Professional Documents
Culture Documents
of the 2014 International Symposium on Electromagnetic Compatibility (EMC Europe 2014), Gothenburg, Sweden, September 1-4, 2014
Abstract—In the paper the results of measurements of In 400 kV networks of B&H after reconstruction and its
voltages and electric fields of extra low frequency (ELF) below reconnection in common energy system (UCTE) and today
400 kV transmission lines in Bosnia and Herzegovina (B&H) are ENTSO-E in October 2004, there were registered a significant
presented. In the high-voltage network in B&H there were the appearance of the power frequency overvoltages, especially
registered a significant number of power frequency overvoltages in the regime of small loads. The IEC 60038 [2] defines a set of
in the regime of small loads after its reconnection in common nominal system voltages and the highest voltages for
energy system UCTE (Union for the Coordination of equipment. The highest voltages for equipment for nominal
Transmission System Operators for Electricity), and today system voltage of 110 kV, 220 kV and 400 kV are 123 kV, 245
ENTSO-E (European Network of Transmission System
kV and 420 kV, respectively. Independent System Operator in
Operators for Electricity) in October 2004. Increased voltages in
the high-voltage network causes increase in the value of electric
Bosnia and Herzegovina operates with network in accordance
field and exposure of human bean to electric fields. On the other with ENTSO-E, Grid Code [3] and IEC 60038. Voltage control
hand, high voltages in the network causes higher power losses in the technical limits of the declared values also contributes to
due to AC corona. Therefore, it is important to determine the the optimal operation of equipment and consumers, as well as
value of electric field in the vicinity of high-voltage lines to assess reducing the losses in transmission from source to the final
their effects on people and equipment as well as value of electric users. The greatest influence are loads on the 400 kV overhead
field at increased voltages to accurate determined power losses lines below the natural capacity (loads do not exceed 20 % of
due to AC corona. The results of measurements of electric fields thermal capacity), as well as very limited opportunities for
in the spatial profiles at 1, 2 and 3 meters above ground at compensation of surplus reactive power in electric power
distances up to 20 meters from line are presented. system in Bosnia and Herzegovina. It should be noted that the
voltages above the allowed values (that last continuously for
Key words—ELF electric field; electric field measuring; corona several hours, even days) adversely affecting the insulation
power loss; international safety standards level of equipment, shortening its lifetime, and at the same time
increase power losses due to AC corona. Duration of these
I. INTRODUCTION power frequency overvoltages are significant and represent a
Electric and magnetic fields (EMF), generated from potential risk to the operation of power system with possibility
electrical equipment are very important from the aspect of their of breakdown of insulation, which can cause outage of
elements of the system and its stability and supply consumers
impact on people and other living organism, as well as on
with electricity.
surrounding objects (pipelines, IT communication lines, etc.).
In the public there is a socio-phenomena opinion about
negative influence of emission from overhead lines, and it is II. POWER FREQUENCY OVERVOLTAGES IN BOSNIA AND
very important to investigate real values of that ELF EMF. HERZEGOVINA POWER SYSTEM
Using digital measuring equipment and software it is Continuous monitoring of voltages in B&H power system
possible to confirm real values of electric fields. Because B&H is done with the details showing the voltage condition at
still does not have standards in this field, it is important to look characteristic points of 400 and 220 kV network in the period
into the situation in European countries and initiate the creation of one year – from January 1st till December 31st (8760 hours).
of the necessary standards documentation in this field. During In that period, hourly values of voltages are analyzed on the
this process it is very important to take into account: ICNIRP buses at the following substations – Table I [4].
[1] (International Commission of Non-Ionizing Radiation
Protection) and European Parliament recommended referent
level for public exposure in the range of 5 kV/m for 50 Hz.
612
Proc. of the 2014 International Symposium on Electromagnetic Compatibility (EMC Europe 2014), Gothenburg, Sweden, September 1-4, 2014
Evert
Ehoriz
Evert Evert
IV. CONCLUSIONS
Increased overvoltages of power frequency occur in 220
and 400 kV Bosnia and Herzegovina power system with long
duration. The highest 400 kV voltages of all considered
substations are recorded in SS Mostar 4 (437.9 kV) and the
longest duration of non-allowed overvoltage of more than 5400
Figure 6. 400 kV OHL Sarajevo 10 – Sarajevo 20, longitudinal profile [6] hours (51.75 %) in 2013. The highest 220 kV voltages are
recorded in SS Prijedor 2 (251.3 kV) and duration of non-
613
Proc. of the 2014 International Symposium on Electromagnetic Compatibility (EMC Europe 2014), Gothenburg, Sweden, September 1-4, 2014
allowed voltages are 784 hours (8.95 %) in 2013. These [2] IEC 60038, IEC Standard Voltages, Edition 7.0, 2009-06
overvoltages are harmful for the insulation of equipment with [3] Independent System Operator in Bosnia and Herzegovina, “Grid Code,”
negative impact on power quality. At the same time increased Sarajevo, May, 2011
power frequency overvoltages increase power losses due to AC [4] Independent System Operator in Bosnia and Herzegovina,”
Identification on unallowable voltages on Bosnia and Herzegovina
corona. transmission network,” Sarajevo, January 2014
Measured values of electric field on 400 kV overhead line [5] CIGRE Technical Brochure, “Technical guide for measurement of low
Sarajevo 10 – Sarajevo 20 at 1, 3 and 3 meters above ground frequency electric and magnetic fields near overhead power lines”, WG
C4.203 (2008)
are some higher than reference level of 5 kV/m for public
exposure. [6] “Measurement of electrical and magnetic fields,” Faculty of Electrical
Engineering, Report dated 24.04.2013., Sarajevo, 2013
[7] S. Carsimamovic, Z. Bajramovic, M. Veledar, M. Ljevak, S. Nuic, P.
ACKNOWLEDGMENT Osmokrovic, “Impact of Tower Dimensions onto Levels of ELF Electric
and Magnetic Fields of 400 kV Overhead Lines,” CIGRE 2008, Paper
This work was supported by the Ministry of Education and C4-105, Paris, France, 2008
Science of the Federation of Bosnia and Herzegovina. [8] S. Carsimamovic, Z. Bajramovic, M. Rascic, M. Veledar, E. Aganovic,
A. Carsimamovic, “Experimental Results of ELF Electric and Magnetic
REFERENCES Fields of Electric Power Systems in Bosnia and Herzegovina,” IEEE-
EUROCON 2011, Lisbon, Portugal, 2011
[1] “Guidelines for Limiting Exposure to Time-Varying Electric and
Magnetic Fields (1 Hz-100 kHz),” Health Physics 99(6):818-836; 2010
614