Professional Documents
Culture Documents
4-20 mA Output
Features
• Permanently calibrated
Case Style 2
• Supply, signal and input fully isolated Case Style 1
• Output overload protected
• 13 different ranges - 6 field selectable
• Internal current generator Part Numbers
• 2 case styles, .94” and 2.13”
window opening
® CR4340 - ❑ ❑ ❑ 4-WIRE CURRENT TRANSMITTER
• Monitors over long distances E154235
Accuracy: 5 0-5 1
±0.5% Full-Scale (FS) 0-10*
Ripple & Noise: 20 0-15* 1
1% Max., peak to peak 0-20*
Calibrated Signal Out: 0-25*
4-20 mA DC
75 0-50* 1
Response Time:
150 ms max., 10-90% FS
0-75*
Max. Signal Out:
30 mA DC 100 0-100 2
Temperature Coefficient: 150 0-150 2
± 0.02%/°C 200 0-200 2
Supply Voltage: 300 0-300 2
120 ±10% Vac 400 0-400 2
Frequency: 600 0-600 2
50/60 Hz
Output Load:
0-1000 ohms
* RANGE SET WITH FIELD SELECTABLE SWITCH
Insulation Class:
600 V, BIL 10 kV Full Wave
Operating Temperature Range:
-30°C to +60°C
Storage Temperature Range:
-55°C to +85°C 10 © 1998 CR MAGNETICS, INC.
4-Wire Current Transmitter
4-20 mA Output
Application Notes
4.50 28
2.68
3.50 .50
1.70
24
.23 12
#6-32 TERMINALS RANGE SWITCH
.44 TYP. 4 PLACES 8
#8-32 TERMINALS
4 PLACES 2.13
DIA.
AC AC + - 4
AC AC
25 50 75 100
4.88 4.50 PERCENTAGE FULL-SCALE (FS)
120 ± 10% + —
Vac
INTERCONNECT
INSTRUMENTATION
RESISTANCE
RESISTANCE
I PRIMARY - I CONTROL
Typical Applications
An external current transformer may be used with the transmitter by The scaling factor may be changed by threading the primary current-
routing the secondary leads through the window opening. Use the carrying wire several times through the window opening. The "actual"
CR4340-5 current transmitter when using 5-Amp secondary instrument measurement range will be the name plate range divided by the number
grade current transformer. For additional details on current transformers, of wire passes. For example, the CR4340-30 has the name plate range
see page 22. of 0-30 ACA. Two passes of the wire through the window opening will
then provide an effective range of 0-15 ACA (30÷2).
CR Magnetics, Inc. 544 Axminister Dr. Fenton, MO 63026 (314) 343-8518 FAX (314) 343-5119
11 © 1998 CR MAGNETICS, INC.