
temperature luminous
3000 fluxrendering
K, colour of index Ra 80; Total luminous flux of
70 % 65
cacy: luminous
lm/W, LED flux with LED
service lifeconverter.
50,000h at Slave
70 %luminaire
luminousfor flux with LED converter. Slave luminaire for
odised finish.
f extruded Opal acrylic
aluminium glass
section PMMA anodised
in natural diffuser with
finish. Opal acrylic glass PMMA diffuser with 2. Luminaire to be passively cooled.
ht over 100%
makes of its face.
the luminaire Luminaire
appear comprises
uniformly housing
bright over 100%andof its face. Luminaire comprises housing and
luding 2 fixing
ludes gear tray,screws. Luminaire
wiring and end-cap wired with halogen-free
set including 2 fixing screws. Luminaire wired with halogen-free 3. Continuous profiles to be supplied
2.1
0. kg
Dimensions: 611 x 72 x 100 mm weight: 2.1 kg with all necessary accessories including
Luminaire classification according to CIE: 100 Luminous emittance 1: mounting profiles, opal covers, brackets
CIE flux code: 56 85 97 100 100
and end caps.
4. Lengths required to be confirmed by
site measurement prior to ordering and
coordinated with Architect Engineer.
5. Fixtures to be of anodised aluminium
silver finish with opal cover.
ceiling level

L5b L5b

ZS_SLO_F_Einbau.jpg ZS_SLO_M_2_LED_alle_600.wmf
L18b
ZS_SLO_M_2_LED_alle_600.wmf
L18b

STD - standard STD - standard

h: 100% PM / 12W
• Lamps: 1 x LED-Z174 • Lamps: 1 x LED-Z174 PM / 12W
luminous flux of luminaire: 858 lm • Total luminous flux of luminaire: 858 lm
• Total 150°
• Luminaire efficacy: 65 lm/W
• Luminaire efficacy: 65 lm/W
• Rated life: 50000h L70 at 25°C
• Rated life: 50000h L70 at 25°C
• Colour Rendering Index min.: 80
• Colour Rendering Index min.: 80
120°
• Colour temperature: 3000 Kelvin
• Colour temperature: 3000 Kelvin The drawings on this page are
• Chromaticity tolerance (initial MacAdam): 4 Page 1
• Chromaticity tolerance (initial MacAdam): 4
• Ballast: 1x LED_Con LED-Converter indicative. Refer to the architectural
• Ballast: 1x LED_Con LED-Converter
• Connected Load: 13.2 W Lambda = 0.98
• Connected Load: 13.2 W Lambda = 0.98 drawings for correct setting out,
• Dimming: LDO dimmable to 10% over DALI
• Dimming: LDO dimmable to 10% over DALI
90° • Maintenance category: D - Enclosed IP2X mounting details and final dimensions.
• Maintenance category: D - Enclosed IP2X

L2j

60° Type:
XL3 XL3

L18b
30°
C180 | C0
C270 | C90
Detail 1 XD1c
LOT_12W_LED830_L611_PM.ldt Sheet 1/5
Detail section of Car Park Bridge from MTC-A-94-TB-L_-_-0-00-09-020

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 109 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
careful examination of all components, there may be isolated instances of technology-related failures of individual LEDs during the
olated instances of technology-related failures of individual LEDs during the
ad are subject to an initial tolerance of up to + / - 10%. Color temperature is subject to a tolerance of up to +/-150 Kelvin from the
Color temperature is subject to a tolerance of up to +/-150 Kelvin from the

anges without prior notice. 17.01.2014 © Zumtobel - 5 year guarantee when you register at
Abu Dhabi Airports Company PJSC Specification, Section 265120

L18b

L18b

Detail 1
Section of Terminal Building from MTC-A-03-TB-L_-_-5-00-00-601

L2c

ARUP LIGHTING
MARK_UPS

L18b
L2c

L5b

Detail 2
Detail section at Level 2.0 ceiling at North Economy Transfer Lounge from MTC-A-41-TB-L2-0-5-13-00-433
L16

L18g

ARU
The drawings on this page are
indicative. Refer to the architectural
MA
drawings for correct setting out, Rev
mounting details and final dimensions.

Type:
L18b

L18b
Sheet 2/5
Detail section of internal buildings from MTC-A-72-B-L_-_-_-__-00-651

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 110 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

ARUP LIGH
ARUP
MARK_UPS
MAR

L18b L18b

L18b L18b

L18b L18b

Detail 5 Detail 6
Detail sections Processor Arrival Immigration Hall from MTC-A-41-TB-L0-1-5-00-00-481

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.

Type:

L18b
Sheet 3/5

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 111 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

L18b

Section through Arrival Corridor from MTC-A-07-TB-L_-_-_-__-00-452.pdf

L18b

L18b

Details 2 2and 3
TYPE L18b - SECTION THROUGH ENTRANCE BRIDGE
3 TYPE L18b - SECTION THROUGH ENTRANCE BRDIGE
SCALE 1:20 SCALE 1:20
Section through Entrance Bridge from MTC-A-94-TB-L_-_-0-00-09-030

TYPE U1c: EXTERIOR QUALITY


ARTURES KERB STIRRUP MOUNTED FLOODLIGHT

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.
L5
L18b

02 31.01.15 BU
TYPE XL1b LIGHT
01 31.10.14 BU

Type:
00 15.07.12 IS

ISS
5 TYPE U1 - SECTION THROUGH BINNACLE UPLIGHT 6 CANOPY CONNECTION DETAIL
SCALE 1:20 SCALE 1:2

Details 3 and 4
L18b
PLANTER Sheet 4/5 ABU DHABI AIRPO

Detail through typical Pier section lighting trays from MTC-A-94-TB-L_-_-0-00-09-003


TYPE S7 & S8 LIGHT

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 112 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
TYPE L2c LIGHT.
LED STRIP GRAZING
TRANSLUCENT GLASS
ABU DH
MI
TYPE S7 LIGHT
Abu Dhabi Airports Company PJSC Specification, Section 265120

U1c

L18b

Detail 4
Side pavilion cladding at wall interface from MTC-A-94-TB-L_-_-0-00-09-047

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

L18b
Sheet 5/5

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 113 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Continuous wall mounted, direct and indirect linear profile
NCOR
Manufacturing
NCOR continuous OPAL-DI standard: EN 60LDE
53W LED830 598 Total luminaire wattage (max): 44W/m
Primary luminaire Extruded aluminium Power factor: > 0.9
ED Luminaire / wall mount
construction material: Rated luminous flux (lm): 2,060lm/m direct, 1,560lm/m indirect
Finish: See Notes Luminaire efficacy:
ender direct/indirect LED luminaire, total power: 52.7W LED (per 1209mm), DALI controllable luminaire with
82lm/W
D converter. LED service life lasts 50000 h before luminous flux is reduced to 80% of initial value. Chromaticity
Accessories: See Notes Beam / distribution: Symmetric, see LDC
erance (initial MavAdam): 4. Total luminous flux of luminaire: 4340 lm (per 1209mm), Luminaire efficacy: 82
Light source type: LED CRI / Colour temperature: > 80 / 3,000K
/W. Colour rendering Ra > 80,Project
colour 1temperature 3000 K. light guided via backlit diffuser luminaire optic.
Driver type: Constant Current Colour Variation:
direct light guided by continuous light-guide section for homogeneous light –point dispersal on ceiling. Closed 19.03.2014
≤ 3 SDCM
Drive current or voltage: 700mA Luminaire Lifetime:
Operator discharge. Luminaire
tical system with protective covers on LED module to prevent damage from electrostatic ≥ 50,000 hours
Telephone
using powder Dimming & type: extruded aluminium
coated of square-edge DALI,section
integral Fax
with visible squaree-Mail Lifetime
cross-section, Basis:
die-cast L70 / F10 @ Ta 250C
uminium endIP: IP20 invisible screw-fitting, lumidenaire colour silver-
pieces painted in matching luminaire colour,
L-DI 53W LED830 LDE LINCOR_DIRECT_INDIRECT_DIFFUSE § / Luminaire Data Sheet
minaire wired with halogen-free leads. Dimensions: - 63 x 64 mm. Weight 3 kg (1209mm). Wall mounting kit
pplied separately.
nt Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
See
e, total power: 52.7W LED (per our luminaire
1209mm), catalog
DALI for an image
controllable of the with
luminaire Welcomers Hall Mezzanine
luminaire.
s 50000 h before luminous flux is reduced to 80% of initial value. Chromaticity
luminous flux of luminaire: 4340 lm (per 1209mm), Luminaire efficacy: 82
our temperature 3000 K. light guided via backlit diffuser luminaire optic.
ght-guide section for homogeneous light –point dispersal on ceiling. Closed
s on LED module to prevent damage from electrostatic discharge. Luminaire
dge extruded aluminium section with visible square cross-section, die-cast Notes:
tching luminaire colour, invisible screw-fitting, lumidenaire colour silver- 1. Refer to Section ‘2.0 Products’ of this
ads. Dimensions: - 63 x 64 mm. Weight 3 kg (1209mm). Wall mounting kit specification for additional requirements.
2. Luminaire to be passively cooled.
3. Continuous profiles to be supplied
with all necessary accessories including
Luminaire classification according to CIE: 57 Luminous emittance 1: wall mounting profiles, opal covers,
CIE flux code: 49 81 97 57 100
ght Distribution STD - standard brackets and end caps.
4. Lengths required to be confirmed by
• Light Distribution: STD - Standard site measurement prior to ordering and
• Lamps: 1 x LED-Z937 / 52.7W coordinated with Architect Engineer.
• Total luminous flux of luminaire: 4340lm (per 1209mm)
• Luminaire efficacy: 82 lm/W 5. Fixtures to be of anodised aluminium
• Rated life: 50000h L80 at 25°C silver finish with opal cover.
• Colour Rendering Index min: 80
continuous,
• Colour temperature: 3000 Kelvin
final length to match location
• Chromaticity tolerance (initial MacAdam): 4
• Ballast: 1 x 28000210 LCAI 970/0300 1010 one4all
• Connected Load: 52.7W
• Dimming: LDE
• Maintenance category: D – Enclosed IP2X

STD - standard

L18d • Light Distribution: STD - L18d Standard


• Lamps: 1 x LED-Z937 / 52.7W
• Total luminous flux of luminaire: 4340lm (per 1209mm)
• Luminaire efficacy: 82 lm/W
• Rated
serve the right to make technical changes withoutlife: 50000h
prior notice. L80 ©atZumtobel
27.11.2012 25°C - 5 year guarantee when you register at www.zumtobel.com/guarantee/registration The drawings on this page are
• Colour Rendering Index min: 80 indicative. Refer to the architectural
• Colour temperature: 3000 Kelvin Page 1
ARUP LIGHTIN
drawings for correct setting out,
• Chromaticity tolerance (initial MacAdam): 4 MARK_UPS
mounting details and final dimensions.
• Ballast: 1 x 28000210 LCAI 970/0300 1010 one4all
L18
• Connected Load: 52.7W
• Dimming: LDE
• Maintenance category: D – Enclosed IP2X Type:

Detail 1
L18d
Sheet 1/2
Section of Terminal Building from MTC-A-03-TB-L_-_-5-00-00-603

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401


prior notice. 27.11.2012 © Zumtobel - 5 year guarantee when you register at www.zumtobel.com/guarantee/registration
Page 114 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

L2c L2c

L18d L18d L18d

Detail 1
Side Elevation of vertical circulation Glazed Passenger Lift ELV-05-09, 10, 11, 63 from MTC-A-07-TB-L_-_-_-__-00-105

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

L18d
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 115 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Continuous wall mounted linear profile


NCOR
Manufacturing
NCOR continuous OPAL-D standard:
31W LED830EN 60LDE 598 Total luminaire wattage (max): 26W/m
Primary luminaire Extruded aluminium Power factor: > 0.9
ED Luminaire / wall mount
construction material: Rated luminous flux (lm): 2,060lm/m
Finish: See Notes
ender direct LED luminaire, total power: 31.0W LED (per 1209mm), DALI controllable luminaire Luminaire
with LED efficacy: 79lm/W
nverter. LEDAccessories: Seeflux
service life lasts 50000 h before luminous Notes Beam
is reduced to 80% of initial value. / distribution:
Chromaticity Symmetric, see LDC
Light
erance (initial source
MavAdam): type:
4. Total luminous flux of LED
luminaire: 2473 lm (per 1209mm), Luminaire CRI efficacy:
/ Colour 82 temperature: > 80 / 3,000K

Driver Ra
/W. Colour rendering type:> 80,Project
colour 1temperature 3000
Constant Current
K. light guided Colouroptic.
via backlit diffuser luminaire Variation: ≤ 3 SDCM
19.03.2014
osed opticalDrive current
system with orcovers
protective voltage:on LED 700mA
module to prevent damage from electrostaticLuminaire
discharge.Lifetime: ≥ 50,000 hours
Operator
minaire housing powder coated of square-edge extruded aluminium section with Telephone
Dimming & type: DALI, integral visible
Fax
e-Mail
Lifetime Basis:
square cross-section,
L70 / F10 @ Ta 250C
e-cast aluminium end pieces painted in matching luminaire colour, invisible screw-fitting, lumidenaire colour
IP: IP20
L-DI
ver- 53W LED830
Luminaire LDE
wired with halogen-free leads. Dimensions: - 63 x LINCOR_DIRECT_DIFFUSE
64 mm. Weight 3 kg (1209mm).§Wall / Luminaire
mounting Data Sheet
supplied separately.
nt Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
See
e, total power: 52.7W LED (per our luminaire
1209mm), catalog
DALI for an image
controllable of the with
luminaire Wall mounted in mezzanine in Level 0.1
luminaire.
s 50000 h before luminous flux is reduced to 80% of initial value. Chromaticity Gatehouses
luminous flux of luminaire: 4340 lm (per 1209mm), Luminaire efficacy: 82
our temperature 3000 K. light guided via backlit diffuser luminaire optic.
ght-guide section for homogeneous light –point dispersal on ceiling. Closed
s on LED module to prevent damage from electrostatic discharge. Luminaire
dge extruded aluminium section with visible square cross-section, die-cast Notes:
tching luminaire colour, invisible screw-fitting, lumidenaire colour silver- 1. Refer to Section ‘2.0 Products’ of this
ads. Dimensions: - 63 x 64 mm. Weight 3 kg (1209mm). Wall mounting kit specification for additional requirements.
2. Luminaire to be passively cooled.
3. Continuous profiles to be supplied
with all necessary accessories including
Luminaire classification according to CIE: 100 Luminous emittance 1: wall mounting profiles, opal covers,
CIE flux code: 49 81 97 100 100
ght Distribution STD - standard brackets and end caps.
4. Lengths required to be confirmed by
• Light Distribution: STD - Standard site measurement prior to ordering and
• Lamps: 1 x LED-Z937 / 31.0W coordinated with Architect Engineer.
• Total luminous flux of luminaire: 2473lm (per 1209mm)
• Luminaire efficacy: 82 lm/W 5. Fixtures to be of anodised aluminium
• Rated life: 50000h L80 at 25°C silver finish with opal cover.
• Colour Rendering Index min: 80
continuous,
• Colour temperature: 3000 Kelvin
L2c final length to match location
• Chromaticity tolerance (initial MacAdam): 4
• Ballast: 1 x 28000210 LCAI 970/0300 1010 one4all
• Connected Load: 31.0W
• Dimming: LDE
• Maintenance category: D – Enclosed IP2X

STD - standard

• Light Distribution: STD - Standard


• Lamps: 1 x LED-Z937 / 52.7W
•L2c
Total luminous flux of luminaire: 4340lm (per 1209mm)
L18f
• Luminaire efficacy: 82 lm/W
• Rated
serve the right to make technical changes withoutlife: 50000h
prior notice. L80 ©atZumtobel
27.11.2012 25°C - 5 year guarantee when you register at www.zumtobel.com/guarantee/registration The drawings on this page are
• Colour Rendering Index min: 80 indicative. Refer to the architectural
• Colour temperature: 3000 Kelvin Page 1 drawings for correct setting out,
• Chromaticity tolerance (initial MacAdam): 4 mounting details and final dimensions.
• Ballast: 1 x 28000210 LCAI 970/0300 1010 one4all
• Connected Load: 52.7W
• Dimming: LDE
• Maintenance category: D – Enclosed IP2X Type:

Detail 1
L18f
Sheet 1/2
Detail section from MTC-A-03-TB-L_-_-5-00-00-601

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401


prior notice. 27.11.2012 © Zumtobel - 5 year guarantee when you register at www.zumtobel.com/guarantee/registration
Page 116 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
final detail TBC with
Architects

cladding zone

Abu Dhabi Airports CompanyD1d


PJSC
structure zone
Specification, Section 265120
D1d
GYB
L4f L4f
01

52

PFT
STN
01
L2o 08

L. +28.92
+28.92
ARRIVALS
LEVEL FFL
D1 STN
L18f 08

STN
L2o
08
PFT L2o
L18f 01 L. +25.80
+25.80
UPPER DECK
BOARDING
LEVEL FFL
D1

STN
L2o
08
PFT DCM
01 L. +22.35 04
+22.35
DEPARTURES
LEVEL FFL

Cross section of Gatehouse Code F from MTC-A-03-TB-L_-_-_-__-00-508

2
GATEHOUSE 1
A30550
CORRIDOR A30550

ELECTRICAL STEEL GRATING ARM


PFT CLOSET 08
01

L. +17.70 L. +17.70
+17.70
FFL & APRON
@ FACADE FFL

CRAWL SPACE CRAWL SPACE


FFC CRAWL SPACE
01 L. +16.15
+16.15
CRAWL SPACE

+15.00
PCA ROOM FFL

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.

Type:

L18f
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 117 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Continuous ceiling recessed linear profile

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 50W/m (RGBW)


Primary luminaire Extruded aluminium Power factor: > 0.5
construction material: Rated luminous flux (lm): 2,100lm/m (RGBW)
Finish: See Notes Luminaire efficacy: 42lm/W (RGBW)
Accessories: See Notes Beam / distribution: Symmetric, see LDC
Light sourceProject type: 1 LED CRI / Colour temperature: > 80 (white) / RGB / 3,000K (W)
13.08.2014
Driver type: Constant Current Colour Variation: ≤ 3 SDCM (white)
Operator
Drive current or voltage: 700mA Telephone
Fax Luminaire Lifetime: ≥ 50,000 hours
SLOTLIGHT II LED single luminaires e-Mail
SLOT2 Dimming & type:
45W LED RGB L1511 LDO DALI, integral 42181394 Lifetime Basis: L70 / F10 @ Ta 250C
IP:
SLOTLIGHT
LED light line II LED batten
IP20
ZUMTOBEL SLOT2 65W LED RGB L1511 Times
LDO WEISS Art. Nr. 42181394 / Luminaire
New§Roman
LED RGBSLOT245 W lightBline,
45WTotalLED RGB fluxL1500 LDO2100 lm, Luminaire efficacy: 32 lm/W, with DALI - LED converter. LED 42181902
luminous of luminaire:
service life 50000 h for luminous flux at 70% of initial value with LED converter. Luminaire made of extruded aluminium section in Data Sheet
Battenfinish.
natural anodised for LED light glass
Opal acrylic lightPMMA diffuser with diffusely patterned outer surface makes the luminaire appear almost
uniformly bright over 100% of its face. Luminaire comprises housing and continuous opal PMMA optic. Includes gear tray, wiring and New Roman
Times
end-cap setBatten luminaire
including
degree of 50000
for LED-RGB
2 x fixing
h forIP40
protection:
light line 45
screws. Luminaire W, with
wired with DALI LED converter.
halogen-free Slave luminaire
leads. Dimensions: 1511for DALI
x 72 control
x 100 mm,(DALI only).
weight: LED service life
4 kg,
luminous flux at 80% of initial value. Luminaire wired with halogen-free leads. Dimensions: 1500 x 72Luminous emittance
x 100 mm, weight:
Luminaire distribution
1: curve (LDC) Location:
2.1 kg

See our luminaire catalog for an image of the Arrivals Bussing Corridor
luminaire.

Notes:
1. Refer to Section ‘2.0 Products’ of this
ZS_SLO_F_2LED_blau.jpg ZS_SLO_M_2_LED_alle_1500.wmf
specification for additional requirements.
ZS_SLO_F_2LED_blau.jpg

Light Distribution RGB > colour white


2. Luminaire to be passively cooled.
Light Distribution STD - standard
180° h: 100% • Light Distribution: RGB > colour white 3. Continuous profiles to be supplied
• Lamps: 1• Light Distribution:
x LED-Z104 / 65WSTD - standard
150° 150° • Lamps:
• Total luminous flux1 of
x LED-Z1060 / 45W
luminaire: 2100 lm
with all necessary accessories including
Luminaire classification according to CIE:
• Rated life:32100
50000h
lm/W L80 at 25°C Luminous emittance 1:
• Luminaire
CIE flux code: 48 79 96 •100 Rated100
life:
efficacy:
• Chromaticity
50000h L70 tolerance
at 25°C (initial MacAdam): 3
mounting profiles, opal covers, brackets
120° 120° • Ballast: 3Index
• Colour Rendering
• Chromaticity tolerance
x 00109104
min.: 90CONV PH Xit 36W 0,12-0,4A
110V(initial
TD MacAdam): 4
and end caps.
• Ballast: 1• Connected
x 00109104Load: CONV 45PHW Xit
Lambda = 0.9
36W 0,12-0,4A
• Dimming:
110V TD LDO dimmable to 1% over
L18 L18
DALI
L18 L18 4. Lengths required to be confirmed by
• Connected Load: 65 W Lambda = 0.9
90° 300 200 100 90° • Dimming: LDO L18
L18 D - Enclosed IP2X
site measurement prior to ordering and
• Maintenance category:
L20
coordinated with Architect Engineer.
L18 L20 L20
60° 60°
5. Allow for Red, Green and Blue LEDs
L20 to be individually controlled.
L18
30°

30°
C180 | C0
L20 6. Fixtures to be of anodised aluminium
cd/klm C270 | C90 silver finish with opal cover.
D32219AA_RGB.ldt

L4 L20
L18

Despite the highest quality standards and careful examination of all components, there may be isolated instances of technology-related failures of individual LEDs during the
specified product lifetime.The failure of 1 LED points causes no functional impairment to the lighting performance of the luminaire and is therefore no reason for complaint
Luminous flux and connected electrical load are subject to an initial tolerance of up to + / - 10%. Color temperature is subject to a tolerance of up to +/-150 Kelvin from the
nominal value.

L20
We reserve the right to make technical changes without prior notice. 21.03.2014 © Zumtobel - 5 year guarantee when you register at
www.zumtobel.com/guarantee/registration
Luminous flux and connected electrical load are subject to an initial tolerance of up to + / - 10%. Color temperature is subject to a tolerance of up to +/-150 Kelvin from the
nominal value.
L18
We reserve the right to make technical changes without prior notice. 16.05.2014 © Zumtobel - 5 year guarantee when you register at
www.zumtobel.com/guarantee/registration

L20
The drawings on this page are
Superseded

Page 1 indicative. Refer to the architectural


Refer to MTC-A-41-TB-L_-_-_-__-00-667
detail 4 in Arup mark-ups for new detail
drawings for correct setting out,
L18
L2c mounting details and final dimensions.
L20
L4

L2c Type:
L2c
L20
L18

L20
L20
L2c
L20 L20
L20 L20

L18 Sheet 1/2


Arrivals Tunnel ceiling from MTC-A-41-TB-L_-_-_-__-00-665
L18
L18 L18 L18 L18

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 118 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
90
L18 L18 L20 L18 L18

210
L20

230
Abu Dhabi Airports Company PJSCL18 L18 L20
Specification, Section 265120

1800
2040

1800
1800
L20 CFM COLD FORMED METAL FRAMING

2040
2040
44
01

0
L18

18
00
20
L20

40
60

18
0

00
L18

20
40
L20 CA'
71
0 LMF CEILING SUSPENSION
33 03 STEEL ANGLE
80
L4 L18

GYB GYPSUM BOARD


L20
01
1030 325
4500
EQ

L18

125
FCL +5.800
+4.50
EQ

200 500
4500
1030 GYB GYPSUM BOARD
L20 01

ARRIVALS TUNNEL
L2c 3 DETAIL
L18 SCALE 1:5
7
0
L4 338 -

0
71
L20 CA
L2c
L18
40
20

00
18
0
60

L20
40
20

00

L18
18

2040

METAL
2040
0

1800
44

1800

L20
1800

2040

L18 L20
Detail 1 L18
230

L20 L18
90

L18 L20 L18 L20


210

L18
Arrivals Tunnel ceiling from MTC-A-41-TB-L_-_-_-__-00-665 10

C2 C1 B9
300 120 15

1 ARRIVALS TUNNEL CEILING AT LB1 & LB2 - SECTOR 5.18


SCALE 1:100 TYPE L20 - LINEAR LED RGB
STRIP LIGHT MOUNTED IN
C2 ARCHITECTURAL DETAILS
SFS STRETCHED FABRIC
01
SPRINKLER

SOUND ABSORBING FAB ARRIVALS TUNNEL


PANEL 01 4 DETAIL
SCALE 1:5
GYB GLZ
CFM COLD FORMED 01 11
01 METAL FRAMING
12 L2c
GYPSUM BOARD GYB 41664
01
1600

GLZ BACK PAINTED


2800

L20
16 LAMINATED GLASS
SFS 6
01 -
GLZ BACK PAINTED
TYPE L20 - LINEAR LED RGB L2c 16 LAMINATED GLASS
STRIP LIGHT MOUNTED IN GLZ
SFS TRANSLUCENT
ARCHITECTURAL DETAILS 16
GLASS DIFFUSER
01 10
4500

TYPE 2c LIGHT FIXTURE

4 GALVINISED MILD STEEL


- BRACKET INTERVAL PER 150
3000

5 PANEL JOINT. SIZE TBD


-
CONTINUOUS LINEAR GRILLE.
SEE MECH. DWG'S

ALUM. EXTRUDED PROFILE

L2c
SFS STRETCHED FABRIC
01 The drawings on this page are 30 200

2 SECTION ACROSS ARRIVALS TUNNEL CORRIDOR indicative. Refer


ESCALATOR WELLto the architectural
DCM
21

SCALE 1:50 drawings


5 DETAIL
for correct setting 03 ST. STEEL TRIM
SCALE 1:5
out, mounting details and final
dimensions.

Type:

L20
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 119 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
4 x 2.4 Watt LEDs no lenses Adjustable mounting bracket

3D LED FLEX 100 . IP 20 . 4 . (length Direct screw fixing into the mounting
variable) . (colour temp. variable) . CRI 80 surface with heat sinks rotated.
Abu Dhabi Airports Company PJSC Specification, Section 265120
Supplied in 1.0 mtr lengths as standard Allows heat sink module to rotate for
Any multiple of 100 mm modules can be precise aiming angle
supplied to order
Luminaire Description: Flexible modular LED system Finish to match heat sink
Integral LV constant current drivers
30 V DC Supply
Manufacturing standard: EN luminaire wattage (max): 80W/m (RGBW)
60 Black
598Finish standard Total
Other RAL colours to order
Primary luminaire Aluminium Power factor: > 0.5
construction material: Rated luminous flux (lm): 2,600lm/m (RGBW)
Finish: 2 x 4.7
Stainless Watt LED arrays with reflectors
steel Luminaire efficacy: 33lm/W (RGBW)Fixed mounting bracket
RAD 3D LED Flex 100 CZ 5 - 2
Accessories: Mounting brackets Beam / distribution: Symmetric, see Where
LDCoveral height is an issue.
Supplied in 1.0 mtr lengths as standard Space for connectors under mounting
Light source type:
Project 1 LED CRI / Colour temperature: > 80 (white) / RGB / 3,000K (W)
bracket.
20.08.2014
Driver type: Constant Current
Integral LV constant current Colour Variation:
drivers ≤ 3 SDCM (white)
30 V DC Supply Operator Heat sink modules remaing parallel to
Drive current or voltage: 700mABlack Finish standard Telephone Fax Luminaire Lifetime: 50,000 hours mounting surface but the system can st
e-Mail
Dimming & type: Other RAL colours to order
DALI, remote Lifetime Basis: L70 / F10 @ Ta angle
250Cto follow complex curves.
IP: IP20Lighting N40NL7002710M 3D LED Flex 100 40 x 2.24 Watt LEDs
Radiant Architectural Finish to match heat sink
per mtr no lenses 700 mA 1000 mm module / Luminaire Data Sheet

Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
See our luminaire catalog for an image of the Integrated into architectural detail in bracket with spring
luminaire.
1 x 8 watt RGBW LED array with colour Adjustable mounting
mixing lens stairs clip fixing

Supplied in 1.0 mtr lengths as standard Where easy instalation and removal in
RAD 3D LED Flex 100 MCE RGBS akward spaces is required.
Integral DMX driver controller or
can be supplied with remote DMX Allows heat sink module to rotate for
driver version precise aiming angle
Notes:
Various beam angles and lens types Finish to match heat sink
24 Volt DC Supply 1. Refer to Section ‘2.0 Products’ of this
Black Finish standard specification for additional requirements.
100

Other RAL colours to order


2. Luminaire to be passively cooled.
350 Rad
3. Continuous profiles to be supplied
Power feed with all necessary Connector
accessories including
Luminaire classification according to CIE: 100 Luminous emittance 1: mounting profiles, covers, brackets and
100

CIE flux code: 44 75 94 100 100 Input to white light 1 mtr strips via 3 pole end caps. Mounting 16bracket
Amp 3 pole Weiland
height connectors are
to be
Weiland connector. confirmed followingused to join white light strips
mock-up.
100

350 Rad
50

16 Amp capacity for power and pwm 4. OT DIM AdaptorThese


to becan
provided
fit under on
the heat sink module
110

dimming line each circuit to ensure


evenall modules
when are mounting
non adjustable
84

brackets are
illuminated when dimmed used.of
to end
670 Rad DMX connectors are fitted to RGBW dimming range.
systems DMX connectors are fitted to RGBW
table mounting 5. Lengths required to be to
systems confirmed by together.
join the strips
et 1 RGBW LED
site measurement prior to ordering and
110
TBC

le with lens.
85.60

84
95

84
100

coordinated with Architect Engineer.


100

Refer to sections indicated in


350 Rad and plans 670 Rad
6. Detail to be coordinated with Architect
50

RCPs
mounting Adjustable mounting
architectural details.
Adjustable mounting
ring clip fixing bracket 1 RGBW LED 1 x 10 Watt Citizen or Sharp LED array Linear module with five 2 x 4.5 Watt
hout optics
bracket 2 LED module
module with lens. with reflectors 7. Finishing diffuser/glass
Citizen or in architectural
Sharp LED arrays with reflecto
with optics
450 Rad ARUP LIGHTING detail to be supplied by others.
RAD 3D LED Flex 100 CZ 10 - 1 MARK_UPS 8. Mock-up required RADto3D LED Flexdesign
confirm 100 CZ 5 2 - Linear 5
intent.
Supplied in 1.0 mtr lengths as standard Wide, medium and narrow reflectors
110
84
95

84

Wide, medium and narrow reflectors plus


diffusing covers and anti glare snoot Integral 30 V DC constant current drivers
670 Rad available.450 Rad
Integral LV constant current drivers Black Finish standard
able mounting Adjustable mounting
30 V DC Supply The drawings on this
Otherpage are to order
RAL colours
t 2 LED module bracket 1 RGBW LED
ptics module with lens. Black Finish standard indicative. Refer to the architectural
Other RAL colours to order drawings for correct setting out,
Page 1
mounting details and final dimensions.
1190
U7
1 x 10 Watt Citizen or Sharp LED array 2 x 4.5 Watt Citizen or Sharp LED array
Elliptical X Elliptical Y
Wide Medium Narrow with reflectors single spotlight Type: with reflectors single spotlight
L20b
New product New product
450 Rad
RAD 3D LED Flex 100 CZ 10 - single RAD 3D LED Flex 100 CZ 5 2 - single

Bracket Type Cover Feed Finish


Wide, medium and narrow reflectors plus
covers and anti
Medium Elliptical X Ellipticaldiffusing
glare snoot
Narrow Y Wide
L20b
Wide, medium and narrow reflectors

available. Integral 30 V DCSheet


or remote
1/2 line voltage
Direct fixing end Clear End Black
Section from MTC-A-94-TB-L_-_-0-00-09-030-031 031
Integral 30 V DC or remote line voltage constant current drivers
Adjustable Filter
1190 column in the table Back White
ption from each
Spring Clip below. Any RAL- constant current drivers
0K . CRI 80 . E . Adjustable . Clear. End . Black . colour Black Finish standard
Contract: Midfield Terminal Building – General
Black FinishContractor,
standard AUH.06.10.0401 OtherPage 120 to
RAL colours oforder
231
Length
(mm)
Colour
Bulletin
Temp. (K)No. CRI
145: Volume
Optics 3 of 4Type
Bracket (Rev 07)
Other
Cover RALFeed
colours to order
Finish January 31, 2015
200mm 27=2,700k 80 120˚ Direct fixing end Clear End Black
30=3,000k 90 E Adjustable Filter Back White

3
-increments 35=3,500k W Spring Clip Any RAL-
of 100mm 40=4,000k M colour
0 ) 20up8348
to- 9003 45=4,500k N
50=5,000k Elliptical X Elliptical Y Wide Medium Narrow
0 ) 20 8348 6478 Products and literature designed by
SCALE 1:20

Abu Dhabi Airports Company PJSC Specification, Section 265120

U7
POLYCARBONATE OPAL
U7 DIFFUSERTO BE REMOVABLE
FOR MAINTENANCE

02 31.01.15 BULLETIN 145


U7 L20b 01 31.10.14 BULLETIN 120
00 15.07.12 ISSUED FOR CONSTRUCTION

ISSUED FOR CONSTRUCTION

5 TYPE U7 & L20b - MUSEUM STAIR DETAIL ABU DHABI


Detail 5 SCALE 1:20
AIRPORTS COMPANY
Section of Museum stair from MTC-A-94-TB-L_-_-0-00-09-031 02 ABU DHABI AIRPORTS COMPANY

Kohn Pedersen Fox Associates


(International) PA
Architects and Planning Consultants
7a Langley Street
London WC2H 9JA
England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com

ABU DHABI INTERNATIONAL AIRPORT


MIDFIELD TERMINAL COMPLEX

TERMINAL BUILDING
as per previous
TYPICAL DETAILS
comments, SECTIONS AND DETAILS
fixture does not
8 UPLIGHT
match U8 fixture
MTC A 94 TB __ L_._ 0.00 09.031 02

KPF MC KF JH 25.09.2009

E
WBS AUH.06.10.0401

2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights reserved. Do not scale.

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

L20b
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 121 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Continuous integrated linear profile

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 22W/m (RGB)


Primary luminaire LED strip mounted on Power factor: > 0.5
construction material: extruded aluminium profile Rated luminous flux (lm): 1,020lm/m (RGB)
Finish: N/A Luminaire efficacy: 46lm/W (RGB)
Accessories: See Notes Beam / distribution: Symmetric, see LDC
Light source type: LED CRI / Colour temperature: N/A / RGB
r lighting solutions
Driver type:
Project 1
Constant Voltage Colour Variation: 14.08.2014
N/A
Drive current or voltage: 24V Operator Luminaire Lifetime: ≥ 50,000 hours
Telephone
LED Linear
Dimming & type:™ – linear lighting solutions
DALI, remote Fax
e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: IP20

Flex RGB HD20Flex RGB HD20


VarioLED™
LED Linear / Luminaire Data Sheet

Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
See our luminaire catalog for an image of the Centre Space Wayfinding Totems
luminaire.

22 Watt/meter
22 Watt/meter
1.016 lumen/meter (lm/m)
Notes:
! White Point Binning
1.016 lumen/meter
1. Refer to Section ‘2.0 Products’ of this
specification for (lm/m)
additional requirements.

! White Point Binning 2. Linear LED strip to be mounted on


a suitable profile to provide sufficient
heat dissipation per manufacturer’s
Aufbau & Maße
Luminaire Assembly
classification according to&
CIE flux code: 45 77 94 100 92
measurement
CIE: 100 Due to missing symmetry properties, no UGR table
can be displayed for this luminaire.
recommendations.
3. Continuous profiles to be supplied
62,5 mm (64 x) with all necessary accessories including
mounting profiles, covers, brackets and
end caps.
+ 24 V

ssembly & measurement


9,5 mm
GND 4. Mock-up sample to be provided.
Final selection of optical lens/cover to be
confirmed during site mock-up.

mm (64 x) 5,25 mm 10,4 mm 10,4 mm 10,4 mm 10,4 mm 10,4 mm 5,25 mm 5. Lengths required to be confirmed by
site measurement prior to ordering and
2,8 mm coordinated with Architect Engineer.
6. Mock-ups required to confirm design
9,5 mm intent.
Elektrische & Optische Betriebsdaten Electrical & optical data
Keine zusätzliche Kühlung 
Abmessungen Dimensions 4.000 mm x 9,5 mm x 2,8 mm
über AL-Profil notwendig.
mm 10,4 mm 10,4 mm 5,25 mm
Teilungsmaß Step length 62,5 mm/6 LED per step
No need for additional heat 
Leistung Power 88 W/22 Watt/meter sinking on AL profile.
2,8 mm The drawings on this page are
Effizienz Efficacy bis zu/up to 46,2 lumen/Watt
indicative. Refer to the architectural
Anzahl LED Number LED 384 LED, 10,4 mm LED pitch L80,
Page 1 drawings for correct setting out,
30.000 hrs
Spannung Voltage (V) 24 Volt (23 Vmin, 25 Vmax) mounting details and final dimensions.

ische Betriebsdaten Electrical & optical data


Strom Current 3,84 A/60 mA per step
Temperatur Temperature tcmin = –25°C, tcmax = +70°C Type:
Lagertemp. Storage temp. tmin = –30°C, tmax = +85°C
Keine zusätzliche Kühlung 
s 4.000 mm x 9,5 mm x 2,8 mm
Außentemperatur Ambient temp. tamin = –25°C, tamax = +45°C
über AL-Profil notwendig. L20c
62,5 mm/6 LED per step Sheet 1/2
VarioLED™ Flex RGB HD20 Art. # lumen/meter (lm/m) No need for additional heat 
Color (λ d)
Nähere Erläuterungen zu Änderungen, Grenz-
 Red (R) 88 W/22 Watt/meter 269 622sinking on AL profile.
werten und Schwankungen im Herstellungs-
Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 prozess finden Sie im LED Linear™ System-
Page 122 of 231
 Green (G)
Bulletin No. 145: Volume
10400
bis zu/up to 46,2 lumen/Watt
3 of 4 (Rev 07)
627 532 katalog, Seite 532. January 31, 2015
 Blue (B) 120 466 For more details regarding catalogue
Lumen gesamt (lm/m)
384 LED, 10,4 mm LED pitch
1.016
L80,
changes, min and max data sheet values
30.000 hrs
and production tolerances see the
24 Volt (23 Vmin, 25 Vmax)
Abu Dhabi Airports Company PJSC Specification, Section 265120

L20c
L20c L20c L20c

L20c L20c L20c L20c

Elevation of Centre Space Wayfinding Totems from MTC-A-94-TB-L_-_-0-00-09-045

L20c
L20c
L20c L20c

L20c
L20c L20c L20c

L20c
L20c L20c L20c

L20c L20c L20c L20c

The drawings on this page are


Detail 1 Detail 2 indicative. Refer to the architectural
Elevation of Centre Space Wayfinding Totems from MTC-A-94-TB-L_-_-0-00-09-045 drawings for correct setting out,
mounting details and final dimensions.

L20c

Type:
L20c
L20c L20c

L20c
L20c L20c L20c
L20c
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 123 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Continuous surface mounted linear profile

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 50W/m


Primary luminaire Extruded aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 3,240lm/m
Finish: See Notes Luminaire efficacy: 65lm/W
Accessories: See Notes Beam / distribution: Symmetric, see LDC
Project 1
Light source type: LED CRI / Colour temperature:
13.08.2014 > 80 / 3,000K

Driver type: Constant Current Operator Colour Variation:


Telephone
≤ 3 SDCM
Drive current or voltage: 1,200mA Fax
e-Mail Luminaire Lifetime: ≥ 50,000 hours
Dimming & type: DALI, integral Lifetime Basis: L70 / F10 @ Ta 250C
ARCHITECTURAL LIGHTING WORKS LPL2.5-500mm-HP14-3000K-EXT 500mm HP14
IP: IP20
3000K LED LUMINAIRE WITH WHITE INTERIOR AND FROSTED FLAT LENS /
Luminaire Data Sheet
U3
Luminaire distribution curve (LDC)
Luminous emittance 1: Location:
per 0.5m
See our luminaire catalog for an image of the Single Loaded Piers
luminaire.

superceded

42180995
Notes:
1. Refer to Section ‘2.0 Products’ of this
Times New Roman specification for additional requirements.
ur rendering index Ra 80; Total luminous flux of
luminous flux with LED converter. Slave luminaire for 2. Luminaire to be passively cooled.
d finish. Opal acrylic glass PMMA diffuser with
er 100% of its face. Luminaire comprises housing and 3. Continuous profiles to be supplied
g 2 fixing screws. Luminaire wired with halogen-free
g
with all necessary accessories including
Luminaire classification according to CIE: 100 Luminous emittance 1: mounting profiles, opal covers, brackets
CIE flux code: 56 85 97 100 100
and end caps.
4. Lengths required to be confirmed by
site measurement prior to ordering and
coordinated with Architect Engineer.
5. Fixtures to be of anodised aluminium
silver finish with opal cover.

ceiling level

superceded

ZS_SLO_M_2_LED_alle_600.wmf
structure to hold
fixture type L21
STD - standard

mps: 1 x LED-Z174 PM / 12W


tal luminous flux of luminaire: 858 lm The drawings on this page are
Page 1
minaire efficacy: 65 lm/W indicative. Refer to the architectural
ated life: 50000h L70 at 25°C fixture L21 drawings for correct setting out,
olour Rendering Index min.: 80 mounted in line
olour temperature: 3000 Kelvin with ceiling mounting details and final dimensions.
hromaticity tolerance (initial MacAdam): 4
llast: 1x LED_Con LED-Converter
onnected Load: 13.2 W Lambda = 0.98
mming: LDO dimmable to 10% over DALI Type:
aintenance category: D - Enclosed IP2X

L21
Sheet 1/2
Detail section of Single Loaded Pier from MTC-A-94-TB-L_-_-0-00-09-032 32

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 124 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
1 TYPE U3 - DETAIL OF UPLIGHT TO FACADE
Abu
SCALE Dhabi
1:10 Airports Company PJSC Specification, Section 265120

L21

4 TYPE L21 - DETAIL OF FLUORESCENT COVE 6 PIER CEILINGS - DETAIL 1


Detail 4 1:10
SCALE SCALE 1:10

Detail section of Single Loaded Pier from MTC-A-94-TB-L_-_-0-00-09-032

DE FIXING
STRUC
OTHER

MIN 150mm
MIN 15
XL2
U3

REFLECTOR TRAY WITH LAMP


AND CONTROL GEAR

2 TYPE U3 - UPLIGHT TO GLAZING FACADE 5 TYPE XL2 - SECTION THROUGH LANDSLIDE APRON FACADE
SCALE 1:10 SCALE 1:10

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

L21
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 125 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Wall recessed linear profile

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 50W


Primary luminaire Extruded aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 4,770lm
Finish: Anodised aluminium silver Luminaire efficacy: 94lm/W
Accessories: N/A Beam / distribution: Asymmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 4,000K
Driver type: Project 1 Constant current Colour Variation: 03.04.2014
≤ 3 SDCM
Drive current or voltage: 375mA Operator Luminaire Lifetime: ≥ 50,000 hours
Telephone
Dimming & type: DALI, integral Fax
e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: IP20
iGuzzini illuminazione S.p.A 12LED A60 PROFILO3 / Luminaire Data Sheet

Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
See our luminaire catalog for an image of the Single Loaded Piers
luminaire.

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
UP
2. Luminaire to be passively cooled.
3. Mounting details to be coordinated
with Architect architectural details.
Luminaire classification according to CIE: 100 Due to missing symmetry properties, no UGR table
CIE flux code: 22 58 94 100 100 can be displayed for this luminaire. 4. Luminaire to be centered in the middle
of the facade panel.
95

1200

The drawings on this page are


indicative. Refer to the architectural
101 Page 1 drawings for correct setting out,
mounting details and final dimensions.
120

Type:

L23
Sheet 1/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 126 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

L23

Detail 1
Section of Single Loaded Pier from MTC-A-03-TB-L_-_-1-00-00-483

1. FOR LIGHT FITTING INTEGRATION AND FIXING DETAILS


REFER TO A-94 & A-93 ARCHITECTURAL DRAWINGS AND
LIGHTING SPECIFICATIONS 265120

2. ARCHITECTURAL BACKGROUNDS ADDED FOR CLARITY

L23

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.

Type:

02 31.01.15 BULLETIN 145

L23
01 31.10.14 BULLETIN 120
00 15.07.12 ISSUED FOR CONSTRUCTION
6 PIER CEILINGS - DETAIL 1
Detail 6
SCALE 1:10
ISSUED FOR CONSTRUCTION
Sheet 2/2
Detail section of Single Loaded Pier from MTC-A-94-TB-L_-_-0-00-09-032
ABU DHABI
AIRPORTS COMPANY
Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 ABU DHABI AIRPORTS COMPANY Page 127 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) Kohn Pedersen Fox Associates
(International) PA
Architects and Planning Consultants
January 31, 2015
7a Langley Street
London WC2H 9JA
England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com

FIXING TO SOLID
STRUCTURE BY
OTHERS
MIN
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Surface mounted adjustable and lockable projector

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 55W


CATION
SPECIFICATION
SHEET luminaire
Primary SHEET Die-cast aluminium lumenbeam lumenbeam ™
Power factor:

> 0.9
Project 1 MEDIUM MEDIUM
construction material: WHITE & STATICRated luminous flux 15.03.2014
COLORS
WHITE & STATIC COLORS (lm): 1,880lm
Client:
Finish: Anodised aluminium silver Operator Luminaire efficacy: 34lm/W
Telephone
ame: Project name:
Accessories: Linear spread lens e-Mail Beam / distribution:
Fax
Asymmetric, see LDC
: Order #:
Light source type: LED CRI / Colour temperature: > 80 / 3,000K
Type: LUMENPULSE Qty:
LIGHTINGQty:
INC. LBL-120/277-40K-NS-LSLH-SI CAST SILVER PAINTED
Driver type: METAL UPPER HOUSING, ConstantCASTCurrent
SILVER PAINTED FINNED Colour METALVariation:
LOWER HOUSING, ≤ 3 SDCM
Drive current ONEor CIRCUIT
voltage: BOARD WITH 36 LEDS, ONE CLEAR PLASTIC
700mA Luminaire OPTIC BELOW EACH LED ≥ 50,000 hours
Lifetime:
NDFEATURES
BENEFITSAND BENEFITS WITH RECESSED MICRO-PRISMATIC BOTTOM CENTER, EACH OPTIC ENCASED IN A
Dimming & type: MOLDED BLACKDALI, integral
PLASTIC FRAME. SILVER PAINTED Lifetime
FLAT METAL Basis: BAFFLE, CLEAR L70 / F10 @ Ta 250C
l : Physical MICRO-LINEAR PRISMATIC PLASTIC INNER LENS, CLEAR FLAT GLASS OUTER LENS
IP:: IN CAST SILVER
pper content high pressure die-cast aluminum housing
IP66
•  Low copper content high pressure die-cast aluminum housing PAINTED METAL FRAME. LENS PRISMS DOWN AND PARALLEL
aluminum formed yoke (standard yoke included)
•  Heavy aluminum formed yoke (standard yoke included) WITH THE 0-DEGREE PLANE. / Luminaire Data Sheet
s steel hardware
•  Stainless steel hardware
 sealing devices
•  Silicone sealing devices
empered glass
•  Clear tempered glass
Light distribution curve
Luminous emittance 1: Location:
amber design for heat management and ease of maintenance
•  Dual chamber design for heat management and ease of maintenance
See our luminaire catalog for an image of the
statically applied polyester powder coat finish
•  Electro-statically applied polyester powder coat finish Welcomers Hall
g / 6.7 lbs
•  3.05 kg / 6.7 lbs luminaire.
ont = 0.46 sq. ft./0.042 sq. m. Side = 0.37 sq. ft./ 0.034 sq. m.
•  EPA: Front = 0.46 sq. ft./0.042 sq. m. Side = 0.37 sq. ft./ 0.034 sq. m. Baggage Reclaim
•  IP66
on-resistant option for marine environments
•  Corrosion-resistant option for marine environments Arrival Lobby
ance :
Performance :
m 1fc (10.7 lux) @ 238 feet (72.5m) distance (4000K, 6° optic)
•  Minimum 1fc (10.7 lux) @ 238 feet (72.5m) distance (4000K, 6° optic)
delivered lumens and 56,521 candelas at nadir
•  1,400 delivered lumens and 56,521 candelas at nadir
K, 6° optic)
    (4000K, 6° optic)
°, 20°, 40° or 60° optics available
•  6°, 10°, 20°, 40° or 60° optics available Wiring detail Wiring detail
ue: 78+ 
•  CRI value: 78+  Notes:
maintenance 120,000 hrs
•  Lumen maintenance 120,000 hrs
[L70 @ 25°C] [L70 @ 25°C] WIRE COLOR / USE
WIRE COLOR / USE
measurements comply with LM - 79 - 08 standard
•  Lumen measurements comply with LM - 79 - 08 standard GREEN GROUND
GREEN GROUND 1. Refer to Section ‘2.0 Products’ of this
ng temperatures:  -25° C to 50° C [-13F to 122F]
•  Operating temperatures:  -25° C to 50° C [-13F to 122F] WHITE NEUTRAL
WHITE NEUTRAL
BLACK LIVE
BLACK
120-277V LIVE 120-277V specification for additional requirements.
al : Electrical :
L5
RED 0-10V
RED / DATA + 0-10V / DATA +
age luminaire for 120 to 277V
•  Line voltage luminaire for 120 to 277V ORANGE 0-10V
ORANGE/ DATA - 0-10V / DATA - 2. Luminaire to be passively cooled.
• Power and data in 1 cable, 3ft/1 m cord (#16-5)
and data in 1 cable, 3ft/1 m cord (#16-5)
ts •  28 watts 3. Luminaire with adjustable and
olt, DMX or DALI dimming options
•  0-10 volt, DMX or DALI dimming options
lockable mechanism for aiming.
Luminaire classification according to CIE: 100 Luminous emittance 1:
9 CIE flux
9 code: 93 97 100 100 108
4 16" "
4 16 0° 0°
[116mm] [116mm]

7 7
7  8 " 7  8 "
[200mm] [200mm]
75° 75°
L4
1" 1" 90° 90°
7 4 7 4
[184mm] [184mm]
9 9
10 " 10 "
16 16
[268mm] [268mm]

superseded

170° 170°
Standard Yoke Mounting
Standard Yoke Mounting
Standard Yoke (as shown, included)
ranty 5 year warranty Standard Yoke (as shown, included) Adjustable pivot limits
Adjustable pivot limits

1/9
lse, 1751 Richardson,Lumenpulse,
Suite 1505,1751
Montreal
Richardson,
(Quebec)Suite
Canada
1505,H3K
Montreal
1G6 (Quebec)
1.877.937.3003
Canada H3K
P. 514.937.3003
1G6 1.877.937.3003
F. 514.937.6289
P. 514.937.3003 F. 514.937.6289
info@lumenpulse.com www.lumenpulse.com
info@lumenpulse.com www.lumenpulse.com
Copyright © 2013 Lumenpulse
Copyright © 2013 Lumenpulse
2013.11.05
Lumenpulse reserves the right
Lumenpulse
to makereserves
changesthe
to right
this product
to makeatchanges
any timetowithout
this product
prior at
notice
any time without prior notice
and such modification shall
andbesuch
effective
modification
immediately.
shall be effective immediately.
EM - R19

Page 1

The drawings on this page are


S1 indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.

L4 L5c

Type:

Detail 2
S1
Detail section through coffer panel end from MTC-A-94-TB-L_-_-0-00-09-033 033

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 128 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Surface mounted adjustable and lockable projector

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 25W


Primary luminaire Die-cast aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 1,880lm
Finish: Anodised aluminium silver Luminaire efficacy: 75lm/W
Accessories: N/A See Notes Beam / distribution: Symmetric, see LDC
Light sourceProject
type: 1 LED CRI / Colour temperature: > 80 / 3,000K
Driver type: Constant current Colour Variation: 03.04.2014
≤ 3 SDCM
Operator
Drive current or voltage: 600mA Telephone Luminaire Lifetime:
Fax
≥ 50,000 hours
Dimming & type: DALI, integral e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: IP20 S.p.A MT44_LU20 Palco: warm white medium body spotlight -
iGuzzini illuminazione
DALI ballast- flood optic / Luminaire Data Sheet

Luminaire distribution curve (LDC)


Luminous emittance 1: Location:
See our luminaire catalog for an image of the Pier chandeliers
luminaire.

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Luminaire to be passively cooled.
3. Luminaire with adjustable and
168 lockable mechanism for aiming.
Luminaire classification according to CIE: 100 Luminous emittance 1:
CIE flux code: 99 100 100 100 106 4. To be supplied with all necessary
mounting accessories.

18xU1b

240
Ø1
40

199

U1b U1b

The drawings on this page are


indicative. Refer to the architectural
Page 1
S1b drawings for correct setting out,
mounting details and final dimensions.

Type:

Detail 6
S1b
Detail section through Type C Chandelier body from MTC-A-94-TB-L3-0-0-00-09-018

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 129 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Surface mounted adjustable and lockable projector

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 43W


Primary luminaire Aluminium alloy Power factor: > 0.9
construction material:
Woody Rated luminous flux (lm): 2,800lm
Finish: Anodised aluminium silver Luminaire efficacy: 65lm/W
Design Mario Cucinella
Accessories: Tree strap iGuzzini
Beam / distribution: Symmetric, see LDC
Light sourceProject
type:1 LED CRI / Colour temperature: > 80 / 3,000K
Driver type: Woody
august
Constant current 2014 Colour Variation: 19.08.2014
≤ 3 SDCM
Operator
Drive current or voltage: 700mA Telephone Luminaire Lifetime: ≥ 50,000 hours
Design Mario Cucinella Fax
iGuzzini
Dimming & type: DALI, integral e-Mail
Lifetime Basis: L70 / F10 @ Ta 600Cv
IP: IP67
iGuzzini illuminazione S.p.A Woody
BU95_LW66 MaxiWoody (compact): Spotlight with bracket
august 2014
- Warm White COB Led - integrat... / Luminaire Data Sheet

Luminaire distribution curve (LDC)


Luminous emittance 1: Location:
code
Woody
See our luminaire catalog for an image of the
BU95 Landscaping
luminaire.

code
Technical
BU95 description
Spotlight designed to use Warm White COB LED lamps and a 10° spot optic. Can b
anchors) and on pole mounting systems. Consists of an optic assembly, componen
Technical description
optical assembly, component box, and glass-holder Notes:frame are made of EN1706AC 4
Spotlight designed to use Warm White COB LED lamps and a 10° spot optic. Can be installed at 
multi-step,
anchors) andpre-treatment
on pole mounting process,
systems.inConsists
which the main
optictophases
of 1. Refer
an are
Section ‘2.0
assembly, degreasing,
Products’
component box, fluoroz
of this glass-ho
specification for additional requirements.
(with a nano­structured silane layer). The next painting stage consists of a primer a
optical assembly, component box, and glass-holder frame are made of EN1706AC 46100LF alum
multi-step, pre-treatment process, in which the main phases are
2. Luminaire
high level of weather and UV ray resistance. The 4 mm thick, tempered, sodium-ca degreasing,
to be passivelyfluorozirconation
cooled. (a p
(with a nano­structured silane layer). The next painting stage consists of a primer and a liquid acr
3. Luminaire
and a seal is included. The 50/60 Shore A silicone seal is subjected to a post­curing
with adjustable and
high level of weather and UV ray resistance. The 4 mm thick,mechanism
lockable tempered,forsodium-calcium,
aiming. closing
Luminaire classification according to The glass unit
CIE: 100 is fixed
Luminous to1:the frame with silicone. The product comes complete with
emittance
CIE flux code: 99 100 100 100 70 and a seal is included. The 50/60 Shore A silicone seal is subjected to a post­curing treatment, in
circuit,
The glass anunit
optic withtoathe
is fixed 99.93% super-pure
frame with aluminium
silicone. The OPTIBEAM
product comes complete reflector withwhite
with a warm a po
ballast. Zinc-coated stainless steel ballast holding plate; simplified
circuit, an optic with a 99.93% super-pure aluminium OPTIBEAM reflector with a polished, anodize extraordinary ma
between the control gear and the LED and the control gear and the wiring terminal
ballast. Zinc-coated stainless steel ballast holding plate; simplified extraordinary maintenance thab
between the control gear and the LED and the control gear and
cover, complete with spacers and captive screws. The floodlight can be adjusted bythe wiring terminal block. Painted
cover, complete with spacers and captive screws. The floodlight can be adjusted by ±115° in the v
bracket, with a graduated scale showing 10° steps and mechanical stops to guaran
bracket, with a graduated scale showing 10° steps and mechanical stops to guarantee stable aim
aiming
aiming isisperformed
performed usingusing the holes
the holes andinslots
and slots in the Access
the bracket. bracket. to Access
the opticaltoassembly
the opticalis s
brass decompression valve which eliminates the
brass decompression valve which eliminates the product internal vacuum. product internal
U1c vacuum. Set up for
Set up for pass-through
nickel­plated brass cable gland (suitable for cables with 7÷16mm diameter). All exte
nickel­plated brass cable gland (suitable for cables with 7÷16mm diameter). All external screws u
and
and areareofofthe
the captive
captive type. type. The luminaire
The luminaire technical
technical characteristics
characteristics conform to conform
EN60598-1 tostandar
EN60

Installation
Installation
The luminaire can be floor, ceiling or wall-mounted using the supporting bracket fixed with screw a
The luminaire
concrete, cementcan
andbe floor,
solid brickceiling or wall-mounted
or various using the supporting
other available accessories. bracket
It can also be fixe
installed on
concrete,
system. cement and solid brick or various other available accessories. It can also
system.
S3 Size (mm) The drawings on this page are
ø260x296 indicative. Refer to the architectural
Size (mm) Page 1
drawings for correct setting out,
ø260x296 mounting details and final dimensions.
Colour
Grey (15)
Colour Type:
Grey (15)
Weight (kg)

Detail 4
4.57
S3
Weight (kg)
Detail of Departures kerb planter from MTC-A-94-TB-L_-_-0-00-09-030
Mounting4.57
wall arm | pole arm | ground surface | wall surface | ground anchored | wall bracket | ceiling surface
Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 130 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Mounting
Wiring info
wall arm | pole arm | ground surface | wall surface | ground anchored | wall bracket |
Control gear complete with DALI dimmable electronic ballast (220÷240V ac 50/60Hz) and quick­co
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Surface mounted adjustable and lockable projector

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 25W


Primary luminaire Aluminium alloy Power factor: > 0.9
construction material: Rated luminous flux (lm): 1,425lm
Finish: Anodised aluminium silver Luminaire efficacy: 57lm/W
Accessories: Earth mounting spike Beam / distribution: Symmetric, see LDC
Light sourceProject
type:1 LED Woody CRI / Colour temperature: > 80 / 3,000K
Driver type: Woody
Constant current Colour Variation: 13.08.2014
≤ 3 SDCM
Operator
Drive current or voltage:
Design Mario Cucinella 500mA Telephone Luminaire
iGuzzini Lifetime: ≥ 50,000 hours
Design Mario Cucinella Fax
iGuzzini
Dimming & type: DALI, remote e-Mail
Lifetime Basis: L70 / F10 @ Ta 600C
IP: august
IP66 S.p.A
iGuzzini illuminazione
2014
BU83_LW70 Woody: Spotlight with base - Warm White
august 2014
COB Led - integrated electronic con... / Luminaire Data Sheet

Luminaire distribution curve (LDC)


Luminous emittance 1: Location:
Woody
Woody
See our luminaire catalog for an image of the Landscaping
luminaire.

code
code
BU83
BU83

Technical description
Technical description
Spotlight designed to use LED lamps and a spot optic. Notes:
Consists of an optical assembly and a ba
Spotlight designed
base and frame holder to use
areLEDmade lamps and a spot46100LF
of EN1706AC optic. Consists
aluminium of an
alloyoptical assembly to
and subjected and a ba
a multi
base and frame holder are made of EN1706AC 1. Refer
46100LF to Section
aluminium ‘2.0 Products’
alloy and of this to a multi
subjected
which the main phases are degreasing, fluorozirconation (a protective
specification surface
for additional film) and sealing (w
requirements.
which the main phases are degreasing, fluorozirconation (a protective surface film) and sealing (w
The next painting stage consists of a primer and a liquid acrylic paint, cured at 150°C, with a high 
The next painting stage consists of a primer and a liquid acrylic paint, cured at 150°C, with a high 
2. Luminaire to be passively cooled.
resistance. The 4 mm thick, tempered, sodium-calcium, closing glass is colourless, transparent a
resistance. The 4 mm thick, tempered, sodium-calcium, closing glass
3. Luminaire is colourless,
with adjustable and
The 50/60 Shore A silicone seal has been subject to post­cooling treatment, in an oven, for 4­6 ho transparent a
The 50/60 Shore A silicone seal has been subject to post­cooling treatment, in an oven, for 4­6 ho
lockable mechanism for aiming.
Luminaire classification according to assembly
CIE: 100 allows vertical
Luminous and1:horizontal adjustments, with the possibility of locking the adjustmen
emittance
CIE flux code: 99 100 100 100 75 assembly allows
frame for rainwater vertical and The
drainage. horizontal adjustments,
optic has with be
a 99.93% 4. To thesupplied
super-purepossibility
with aofspike
aluminium locking
reflector the
for earth adjustmen
with a polishe
frame for rainwater drainage. The optic has a 99.93% super-pure
mounting. aluminium
with Warm White colour monochrome LED circuit. The cable gland for connecting the wiring reflector with a polishe
asse
with Warm White colour monochrome LED circuit. The cable gland for connecting
made of M11x1 stainless steel. For the power supply, the device is fitted with a black polyamide the wiring asse
P
made
to 11.5ofmm M11x1 stainless
cables. steel. For
All external the used
screws powerare
supply,
madethe device
of A2 is fitted
stainless withThe
steel. a black polyamide
luminaire technP
to 11.5 mm standards
EN60598-1 cables. Alland
external screws
particular used are made of A2 stainless steel. The luminaire techn
requirements.
EN60598-1 standards and particular requirements.
Stainless steel plate with spike
Installation
Design Mario Cucinella Installation
The luminaire can be floor, ceiling or wall-mounted
iGuzzini using either screw anchors for concrete, cemen
The luminaire can be
available accessories.floor, ceiling or wall-mounted using either screw anchors for concrete, cemen
April available
2014 accessories.

earth mounting spike Size (mm)


Size (mm)
ø140x230
Stainless steel plate with spike - Stainless steel plate with spike for installation in gardens
ø140x230

Colour
Product code:
Colour
B989Black (04) | Grey (15)
Black (04) | Grey (15)
Technical description:
The drawings on this page are
Weight
Stainless steel (kg)
plate with spike for installation in gardens
indicative. Refer to the architectural
Weight
2.10 (kg) Page 1
Colour: drawings for correct setting out,
2.10 mounting details and final dimensions.
Indeterminate (00)
Mounting
Weight [Kg]:
Mounting
0,22 wall arm | wall surface | ground anchored | ground spike | ceiling surface
Type:
wall arm | wall surface | ground anchored | ground spike | ceiling surface

Wiring info
Wiring info
Control gear complete with electronic ballast (220÷240Vac 50/60Hz)
Control gear complete with electronic ballast (220÷240Vac 50/60Hz)
S4
Sheet 1/2
Complies with
Complies with
Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 131 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

S4

Detail 7
Detail of Departures kerb planter from MTC-A-94-TB-L_-_-0-00-09-030

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

S4
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 132 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Surface mounted adjustable and lockable projector

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 62W


Primary luminaire Die-cast aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 4,750lm
Finish: Anodised aluminium silver Luminaire efficacy: 77lm/W
Accessories: N/A See Notes Beam / distribution: Symmetric, see LDC
Light sourceProject
type: 1 LED CRI / Colour temperature: > 80 / 3,000K
Driver type: Constant current Colour Variation: 03.04.2014
≤ 3 SDCM
Operator
Drive current or voltage: 1,050mA Telephone Luminaire Lifetime:
Fax
≥ 50,000 hours
Dimming & type: DALI, remote e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: IP20 S.p.A. Eulumdat wide flood 48g TZ90 wide flood 48g TZ90 D8B
iGuzzini Illuminazione
D8C D8D / Luminaire Data Sheet

Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
See our luminaire catalog for an image of the Departures Hall chandeliers
luminaire.
Centre Space chandeliers

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Luminaire to be passively cooled.
3. Luminaire with adjustable and
lockable mechanism for aiming.
Luminaire
168 classification according to CIE: 100 Luminous emittance 1:
CIE flux code: 99 100 100 100 80 4. To be supplied with all necessary
mounting accessories.

240
Ø1
40

199

The drawings on this page are


Page 1
indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.

Type:

S6
Sheet 1/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 133 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

U1 U1 U1 U1
U1 U1

S6 S6

S6

L2q L2q L2q L2q L2q L2q


L2q L2q L2q L2q L2q

Detail 3
Type A Chandelier detail and section from MTC-A-94-TB-L3-0-0-00-09-004

U1 U1

S6

L2q L2q L2q

Detail 4
Type B Chandelier detail and section from MTC-A-94-TB-L3-0-0-00-09-004

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

S6
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 134 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Surface mounted adjustable and lockable projector

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 82W


Primary luminaire Die-cast aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 6,040lm
Finish: Anodised aluminium silver Luminaire efficacy: 74lm/W
Accessories: See Notes Beam / distribution: Asymmetric, see LDC
Light sourceProject
type: 1 LED CRI / Colour temperature: > 80 / 4,200K
27.10.2014
Driver type: Constant current Operator
Colour Variation: ≤ 3 SDCM
Drive current or voltage: 500mA Telephone
Fax Luminaire Lifetime: ≥ 50,000 hours
e-Mail
Dimming & type: DALI, remote Lifetime Basis: L70 / F10 @ Ta 250C
IP: IP4448, 4200K, 40x12 Degree ACDC1188-48/42/40x12 / Luminaire
ACDC Lighting Fusion
Data Sheet
Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
See our luminaire catalog for an image of the Sana Al-Nour artwork
luminaire. acdclighting.com/LED/FUSION
acdclighting.com/LED/FUSION
acdclighting.com/LED/FUSION

48
48
N 48
Notes:

nt,
elligent,
nt,highly
highlyhighly
efficient,
efficient,
efficient,
IP66
IP66architectural
architectural
IP66 architectural
LED
LEDfloodlights
floodlights
LED floodlights
delivering
delivering
delivering
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
m
000lm
ininsingle
single
in single
colour,
colour,
colour,
with
withcolour
colour
with colour
change
changechange
or
ordynamic
dynamic
or dynamic
white
whitewhite
options
options
options
2. Luminaire to be passively cooled.
viding
gphotometric
photometric
photometric
performance
performance
performance
ofof17
17lux
of
lux17
at
atlux
aadistance
distance
at a distance
ofof90m*
90m*
of 90m*3. Luminaire with adjustable and
lockable mechanism for aiming.
t 500mA. Luminaire classification according to CIE: 99 Due to missing symmetry properties, no UGR table
CIE flux code: 94 98 100 99 100 can be displayed for this luminaire. 4848
top
top topMock-up sample to be provided.
484.
0º 0º 0º S8 Final selection of optical control to be
confirmed during site mock-up.
+50º
+50º +50º
288.5mm
288.5mm

288.5mm

+45º
+45º +45º -45º
-45º -45º
-95º
-95º -95º

357mm
357mm 357mm 140mm
140mm 140mm
0º 0º 0º

Performance
Performance
Performance
ngse
s made
housings
madefrom from
made
high
highfrom
pressure,
pressure,
high die cast,dieLumen
pressure,
diecast, Lumen
cast, Maintenance:
Maintenance:
Lumen Maintenance: High
Highefficiency
efficiency
High efficiency
LEDs
LEDstested
tested
LEDs
totoLM80
tested
LM80standards,
to
standards,
LM80 standards,
m.
aluminium.
m.Specialist
Specialist Specialist
Alodine®
Alodine® Alodine®
treatment
treatment treatment 50,000hrs
50,000hrslifetime
50,000hrs
lifetimewithwith
lifetime
lumen
lumen
with
maintenance
maintenance
lumen maintenanceatatL70.
L70. at L70.
wder
owder
stagecoatingpowder
coatingpaint coating
paintprocess
process
paint process Initial
Initiallamp
lamp
Initial
Lumen
Lumen
lamp output**:
output**:
Lumen 8563lm
output**:
8563lm 8563lm
nce
performance
anceinineven eventhe the
in harshest
even
harshest
theexternal
harshest
externalexternal
Lamp
Lamplumenslumens
Lamp inc
inc
lumens
thermal
thermal incand
thermal
andoptical
optical
and losses**:
losses**:
optical8135lm
losses**:
8135lm 8135lm
*. Luminaire
Luminaire Luminaire
Lumens
Lumens output**:
Lumens
output**: output**:
7526lm
7526lm 7526lm
0º,
0ºx x12º
64º,
12ºlinear.
40º
linear.
x 12º linear. Power
Powerconsumption
consumption
Power consumption (inc
(inc85%
85%efficient
(inc
efficient
85%driver):
efficient
driver):8282
driver): 82
ground
,t,ground
louvre, spike,
spike,
ground wall
wall
spike,
armarmbracket,
wall
bracket,
S7 arm1m,bracket,
1m, Efficacy
Efficacy
1m, (Lm/W)**:
Efficacy
(Lm/W)**: (Lm/W)**:
92 92 92
m,
ables.
10m,10m,1m,
20m,
20m, 10m,
supply
supply
20m,cable.
cable.
supply T-Piece
T-Piece
cable. T-Piece CRI:
CRI:8080 CRI: 80
The drawings on this page are
Binning:
Binning:Colour
Binning:
Colourconsistency
consistency
Colour consistency
ensured
ensuredacross
ensured
acrossa aproject
across
project a- 2-project
2step
step - 2 step
e k,
ck,twist
one
one lock,
tool
tool installation
one
installation
tool installation
andand the
the and the MacAdam Page 1 indicative. Refer to the architectural
MacAdam MacAdam
ellipse.
ellipse. ellipse.
ple,
e,
ures one
one
simple,
person
persononeinstallation
installation
person installation S7 drawings for correct setting out,
LED
LEDColour:
Colour:
LED Colour:
2700°K,
2700°K, 3000°K,
3000°K,
2700°K, 4200°K,
4200°K,
3000°K, 6000°K,
6000°K,
4200°K, 2700ºK/6000ºK.
2700ºK/6000ºK.
6000°K, 2700ºK/6000ºK.
(Dynamic
(Dynamic(Dynamic
mounting details and final dimensions.
rward
95°
-95°backback
or -95°
andandback
rotates
rotates
and+ +/-
rotates
/-45°
45°from
from
+ /-0°
45°
0° from
White),0° RGB,
White), RGB,
White),
RGBA,
RGBA,
RGB,RGBW,
RGBW,
RGBA,R,R,G,
RGBW,
G,B,B,A.A.
R, G, B, A.
mo50°C-10°C
50°C to 50°C Driver:
Driver:Switched,
Driver: Switched,
Switched, DMX
DMX DMX
ce Listings:
Listings:CE,Listings:
CE,ETL ETLus/c
us/c
CE,pending
ETL
pending
us/c pending
Type:
board
rmal
ermalmanagement
thermal
management management
automatically
automaticallyautomatically IPIPrating:
rating:IP66
IPIP66
rating: IP66
atures
ures
emperatures
exceed
exceed50°C exceed
50°Cwithwith50°C
temperature
temperature
with temperatureWarranty:
Warranty: Warranty:
5 5years
years 5 years

S7
ms
ure
e tocolour
colour
ensure ininconsistency
colour
consistency eveninin even inWeight:
in consistency
even Weight:5.4kgWeight: 5.4kg
5.4kg
ent.
nvironment.
t. **Based
**Basedon **Based
on3000ºK
3000ºK on
with
with
3000ºK
10º
10ºoptics
with
optics10º optics
dual
te
oteconfiguration Detail
configuration
remote 3
configuration
mming
ozero,
zero,using
usingDetail
to zero, section
Hydradrive
Hydradrive
using through
drive Sana
Hydradrive
drive drive Al-Nour artwork from MTC-A-51-TB-L_-_-_-__-00-105

m
uantity
quantity
orderapplies.
quantity
applies. applies.
Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 135 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
s
ct Size Finish
Finish Finish Colour
ColourTemp
Temp
Colour Temp Optics
Optics Optics Accessories
AccessoriesAccessories
48 48White
White WHI
WHI
White WHI 2700ºK
2700ºK 2700ºK 2727 27 10º10º 10R
10R
10º 10R None
None NN
None N
3000ºK
3000ºK 3000ºK 3030 30
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Surface mounted adjustable and lockable projector

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 80W


Primary luminaire Die-cast aluminium Power factor: > 0.5
construction material: Rated luminous flux (lm): 2,400lm
Finish: Anodised aluminium silver Luminaire efficacy: 30lm/W
Accessories: See Notes Beam / distribution: Asymmetric, see LDC
Light sourceProject
type: 1 LED CRI / Colour temperature: N/A / RGB
27.10.2014
Driver type: Constant current Operator
Colour Variation: N/A
Drive current or voltage: 500mA Telephone
Fax Luminaire Lifetime: ≥ 50,000 hours
e-Mail
Dimming & type: DALI, remote Lifetime Basis: L70 / F10 @ Ta 250C
IP: IP4448, 4200K, 40x12 Degree ACDC1188-48/42/40x12 / Luminaire
ACDC Lighting Fusion
Data Sheet
Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
See our luminaire catalog for an image of the
luminaire.
acdclighting.com/LED/FUSION
acdclighting.com/LED/FUSION
acdclighting.com/LED/FUSION
Sana Al-Nour artwork

48
48
N 48
Notes:
nt,
elligent,
nt,highly
highlyhighly
efficient,
efficient,
efficient,
IP66
IP66architectural
architectural
IP66 architectural
LED
LEDfloodlights
floodlights
LED floodlights
delivering
delivering
delivering
1. Refer to Section ‘2.0 Products’ of this

m
000lm
ininsingle
single
in single
colour,
colour,
colour,
with
withcolour
colour
with colour
change
changechange
or
ordynamic
dynamic
or dynamic
white
whitewhite
options
options
options
specification for additional requirements.
2. Luminaire to be passively cooled.
viding
gphotometric
photometric
photometric
performance
performance
performance
ofof17
17lux
of
lux17
at
atlux
aadistance
distance
at a distance
ofof90m*
90m*
of 90m*3. Luminaire with adjustable and
t 500mA. lockable mechanism for aiming.
Luminaire classification according to CIE: 99 Due to missing symmetry properties, no UGR table
4848
top
top 48 top
CIE flux code: 94 98 100 99 100 can be displayed for this luminaire. S8 4. Mock-up sample to be provided.
0º 0º 0º
Final selection of optical control to be
confirmed during site mock-up.
+50º
+50º +50º
288.5mm
288.5mm

288.5mm

+45º
+45º +45º -45º
-45º -45º
-95º
-95º -95º

357mm
357mm 357mm 140mm
140mm 140mm
0º 0º 0º

Performance
Performance
Performance
ngse
s made
housings
madefrom from
made
high
highfrom
pressure,
pressure,
high die cast,dieLumen
pressure,
diecast, Lumen
cast, Maintenance:
Maintenance:
Lumen Maintenance: High
Highefficiency
efficiency
High efficiency
LEDs
LEDstested
tested
LEDs
totoLM80
tested
LM80standards,
to
standards,
LM80 standards,
m.
aluminium.
m.Specialist
Specialist Specialist
Alodine®
Alodine® Alodine®
treatment
treatment treatment 50,000hrs
50,000hrslifetime
50,000hrs
lifetimewithwith
lifetime
lumen
lumen
with
maintenance
maintenance
lumen maintenanceatatL70.
L70. at L70.
wder
owder
stagecoatingpowder
coatingpaint coating
paintprocess
process
paint process Initial
Initiallamp
lampInitial
Lumen
Lumen
lamp output**:
output**:
Lumen 8563lm
output**:
8563lm 8563lm
nce
performance
anceinineven eventhe the
in harshest
even
harshest
theexternal
harshest
externalexternal
Lamp
Lamplumenslumens
Lamp inc
inc
lumens
thermal
thermal incand
thermal
andoptical
optical
and losses**:
losses**:
optical8135lm
losses**:
8135lm 8135lm
*. Luminaire
Luminaire Luminaire
Lumens
Lumens output**:
Lumens
output**: output**:
7526lm
7526lm 7526lm
0º,
0ºx x12º
64º,
12ºlinear.
40º
linear.
x 12º linear. Power
Powerconsumption
consumption
Power consumption (inc
(inc85%
85%efficient
(inc
efficient
85%driver):
efficient
driver):8282
driver): 82
ground
,t,ground
louvre, spike,
spike,
ground wall
wall
spike,
arm
S7
armbracket,
wall
bracket,
arm1m, bracket,
1m, Efficacy
Efficacy
1m, (Lm/W)**:
Efficacy
(Lm/W)**: (Lm/W)**:
92 92 92
m,
ables.
10m,10m,1m,
20m,
20m, 10m,
supply
supply
20m,cable.
cable.
supply T-Piece
T-Piece
cable. T-Piece CRI:
CRI:8080 CRI: 80
Binning:
Binning:Colour
Binning:
Colourconsistency
consistency
Colour consistency
ensured
ensuredacross
ensured
acrossa aproject
across
project a- 2-project
2step
step - 2 step
The drawings on this page are
e k,
ck,twist
one
one lock,
tool
tool installation
one
installation
tool installation
andand the
theS7 and the MacAdam
MacAdam MacAdam
ellipse.
ellipse. ellipse. Page 1 indicative. Refer to the architectural
ple,
e,
ures one
one
simple,
person
persononeinstallation
installation
person installation LED
LEDColour:
Colour:LED Colour:
2700°K,
2700°K, 3000°K,
3000°K,
2700°K, 4200°K,
4200°K,
3000°K, 6000°K,
6000°K,
4200°K, 2700ºK/6000ºK.
2700ºK/6000ºK.
6000°K, 2700ºK/6000ºK.
(Dynamic
(Dynamic(Dynamic
drawings for correct setting out,
rward
95°
-95°backback
or -95°
andandback
rotates
rotates
and+ +/-
rotates
/-45°
45°from
from
+ /-0°
45°
0° from 0° RGB,
White),
White), RGB,
White),
RGBA,
RGBA,
RGB, RGBW,
RGBW,
RGBA,R,R,G,
RGBW,
G,B,B,A.A.
R, G, B, A. mounting details and final dimensions.
mo50°C-10°C
50°C to 50°C Driver:
Driver:Switched,
Driver: Switched,
Switched, DMX
DMX DMX
ce Listings:
Listings: Listings:
CE,
CE, ETL
ETLus/c
us/c
CE, pending
ETL
pending
us/c pending
board
rmal
ermalmanagement
thermal
management management
automatically
automaticallyautomatically IPIP
rating:
rating: IP
IP66 rating:
IP66 IP66 Type:
atures
ures
emperatures
exceed
exceed50°C exceed
50°Cwithwith50°C
temperature
temperature
with temperatureWarranty:
Warranty: Warranty:
5 5years
years 5 years
ms
ure
e tocolour
colour
ensure ininconsistency
colour
consistency eveninin even inWeight:
in consistency
even Weight:5.4kg Weight: 5.4kg
5.4kg
ent.
nvironment.
t.
dual
te
oteconfiguration
Detail 3
configuration
remote configuration
**Based
**Basedon **Based
on3000ºK
3000ºK on
with
Detail section through Sana Al-Nour artwork from MTC-A-51-TB-L_-_-_-__-00-105
with
3000ºK
10º
10ºoptics
with
optics10º optics
S8
mming
ozero,
zero,using
using
to zero,
Hydradrive
Hydradrive
using Hydradrive
drive
drive drive
Note S8 fixtures located at same position as S7 fixtures
m
uantity
quantity
orderapplies.
quantity
applies. applies.
Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 136 of 231
s Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
ct Size Finish
Finish Finish Colour
ColourTemp
Temp
Colour Temp Optics
Optics Optics Accessories
AccessoriesAccessories
48 48White
White WHI
WHI
White WHI 2700ºK
2700ºK 2700ºK 2727 27 10º10º 10R
10R
10º 10R None
None NN
None N
3000ºK
3000ºK 3000ºK 3030 30
Black
Black BLK
BLK
Black BLK 16º16º 16R
16R
16º 16RLouvre
Louvre
&& Louvre &LVR
Snoot
Snoot LVR
Snoot LVR
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: LED modular element for ceiling uplighting

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 100W


Primary luminaire Die-cast aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 10,500lm
Finish: Anodised aluminium silver Luminaire efficacy: 105lm/W
Accessories: N/A See Notes Beam / distribution: Asymmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 4,000K
Driver type: Constant
27.03.2014
current Max Colour Variation: ≤ 3 SDCM
Drive
Operator current or voltage: 420mA Luminaire Lifetime: ≥ 50,000 hours
Telephone
DimmingFax
e-Mail
& type: DALI, remote Lifetime Basis: L70 / F10 @ Ta 400C
IP / IK rating: IP65
65 (Profile_03)-Provvisorio / Luminaire Data Sheet

Luminous emittance 1: Location:


he Departures Hall chandeliers
Centre Space chandeliers

Notes:

1. Refer to Section ‘2.0 Products’ of this specification for additional


requirements.
2. Luminaire to be passively cooled.
UP 3. Weight of remote driver and luminaire (including bracket and

Main Chandelier Redesign accessories) to be less than 16kg.


4. Operating temperature rating for luminaires shall be between
-40°C and +40°C at a minimum Relative Humidity (RH) of 95%.
00 Due to missing symmetry properties, no UGR table
can be displayed for this luminaire. 5. Storage (i.e. non-operating/daytime) temperature: all fixture
components to be designed to tolerate between -40°C and +80°C
at a minimum maximum 95% Relative Humidity (RH).
6. All luminaires to have some means of built-in overheat thermal
protection in the form of an automatic dimming or stepping/holding
down of the driver where temperature exceeds operational limits.
7. Both LED module and driver shall be able to be replaced without
soldering or sending the luminaire back to the manufacturer.
Quick-connect devices are required.
8. Exact positioning of LED modules to be coordinated with
Architect architectural details.
9. Fixtures to be supplied with all necessary accessories including
mounting profiles.
10. Contractor to provide setting out of light fixtures for
Engineer’s approval.
Top View – Chandelier
Top viewno 1,10- Chandelier no 1,10 (50 U1 fixtures)
6.3m

The drawings on this page are


indicative. Refer to the architectural
Page 1 drawings for correct setting out,
mounting details and final dimensions.

Type:

Top View – Chandelier no 5-7, 14-16 Typical Section – Chandelier no 1,10 U1


Sheet 1/5
Top view - Chandelier no 5-7, 14-16 (48 U1 fixtures)

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 137 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Top view Fixtures in cluster configuration (top view)

Space between single fixtures


L < 550mm
U1 U1

S > 150mm
To remote driver
U1 U1
W < 400mm

Glass cover

Side view
Die cast Aluminium body
H4 > 300mm H1 < 100mm
H3 < 600mm

H2 < 100mm

Remote driver

Support to hold fixture above


driver and allow for ventilation

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.

Type:

U1
Sheet 2/5

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 138 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Fixtures in cluster
configuration (top view)
Space between single fixtures

The drawings on this page are


U1 U1 indicative. Refer to the architectural
drawings for correct setting
S > 150mm

out, mounting details and final


U1 U1 dimensions.

Type:

U1
Sheet 3/5

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 139 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

50 x U1 48 x U1
12 x S6 8 x S6

1 TYPE A CHANDELIER PLAN 2 TYPE B CHANDELIER PLAN


Detail 1
SCALE 1:50 SCALE 1:50

TYPE U1 LIGHT

U1 U1

U1 U1

TYPE S6 LIGHT

TYPE S6 LIGHT
U1 U1 U1 U1
4 x TYPE L2q LIGHT 4 x TYPE L2q LIGHT 3 x TYPE L2q LIGHT U1 U1

S6 S6

S6

L2q L2q L2q L2q L2q L2q


L2q L2q L2q L2q L2q

3 TYPE A CHANDELIER DETAIL & SECTION 4 TYPE B CHANDELIER DETAIL & SECTION
SCALE 1:50 SCALE 1:50

Detail 3
Type A Chandelier detail and section from MTC-A-94-TB-L3-0-0-00-09-004 The drawings on this page are
indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

U1
Sheet 4/5

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 140 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

1. FOR LIGHT FITTING INTEGRATION AND FIXING DETAILS


REFER TO A-94 & A-93 ARCHITECTURAL DRAWINGS AND
LIGHTING SPECIFICATIONS 265120

48 x U1 2. ARCHITECTURAL BACKGROUNDS ADDED FOR CLARITY

8 x S6

Detail 1

2 TYPE B CHANDELIER PLAN


SCALE 1:50

02 31.01.15 BULLETIN 145


01 31.10.14 BULLETIN 120
00 15.07.12 ISSUED FOR CONSTRUCTION

ISSUED FOR CONSTRUCTION

U1 U1
ABU DHABI
AIRPORTS COMPANY
S6 ABU DHABI AIRPORTS COMPANY
TYPE U1 LIGHT
Kohn Pedersen Fox Associates
(International) PA
Architects and Planning Consultants

L2q L2q L2q 7a Langley Street


London WC2H 9JA
England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com

U1 U1

TYPE S6 LIGHT
Detail 4
Type B Chandelier detail and section from MTC-A-94-TB-L3-0-0-00-09-004
ABU DHABI INTERNATIONAL AIRPORT
MIDFIELD TERMINAL COMPLEX
3 x TYPE L2q LIGHT

CENTRE SPACE
CHANDELIER DETAILS
PLAN, SECTIONS AND DETAILS

MTC A 94 TB __ L3.0 0.00 09.004 02

KPF MC KF JH 25.09.2009

4 TYPE B CHANDELIER DETAIL & SECTION


SCALE 1:50 WBS AUH.06.10.0401

2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights reserved. Do not scale.

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

U1
Sheet 5/5

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 141 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: LED modular element for ceiling uplighting

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 100W


Primary luminaire Die-cast aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 10,500lm
Finish: Anodised aluminium silver Luminaire efficacy: 105lm/W
Accessories: N/A See Notes Beam / distribution: Asymmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 4,000K
Driver type: Constant
27.03.2014
current Max Colour Variation: ≤ 3 SDCM
Drive
Operator current or voltage: 420mA Luminaire Lifetime: ≥ 50,000 hours
Telephone
DimmingFax
e-Mail
& type: DALI, remote Lifetime Basis: L70 / F10 @ Ta 400C
IP / IK rating: IP65
65 (Profile_03)-Provvisorio / Luminaire Data Sheet

Luminous emittance 1: Location:


he Pier chandeliers

Notes:

1. Refer to Section ‘2.0 Products’ of this specification for additional


requirements.
2. Luminaire to be passively cooled.
UP 3. Weight of remote driver and luminaire (including bracket and
accessories) to be less than 16kg.
4. Operating temperature rating for luminaires shall be between
-40°C and +40°C at a minimum Relative Humidity (RH) of 95%.
00 Due to missing symmetry properties, no UGR table
can be displayed for this luminaire. 5. Storage (i.e. non-operating/daytime) temperature: all fixture
components to be designed to tolerate between -40°C and +80°C
at a minimum maximum 95% Relative Humidity (RH).
6. All luminaires to have some means of built-in overheat thermal
protection in the form of an automatic dimming or stepping/holding
down of the driver where temperature exceeds operational limits.
7. Both LED module and driver shall be able to be replaced without
soldering or sending the luminaire back to the manufacturer.
Quick-connect devices are required.
8. Exact positioning of LED modules to be coordinated with
Architect architectural details.
9. Fixtures to be supplied with all necessary accessories including
mounting profiles.
10. Contractor to provide setting out of light fixtures for
Engineer’s approval.

The drawings on this page are


indicative. Refer to the architectural
Page 1 drawings for correct setting out,
mounting details and final dimensions.

Type:

U1b
Sheet 1/4
Top view - Pier Chandelier (18 U1b fixtures)

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 142 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Top view Fixtures in cluster configuration (top view)

Space between single fixtures


L < 550mm
U1b U1b

S > 150mm
To remote driver
U1b U1b
W < 400mm

Glass cover

Side view
Die cast Aluminium body
H4 > 300mm H1 < 100mm
H3 < 600mm

H2 < 100mm

Remote driver

Support to hold fixture above


driver and allow for ventilation

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.

Type:

U1b
Sheet 2/4

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 143 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Fixtures in cluster
configuration (top view)
Space between single fixtures

The drawings on this page are


U1b U1b indicative. Refer to the architectural
drawings for correct setting
S > 150mm

out, mounting details and final


U1b U1b dimensions.

Type:

U1b
Sheet 3/4

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 144 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

18xU1b

18xU1b

Detail 3

U1b U1b

U1b U1b
S1b

S1b

Detail 6
Plan and section through Type C Chandelier body from MTC-A-94-TB-L3-0-0-00-09-018

18xU1b
18xU1b

Detail 3

U1b U1b The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
U1b U1b out, mounting details and final
dimensions.

Type:

Detail 6
U1b
Sheet 4/4
Plan and section through Type D Chandelier body from MTC-A-94-TB-L3-0-0-00-09-019

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 145 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: LED fixture for ceiling uplighting

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 100W


Primary luminaire Die-cast aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 10,500lm
Finish: Anodised aluminium silver Luminaire efficacy: 105lm/W
Accessories: N/A See Notes Beam / distribution: Asymmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 4,000K
Driver type: Constant
27.03.2014
current Max Colour Variation: ≤ 3 SDCM
Drive
Operator current or voltage: 420mA Luminaire Lifetime: ≥ 50,000 hours
Telephone
DimmingFax
e-Mail
& type: DALI, remote Lifetime Basis: L70 / F10 @ Ta 400C
IP / IK rating: IP65
65 (Profile_03)-Provvisorio / Luminaire Data Sheet

Luminous emittance 1: Location:


he Departures Hall
Centre Space
Piers

Notes:

1. Refer to Section ‘2.0 Products’ of this specification for additional


requirements.
2. Luminaire to be passively cooled.
UP 3. Weight of remote driver and luminaire (including bracket and
accessories) to be less than 16kg.
4. Operating temperature rating for luminaires shall be between
-40°C and +40°C at a minimum Relative Humidity (RH) of 95%.
00 Due to missing symmetry properties, no UGR table
can be displayed for this luminaire. 5. Storage (i.e. non-operating/daytime) temperature: all fixture
components to be designed to tolerate between -40°C and +80°C
at a minimum maximum 95% Relative Humidity (RH).
6. All luminaires to have some means of built-in overheat thermal
protection in the form of an automatic dimming or stepping/holding
down of the driver where temperature exceeds operational limits.
7. Both LED module and driver shall be able to be replaced without
soldering or sending the luminaire back to the manufacturer.
Quick-connect devices are required.
8. Exact positioning of LED modules to be coordinated with
Architect architectural details.
9. Fixtures to be supplied with all necessary accessories including
mounting profiles.
10. Contractor to provide setting out of light fixtures for
Engineer’s approval.

The drawings on this page are


indicative. Refer to the architectural
Page 1 drawings for correct setting out,
mounting details and final dimensions.

Type:

U1c
Sheet 1/5

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 146 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Top view Fixtures in cluster configuration (top view)

Space between single fixtures


L < 550mm
U1c U1c U1c

S > 150mm
To remote driver

Maintenance access,
W > 800 mm
W < 400mm

U1c U1c U1c

U1c U1c U1c

U1c U1c U1c

Glass cover
Clusters of 9 fixtures

Side view
Die cast Aluminium body
H4 > 300mm H1 < 100mm
H3 < 600mm

H2 < 100mm

Remote driver

Support to hold fixture above


driver and allow for ventilation

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.

Type:

U1c
Sheet 2/5

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 147 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Fixtures in cluster
configuration (top view)
Space between single fixtures

The drawings on this page are


U1c U1c indicative. Refer to the architectural
drawings for correct setting
S > 150mm

out, mounting details and final


U1c U1c dimensions.

Type:

U1c
Sheet 3/5

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 148 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

U1c

XL1b

Detail 5
Section through Binnacle uplight from MTC-A-94-TB-L_-_-0-00-09-030

U1c
U1c U1c U1c

L17

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Detail 2 Type:
Section of vertical circulation of Glazed Passenger lifts from MTC-A-94-TB-L_-_-0-00-07-018

U1c
Sheet 4/5

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 149 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

U1c

L18b

Detail 4
Side pavilion cladding at wall interface from MTC-A-94-TB-L_-_-0-00-09-047

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

U1c
Sheet 5/5

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 150 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Ground recessed adjustable and lockable uplight

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 15W


Primary luminaire Stainless steel Power factor: > 0.9
construction material: Rated luminous flux (lm): 760lm
Finish: Stainless steel Luminaire efficacy: 50lm/W
Accessories: Installation housing Beam / distribution: Symmetric, see LDC
Light sourceProject
type:1 LED CRI / Colour temperature: > 80 / 3,000K
Driver type: Constant current Colour Variation: 10.12.2014
≤ 3 SDCM
Operator
Drive current or voltage: 350mA Telephone Luminaire Lifetime:
Fax
≥ 50,000 hours
Dimming & type: DALI, integral e-Mail
Lifetime Basis: L70 / F10 @ Ta 600C (exterior)
IP: IP67 S.p.A TYG4 Light UP Walk profess (LED): 12 x 1W warm white L70 / F10 @ Ta 250C (interior)
iGuzzini illuminazione
adjustable spot optic ±15 / Luminaire Data Sheet

Luminaire distribution curve (LDC)


Luminous emittance 1: Location:
See our luminaire catalog for an image of the Arrivals Entry/Forecourt
luminaire.
Welcomers Hall
Departures Hall
Concourses
Bussing gates

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Luminaire to be passively cooled.
3. To be supplied with an installation
housing.
Luminaire classification according to CIE: 100 Luminous emittance 1:
CIE flux code: 99 100 100 100 63 4. Mounting details to be coordinated
with architectural details.
5. Luminaire with adjustable and
lockable mechanism for aiming.
6. Surface temperature of luminaire to
be < 60°C.
7. To be supplied with ± 20° double
adjustable optic.

Installation housing (nominal)

The drawings on this page are


indicative. Refer to the architectural
DIALux 4.12 by DIAL GmbH Page 1
drawings for correct setting out,
mounting details and final dimensions.

Type:

U3
Sheet 1/4

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 151 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

XD1d XD1d XD1d


XD1d

L17 D12 D12


L17
L17 L17 L17

U3
U3 U3 U3 U3
U3

Section detail of entrance doors from MTC-A-94-TB-L_-_-0-00-09-038

XD1d XD1d XD1d

L17 L17

U3 U3 U3 U3

Detail 3
Section detail of entrance doors from MTC-A-94-TB-L_-_-0-00-09-038

L17b
D12
D12

D12

D12
L17b
D12
D12 D12
D12

D12
L17b
D12
D12
U3 U3 D12
The drawings on this page are
U3
indicative. Refer to the architectural
L17b

drawings for correct setting out,


U3
mounting details and final dimensions.
U3

U3

Type:

Detail 1 U3
Plan of entrance doors from MTC-A-94-TB-L_-_-0-00-09-038 Sheet 2/4

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 152 of 231
XD1d XD1d XD1d
XD1d

Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015

L17 D12 D12


L17
L17 L17 L17
U3

Abu Dhabi Airports Company PJSC Specification, Section 265120


L23

1 TYPE U3 - DETAIL OF UPLIGHT TO FACADE


SCALE 1:10

U3

L23

L21

TYPE U3 - DETAIL OF UPLIGHT TO FACADE


SCALE 1:10
Detail 1
Detail of uplight to facade from MTC-A-94-TB-L_-_-0-00-09-032

4 TYPE L21 - DETAIL OF FLUORESCENT COVE 6 PIER CEILINGS - DETAIL 1


SCALE 1:10
5 SCALE 1:10

U3

L21

FACADE

MIN 150mm
XL2
4 TYPE L21 - DETAIL OF FLUORESCENT COVEU3 6 PIER CEILINGS - DETAIL 1
SCALE 1:10 SCALE 1:10

REFLECTOR TRAY WITH LAMP


AND CONTROL GEAR

Detail 2
Detail2 ofTYPE
uplight to glazing
U3 - UPLIGHT facade
TO GLAZING from MTC-A-94-TB-L_-_-0-00-09-032
FACADE 5 TYPE XL2 - SECTION THROUGH LANDSLIDE APRON FACADE
SCALE 1:10 SCALE 1:10

FIXING TO SOLID
STRUCTURE BY
OTHERS
MIN 150mm

U3 U3 MIN 150mm
XL2
U3

The drawings on this


REFLECTOR TRAYpage are
WITH LAMP
AND CONTROL GEAR
indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.
2 TYPE U3 - UPLIGHT TO GLAZING FACADE 5 TYPE XL2 - SECTION THROUGH LANDSLIDE APRON FACADE
SCALE 1:10 SCALE 1:10

Type:

Detail 1 - U3 on stone on unbonded screed Detail 2 - U3 at stone bonded to sealed raised floor U3
Floor details from MTC-A-80-TB-L_-_-0-00-00-602 Sheet 3/4

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 153 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

U8
U3

Detail 6
Detail of uplight to perimeter glazing from MTC-A-94-TB-L_-_-0-00-09-031

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

U3
Sheet 4/4

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 154 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Ground recessed adjustable and lockable uplight

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 15W


Primary luminaire Stainless steel Power factor: > 0.9
construction material: Rated luminous flux (lm): 680lm
Finish: Stainless steel Luminaire efficacy: 45lm/W
Accessories: Installation housing Beam / distribution: Symmetric, see LDC
Light sourceProject
type:1 LED CRI / Colour temperature: > 80 / 3,000K
Driver type: Constant current Colour Variation: 10.12.2014
≤ 3 SDCM
Operator
Drive current or voltage: 350mA Telephone Luminaire Lifetime:
Fax
≥ 50,000 hours
Dimming & type: DALI, integral e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: IP67 S.p.A TYG5 Light UP Walk profess (LED): 12 x 1W warm white
iGuzzini illuminazione
adjustable flood optic 0°-15 / Luminaire Data Sheet

Luminaire distribution curve (LDC)


Luminous emittance 1: Location:
See our luminaire catalog for an image of the Welcomers Hall
luminaire.
Central Area Pavilion

Notes:
1. Refer to Section ‘2.0 Products’ of this
UP specification for additional requirements.
2. Luminaire to be passively cooled.
3. To be supplied with an installation
housing.
Luminaire classification according to CIE: 100 Luminous emittance 1:
CIE flux code: 96 99 100 100 56 4. Mounting details to be coordinated
with architectural details.
5. Luminaire with adjustable and
lockable mechanism for aiming.
6. Surface temperature of luminaire to
be < 60°C.
7. To be supplied with ± 20° double
adjustable optic.

Installation housing (nominal)

The drawings on this page are


indicative. Refer to the architectural
DIALux 4.12 by DIAL GmbH Page 1 drawings for correct setting out,
mounting details and final dimensions.

Type:

U3b
Sheet 1/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 155 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

U3

Detail 2 - U3 at stone bonded to sealed raised floor


Floor details from MTC-A-80-TB-L_-_-0-00-00-602
Note U3b fixtures are mounted similarly to U3

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

U3b
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 156 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Uplight integrated in bollard

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 15W


Primary luminaire Stainless steel Power factor: > 0.9
construction material: Rated luminous flux (lm): 860lm
Finish: Stainless steel Luminaire efficacy: 57lm/W
Accessories: Installation housing Beam / distribution: Symmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 3,000K
Driver type: Project 1 Constant current Colour Variation: ≤ 3 SDCM
10.12.2014
Drive current or voltage: 350mA Operator
Luminaire Lifetime: ≥ 50,000 hours
Dimming & type: DALI, integral Telephone
Fax Lifetime Basis: L70 / F10 @ Ta 600C
e-Mail
IP: IP67
iGuzzini illuminazione S.p.A U4b Light up wflood / Luminaire Data Sheet
Luminaire distribution curve (LDC)
Luminous emittance 1:
Location:
150X150X80 stone
See our luminaire catalog for an image of the pavers Processor curb bollards
luminaire.

Local widening of
plinth at signage

Notes:
1. Refer to Section ‘2.0 Products’ of this
UP specification for additional requirements.
2. Luminaire to be passively cooled.
9
3. To be supplied with an installation
housing for recessing within concrete
Luminaire classification according to CIE: 100 Luminous emittance 1: bollard.
CIE flux code: 65 87 97 100 53
4. Bollard design and mounting detail to
NOTE:
Road and Pedestrian surface finishes, r
3mm stainless steel DCM Installation housing (nominal) be coordinated with architectural details.
MTC-A-34-TB-_-L_._-_.__-00.680
bollard cladding 09 Refer to structural engineer's drawings
structure & plinth details
Precast concrete parapet to 5. Surface temperature of luminaire toengineer's drawings for firs
Refer to civil
01 civil engineer's specifications drop-off structure, concrete parapet det
be < 60°C. foundations at Arrivals curb details &
pavement buildup details
Refer to lighting consultant's specificatio
light fittings
3000

Shadow gap ARUP LIGHTING


MARK_UPS
8

9 Stainless Steel Bollard Cap Detail


SCALE 1:1

U4b
01 26.10.12 BULLETIN 03

9 00 15.07.12 ISSUED FOR CONSTRUCTION

The drawings on this page are ISSUED FOR CONSTRUC


Reinforced Concrete indicative. Refer to the architectural
DIALux 4.12 by DIAL GmbH
bollard refer to civil
engineer's drawings Page 1
drawings for correct setting out, ABU D
mounting details and final dimensions. AIRPORTS
ABU DHABI AIRPORTS COMPANY

3mm stainless steel Kohn Pedersen Fox Associat


bollard cladding (International) PA
Architects and Planning Con
7a Langley Street
London WC2H 9JA

Type:
England
T: +44 (0)207 319 5300
01 01 01 01
F: +44 (0)207 497 1175
www.kpf.com

U4b
ABU DHABI INTERNATIONA
MIDFIELD TERMINAL CO
Detail 6 Sheet 1/2
Detail section of Processor curb bollard from MTC-A-34-TB-L_-_-_-__-00-690

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 157 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015

cs for

2012 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All


Abu Dhabi Airports Company PJSC Specification, Section 265120

150

Detail 4
Detail section of Processor curb bollard with uplight from MTC-A-94-TB-L_-_-0-00-09-022

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

U4b
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 158 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Ground recessed adjustable and lockable uplight

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 43W


Primary luminaire Stainless steel Power factor: > 0.9
construction material: Rated luminous flux (lm): 4,500lm
Finish: Stainless steel Luminaire efficacy: 105lm/W
Accessories: See Notes Beam / distribution: Symmetric, see LDC
Light sourceProject
type: 1 LED CRI / Colour temperature: > 80 / 3,000K
Driver type: Constant voltage Colour Variation: 03.04.2014
≤ 3 SDCM
Operator
Drive current or voltage: 12V Telephone Luminaire Lifetime:
Fax
≥ 50,000 hours
Dimming & type: DALI, integral e-Mail
Lifetime Basis: L70 / F10 @ Ta 600C
IP: IP67
WE-EF;Eulumdat2 185-2726+185-2719 ETC140-GB[EE] VA:IP67:LED-24/24W/3K + IO-
Datenblatt · Datasheet 4.0308_U5_MM011214
180°;ETC140-GB LED , Inground Uplights / Luminaire Data Sheet
nblatt · Datasheet 4.0308_U5_MM011214

08 | Ground mounted-Light out of 316L stainless steel, 45°


Luminaire
4.0308 | Ground mounted-Light out of 316L stainless steel, distribution
45°emittance
Luminous 1:
curve (LDC)
U5
U5
Location:
See our luminaire catalog for an image of the Exterior facades
luminaire.
dEsCRIptIon dEsCRIptIon
IP67 IP67
· protection system Ip67 · protection system Ip67 5000

· Made entirely of marine grade · Made entirely of marine grade V4A V4A
EDELSTAHL EDELSTAHL
316L stainless steel 316L stainless steel
4000
· with round cover · with round cover
· temperature-resistant silicon seal
· temperature-resistant silicon 5.0
seal t
· toughened safety glass (EsG) – 5.0 t
withstands loads of up to 5000 kg
· toughened safety glass (EsG) – INKL
3000 INKL
withstands loads of up to 5000
KABELkg
· Cable gland pG 16/21, nickel-plated brass
INKL 12 V KABEL
· poW-LEd 12 V-dC for parallel connection · Cable gland pG 16/21, nickel-plated brass
INKL 12 V
· poW-LEd-platine temperatur control (ntC) · poW-LEd 12 V-dC for parallel connection
Notes:
2000
· with poM installation housing · poW-LEd-platine temperatur control (ntC)
· with poM installation housing
appLICatIon
· Flexible lighting for varied applications
including lighting appLICatIon 1. Refer to Section ‘2.0 Products’ of this
of building facades, green areas and parks, · Flexible lighting for varied applications specification for additional requirements.
outdoor facilities and many more. including lighting
of building facades, green areas and parks,
outdoor facilities and many more.
2. Luminaire to be passively cooled.
3. To be supplied with a linear spread
lens and an installation housing.
Luminaire classification according to CIE: 0 No UGR diagram can be displayed for this luminaire.
CIE flux code: 00 00 00 00 73
177
4. Mounting details to be coordinated
with architectural details.
177 5. Gravel mounting detail to follow
Landscape Architect’s specification.
260 6. Luminaire with adjustable and
lockable mechanism for aiming.
5

260 7. Surface temperature of luminaire to


be < 60°C.
5

240 260
8. To be supplied with ± 20° double
adjustable optic.

240 260
9. Housing detail for U5 to be
183
developed with Landscape designer.
236

umber Lamps Light colour Wattage (tLF) tension Radation angle temperature

ht
25.62_U5 36 poW-LEd warm white 3.000K total 43 W (4500 lm) 12 V-dC 45° <40°C
183

supply 236

XL2
65.60 for max. 36 poW-LEd 12 V-dC, Ip65
65.15 for max. 108 poW-LEd 12 V-dC, Ip65

article number Lamps Light colour Wattage (tLF) tension Radation angle temperature
03.15 dimming module, 1…10 V, dali
spotlight The drawings on this page are
4.0308.25.62_U5 36 poW-LEd warm white
Elektrogeräte GmbH & Co. KG · info@wibre.de · +49(0)7131 9053-0 · Leingarten/Germany
3.000K total 43 W (4500 lm)
WWW.WIBRE.dE
12 V-dC 45° <40°C indicative. Refer to the architectural
Page 1
power supply drawings for correct setting out,
5.0600.65.60 for max. 36 poW-LEd 12 V-dC, Ip65 mounting details and final dimensions.
5.0600.65.15 for max. 108 poW-LEd 12 V-dC, Ip65

5.0690.03.15 dimming module, 1…10 V, dali

WIBRE Elektrogeräte GmbH & Co. KG · info@wibre.de · +49(0)7131 9053-0 · Leingarten/Germany WWW.WIBRE.dE Type:

U5
U5
Section and detail section from MTC-A-03-TB-L_-_-1-00-00-482

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 159 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Wall mounted adjustable and lockable projector

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 28W (RGBW)


Primary luminaire Die-cast aluminium Power factor: > 0.5
construction material: Rated luminous flux (lm): 845lm (RGBW)
Finish: Stainless steel Luminaire efficacy: 30lm/W (RGBW)
Accessories: Wall mounting bracket Beam / distribution: Symmetric, see LDC
Light sourceProject
type: 1 LED CRI / Colour temperature: > 80 (white) / RGB / 3,000K (W)
Driver type: Constant Voltage Colour Variation: 22.08.2014
≤ 3 SDCM (white)
Operator
Drive current or voltage: 24V Telephone
Fax
Luminaire Lifetime: ≥ 50,000 hours
Dimming & type: DALI, remote e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
___________________
IP: Type: _________________________
IP66
PHILIPS COLOR KINETICS COLOR BURST 6 CLEAR CAST ALUMINUM HOUSING,
CLEAR GLASS ENCLOSURE. / Luminaire Data Sheet
_________________________________________________
Luminaire distribution curve (LDC)
Luminous emittance 1: Location:
_________________________________________________
See our luminaire catalog for an image of the Centre Space Museum stair
luminaire.

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.

D spotlight with intelligent color light 2. Luminaire to be passively cooled.


3. Wall mounting bracket to be provided
for wall installation.
of Luminaire
8.4 in
213 mm
classification according to CIE: 100 Luminous emittance 1:
CIEDiameter
Rotation flux code: 97 100 100 100 100 4. Mounting details to be coordinated
he 7.5 in
191 mm
2.4 in with Architect.
61 mm
osed in Ø6.7 in
170 mm
Assembly OD
6.7 in 5. Allow for Red, Green and Blue LEDs
ompact Fixture OD 170 mm
to be individually controlled.
cts 6. Surface temperature of luminaire to
ffects 8.2 in
be < 60°C.
g gives 208 mm
6 in
152 mm
um 4.9 in
3.6 in
91 mm
125 mm
three- Refer to sections indicated in
8.4 in
, egg- 213 mm
Rotation Diameter
RCPs and plans

7.5 in 2.4 in
191 mm 61 mm
Assembly OD

ARUP LIGHTING
Ø6.7 in
170 mm 6.7 in
Fixture OD 170 mm
osted MARK_UPS
m 2.5 in
64 mm

for 8.2 in
208 mm
gle). Ø4.5 in
11.4 mm
1.2 in
30 mm
6 in
152 mm
3.6 in
4.9 in
91 mm
Each
125 mm
The drawings on this page are
lumens Page 1 indicative. Refer to the architectural
drawings for correct setting out,
sity. mounting details and final dimensions.
0° ColorBurst 6 can be freestanding on a floor.
ture Each mounting base comes with a native 60 ft
U7
12 º 22 º

Type:
L20b

(18.3 m) power and data cable to minimize


2.5 in
64 mm
wiring.
Ø4.5 in
11.4 mm • On-board temperature monitoring — A
1.2 in
30 mm

compensation circuit prevents damage to the


U7
Sectionfixture if operating temperatures rise to unsafe
from MTC-A-94-TB-L_-_-0-00-09-030-031 031
ng and
gg levels. An auto-cycling feature automatically
Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401
restores normal operation after 30 minutes. Page 160 of 231
ead Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
essory • Industry-leading controls — ColorBurst 6
12 º 22 º

ousing. fixtures work seamlessly with the complete


line of Philips Color Kinetics controllers,
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Ground recessed adjustable and lockable uplight

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 28W (RGBW)


Primary luminaire Stainless steel Power factor: > 0.5
construction material: Rated luminous flux (lm): 845lm (RGBW)
Finish: Stainless steel Luminaire efficacy: 30lm/W (RGBW)
Accessories: Installation housing Beam / distribution: Symmetric, see LDC
Light sourceProject
type: 1 LED CRI / Colour temperature: > 80 (white) / RGB / 3,000K (W)
Driver type: Constant current Colour Variation: 22.08.2014
≤ 3 SDCM (white)
Operator
Drive current or voltage: 350mA Telephone
Fax
Luminaire Lifetime: ≥ 50,000 hours
Dimming & type: DALI, remote e-Mail
Lifetime Basis: L70 / F10 @ Ta 250C
IP: IP66
PHILIPS COLOR KINETICS COLOR BURST 6 CLEAR CAST ALUMINUM HOUSING,
TYPE XT3 LIGHT
CLEAR GLASS ENCLOSURE. / Luminaire Data Sheet

Luminaire distribution curve (LDC)


Luminous emittance 1: Location:
See our luminaire catalog for an image of the Centre Space Museum stair
luminaire.

1. FOR LIGHT FITTING INTEGRATION AND FIXING DETAILS


REFER TO A-94 & A-93 ARCHITECTURAL DRAWINGS AND
LIGHTING SPECIFICATIONS 265120

Notes:
2. ARCHITECTURAL BACKGROUNDS ADDED FOR CLARITY

1. Refer to Section ‘2.0 Products’


of this specification for additional
requirements.
2. Luminaire to be passively cooled.
3. Luminaire with adjustable and
Luminaire classification according to CIE: 100 Luminous emittance 1:
CIE flux code: 97 100 100 100 100
lockable mechanism for aiming.
4. Surface temperature of luminaire to
be < 60°C.
5. To be supplied with ± 15° double
adjustable optic.

8 SECTION AT SEATING WITH FIXED LIGHT FIXTURE HEIGHT


SCALE 1:20

U7 The drawings on this page are


POLYCARBONATE OPAL Page 1 indicative. Refer to the architectural
U7 DIFFUSERTO BE REMOVABLE
FOR MAINTENANCE drawings for correct setting
02 31.01.15 BULLETIN 145
out, mounting details and final
U7 L20b 01 31.10.14 BULLETIN 120 dimensions.
00 15.07.12 ISSUED FOR CONSTRUCTION

Type:
ISSUED FOR CONSTRUCTION

5 TYPE U7 & L20b - MUSEUM STAIR DETAIL


Detail 5 SCALE 1:20
ABU DHABI U7
AIRPORTS COMPANY Sheet 1/2
Section of Museum stair from MTC-A-94-TB-L_-_-0-00-09-031 02 ABU DHABI AIRPORTS COMPANY

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Kohn Pedersen Fox Associates
(International) PA
Architects and Planning Consultants Page 161 of 231
January 31, 2015
7a Langley Street

Bulletin No. 145: Volume 3 of 4 (Rev 07) London WC2H 9JA


England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com
BAL GLASS BALUSTRADE
Abu Dhabi
05Airports Company PJSC Specification, Section 265120

GLZ
02

GLAS
STN STONE TYPE 10 UP TO
10
P14I
1
DIFFU
TO PE
2
P15
3 U7 P16E
U8
4 U7
U8
U8 TYPE
5 U7 ROTATION
AXIS
6
U7
U8
7 U8
U7
U7
U8 U8
EVER
REQU
50M A

39 risers @ 141mm
PREC
U7 LED SPOTLIGHT RECESSED IN CONCRETE.
omit
just
recta
body
DE
CONTINUOUS RECESS FOR CABLES
CO
(ACCESS LOCATIONS TO BE DEFINED
BY ELECTRICAL CONTRACTOR)
Detail 2
2
Stair geometrySTAIR GEOMETRY
of Museum stair from/MTC-A-07-TB-L_-_-_-__-00-650
L1.0 PLAN 3 STAIR GEOMETRY / E
SCALE 1:50 SCALE 1:50
SECTION

this is not the same detail


as it was before and this
does not make sense.
refer to Arup's originalU7
mark-up on The drawings on this page are
MTC-A-94-TB-L_-_-0-00-0 indicative. Refer to the architectural
9-031 issued in August drawings for correct setting
out, mounting details and final
dimensions.
RECESSED
LIGHT-BOX EDGE
GHT 6 U7 SECTION Type:
2NDFLIGHT
SCALE 1:10

Detail 5
U7
Sheet 2/2
Section of 1st flight of Museum stair from MTC-A-07-TB-L_-_-_-__-00-651

Secondary– General Contractor, AUH.06.10.0401


Contract: Midfield Terminal Building Page 162 of 231
Structure
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
by contractor STAIR GEOMETRY 3D VIEW
5
SCALE NTS
these should be another light SS SKIRTING
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Ground recessed uplight

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 35W (RGBW)


Primary luminaire Cast aluminium Power factor: > 0.5
construction material: Rated luminous flux (lm): 1,200lm (RGBW)
Light Up Walk professional
Finish: TBC Stainless steel Luminaire efficacy: 34lm/W (RGBW)
Design Jean Michel Wilmotte iGuzzini
Accessories: Installation housing Beam / distribution: Symmetric, see LDC
April 2014
Light sourceProject
type: 1 LED CRI / Colour temperature: > 80 (white) / RGB / 3,000K (W)
Driver type: Constant current Light Up Walk Colour Variation: 21.08.2014
≤ 3 SDCM (white)
professional - 12 LED RGB DALI - adjustable flood optic ±15
Operator
Drive current or voltage: Light VariesUp Walk professional Telephone
Fax
Luminaire Lifetime: ≥ 50,000 hours
Product code:
e-Mail
Dimming & type: DALI, integral BB37 Lifetime Basis: L70 / F10 @ Ta 250C
Design Jean Michel Wilmotte iGuzzini
IP: IP67 S.p.A U8rgbw Light
iGuzzini illuminazione up Tagadà
Technical RGBW medium / Luminaire
description:
Ground recessed luminaire for uplight with LED light sources. RGB version with 12 24Wmax multicolour LED, ± 15° double adjustable
April 2014 Data Sheet
optic, plastic lenses for FLOOD version, complete with DALI 48÷56Vdc electronic control board. The luminaire is provided
with RGB DIRECT DIM for regulation by means of standard button with the following functions: Soft ON/OFF, colour change,
Luminaire
lastLuminous
distribution
emittance
colour memory,
curve (LDC) Location:
default1:dynamic sequence. Made of circular body, low outer casing and frame. The body and outer casing
are made of cast aluminium with AISI 304 stainless steel frame. The outer casing must be ordered separately from the optical
Light Up Walk professional - 12 LED RGB DALI - adjustable flood optic ±15
See our luminaire catalog for an image of the assembly. The optical assembly is closed on top by a tempered glassMuseum (thickness 15stair
mm) complete with silicone gasket compressed
luminaire. Design iGuzzini iGuzzini
by the AISI 304 stainless steel frame. The lower section houses a decompression box for connection, 6-pole terminal block
and M24x1,5 stainless steel double cable clamp, suitable for cables with 7÷16 mm diameter. The wiring section is connected
Product code: to the optical assemblyjune
by a2014
nickel-plated brass cable clamp M15x1. This makes it easier to open the upper glass by eliminating
BB37 negative pressure inside the optical assembly and the pump effect on the supply cable. The body-optical assembly is equipped
with a locking system having 2 stainless-steel captive screws on which 2 extruded-aluminium supports slide. The locking system
Technical description: ensures positioning and anchoring of the optical assembly to the outer casing. The acrylic painting of the body/optical assembly
Ground recessed luminaire foranduplight withensures
outer casing LED light
Outer sources.
protection
casing RGB
against
for UV version
rays
Light and with
UptheLight 12 24Wmax
external environment. multicolour LED,
The assembly formed± 15° double
of frame, adjustable
optical assembly
and outer
optic, plastic lenses for FLOOD casing
version, guaranteeswith
complete 5000DALI
Kg resistance
48÷56Vdcagainst static load.control
electronic All external screwsThe
board. are made of stainless
luminaire steel A2.
is provided
with RGB DIRECT DIM for regulation
Installation:by means of standard button with the following Notes:
functions: Soft ON/OFF, colour change,
Recessed into
last colour memory, default dynamic sequence. code
the floor with
Madeouterofcasing. Thebody,
circular top rim low
of theouter
outer casing
casing must
andnotframe.
jut out from
Thethe floorand
body surface (1 mm
outer casing
B992diameter=289mm; lower diameter=397mm;
MAX). Outer casing upper 1. Refer
h=125mm.to Section ‘2.0 Products’ of this
are made of cast aluminium with AISI 304 stainless steel frame. The outer casing must be ordered separately from the optical
Dimension:
specification for additional requirements.
assembly. The optical assembly is closed on top by a tempered glass (thickness 15 mm) complete with silicone gasket compressed
D=312mm - H=124mm
by the AISI 304 stainless steel frame. The lower Technical description
section houses a decompression box 2. Luminaire
for connection,to be6-pole
passively
terminalcooled.
block
and M24x1,5 stainless steel Colour:
double cable clamp, Plastic outerfor
suitable casting
cables complete
with 7÷16 with double
mm 3. To
diameter.
be EPDM
The wiring
supplied black cable-clamp.
section
with an is connected
installation
Design iGuzzini Steel (13)
iGuzzini
to the optical assembly by a nickel-plated brass cable clamp M15x1. This makes it housing. easier to open the upper glass by eliminating
Luminaire classification according Weight
to CIE: 100inside the optical [Kg]: emittance 1:
Luminous
negative pressure assembly and the pump effect on the supply cable. The body-optical assembly is equipped
CIE flux code: 94 99 100june 100 60 6,4 Installation 4. Mounting details to be coordinated
with a 2014
locking system having 2 stainless-steel captive screws on which 2 extruded-aluminium supports slide. The locking system
Mounting:
Recessed into the ground or into the paving
with with aarchitectural
Architect concrete slab details.
and a drainage channel.
Installation housing and dimensionsensures positioning and anchoring of the optical assembly to the outer casing. The acrylic painting of the body/optical assembly
Ground recessed
and outer casing ensures protection against UV rays and the external environment.5. Allow for Red,
The assembly Green,
formed Blueoptical
of frame, and White
assembly
Outer
and casing
outer casing for Light Up
guarantees
Wiring:
Light
5000 Kg resistanceSizeagainst
(mm) static load. All external screws to bearecontrolled
made of individually.
stainless steel A2.
Electronic control gear to be ordered separately (code BZ14 - 100W Vin=100-240Vac Vout=48/56Vdc, code BZ15 - 240W Vin=100-240Vac
390x190
Installation: Vout=48/56Vdc , code BZ16 - 480W Vin=100-240Vac Vout=48/56Vdc) 6. Surface temperature of luminaire to
code
Recessed outer casing. The top rim of the outer casing must not be
into the floor with Notes: < 60°C.
jut out from the floor surface (1 mm
The electronic board Colour
B992 Outer casing upper diameter=289mm; takes three DALI addresses and absorbs one DALI load. Complete with lamp. Outer case code B901 to be
MAX). lower diameter=397mm; h=125mm.
Black (04)available: refractor for elliptical distribution of luminous flow, diffusing glass, closing
ordered separately. Accessories
Dimension: plug for outer casing and suction cup.
Technical
D=312mm description
- H=124mm Product configuration: BB37+LED
Plastic outer casting complete with
BB37: 12 Weight
LED double EPDM
RGB DALI (kg)
black
- adjustable floodcable-clamp.
optic ±15
Colour: LED: LED RGB 0.65
Steel (13) Product characteristics:
Installation
Total lighting output [Lm]: 256.8 Total luminous flux at or above an angle of 90° [Lm]: 0 Compl
Weight [Kg]:into the ground or into the paving with a concrete slab and a drainage channel.
Recessed Total power [W]: 15.3 Emergency luminous flux [Lm]: /
6,4 Luminous efficacy [Lm/W]: 16.78 Voltage [V]: -
Number of optical assemblies: 2
Mounting:
Size (mm)
Optical assembly Characteristics 1:
390x190
Ground recessed
Light Output Ratio (L.O.R.) [%]: 47 Number of lamps for optical assembly: 1
Lamp code: LED Socket: /
Wiring:
ZVEI Code: LED Ballast losses [W]: 1.65
Colour control gear to be Nominal
Electronic ordered separately
power [W]: 6
(code BZ14 - 100W Vin=100-240Vac Vout=48/56Vdc, code BZ15 - 240W Vin=100-240Vac
Colour temperature [K]: 6000
Black (04)
Vout=48/56Vdc , code BZ16Nominal
- 480Wluminous
Vin=100-240Vac
[Lm]: 271 Vout=48/56Vdc) CRI: /
The drawings on this page are
Lamp maximum intensity [cd]: / Wavelength [Nm]: /
Notes: Beam angle [°]: 28° indicative.
Page 1 MacAdam Step: / Refer to the architectural
Weight
The (kg) board takes three DALI addresses and absorbs one DALI load. Complete
electronic drawings for correct
with lamp. Outer setting
case codeout,
B901 to be
Complies with EN60598-1 and pertinent regulations
0.65 separately. Accessories available: refractor for elliptical distribution of luminous
ordered mounting details glass,
flow, diffusing and final dimensions.
closing
plug for outer casing and suction cup.
Complies with EN60598-1 and pertinent regulatio
Product configuration: BB37+LED
BB37: 12 LED RGB DALI - adjustable flood optic ±15 Type:
LED: LED RGB

U8
Product characteristics:
Total lighting output [Lm]: 256.8 Total luminous flux at or above an angle of 90° [Lm]: 0
Total power [W]: 15.3 Emergency luminous flux [Lm]: /
Sheet 1/2
Luminous efficacy [Lm/W]: 16.78 Voltage [V]: -
Number of optical assemblies: 2
Contract: Midfield Terminal Building – assembly
Optical GeneralCharacteristics
Contractor, AUH.06.10.0401
1: Page 163 of 231
Bulletin No. 145: Volume 3 of 4Light
(Rev 07) Ratio (L.O.R.) [%]: 47
Output Number of lamps for optical assembly: 1 January 31, 2015
Lamp code: LED Socket: /
ZVEI Code: LED Ballast losses [W]: 1.65
Nominal power [W]: 6 Colour temperature [K]: 6000
Nominal luminous [Lm]: 271 CRI: /
Abu Dhabi Airports Company PJSC Specification, Section 265120

L8

P14I
1

2
P15
3 U7 P16E
U8
4 U7
U8
U8
5 U7 ROTATION
AXIS
6
U7
U8
7 U8
U7
U7
U8 U8

39 risers @ 141mm
Detail 2
2
Stair geometrySTAIR GEOMETRY
of Museum stair from/MTC-A-07-TB-L_-_-_-__-00-650
L1.0 PLAN 3 STAIR GEOMETRY / E
SCALE 1:50 SCALE 1:50

this is not the same detail


as it was before and this
does not make sense.
refer to Arup's original
mark-up on The drawings on this page are
MTC-A-94-TB-L_-_-0-00-0 indicative. Refer to the architectural
9-031 issued in August drawings for correct setting
out, mounting details and final
dimensions.
RECESSED U8
LIGHT-BOX EDGE Type:

Detail 7
U8
Sheet 2/2
Section through Museum stair from MTC-A-94-TB-L_-_-0-00-09-031

Secondary– General Contractor, AUH.06.10.0401


Contract: Midfield Terminal Building Page 164 of 231
Structure
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
by contractor STAIR GEOMETRY 3D VIEW
5
SCALE NTS
these should be another light SS SKIRTING
DIMENSIONS:

LAMP
AbuTYPE
Dhabi&Airports
REF: Company
150W 230V
PJSCWarm
white (3000K) Ceramic Metal Halide G12 Specification, Section 265120
(Osram ref: HCI-TM 150/830 WDL PB - G12 base)
tirrup mounted washlight with narrow asymmetric bright
POWER: 230V / 150W
Luminaire
r and internal shield usingWall
Description:
anti-glare mounted
a single egress light
230V/150W
metalFIXING
halide lamp with warm white
METHOD: (3000K)
To be double colour
bolted through stirrup precisely within angle as shown on
Manufacturing
be supplied with integralstandard:
digitally EN 60 598
lighting layout drawings. gear
switching electronic Lamp Type: Ceramic Metal Halide
Primary luminaire Aluminium Lamp Wattage: 150W (G12)
COMMENTS:
construction material:Full specification of this equipment Lamp is also Manufacturer:
dependent on resultant-submitted
Project 1
Finish: calculations of the
Stainless full lumen outputBeam
steel of lamp, reflector and louver
/ distribution: 23.01.2015 -
as detailed
Accessories: on following
N/A pages. No substitution is acceptable without fully demonstrated
Operator CRI / Colour temperature: > 80 / 3,000K
calculations to achieve resultant light levels as demonstrated with no increase
Telephone
IP: IP67
of wattage or power consumption. e-Mail Ballast/Transformer:
Fax
electronic, integral
Lamp life: ≥ 15,000 hours
m white (3000K) Ceramic MetalSill
ILLUSTRATION: Halide G12
Lighting 453 5 015 35 Plane Projector 150 / Luminaire Data Sheet
-TM 150/830 WDL PB - G12 base) Luminaire distribution curve (LDC) Location:
Luminous emittance 1:

See our luminaire catalog for an image of the Gatehouse egress light
luminaire.

ted through stirrup precisely within angle as shown on


awings.

of this equipment is also dependent on resultant submitted


e full lumen output of lamp, reflector and louver as detailed
es. No substitution is acceptable without fully demonstrated
hieve resultant light levels as demonstrated with no increase
wer consumption. Notes:
1. Refer to Section ‘2.0 Products’
Luminaire classification according to CIE: 100 Due to missing symmetry properties, no UGR table of this specification for additional
CIE flux code: 34 66 98 100 68 can be displayed for this luminaire. requirements.
2. Mounting detail to Architect’s
specification.
3. 10,065lm rated luminaire luminous
flux.

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 92 of 120


Construction Document: Volume 3 of 4 July 2012

Page 1

The drawings
drawingson onthis
thispage
pageare
are
indicative. Refer
indicative. Refertotothe
thearchitectural
architectural
drawings for
drawings forcorrect
correctsetting out,
setting
ntractor, AUH.06.10.0401 Page 92 of 120 out, mounting
mounting detailsdetails and
and final final
dimensions.
dimensions.
July 2012

Type:

U11
Sheet 1/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 165 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

3 x U11 3 x U11

Detail 2 - Elevation Type E Detail 4 - Elevation Type F


Gatehouse lighting detail from MTC-A-93-TB-L_-_-_-__-00-542

3 x U11

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

U11
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 166 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Wall recessed step marker

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 2W


Primary luminaire Anodised aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 125lm
Finish: Anodised aluminium silver Luminaire efficacy: 63lm/W
Accessories: Installation housing Beam / distribution: Asymmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 3,000K
Driver type: Constant current Colour Variation: ≤ 3 SDCM
Drive current or voltage: 700mA Luminaire Lifetime: ≥ 50,000 hours
Dimming & type: DALI, remote Lifetime Basis: L70 / F10 @ Ta 250C
IP: IP65

Luminaire distribution curve (LDC) Location:


Arrivals Feature Stair

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
46
46 2. Luminaire to be passively cooled.
36
36 2.5
3. To be supplied with an installation
housing.
LD47
60x60sq 4. Mounting details to be coordinated
ut-Out
Cut-out
Ø50
Ø50
Ø44.4
Ø44.4 Ø63 with Architect architectural details.
LD48
20º Ø63
20° 5. Surface temperature of luminaire to
be < 60°C.
14.6
14.6

D10 D10

D10 D10

D10

D10

D10 D10

D10 D10
W1 W1 W1 W1 W1
W1
W1
D10 W1
W1
W1
W1
W1
W1
D10 W1 D10
W1
D10 W1 D10
W1
W1 D10
W1
W1
W1 D10
W1
W1
D10 D10
W1
W1
W1 D10 D10
W1 W1 W1 W1 W1 W1 W1 W1
W1
W1
D10 W1
W1
W1
W1
W1
W1
D10

D10 W1
W1
W1

D10
D10
The drawings on this page are
indicative. Refer to the architectural
W1
W1 D10
W1
W1

W1
W1
W1

D10
D10
drawings for correct setting out,
mounting details and final dimensions.
D10
W1
W1
W1 D10 D10
W1 W1 W1 W1 W1 W1 W1 W1
W1
D10 W1
W1
W1
W1
W1
W1
W1

W1
W1
W1
Type:
W1
W1
W1
W1
W1
W1
W1

W1
W1
W1
W1
W1 W1 W1

Sheet 1/3
Section of Arrivals Feature Stair from MTC-A-94-TB-L_-_-0-00-07-009

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 167 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

D10
D10 D10
D10

D10
D10 D10
D10

D10
D10

D10
D10

D10
D10 D10
D10
W1
W1 W1
W1 W1
W1
D10
D10 D10
D10
W1
W1
W1
W1
D10
D10 D10
D10
W1
W1
W1
W1
W1
W1
D10
D10
W1 D10
D10
W1
D10
D10 D10
D10
W1
W1
W1 D10
D10
W1
W1
W1 D10
D10
W1
W1 D10
D10 D10
D10
W1
W1 W1
W1 W1
W1 W1
W1 W1
W1
D10
D10 D10
D10
W1
W1
W1
W1
D10
D10
W1
W1
W1
W1
W1
W1
D10
D10 D10
D10
W1
W1
D10
D10 D10
D10
W1
W1
W1 D10
D10
W1
W1
W1 D10
D10

W1
W1 D10
D10 D10
D10
W1
W1 W1
W1 W1
W1 W1
W1 W1
W1
D10
D10 D10
D10
W1
W1
W1
W1
D10
D10
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1 W1
W1

Detail 2

W1 W1 W1 W1 W1 W1 W1
W1 W1 W1 W1 W1
W1
W1 W1 W1 W1
W1 W1 D10
D10 D10
D10 D10
D10 W1 W1
W1 D10
D10 D10
D10 W1
W1
D10
D10 D10
D10
W1 W1
W1 W1
W1
W1
W1
W1 W1

W1 W1
W1 W1
W1 W1
W1 D10
D10 W1
W1 D10
D10 W1
W1 D10
D10
D10
D10 D10
D10
D10 D10
D10 D10
W1 W1 W1
W1 W1 W1 W1 W1
W1 W1
W1 W1 W1 W1 W1 W1 W1 W1 W1 W1

Detail 3
Section and typical level plan of Arrivals Feature Stair from MTC-A-94-TB-L_-_-0-00-07-009 The drawings on this page are
indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

W1
Sheet 2/3

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 168 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

W1

D10

Detail 1
Cross section of Arrivals Feature Stair from MTC-A-07-TB-L_-_-_-__-00-902

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

W1
Sheet 3/3

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 169 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
NIVERSAL OPEN
SFDFTTFEEPXOMJHIUXJUIEFFQTFUSFnFDUPS
t 'JYFESFDFTTFEEPXOMJHIUXJUIEFFQTFUSFnFDUP
Abu Dhabi Airports Company PJSC Specification, Section 265120

TUDPOTUSVDUJPO
t %JFDBTUDPOTUSVDUJPO
Luminaire Description: Ceiling recessed fixed downlight
FDFTTFEEPXOMJHIUXJUIEFFQTFUSFnFDUPS
Manufacturing standard: EN 60 598 Total luminaire wattage (max): 24W

DPOUSPMTFDPOEBSZSFnFDUPS
t (MBSFDPOUSPMTFDPOEBSZSFnFDUPS
Primary luminaire Die-cast aluminium Power factor: > 0.9
TUDPOTUSVDUJPO construction material: Rated luminous flux (lm): 1,550lm
Finish: Stainless steel Luminaire efficacy: 65lm/W

DPOUSPMTFDPOEBSZSFnFDUPS
Accessories:
FEXJUIQSFXJSFESFNPUFOPOEJNNJOHESJWFS
t 4VQQMJFEXJUIQSFXJSFESFNPUFOPOEJNNJOHE
Light source type:
Project 1
N/A
LED
Beam / distribution: Symmetric, see LDC
CRI / Colour temperature: > 80 / 3,000K
Driver type: Constant current Colour Variation: 17.10.2014 ≤ 3 SDCM

FEXJUIQSFXJSFESFNPUFOPOEJNNJOHESJWFS
Drive current or voltage:
BUJWFSBOHFPGBDDFTTPSJFT
t %FDPSBUJWFSBOHFPGBDDFTTPSJFT
Dimming & type:
700mA
DALI, remote
Operator
Telephone
Fax
e-Mail
Luminaire Lifetime:
Lifetime Basis:
≥ 50,000 hours
L70 / F10 @ Ta 600C
IP: IP66
BUJWFSBOHFPGBDDFTTPSJFT Projection Lighting AQ20**8W* Universal Aqua / Luminaire Data Sheet

Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
See our luminaire catalog for an image of the Recessed in exterior trays to illuminate
QUA luminaire. columns

eflector

ng driver

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Luminaire to be passively cooled.
80+ 2000lm CRI 80+CRI 80+ 3000lm
m CRI400/700/1000/1300lm 2000lm CRI
CRI 80+
80+ 3000lm CRI 80+
mI CRI 400/700lm
98 80+ 2000lm
1000lm CRI
CRICRI
80+9898 1300lm
1000lm
3000lm CRI 98
CRI 98
CRI 80+ 1300lm CRI 98
Luminaire classification according to CIE: 100 Luminous emittance 1:
98 1000lm CRI 98
CIE flux code: 96 99 1001300lm
100 86 CRI 98

115mm 127mm
115mm 127mm
96mm 96mm
115mm PRODUCT CODE 127mm
96mm Lumen Output:
(04) 400 lm
(07) 700 lm
(10) 1000 lm

108mm
(13) 1300 lm
(20) 2000 lm
(30) 3000 lm

Cut Out: Ø95mm Cut Out: Ø95mm


Colour Temps:
(27) 2700K
Cut Out: Ø95mm (30) 3000K
(35) 3500K
(40) 4000K
(3500K available in 700 Lumens and above)

Colour Rendering:
(7) Vibrancy
(8) CRI 80+
(9) CRI 98
(CRI 98 up to 1300 Lumens)

Beam Angles:

ee by
by
Available
specialorder
special order
by special order
(M) Medium: 40°
(W) Wide: 60°
Colour:
(W) White
(B) Black
(N) Nickel Satin
The drawings on this page are
AQ _ _ _ _ _ _ _ /**/ ** indicative. Refer to the architectural
drawings for correct setting out,

tt
/JDLFM4BUJOPQUJPO
/JDLFM4BUJOPQUJPO
t /JDLFM4BUJOPQUJPO
mounting details and final dimensions.
Options:
Dimming: / M3 Emergency
XL1 XL1 Page 1
/ DT Trailing Edge
/ DL Leading Edge
/ DD DALI
130

/ DA Analogue (1-10V)
XD1 81
(Other dimming options available by special order)

Type:
XD1
1000

CL
NG MPC MPC METAL UNPERFORATED CLADDING
20/03/2014 12:55
AY 04B 04B LIGHTING TRAY

3
Detail 3
SECTION DETAIL 03
SCALE 1:10
XD1
Detail of Processor Arrival ceiling components from MTC-A-41-TB-L0-1-5-00-00-874

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 170 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) L5 January 31, 2015

L2c L2c
315

L18 L18
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Concrete recessed fixed downlight

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 31W


Primary luminaire Aluminium alloy Power factor: > 0.9
construction material: Rated luminous flux (lm): 2,700lm
Finish: Stainless steel Luminaire efficacy: 87lm/W
Accessories: Concrete housing Beam / distribution: Symmetric, see LDC
Light sourceProject
type: 1 LED CRI / Colour temperature: > 80 / 3,000K
iRound
Driver type: Constant current Colour Variation: 21.08.2014
≤ 3 SDCM
iRound Operator
Drive current or voltage:
Design Maurizio Varratta 700mA Telephone
Fax
Luminaire Lifetime:
iGuzzini ≥ 50,000 hours
Dimming & type:
Design Maurizio Varratta DALI, remote e-Mail
Lifetime Basis:
iGuzzini L70 / F10 @ Ta 600C
IP: IP66 S.p.A
iGuzzini illuminazione august 2014 iRound (LED): Ceiling-mounted recessed
BV43_LZ30
with IP66 protection ratin... / Luminaire Data Sheet
august 2014
luminaire

Luminaire distribution curve (LDC)


Luminous emittance 1: Location:
See our luminaire catalog for an imageiRound
of the Recessed in concrete ceiling in Car Park
luminaire.
iRound
bridges

code code
BV43BV43

Technical
Technical description
description
Downlighter designed
Downlighter to use warm
designed to use white
warmCOB Led COB
white lampsLed aNotes:
withlampsfixedwith
Flooda optic.
fixed Consists of a Consists
Flood optic. round optical of aasr
laterallateral
component holder box and an outer casing to be
component holder box and an outer casing to 1. Refer ordered separately
be ordered where
to Section necessary.
separately
‘2.0 where
Products’The optical assem
ofnecessary.
this The
mademade of EN1706AC 46100LF
of EN1706AC aluminium
46100LF alloy and alloy
aluminium subjected
and to a multi-step,
subjected apre-treatment
to for
specification multi-step, process, in which
pre-treatment
additional requirements. the
proce
degreasing, fluorozirconation (a protective surface film) and sealing (with a nano-structured silane layer). The ne
degreasing, fluorozirconation (a protective surface film) and sealing (with a nano-structured
2. Luminaire to be passively cooled. silane
consists of a primer and a liquid acrylic paint, cured at 150°C, with a high level of weather and UV ray resistance
consists of a primer and a liquid acrylic paint, cured at 150°C, with a high level of weather and UV
sodium-calcium sealing glass is transparent, with customised serigraphy 3. Concreteon the edge,
housing to be4mm thick,forjoined to the
provided
Completesodium-calcium
with monochromesealingWarm glass is transparent,
White COB LED circuit withand
customised
cast
an optic serigraphy
in concrete
with on
installation.
a 99.93% the edge,
polished 4mm thick
super-pure alum
Complete
Luminaire classification according to CIE:
CIE flux code: 91 99 100 100a76
100 with monochrome
Luminous emittance 1: Warm White COB LED circuit and an optic with a 99.93% polished s
polished, anodized surface and built-in DALI electronic ballast. The lateral component holder box and top end
a polished,
performance blackanodized surfacewith
plastic; supplied anda built-in
silicone DALI electronic
internal ballast. The
seal to guarantee lateral component
watertightness. The optical holder
assem bo
lateralperformance blackby
box are connected plastic; supplied
nickel-plated brasswiththreaded
a silicone internalwith
connectors sealrubber
to guarantee
cable glandswatertightness.
for a watertight These
L=500mm lateral box are
rubber connected
cable. Set up forby nickel-plated
pass-through brass
wiring threaded
using two PG13.5 connectors with rubber
grey polyamide cablecable
glands, glands fo
suitable
diameter 8.5÷12.5mm. Ceiling­mounting system consists of special A2 stainless steel screws complete with bla
L=500mm rubber cable. Set up for pass-through wiring using two PG13.5 grey polyamide cable g
and plastic coupling supports. The frame comes complete with A2 stainless steel captive screws. There is a sin
diameter 8.5÷12.5mm. Ceiling­mounting system consists of special A2 stainless steel screws co
key) forand opening
plasticthe frame and
coupling for the fixing
supports. system.comes
The frame The outer casing for
complete withconcrete ceilingssteel
A2 stainless is made
captiveof black-pain
screws
galvanised sheet aluminium complete with an end cap and threaded bar, to be ordered separately. All external s
key) for opening the frame and for the fixing system. The outer casing for concrete ceilings is ma
made of A2 stainless steel.
galvanised sheet aluminium complete with an end cap and threaded bar, to be ordered separatel
made of A2 stainless steel.
Installation
Recessed in false ceilings 5 ­ 50mm thick. Hole for preparation of false ceiling ø=125mm. Installed on concrete 
Design iGuzzini outer Installation
casing, to be ordered
iGuzzini separately.
Recessed in false ceilings 5 ­ 50mm thick. Hole for preparation of false ceiling ø=125mm. Installe
june 2014 outer casing, to be ordered separately.
Size (mm)
Concrete housing and dimensions
ø228x240

Casing forSize (mm)


concrete ceilings 38
ø228x240
Colour 0

Grey (15)
code The drawings on this page are
MW89 Ø254
indicative. Refer to the architectural
Colour Page 1
drawings for correct setting out,
Weight (kg)(15)
Grey mounting details and final dimensions.
235

3.50 description
Technical
Casing for concrete ceilings
Weight (kg)
Mounting
3.50
Installation
Type:
ceiling recessed 560
.

Colour
Mounting
Wiring info
(04) ceiling recessed
BlackControl gear complete with dimmable DALI electronic ballast (220÷240Vac 50/60Hz)
XD1c
Sheet 1/2

NotesWiring info Complies with EN60598-1 and pertinent regulatio


Contract: Midfield Terminal Building Plastic
– General Contractor,
adapter disk AUH.06.10.0401
available for flush-mounting the frame on ceilings made Page
of concrete 171 of to
exposed 231view (can on
Control gear complete with dimmable DALI electronic ballast (220÷240Vac 50/60Hz)
Bulletin No. 145: Volume 3 of 4 (Revproduct Januaryof31,
07) with aluminium frame, without the stainless cover). Products set up for installation 2015 steel s
a stainless

Notes Complies with EN60598-1 and


Plastic adapter disk available for flush-mounting the frame on ceilings made of concrete exposed
Abu Dhabi Airports Company PJSC Specification, Section 265120

L5b L5b

L18b L18b

L2b L2b

XS1 XS1

XD1c

Detail 1
Detail section of Car Park Bridge from MTC-A-94-TB-L_-_-0-00-09-020

CAR PARK BRIDGE- CROSS SECTION


SCALE 1:50
The drawings on this page are
indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

XD1c
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 172 of 231
FINISH TO BE MATTE WHITE
Bulletin No. 145: Volume 3 of 4 (Rev 07) FOR OPTIMUM RESULTS January 31, 2015

TYPE L5b LIGHT


Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Ceiling recessed fixed downlight

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 14W


Primary luminaire Aluminium alloy Power factor: > 0.9
construction material: Rated luminous flux (lm): 1,026lm
Finish: Stainless steel Luminaire efficacy: 73lm/W
Accessories: N/A Beam / distribution: Symmetric, see LDC
Light sourceProject
type: 1 LED CRI / Colour temperature: > 80 / 3,000K
iRound
Driver type: Constant current Colour Variation: 19.08.2014
≤ 3 SDCM
iRound Operator
Drive current or voltage:
Design Maurizio Varratta 700mA Telephone
Fax
Luminaire
iGuzzini Lifetime: ≥ 50,000 hours
Dimming & type:
Design Maurizio Varratta DALI, remote e-Mail
Lifetime Basis:
iGuzzini L70 / F10 @ Ta 600C
IP: IP66 august
iGuzzini illuminazione S.p.A2014
BV29_LZ22 iRound (LED): Ceiling-mounted recessed
with IP66 protection ratin... / Luminaire Data Sheet
august 2014
luminaire

Luminaire distribution curve (LDC)


Luminous emittance 1: Location:
See our luminaire catalog for aniRound
image of the Departures Kerb
luminaire.
iRound
Processor Arrival pick-up
code
code
BV29
BV29

Technicaldescription
Technical description
Downlighter
Downlighter designed
designed to use
to use warm whitewhite
warm COBCOB Led lamps with aNotes:
Led lamps fixed
with aFlood
fixedoptic.
Flood Consists of a roundof
optic. Consists optical
a rounas
output cable, and outer casing, to be ordered separately
output cable, and outer casing, to be ordered separately where where necessary. The optical
1. Refernecessary.
to Section The
‘2.0 assembly and
this frame and
opticalofassembly
Products’ are
46100LF
46100LFaluminium
aluminium alloy andand
alloy subjected to a multi-step,
subjected pre-treatment
to a multi-step, process,
pre-treatment
specification in which in
forprocess,
additional
L17b
the main phases
which the main
requirements. arepha
de
D12
fluorozirconation (a protective surface film) and sealing (with a nano-structured silane layer). The next painting s
D12
fluorozirconation (a protective surface film) and sealing (with a nano-structured silane
2. Luminaire to be passively cooled. layer). The nex
D12 primer and a liquid acrylic paint, cured at 150°C, with a high level of weather and UV ray resistance. The temper
primer and a liquid acrylic paint, cured at 150°C, with a high level of weather and UV ray resistance. T
D12
sealing glass is transparent, with customised serigraphy on the edge, 4 mm thick, joined to the frame with silico
D12
D12
sealing glass
monochrome is transparent,
Warm WhiteD12
COB with circuit
LED customised
and an serigraphy
optic with a on the edge,
99.93% 4 mm
polished thick, joined
super-pure to the
aluminium frame
L17b

reflector
monochrome Warm White COB 1:LED circuit and an optic with a 99.93% polished super-pure aluminiu
D12
Luminaire classification according to CIE: 100 Luminous emittance
CIE flux code: 97 100 100 100 anodized
76 surface and D12 built-in electronic ballast. Supplied with an output cable L=1m long. Ceiling-mounting syst

anodized
special surface and
A2 stainless steelbuilt-in
screws
D12 electronic ballast.
complete with blackSupplied
aluminiumwithalloyanand
output
L17b
cable
plastic L=1m
coupling long. Ceiling-mo
supports. The frame
U3 U3
special
with A2 A2 stainless
stainless steel
D12
steel
captive
D12
screws
screws. complete
There is awith black
single tool aluminium
(No. 3 Allen alloy
key) and
for plastic
opening coupling
the frame supports
and for the
U3
with casing
outer A2 stainless steel ceilings
for concrete captiveisscrews.
made ofThere is a single
black-painted tool (No. 3 Allen
ready-galvanised sheetkey) for opening
aluminium completethe with
framean ae
threaded
outer casing bar, tofor
beconcrete
ordered separately.
ceilings is All external
made screws used are
of black-painted made of A2 stainless
ready-galvanised sheetsteel.
aluminium comple
L17b

threaded bar, toU3 be ordered separately. All external screws used are made of A2 stainless steel.
Installation U3

Recessed in false ceilings 5 ­ 50mm thick. Hole for preparation of false ceiling ø=125mm. Installed on concrete 
U3
Installation
outer casing, to be ordered separately.
Recessed in false ceilings 5 ­ 50mm thick. Hole for preparation of false ceiling ø=125mm. Installed on
outer casing, to be ordered separately.
Size (mm)
ø140x163
Size (mm)
ø140x163
Colour
Grey (15)
XD1d XD1d Colour XD1d
Grey (15)
XD1d

Weight (kg)
0.95
The drawings on this page are
Weight (kg) Page 1 indicative. Refer to the architectural
L17 Mounting
0.95 L17
L17 D12
drawings for correct setting out,
D12
L17
L17

ceiling recessed mounting details and final dimensions.

Mounting
Wiring info
ceiling recessed Type:
Control gear complete with electronic ballast (220÷240Vac 50/60Hz)
U3
U3 U3 U3 U3
U3

Wiring info
Notes
Control gear complete with electronic ballast (220÷240Vac 50/60Hz)
Plastic adapter disk available for flush-mounting the frame on ceilings made of concrete exposed to view (can on
XD1d
product with aluminium frame, without the stainless cover). Products set up for installation ofSheet
a stainless
1/3 steel s
Section detail of entrance doors from MTC-A-94-TB-L_-_-0-00-09-038
Notes
Contract: Midfield Terminal Building –Plastic
Generaladapter disk available
Contractor, for flush-mounting the frame on ceilings madeComplies
AUH.06.10.0401 Page 173with
of EN60598-1
of concrete 231
exposed toand
v
Bulletin No. 145: Volume 3 of 4 (Revproduct
07) January 31, 2015
with aluminium frame, without the stainless cover). Products set up for installation of a stainl

Complies with EN6


Abu Dhabi Airports Company PJSC Specification, Section 265120

XD1d XD1d XD1d

L17 L17

XL2e

XD1d XD1d XD1d


XD1d

U3 U3 U3 U3

XL2e

Detail 3
Section detail of entrance doors from MTC-A-94-TB-L_-_-0-00-09-038

XL2e

XD1d XD1d XD1d


XD1d

XL2e
XL2e

adjustable LED
downlight

XD1d XD1d

XL2e

XL2e

adjustable LED
downlight

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.
XL2e XD1d XL2e

XD1b
solid to Type:
eliminate
shadows ARUP LIGHTING
MARK_UPS
Detail 3
Rev1 XD1d
Sheet 2/3
Detail plans and section of Lighting Lozenge from MTC-A-93-TB-L_-_-_-__-00-530

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 174 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

XL2e
XL2e

XD1
XD1d XD1d XD1d

Detail 1

XL2e

XD1d XD1d

XL2e

adjustable LED
downlight

Detail 5
Detail plans of Lighting Lozenge from MTC-A-93-TB-L_-_-_-__-00-530

XD1b

ARUP LIGHTING
MARK_UPS
Rev1

XL2e XL2e

The drawings on this page are


solid to
eliminate indicative. Refer to the architectural
shadows drawings for correct setting
out, mounting details and final
dimensions.

Type:

XD1d
Sheet 3/3

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 175 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Recessed fixed downlight

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 34W


Primary luminaire Aluminium alloy Power factor: > 0.9
construction material: Rated luminous flux (lm): 2,700lm
Finish: Stainless steel Luminaire efficacy: 79lm/W
Accessories: N/A Beam / distribution: Symmetric, see LDC
Light sourceProject
type: 1 LED CRI / Colour temperature: > 80 / 3,000K
iRound
Driver type: Constant current Colour Variation: 20.08.2014
≤ 3 SDCM
iRound Operator
Drive current or voltage:
Design Maurizio Varratta 700mA Telephone
Fax
Luminaire
iGuzzini Lifetime: ≥ 50,000 hours
Dimming & type:
Design Maurizio Varratta DALI, remote e-Mail
Lifetime Basis:
iGuzzini L70 / F10 @ Ta 600C
IP: IP66 S.p.A
iGuzzini illuminazione august 2014 iRound (LED): Ceiling-mounted recessed
BV43_LZ30
with IP66 protection ratin... / Luminaire Data Sheet
august 2014
luminaire

Luminaire distribution curve (LDC)


Luminous emittance 1: Location:
iRound
See our luminaire catalog for an image of the Processor Arrival pick-up
luminaire.
iRound

code
code
BV43
BV43

Technical
Technical description
description
Downlighter
Downlighterdesigned to use to
designed warmusewhite
warmCOB LedCOB
white lampsLedwith aNotes:
lamps fixed Flood
with optic.Flood
a fixed Consists of aConsists
optic. round optical
of a as
ro
lateral component holder box and an outer casing
lateral component holder box and an outer casing to be to be ordered separately
ordered
1. Refer where ‘2.0
necessary.
separately
to Section whereThe
Products’ optical assem
necessary.
of this The
made of EN1706AC
made 46100LF
of EN1706AC aluminium
46100LF alloy andalloy
aluminium subjected to specification
a multi-step,
and subjected pre-treatment
to afor
multi-step, process, in which
pre-treatment
additional requirements. proces the
degreasing, fluorozirconation (a protective surface film) and sealing (with a nano-structured silane layer). The ne
degreasing, fluorozirconation (a protective surface film)2. Luminaire and sealing (with a nano-structured
to be passively cooled. silane
consists of a primer and a liquid acrylic paint, cured at 150°C, with a high level of weather and UV ray resistance
consists of a primer and a liquid acrylic paint, cured at 150°C, with a high level of weather and UV
sodium-calcium sealing glass is transparent, with customised serigraphy on the edge, 4mm thick, joined to the
sodium-calcium
Complete sealing
with monochrome glass
Warm is transparent,
White with and
COB LED circuit customised serigraphy
an optic with a 99.93%on the edge,
polished 4mm thick,
super-pure alum
Luminaire classification according to Complete
polished, anodized surface and built-in DALI electronic ballast. The lateral component holder box and top endsu
with monochrome Warm White COB LED circuit and an optic with a 99.93% polished
CIE: 100 Luminous emittance 1:
CIE flux code: 91 99 100 100a76
a polished,
performance anodized
black surface with
plastic; supplied and abuilt-in
siliconeDALI electronic
internal ballast. The
seal to guarantee lateral component
watertightness. holder
The optical assembox
lateralperformance black plastic;
box are connected suppliedbrass
by nickel-plated withthreaded
a silicone internal seal
connectors to guarantee
with rubber watertightness.
cable glands for a watertightThese
L=500mmlateralrubber
box are connected
cable. Set up forbypass-through
nickel-platedwiringbrass threaded
using connectors
two PG13.5 with rubber
grey polyamide cablecable glands
glands, for
suitable
diameter 8.5÷12.5mm. Ceiling­mounting system consists of special A2 stainless steel screws complete with bla
L=500mm rubber cable. Set up for pass-through wiring using two PG13.5 grey polyamide cable gl
and diameter 8.5÷12.5mm. Ceiling­mounting system consists of special A2 stainless steel screws com
plastic coupling supports. The frame comes complete with A2 stainless steel captive screws. There is a sin
key)and for opening
plastic the frame supports.
coupling and for the Thefixingframe
system. The outer
comes casingwith
complete for concrete ceilings
A2 stainless is made
steel of black-pain
captive screws.
galvanised sheet aluminium complete with an end cap and threaded bar, to be ordered separately. All external s
key) for opening the frame and for the fixing system. The outer casing for concrete ceilings is mad
made of A2 stainless steel.
galvanised sheet aluminium complete with an end cap and threaded bar, to be ordered separately
made of A2 stainless steel.
Installation
Recessed in false ceilings 5 ­ 50mm thick. Hole for preparation of false ceiling ø=125mm. Installed on concrete 
outerInstallation
casing, to be ordered separately.
Recessed in false ceilings 5 ­ 50mm thick. Hole for preparation of false ceiling ø=125mm. Installed
outer casing, to be ordered separately.
Size (mm)
ø228x240
Size (mm)
ø228x240
Colour
Grey (15) The drawings on this page are
indicative. Refer to the architectural
Colour Page 1
drawings for correct setting out,
Weight (kg)
Grey (15) mounting details and final dimensions.
3.50

Weight (kg)
Mounting
3.50 Type:
ceiling recessed

Mounting
Wiring info
ceiling recessed
Control gear complete with dimmable DALI electronic ballast (220÷240Vac 50/60Hz)
XD2
Notes
Wiring info
Contract: Midfield Terminal Building Plastic
– General Contractor,
adapter AUH.06.10.0401
disk available Page
for flush-mounting the frame on ceilings made of concrete 176 of to
exposed 231
view (can on
Control gear complete with dimmable DALI electronic ballast (220÷240Vac 50/60Hz)
Bulletin No. 145: Volume 3 of 4 (Revproduct Januaryof31,
07) with aluminium frame, without the stainless cover). Products set up for installation 2015 steel s
a stainless

Notes Complies with EN60598-1 and


Plastic adapter disk available for flush-mounting the frame on ceilings made of concrete exposed t
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Surface mounted linear luminaire

Manufacturing standard:
Project 1 EN 60 598 Lamp Type: T5 - High Output, Long Life
Primary luminaire Extruded aluminium Lamp Wattage: 2 x 50W
03.04.2014

Operator
construction material: Telephone
Fax
Lamp Manufacturer: -
e-Mail
Finish: Stainless steel Beam / distribution: Asymmetric, see LDC
Accessories: ELLIPTIPARMounting brackets
F164-D255-H-02-1-00-0-00-00 CRI / Colour
EXTRUDED temperature:
SEMI-SPECULAR METAL > 80 / 3,000K
REFLECTOR WITH DIFFUSE METAL END PLATES, EXTRUDED WHITE PAINTED
IP: Ballast/Transformer:
METAL BALLAST COVER, EXTRUDED CLEAR PLASTIC LENS, EXTRUDED WHITE DALI, integral
IP54
PAINTED METAL FORWARD VISOR WITH FABRICATED Lamp
WHITElife:
PAINTED METAL END ≥ 48,000 hours
PLATES. / Luminaire Data Sheet

Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
See our luminaire catalog for an image of theT5 Fluorescent Style
Processor 164 lighting tray
Arrival exterior
luminaire.
Pendant Hanger
ƒ



 
…†‡

ˆ


 
Notes:
ngUplighting Medium T5 Fluorescent
Plate Cove* 1:10outdoor,
Scale integral 1. Refer to Section ‘2.0 Products’ of this
 Luminaire classification according to CIE: 1 Due to missing symmetry properties, no UGR table
Style
 F164 1:8 Scale CIE flux code: 11 27 40 01 60 cantobe displayed for this luminaire.
Pendantspecification
Hanger for additional requirements.
Lamp Length (center
Š ˆ Length center of hubs) 2. Luminaire with adjustable and

  ‹ Œ‹ lockable mechanism for aiming.
  †‡Ž 1 x 2' 25-1/4" (640mm)
  3. When indicated as a continuous
1 x 3' 37" (940mm)
 line on drawing , luminaires shall be
300 1 x 4' 48-3/4" (1240mm)

mounted end to end.
 €   1 x 5' 60-5/8" (1540mm)
 ‰ 4. Mounting detail to be coordinated with
  2 x 3' 72" (1830mm)
Architect.
 2 x 4' 96" (2440mm)
* For cove design guidance,
see Applications
150 Section
1240
Features
Surface Hanger Mounting Plate Cove * 1:10 Scale
ubs with G Specular extruded K Tubular steel arm or stem  Reflector optimized for T5 – uplight canopies, vaults,
g gaskets aluminum reflector L Aluminum mounting plate soffits with unequaled uniformity from minimal setbacks
parately) H Surface or pendant  Secure snap-on UVLamp
resistantLength
acrylic(center
lens – to
easy to relamp
tronic ballast/ hangers with hubs
M Access with gasketed Length center of hubs)
 Extruded visor provides shielding – concealed drainage
U
way (ordered separately)
cover (electrical feed)
1 x 2' 25-1/4"1000
(640mm) 2.2
 Polyester powder coat – exceeds hour salt spray test
N Recessed outlet box
nduit supports J Aluminum cover 1 x 3' – 37"
 Integral electronic ballast (940mm)
internal wireway for thru wiring
(conceals fasteners) O 1/2" fittings (by others)
1 x 4' 48-3/4" (1240mm)
Performance 1 x 5' 60-5/8" (1540mm)
Page 1
TYPE:
2 x 3' 72" (1830mm)
ˆ‘
Two parabolic reflector
sections drive light across ’
-2-00-0-30-00-G 2 x 4' 96" (2440mm)
the overhead
* For cove design guidance, plane from
see Applications
one Section
edge. An elliptical ˆ‘
ace Linear Fluoroscent, Integral Ballast; 2-55W T5HO section redirects its light ’
EndSpecifications XL1
and Intermediate Mounting Hubs; Semi-Gloss White; 277V to a parabola and shields
XL1
The drawings on this Features
page are
orA CSA certified the lamp. Asymmetry is
UV and impact for United States;
resistant 3000K;hubs
D Aluminum No with
Options; Revision
G Specular extruded
maximized resulting in K Tubular steel
   indicative.
arm or stem Refer to the architectural
Reflector optimized for T5 – upl
acrylic snap-on lens silicone o-ring gaskets aluminum
highreflector
beam efficiency L Aluminum drawings
Πmounting plate soffits with
for correct setting out, unequaled uniformi
with silicone gasket (ordered separately) H Surfaceand superior surface
or pendant mounting details and Secure
final dimensions.
snap-on UV resistant acr
M Access with gasketed
B Die-cast aluminum E Integral electronic ballast/ hangersuniformity.
with hubsThe fast cover (electrical feed) Extruded visor provides shieldin
“runback” minimizes L5c

end plates internal wireway (ordered separately)


wasted spill light. N Recessed Adjustable – Polyester powder coat – exceed
outlet box
maximum Cd
C Extruded aluminum visor F 1/2" rigid conduit supports J Aluminum Note:cover
Lamp light output may
shown
O 1/2" fittings
Type:
aimed
(by others)
Integral electronic ballast – inte
with stamped end XL3 plates (by others) be fasteners)
(conceals
XL3 diminished when operated
in low ambient temperatures. 25° above
horizontal.
For complete Performance
TYPE:photometrics,
XL1
PROJECT NAME: Abi Dhabi
visit thelightingquotient.com
Detail 1 Two parabolic reflector
CATALOG NUMBER: F164-T255-H-02-2-00-0-30-00-G Cradle to Cradle CertifiedCM sections drive light across
Section of Processor Arrival exterior lighting tray from MTC-A-41-TB-L0-1-5-00-00-874
is a certification mark licensed the overhead Sheet 1/2
plane from
by the Cradle to Cradle Products
2; U.K. Patent 2,415,773. Innovation Institute.
one edge. An elliptical
U2.2 Up Lighting; Outdoor Medium Surface Linear Fluoroscent, Integral Ballast; 2-55W T5HO section redirects its light
Fluorescent Lamp
Contract: (included);
Midfield TerminalUse with –End
Building and Intermediate
General Mounting Hubs; Semi-Gloss White; 277V
Contractor, AUH.06.10.0401 to a parabola
Page 177 andofshields
231
Electronic Ballast; No Volume
Options; UL4listed or CSA certified for United States; 3000K; No Options; Revision the lamp. Asymmetry is
Bulletin No. 145: 3 of (Rev 07) January 31, 2015
maximized resulting in
G 12-19-12 high beam efficiency
and superior surface
uniformity. The fast
“runback” minimizes
A
Abu Dhabi Airports Company PJSC Specification, Section 265120

XL1 XL1

130
XD1 XD1
1000

CL
NG MPC MPC METAL UNPERFORATED CLADDING
AY 04B 04B LIGHTING TRAY

3 SECTION DETAIL 03

Detail 3 SCALE 1:10

Detail of Processor Arrival ceiling components from MTC-A-41-TB-L0-1-5-00-00-874

L5

L2c L2c
315

L18 L18
4800

3650 3650

7300

CL
MPC METAL PERFORATED CLADDING 03 30.11.14 BULLETIN 134
04A SERVICE BOOM 02 31.10.14 BULLETIN 120
01 25.02.13 BULLETIN 07
04 00 15.07.12 ISSUED FOR CONSTRUCTION

ISSUED FOR CONSTRUCTION

FILE @ 5A SHOWN DOTTED


ABU DHABI
AIRPORTS COMPANY
L5 ABU DHABI AIRPORTS COMPANY

Kohn Pedersen Fox Associates


(International) PA
Architects and Planning Consultants
7a Langley Street
London WC2H 9JA
England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com

ABU DHABI INTERNATIONAL AIRPORT


L2c L2c MIDFIELD TERMINAL COMPLEX
275

330

L18 L18
4800
PROCESSOR ARRIVAL
CEILING COMPONENTS - LIGHTING TRAY/
7500 SERVICE BOOM
CL
MTC A 41 TB __ L0.1 5.00 00.874 03

05/5a KPF MC KF JH 15.07.2012

WBS AUH.06.10.0401

2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights reserved. Do not scale.

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

XL1
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 178 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Canopy recessed linear profile

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 33W


Primary luminaire Aluminium alloy Power factor: > 0.9
construction material: Rated luminous flux (lm): 1,776lm
Finish: Stainless steel Luminaire efficacy: 54lm/W
Accessories: Installation housing Beam / distribution: Asymmetric, see LDC
Project 1
Light source type: LED CRI / Colour temperature:
04.04.2014 > 80 / 3,000K
BEGA Lichttechnische Spezialfabrik
Driver type: Constant currentHennenbusch · D -Colour
Operator
Telephone
BEGA Lichttechnische
58708 Menden
Spezialfabrik
!
Variation: ≤ 3 SDCM
Drive current or voltage: 350mA - 58708Luminaire
Fax
Hennenbusch · D e-Mail Menden !
Lifetime: ≥ 50,000 hours
Recessed ceiling luminaire IP 65 6845
Dimming & type: DALI, integral Lifetime Basis:
6845 TWO L70 / F10 @ Ta 60 C
0
Recessed ceiling luminaire
BEGA-US IPX 65
6845LED 25-1/2"W. 5-3/8"L. X 3-3/4"H. LINEAR LED LUMINAIRE
IP: IP65
MODULES WITH TWELVE 3000K LEDSDate ALUMINUM REFLECTOR AND PRISMATIC
Date ACRYLIC LENS / Luminaire Data Sheet

Luminaire distribution curve (LDC)


Luminous emittance 1: Location:
See our luminaire catalog for an image of the Departures external canopy
luminaire.

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Luminaire to be passively cooled.
3. Luminaires to be mounted end to end
123 x 635 to form a continuous row.
asymmetrical Luminaire classification according to CIE: 100 Due to missing symmetry properties, no UGR table
angestrahlte Fläche · illuminated surface

CIE flux code: 42 79 96 100 100 can be displayed for this 123 x 635
luminaire. 4. Mounting detail to be coordinated with
metrical
135
angestrahlte Fläche · illuminated surface

25 - 60

ass and low the Architect.


surface éclairée
135

lighting
low tasks.
25 - 60

nd
gings of
surface éclairée

tasks.
f
100
100

oy, aluminium
minium 645

e 645

Lamp Article No. 6845


e aluminium LED 3000 K 28.6Article
W Colour temperature 3000 K.
x 123 mm Lamp No. 6845
inium Connected
LED 3000 K wattage 28.6 W 33Colour
W Also available with
temperature 30004000
K. K on request.
mm Lamp wattage
Connected luminous flux 33 2400
W lm available
Also 3000 K –with article
4000number
K on request.
hieved by Luminaire luminous flux 17763000
lm K 4000 K – article number + K4
Lamp luminous flux 2400 lm – article number
ddbyclaws Colour rendering
XL1b
fluxindex Ra > 4000
80 K – article number + K4
ss steel to Luminaire
ws BEGA
luminous
Article No.
1776 lm
2x LED-0178/830
Colour white or silver
Colour rendering index R > 80
eelopening
to
a
Colourwhite
white– orarticle
silvernumber
of mains BEGALED
ging Article No.
4000 K
2x LED-0178/830
white
28.6 W
silver
– – article
article number number + A
ains silver – article number +A
Connected
LED 4000 K wattage 28.6 W 33 W Accessories
Lamp luminous
Connected wattage flux 2560 lm
33 W Accessories767 Installation housing
Lamp Luminaire
luminous fluxluminous flux 2560 lm1894767 For preparing
lm Installation the recess opening it can be
housing
practicaltheto use an installation housing The drawings on this page are
Colour
Luminaire rendering
luminous fluxindex 1894 lm Ra > For
80 preparing recess opening it can be made of
Page 1
indicative. Refer to the architectural
ColourBEGA Article
rendering No.
index 2x LED-0178/840
Ra > 80 practical aluminium.
to use an installation housing made of drawings for correct setting out,
BEGA Article No. 2x LED-0178/840 aluminium.
A separate instructions for use can be mounting details and final dimensions.
provided
A separate upon request.
instructions for use can be
provided upon request.
Type:

t water jets
r jets
Detail 5
XL1b
Section from departures external canopy MTC-A-34-TB-L2-0-_-__-00-405 Sheet 1/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 179 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

XL1b

Detail 6
Canopy connection detail from MTC-A-94-TB-L_-_-0-00-09-030

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

XL1b
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 180 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Continuous integrated linear profile

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 21W/m


Primary luminaire Extruded aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 1,200lm/m
Finish: See Notes Luminaire efficacy: 57lm/W
Accessories: See Notes Beam / distribution: Symmetric, see LDC, see LDC
Light sourceProject
type:1 LED CRI / Colour temperature: > 80 / 3,000K
Driver type: Constant current Colour Variation: 04.04.2014
≤ 3 SDCM
42181011 Operator
Drive current or voltage: 700mA Telephone Luminaire Lifetime:
Fax
≥ 50,000 hours
e-Mail
Dimming & type: DALI, integral Lifetime Basis: L70 / F10 @ Ta 600C
Times New Roman
e 3000 K, IP: ZUMTOBEL
colour rendering index IP54 luminous
42181011
Ra 80, Total (STD - Standard)
flux of SLOT2 24W LED830 L1253 PM LDO IP54 /
50,000h at 70 % luminous flux with LED converter. Slave luminaire Luminaire Data Sheet
in natural anodised finish. Opal acrylic glass PMMA diffuser with Luminaire distribution curve (LDC)
ost uniformly bright over 100% of its face. Luminaire comprises Luminous emittance 1: Location:
lastic end-cap set. Luminaire
See our wired
luminairewith halogen-free
catalog leads. Degree
for an image of the Integrated in exterior perimeter detail
g luminaire.
Centre space showers
Gatehouses exterior

42180995
Notes:

Times New Roman 1. Refer to Section ‘2.0 Products’ of this


rendering index Ra 80; Total luminous flux of specification for additional requirements.
uminous flux with LED converter. Slave luminaire for
finish. Opal acrylic glass PMMA diffuser with 2. Luminaire to be passively cooled.
100% of its face. Luminaire comprises housing and 3. Continuous profiles to be supplied
2 fixing screws. Luminaire wired with halogen-free with all necessary accessories including
Luminaire classification according to CIE: 100 Luminous emittance 1:
CIE flux code: 48 79 95 100 100
mounting profiles, opal covers, brackets
and end caps.
4. Lengths required to be confirmed by
site measurement prior to ordering and
coordinated with Architect.
5. Fixtures to be of stainless steel finish
with opal cover.

ZS_SLO_M_2_LED_alle_1200.wmf
ceiling level

STD - standard

• Light Distribution: STD - standard


• Lamps: 1 x LED-Z196 / 24W
• Total luminous flux of luminaire: 1498 lm
• Luminaire efficacy: 57 lm/W
• Rated life: 50000h L70 at 25°C
ZS_SLO_M_2_LED_alle_600.wmf
• Colour Rendering Index min.: 80XL2 The drawings on this page are
• Colour temperature:
STD -3000 Kelvin
standard indicative. Refer to the architectural
Page 1
• Chromaticity tolerance (initial MacAdam): 4 drawings for correct setting out,
• Ballast: 1 x 00109069 CONV PH Xit 75W 0,12-0,4A
ps: 1 x LED-Z174 PM / 12W
mounting details and final dimensions.
215V
l luminous flux of luminaire: 858TD
lm
• Connected
inaire efficacy: 65 lm/W Load: 26.3 W Lambda = 0.98
ed life: 50000h• Dimming:
L70 at 25°CLDO dimmable to 10% over DALI Type:
our Rendering• Index min.: 80 category: E - Dust-proof IP5X
Maintenance
our temperature: 3000 Kelvin U5
omaticity tolerance (initial MacAdam): 4
ast: 1x LED_Con LED-Converter
nected Load: 13.2 1W Lambda = 0.98
Detail
XL2
ming: LDO dimmable to 10% over DALI Sheet 1/2
Section Dof- Single
ntenance category: Loaded
Enclosed IP2X Pier from MTC-A-03-TB-L_-_-1-00-00-482

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 181 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

1. FOR LIGHT FITTING INTEGRATION AND FIXING DETAILS


REFER TO A-94 & A-93 ARCHITECTURAL DRAWINGS AND
LIGHTING SPECIFICATIONS 265120

2. ARCHITECTURAL BACKGROUNDS ADDED FOR CLARITY

L23

XL2

Detail 1
Section of a Gatehouse exterior from MTC-A-30-TB-L_-_-0-00-00-550
02 31.01.15 BULLETIN 145
01 31.10.14 BULLETIN 120
00 15.07.12 ISSUED FOR CONSTRUCTION
S - DETAIL 1

ISSUED FOR CONSTRUCTION

ABU DHABI
AIRPORTS COMPANY
ABU DHABI AIRPORTS COMPANY

Kohn Pedersen Fox Associates


(International) PA
Architects and Planning Consultants
7a Langley Street
London WC2H 9JA
England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com

FIXING TO SOLID
STRUCTURE BY
OTHERS
MIN 150mm

ABU DHABI INTERNATIONAL AIRPORT


MIDFIELD TERMINALThe
COMPLEX
drawings on this page are
MIN 150mm indicative. Refer to the architectural
XL2
PIER TYPICAL SECTION drawings for correct setting out,
TYPICAL DETAILS mounting details and final dimensions.
SECTIONS AND DETAILS
REFLECTOR TRAY WITH LAMP
AND CONTROL GEAR
MTC A 94 TB __ L_._ 0.00 09.032 02
Type:
KPF MC KF JH 25.09.2009

CTION THROUGH LANDSLIDE APRON FACADE


Detail 5
WBS AUH.06.10.0401 XL2
Section through Landslide Apron facade from MTC-A-94-TB-L_-_-0-00-09-032
2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights reserved. Do not scale.
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 182 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
FLUORESCENT

Abu Dhabi Airports CompanyMT-50


PJSC IP67 Specification, Section 265120
Waterproof Lighting
Luminaire Description: Surface mounted luminaire in a staggered arrangement
Clear cover
230v Part nr Wattage Length LOr Lm/W CIrCuIt
nate
coat steel
Manufacturing
50Hz
standard: EN 60 598 Lamp Type:
POWer W
T5 - High Efficiency, Long Life
MT50 8w 8w 403-433 90 43.1 11
Primary
IP67 luminaire
Class I MT50 14w 14w Plastic
660-690 101 62.6 Lamp Wattage:
15.5 13W, 19W, 25W, 32W
MT50 21w 21w 960-990 100 68.3 23
constructionProject
material: Lamp Manufacturer: -
amp, 1
ounting bracket MT50 28w 28w 1260-1290 106 73.1 30

T5 Waterproof Lighting
F 03.04.2014
Finish: Stainless steel Beam / distribution: Symmetric, see LDC
T5 G5 MT50 35w 35w 1560-1590 99 76.5 38
MT50 21w LED-EC 21w 1000-1030 100 68.3 26.5 Operator
Telephone
106 Accessories:
EEI 850 MT50 28w LED-EC 28w
Mounting brackets
1300-1330 106 73.1 33.5 Fax CRI / Colour temperature: > 80 / 3,000K
A2 GWT MT50 35w LED-EC 35w 1600-1630 99 76.5 41.5 e-Mail
f
IP: Satin cover
IP54 Ballast/Transformer: DALI, integral
d TUBE CAP
ø 50mm ø 52mm Encapsulite
Part nr
International
Wattage Length
Ltd.
LOr Lm/W
MT50 14W
CIrCuIt
linear Lamp life:
cylindrical luminaire with clear cover ≥ 48,000 hours
cy conversion
steel mounting
data derived from
POWer W range test series / Luminaire Data Sheet
MT50 8w SC 8w 403-433 82 40.7 11
ured sleeves MT50 14w SC 14w 660-690 92 59.5 15.5 Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
eflectors MT50 21w SC 21w 960-990 91 63.4 23
on kit
caps
See
MT50our
28wluminaire
SC catalog
28w for an image
1260-1290 97 of67.6
the 30 Processor Arrival
e +10°C only luminaire.
MT50 35w SC 35w 1560-1590 91 71.5 38
9w 49w and 54w MT50 21w SC LED-EC21w 1000-1030 91 63.4 26.5
please enquire MT50 28w SC LED-EC28w
MT50 35w SC LED-EC35w
1300-1330
1600-1630
97
91
67.6
71.5
33.5
41.5
FLUORESCENT
bracket cost option
MT-50 IP67

MT-50 IP67
Add 1-10v, DALI or DSI to product code for dimmable option +10C only.
Photometric files Add ST Standard, TW Thru wired, or P&G plug and go.
available
TW and P&G are 30mm longer.
ST (Standard)

TW (Thru-Wired)
Waterproof Lighting
PG (Plug and Go)
Notes:
Specification Clear cover
Need 1. Refer to Section ‘2.0 Products’ of this
Luminaire classification according to CIE: 88
something Polycarbonate 230v Luminous
Part nr
emittance 1: Wattage Length LOr Lm/W for additional
CIrCuIt requirements.
Outer case specification
changed to CIE flux code: 33 61 84 87 82 50Hz POWer W
reflector
suit your
If we can,
White pre coat steel 2. Lamp wattages indicated (13W,
we will. MT50 8w 8w 403-433 90 43.1 11
project? 19W, 25W, 32W) refer to different types
Lamp holder Please ask!
T5 G5 MT50 14w 14w 660-690 101 62.6 15.5
IP67 Class I of lamps to be combined to form a
MT50 21w 21w 960-990 continuous
100 68.3line. Lengths
23 required to be
Includes M3 x 16 Col 840 lamp, ø 50 mm
confirmed by site measurement prior to
2 part mounting bracket MT50 28w 28w 1260-1290 106 73.1 30

T5 Waterproof Lighting
F ordering and coordinated with Architect.
T5 G5
Please Note: Do not use or clean with chemicals. MT50 35w 35w 1560-1590 99 76.5 38
energy efficiency A2 66mm Not for use submerged in water. 3. Luminaires to be mounted in a
MT50 21w LED-EC 21w 1000-1030 100 68.3 26.5
staggered arrangement with a minimum
Light output 5mm
25mm

ratio (LOR) 82-106


Please call for further information
EEI 850 MT50 28w LED-EC 28w 1300-1330 lamp
106 overlap
73.1 of 100mm.
33.5
or options on 01525 376974
A2 GWT MT50 35w LED-EC 35w 1600-1630 99 76.5 brackets
4. Mounting 41.5
to be provided.
or email reply@encapsulite.co.uk
Photometrics ldt 25mm
ies pdf 17
125mm

Options Thru wired TUBE CAP Satin cover


Plug & Go ø 50mm ø 52mm Part nr Wattage Length LOr Lm/W CIrCuIt
Emergency conversion POWer W
Stainless steel mounting
clips MT50 8w SC 8w 403-433 82 40.7 11
DDP coloured sleeves MT50 14w SC 14w 660-690 92 59.5 15.5
Custom reflectors MT50 21w SC 21w 960-990 91 63.4 23
Suspension kit
MT50 28w SC 28w 1260-1290 97 67.6 30
Black end caps
Indication of minimum lamp overlap MT50 35w SC 35w 1560-1590 91 71.5 38
Dimmable +10°C only
MT50 21w SC LED-EC21w Page 1
1000-1030 91 63.4 26.5
HO 24w 39w 49w and 54w
available please enquire MT50 28w SC LED-EC28w 1300-1330 97 67.6 33.5
MT50 35w SC LED-EC35w 1600-1630 91 71.5 41.5
The drawings on this page are
MT-50 IP67

Mounting bracket cost option


indicative. Refer to the architectural
Add 1-10v, DALI or DSI to product code for dimmable option +10C only.
drawings for correct setting out,
Photometric files Add ST Standard, TW Thru wired, or P&G plug andmounting
go. details and final dimensions.
available
TW and P&G are 30mm longer.
ST (Standard)
Type:

TW (Thru-Wired)
XL2c
Sheet 1/2

PG (Plug and Go)

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 183 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Need
something
changed to
If we can,
02 31.01.15 BULLETIN 145
01 31.10.14 BULLETIN 120
00 25.05.13 BULLETIN 14

Abu Dhabi Airports Company PJSC ISSUED FOR CONSTRUCTION Specification, Section 265120

ABU DHABI
AIRPORTS COMPANY
ABU DHABI AIRPORTS COMPANY

Kohn Pedersen Fox Associates


(International) PA
XL2c Architects and Planning Consultants
7a Langley Street
London WC2H 9JA
England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com
180

ABU DHABI INTERNATIONAL AIRPORT


MIDFIELD TERMINAL COMPLEX

PROCESSOR ARRIVAL
TYPE H: CURB RCP &
CEILING SECTIONS

Detail
5 5 SECTION
DETAIL MTC A 41 TB __ L0.0 5.00 00.188 02
SCALE 1:5
Ceiling section of Processor Arrival from MTC-A-41-TB-L0-0-5-00-00-188
KPF MC KF JH 25.05.2013

WBS AUH.06.10.0401

2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights reserved. Do not scale.

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

XL2c
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 184 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Continuous integrated linear profile

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 15W/m


Primary luminaire LED strip mounted on Power factor: > 0.9
construction material: extruded aluminium profile Rated luminous flux (lm): 1,265lm/m
Finish: N/A Luminaire efficacy: 84lm/W
Accessories: See Notes Beam / distribution: Symmetric, see LDC
Light source type: LED CRILED
/ Colour temperature:
Linear ™ – VarioLED™> 80 / 3,000K
Driver type: Project 1 Constant Voltage Colour Variation: 10.08.2014
≤ 3 SDCM LED Linear ™ – VarioL
Drive current or voltage: 24V Operator Luminaire Lifetime: ≥ 50,000 hours
Telephone
Dimming & type: DALI, remote Lifetime Basis: L70 / F10 @ Ta 600C
YDRA HD15 IP67
Fax
e-Mail

IP: IP67
VarioLED™ HYDRA HD15 IP67 Wasser- und UV-geschützte Linearleuchte
LED Linear GmbH / Luminaire Data Sheet

Luminaire
im Aluminiumprofil in bis zu 2 m Länge im Luminous distribution
emittance 1: curve (LDC) Location:
Polyurethanverguss mit 110 mm IP67 Steck-
See our luminaire catalog for an image of the Wasser- und UV-geschützte Linearleuchte
Exterior Lighting Lozenges
luminaire. verbinder an beiden Enden.
im Aluminiumprofil in bis zu 2 m Länge im
LED Linear ™ – Vario
Up to 2 m length, water & UV resistant Polyurethanverguss mit 110 mm IP67 Steck-
LED Luminaire with polyurethane en-
verbinder an beiden Enden.
capsulation in AL profile and 110 mm
VarioLED™ HYDRA HD15 IP67 Up to 2 m length, water & UV resistant Notes:
IP67 plug in connectors on both ends.

LED Luminaire with polyurethane en-


capsulation
Wasser-inund
AL profile and 110 Linearleuchte
UV-geschützte mm 1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
Längen Dimensions & available length IP67 plug in connectors on
im Aluminiumprofil both
in bis zuends.
2 m Länge im
Polyurethanverguss mit 110 mm IP672. Linear
Steck- LED strip to be mounted on
a suitable profile to provide sufficient
18
4,5

Tc-Punkt: Gesamte Profilrückseite verbinder an beiden Enden. heat dissipation per manufacturer’s
Tc-point:
Luminaire classification according Entire
to CIE: 100 Al-profile rear side
Due to missing symmetry properties, no UGR table recommendations.
15,5

17,5

CIE flux code: 46 78 96 100 115 Up to 2 m length, water & UV resistant


can be displayed for this luminaire.
3. Continuous profiles to be supplied
Abmessungen & Längen Dimensions & available length LED Luminaire with polyurethane en- with all necessary accessories including
17,5

A mm varies
19
capsulation in AL profile and 110 mmmounting profiles, brackets and end
18 caps.
4,5

IP67 plug in Tc-Punkt:


connectors on bothProfilrückseite
Gesamte ends.
4. Lengths required to be confirmed by
18
4,5

Tc-point: Entire Al-profile


siterear side
measurement prior to ordering and
15,5

17,5

coordinated with Architect Engineer.


Tc
5. When required, profile sections to be
15,5

17,5

A mm cut to match required radius.


Abmessungen &19Längen Dimensions & available length
+ 6. Mock-ups required to confirm design
intent.
18 –
4,5

19 Tc-Punkt: Gesamte Profilrückseite


18 Amax = 31 x 62,5 + 19 = 1.956,5
4,5

Amin = 1 x 62,5 + 19 = 81,5; Übersicht VarioContour IP67 ab Seite 474. Tc-point: Entire Al-profile rear side
15,5

17,5

Overview VarioContour IP67 from page 474.


Tc
15,5

Order Code: VarioLED HYDRA HD15 Wxxx/A IP67


17,5

A mm
19

+
ische Betriebsdaten Electrical & optical data
19 The drawings on this page are
indicative. Refer to the architectural –
Profile sections cut to match radius drawings for correct setting out,
Page 1
lumen/meter Farbtemperatur Es gelten die selben Daten wie für VarioLED™ Flex HYDRA HD15 mit Tc mounting
A = N x 62,5 + 19; N = 1 … 31; A = 1 x 62,5 + 19 = 81,5; A = 31 x 62,5 + 19 = 1.956,5
min max Übersicht VarioContour IP67 ab Seite
details474.
and final dimensions.
(lm/m) Color Temperature (K) folgenden Ausnahmen: 30% Lichtverlust und Farbverschiebung im
Vergleich zum nicht vergossenen LED Strip. Overview VarioContour IP67 from page 474.
877 2.500
Nähere Erläuterung zu den technischen Daten des PU-Schutzes Type: +
1.201 3.300
Bestellnummer
1.282
Order Code: VarioLED HYDRA HD15 Wxxx/A IP67
4.000
im LED Linear™ Systemkatalog, Seite 584.

Same data as for VarioLED™ Flex HYDRA HD15 apply, except: 30%
1.350 4.600 light loss and color shift compared to non encapsulatedÜbersicht
A = N x 62,5 + 19; N = 1 … 31; Amin = 1 x 62,5 + 19 = 81,5; Amax = 31 x 62,5 + 19 = 1.956,5 LED strip. VarioContour IP67 ab Seite 474. XL2e
1.382 6.300
Elektrische & Optische Betriebsdaten Electrical & optical data
1.451 10.000
More details regarding the PU-protection in the LED Linear™
catalogue, page 584.
systemVarioContour IP67 from page 474.
Overview Sheet 1/3

VarioLED Bestellnummer
Contract: Midfield Terminal Order–Code:
Building
lumen/meter VarioLED
GeneralFarbtemperatur
Bulletin No. 145: Volume 3 of 4 (Rev 07)
Contractor, HYDRA HD15
AUH.06.10.0401 Es geltenWxxx/A IP67wie für VarioLED™
die selben Daten Page
Flex185 of 231
HYDRA HD15 mit
January 31, 2015
HYDRA HD15 IP67 (lm/m) Bitte sprechen
ColorSieTemperature (K)
uns an für kundenspezifische folgenden Ausnahmen: 30% Lichtverlust und Farbverschiebung im
Anpassungen,
wie z. B. Kabellängen und Stecker. Vergleich zum nicht vergossenen LED Strip.
W824 877 2.500
Elektrische & OptischePlease
Betriebsdaten Electrical
ask for custom specific adaptions &length
like cable optical
Nähere and plugs.data
Erläuterung zu den technischen Daten des PU-Schutzes
Abu Dhabi Airports Company PJSC Specification, Section 265120

XL2e

XD1d XD1d XD1d


XD1d

XL2e
XL2e

adjustable LED
downlight

XD1d XD1d

XL2e

XL2e

adjustable LED
downlight

XL2e XD1d XL2e

solid to
XD1b
eliminate
shadows ARUP LIGHTING
MARK_UPS
Detail 3 Rev1
Detail plans and section of Lighting Lozenge from MTC-A-93-TB-L_-_-_-__-00-530

XL2e XD1d XL2e

solid to The drawings on this page are


eliminate indicative. Refer to the architectural
shadows drawings for correct setting out,
mounting details and final dimensions.

Type:

XL2e
Sheet 2/3

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 186 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

XL2e
XL2e

XD1
XD1d XD1d XD1d

Detail 1

XL2e

XD1d XD1d

XL2e

adjustable LED
downlight

Detail 5
Detail plans of Lighting Lozenge from MTC-A-93-TB-L_-_-_-__-00-530

XD1b

ARUP LIGHTING
MARK_UPS
Rev1

XL2e XL2e

The drawings on this page are


solid to
eliminate indicative. Refer to the architectural
shadows drawings for correct setting
out, mounting details and final
dimensions.

Type:

XL2e
Sheet 3/3

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 187 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Continuous integrated linear profile

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 15W/m


Primary luminaire LED strip mounted on Power factor: > 0.9
construction material: extruded aluminium profile Rated luminous flux (lm): 1,265lm/m
Finish: N/A Luminaire efficacy: 84lm/W
Accessories: See Notes Beam / distribution: Symmetric, see LDC
Light source type: LED CRILED
/ Colour temperature:
Linear ™ – VarioLED™> 80 / 3,000K
Driver type: Project 1 Constant Voltage Colour Variation: 10.08.2014
≤ 3 SDCM LED Linear ™ – VarioL
Drive current or voltage: 24V Operator Luminaire Lifetime: ≥ 50,000 hours
Telephone
Dimming & type: DALI, remote Lifetime Basis: L70 / F10 @ Ta 600C
YDRA HD15 IP67
Fax
e-Mail

IP: IP67
VarioLED™ HYDRA HD15 IP67 Wasser- und UV-geschützte Linearleuchte
LED Linear GmbH / Luminaire Data Sheet

Luminaire
im Aluminiumprofil in bis zu 2 m Länge im Luminous distribution
emittance 1: curve (LDC) Location:
Polyurethanverguss mit 110 mm IP67 Steck-
See our luminaire catalog for an image of the Wasser- und UV-geschützte Linearleuchte
Car Park bridges
luminaire. verbinder an beiden Enden.
im Aluminiumprofil in bis zu 2 m Länge Processor
im
LED Linear ™ – Vario
Arrival exterior lighting tray
Up to 2 m length, water & UV resistant Polyurethanverguss mit 110 mm IP67 Steck-
LED Luminaire with polyurethane en-
verbinder an beiden Enden.
capsulation in AL profile and 110 mm
VarioLED™ HYDRA HD15 IP67 Up to 2 m length, water & UV resistant Notes:
IP67 plug in connectors on both ends.

LED Luminaire with polyurethane en-


capsulation
Wasser-inund
AL profile and 110 Linearleuchte
UV-geschützte mm 1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
Längen Dimensions & available length IP67 plug in connectors on
im Aluminiumprofil both
in bis zuends.
2 m Länge im
Polyurethanverguss mit 110 mm IP672. Linear
Steck- LED strip to be mounted on
a suitable profile to provide sufficient
18
4,5

Tc-Punkt: Gesamte Profilrückseite verbinder an beiden Enden. heat dissipation per manufacturer’s
Tc-point:
Luminaire classification according Entire
to CIE: 100 Al-profile rear side
Due to missing symmetry properties, no UGR table recommendations.
15,5

17,5

CIE flux code: 46 78 96 100 115 Up to 2 m length, water & UV resistant


can be displayed for this luminaire.
3. Continuous profiles to be supplied
Abmessungen & Längen Dimensions & available length LED Luminaire with polyurethane en- with all necessary accessories including
17,5

A mm varies
19
capsulation in AL profile and 110 mmmounting profiles, brackets and end
18 caps.
4,5

IP67 plug in Tc-Punkt:


connectors on bothProfilrückseite
Gesamte ends.
4. Lengths required to be confirmed by
18
4,5

Tc-point: Entire Al-profile


siterear side
measurement prior to ordering and
15,5

17,5

coordinated with Architect Engineer.


Tc
5. When required, profile sections to be
15,5

17,5

A mm cut to match required radius.


Abmessungen &19Längen Dimensions & available length
+ 6. Mock-ups required to confirm design
intent.
18 –
4,5

19 Tc-Punkt: Gesamte Profilrückseite


18 Amax = 31 x 62,5 + 19 = 1.956,5
4,5

Amin = 1 x 62,5 + 19 = 81,5; Übersicht VarioContour IP67 ab Seite 474. Tc-point: Entire Al-profile rear side
15,5

17,5

Overview VarioContour IP67 from page 474.


Tc
15,5

Order Code: VarioLED HYDRA HD15 Wxxx/A IP67


17,5

A mm
19

+
ische Betriebsdaten Electrical & optical data
19 The drawings on this page are
indicative. Refer to the architectural –
Page 1 drawings for correct setting out,
lumen/meter Farbtemperatur Es gelten die selben Daten wie für VarioLED™ Flex HYDRA HD15 mit Tc mounting
A = N x 62,5 + 19; N = 1 … 31; A = 1 x 62,5 + 19 = 81,5; A = 31 x 62,5 + 19 = 1.956,5
min max Übersicht VarioContour IP67 ab Seite
details474.
and final dimensions.
(lm/m) Color Temperature (K) folgenden Ausnahmen: 30% Lichtverlust und Farbverschiebung im
Vergleich zum nicht vergossenen LED Strip. Overview VarioContour IP67 from page 474.
877 2.500
Nähere Erläuterung zu den technischen Daten des PU-Schutzes Type: +
1.201 3.300
Bestellnummer
1.282
Order Code: VarioLED HYDRA HD15 Wxxx/A IP67
4.000
im LED Linear™ Systemkatalog, Seite 584.

Same data as for VarioLED™ Flex HYDRA HD15 apply, except: 30%
1.350 4.600 light loss and color shift compared to non encapsulatedÜbersicht
A = N x 62,5 + 19; N = 1 … 31; Amin = 1 x 62,5 + 19 = 81,5; Amax = 31 x 62,5 + 19 = 1.956,5 LED strip. VarioContour IP67 ab Seite 474. XL3
1.382 6.300
Elektrische & Optische Betriebsdaten Electrical & optical data
1.451 10.000
More details regarding the PU-protection in the LED Linear™
catalogue, page 584.
systemVarioContour IP67 from page 474.
Overview Sheet 1/2

VarioLED Bestellnummer
Contract: Midfield Terminal Order–Code:
Building
lumen/meter VarioLED
GeneralFarbtemperatur
Bulletin No. 145: Volume 3 of 4 (Rev 07)
Contractor, HYDRA HD15
AUH.06.10.0401 Es geltenWxxx/A IP67wie für VarioLED™
die selben Daten Page
Flex188 of 231
HYDRA HD15 mit
January 31, 2015
HYDRA HD15 IP67 (lm/m) Bitte sprechen
ColorSieTemperature (K)
uns an für kundenspezifische folgenden Ausnahmen: 30% Lichtverlust und Farbverschiebung im
Anpassungen,
wie z. B. Kabellängen und Stecker. Vergleich zum nicht vergossenen LED Strip.
W824 877 2.500
Elektrische & OptischePlease
Betriebsdaten Electrical
ask for custom specific adaptions &length
like cable optical
Nähere and plugs.data
Erläuterung zu den technischen Daten des PU-Schutzes
Abu Dhabi Airports Company PJSC Specification, Section 265120

XL1 XL1

XL3 XL3

L2j

Detail 1 ARUP LIGHTING


MARK_UPS
Section of Processor Arrival exterior lighting tray from MTC-A-41-TB-L0-1-5-00-00-874

L5

L18
L4d

XL3
XL3

recommend to make
this narrower to
improve fixture
efficiency

Section of Car Park bridge from MTC-A-94-TB-L_-_-0-00-09-020


L5

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.

L5c L5c

Type:
L18

L4d

XL3
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 189 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Flexible modular LED system

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 50W/m


Primary luminaire Aluminium Power factor: > 0.9
construction material: 4 x 2.4 Watt LEDs no lenses
Rated luminous flux (lm): 3,200lm/m Adjustable mounting bracket
Finish: Stainless steel Luminaire efficacy: 64lm/W
3D LED FLEX 100 . IP 20 . 4 . (length Direct screw fixing into the mounting
Accessories: Mounting . (colour temp. variable)Beam
brackets
variable) . CRI 80 / distribution: Symmetric, see surface
LDC with heat sinks rotated.
Light source type: LED CRI / Colour temperature: > 80 / 3,000K
Supplied in 1.0 mtr lengths as standard Allows heat sink module to rotate for
Driver type: Constant multiple of 100 mm modulesColour
Any Current can be Variation: ≤ 3 SDCM precise aiming angle
Drive current or voltage: 350mAsupplied to order Luminaire Lifetime: 50,000 hours Finish to match heat sink
Dimming & type: DALI, remote Lifetime Basis: L70 / F10 @ Ta 250C
Project 1
Integral LV constant current drivers 22.08.2014

30 V DC Supply Operator

IP: IP20 Black Finish standard


Telephone
Fax
e-Mail

Other RAL colours to order


Radiant Architectural Lighting CXPE40TM35010M 3D LED Flex 25 40 x 1.085 Watt LEDs
per mtr Tina M lenses 1000 mm module / LDC (Polar)

Luminaire distribution curve (LDC) Location:


Luminaire: Radiant Architectural Lighting CXPE40TM35010M 3D LED Flex 25 40 x 1.085 Watt LEDs per mtr
Tina M lenses 1000 mm module
Lamps: 40 x Cree XPE

2 x 4.7 Watt LED arrays with reflectors Fixed mounting


Integrated into architectural bracket
detail at
RAD 3D LED Flex 100 CZ 5 - 2
base of columns
Where overal height is an issue.
Supplied in 1.0 mtr lengths as standard Space for connectors under mounting
bracket.
Integral LV constant current drivers
30 V DC Supply Heat sink modules remaing parallel to
Black Finish standard mounting surface but the system can st
Other RAL colours to order angle to follow complex curves.
Notes:
Finish to match heat sink
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
100

2. Luminaire to be passively cooled.

350 Rad 1 x 8 watt RGBW LED array with colour 3. Continuous profiles to be mounting
Adjustable suppliedbracket with spring
mixing lens with all necessary accessories
clip fixing including
mounting profiles, covers, brackets and
Supplied in 1.0 mtr lengths as standard end caps. Mounting bracket
Where easy height to be
instalation and removal in
100

RAD 3D LED Flex 100 MCE RGBS confirmed followingakward


mock-up.spaces is required.
100
100

Integral DMX driver controller or 350 Rad Page 1


50

can be supplied with remote DMX


4. OT DIM AdaptorAllows
to be heat
provided on to rotate for
sink module
84 25

each circuit to ensure all aiming


precise modules are
angle
110

driver version
illuminated when dimmed to end of
Various beam angles and lens types dimming range. Finish to match heat sink
670 Rad
24 Volt DC Supply 5. Lengths required to be confirmed by
Adjustable mounting Black Finish standard
bracket 1 RGBW LED site measurement prior to ordering and
Other RAL colours to order
110
100
TBC

module with lens.


100 85.60

coordinated with Architect.


84
95

84

Superseded

350 Rad
6. Final selection of optical lens/cover to
50

670 Rad
Power feed be confirmed during
ARUP LIGHTING site mock-up.
Connector
ed mounting bracket Adjustable mounting Adjustable mounting Adjustable mounting
dule without optics bracket. Spring clip fixing bracket 2 LED module bracket 1 RGBW LED MARK_UPS 7. Finishing diffuser/glass in architectural
Module without optics Input
module withto white
light 1 mtr strips via 3 pole
lens. 16 Amp 3 pole Weiland connectors are
with optics detail to be supplied by others.
450 Rad Weiland connector. used to join white light strips
8. Detail to be coordinated with Architect.
16 Amp capacity for power and pwm These can fit under the heat sink module
dimming line 9. Mock-up required to when
even confirm
non design
adjustable mounting
110
85.60

84
95

84

intent. brackets are used.


XL4
DMX connectors are fitted to RGBW
450 Rad
systems 670 Rad DMX connectors are fitted to RGBW
ustable mounting Adjustable mounting Adjustable mounting systems
The drawings on this to join
page are the strips together.
cket. Spring clip fixing bracket 2 LED module bracket 1 RGBW LED
dule without optics with optics module with lens. indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.
1190
1 x 10 Watt Citizen or Sharp LED array Linear module with five 2 x 4.5 Watt
with reflectors Citizen or Sharp LED arrays with reflecto
Elliptical X Elliptical Y Wide Medium Narrow
450 Rad
Type:
RAD 3D LED Flex 100 CZ 10 - 1 RAD 3D LED Flex 100 CZ 5 2 - Linear 5

Supplied in 1.0 mtr lengths as standard Wide, medium and narrow reflectors

Optics Detail
Bracket Type6 Cover Feed Finish
Wide, medium and narrow reflectors plus
diffusing covers
Ellipticaland anti glare
X Elliptical Y snoot Medium Narrow
Wide
XL4
Integral 30 V DC constant current driver
available.
120˚ Direct fixing end
Plan of seating pillar Clear End Black
from MTC-Q-04-TB-L_-_-_-__-00-571
E Adjustable Filter 1190 Back White Integral LV constant current drivers Black Finish standard
te
Wan order-code by selecting
Spring Clip one option from each column in the table below.
3DM LED FLEX 100 . IP20 . 4 . 200mm . 40K . CRI 80 . E . Adjustable
Any
. Clear.
RAL-
End . Black . 30 V DC Supply Other RAL colours to order
colour
N
Contract: Midfield Terminal Building – General Black FinishContractor,
standard AUH.06.10.0401 Page 190 of 231
duct No. of LEDs Length Colour Other RAL colours to order
e Bulletin
IP No. 145:
per module (mm) Volume 3 of 4CRI(RevOptics
Temp. (K) 07) Bracket Type Cover Feed Finish January 31, 2015
ED FLEX 100 20 4=25mm 200mm
27=2,700k 80 120˚ Direct fixing end Clear End Black
30=3,000k 90 E Adjustable Filter Back White
2=50mm -increments
35=3,500k W Spring Clip Any RAL-
of 100mm
40=4,000k M 1 x 10 Watt Citizen or Sharp LED array colour 2 x 4.5 Watt Citizen or Sharp LED array
+ 44 ( 0 ) 20 8348 9003
1=100mm up to-
45=4,500k Elliptical XN Elliptical
with Yreflectors
Wide single
Mediumspotlight
Narrow with reflectors single spotlight
+ 44 ( 0 ) 20 8348 6478
New product 50=5,000k
Products and literature designed by
New product
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: LED floodlight

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 54W


Primary luminaire Aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 4,140lm
Finish: Stainless steel Luminaire efficacy: 77lm/W
Accessories: - Beam / distribution: Symmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 4,000K
Terminal Building_sector 5.19
Driver type: Constant Current Colour Variation: 19.11.2014
≤ 3 SDCM
Drive current or voltage: 900mA Operator Luminaire Lifetime: 50,000 hours
Telephone
Dimming & type: DALI, remote Fax
e-Mail
Lifetime Basis: L70 / F10 @ Ta 600C
IP: IP65
BEGA 7659 / Luminaire Data Sheet

Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
See our luminaire catalog for an image of the Car Park bridges
luminaire.

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Luminaire to be passively cooled.
3. Detail to be coordinated with
architectural details.
Luminaire classification according to CIE: 100 Luminous emittance 1:
CIE flux code: 98 100 100 100 100

The drawings on this page are


indicative. Refer to the architectural
Page 1
drawings for correct setting out,
mounting details and final dimensions.

Type:

XS1
Sheet 1/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 191 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC
1. FOR LIGHT FITTING INTEGRATION AND FIXING DETAILS
REFER TO A-94 & A-93 ARCHITECTURAL DRAWINGS AND
LIGHTING SPECIFICATIONS 265120

2. ARCHITECTURAL BACKGROUNDS ADDED FOR CLARITY


Specification, Section 265120

L2b

02 31.01.15 BULLETIN 145


01 31.10.14 BULLETIN 120
00 15.07.12 ISSUED FOR CONSTRUCTION

ISSUED FOR CONSTRUCTION

XS1 ABU DHABI


AIRPORTS COMPANY
ABU DHABI AIRPORTS COMPANY

Kohn Pedersen Fox Associates


(International) PA
Architects and Planning Consultants
7a Langley Street
London WC2H 9JA
England
T: +44 (0)207 319 5300
F: +44 (0)207 497 1175
www.kpf.com

Detail 1
ABU DHABI INTERNATIONAL AIRPORT
Detail of concrete facade interface of Processor Arrival Car Park Link
MIDFIELD bridge
TERMINAL from MTC-A-94-TB-L_-_-0-00-09-020
COMPLEX

PROCESSOR ARRIVAL
CARPARK LINK BRIDGE
SECTIONS AND DETAILS
3 CONCRETE-FACADE INTERFACE- LIGHTING DETAIL
SCALE 1:5 MTC A 94 TB __ L_._ 0.00 09.020 02

KPF MC KF JH 25.09.2009

WBS AUH.06.10.0401

2014 KOHN PEDERSEN FOX ASSOCIATES (INTERNATIONAL) PA. All rights reserved. Do not scale.

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting
out, mounting details and final
dimensions.

Type:

XS1
Sheet 2/2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 192 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: 10m column with four (4) adjustable spotlights

Manufacturer: standard:
Manufacturing EN 60 598 Total luminaire wattage (max): 4 x 53W
Primary luminaire Die-cast aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 4 x 4,250lm
Finish: Stainless steel
Olivio Luminaire
Universal efficacy:
Grande 80lm/W
Accessories: Mounting brackets Beam / distribution: Symmetric, see LDC
Light source type: LED
SX 963CRI 12-9
/ Colour temperature: > 80 / 3,000K
Driver type: Project 1 Constant current Colour Variation: 03.04.2014
≤ 3 SDCM
Projector
Drive current or voltage: 1,000mA Operator Luminaire Lifetime: ≥ 50,000 hours rotationally symmetric, wide
Telephone
Dimming & type: DALI, integral Olivio Universal
Fax Lifetime
e-Mail
Basis:Grande L70 / F10 @ Ta LED 600C4250 lm, 3000K, CRI > 80
load: 53 W
IP: IP68 SX 963 12-9
selux Copyright SXKat V SX 960 12-9 Olivio Grande / Luminaire Data Sheet surface mounted luminaire, h
Luminaire distribution curve (LDC) Location: aluminium,
Projector aluminium, stain
Luminous emittance 1:
stainless steel,
rotationally easy maintena
symmetric, wide be
See our luminaire catalog for an image of the mechanism,
LED 4250 lm, the power
3000K, CRI cord
> 80,ise
luminaire. Arrival and departure forecourts
2-way
load: 53adjustable
W head joint, l
adjusted by the 2-way adjusta
from 20°
surface to 195°luminaire,
mounted and rotatedhou
9.2m aluminium,
toughened aluminium,
glass stainle
stainless steel,reflector
Optic: flood easy maintenan
mechanism, the power cord is i
8.6m
2-way adjustable
CE, IP67, headclass
Protection joint,
I lig
Notes: adjusted by the 2-way adjustab
8.0m 1. Refer to Sectionfrom
‘2.0 20° to 195°
Products’
Manufacturer: and
this rotated
ofSelux, Type: SX+/
toughened
specification for additional
or choice glass
requirements.
of colours]
Optic: flood reflector
7.4m 2. Luminaire to be passively cooled.
3. Mounting brackets
CE, for column
IP67,
Outreach: fixing
mmtoclass I
Protection
503
be provided. Diameter Ø: 275 mm
Luminaire classification according to CIE: 100 Due to missing symmetry properties, no UGR table
CIE flux code: 84 96 100 100 102 can be displayed for this luminaire.
Manufacturer:
Height H: 320Selux,
mm Type: SX 9
or choice of colours]
Weight: 10.00 kg
Windage area: 0.08 m²

Ø 275 Outreach: 503 mm


Colours
Diameter Ø: 275 mm
10m column

Selux graphite
Height H: 320 mmor choice of co
Weight: 10.00 kg
Windage area: 0.08 m²

Colours
Ø 320 Selux graphite or choice of colo

The drawings on this page are


indicative. Refer to the architectural
Page 1 drawings for correct setting out,
mounting details and final dimensions.

Type:

XT1
Modifications are possible due to the constant development and improvement of LED technology.
© Selux AG, Subject to technical modification 02.2014
Selux AG, Motzener Straße 34, D-12277 Berlin, T +49 30 72001-0, F -100, info@selux.com, www.selux.co

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 193 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January
Modifications are possible due to the constant development and improvement of LED31, 2015
technology.
© Selux AG, Subject to technical modification 02.2014
Selux AG, Motzener Straße 34, D-12277 Berlin, T +49 30 72001-0, F -100, info@selux.com, www.selux.com
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Exterior pole top luminaire with secondary reflector including pole

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 70W


Primary luminaire Extruded aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 3,100lm
Finish: Stainless steel Luminaire efficacy: 44lm/W
e 330-E/1x70HIT
Accessories: L G3 N/A Beam / distribution: Asymmetric, see LDC
Light source type: LED CRI / Colour temperature: > 80 / 3,000K
Project 1
Driver type: Constant current Colour Variation: 21.03.2014
≤ 3 SDCM
Drive current or voltage: 1,000mA Operator Luminaire Lifetime: file ≥
TX030328
50,000 hours
Telephone
. Dimming & type: DALI, integral Fax
e-Mail
Lifetime Basis: L70 / F10 @ Ta 600C
IP:
330-E/1x70HIT L G3 IP65
TRILUX Palme 330-E/1x70HIT G3 IND / Luminaire Data Sheet

Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
with file TX030328

support.
135° 150° 165° 180° 165° 150° 135°
240 Arrival forecourts
c0-c180
200
c90-c270

weather
120° 160 120°

120

DB
port.703 / 105° c0-c180
c90-c270
80 105°

ather 90°
Colour 90° ···G3
03 / Weight 26.7 kg
lector, Colour
Notes:
Degree of protection
···G3 IP 65
75° 75°

Weight 26.7 kg
gor,with Degree of protection 60° IP 65Safety class 60°
1. Refer to ISection ‘2.0 Products’ of this
th specification for additional requirements.
Safety class Socket
I G12
Socket G12 2. Luminaire to be passively cooled.
45° 30° 15° 0° 15° 30° 45°

of cd/klm
C0 - C180 C90 - C270
 47%
3. Mounting detail to Architect’s
specification.
n 410 422
Luminaire classification according to CIE: 83 Due to missing symmetry properties, no UGR table
CIE flux code: 34 66 88 83 47 can be displayed for this luminaire.
ction 410 422

as
Luminaire head of cast aluminium.
864

Post of extruded aluminium profile, with continuously bitumised underground


support.
864

Colour ···G3 with metal effect, highly weather resistant, powder-coated,


similar to DB 703 / 534.
tion 108 Lamp compartment with primary reflector, closed with cast aluminium cover
ring with sealed non-laminated safety glass.
3300

Optical system of primary reflector of anodised aluminium in closed lamp


compartment and white-coated reflection surface of luminaire head

nection
2436

functioning as secondary reflector.

108 Relamping via release of cover ring.


or 85 x 400
Electrical connection to 3-pole connection terminal near post door. With C-
rail for mounting of a junction box to be ordered separately.
ered
3300

Electrical version
600

With low-loss inductive ballast.


2436

Windage area FW = 0.50 m².


500
800

50 x 150
85 x 400
600
500

The drawings on this page are


800

50 x 150
indicative. Refer to the architectural
DIALux 4.11 by DIAL GmbH Page 1 drawings for correct setting out,
mounting details and final dimensions.

Type:

XT2

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 194 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: Floor luminaire

Manufacturing standard: EN 60 598 Lamp Type: Compact Fluorescent, Long Life


Primary luminaire Aluminium Lamp Wattage: 24W (2G11)
construction material: Lamp Manufacturer: -
Finish: Stainless steel Beam / distribution: -
Accessories: N/A CRI / Colour temperature: > 80 / 3,000K
IP: IP65 Ballast/Transformer: DALI, integral
Lamp life: ≥ 48,000 hours (See Notes)
FLORA
Future Systems, 2008
Luminaire distribution curve (LDC) Location:
Centre space seating
A B

Notes:
FLORA
1. Refer to Section ‘2.0 Products’ of this
Future Systems, 2008 specification for additional requirements.
2. Mounting detail to Architect’s
specification.
CODICE TENSIONE LAMPADINA CARATTERISTICHE DIMENSIONI in cm
Code/Code
Kode/Código 150mm
A Voltage/Tension
Spannung/Tensión 1720mm
Bulb/Ampoule
B
Glühbirne/Bombilla
Features/Caractéristiques
Merkmale/Características3. Lamp
Dimensions in cm/Dimensions en cm
life
Abmessungen of 48,000hours
in cm/Dimensiones en cm based on an
4008 230V IP54
1x24W max 2G11 (FL) A: 15 - B: 172 - C: 208
electronic ballast and a switching cycle
12 hours with 10% lamp failure rate.
Conforme alle norme di riferimento EN60598-1 e EN60598-2-4 e alle Direttive vigenti Bassa Tensione 2006/95.
In compliance with EN60598-1and EN60598-2-4 and with current Low Voltage Directives 2006/95.

4. 1,250lm rated luminaire luminous flux.


Conforme à la norme de référence EN60598-1 et EN60598-2-4 et aux Directives Basse Tension 2006/95 en vigueur.
Der Norm EN60598-1 und EN60598-2-4 und den geltenden Niederspannungsrichtlinien 2006/95 entsprechend.
Conforme a la norma EN60598-1 y EN60598-2-4 y a las directivas de Baja Tensión 2006/95 vigentes.

5. LED alternatives will be acceptable if


2080mm

Applicabile su superfici normalmente infiammabili.


Can be applied to normally inflammable surfaces. they meet the performance specification
Installable sur des surfaces normalement inflammables.
Auf normalerweise entzündbaren Öberflächen montierbar.
C and the following criteria:
Aplicable sobre superficies normalmente inflamables.

• CRI: >80
Prima di ogni operazione sull’apparecchio, disinserire la tensione di rete.
Before any operation on the fixture, please disconnect the power supply.
Avant toute opération sur l’appareil déconnecter la tension de réseau.
• Colour Temperature: 3,000K
Vor jeder Montage oder Instandsetzung des Geräts den Strom ausschalten.
Antes de efectuar cualquier operación sobre el aparato, desconectar la tensión de red.
• Colour Variation: ≤ 3 SDCM
• Luminaire lifetime: ≥ 50,000 hours
In caso di danneggiamento del cavo di alimentazione, per la sostituzione contattare un rivenditore FontanaArte o personale qualificato.
In case of damage to the feeding cable, please contact a FontanaArte dealer or qualified personnel for replacement.
En cas d’endommagement du câble d’alimentation, pour le remplacement il faut contacter un revendeur FontanaArte ou un personnel compétent.
• Lifetime Basis: L70 / F10 @ Ta 600C
Im Fall von Beschädigung des elektrischen Kabels, bitte Kontakt mit einem FontanaArte Händler oder mit einem qualifizierten Handwerker aufnehmen.
Si el cable de alimentación estuviera dañado, contactar a un vendedor de FontanaArte o a personal cualificado para sustituirlo.

FontanaArte si riserva di apportare tutte le modifiche necessarie al miglioramento del presente prodotto in qualsiasi momento e senza preavviso.
FontanaArte reserves the right to introduce all changes required for the improvement of the present product at any time and without prior notice.
FontanaArte se réserve d’apporter à n’importe quel moment et sans préavis toute modification nécessaire pour l’amélioration du produit.
FontanaArte kann jederzeit und ohne Vorankündikung die technischen und die strukturellen Merkmale verändern, um ihre Produkte zu verbessern.
FontanaArte se reserva el derecho de efectuar las modificaciones que considera puedan mejorar este producto en cualquier momento y sin aviso previo.

009400801

CODICE TENSIONE LAMPADINA CARATTERISTICHE DIMENSIONI in cm


Code/Code Voltage/Tension Bulb/Ampoule Features/Caractéristiques Dimensions in cm/Dimensions en cm
Kode/Código Spannung/Tensión Glühbirne/Bombilla Merkmale/Características Abmessungen in cm/Dimensiones en cm
4008 230V 1x24W max 2G11 (FL) IP54 A: 15 - B: 172 - C: 208
The drawings on this page are
Conforme alle norme di riferimento EN60598-1 e EN60598-2-4 e alle Direttive vigenti Bassa Tensione 2006/95.
indicative. Refer to the architectural
In compliance with EN60598-1and EN60598-2-4 and with current Low Voltage Directives 2006/95. drawings for correct setting out,
Conforme à la norme de référence EN60598-1 et EN60598-2-4 et aux Directives Basse Tension 2006/95 en vigueur.
Der Norm EN60598-1 und EN60598-2-4 und den geltenden Niederspannungsrichtlinien 2006/95 entsprechend. mounting details and final dimensions.
Conforme a la norma EN60598-1 y EN60598-2-4 y a las directivas de Baja Tensión 2006/95 vigentes.

Applicabile su superfici normalmente infiammabili.


Can be applied to normally inflammable surfaces.
Installable sur des surfaces normalement inflammables. Type:
Auf normalerweise entzündbaren Öberflächen montierbar.
Aplicable sobre superficies normalmente inflamables.

Detail 2
Prima di ogni operazione sull’apparecchio, disinserire la tensione di rete.
Before any operation on the fixture, please disconnect the power supply.
Avant toute opération sur l’appareil déconnecter la tension de réseau.
XT3
Vor jeder Montage oder Instandsetzung des Geräts den Strom ausschalten.
Antes de efectuar cualquier operación sobre el aparato, desconectar la tensión de red.
Section of interior planters from of seating pillar from MTC-A-96-TB-L_-_-_-__-00-600
In caso di danneggiamento del cavo di alimentazione, per la sostituzione contattare un rivenditore FontanaArte o personale qualificato.
Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401
In case of damage to the feeding cable, please contact a FontanaArte dealer or qualified personnel for replacement.
En cas d’endommagement du câble d’alimentation, pour le remplacement il faut contacter un revendeur FontanaArte ou un personnel compétent.
Page 195 of 231
Bulletin No.Im145: Volume 3 of 4 (Rev 07)
Fall von Beschädigung des elektrischen Kabels, bitte Kontakt mit einem FontanaArte Händler oder mit einem qualifizierten Handwerker aufnehmen.
Si el cable de alimentación estuviera dañado, contactar a un vendedor de FontanaArte o a personal cualificado para sustituirlo.
January 31, 2015

FontanaArte si riserva di apportare tutte le modifiche necessarie al miglioramento del presente prodotto in qualsiasi momento e senza preavviso.
FontanaArte reserves the right to introduce all changes required for the improvement of the present product at any time and without prior notice.
FontanaArte se réserve d’apporter à n’importe quel moment et sans préavis toute modification nécessaire pour l’amélioration du produit.
FontanaArte kann jederzeit und ohne Vorankündikung die technischen und die strukturellen Merkmale verändern, um ihre Produkte zu verbessern.
Pole
Pole mounted
mounted
Abu Dhabi Airports Company PJSC Specification, Section 265120

To
To be
beLuminaire
supplied
supplied with
withCluster
Description: custom
custom height
height
of 3 pendants pole
mountedpole
at 2.5mto
to deliver
deliver
above the
the
finish floor level on lantern
alantern
custom pole.height
height of of
2500mm
2500mm above
above
Manufacturing finished
finished
standard: floor
EN 60 598 floor level
levelLampto
toType:
base
base of of pendant.
pendant. All
All column
Compact Fluorescent, column
Long Life fini
fini
and
nd base
base mounting
mounting
Primary luminaire
construction material:
to
to
TBC
architect’s
architect’s co-ordinated
co-ordinated
Lamp Wattage:
Lamp Manufacturer:
specification.
specification.
3 x (4 x 18W)
-
Finish: Anodised aluminium silver Beam / distribution: -
Accessories: N/A CRI / Colour temperature: > 80 / 3,000K
IP: IP20 / IK07 Ballast/Transformer: DALI, integral
Lamp life: ≥ 30,000 hours (See Notes)

Luminaire distribution curve (LDC) Location:


Food court

Notes:
1. Refer to Section ‘2.0 Products’ of this
specification for additional requirements.
2. Mounting detail to Architect’s
specification.
3. Lamp life of 30,000hours based on
an electronic ballast (warmstart) and a
switching cycle of 12 hours with 10%
lamp failure rate.

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.

Type:

XT4

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 196 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: 3.8m column with two (2) elements of two (2) LED adjustable lighting modules

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 2 modules of 2 x 23W (92W)
Primary luminaire Aluminium and cast Power factor: > 0.9
construction material: aluminium Rated luminous flux (lm): 2 modules of 2 x 1,270lm
Finish: Stainless steel Luminaire efficacy: 55lm/W
Accessories: N/A Beam / distribution: Symmetric, see LDC, see LDC
Light sourceProject
type: 1 LED CRI / Colour temperature: > 80 / 3,000K
Driver type: Constant current Colour Variation: 14.08.2014
≤ 3 SDCM
Speclight Associates JLT Operator Steve Roiser
Drive current or voltage: 500mA Luminaire
Telephone +44
Fax
(0)7788 299441 Lifetime: ≥ 50,000 hours
Dimming & 1type: DALI, integral Lifetime Basis: L70 / F10 @ Ta 250C6
e-Mail steve.rosier@googlemail.com
2 3 4 5 7

IP: HESS Licht & FormIP65


A
Type 1
City Elements 230 BS 300_L3.3_1x Xicato XSM 8027 3000 C 500mA
25° (XSA 41] / Luminaire Data Sheet
Type 2
Luminaire
Luminous distribution
emittance 1: curve (LDC) Location:
See our luminaire catalog for an image of the Landscaping
luminaire.
one module
800

800
B

Notes:
180
one module
800

1. Refer to Section ‘2.0 Products’ of this


specification for additional requirements.
2. Luminaire to be passively cooled.
2200

C 180
3 4 5 6 7 8

Luminaire classification according to CIE: 100 Luminous emittance 1:


Type 2
CIE flux code: 97 98 99 100 100
A
400
2200

600
800

D
°
30

B
400

180
one module
600

tolerance / Toleranz
2200

0 C These documents a
form and positions company and shall
E general tolerance / a third party is o
workpiece edge / tolerance / surface /
Allgmeintoleranz accordance wit
Werkstückkanten Form- und Lage- Oberflächen
DIN ISO Competition (UWG
DIN ISO 13715 toleranz ISO 1302
2768 - mK any other protect
DIN ISO 1101
any transla
400

300 specific tolerance / spezielle Toleranz:


scale/ Maßst
200
model / Modell:
material / We
1 0° project / Kommission:
shape / Halb
600

date / name / titel / Beschreibung:


Datum Name
arranged/
D

The drawings on this page are


Bearbeitet
200
300

autited/
Geprüft

indicative. Refer to the architectural


approved/
Freigabe
Page 1
F 22 drawings for correct setting out, document# / Dokum

mounting details and final dimensions.


drawingtyp / Zeichnu
1 2 3 4 rev. / modification # / date/ name /
part # / Materialnumm
Vers. Änderungnummer Datum Name

tolerance / Toleranz Notice of ownership


These documents and the objects depicted in them are the intellectual property of the Hess

Type:
form and positions company and shall only be used for the purpose that we have agreed to. Passing them on to
general tolerance / a third party is only allowed with our express permission. You are hereby entrusted in
workpiece edge / tolerance / surface /
Allgmeintoleranz accordance with the meaning of Section 17 of the GermanFederal Law Against Unfair
Werkstückkanten Form- und Lage- Oberflächen
DIN ISO Competition (UWG). We reserve the right of and the right to apply for patent, copyright or
DIN ISO 13715 toleranz ISO 1302
2768 - mK any other protection. The German text of this Notice of Ownership shall be solely binding;
DIN ISO 1101
any translation shall be deemed to have been made for convenience only.
specific tolerance / spezielle Toleranz:
scale/ Maßst. 1:20 weight / Gewicht: 39.27 KG

XT5
model / Modell:
material / Werkstoff:
project / Kommission:
shape / Halbzeug:
date / name / titel / Beschreibung:
Datum Name
arranged/
Bearbeitet
200
300

autited/
Geprüft
approved/
Freigabe

document# / Dokumentnummer: Urheber- rev. / Version


schutzvermerk
ISO 16016

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401


3 4 rev. / modification # /
Vers. Änderungnummer
date/
Datum
name /
Name
drawingtyp / Zeichnungsart:

part # / Materialnummer:
print date/Plotdatum: .

in exchange for / Ersatz für: Page 197 of 231


Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120

Luminaire Description: 3m column with one (1) elements of two (2) LED modules

Manufacturing standard: EN 60 598 Total luminaire wattage (max): 2 x 18W


Primary luminaire Aluminium Power factor: > 0.9
construction material: Rated luminous flux (lm): 2 x and
Product variants
Product and
variants
materials materials
1,695lm
Finish: Anodised aluminium silver – Base body
– Base
made
Luminaire efficacy: body
of aluminium,
made
94lm/W PMMA tube PMMA
of aluminium, (satiné)
tube (satiné)
– Flush service
– Flush door,
service withdoor,
junction
with box
junction box
Accessories: N/A Beam / distribution: Asymmetric, see LDC
– Surface:– polyester
Surface: polyester
powder coating,
powder anthracite
coating, anthracite
(DB 703), (DB
Light source type: LED CRI /other
Colour temperature:
colours
otheroncolours
> 80 / 3,000K
requeston request
Project 1
Driver type: Constant current Colour Variation: 22.08.2014
≤ 3 SDCM
Drive current or voltage: 500mA Operator Luminaire Lifetime:
LED technology≥ 50,000 hours
LED technology
Telephone
Dimming & type: DALI, integral Fax
e-Mail
Lifetime Basis:
– Symmetrical
– Symmetrical
beam LED module L70
beam/ F10
LED @ Ta 250C
module
IP: IP65 – Light colour:
– Lightcool
colour:
whitecool
(5,700
white
K) /(5,700
neutral
K) /
white
neutral
(4,000
white
K)
ewo led_LS34-3MC2_SRGB-W on request
RGB-W
/ Luminaire on request
Data Sheet
– Current –feed: Current
200 mA
feed:
– 500200
mA,mAdepending
– 500 mA, depending
on ambienton
temperatur
ambient t
Luminaire distribution curve (LDC)
Luminous emittance 1: Location:
– Electronic
– Electronic
operating operating
device with device
interface
with interface
DALI or 1 -DALI
10 V or
See our luminaire catalog for an image of the or standalone or standalone
programming programming
Quiet area seating
luminaire.

IP66 RoHS IP66 RoHS


one module

Notes:
3000

H1 LPH H1 LPH 1. Refer to Section ‘2.0 Products’ of this


specification for additional requirements.
190
D1 D1 2. Luminaire to be passively cooled.

H2 H2

Luminaire classification according to CIE: 100 Due to missing symmetry properties, no UGR table
CIE flux code: 44 81 99 100 68 can be displayed for this luminaire.

The drawings on this page are


indicative. Refer to the architectural
drawings for correct setting out,
mounting details and final dimensions.
Page 1

Type:

XT6

Contract: Midfield Terminal Building – General Contractor, AUH.06.10.0401 Page 198 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
Channel Fitting Ref Qty W Lamp Source Dim/Switch Total Lamp Load (W)

LB2 - Tunnel
Escalator Lobby
Floor Level
LB2-PE-F03 L2c (per m) 59 15 LED D 885
L2c (per m) 12 15 LED D 180
L2c (per m) 23 15 LED D 345
Total 1,410
Corridor
Floor Level
LB2-PE-F02 L3 (per m) 222 15 LED D 3,330
Total 3,330
Ceiling Level
LB2-PE-C01 D1 L18 (per m) 2 4 19 28 LED D 38 104
LB2-PE-C02 L18 (per m) 66 28 LED D 1,848
LB2-PE-C03 L4 (900mm) L4 (1200mm) 62 20 27 FL D 1,237 1,666
LB2-PE-C04 L20 (per m) 28 50 LED D 1,400
LB2-PE-C05 L18 (per m) 35 28 LED D 980
LB2-PE-C06 L4 (900mm) L4 (1200mm) 27 20 27 FL D 539 726
LB2-PE-C07 L18 (per m) 21 28 LED D 588
LB2-PE-C08 D12 2 11 LED D 22
LB2-PE-C09 L18 (per m) 2 28 LED D 59
LB2-PE-C10 D12 5 11 LED D 55
LB2-PE-C10b D12b 3 1 LED D 3
LB2-PE-C11 L18 (per m) 22 28 LED D 617
LB2-PE-C11b L4 (900mm) L4 (1200mm) 30 20 27 FL D 599 806
LB2-PE-C12 L18 (per m) 18 28 LED D 504
LB2-PE-C13 D12 5 11 LED D 55
LB2-PE-C14 L18 (per m) 310 28 LED D 8,680
LB2-PE-C15 D12 2 11 LED D 22
LB2-PE-C16 L18 (per m) 7 3 28 LED D 196 76
LB2-PE-C17 D12b 5 1 LED D 5
LB2-PE-C17b D1 1 19 LED D 19
LB2-PE-C18 L4 (900mm) L4 (1200mm) 308 20 27 FL D 6,145 8,278
LB2-PE-C19 D12b 8 1 LED D 8
LB2-PE-C20 L18 (per m) 5 28 LED D 140
LB2-PE-C21 D12 7 11 LED D 77
LB2-PE-C22 L18 (per m) 44 28 LED D 1,232
LB2-PE-C23 D1 6 19 LED D 114
LB2-PE-C24 D1 2 19 LED D 38
LB2-PE-C25 D12 2 11 LED D 22
LB2-PE-C25b D12 2 11 LED D 22
LB2-PE-C26 L18 (per m) 3 28 LED D 77
LB2-PE-C27 L18 (per m) 3 28 LED D 76
LB2-PE-C28 D12 12 11 LED D 132
LB2-PE-C29 L2b (per m) 20 25 LED D 511
LB2-PE-C30 L18 (per m) 49 28 LED D 1,372
LB2-PE-C31 D12b 6 1 LED D 6
LB2-PE-C32 D12 9 11 LED D 99
LB2-PE-C33 L18 (per m) 7 28 LED D 202
LB2-PE-C34 L18 (per m) 19 28 LED D 532
LB2-PE-C35 L4 (900mm) L4 (1200mm) 38 20 27 FL D 758 1,021
LB2-PE-C36 L18 (per m) 14 28 LED D 392
LB2-PE-C37 L4 (900mm) L4 (1200mm) 26 20 27 FL D 519 699
LB2-PE-C38 L18 (per m) 10 28 LED D 267
LB2-PE-C39 D1 48 19 LED D 912
LB2-PE-C40 D1d 16 47 LED D 744
LB2-PE-C41 D16 7 80 LED D 560

Total 32,421 35,766


LB2 Lit Walls
LB2-PE-LW01 L2b (per m) 489 25 LED D 12,225
LB2-PE-LW02 L2b (per m) 63 25 LED D 1,575

Total 13,800

L0.0-2 Arrivals Hall Level - Arrivals Entry/Forecourt


Area AF
Floor level
L0-2-AF-F01 B1 350 28 LED D 9,800
L0-2-AF-F02 U3 192 15 LED D 2,880
L0-PE-F02 L13c (per m) 48 15 LED D 720

Total 13,400
Area AE
Floor level
L0-2-AE-F01 U3 90 15 LED D 1,350
L0-2-AE-F03 U3b 32 15 LED D 480
L0-2-AE-F07 U3 42 28 15 LED D 630 420
L0-2-AE-F08 S4 20 25 LED D 500

Total 2,960 2,750


Ceiling level
L0-2-AE-C03 D12 84 11 LED D 924
L0-2-AE-C04 L17 (1500mm) 28 35 FL D 968

Total 1,892
L0.0-2 Arrivals Hall Level - Arrivals Central Area
Floor level
Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 199 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
L0-2-AC-F02 U3 41 15 LED D 615
L0-2-AC-F06 L8 (per m) 76 32 LED D 2,432
L0-2-AC-F08 U3 8 4 15 LED D 120 60
L0-2-AC-F13 S4 24 25 LED D 600

Total 3,767 3,707

Ceiling level
L0-2-AC-C20 D12 12 11 D 132
L0-2-AC-C21 L17 (1500mm) 4 35 FL D 138
L0-2-AC-C23 L7 (per m) 100 30 LED D 3,000
Total 3,270
Ceiling level
L00-6-AC-C01 L4 (1200mm) 365 27 FL D 9,809
L00-6-AC-C02 L5b (1200mm) 323 269 54 FL D 17,586 14,646
L00-6-AC-C03 L18b (per m) 328 28 LED D 9,184
L00-6-AC-C04 L14 (per m) 405 15 LED D 6,075
L00-6-AC-C05 L18b (per m) 530 28 LED D 14,840
L00-6-AC-C06 L18 (per m) 138 70 28 LED D 3,864 1,960
L00-6-AC-C06b L4 (1200mm) 40 27 FL D 1,075
L00-6-AC-C07 D1 9 19 LED D 171
D2 45 54 LED D 2,430
L00-6-AC-C08 D11 231 239 25 LED D 5,775 5,975
L00-6-AC-C09 L18 (per m) 141 28 LED D 3,948
L00-6-AC-C10 D1 27 19 LED D 513
D6 12 19 LED D 228
L00-6-AC-C11 L18 (per m) 69 28 LED D 1,940
L00-6-AC-C12 L4 (1200mm) 137 27 FL D 3,682
D1 19 19 LED D 361
L00-6-AC-C13 L18 (per m) 50 28 LED D 1,411
L4 (1200mm) 17 27 FL D 457
L00-6-AC-C14 L4 (1200mm) 172 27 FL D 4,623
D11b 20 39 LED D 780
D9b 4 80 LED D 320
D16 4 80 LED D 320
L00-6-AC-C15 L18 (per m) 75 28 LED D 2,100
L00-6-AC-C16 D12 20 11 LED D 220
D12b 12 1 LED D 12
L00-6-AC-C16b D1 3 19 LED D 57
L00-6-AC-C17 L18 (per m) 71 28 LED D 1,988
L00-6-AC-C18 D12 20 11 LED D 220
D12b 12 1 LED D 12
L00-6-AC-C18b D1 3 19 LED D 57
L00-6-AC-C19 L18 (per m) 100 28 LED D 2,800
L00-6-AC-C20 D12 15 11 LED D 165
D12b 8 1 LED D 8
L00-6-AC-C20b D1 1 19 LED D 19
L00-6-AC-C21 L18 (per m) 159 28 LED D 4,452
L00-6-AC-C22 D12 22 11 LED D 242
D12b 14 1 LED D 14
L00-6-AC-C22b D1 2 19 LED D 38
L00-6-AC-C23 L18 (per m) 99 28 LED D 2,772
L00-6-AC-C24 D12 13 11 LED D 143
D12b 6 1 LED D 6
D6 1 19 LED D 19
L00-6-AC-C24b D1 3 19 LED D 57
L00-6-AC-C25 L18 (per m) 97 28 LED D 2,722
L00-6-AC-C26 D12 13 11 LED D 143
D12b 6 1 LED D 6
D6 1 19 LED D 19
L00-6-AC-C26b D1 3 19 LED D 57
L00-6-AC-C27 L18 (per m) 85 28 LED D 2,380
L00-6-AC-C28 L18 (per m) 69 28 LED D 1,932
Total 112,051 107,407
L0.0 Arrival Wall
L0-2-AC-F15 L17 (900mm) 2750 20 FL D 54,863

Total 54,863
L0.0 Arrivals Hall Level - Car Park Bridges
Floor level
L00-UT-C01 XL3 (per m) XS1 984 188 15 54 LED D 14,760 10,152
Total 14,760 10,152
Ceiling level
L00-UT-C02 XD1c 86 31 LED D 2,666
Total 2,666
L0.1 Utilidor Level
Area UT
Floor level
L01-UT-F17 L2b (per m) 478 25 LED D 11,950
L01-UT-F18 L3 (per m) 234 15 LED D 3,516
L01-UT-C09 S7 24 82 LED D 1,968
L01-UT-C10 S8 24 80 LED D 1,920

Total 19,354
Ceiling level
L01-UT-C01 L5b (1200mm) 291 54 FL D 15,843
L01-UT-C02 L18b (per m) 350 28 LED D 9,800

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 200 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
L01-UT-C06 D1 8 19 LED D 152
L01-UT-C07 S7 24 82 LED D 1,968
L01-UT-C08 S8 24 80 LED D 1,920

Total 29,683
L0.1 Utilidor Level - Arrivals Central Area
Area AC
Ceiling level
L01-6-AC-C01 L5 (1200mm) 496 106 FL D 52,815
L01-6-AC-C02 D1 92 19 LED D 1,748
L01-6-AC-C03 S1 46 55 LED D 2,530
L01-6-AC-C04 L4 (1200mm) 965 27 FL D 25,934
L01-6-AC-C05 S1 58 55 LED D 3,190
L01-6-AC-C06 L4 (1200mm) 825 27 FL D 22,172
L01-6-AC-C07 L2c (per m) 460 15 LED D 6,900
L01-6-AC-C08 L5 (1200mm) 460 106 FL D 48,981
L01-6-AC-C09 L2c (per m) 165 15 LED D 2,475
L01-6-AC-C10 L5 (1200mm) 151 106 FL D 16,079
L01-6-AC-C12 D9 30 65 LED D 1,950
L01-6-AC-C12b D9b 40 80 LED D 3,200
D9f 30 80 LED D 2,400
L01-6-AC-C12c D9 4 65 LED D 260
L01-6-AC-C12d D9b 20 80 LED D 1,600
L01-6-AC-C12e D9b 8 80 LED D 640
L01-6-AC-C12f D9b 16 32 80 LED D 1,280 2,560
L01-6-AC-C12g D9b 48 80 LED D 3,840
L01-6-AC-C13 D9b 16 80 LED D 1,280
L01-6-AC-C13b D9b 60 80 LED D 4,800
D9d 4 55 LED D 220
L01-6-AC-C14 L5 (1200mm) 112 106 FL D 11,926
L01-6-AC-C15 D8 252 62 LED D 15,624
L01-6-AC-C15b D8c 105 62 LED D 6,510
D8d 16 62 LED D 992
L01-6-AC-C16 L5 (1200mm) 252 106 FL D 26,833
L01-6-AC-C17 L18b (per m) 450 28 LED D 12,600
L01-6-AC-C18 L4 (1200mm) 573 27 FL D 15,392
L01-6-AC-C19 D13 156 90 LED D 14,040
L01-6-AC-C20 D9b 50 80 LED D 4,000
L01-6-AC-C21 L14 (per m) 170 15 LED D 2,550
L01-6-AC-C22 L4 (900mm) L4 (1200mm) 50 20 27 FL D 998 1,344
L01-6-AC-C23 L18 (per m) 63 28 LED D 1,764
L01-6-AC-C23b L18 (per m) 41 28 LED D 1,148
L01-6-AC-C24 D12 5 11 LED D 55
D12b 12 1 LED D 12
L01-6-AC-C25 L18 (per m) 37 28 LED D 1,022
L01-6-AC-C26 D12 10 11 LED D 110
D12b 3 1 LED D 3
L01-6-AC-C26b D1 3 19 LED D 57
L01-6-AC-C27 L4 (900mm) L4 (1200mm) 13 10 20 27 FL D 266 263
L01-6-AC-C28 D12 4 5 11 LED D 44 55
L01-6-AC-C29 L4 (900mm) D12 20 2 20 11 FL LED D 399 22
L01-6-AC-C30 L18 (per m) 7 28 LED D 196
L01-6-AC-C31 L4 (900mm) 10 20 FL D 200
L01-6-AC-C32 D12 4 11 LED D 44
L01-6-AC-C33 L4 (900mm) 16 20 FL D 319
L01-6-AC-C34 L4 (900mm) L4 (1200mm) 19 27 20 27 FL D 379 726
L01-6-AC-C35 L18 (per m) 7 17 28 LED D 202 484
L01-6-AC-C36 L4 (900mm) L4 (1200mm) 23 15 20 27 FL D 459 390
L01-6-AC-C37 L18 (per m) 10 28 LED D 280
L01-6-AC-C38 D12 8 11 LED D 88
L01-6-AC-C38b D1 2 19 LED D 38
L01-6-AC-C39 L18 (per m) 3 28 LED D 84
L01-6-AC-C40 L18 (per m) 626 28 LED D 17,528
L01-6-AC-C41 L18 (per m) 97 28 LED D 2,716
L18d (per m) 245 44 LED D 10,780
L18f (per m) 55 26 LED D 1,417
L01-6-AC-C42 L18b (per m) 517 28 LED D 14,476
L01-6-AC-C43 D9d 20 55 LED D 1,100
L01-6-AC-C44 D9 12 11 65 LED D 132 780
L01-6-AC-C45 D9 4 65 LED D 260
L01-6-AC-C46 D12 2 11 LED D 22
L01-6-AC-C47 L18 (per m) 10 28 LED D 291
L01-6-AC-C48 D12 4 11 LED D 44
D12b 2 1 LED D 2
L01-6-AC-C49 L18 (per m) 14 28 LED D 392
L01-6-AC-C50 D12 4 11 LED D 44
D12b 2 1 LED D 2
L01-6-AC-C51 D1 1 19 LED D 19
L01-6-AC-C52 L4 (1200mm) 20 27 FL D 538
L01-6-AC-C53 L18 (per m) 11 28 LED D 294
L01-6-AC-C54 L4 (1200mm) 9 27 FL D 237
L01-6-AC-C55 D12 3 11 LED D 33
L01-6-AC-C56 L4 (1200mm) 7 27 FL D 175
Total 371,358 375,135
L0.1 Utilidor Level - Arrivals Entry/Forecourt
Area AE
Ceiling level
L0-6-AE-C01 D1 28 19 LED D 532
XD1 80 24 LED D 1,880

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 201 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
L0-6-AE-C02 L5 (1200mm) 245 106 FL D 26,088
XL1 (1200mm) 787 106 FL D 83,801
L0-6-AE-C03 L5 (1200mm) 214 106 FL D 22,787
XL1 (1200mm) 634 106 FL D 67,509
L0-6-AE-C04 L2c (per m) 314 15 LED D 4,710
XL3 (per m) 750 15 LED D 11,250
L0-6-AE-C05 XL2c (1200mm) 2840 27 FL D 76,325
L0-6-AE-C06 D9b 86 80 LED D 6,880
L0-6-AE-C06b D9b 44 80 LED D 3,520
L0-6-AE-C07 L2c (per m) 261 128 15 LED D 3,915 1,920
L0-6-AE-C08 L4 (1200mm) 856 27 FL D 23,005
L0-6-AE-C09 S1 42 55 LED D 2,310
L0-6-AE-C10 XL2e 758 15 LED D 11,370
L0-6-AE-C11 XD1d 244 14 LED D 3,416
L0-6-AE-C12 XL2c (1200mm) 2243 27 FL D 60,281
L0-6-AE-C13 XD2 148 34 LED D 5,032
L0-6-AE-C13b L18 (per m) 314 28 LED 8,792
L0-6-AE-C14 D9 77 65 LED D 5,005
Total 428,408 426,413
L1.0 Apron Level
Bussing gate
L1-BG-F04 S4 24 25 LED D 600
L1-BG-F05 U3 124 15 LED D 1,860
L1-BG-F07 XT3 10 24 CFL D 240
L1-BG-F08 XT5 4 92 LED D 368
L1-BG-F09 L2o (per m) 132 12 LED D 1,584

Total 4,652

Gates
Area GN-A1
L1-A1-F01 XL2 (per m) 56 112 21 LED D 1,176 2,352
Total 1,176 2,352
Area GN-A2
L1-A2-F01 XL2 (per m) 54 21 LED D 1,134

Total 1,134
Area GN-A3
L1-A3-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134

Area GN-A4
L1-A4-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134

Area GN-A5
L1-A5-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134
Area GN-A6
L1-A6-F01 XL2 (per m) 54 21 LED D 1,134

Total 1,134
Area GN-A7
L1-A7-F01 XL2 (per m) 54 21 LED D 1,134

Total 1,134

Area GN-A8
L1-A8-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134

Area GN-A9
L1-A9-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134
Area GN-B1
L1-B1-F01 XL2 (per m) 54 21 LED D 1,134

Total 1,134
Area GN-B2
L1-B2-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134
Area GN-B3
L1-B3-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134
Area GN-B4
L1-B4-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134

Area GN-B5
L1-B5-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134
Area GN-B6
L1-B6-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134

Area GN-C1
L1-C1-F01 XL2 (per m) 56 21 LED D 1,176

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 202 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
Total 1,176
Area GN-C2
L1-C2-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134

Area GN-C3
L1-C3-F01 XL2 (per m) 56 112 21 LED D 1,176 2,352
Total 1,176 2,352
Area GN-C4
L1-C4-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134
Area GN-C5
L1-C5-F01 XL2 (per m) 54 21 LED D 1,134

Total 1,134
Area GN-C6
L1-C6-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134
Area GN-C7
L1-C7-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134
Area GN-C8
L1-C8-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134
Area GN-C9
L1-C9-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134

Area GN-C10
L1-C10-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134

Area GN-C11
L1-C11-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134

Area GN-C12
L1-C12-F01 XL2 (per m) 56 21 LED D 1,176

Total 1,176
Area GN-C13
L1-C13-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134

Area GN-C14
L1-C14-F01 XL2 (per m) 54 21 LED D 1,134

Total 1,134
Area GN-C15
L1-C15-F01 XL2 (per m) 56 21 LED D 1,176
Total 1,176
Area GN-C17
L1-C17-F01 XL2 (per m) 56 21 LED D 1,176
Total 1,176
Area GN-D1
L1-D1-F01 XL2 (per m) 50 21 LED D 1,050
Total 1,050
Area GN-D2
L1-D2-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134

Area GN-D3
L1-D3-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134

Area GN-D4
L1-D4-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134
Area GN-D5
L1-D5-F01 XL2 (per m) 54 21 LED D 1,134

Total 1,134
Area GN-D6
L1-D6-F01 XL2 (per m) 54 21 LED D 1,134

Total 1,134
Area GN-D7
L1-D7-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134
Area GN-D8
L1-D8-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134
Area GN-D9

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 203 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
L1-D9-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134
Area GN-D10
L1-D10-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134
Area GN-D11
L1-D11-F01 XL2 (per m) 54 21 LED D 1,134

Total 1,134
Area GN-D12
L1-D12-F01 XL2 (per m) 54 21 LED D 1,134

Total 1,134
Area GN-D13
L1-D13-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134
Area GN-D14
L1-D14-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134
Area GN-D15
L1-D15-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134
Area GN-D16
L1-D16-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134

Area GN-D17
L1-D17-F01 XL2 (per m) 54 21 LED D 1,134
Total 1,134

CONCOURSES
Concourse A
L1-CA-F02 XT2 20 80 MH LED D 1,600
L1-CA-F02b XT2 8 80 MH LED D 640
L1-CA-F03 U5 121 29 45 LED D 3,509 5,445
Total 5,749 7,685
Concourse B
L1-CB-F02 U5 112 29 45 LED D 3,248 5,040
Total 3,248 5,040
Bussing gates
Ceiling level
L1-BG-C01 L4 (900mm) L4 (1200mm) 704 20 27 FL D 14,038 18,910
L1-BG-C02 L18 (per m) 1075 28 LED D 30,100
L1-BG-C02b D1 6 19 LED D 114
L1-BG-C03 L4 (900mm) L4 (1200mm) 442 20 27 FL D 8,814 11,874
L1-BG-C04 D12 228 11 LED D 2,508
D1 33 19 LED D 627
L1-BG-C06 L2c (per m) 64 15 LED D 957
L1-BG-C07 D3 12 13 LED D 156
L1-BG-C10 L18 (per m) 3 28 LED D 84
L1-BG-C11 D12 2 11 LED D 22
L1-BG-C12 L18 (per m) 2 28 LED D 56
L1-BG-C13 D12 2 11 LED D 22
L1-BG-C13b D1 2 19 LED D 38
L1-BG-C14 L18 (per m) 35 28 LED D 980
L1-BG-C15 D12b 7 1 LED D 7
L1-BG-C17 D12 12 11 LED D 132
L1-BG-C18 L18 (per m) 39 28 LED D 1,092
L1-BG-C19 D12 12 11 LED D 132
L1-BG-C21 D12b 6 1 LED D 6
L1-BG-C22 L18 (per m) 2 28 LED D 56
L1-BG-C23 D12 2 11 LED D 22
L1-BG-C23b D1 2 19 LED D 38
L1-BG-C24 L18 (per m) 2 28 LED D 67
L1-BG-C25 D12 2 11 LED D 22
L1-BG-C26 L18 (per m) 27 28 LED D 756
L1-BG-C27 D12 8 11 LED D 88
D12b 6 1 LED D 6
L1-BG-C28 L18 (per m) 32 28 LED D 882
L1-BG-C29 D12 12 11 LED D 132
D12b 6 1 LED D 6
L1-BG-C30 L18 (per m) 4 2 28 LED D 112 56
L1-BG-C31 D12 2 11 LED D 22
L1-BG-C31b D1 1 19 LED D 19
L1-BG-C32 L18 (per m) 3 28 LED D 76
L1-BG-C33 D12 2 11 LED D 22
L1-BG-C34 L18 (per m) 15 4 28 LED D 420 112
L1-BG-C35 D12b 6 1 LED D 6
L1-BG-C36 L18 (per m) 16 30 28 LED D 445 826
L1-BG-C37 D12 10 7 11 LED D 110 77
L1-BG-C38 L18 (per m) 23 28 LED D 644
L1-BG-C39 D12 7 11 LED D 77
D12b 4 1 LED D 4
L1-BG-C40 L4 (900mm) L4 (1200mm) 16 20 27 FL D 326 440
L1-BG-C41 D12 6 11 LED D 66
Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 204 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
L1-BG-C42 L4 (900mm) L4 (1200mm) 17 20 27 FL D 345 464
L1-BG-C43 L18 (per m) 12 28 LED D 336
L1-BG-C44 L4 (900mm) L4 (1200mm) 15 20 27 FL D 308 415
L1-BG-C45 L18 (per m) 7 28 LED D 202
L1-BG-C46 L4 (900mm) L4 (1200mm) 15 20 27 FL D 308 415
L1-BG-C47 D12 4 11 LED D 44
L1-BG-C48 L18 (per m) 142 28 LED D 3,976
Total 69,828 78,191
ARRIVAL TUNNEL
L1-AT-C01 L6 (per m) TBC TBC LED D TBC
L2b (per m) TBC TBC LED D TBC

Total TBC

L1-PA-C01 L18b (per m) 253 28 LED D 7,073


L1-PA-C02 D1 4 19 LED D 76

Total 7,149
CONCOURSES
Concourse A
L1-CA-C01 XL2 (per m) 792 21 LED D 16,632
L1-CA-C02 L4 (900mm) L4 (1200mm) 53 20 27 FL D 1,052 1,417
L1-CA-C03 D1 2 19 LED D 38
D6 2 19 LED D 38
L1-CA-C04 D3 7 13 LED D 91
L1-CA-C05 L2c (per m) 24 15 LED D 358
L1-CA-C06 L4 (900mm) L4 (1200mm) 21 20 27 FL D 417 562
L1-CA-C07 D12 4 2 11 LED D 44 22
L1-CA-C08 L4 (900mm) L4 (1200mm) 15 20 27 FL D 308 415
L1-CA-C09 L18 (per m) 5 28 LED D 140
L1-CA-C10 L4 (900mm) L4 (1200mm) 19 20 27 FL D 381 513
L1-CA-C11 L18 (per m) 13 28 LED D 364
L1-CA-C12 L4 (900mm) L4 (1200mm) 34 20 27 FL D 671 904
L1-CA-C13 D12 6 3 11 LED D 66 33
Total 20,600 21,527
Concourse B
L1-CB-C01 XL2 (per m) 856 21 LED D 17,976
L1-CB-C02 L4 (900mm) L4 (1200mm) 52 20 27 FL D 1,034 1,393
L1-CB-C03 D1 2 19 LED D 38
D6 2 19 LED D 38
L1-CB-C04 D3 7 13 LED D 91
L1-CB-C05 L2c (per m) 24 15 LED D 358
L1-CB-C06 L4 (900mm) L4 (1200mm) 23 20 27 FL D 453 611
L1-CB-C07 D12 4 2 11 LED D 44 22
L1-CB-C08 L4 (900mm) 34 20 FL D 671
L1-CB-C09 D12 7 11 LED D 77
L1-CB-C10 L4 (900mm) 15 20 FL D 290
L1-CB-C11 L18 (per m) 6 28 LED D 168
L1-CB-C12 L4 (900mm) 19 20 FL D 381
L1-CB-C13 L18 (per m) 11 28 LED D 302

Total 21,921 20,526


Concourse C
L1-CC-C01 XL2 (per m) 1034 21 LED D 21,714

Total 21,714
Concourse D
L1-CD-C01 XL2 (per m) 1182 21 LED D 24,822
Total 24,822
L2.0 Departures Forecourt
Floor level
L2-PF-F01 XL1b (per m) 441 33 LED D 14,553
L2-PF-F02 S3 30 43 LED D 1,290
L2-PF-F03 S4 65 25 LED D 1,625
L2-PF-F04 U4b 196 15 LED D 2,940
L2-PF-F05 XT1 26 212 LED D 5,512
L2-PF-F06 XD1d 24 14 LED D 336
L2-PF-F07 U3 44 15 LED D 660
L2-PF-F09 XT1 18 212 LED D 3,816
L2-PF-F10 S4 24 25 LED D 600

Total 31,332
L2.0 Departures Entry
ENTRANCE DOORS AND VOIDS
Floor level
L2-PE-F17 L17 (1500mm) 66 35 FL D 2,281
Total 2,281
Ceiling level
L0-2-AE-C03 D12 132 11 LED D 1,452

Total 1,452
INFORMATION DESKS
Floor level
L2-PE-F02 L13c (per m) 66 15 LED D 990
L2-PE-F03 L2b (per m) 31 25 LED D 770
Total 1,760
COLUMN UPLIGHTS AND LANDSCAPE
Floor level
Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 205 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
L2-PE-F04 XL4 (per m) 88 45 LED D 3,942
L2-PE-F09 S4 32 25 LED D 800

Total 4,742
CENTRAL PAVILLION
Ceiling level
L2-PE-C04 L2c (per m) 47 32 15 LED D 707 480
L2-PE-C05 D6 4 19 LED D 76

Total 783 556


CHECK-IN ZONES
Floor level
L2-PE-F10 L13c (per m) 19 15 LED D 281
L2-PE-F14 L7 (per m) 126 30 LED D 3,765
L2-PE-F18 S4 28 25 LED D 700
L2-PE-F23 L7 (per m) 315 30 LED D 9,458

Total 14,203
CHECK-IN DESKS (1-5)
Floor level
L2-PE-F24 L13c (per m) 148 15 LED D 2,220
L2-PE-F25 L8 (per m) 197 32 LED D 6,310
L2-PE-F27 L17 (1200mm) 103 27 FL D 2,774
Total 11,304
SECURITY
Floor level
L2-PE-F28 L8 (per m) 7 32 LED D 230
L2-PE-F29 L8 (per m) 22 32 LED D 691
L2-PE-F30 L8 (per m) 19 32 LED D 614
L2-PE-F31 L7 (per m) 30 30 LED D 909
L2-PE-F32 L13c (per m) 7 15 LED D 102
L2-PE-F33 D1 6 19 LED D 114

Total 2,661
Ceiling level
L2-PE-C08 L4 (1200mm) 297 189 27 FL D 7,982 5,090
L2-PE-C09 D2 137 54 LED D 7,398
D6 12 19 LED D 228
L2-PE-C10 L2c (per m) 86 51 15 LED D 1,290 765
L2-PE-C12 D9 39 18 65 LED D 2,535 1,170
L2-PE-C13 L2c (per m) 150 70 15 LED D 2,256 1,046
L2-PE-C14 D9 72 93 65 LED D 4,680 6,045
L2-PE-C15 D9 D8c 33 32 65 62 LED D 2,145 1,984
L2-PE-C16 L18 (per m) 332 28 LED D 9,296
L2-PE-C18 D1 1 19 LED D 19
L2-PE-C19 D9 10 10 65 LED D 650 650
L2-PE-C20 D12 4 11 LED D 44
D12b 2 1 LED D 2
L2-PE-C21 L18 (per m) 16 28 LED D 454
L2-PE-C22 L18 (per m) 2 28 LED D 56
L2-PE-C23 D12 2 11 LED D 22
L2-PE-C24 L18 (per m) 25 28 LED D 700
L2-PE-C25 D12 4 11 LED D 44
D12b 4 1 LED D 4
L2-PE-C26 D12b 8 1 LED D 8
L2-PE-C27 L18 (per m) 4 28 LED D 112
L2-PE-C28 D12 13 11 LED D 143
L2-PE-C29 L18 (per m) 49 28 LED D 1,380
L2-PE-C30 D12 9 11 LED D 99
L2-PE-C31 L18 (per m) 40 28 LED D 1,117
L2-PE-C32 D12b 8 1 LED D 8
L2-PE-C33 D1 1 19 LED D 19
L2-PE-C34 D12 2 11 LED D 22
L2-PE-C35 L18 (per m) 2 28 LED D 56
L2-PE-C36 L18 (per m) 3 28 LED D 76
L2-PE-C37 D12 2 11 LED D 22
L2-PE-C38 D12b 4 1 LED D 4
L2-PE-C38b D1 2 19 LED D 38
L2-PE-C39 L18 (per m) 8 28 LED D 231
L2-PE-C40 L18 (per m) 34 28 LED D 946
L2-PE-C41 D12 9 11 LED D 99
L2-PE-C42 L18 (per m) 4 28 LED D 109
L2-PE-C43 D12 2 11 LED D 22
L2-PE-C44 L18 (per m) 30 28 LED D 840
L2-PE-C45 D12 6 11 LED D 66
L2-PE-C47 D12 D12b 5 11 1 LED D 55 5
L2-PE-C48 L18 (per m) 2 28 LED D 56
L2-PE-C49 D12 2 11 LED D 22
L2-PE-C49b D1 1 19 LED D 19
L2-PE-C50 L18 (per m) 15 28 LED D 428
L2-PE-C51 D12 3 11 LED D 33
D12b 1 1 LED D 1
L2-PE-C52 L18 (per m) 15 28 LED D 423
L2-PE-C53 D12 3 11 LED D 33
D12b 1 1 LED D 1
L2-PE-C54 L4 (1200mm) 86 27 FL D 2,321
L2-PE-C55 D1 13 19 LED D 247
L2-PE-C56 L4 (1200mm) 50 27 FL D 1,334
L2-PE-C57 D1 20 19 LED D 380
L2-PE-C58 D1 19 19 LED D 361
Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 206 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
L2-PE-C59 L4 (1200mm) 50 27 FL D 1,346
L2-PE-C60 L4 (1200mm) 87 27 FL D 2,343
L2-PE-C61 D1 13 19 LED D 247
L2-PE-C62 D12 3 11 LED D 33
D12b 1 1 LED D 1
L2-PE-C62b D1 1 19 LED D 19
L2-PE-C63 L18 (per m) 15 28 LED D 431
L2-PE-C64 D12 4 11 LED D 44
D12b 2 1 LED D 2
L2-PE-C65 L18 (per m) 15 28 LED D 423
L2-PE-C66 D12 2 11 LED D 22
D12b 0 1 LED D 0
L2-PE-C67 L18 (per m) 2 28 LED D 67
L2-PE-C68 L18 (per m) 30 28 LED D 829
L2-PE-C69 D12 2 11 LED D 22
L2-PE-C70 L18 (per m) 4 28 LED D 109
L2-PE-C71 D12 6 11 LED D 66
D12b 5 1 LED D 5
L2-PE-C72 L18 (per m) 35 8 28 LED D 970 224
L2-PE-C73 D12 9 11 LED D 99
D12b 4 1 LED D 4
L2-PE-C74 L18 (per m) 8 28 LED D 210
L2-PE-C75 D1 2 19 LED D 38
L2-PE-C76 L18 (per m) 0 28 LED D 0
Total 58,267 52,683
L2.0 Departures Airside lounge
COLUMN UPLIGHTS AND LANDSCAPE
Floor level
L2-PA-F01 XL4 (per m) 152 45 LED D 6,840
L2-PA-F02 S3 6 43 LED D 258
Total 7,098

GENERAL CENTRE SPACE


Floor level
L2-PA-F04 XT3 52 29 24 CFL D 1,248 696
L2-PA-F06 S4 235 157 25 LED D 5,875 3,925
L2-PA-F09 U3 99 15 LED D 1,485
L2-PA-F10 U3 60 15 LED D 900
L2-PA-F11 L13c (per m) 17 15 LED D 258
L2-PA-F13 L13c (per m) 45 34 15 LED D 672 507
L2-PA-F14 L13c (per m) 0 15 LED D 0
L2-PA-F29 L20b (per m) 25 80 LED D 2,000
L2-PA-F30 L2c (per m) 59 29 15 LED D 882 441
L2-PA-F31 U7 29 28 LED D 812
L2-PA-F32 U8 8 35 LED D 280
L2-PA-F33 XT3 26 22 24 CFL D 624 528
L2-PA-F34 L20c (per m) 43 153 22 LED D 946 3,366
L2-PA-F35 XT6 11 36 LED D 396

Total 16,378 15,594


RETAIL AREAS
Ceiling level
L2-PA-C01 D1 8 19 LED D 152
L2-PA-C02 D1 61 54 19 LED D 1,159 1,026
L2-PA-C03 L18b (per m) 856 276 28 LED D 23,968 7,728
L2c (per m) 970 15 LED D 14,556
L2-PA-C04 L4 (1200mm) 54 27 FL D 1,444
L2-PA-C04b L18 (per m) 22 24 28 LED D 608 672
L2-PA-C05 L18 (per m) 188 28 LED D 5,251
L2-PA-C06 L4 (1200mm) 112 122 27 FL D 3,020 3,271
L2-PA-C07 L4 (1200mm) 156 133 27 FL D 4,195 3,582
L2-PA-C08 L4 (1200mm) 155 117 27 FL D 4,171 3,144
L2-PA-C09 L18 (per m) 89 45 28 LED D 2,503 1,260
L2-PA-C10 L18 (per m) 68 28 LED D 1,915
D1 1 19 LED D 19
L2-PA-C11 L4 (1200mm) 89 27 FL D 2,394
L2-PA-C12 L18 (per m) 171 105 28 LED D 4,788 2,940
L2-PA-C13 L4 (1200mm) 195 126 27 FL D 5,238 3,374
L2-PA-C14 L18 (per m) 105 72 28 LED D 2,940
D6 2 19 LED D 38
L2-PA-C15 L4 (1200mm) 201 154 27 FL D 5,397 4,144
L2-PA-C17 L18 (per m) 49 28 LED D 1,378
L2-PA-C18 L4 (1200mm) 58 27 FL D 1,561
L2-PA-C19 D1 59 55 19 LED D 1,121 1,045
D2 67 94 54 LED D 3,618 5,076
L18 (per m) 10 25 28 LED D 269 706
L2-PA-C20 L4 (1200mm) 353 360 27 FL D 9,485 9,665
L2-PA-C21 L2b (per m) 27 25 LED D 678
L2-PA-C22 L18 (per m) 24 28 LED D 672
L2-PA-C23 L5b (1200mm) 349 360 54 FL D 18,974 19,595
L2-PA-C24 L18 (per m) 43 28 LED D 1,210
L2-PA-C25 D12 8 11 LED D 88
D12b 10 1 LED D 10
L2-PA-C26 L18 (per m) 5 28 LED D 140
XL2 (per m) 7 21 LED D 149
L2-PA-C27 D12 2 11 LED D 22
D18 5 4 11 LED D 55 44
L2-PA-C27b D1 1 19 LED D 19
L2-PA-C28 L18 (per m) 51 28 LED D 1,428

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 207 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
L2-PA-C29 D12 14 11 LED D 154
D12b 10 1 LED D 10
L2-PA-C30 L18 (per m) 6 28 LED D 168
XL2 (per m) 6 21 LED D 126
L2-PA-C31 D12 3 11 LED D 33
D18 4 11 LED D 44
L2-PA-C31b D1 2 19 LED D 38
L2-PA-C32 L4 (1200mm) 24 27 FL D 633
L2-PA-C33 L4 (1200mm) 13 27 FL D 359
L2-PA-C34 D12 8 11 LED D 88
L2-PA-C35 D12 15 11 LED D 165
L2-PA-C36 L4 (1200mm) 39 27 FL D 1,051
L2-PA-C39 L4 (1200mm) 7 27 FL D 182
L2-PA-C40 D12 3 11 LED D 33
L2-PA-C40b D1 1 19 LED D 19
L2-PA-C41 L18 (per m) 18 28 LED D 504
L2-PA-C42 L4 (1200mm) 24 27 FL D 653
L2-PA-C43 L4 (1200mm) 10 27 FL D 274
L2-PA-C44 D12 4 11 LED D 44
L2-PA-C45 L4 (1200mm) 20 27 FL D 531
L2-PA-C46 L18 (per m) 13 28 LED D 370
L2-PA-C47 D12 2 11 LED D 22
L2-PA-C48 L18 (per m) 3 28 LED D 84
L2-PA-C49 D12 14 11 LED D 154
D12b 12 1 LED D 12
L2-PA-C49b D1 2 19 LED D 38
L2-PA-C50 L18 (per m) 50 28 LED D 1,403
L2-PA-C51 D12 13 11 LED D 143
D12b 8 1 LED D 8
L2-PA-C52 L18 (per m) 39 28 LED D 1,103
L2-PA-C53 D12 6 11 LED D 66
D12b 8 1 LED D 8
L2-PA-C53b D1 3 19 LED D 57
L2-PA-C54 L18 (per m) 24 28 LED D 678
L2-PA-C55 L18 (per m) 2 28 LED D 50
L2-PA-C56 D12 2 11 LED D 22
L2-PA-C57 L18 (per m) 3 28 LED D 84
L2-PA-C58 D12 2 11 LED D 22
L2-PA-C59 D12 11 11 LED D 121
D12b 8 1 LED D 8
L2-PA-C60 L18 (per m) 47 28 LED D 1,302
L2-PA-C61 L4 (1200mm) 26 27 FL D 709
L2-PA-C62 L18 (per m) 18 28 LED D 504
L2-PA-C63 L4 (1200mm) 20 27 FL D 547
L2-PA-C64 L18 (per m) 12 28 LED D 336
L2-PA-C65 L4 (1200mm) 13 27 FL D 353
L2-PA-C66 D12 6 11 LED D 66
L2-PA-C67 D12 18 21 11 LED D 198 231
L2-PA-C67b D1 2 19 LED D 38
L2-PA-C68 L4 (1200mm) 30 27 FL D 802
L2-PA-C69 L4 (1200mm) 34 27 FL D 909
L2-PA-C70 L4 (1200mm) 24 27 FL D 653
L2-PA-C71 D12 8 11 LED D 88
D12b 8 1 LED D 8
L2-PA-C72 L18 (per m) 39 28 LED D 1,078
L2-PA-C73 XL2 (per m) 5 21 LED D 95
L2-PA-C74 D18 3 11 LED D 33
L2-PA-C75 XL2 (per m) 3 21 LED D 55
L2-PA-C76 D18 2 11 LED D 22
D1 1 19 LED D 19
L2-PA-C77 D12 2 11 LED D 22
L2-PA-C78 L18 (per m) 3 28 LED D 84
L2-PA-C78b D1 2 19 LED D 38
L2-PA-C79 L18 (per m) 3 28 LED D 84
L2-PA-C80 D12 3 11 LED D 33
L2-PA-C81 D18 2 11 LED D 22
L2-PA-C82 XL2 (per m) L18 (per m) 2 3 21 28 LED D 50 84
L2-PA-C82b XL2 (per m) 2 21 LED D 42
L2-PA-C83 D18 3 11 LED D 33
L2-PA-C84 XL2 (per m) 4 21 LED D 88
L2-PA-C85 L18 (per m) 45 28 LED D 1,268
L2-PA-C86 D12 14 11 LED D 154
D12b 10 1 LED D 10
L2-PA-C89 D2 4 54 LED D 216
L2-PA-C90 L18 (per m) 13 28 LED D 370
L2-PA-C91 L18 (per m) 10 28 LED D 269
Total 129,128 116,194
L2.0 Concourse A
Area CA
Floor level
L2-CA-F01 L3 (per m) 543 15 LED D 8,145
Total 8,145
Ceiling level
L2-CA-C01 L5 (1200mm) 484 106 FL D 51,555
L2-CA-C03 L18b (per m) 589 28 LED D 16,492
L2-CA-C04 L21 (per m) 374 50 LED D 18,700
L2-CA-C05 L4 (1200mm) 28 27 FL D 753
D6 2 19 LED D 38
Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 208 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
L2-CA-C06 L18 (per m) 4 28 LED D 118
L2-CA-C07 L18 (per m) 16 28 LED D 445
L2-CA-C08 D12 3 11 LED D 33
D12b 2 1 LED D 2
L2-CA-C09 L18 (per m) 17 28 LED D 480
L2-CA-C10 D12 5 11 LED D 55
D12b 3 1 LED D 3
L2-CA-C11 L4 (1200mm) 12 27 FL D 313
L2-CA-C12 L18 (per m) 4 28 LED D 112
L2-CA-C13 L4 (1200mm) 11 27 FL D 293
L2-CA-C14 D12 2 11 LED D 22
L2-CA-C15 L4 (1200mm) 14 27 FL D 366
L2-CA-C16 D12 4 11 LED D 44
L2-CA-C17 L4 (1200mm) 13 27 FL D 344
L2-CA-C18 L18 (per m) 5 28 LED D 151

Total 88,673 90,319


Area GN-A1 and Lounge
Floor level
L2-A1-F01 U3 60 15 LED D 900
L2-A1-F03 L2c (per m) 52 15 LED D 780
L2-A1-F04 L17 (1200mm) 31 27 FL D 833
L17 (600mm) 4 14 FL D 57
L2-A1-F05 S4 12 25 LED D 300

Total 2,870
Ceiling level
L2-A1-C01 L2c (per m) 23 15 LED D 345
L2-A1-C02 D1c 4 47 LED D 186
L2-A1-C03 D2 46 54 LED D 2,484
L2-A1-C04 L4 (1200mm) 129 27 FL D 3,467
L2-A1-C05 L18 (per m) 228 28 LED D 6,384
L2-A1-C06 L18 (per m) 209 28 LED D 5,852
L18b (per m) 213 233 28 LED D 5,964 6,518
D1 83 88 19 LED D 1,577 1,672
L2-A1-C07 L18 (per m) 81 28 LED D 2,260
Total 28,518 23,316
Area GN-A2
Floor level
L2-A2-F01 U3 52 15 LED D 780
L2-A2-F03 L2c (per m) 104 15 LED D 1,560
L2-A2-F04 L17 (1200mm) 71 27 FL D 1,908
L17 (600mm) 7 14 FL D 100
L2-A2-F05 S4 24 25 LED D 600

Total 4,948

Ceiling level
L2-A2-C01 L2c (per m) 23 15 LED D 345
L2-A2-C02 D1c 4 47 LED D 186
L2-A2-C03 D2 4 54 LED D 216
L2-A2-C04 L4 (1200mm) 11 27 FL D 296
L2-A2-C05 L18 (per m) 34 28 LED D 938
L2-A2-C06 L4 (1200mm) 29 27 FL D 774
L2-A2-C07 L18 (per m) 19 28 LED D 538
Total 3,293

Area GN-A3
Floor level
L2-A3-F01 U3 22 15 LED D 330
L2-A3-F03 L2c (per m) 52 15 LED D 780
L2-A3-F04 L17 (1200mm) 40 27 FL D 1,075
L17 (600mm) 2 14 FL D 29
L2-A3-F05 S4 12 25 LED D 300

Total 2,514
Ceiling level
L2-A3-C01 L2c (per m) 23 15 LED D 345
L2-A3-C02 D1c 4 47 LED D 186

Total 531
Area GN-A4
Floor level
L2-A4-F01 U3 22 15 LED D 330
L2-A4-F03 L2c (per m) 52 15 LED D 780
L2-A4-F05 S4 24 25 LED D 600
Total 1,710
Ceiling level
L2-A4-C01 L2c (per m) 23 15 LED D 345
L2-A4-C02 D1c 4 47 LED D 186

Total 531
Area GN-A5
Floor level
L2-A5-F01 U3 22 15 LED D 330
L2-A5-F03 L2c (per m) 52 15 LED D 780
L2-A5-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-A5-F05 S4 12 25 LED D 300
Total 1,962

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 209 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
Ceiling level
L2-A5-C01 L2c (per m) 23 15 LED D 345
L2-A5-C02 D1c 4 47 LED D 186

Total 531
Area GN-A6
Floor level
L2-A6-F01 U3 22 15 LED D 330
L2-A6-F03 L2c (per m) 52 15 LED D 780
L2-A6-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-A6-F05 S4 12 25 LED D 300
Total 1,962

Ceiling level
L2-A6-C01 L2c (per m) 23 15 LED D 345
L2-A6-C02 D1c 4 47 LED D 186

Total 531
Area GN-A7
Floor level
L2-A7-F01 U3 5 15 LED D 75
L2-A7-F05 S4 2 25 LED D 50

Total 125
Ceiling level
L2-A7-C01 L2c (per m) 23 15 LED D 345
L2-A7-C02 D1c 4 47 LED D 186

Total 531

Area GN-A8
Floor level
L2-A8-F01 U3 7 15 LED D 105
L2-A8-F05 S4 3 25 LED D 75

Total 180
Ceiling level
L2-A8-C01 L2c (per m) 23 15 LED D 345
L2-A8-C02 D1c 4 47 LED D 186

Total 531
Area GN-A9
Floor level
L2-A9-F01 U3 27 15 LED D 405
L2-A9-F05 S4 13 25 LED D 325

Total 730

Ceiling level
L2-A9-C01 L2c (per m) 23 15 LED D 345
L2-A9-C02 D1c 4 47 LED D 186

Total 531
L2.0 Concourse B
Area CB
Floor level
L2-CB-F01 L3 (per m) 517 15 LED D 7,749

Total 7,749
Ceiling level
L2-CB-C01 L5 (1200mm) 455 106 FL D 48,449
L2-CB-C03 L18b (per m) 553 28 LED D 15,484
L2-CB-C04 L21 (per m) 328 50 LED D 16,400
L2-CB-C05 L18 (per m) 4 28 LED D 118
L2-CB-C06 L18 (per m) 14 28 LED D 384
L2-CB-C07 D12 3 11 LED D 33
D12b 2 1 LED D 2
L2-CB-C08 L18 (per m) 13 28 LED D 350
L2-CB-C09 D12 3 11 LED D 33
D12b 2 1 LED D 2
Total 81,254

Area GN-B1
Floor level
L2-B1-F01 U3 39 15 LED D 585
L2-B1-F03 L2c (per m) 104 15 LED D 1,560
L2-B1-F04 L17 (1200mm) 23 27 FL D 618
L17 (600mm) 2 14 FL D 29
L2-B1-F05 S4 22 25 LED D 550
Total 3,342
Ceiling level
L2-B1-C01 L2c (per m) 23 15 LED D 345
L2-B1-C02 D1c 4 47 LED D 186

Total 531
Area GN-B2
Floor level
L2-B2-F01 U3 22 15 LED D 330
L2-B2-F03 L2c (per m) 52 15 LED D 780
L2-B2-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-B2-F05 S4 12 25 LED D 300

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 210 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
Total 1,962
Ceiling level
L2-B2-C01 L2c (per m) 23 15 LED D 345
L2-B2-C02 D1c 4 47 LED D 186

Total 531
Area GN-B3
Floor level
L2-B3-F01 U3 22 15 LED D 330
L2-B3-F03 L2c (per m) 52 15 LED D 780
L2-B3-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-B3-F05 S4 12 25 LED D 300

Total 1,962
Ceiling level
L2-B3-C01 L2c (per m) 23 15 LED D 345
L2-B3-C02 D1c 4 47 LED D 186

Total 531
Area GN-B4
Floor level
L2-B4-F01 U3 22 15 LED D 330
L2-B4-F03 L2c (per m) 52 15 LED D 780
L2-B4-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-B4-F05 S4 12 25 LED D 300

Total 1,962
Ceiling level
L2-B4-C01 L2c (per m) 23 15 LED D 345
L2-B4-C02 D1c 4 47 LED D 186

Total 531
Area GN-B5
Floor level
L2-B5-F01 U3 22 15 LED D 330
L2-B5-F03 L2c (per m) 52 15 LED D 780
L2-B5-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-B5-F05 S4 12 25 LED D 300

Total 1,962
Ceiling level
L2-B5-C01 L2c (per m) 23 15 LED D 345
L2-B5-C02 D1c 4 47 LED D 186

Total 531

Area GN-B6
Floor level
L2-B6-F01 U3 42 15 LED D 630
L2-B6-F04 L17 (1200mm) 10 27 FL D 269
L17 (600mm) 2 14 FL D 29
L2-B6-F05 S4 13 25 LED D 325

Total 1,252
Ceiling level
L2-B6-C01 L2c (per m) 23 15 LED D 345
L2-B6-C02 D1c 4 47 LED D 186

Total 531
L2.0 Concourse C
Area CC
Floor level
L2-CC-F01 L3 (per m) 427 15 LED D 6,408
L2-CC-F06 S4 30 25 LED D 750
L2-CC-F07 XT3 8 24 CFL D 192

Total 7,350
Ceiling level
L2-CC-C01 L2b (per m) 534 25 LED D 13,350
L2-CC-C06 L5 (1200mm) 1030 106 FL D 109,676
L2-CC-C08 L18b (per m) 1237 28 LED D 34,636
L2-CC-C09 L18 (per m) 306 28 LED D 8,568
L2-CC-C10 L4 (1200mm) 11 24 27 FL D 303 635
L2-CC-C11 L18 (per m) 4 11 28 LED D 101 314
L2-CC-C12 L4 (1200mm) 11 15 27 FL D 304 406
L2-CC-C13 D12 2 5 11 LED D 22 55
L2-CC-C14 L4 (1200mm) 12 24 27 FL D 309 643
L2-CC-C15 L18 (per m) 6 11 28 LED D 157 305
L2-CC-C16 L4 (1200mm) 12 12 27 FL D 317 335
L2-CC-C17 D12 5 11 LED D 55

Total 167,797 168,977


Area GN-C1 - Lounge
Floor level
L2-C1-F01 U3 39 15 LED D 585
L2-C1-F04 L17 (1200mm) 56 27 FL D 1,505
L17 (600mm) 8 14 FL D 114

Total 2,204

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 211 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
Ceiling level
L2-C1-C01 L2c (per m) 23 15 LED D 345
L2-C1-C02 D1c 4 47 LED D 186
L2-C1-C03 D2 8 54 LED D 432
L2-C1-C04 L4 (900mm) L4 (1200mm) 25 20 27 FL D 495 667
L2-C1-C05 L18 (per m) 33 28 LED D 929
L2-C1-C06 L18 (per m) 95 28 LED D 2,660
Total 5,047 5,218
Area GN-C2
Floor level
L2-C2-F01 U3 26 15 LED D 390
L2-C2-F03 L2c (per m) 52 15 LED D 780
L2-C2-F05 S4 12 25 LED D 300

Total 1,470
Ceiling level
L2-C2-C01 L2c (per m) 23 15 LED D 345
L2-C2-C02 D1c 4 47 LED D 186

Total 531
Area GN-C3
Floor level
L2-C3-F01 U3 40 15 LED D 600
L2-C3-F03 L2c (per m) 52 15 LED D 780
L2-C3-F05 S4 12 25 LED D 300
Total 1,680
Ceiling level
L2-C3-C01 L2c (per m) 23 15 LED D 345
L2-C3-C02 D1c 4 47 LED D 186
L2-C3-C03 D2 53 54 LED D 2,862
L2-C3-C04 L4 (1200mm) 150 27 FL D 4,031
L2-C3-C05 L18 (per m) 381 28 LED D 10,657
D1 5 19 LED D 95
L2-C3-C06 L18 (per m) 149 28 LED D 4,172
L18b (per m) 269 279 28 LED D 7,532 7,801
D1 90 101 19 LED D 1,710 1,919
L2-C3-C08 L2b (per m) 593 25 LED D 14,825
L2-C3-C09 L4 (1200mm) 59 27 FL D 1,578
L2-C3-C10 L18 (per m) 44 28 LED D 1,218
Total 49,211 45,421
Area GN-C4
Floor level
L2-C4-F01 U3 22 15 LED D 330
L2-C4-F03 L2c (per m) 52 15 LED D 780
L2-C4-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-C4-F05 S4 12 25 LED D 300

Total 1,962
Ceiling level
L2-C4-C01 L2c (per m) 23 15 LED D 345
L2-C4-C02 D1c 4 47 LED D 186

Total 531

Area GN-C5
Floor level
L2-C5-F01 U3 22 15 LED D 330
L2-C5-F03 L2c (per m) 52 15 LED D 780
L2-C5-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-C5-F05 S4 12 25 LED D 300

Total 1,962

Ceiling level
L2-C5-C01 L2c (per m) 23 15 LED D 345
L2-C5-C02 D1c 4 47 LED D 186

Total 531
Area GN-C6
Floor level
L2-C6-F01 U3 22 15 LED D 330
L2-C6-F03 L2c (per m) 52 15 LED D 780
L2-C6-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-C6-F05 S4 12 25 LED D 300

Total 1,962
Ceiling level
L2-C6-C01 L2c (per m) 23 15 LED D 345
L2-C6-C02 D1c 4 47 LED D 186

Total 531
Area GN-C7
Floor level
L2-C7-F01 U3 22 15 LED D 330
L2-C7-F03 L2c (per m) 52 15 LED D 780
L2-C7-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-C7-F05 S4 12 25 LED D 300
Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 212 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
Total 1,962
Ceiling level
L2-C7-C01 L2c (per m) 23 15 LED D 345
L2-C7-C02 D1c 4 47 LED D 186

Total 531
Area GN-C8
Floor level
L2-C8-F01 U3 22 15 LED D 330
L2-C8-F03 L2c (per m) 52 15 LED D 780
L2-C8-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-C8-F05 S4 12 25 LED D 300

Total 1,962
Ceiling level
L2-C8-C01 L2c (per m) 23 15 LED D 345
L2-C8-C02 D1c 4 47 LED D 186

Total 531
Area GN-C9
Floor level
L2-C9-F01 U3 22 15 LED D 330
L2-C9-F03 L2c (per m) 52 15 LED D 780
L2-C9-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-C9-F05 S4 12 25 LED D 300

Total 1,962
Ceiling level
L2-C9-C01 L2c (per m) 23 15 LED D 345
L2-C9-C02 D1c 4 47 LED D 186

Total 531
Area GN-C10 and Lounge
Floor level
L2-C10-F01 U3 44 15 LED D 660
L2-C10-F03 L2c (per m) 104 15 LED D 1,560
L2-C10-F04 L17 (1200mm) 40 27 FL D 1,075
L17 (600mm) 2 14 FL D 29
L2-C10-F05 S4 24 25 LED D 600

Total 3,924

Area GN-C11
Floor level
L2-C11-F01 U3 22 15 LED D 330
L2-C11-F03 L2c (per m) 52 15 LED D 780
L2-C11-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-C11-F05 S4 12 25 LED D 300

Total 1,962

Ceiling level
L2-C11-C01 L2c (per m) 23 15 LED D 345
L2-C11-C02 D1c 4 47 LED D 186

Total 531

Area GN-C12
Floor level
L2-C12-F01 U3 9 15 LED D 135
L2-C12-F04 L17 (1200mm) 2 27 FL D 54
L2-C12-F05 S4 4 25 LED D 100

Total 289
Ceiling level
L2-C12-C01 L2c (per m) 24 15 LED D 360
L2-C12-C02 D1c 4 47 LED D 186
L2-C12-C03 L4 (1200mm) 67 27 FL D 1,801
L2-C12-C04 D2 21 54 LED D 1,134
L2-C12-C05 L18 (per m) 100 28 LED D 2,800
L2-C12-C06 L18 (per m) 5 28 LED D 140
L2-C12-C07 D12 4 11 LED D 44

Total 6,465
Area GN-C13
Floor level
L2-C13-F01 U3 22 15 LED D 330
L2-C13-F03 L2c (per m) 52 15 LED D 780
L2-C13-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-C13-F05 S4 12 25 LED D 300

Total 1,962
Ceiling level
L2-C13-C01 L2c (per m) 23 15 LED D 345
L2-C13-C02 D1c 4 47 LED D 186

Total 531
Area GN-C14
Floor level
L2-C14-F01 U3 15 15 LED D 225

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 213 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
L2-C14-F05 S4 5 25 LED D 125

Total 350

Ceiling level
L2-C14-C01 L2c (per m) 23 15 LED D 345
L2-C14-C02 D1c 4 47 LED D 186
L2-C14-C03 L18 (per m) 4 28 LED D 112
L2-C14-C04 D12 4 11 LED D 44

Total 687
Area GN-C15
Floor level
L2-C15-F01 U3 9 15 LED D 135
L2-C15-F04 L17 (1200mm) 2 27 FL D 54
L2-C15-F05 S4 4 25 LED D 100

Total 289

Ceiling level
L2-C15-C01 L2c (per m) 23 15 LED D 345
L2-C15-C02 D1c 4 47 LED D 186
L2-C15-C03 L4 (1200mm) 51 27 FL D 1,371
L2-C15-C04 D2 19 54 LED D 1,026
L2-C15-C05 L18 (per m) 104 28 LED D 2,912
L2-C15-C06 L18 (per m) 5 28 LED D 140
L2-C15-C07 D12 4 11 LED D 44

Total 6,024
Area GN-C16 - Lounge
Floor level
L2-C16-F01 U3 16 15 LED D 240
L2-C16-F04 L17 (1200mm) 2 27 FL D 54
L2-C16-F05 S4 4 25 LED D 100

Total 394
Ceiling level
L2-C16-C01 L2c (per m) 24 15 LED D 360
L2-C16-C02 D1c 4 47 LED D 186
L2-C16-C03 L4 (1200mm) 81 27 FL D 2,177
L2-C16-C04 D2 36 54 LED D 1,944
L2-C16-C05 L18 (per m) 89 28 LED D 2,489
L2-C16-C06 L18 (per m) 4 28 LED D 112
L2-C16-C07 D12 4 11 LED D 44

Total 7,312

Area GN-C17
Floor level
L2-C17-F01 U3 7 15 LED D 105
L2-C17-F05 S4 2 25 LED D 50
Total 155

Ceiling level
L2-C17-C01 L2c (per m) 24 15 LED D 360
L2-C17-C02 D1c 4 47 LED D 186

Total 546
L2.0 Concourse D
Area CD
Floor level
L2-CD-F01 L3 (per m) 534 15 LED D 8,010
L2-CD-F02 L7 (per m) 78 30 LED D 2,331
L2-CD-F06 S4 30 25 LED D 750
L2-CD-F07 XT3 8 24 CFL D 192

Total 11,283
Ceiling level
L2-CD-C01 L2b (per m) 656 25 LED D 16,400
L2-CD-C02 L2b (per m) 442 25 LED D 11,050
L2-CD-C06 L18 (per m) 171 28 LED D 4,788
L2-CD-C07 L5 (1200mm) 940 106 FL D 100,093
L2-CD-C09 L18b (per m) 1128 28 LED D 31,584
L2-CD-C10 L4 (1200mm) 9 23 27 FL D 247 618
L2-CD-C11 L18 (per m) 2 12 28 LED D 67 336
L2-CD-C12 L4 (1200mm) 13 25 27 FL D 349 682
L2-CD-C13 D12 5 7 11 LED D 55 77
L2-CD-C14 L4 (1200mm) 9 24 27 FL D 249 638
L2-CD-C14b D12 2 11 LED D 22
L2-CD-C15 L18 (per m) 2 13 28 LED D 56 372
L2-CD-C16 L4 (1200mm) 16 15 27 FL D 423 403
L2-CD-C17 D12 3 6 11 LED D 33 66

Total 165,394 167,129


Area GN-D2
Floor level
L2-D2-F01 U3 22 15 LED D 330
L2-D2-F03 L2c (per m) 52 15 LED D 780
L2-D2-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-D2-F05 S4 12 25 LED D 300

Total 1,962
Ceiling level
L2-D2-C01 L2c (per m) 23 15 LED D 345
Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 214 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
L2-D2-C02 D1c 4 47 LED D 186

Total 531

Area GN-D3
Floor level
L2-D3-F01 U3 22 15 LED D 330
L2-D3-F03 L2c (per m) 52 15 LED D 780
L2-D3-F05 S4 12 25 LED D 300

Total 1,410
Ceiling level
L2-D3-C01 L2c (per m) 23 15 LED D 345
L2-D3-C02 D1c 4 47 LED D 186
Total 531
Area GN-D4
Floor level
L2-D4-F01 U3 22 15 LED D 330
L2-D4-F03 L2c (per m) 52 15 LED D 780
L2-D4-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-D4-F05 S4 12 25 LED D 300

Total 1,962

Ceiling level
L2-D4-C01 L2c (per m) 23 15 LED D 345
L2-D4-C02 D1c 4 47 LED D 186

Total 531
Area GN-D5
Floor level
L2-D5-F01 U3 22 15 LED D 330
L2-D5-F03 L2c (per m) 52 15 LED D 780
L2-D5-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-D5-F05 S4 12 25 LED D 300

Total 1,962

Ceiling level
L2-D5-C01 L2c (per m) 23 15 LED D 345
L2-D5-C02 D1c 4 47 LED D 186

Total 531

Area GN-D6
Floor level
L2-D6-F01 U3 22 15 LED D 330
L2-D6-F03 L2c (per m) 52 15 LED D 780
L2-D6-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-D6-F05 S4 12 25 LED D 300

Total 1,962
Ceiling level
L2-D6-C01 L2c (per m) 23 15 LED D 345
L2-D6-C02 D1c 4 47 LED D 186

Total 531
Area GN-D7
Floor level
L2-D7-F01 U3 22 15 LED D 330
L2-D7-F03 L2c (per m) 52 15 LED D 780
L2-D7-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-D7-F05 S4 12 25 LED D 300

Total 1,962
Ceiling level
L2-D7-C01 L2c (per m) 23 15 LED D 345
L2-D7-C02 D1c 4 47 LED D 186

Total 531
Area GN-D8
Floor level
L2-D8-F01 U3 22 15 LED D 330
L2-D8-F03 L2c (per m) 52 15 LED D 780
L2-D8-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-D8-F05 S4 12 25 LED D 300

Total 1,962

Ceiling level
L2-D8-C01 L2c (per m) 23 15 LED D 345
L2-D8-C02 D1c 4 47 LED D 186

Total 531
Area GN-D9
Floor level
L2-D9-F01 U3 22 15 LED D 330
L2-D9-F03 L2c (per m) 52 15 LED D 780
L2-D9-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-D9-F05 S4 12 25 LED D 300
Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 215 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
Total 1,962
Ceiling level
L2-D9-C01 L2c (per m) 23 15 LED D 345
L2-D9-C02 D1c 4 47 LED D 186

Total 531
Area GN-D10
Floor level
L2-D10-F01 U3 22 15 LED D 330
L2-D10-F03 L2c (per m) 52 15 LED D 780
L2-D10-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-D10-F05 S4 12 25 LED D 300

Total 1,962
Ceiling level
L2-D10-C01 L2c (per m) 23 15 LED D 345
L2-D10-C02 D1c 4 47 LED D 186

Total 531
Area GN-D11
Floor level
L2-D11-F01 U3 22 15 LED D 330
L2-D11-F03 L2c (per m) 52 15 LED D 780
L2-D11-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-D11-F05 S4 12 25 LED D 300

Total 1,962
Ceiling level
L2-D11-C01 L2c (per m) 23 15 LED D 345
L2-D11-C02 D1c 4 47 LED D 186

Total 531

Area GN-D12
Floor level
L2-D12-F01 U3 22 15 LED D 330
L2-D12-F02 L2-D12-F03 L2c (per m) 52 15 LED D 780
L2-D12-F04 L17 (1200mm) 20 27 FL D 538
L17 (600mm) 1 14 FL D 14
L2-D12-F05 S4 12 25 LED D 300

Total 1,962

Ceiling level
L2-D12-C01 L2c (per m) 23 15 LED D 345
L2-D12-C02 D1c 7 47 LED D 326

Total 671
Area GN-D13 and Lounge
Floor level
L2-D13-F01 U3 44 15 LED D 660
L2-D13-F03 L2c (per m) 104 15 LED D 1,560
L2-D13-F04 L17 (1200mm) 40 27 FL D 1,075
L17 (600mm) 2 14 FL D 29
L2-D13-F05 S4 24 25 LED D 600

Total 3,924
Ceiling level
L2-D13-C01 L2c (per m) 23 15 LED D 345
L2-D13-C02 D1c 4 47 LED D 186

Total 531
Area GN-D14
Floor level
L2-D14-F01 U3 10 15 LED D 150
L2-D14-F04 L17 (1200mm) 2 27 FL D 54
L2-D14-F05 S4 5 25 LED D 125

Total 329
Ceiling level
L2-D14-C01 L2c (per m) 26 15 LED D 390
L2-D14-C02 D1c 4 47 LED D 186
L2-D14-C03 L18 (per m) 4 28 LED D 112
L2-D14-C04 D12 4 11 LED D 44

Total 732
Area GN-D15
Floor level
L2-D15-F01 U3 9 15 LED D 135
L2-D15-F04 L17 (1200mm) 2 27 FL D 54
L2-D15-F05 S4 5 25 LED D 125

Total 314
Ceiling level
L2-D15-C01 L2c (per m) 26 15 LED D 390
L2-D15-C02 D1c 4 47 LED D 186
L2-D15-C03 L18 (per m) 4 28 LED D 112
L2-D15-C04 D12 4 11 LED D 44

Total 732
Area GN-D16
Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 216 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
Floor level
L2-D16-F01 U3 15 15 LED D 225
L2-D16-F05 S4 5 25 LED D 125

Total 350
Ceiling level
L2-D16-C01 L2c (per m) 43 15 LED D 645
L2-D16-C02 D1c 7 47 LED D 326
L2-D16-C03 L18 (per m) 4 28 LED D 112
L2-D16-C04 D12 4 11 LED D 44

Total 1,127
Area GN-D17
Floor level
L2-D17-F01 U3 6 15 LED D 90
L2-D17-F05 S4 2 25 LED D 50

Total 140
Ceiling level
L2-D17-C01 L2c (per m) 41 15 LED D 615
L2-D17-C02 D1c 7 47 LED D 326

Total 941
Area GN-D18 - Lounge
Floor level
L2-D18-F01 U3 16 15 LED D 240
L2-D18-F04 L17 (1200mm) 3 27 FL D 81
L2-D18-F05 S4 5 25 LED D 125
L2-D18-C03 L18 (per m) 4 28 LED D 112
L2-D18-C04 D12 4 11 LED D 44

Total 602
L2.1
Hotel Perimeter
Floor Level
L2.1-PE-C01 L18b (per m) 584 28 LED D 16,338

Total 16,338
Hotel Interior Elevation
Floor Level
L2-PE-F97 L17 (1500mm) 30 35 FL D 1,037
L17 (1200mm) 21 27 FL D 564
L17 (900mm) 2 20 FL D 40

Total 1,641
Office Interior Elevation
Floor Level
L2-PE-F98 L17 (1500mm) 21 35 FL D 726
L17 (1200mm) 19 27 FL D 511
L17 (900mm) 9 20 FL D 180

Total 1,416
L3.0 Departures Entry
PROCESSOR ENTRY
Floor level
L3-PE-F01 U1c 556 100 LED D 55,600
L3-PE-F01 U1c 468 536 100 LED D 46,800 53,600
L3-PE-F02 U1c 35 100 LED D 3,500
L3-PE-F04 U1c 496 100 LED D 49,600
L3-PE-C05 L2p (per m) 2910 15 LED D 43,650

Total 199,150 150,350


Ceiling level
L3-PE-C01 L18 (per m) 200 34 28 LED D 5,600 960
L18b (per m) 185 28 LED D 5,180
L3-PE-C02 L18 (per m) 221 34 28 LED D 6,188 960
L18b (per m) 185 28 LED D 5,180
L3-PE-C03 D9 20 65 LED D 1,300
Total 23,448 13,581

PROCESSOR ENTRY / CHECK-IN CHANDELIERS


Floor level
L3-PE-F05 U1 300 100 LED D 30,000
L3-PE-F42 L2q (per m) 360 25 LED D 9,000
L3-PE-F43 S6 72 62 LED D 4,464

Total 43,464
CENTRAL AREA PAVILIONS
Floor level
L3-PE-F47 U3 U3b 42 15 LED D 630

Total 630
BRIDGE WALKWAY / WELLWISHERS F&B BALCONY
Floor level
L3-PE-F55 L7 (per m) 38 30 LED D 1,143
L3-PE-F56 L2m (per m) L2c (per m) 227 6 15 LED D 1,362 3,405
L3-PE-F102 XT4 8 216 CFL D 1,728

Total 3,090 6,276


L3.0 Departures Airside lounge
CONCOURSE A/B ENTRY

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 217 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
Floor level
L3-PA-F01 U1b 126 100 LED D 12,600
L3-PA-F83 S1b 42 25 LED D 1,050

Total 13,650
CENTRAL AREA CHANDELIERS
Floor level
L3-PA-F11 U1 480 100 LED D 48,000
L3-PA-F84 L2q (per m) 350 25 LED D 8,750
L3-PA-F85 S6 96 80 62 LED D 5,952 4,960
L3-PA-F109 L2q (per m) 70 25 LED D 1,750
L3-PA-F110 S6 16 62 LED D 992
Total 65,444 64,452
TRANSIT AREA SECURITY
Floor level
L3-PA-F77 D1 28 19 LED D 532
L3-PA-F78 L7 (per m) 600 473 30 LED D 18,000 14,190
L3-PA-F79 D1 30 19 LED D 570
Total 18,000 15,292
Ceiling level
L3-PA-C01 L18 (per m) 158 153 28 LED D 4,424 4,281
L2b (per m) 214 25 LED D 5,350
L3-PA-C02 L18 (per m) 145 28 LED D 4,060
L2b (per m) 145 397 25 LED D 3,625 9,913
L3-PA-C03 D1 144 19 LED D 2,736
L3-PA-C04 L4 (1200mm) 189 27 FL D 5,090
L3-PA-C05 D1 8 19 LED D 152
L3-PA-C06 L4 (1200mm) 16 27 FL D 430
L3-PA-C07 D12 2 11 LED D 22
L3-PA-C08 L18 (per m) 3 28 LED D 84
L3-PA-C09 D12 2 11 LED D 22
L3-PA-C10 L18 (per m) 3 28 LED D 81
L3-PA-C11 D12 2 11 LED D 22
L3-PA-C12 L18 (per m) 4 28 LED D 101
L3-PA-C13 D12 3 11 LED D 33
L3-PA-C14 L18 (per m) 4 28 LED D 101
L3-PA-C15 D12 2 11 LED D 22
L3-PA-C16 L18 (per m) 3 28 LED D 76
L3-PA-C17 L18 (per m) 14 28 LED D 378
D1 2 19 LED D 38
L3-PA-C18 L4 (1200mm) 51 27 FL D 1,371
L3-PA-C21 D12 2 11 LED D 22
L3-PA-C22 L18 (per m) 3 28 LED D 76
L3-PA-C23 D12 2 11 LED D 22
L3-PA-C24 L18 (per m) 3 28 LED D 90
L3-PA-C25 D12 2 11 LED D 22
L3-PA-C26 L18 (per m) 2 28 LED D 62
L3-PA-C27 D12 21 17 11 LED D 231 187
D12b 9 1 LED D 9
L3-PA-C28 L18 (per m) 54 47 28 LED D 1,512 1,316
L3-PA-C29 D12 18 15 11 LED D 198 165
D12b 8 1 LED D 8
L3-PA-C30 L18 (per m) 52 44 28 LED D 1,456 1,238
L3-PA-C30b D1 2 1 19 LED D 38 19
L3-PA-C31 D12 15 2 11 LED D 165 22
D12b 8 1 LED D 8
L3-PA-C32 L18 (per m) 40 3 28 LED D 1,120 78
L3-PA-C33 D12 16 2 11 LED D 176 22
D12b 8 1 LED D 8
L3-PA-C34 L18 (per m) 36 3 28 LED D 1,008 76
L3-PA-C34b D6 1 2 19 LED D 19 38
L3-PA-C35 L18 (per m) 45 39 28 LED D 1,260 1,100
L3-PA-C35b D12 16 13 11 LED D 176 143
D12b 7 8 1 LED D 7 8
L3-PA-C36 L18 (per m) 43 37 28 LED D 1,204 1,025
L3-PA-C36b D12 12 14 11 LED D 132 154
D12b 8 1 LED D 8
L3-PA-C37 D1 1 19 LED D 19
L4 (900mm) 58 20 FL D 1,157
L18 (per m) 13 28 LED D 364
L3-PA-C38 D12 32 12 11 LED D 352 132
D12b 15 7 1 LED D 15 7
L3-PA-C39 L18 (per m) 69 47 28 LED D 1,932 1,310
L3-PA-C39b D1 2 1 19 LED D 38 19
L3-PA-C40 D12 24 2 11 LED D 264 22
D12b 11 1 LED D 11
L3-PA-C41 L18 (per m) 53 3 28 LED D 1,484 78
L3-PA-C42 D12 18 8 11 LED D 198 88
D12b 9 8 1 LED D 9 8
L3-PA-C43 L18 (per m) 42 40 28 LED D 1,176 1,106
L3-PA-C43b D1 D12 3 19 11 LED D 57 33
L3-PA-C44 D12 20 2 11 LED D 220 22
D12b 8 1 LED D 8
L3-PA-C45 L18 (per m) 37 2 28 LED D 1,036 56
L3-PA-C46 D12 11 11 LED D 121
D12b 9 1 LED D 9
L3-PA-C46b D1 2 19 LED D 38
L3-PA-C47 L18 (per m) 37 28 LED D 1,042

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 218 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
L3-PA-C48 D12 2 11 LED D 22
L3-PA-C49 L18 (per m) 3 28 LED D 70
L3-PA-C50 D12 2 11 LED D 22
L3-PA-C51 L18 (per m) 1 28 LED D 39
L3-PA-C52 D12 13 11 LED D 143
D12b 8 1 LED D 8
L3-PA-C52b D1 1 19 LED D 19
L3-PA-C53 L18 (per m) 47 28 LED D 1,316
L3-PA-C54 D1 2 19 LED D 38
L3-PA-C55 D12 2 11 LED D 22
L3-PA-C56 L18 (per m) 2 28 LED D 62
L3-PA-C57 D12 2 11 LED D 22
L3-PA-C58 L18 (per m) 2 28 LED D 56
L3-PA-C59 D12 8 11 LED D 88
D12b 5 1 LED D 5
D1 3 19 LED D 57
L3-PA-C59b D1 1 19 LED D 19
L3-PA-C60 L18 (per m) 26 28 LED D 739
L3-PA-C61 D12 6 11 LED D 66
D12b 6 1 LED D 6
D1 1 19 LED D 19
L3-PA-C62 L18 (per m) 29 28 LED D 815
L3-PA-C63 D1 1 19 LED D 19
L3-PA-C64 D12 9 11 LED D 99
D12b 6 1 LED D 6
D1 3 19 LED D 57
L3-PA-C65 L18 (per m) 31 28 LED D 854
L3-PA-C66 D1 3 19 LED D 57
L3-PA-C67 L18 (per m) 2 28 LED D 56
L3-PA-C68 D12 2 11 LED D 22
L3-PA-C69 L18 (per m) 6 28 LED D 179
L3-PA-C70 D1 2 19 LED D 46
L3-PA-C71 L18 (per m) 2 28 LED D 67
L3-PA-C72 D12 2 11 LED D 22
L3-PA-C73 L18 (per m) 18 28 LED D 507
L3-PA-C74 L18 (per m) 16 28 LED D 454
L3-PA-C75 D12 6 11 LED D 66
D12b 2 1 LED D 2
L3-PA-C76 L18 (per m) 19 28 LED D 524
L3-PA-C77 D12 4 11 LED D 44
D12b 4 1 LED D 4
L3-PA-C78 L18 (per m) 14 28 LED D 402
L3-PA-C79 D12 4 11 LED D 44
D12b 2 1 LED D 2
L3-PA-C80 D1 2 19 LED D 38
L3-PA-C81 D12 13 11 LED D 143
D12b 10 1 LED D 10
D1 3 19 LED D 57
L3-PA-C81b D1 1 19 LED D 19
L3-PA-C82 L18 (per m) 44 28 LED D 1,224
L3-PA-C83 D12 2 11 LED D 22
L3-PA-C84 L18 (per m) 3 28 LED D 81
L3-PA-C86 D12 2 11 LED D 22
L3-PA-C86b D1 1 19 LED D 19
L3-PA-C87 L18 (per m) 3 28 LED D 77

Total 34,542 43,867


L3.0 Concourse A
Area CA
Ceiling Level
L3-CA-C01 L18 (per m) 18 28 LED D 504
L3-CA-C02 D12 3 11 LED D 33
D12b 2 1 LED D 2
L3-CA-C03 D1 1 19 LED D 19
L3-CA-C04 D12 2 11 LED D 22
L3-CA-C05 L18 (per m) 3 28 LED D 90
L3-CA-C06 L18 (per m) 22 28 LED D 616
L3-CA-C07 D12 4 11 LED D 44
D12b 2 1 LED D 2

Totals 1,242 1,332


Area GN-A9
Ceiling Level
L3-A9-C01 U1c 36 100 LED D 3,600

Totals 3,600
L3.0 Concourse B
Ceiling level
L3-CB-C01 L18 (per m) 18 28 LED D 504
L3-CB-C02 D12 3 11 LED D 33
D12b 2 1 LED D 2
L3-CB-C03 D1 1 19 LED D 19
L3-CB-C04 D12 2 11 LED D 22
L3-CB-C05 L18 (per m) 4 28 LED D 101
L3-CB-C06 L18 (per m) 16 28 LED D 448
L3-CB-C07 D12 4 11 LED D 44
D12b 2 1 LED D 2
L3-CB-C08 L18 (per m) 6 28 LED D 157

Totals 1,175 1,332


Area GN-B6
Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 219 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
Ceiling Level
L3-B6-C01 U1c 36 100 LED D 3,600

Totals 3,600
L3.0 Concourse C
L3-CC-C03 L4 (900mm) L4 (1200mm) 78 20 27 FL D 1,560 2,101
L3-CC-C04 L18 (per m) L4 (1200mm) 69 57 28 27 LED FL D 1,932 1,532
L3-CC-C05 D6 26 19 LED D 494
L3-CC-C06 L18 (per m) 2 28 LED D 50
L3-CC-C07 D12 2 11 LED D 22
L3-CC-C08 L18 (per m) 2 28 LED D 50
L3-CC-C09 D12 2 11 LED D 22
L3-CC-C10 L18 (per m) 21 28 LED D 588
L3-CC-C11 D12 7 11 LED D 77
D12b 3 1 LED D 3
L3-CC-C12 L18 (per m) 28 28 LED D 784
L3-CC-C13 D12 5 11 LED D 55
D12b 4 1 LED D 4
L3-CC-C14 D1 2 19 LED D 38

Totals 5,680 5,783


L3.0 Concourse D
Ceiling Level
L3-CD-C12 L4 (900mm) L4 (1200mm) 79 20 27 FL D 1,578 2,126
L3-CD-C13 L18 (per m) L4 (1200mm) 69 50 28 27 LED FL D 1,932 1,344
L3-CD-C14 D6 26 19 D 494
L3-CD-C15 L18 (per m) 2 28 LED D 56
L3-CD-D16 D12 2 11 LED D 22
L3-CD-C17 L18 (per m) 2 28 LED D 56
L3-CD-C18 D12 2 11 LED D 22
L2-CD-C19 L18 (per m) 23 28 LED D 644
L3-CD-C20 D12 7 11 LED D 77
D12b 3 1 LED D 3
L3-CD-C21 L18 (per m) 27 28 LED D 756
L30CD-C22 L3-CD-C22 D12 5 11 LED D 55
D12b 4 1 LED D 4

Totals 5,699 5,658


GARDEN/ MUSEUM/RETAIL CENTRAL AREA
Floor Level
L3-PA-F101 XT4 26 8 216 CFL D 5,616 1,728
L3-PA-F102 XT4 18 216 CFL D 3,888

Totals 5,616 5,616


L3.0 Concourse A
Area CA
Floor level
L3-CA-F01 L7 (per m) 1270 1133 30 LED D 38,100 33,990
L3-CA-F02 U3 48 15 LED D 720
L3-CA-F03 L3 (per m) 460 15 LED D 6,900
L3-CA-F04 L23 380 303 50 LED D 19,000 15,150
Total 64,720 56,760
Area GN-A1
Floor level
L3-A1-F01 L7 (per m) 440 30 LED D 13,200
Total 13,200
Area GN-A2
Floor level
L3-A2-F01 U1b 216 100 LED D 21,600
L3-A2-F06 S1b 60 25 LED D 1,500

Total 23,100
Area GN-A3
Floor level
L3-A3-F01 U1b 72 100 LED D 7,200
U1c 18 100 LED D 1,800
L3-A3-F06 S1b 24 25 LED D 600

Total 9,600

Area GN-A4
Floor level
L3-A4-F01 U1b 90 100 LED D 9,000
L3-A4-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-A5
Floor level
L3-A5-F01 U1b 72 100 LED D 7,200
U1c 18 100 LED D 1,800
L3-A5-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-A6
Floor level
L3-A6-F01 U1b 90 100 LED D 9,000
L3-A6-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-A7
Floor level
Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 220 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
L3-A7-F01 U1b 18 100 LED D 1,800
L3-A7-F06 S1b 6 25 LED D 150

Total 1,950
Area GN-A8
Floor level
L3-A8-F01 U1b 18 100 LED D 1,800
L3-A8-F06 S1b 6 25 LED D 150

Total 1,950
Area GN-A9
Floor level
L3-A9-F01 U1b 72 100 LED D 7,200
L3-A9-F06 S1b 24 25 LED D 600

Total 7,800
L3.0 Concourse B
Area CB
Floor level
L3-CB-F01 L7 (per m) 1065 1190 30 LED D 31,950 35,700
L3-CB-F02 U3 42 15 LED D 630
L3-CB-F03 L3 (per m) 321 15 LED D 4,815
L3-CA-F04 L3-CB-F04 L23 332 266 50 LED D 16,600 13,300
Total 53,995 54,445
Area GN-B1
Floor level
L3-B1-F01 U1b 162 100 LED D 16,200
L3-B1-F06 S1b 42 25 LED D 1,050

Total 17,250
Area GN-B2
Floor level
L3-B2-F01 U1b 72 100 LED D 7,200
U1c 18 100 LED D 1,800
L3-B2-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-B3
Floor level
L3-B3-F01 U1b 90 100 LED D 9,000
L3-B3-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-B4
Floor level
L3-B4-F01 U1b 72 100 LED D 7,200
U1c 18 100 LED D 1,800
L3-B4-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-B5
Floor level
L3-B5-F01 U1b 90 100 LED D 9,000
L3-B5-F06 S1b 24 25 LED D 600

Total 9,600

Area GN-B6
Floor level
L3-B6-F01 U1b 108 100 LED D 10,800
L3-B6-F06 S1b 36 25 LED D 900

Total 11,700
L3.0 Concourse C
Area CC
Floor level
L3-CC-F01 L7 (per m) 1510 1700 30 LED D 45,300 51,000
L3-CC-F02 L3 (per m) 1032 15 LED D 15,480
L3-CC-F03 U1c 74 100 LED D 7,400
L3-CC-F04 L7 (per m) 295 30 LED D 8,850
Total 77,030 73,880
Area GN-C2
Floor level
L3-C2-F01 U1b 108 100 LED D 10,800
L3-C2-F06 S1b 30 25 LED D 750

Total 11,550
Area GN-C4
Floor level
L3-C4-F01 U1b 90 100 LED D 9,000
L3-C4-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-C5
Floor level
L3-C5-F01 U1b 90 100 LED D 9,000
L3-C5-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-C6
Floor level
L3-C6-F01 U1b 72 100 LED D 7,200
Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 221 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
U1c 18 100 LED D 1,800
L3-C6-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-C7
Floor level
L3-C7-F01 U1b 72 100 LED D 7,200
U1c 18 100 LED D 1,800
L3-C7-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-C8
Floor level
L3-C8-F01 U1b 90 100 LED D 9,000
L3-C8-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-C9
Floor level
L3-C9-F01 U1b 90 100 LED D 9,000
L3-C9-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-C10
Floor level
L3-C10-F01 U1b 180 100 LED D 18,000
L3-C10-F06 S1b 48 25 LED D 1,200
Total 19,200
Area GN-C11
Floor level
L3-C11-F01 U1b 90 100 LED D 9,000
L3-C11-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-C12
Floor level
L3-C12-F01 U1b 36 100 LED D 3,600
L3-C12-F03 L17 (1200mm) 2 27 FL D 54
L3-C12-F06 S1b 12 25 LED D 300
L3-C12-F09 S4 24 25 LED D 600

Total 4,554
Ceiling level
L3-C12-F10 D12 4 11 LED D 44
L3-C12-F11 L18 (per m) 4 28 LED D 112

Total 156
Area GN-C13
Floor level
L3-C13-F01 U1b 90 100 LED D 9,000
L3-C13-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-C14
Floor level
L3-C14-F01 U1b 36 100 LED D 3,600
L3-C14-F06 S1b 12 25 LED D 300

Total 3,900
Area GN-C15
Floor level
L3-C15-F01 U1b 36 100 LED D 3,600
L3-C15-F03 L17 (1200mm) 2 27 FL D 59
L3-C15-F06 S1b 12 25 LED D 300
L3-C15-F09 S4 24 25 LED D 600

Total 4,559
Ceiling level
L3-C15-F10 D12 4 11 LED D 44
L3-C15-F11 L18 (per m) 4 28 LED D 112

Total 156
Area GN-C16
Floor level
L3-C16-F01 U1b 36 100 LED D 3,600
L3-C16-F03 L17 (1200mm) 2 27 FL D 59
L3-C16-F06 S1b 12 25 LED D 300
L3-C16-F09 S4 24 25 LED D 600

Total 4,559
Ceiling level
L3-C16-F10 D12 4 11 LED D 44
L3-C16-F11 L18 (per m) 4 28 LED D 112

Total 156
Area GN-C17
Floor level
L3-C17-F01 U1b 18 100 LED D 1,800
L3-C17-F06 S1b 12 25 LED D 300
Total 2,100
L3.0 Concourse D
Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 222 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
Area CD
Floor level
L3-CD-F01 L7 (per m) 2065 30 LED D 61,950
L3-CD-F02 L3 (per m) 1246 15 LED D 18,690
L3-CD-F03 U1c 75 100 LED D 7,500

Total 88,140
Area GN-D2
Floor level
L3-D2-F01 U1b 72 100 LED D 7,200
U1c 18 100 LED D 1,800
L3-D2-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-D3
Floor level
L3-D3-F01 U1b 90 100 LED D 9,000
L3-D3-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-D4
Floor level
L3-D4-F01 U1b 90 100 LED D 9,000
L3-D4-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-D5
Floor level
L3-D5-F01 U1b 72 100 LED D 7,200
U1c 18 100 LED D 1,800
L3-D5-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-D6
Floor level
L3-D6-F01 U1b 90 100 LED D 9,000
L3-D6-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-D7
Floor level
L3-D7-F01 U1b 90 100 LED D 9,000
L3-D7-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-D8
Floor level
L3-D8-F01 U1b 72 100 LED D 7,200
U1c 18 100 LED D 1,800
L3-D8-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-D9
Floor level
L3-D9-F01 U1b 90 100 LED D 9,000
L3-D9-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-D10
Floor level
L3-D10-F01 U1b 90 100 LED D 9,000
L3-D10-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-D11
Floor level
L3-D11-F01 U1b 72 100 LED D 7,200
U1c 18 100 LED D 1,800
L3-D11-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-D12
Floor level
L3-D12-F01 U1b 90 100 LED D 9,000
L3-D12-F06 S1b 24 25 LED D 600

Total 9,600
Area GN-D13
Floor level
L3-D13-F01 U1b 180 100 LED D 18,000
L3-D13-F06 S1b 48 25 LED D 1,200

Total 19,200
Area GN-D14
Floor level
L3-D14-F01 U1b 36 100 LED D 3,600
L3-D14-F06 S1b 12 25 LED D 300

Total 3,900
Area GN-D15
Floor level
L3-D15-F01 U1b 36 100 LED D 3,600
L3-D15-F06 S1b 12 25 LED D 300
Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 223 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
Total 3,900
Area GN-D16
Floor level
L3- D16-F01 U1b 36 100 LED D 3,600
L3-D16-F06 S1b 12 25 LED D 300

Total 3,900
Area GN-D17
Floor level
L3-D17-F01 U1b 18 100 LED D 1,800
L3-D17-F06 S1b 6 25 LED D 150

Total 1,950
Area GN-D18
Floor level
L3-D18-F01 U1b 36 100 LED D 3,600
L3-D18-F06 S1b 12 25 LED D 300

Total 3,900
L3.1 Level
Pavillion Roof
Floor Level
L3.1-PE-F01 U1c 556 100 LED D 55,600
Total 55,600
Hotel
Floor Level
L3.1-PE-F06 L16 (per m) 253 36 LED D 9,097

Total 9,097
Office
Floor Level
L3.1-PE-F07 L16 (per m) 238 36 LED D 8,585

Total 8,585
CENTRAL AREA CHANDELIERS
Floor level
L3.1-PA-F01 U1c 564 100 LED D 56,400

Total 56,400
Level 3.2
Hotel
Floor Level
L3.2-PE-F02 L16 (per m) 243 36 LED D 8,748

Total 8,748
Office
Floor Level
L3.2-PE-F01 L16 (per m) 259 36 LED D 9,310

Total 9,310
Level 3.3
Hotel
Floor Level
L3.3-PE-F01 L3.3-PE-F02 L16 (per m) 149 36 LED D 5,360

Total 5,360
Office
Floor Level
L3.3-PE-F01 L16 (per m) 112 36 LED D 4,044

Total 4,044
Level 3.4
Hotel
Floor level
L3.4-PE-F01 U1c 41 100 LED D 4,100

Total 4,100
Office
Floor level
L3.4-PE-F05 U1c 41 100 LED D 4,100

Total 4,100
Level 4.0
Transit roof 1
Ceiling Level
L4.0-PA-C03 L15 (1200mm) 536 54 FL D 29,182
L15 (900mm) 4 39 FL D 154
L15 (600mm) 8 21 FL D 169
L4.0-PA-C04 L15 (1200mm) 536 54 FL D 29,182
L15 (900mm) 4 39 FL D 154
L15 (600mm) 8 21 FL D 169
L4.0-PA-C08 D9b 592 80 LED D 47,360
L4.0-PA-C09 D9b 90 81 80 LED D 7,200 6,480
Total 113,570 112,850
Transit roof 2
Ceiling Level
L4.0-PA-C01 L15 (1200mm) 713 54 FL D 38,819
L15 (900mm) 7 39 FL D 270
L15 (600mm) 7 21 FL D 148
L4.0-PA-C02 L15 (1200mm) 713 54 FL D 38,819
Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 224 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
L15 (900mm) 7 39 FL D 270
L15 (600mm) 7 21 FL D 148
L4.0-PA-C05 D9b 550 80 LED D 44,000
L4.0-PA-C06 D9b 84 80 LED D 6,720

Total 129,193
Main Roof Processor Entry
Ceiling Level
L4.0-PE-C01 D8e 240 100 LED D 24,000
L4.0-PE-C02 D8e 160 100 LED D 16,000
L4.0-PE-C03 D8f 20 100 LED D 2,000
L4.0-PE-C04 D8g 20 100 LED D 2,000
Total 44,000

Main Roof Central Area


Ceiling Level
L4.0-PA-C01 D8e 276 100 LED D 27,600

Total 27,600
L4.0-PE-C02 D8e 160 100 LED D 16,000
L4.0-PE-C03 D8f 20 100 LED D 2,000
L4.0-PE-C04 D8g 20 100 LED D 2,000
Total 75,200
Main Roof Central Area
Ceiling Level
L4.0-PA-C01 D8e 276 100 LED D 27,600

Total 27,600
GATEHOUSES TYPICAL
Code E Departures Level
Floor level
DL-GN-F01 L2o (per m) 12 12 LED D 144
DL-GN-F02 L2b (per m) 20 25 LED D 500

Total 644
Ceiling level
DL-GN-C01 DL-GN-C03 D1 D1c 9 15 19 47 LED D 171 698
DL-GN-C02 DL-GN-C04 L2c (per m) 49 82 15 LED D 732 1,230
DL-GN-C04 DL-GN-C07 D1 13 19 LED D 247
DL-GN-C05 DL-GN-C02 L18 (per m) 7 10 28 LED D 196 286
DL-GN-C06 DL-GN-C05 D1 3 19 LED D 57
DL-GN-C07 DL-GN-C06 L2c (per m) 12 15 LED D 180
DL-GN-C08 U11 3 150 MH S 450

Total 1,583 3,147


Code E Arrivals Level
Ceiling level
AL-GN-C01 D1c 9 14 47 LED D 419 651
D1d 25 11 47 LED D 1,163 512
D1e 6 20 47 LED D 279 930
AL-GN-C02 L2c (per m) 52 83 15 LED D 777 1,245
AL-GN-C03 L18 (per m) 16 28 LED D 454
AL-GN-C04 AL-GN-C05 L2c (per m) 55 15 LED D 823
AL-GN-C06 L2c (per m) 39 15 LED D 578
AL-GN-C07 AL-GN-C04 L2c (per m) 70 72 15 LED D 1,050 1,074

Total 5,541 6,265

Code E Typical Total 7,768 10,056

Code F Departures Level


Floor level
DL-GN-F01 L2o (per m) 13 12 LED D 156
DL-GN-F02 L2b (per m) 19 25 LED D 475
Total 631
Ceiling level
DL-GN-C01 L2c (per m) 18 15 LED D 270
DL-GN-C02 L18 (per m) 12 28 LED D 330
L18f (per m) 16 26 LED D 416
DL-GN-C03 D1c 9 47 LED D 419
DL-GN-C04 L2c (per m) 45 15 LED D 681
DL-GN-C05 D1 3 19 LED D 57
DL-GN-C06 L2c (per m) 16 15 LED D 240
DL-GN-C07 D1 22 19 LED D 418
DL-GN-C08 U11 3 150 MH S 450

Total 2,413 3,281


Code F Priority Boarding Level
Ceiling level
PL-GN-C02 D1 35 13 19 LED D 665 247
Total 665 247

Code F Arrivals Level


Ceiling level
AL-GN-C01 D1c 8 47 LED D 372
D1d 27 47 LED D 1,256
D1e 6 47 LED D 279
AL-GN-C02 L2c (per m) 44 15 LED D 663

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 225 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
AL-GN-C03 L18 (per m) 16 28 LED D 454
AL-GN-C04 L2c (per m) 68 15 LED D 1,020
AL-GN-C05 L2c (per m) 62 15 LED D 933
AL-GN-C06 L2c (per m) 45 15 LED D 675
Total 5,651

Code F Typical Total 9,360 9,810

GATEHOUSES +13m
Code E Departures Level
Floor level
DL-GN-F01 L2o (per m) 12 12 LED D 144
DL-GN-F02 L2b (per m) 20 25 LED D 500

Total 644
Ceiling level
DL-GN-C01 DL-GN-C03 D1 D1c 11 14 19 47 LED D 209 651
DL-GN-C02 DL-GN-C04 L2c (per m) 75 15 LED D 1,121
DL-GN-C04 DL-GN-C07 D1 13 19 LED D 247
DL-GN-C05 DL-GN-C02 L18 (per m) 7 10 28 LED D 196 286
DL-GN-C06 DL-GN-C05 D1 3 19 LED D 57
DL-GN-C07 DL-GN-C06 L2c (per m) 12 15 LED D 180
DL-GN-C08 U11 3 150 MH S 450
Total 2,010 2,991
Code E Arrivals Level
Ceiling level
AL-GN-C01 D1c 9 13 47 LED D 419 605
D1d 25 11 47 LED D 1,163 512
D1e 6 20 47 LED D 279 930
AL-GN-C02 L2c (per m) 75 15 LED D 1,121
AL-GN-C03 L18 (per m) 16 28 LED D 454
AL-GN-C04 AL-GN-C05 L2c (per m) 55 15 LED D 823
AL-GN-C06 L2c (per m) 39 15 LED D 578
AL-GN-C07 AL-GN-C04 L2c (per m) 94 15 LED D 1,410
Total 6,244 6,430

Code E +13 Total 8,898 10,065

Code F Departures Level


Floor level
DL-GN-F01 L2o (per m) 13 12 LED D 156
DL-GN-F02 L2b (per m) 19 25 LED D 475
Total 631
Ceiling level
DL-GN-C01 L2c (per m) 18 15 LED D 270
DL-GN-C02 L18 (per m) 12 28 LED D 330
L18f (per m) 16 26 LED D 416
DL-GN-C03 D1c 13 46.5 LED D 605
DL-GN-C04 L2c (per m) 74 15 LED D 1,116
DL-GN-C05 D1 3 19 LED D 57
DL-GN-C06 L2c (per m) 16 15 LED D 240
DL-GN-C07 D1 22 19 LED D 418
DL-GN-C08 U11 3 150 MH S 450

Total 3,034 3,902


Code F Priority Boarding Level
Ceiling level
PL-GN-C02 D1 35 13 19 LED D 665 247
Total 665 247
Code F Arrivals Level
Ceiling level
AL-GN-C01 D1c 12 46.5 LED D 558
D1d 27 46.5 LED D 1,256
D1e 6 46.5 LED D 279
AL-GN-C02 L2c (per m) 70 15 LED D 1,050
AL-GN-C03 L18 (per m) 16 28 LED D 454
AL-GN-C04 L2c (per m) 94 15 LED D 1,410
AL-GN-C05 L2c (per m) 62 15 LED D 933
AL-GN-C06 L2c (per m) 45 15 LED D 675
Total 6,614

Code F +13 Total 10,944 11,394

GATEHOUSES +17m
Code E Departures Level
Floor level
DL-GN-F01 L2o (per m) 12 12 LED D 144
DL-GN-F02 L2b (per m) 20 25 LED D 500
Total 644
Ceiling level
DL-GN-C01 DL-GN-C03 D1 D1c 15 19 47 LED D 285 698
DL-GN-C02 DL-GN-C04 L2c (per m) 83 15 LED D 1,245
DL-GN-C04 DL-GN-C07 D1 13 19 LED D 247
DL-GN-C05 DL-GN-C02 L18 (per m) 7 10 28 LED D 196 286
DL-GN-C06 DL-GN-C05 D1 3 19 LED D 57
Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 226 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
DL-GN-C07 DL-GN-C06 L2c (per m) 12 15 LED D 180
DL-GN-C08 U11 3 150 MH S 450
Total 2,210 3,162
Code E Arrivals Level
Ceiling level
AL-GN-C01 D1c 14 47 LED D 651
D1d 25 11 47 LED D 1,163 512
D1e 6 20 47 LED D 279 930
AL-GN-C02 L2c (per m) 83 15 LED D 1,245
AL-GN-C03 L18 (per m) 16 28 LED D 454
AL-GN-C04 AL-GN-C05 L2c (per m) 55 15 LED D 823
AL-GN-C06 L2c (per m) 39 15 LED D 578
AL-GN-C07 AL-GN-C04 L2c (per m) 100 15 LED D 1,500
Total 6,691 6,691

Code E +17 Total 9,545 10,497

Code E & F Total Gatehouses


Concourse A
GN-A1 Code F +13m Total 10,944 11,394
GN-A2 Code E Total 7,768 10,056
GN-A3 Code E Total 7,768 10,056
GN-A4 Code E Total 7,768 10,056
GN-A5 Code E Total 7,768 10,056
GN-A6 Code E Total 7,768 10,056
GN-A7 Code E Total 7,768 10,056
GN-A8 Code E Total 7,768 10,056
GN-A9 Code E Total 7,768 10,056
Total 73,087 91,846
Concourse B
GN-B1 Code F Total 9,360 9,810
GN-B2 Code E Total 7,768 10,056
GN-B3 Code E Total 7,768 10,056
GN-B4 Code E Total 7,768 10,056
GN-B5 Code E Total 7,768 10,056
GN-B6 Code E Total 7,768 10,056
GN-B7 Code E Total 7,768 10,056
Total 55,967 70,149
Concourse C
GN-C1 Code F Total 9,360 9,810
GN-C3 Code F Total 9,360 9,810
GN-C4 Code E Total 7,768 10,056
GN-C5 Code E Total 7,768 10,056
GN-C6 Code E Total 7,768 10,056
GN-C7 Code E Total 7,768 10,056
GN-C8 Code F Total 9,360 9,810
GN-C9 Code F +13m Total 10,944 11,394
GN-C10 Code E Total 7,768 10,056
GN-C11 Code F Total 9,360 9,810
GN-C12 Code E Total 7,768 10,056
GN-C13 Code E Total 7,768 10,056
GN-C14 Code E Total 9,360 10,056
GN-C15 Code E Total 9,360 10,056
GN-C16 Code E Total 7,768 10,056
GN-C17 Code E Total 10,056
Total 129,247 161,255
Concourse D
GN-D2 Code F Total 9,360 9,810
GN-D3 Code E Total 7,768 10,056
GN-D4 Code E Total 7,768 10,056
GN-D5 Code E Total 7,768 10,056
GN-D6 Code E Total 7,768 10,056
GN-D7 Code E Total 7,768 10,056
GN-D8 Code E +13m Total 8,898 10,065
GN-D9 Code E +17m Total 9,545 10,497
GN-D10 Code E Total 7,768 10,056
GN-D11 Code E +13m Total 8,898 10,065
GN-D12 Code E Total 7,768 10,056
GN-D13 Code E Total 7,768 10,056
GN-D14 Code E Total 7,768 10,056
GN-D15 Code E Total 7,768 10,056
GN-D16 Code E Total 7,768 10,056
GN-D17 Code E Total 9,360 10,056
GN-D18 Code E Total 9,360 10,056
Total 140,867 171,172

Code E and F Total 399,168 494,421

LX.0 Typical Pavillion


Male Toilet
Ceiling level
L2-TL-C01 D1 6 19 LED D 114
L2-TL-C02 D12 14 11 LED D 154
D12b 6 1 LED D 6
L2-TL-C03 L18 (per m) 35 28 LED D 974

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 227 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
Male Toilet Total 1,248
Female Toilet
Ceiling level
L2-TL-C04 D1 6 19 LED D 114
L2-TL-C05 D12 17 11 LED D 187
D12b 6 1 LED D 6
L2-TL-C06 L18 (per m) 33 28 LED D 924

Female Toilet Total 1,231


Unisex Toilet
Ceiling level
L2-TL-C07 D1 6 19 LED D 114
L2-TL-C08 D12 12 11 LED D 132
D12b 6 1 LED D 6
L2-TL-C09 L18 (per m) 30 28 LED D 834
L2-TL-C10 D1 2 19 LED D 38

Unisex Toilet Total 1,124


Lounge
Ceiling level
L2-TL-C11 D1 6 19 LED D 114
L2-TL-C12 D12 10 11 LED D 110
D12b 6 1 LED D 6
L2-TL-C13 L18 (per m) 30 28 LED D 840
L2-TL-C14 D1 2 19 LED D 38

Lounge Total 1,108


F&B
Ceiling level
L2-TL-C15 D1 6 19 LED D 114
L2-TL-C16 D12 4 11 LED D 44
L2-TL-C17 L18 (per m) 4 28 LED D 101
L2-TL-C18 D1 9 19 LED D 171
L2-TL-C19 D12 4 11 LED D 44
L2-TL-C20 L18 (per m) 4 28 LED D 101

F&B Total 575

Male Toilet
Ceiling level
L3-TL-C01 D1 3 19 LED D 57
L3-TL-C02 D12 15 11 LED D 165
D12b 8 1 LED D 8
L3-TL-C03 L18 (per m) 42 28 LED D 1,173

Male Toilet Total 1,403


Female Toilet
Ceiling level
L3-TL-C04 D1 3 19 LED D 57
L3-TL-C05 D12 18 11 LED D 198
D12b 8 1 LED D 8
L3-TL-C06 L18 (per m) 41 28 LED D 1,142

Female Toilet Total 1,405

Unisex Toilet
Ceiling level
L3-TL-C07 D1 6 19 LED D 114
L3-TL-C08 D12 13 11 LED D 143
D12b 6 1 LED D 6
L3-TL-C09 L18 (per m) 35 28 LED D 977
L3-TL-C10 D6 2 19 LED D 38
D1 1 19 LED D 19

Unisex Toilet Total 1,297


Total Pavillions
Concourse A (Level 2)
Area GN-A1 F&B Total 575
Area GN-A2 Unisex Toilet Total 0 1,124
Area GN-A2 F&B Total 575
Area GN-A3 Unisex Toilet Total 0 1,124
Area GN-A4 Unisex Toilet Total 0 1,124
Area GN-A5 F&B Total 575
Area GN-A6 Unisex Toilet Total 0 1,124
Concourse A (L2) Total 1,724 6,221
Concourse B (Level 2)
Area GN-B1 Unisex Toilet Total 0 1,124
Area GN-B1 F&B Total 575
Area GN-B2 Unisex Toilet Total 0 1,124
Area GN-B3 Unisex Toilet Total 0 1,124
Area GN-B4 F&B Total 575
Area GN-B5 Unisex Toilet Total 0 1,124
Concourse B (L2) Total 1,149 5,647
Concourse C (Level 2)
Area GN-C2 F&B Total 575
Area GN-C3 F&B Total 575
Area GN-C4 Female Toilet Total 1,231
Area GN-C5 Male Toilet Total 0 1,248
Area GN-C6 F&B Total 575
Area GN-C7 F&B Total 575
Area GN-C8 Female Toilet Total 1,231
Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 228 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
Area GN-C9 Male Toilet Total 0 1,248
Area GN-C10 Female Toilet Total 1,231
Area GN-C10 Lounge Total 0 1,248
Area GN-C11 F&B Total 575
Area GN-C13 Male Toilet Total 0 1,248
Concourse C (L2) Total 6,566 11,560
Concourse D (Level 2)
Area GN-D2 Female Toilet Total 1,231
Area GN-D3 F&B Total 575
Area GN-D4 F&B Total 575
Area GN-D5 Male Toilet Total 0 1,248
Area GN-D6 Female Toilet Total 1,231
Area GN-D7 F&B Total 575
Area GN-D8 F&B Total 575
Area GN-D9 Male Toilet Total 0 1,248
Area GN-D10 Lounge Total 0 1,248
Area GN-D11 F&B Total 575
Area GN-D12 Female Toilet Total 1,231
Area GN-D13 Male Toilet Total 0 1,248
Area GN-D13 Unisex Toilet Total 0 1,124
Concourse D (L2) Total 6,566 12,684
Concourse A (Level 3)
Area GN-A3 Unisex Toilet Total 1,297
Area GN-A5 Unisex Toilet Total 1,297

Concourse A (L3) Total 2,594


Concourse B (Level 3)
Area GN-B2 Unisex Toilet Total 1,297
Area GN-B4 Unisex Toilet Total 1,297

Concourse B (L3) Total 2,594


Concourse C (Level 3)
Area GN-C6 Male Toilet Total 0 1,403
Area GN-C7 Female Toilet Total 0 1,405
Concourse C (L3) Total 0 2,809
Concourse C (Level 3)
Area GN-D4 Female Toilet Total 0 1,405
Area GN-D7 Male Toilet Total 0 1,403
Area GN-D8 Female Toilet Total 0 1,405
Area GN-D11 Male Toilet Total 0 1,403
Concourse D (L3) Total 0 5,617

Pavilions Total 5,189 49,726

VERTICAL CIRCULATION
LIFTS AND ESCALATORS
Business Arrivals Area Elevations and Sections
L1-BG-F02 L3 (per m) 235 15 LED D 3,525
L1-BG-F03 L2b (per m) 161 25 LED D 4,028
L1-BG-F06 L13 (per m) 146 6 LED D 876

Total 8,429
Main Processor Glazed Passenger Lift ELV-05-09, 10, 11, 63
L2-PE-F79 L2b (per m) 82 25 LED D 2,050
L2c (per m) 22 15 LED D 330
L2-PE-F87 L17 (1200mm) 12 27 FL D 323
L2-PE-F88 L17 (1200mm) 12 27 FL D 323
L2-PE-F89 L17 (1200mm) 12 27 FL D 323
L2-PE-F90 L17 (1200mm) 12 27 FL D 323

Total 3,670
Main Processor Glazed Passenger Lift ELV-05-12, 13, 14, 15
L2-PE-F79 L2b (per m) 82 25 LED D 2,050
L2c (per m) 22 15 LED D 330
L2-PE-F87 L17 (1200mm) 12 27 FL D 323
L2-PE-F88 L17 (1200mm) 12 27 FL D 323
L2-PE-F89 L17 (1200mm) 12 27 FL D 323
L2-PE-F90 L17 (1200mm) 12 27 FL D 323

Total 3,670
Lower Main Processor ESC-05-21, STAIR-05-66, ESC-05-22
L0-2-AE-F09 L3 (per m) 96 15 LED D 1,440
L0-2-AE-F10 L13 (per m) 60 6 LED D 360
Total 1,800
Lower Main Processor ESC-05-23, STAIR-05-67, ESC-05-24
L0-2-AE-F09 L3 (per m) 96 15 LED D 1,440
L0-2-AE-F10 L13 (per m) 60 6 LED D 360
Total 1,800
Arrivals Feature Stairs
L0-2-AC-F16 D10 42 11 LED D 462
L0-2-AC-F17 W1 189 2 LED D 378

Total 840
Main Arrivals ESC-05-59,60, STAIR-05-AG-AH, ESC-05-03,04, ESC-05-05,06
L0-2-AL-F02 L13 (per m) 144 6 LED D 864
L0-2-AL-F04 L3 (per m) 284 15 LED D 4,260

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 229 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
L0-2-AL-F06 L2c (per m) 20 15 LED D 306
Total 5,430
ESC-01-07,08
L2-CB-C10 L3 (per m) 68 15 LED D 1,014
Total 1,014
ESC-01-09,10
L2-CA-C11 L3 (per m) 68 15 LED D 1,014
Total 1,014
Glazed Passenger Lifts ELV-05-72, 96
V7.021-F01 L2c (per m) 24 15 LED D 360
V7.021-F02 L17 (900mm) 4 20 FL D 80

Total 440
Glazed Passenger Lifts ELV-05-79, 97
V7.022-F01 L2c (per m) 24 15 LED D 360
V7.022-F02 L17 (900mm) 4 20 FL D 80

Total 440
Panoramic Passenger Lift ELV-05-66,67, 76,77, 111, 27, 28
V7.031-F01 L2c (per m) 48 15 LED D 720
L17 (600mm) 0 14 FL D 0
V7.031-F02 L17 (1200mm) 8 27 FL D 215
V7.031-F03 L17 (1200mm) 21 27 FL D 564
L17 (600mm) 2 14 FL D 29
Total 1,528
Esc-05 80/81, 86/87 stair-05-90,93
V7.024-F01 L3 (per m) 126 15 LED D 1,890
V7.024-F02 L13 (per m) 277 6 LED D 1,661

Total 3,551
Main Arrivals Glazed Tube ESC-05-39, STAIR-05-D, ESC-05-40
Arrivals Escalator and Stair
L3-PA-F22 L3 (per m) TBC 116 TBC 15 LED D TBC 1,734
L3-PA-F81 L2c (per m) TBC TBC LED D TBC
L3-PA-F19 L13 (per m) TBC 259 TBC 6 LED D TBC 1,554
L3-PA-F86 L6 (per m) TBC TBC LED D TBC

Total TBC 3,288


ESC-05-07,08 Business gates
V7-027-F01 L3 (per m) 58 15 LED D 870
V7-027-F02 L2c (per m) 23 15 LED D 345
Total 1,215
ESC-05-27,28 Business gates
V7-027-F03 L3 (per m) 58 15 LED D 870
V7-027-F04 L2c (per m) 23 15 LED D 345
Total 1,215
Vertical Circulation ESC-05-52 Food and beverage
V7-026-F01 L2c (per m) 42 15 LED D 630
V7-026-F02 L3 (per m) 27 15 LED D 405
Total 1,035
Vertical Circulation ESC-05-50 Food and beverage
V7-026-F01 L2c (per m) 42 15 LED D 630
V7-026-F02 L3 (per m) 27 15 LED D 405

Total 1,035
Vertical Circulation ESC-05-51, STAIR-05-AE Food and Beverage
V7-025-F01 L3 (per m) 36 15 LED D 540
V7-025-F02 L13 (per m) 40 6 LED D 240
V7-025-F03 L2c (per m) 27 15 LED D 405

Total 1,185
Vertical Circulation ESC-05-49, STAIR-05-AF Food and Beverage
V7-025-F04 L3 (per m) 36 15 LED D 540
V7-025-F05 L13 (per m) 40 6 LED D 240
V7-025-F06 L2c (per m) 27 15 LED D 405
Total 1,185
Vertical Circulation ESC-05-31,32 Hotel
V7-024-F01 L2c (per m) 28 15 LED D 420
V7-024-F02 L3 (per m) 95 15 LED D 1,425

Total 1,845
Vertical Circulation ESC-05-53,54,STAIR-05-AB,AN,ESC-05-67,68 Lounge
V7-028-F01 L3 (per m) 33 15 LED D 492
V7-028-F02 L13 (per m) 38 6 LED D 230
V7-028-F03 L3 (per m) 48 15 LED D 720
V7-028-F04 L13 (per m) 64 6 LED D 384
V7-029-F01 L3 (per m) 33 15 LED D 492
V7-029-F02 L13 (per m) 38 6 LED D 230
V7-029-F03 L3 (per m) 48 15 LED D 720
V7-029-F04 L13 (per m) 64 6 LED D 384

Total 3,653
Vertical Circulation Main Processor ESC-05-45, STAIR-16, STAIR-05-68, ESC-05-46
L2-PE-F80 L2c (per m) 45 15 LED D 675
L2-PE-F12 L3 (per m) 88 15 LED D 1,320
Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 230 of 231
Bulletin No. 145: Volume 3 of 4 (Rev 07) January 31, 2015
Abu Dhabi Airports Company PJSC Specification, Section 265120
L2-PE-F13 L13 (per m) 77 6 LED D 462

Total 2,457
Vertical Circulation Main Processor ESC-05-43, STAIR-05-16, ESC-05-44
L2-PE-F81 L2c (per m) 45 15 LED D 675
L2-PE-F15 L3 (per m) 88 15 LED D 1,320
L2-PE-F16 L13 (per m) 77 6 LED D 462
Total 2,457
Glazed passenger Lifts ELV-05-68
V7.016-F01 L17 (900mm) 1 20 FL D 20
V7.016-F02 L17 (900mm) 1 20 FL D 20
V7.016-F03 L17 (1500mm) 2 35 FL D 69
L17 (1200mm) 4 27 FL D 108
L17 (900mm) 4 20 FL D 80

Total 296
Glazed passenger Lifts ELV-05-69
V7.016-F04 L17 (900mm) 1 20 FL D 20
V7.016-F05 L17 (900mm) 1 20 FL D 20
V7.016-F06 L17 (1500mm) 2 35 FL D 69
L17 (1200mm) 4 27 FL D 108
L17 (900mm) 4 20 FL D 80
Total 296
Glazed Passenger Lifts ELV-05-103-104
V7.019-F01 L2c (per m) 30 15 LED D 450
V7.019-F02 L17 (900mm) 2 20 FL D 40
V7.019-F03 L17 (900mm) 2 20 FL D 40

Total 530
Glazed Passenger Lifts ELV-05-105-106
V7.019-F04 L2c (per m) 30 15 LED D 450
V7.019-F05 L17 (900mm) 2 20 FL D 40
V7.019-F06 L17 (900mm) 2 20 FL D 40

Total 530
Glazed Passenger Lifts ELV-05-95
V7.20-F01 L2c (per m) 47 15 LED D 703
V7.20-F02 L17 (900mm) 2 20 FL D 40

Total 743
Glazed Passenger Lifts ELV-05-52,92
V7.23-F01 L17 (900mm) 2 20 FL D 40
V7.23-F02 L17 (900mm) 2 20 FL D 40
V7.23-F03 L17 (900mm) 2 20 FL D 40

Total 120
ESC-02-24, 25, 26 Pier 2 Holdroom
V7.030-F01 L3 (per m) 34 15 LED D 510
V7.030-F02 L13 (per m) 66 6 LED D 396
V7.030-F03 L2c (per m) 19 15 LED D 285
V7.030-F01b L3 (per m) 34 15 LED D 510
V7.030-F02b L13 (per m) 66 6 LED D 396
V7.030-F03b L2c (per m) 19 15 LED D 285
V7.030-F01c L3 (per m) 34 15 LED D 510
V7.030-F02c L13 (per m) 66 6 LED D 396
V7.030-F03c L2c (per m) 19 15 LED D 285
Total 3,573

Departures Central Pavilion


V7.018-F01 L13 (per m) 68 6 LED D 408
Total 408

Contract: Midfield Terminal Building - General Contractor, AUH.06.10.0401 Page 231 of 231