PPR- MCore

Ref. Doc
Trip Time Reach
Instantaneous (~30mSec ie IED op.time)
(or) Within max 1.5 cycle, 80% of P-Line 1-1-3
CB trip coil to get energized
Zone-1 100msec
Note: For allowing Distance
80% of P-Line with Series Compensation
Measurement after series capacitor is
bypassed
350mSec for P-Line < 100km Which is Greater in 1 & 2 below:
Zone-2 1) (120% of P-Line)
500mSec for P-Line > 100km 2) (100% of P-Line) + (50% of AS-Line)
Which is Smaller in 1 & 2 below:
1) (120% of P-Line) + (100% of AL-Line)
Zone-3 1000 mSec
2) (100% of P-Line) + (100% of AL-Line) +
(25% of AL-Line)
Zone-3R
Reverse 1000 mSec 25% of P-Line in Reverse Direction
Zone

KPTCL Spec: 220kV Lines PGCIL Spec:


Types of << It is PPR notes >>
Faults in Due to Natural Reasons: << Detailed spec Not specified>>
Transmi  Trees Touching the Transmission Lines  Mostly Causing << It is PPR notes >>
ssion Temporary Faults.
Lines /  Fault with Arcs : Tree faults with Arc, Insulator Failure with
Reason Arc, Fallen Conductor to Ground with Arc
for  Broken Conductor
Tripping  Weekend in-feed type of faults
 Insulator Failures
 Wind causing adjacent conductors to come closer & arc
flashing between lines.
 FOG creating voltage short circuits
 Lightning Strokes

Due to PS System reasons:


 Load Encroachment & Load Discrimination
 False settings Parallel Line mutual compensation
 False settings of Series compensated lines
 PLCC – Trip received from other end substation IED
 Improper Residual Compensation
 U/V & O/V
 SOTF

Due to Substation Equipment Faults:


 PT Fuse Failure (or) Very low in-feed of voltage (PT Failures)
 Current Supervision (CT Failures)
 LBB (CB Failures)

Page: 1 of 5
PPR- MCore

System  Method1: Auto Reclose 


Restorat  Method2: After fault clearing, Manual Charging of lines
ion
System  Disturbance Recorder 
Analysis  Fault Locator
 Event List
Distance It shall have:
Protecti  Relay characteristic setting range: 30 - 750  RCA Range: 30-850
on  3 Forward and 1-Reverse zone  3 Forward and 1-Reverse zone
Function  Quadrilateral Characteristic  Quadrilateral / mho /.. Characteristic
Block  Suitable for - Any type of Line Length;  Zone-2 time range: 0-3Sec; Zone-3: 0-5Sec
 Suitable for Heavily Loaded / Lightly Loaded lines
 Operating time For SIR 0.01-to-4: < 30mSec to 40mSec
 Operating time For SIR 4-to-15: < 35mSec to 45mSec
(This does not include carrier transmission time)
SIR: Ratio of “ Source Impedance” to “LINE Impedance”

 Reset Time: < 35mSec


 Reset time <55mSec
 Characteristic offsetting for Zone-3
 Characteristic offsetting for Zone-3 (10-20%)
 Residual Compensation for 30-150%
 Variable Residual Compensation
 Parallel line – mutual compensation

PLCC  Permissive Over reach, Permissive Under reach & blocking  Permissive Over reach, Permissive Under reach & blocking
communication modes communication modes
 Carrier transmission time ~ 20mS
Auto  1Φ & 3Φ auto reclosing facility For 765/400/220kV Lines
Reclose  Be of Single Shot type  Have 1Φ reclosing facilities (3ph-not there/deleted)
 Dead time range – 0.1 to 2Sec (for both 1Φ & 3Φ )  Be of Single Shot type
 Reclaim time range – 5 – 25 Sec  A/R fun shall be in separate IED other than Main-1 and Main-2
 A/R Selection Switch – Off / 1Φ / 3Φ / (1Φ & 3Φ)  Dead time range – 0.1 to 2Sec (for both 1Φ & 3Φ )
 A/R lockout – when distance protection schemes are faulty  Reclaim time range – 5 – 300 Sec
/ Permanent fault / out of service  A/R 2-Pos Selection Switch – Off or 1Φ
 have priority circuit to closing of both circuit breakers in case
one and half breaker arrangements in a sequential closing of
breakers process
 A/R Function Shall be in BCU (if BCU provided)

132kV Lines
 For 132kV Lines A/R function can be integral part of Main
Protection IED.
Check  Time Setting range: 0.5 to 5 Sec  Time Setting range: 0.5 to 5 Sec
Synchro  Response time <200mSec (with the timer disconnected)  Response time <200mSec (with the timer disconnected)
nising  Have Deadline charging feature  Have phase angle setting not exceeding 35 Degree
Dead Line : Fixed setting of 20% of rated voltage  Have voltage angle setting not exceeding 10%
Live Line: Fixed setting of 80% of rated voltage  Have Deadline charging feature
Dead Line : Fixed setting of 20% of rated voltage
Live Line: Fixed setting of 80% of rated voltage
 Why check sync spec deleted in PGCIL spec..?

IED  CT Cores – Continuously Load.: 1.2 Times of Full Load current  CT Cores – Continuously Load.: 1.2 Times of Full Load current
hardwar  CT Cores – Short Time Ratin… : 70 Times of Full Load current  CT Cores – Short Time Ratin… : 70 Times of Full Load current
e Spec  PT Cores…………………………….: 1.2 Times of Nominal Voltage  PT Cores…………………………….: 1.2 Times of Nominal Voltage
 DI/DO : See IED spec  DI/DO : See IED spec

Fault  It shall be impedance Based. Suitable for all L-N, L-L , L-L-L 
Locator faults & broken conductor
 Measurement will be based on measuring values prior to
and during the fault
 Accuracy – 3% or better.
 The accuracy of the measurement shall not be
affected / influenced by :
 line leading prior to the fault ,
 remote infeed,
 magnitude of the fault resistance
 mutual effect of parallel line(s),
 CVT transients,
 DC component of in fault current,
 heavy load conditions,
 temperature variations,
 Frequency divisions.
 Shall be suitable for “ Three (3) cycle CB “

Page: 2 of 5
PPR- MCore

LBB  It shall be based on Current Principle  Be 3-Pole type


 It shall be based on Current Principle
 Current setting range: 20-80% of rated current
(Continuous thermal withstand rating: 2 times rated current)
 Timer range: 0.1 –to- 1 Sec
 Operating time <15mSec
 Reset Time< 15mSec
 Line Prot: Get individual initiation from corresponding LBB
phase
 Trafo/Reactor: 3Ph initiation is acceptable
Master  High Speed, DC Operated  Contact Rating: @ 220V DC, 30A for 0.2 Sec with L/R>10mSec
Trip  Max Operating time: 10mSec;  Operating time <=10mS
Relay  Reset time: 20mSec
TSR  All Trip coils shall be supervised. DC fail in trip circuits shall 
be supervised
 Time Delay on drop off – not less than 200mSec
(To avoid false annunciation during temporary surges)
 Provided with Operation Indication (LED)
DC Ckt  Time Delay on drop off – not less than 100mSec 
Sup.  Separate DC supply-monitoring relay shall be provided for
DC main
circuit, control circuit of tripping relay and protection circuit
of each panel
 Provided with Operation Indication (LED)
 Alarm, Accept & Reset ckt shall be built
Voltage  PT Selection circuits between line CVT & Bus CVT. 
Selectio When line CVT is failed, manually protections shall be
n switched to Bus CVT.
Disturba  It shall have minimum: 
nce  8-Analog channels
Recorde  16-Event Channels
r  COMTRADE Format
 Response Freq: 5Hz to (250Hz or better on upper side)
Scan Rate: 1000 Hz/Channel or better
(1000 sample per second; ie.,20 samples per 50Hz cycle)
 Starting Sensors: DR shall start when O/v, abnormal di/dt,
df/dt
 Pre-fault duration: 160mS; Post-fault Duration: 2-5 Sec
 If one disturbance occurs during Post-fault duration, same
shall also be recorded
 Analog Amplitude Resolution >= 8bit;
Event Resolution >=2mSec
 It shall have own-time generator. Allowed Drift 0.5sec/day
 If no separate time-sync equip. available, use any one IED
time to synchronize other IEDs time.

System << Not specified >>  The maximum fault current could be as high as 63kA
Fault  Minimum fault current could be as low as 20% of rated current
Level of CT secondary.
Backup Over Current / Earth Fault relay A) For 765kV/400kV/220kV Lines :
Protecti  Electro-magnetic type Dir. Earth Fault relay
ons  Single Pole, Directional/ Non Directional  IDMT Characteristic
 IDMT characteristic  Normal Inverse IEC Curve to be used
O/C Setting range: 50-200% of full load current  Must have a current reversal guard feature
E/F Setting Range: 20-80% (or) 10-40%
 Def. time: 3 Sec @ 10 times of setting B) For 132kV Lines:
 Directional element shall be voltage polarized Dir. Over Current & Earth Fault Protection:
 Max. Relay Char. Torque Angle (RCA) shall be 450  Three O/C and One E/F Elements
Earth Fault relay additional features  VT Fuse fail alarm feature
 Operating coil of DEFR shall be connected in residual circuit  IDMT with definite min time of 3Sec at 10 times setting
of star connection of line CTs  Current Setting range: 50-200% of rated current
 Polarization voltage shall be obtained from OPEN DELTA  RCA: 30/45 degree lead
connection VT secondary ckt.  Hand reset flag / LEDs

Earth Fault Element:


 IDMT with definite min time of 3Sec at 10 times setting
 Current Setting range: 20-80% of rated current
 RCA: 45/60 degree lag
Over NA  Two independent Stages
Voltage  Can be built in function of Main-1/Main-2 IED
 Stage1 Setting Range: 100-170% of rated voltage
 Stage1 Time setting range: 1-60Sec
 Stage2 Setting Range: 100-170% of rated voltage
 Stage2 Time setting range: 100-200mSec
 Drop off to Pickup ratio: 95% (Hysteresis)
 Provide separate output contacts for each PHASE and STAGE
for breaker trip relays and EL/DR etc

Page: 3 of 5
PPR- MCore

Event 
Recorde
r

Typical
Line
Data

PGCIL Spec Continued…

Secondary Impedance…? (After Trafo..?)

NOTE: As per PGCIL Spec Fault Case Studies – To be tested and note down the reading & observations

Page: 4 of 5
PPR- MCore

Protection Philosophy:

KPTCL Spec PGCIL Spec


765kV 132kV
220kV 110 kV Lines
Line Protection / 400kV
Lines / 66kV Lines
/ 220kV
Main1:
Distance Protection (21) √ √ √ √
L-N, L-L, L-L-L
Main2:
Distance Protection (21) NA NA √ NA
L-N, L-L, L-L-L
Carrier aided Distance
protection (PLCC) with
√ NA √ (??)
Permissive over reach &
under reach
Broken Conductor √ √ √ √
SOTF √ √ √ √
Weekend In-feed √ √ √ √
O/V √ NA √ NA
U/V for Iso/Esw
√ √ √ √
Interlocks
Power Swing √ NA √ (??)
CT/PT Supervision √ √ √ √
DR / EL / Fault-Locator √ √ √ √
LBB √ √ √ √
Auto Reclose √ NA √ √
Check Synch √ NA √ (??)

Backup O/C Protection √ NA √
Note-1
Backup E/F protection √ √ √ √
Special Note: Note-2 Note-3

Note1:- As per KPTCL spec : Back up protection shall be of Electromagnetic type.

Note2:- VT Sources : Line CVT is preferred. If it fails use Bus CVT. PT Selection scheme shall be built

Note3:- VT Sources : Bus CVT shall be used.

PGCIL:-

1) Main-1 and Main-2 – Relay makes shall be different.


2) Further, If specified in the “Section- Project “, back up Over current and Earth fault protection shall be provided instead of Main -II protection
scheme for 220KV lines to match with requirements at the remote ends.

Page: 5 of 5