You are on page 1of 2

Thursday, March 1, 2018

SBH 118 - Cell data sheet


Classification

Brand Saft
Cell type SBH 118
Cell P/N 310251172
Capacity at 5 hours rate 118 Ah
IEC Designation KH118P
According to IEC 60623

Physical data

Overall height 350 mm


Width 195 mm Weight per cell 11.0 Kg
Length Block length - 2 cells 183 mm
Block length - 3 cells 268 mm Block length - 4 cells
Block length - 5 cells Block length - 6 cells
Block length - 7 cells Block length - 8 cells
Block length - 9 cells Block length - 10 cells

Construction

Container material Polypropylene No. of terminals/polarity 1


Separator type Grid Terminal material Steel
Connection torque 30.0 +/- 3.0 Nm Vent type flame arresting vent
Terminal size M10 (large)

Plates

Positive Negative
Type of plates Pocket Type of plates Pocket

Electrolyte

Electrolyte type: Renewal E13 Max/Min 50 mm


Electrolyte type: Initial E22 Vent oil quantity
Electrolyte per cell: Liquid 2.7 liters

Connection

Cable area 120 mm²

SAFT confidential and proprietary. The data herein given are for information purposes only and are not binding on SAFT. They may be modified
without prior notice. Please contact a SAFT representative in order to obtain confirmation of the above data.
Visit our website at www.saftbatteries.com
(376961) Version: 2.1, Last updated on 11/2017 P 1/2
Thursday, March 1, 2018

SBH 118 - Cell data sheet

Charging

Float voltage 1.4 V/Cell High rate voltage (min) 1.45 V/Cell
Single-level voltage 1.43 V/Cell

Resistance/Short circuit

Internal resistance 0.33 mOhm Short circuit current 4125 A

Performance data

Stationary performance
After prolonged float charge of fully charged cells. Available amperes at +20°C +/- 5°C (+68°F +/- 9°F)

V/Cell 10h 8h 5h 3h 2h 1.5h 1h 30m 20m 15m 10m 5m 1m 30s 5s 1s

1 11.8 14.8 23.6 38.8 57.6 75.8 111 203 273 318 379 470 608 694 874 959

1.05 11.8 14.7 23.2 38.3 56.5 74.2 107 193 236 272 323 383 518 590 728 781

1.1 11.5 14.3 22.6 37.2 54.7 71.5 102 157 189 213 241 297 408 472 578 648

1.14 11.1 13.8 21.8 35.8 52.3 67.7 89.9 123 146 164 186 227 326 378 472 496

1.16 10.8 13.5 21.3 34.3 48.0 60.3 72.8 101 123 134 149 187 277 316 393 423

Performance data

Stationary performance
Available power (W), after prolonged float charged of fully charged cells at +20°C +/- 5°C (+68°F +/- 9°F)

V/Cell 10h 8h 5h 3h 2h 1.5h 1h 30m 20m 15m 10m 5m 1m 30s 5s 1s

1 14.3 17.9 28.2 45.9 67.9 86.0 120 211 280 323 382 470 608 694 874 959

1.05 14.2 17.8 27.8 45.4 66.6 85.0 119 208 252 289 341 402 544 620 765 821

1.1 13.9 17.3 27.0 44.1 64.5 82.9 116 176 210 236 266 327 449 519 636 713

1.14 13.4 16.8 26.0 42.4 61.7 79.2 104 141 167 188 212 259 372 431 538 566

1.16 13.0 16.3 25.4 40.7 56.6 70.9 85.2 118 143 155 173 217 321 367 456 491

SAFT confidential and proprietary. The data herein given are for information purposes only and are not binding on SAFT. They may be modified
without prior notice. Please contact a SAFT representative in order to obtain confirmation of the above data.
Visit our website at www.saftbatteries.com
(376961) Version: 2.1, Last updated on 11/2017 P 2/2