Savio

USER MANUAL AND INSTRUCTIONS

PLUS COMBI
WALL HUNG GAS BOILER FOR
CENTRAL HEATING SUPPLY
Please Read Instructions Carefully
Save for Future Reference

WARNING: If the information in this manual is not followed


exactly, a fire or explosion may result causing property dam-
age, personal injury or loss of life.

— Do not store or use gasoline or other flammable vapors and liquids


in the vicinity of this or any other appliance.

— WHAT TO DO IF YOU SMELL GAS


• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your
building.
• Immediately call your gas supplier from a neighbor’s phone. Fol-
low the gas supplier’s instructions.
• If you can not reach your gas supplier call the fire department.

— Installation and service must be performed by a qualified installer,


service agency or the gas supplier.
Dear Customer:

Thank you for buying a SAVIO Plus Combi.

The SAVIO Plus Combi is a high efficiency condensing, wall mounted gas boiler which
provides central heat.

We realize that it is not possible to answer all questions about the SAVIO Plus Combi in this
manual. Reading this installation manual does not make the reader an expert in all aspects
of installation and operation, and does not replace the need for a qualified, licensed heating
contractor. We urge you to contact your installing contractor or distributor if you are in question
about any aspect of your boiler’s performance. Our main concern is that you are satisfied with
your boiler and its performance. We require that your contractor complete efficiency tests using
instruments.

The external controls and accessories listed in this manual (excluding those supplied inside
the boiler) are intended to serve as guidelines rather than specific recommendations. We re-
alize that other makes and models of such devices are available and can be used as suc-
cessfully as those we specify. The installing contractor is the best judge of a system’s specific
requirements, as well as the local availability of certain makes and models of controls and
accessories. The preceding does not apply, however, to the equipment that comes with every
boiler, such as the overheat control and pressure relief valves. The installation of the spe-
cific devices supplied with every boiler is absolutely necessary to the safe operation of
the boiler and protection of the heating system.

All SAVIO wall hung boilers are built in accordance with the ASME boiler and pressure vessel
code, and bear the “H” stamp. The Entire range of applications for the SAVIO Plus Combi has
been tested to standard CSA 4.9 and is CSA compliant.

This SAVIO Plus Combi has a 2 year warranty on the boiler, and 10 years on the heat exchanger
a copy of which is provided with the boiler. Please be sure to return the warranty registration card as
the warranty will be void without your boiler’s serial numbers (located on the ratings label affixed to
the boiler), date of installation and the name of your installer being on record in our files.

Thank you for purchasing our SAVIO Plus Combi. If you have questions or comments, please
don’t hesitate to contact us immediately. Our goal is 100% customer satisfaction.

BOYERTOWN

2 SAVIO PLUS COMBI USER MANUAL


Table of Contents
Section Title Section Number Page Number

Warnings - 4-5
Important Information - 6
General Information 1 7
Technical Information 2 7-8
Appliance Description 3 9
Operation Lights 4 10
Instructions for Use 5 11-14
Warnings 5.1 11
Refilling Procedure 5.2 11
Lighting/Operation Instruction 5.3 12
Central Heating Circuit Temp. 5.4 12-13
Extinguishing Instructions 5.5 13
Domestic Hot Water Temperature 5.6 14
Useful Advice 6 15-17
Central Heating 6.1 15
Frost Protection 6.2 15
Periodic Maintenance 6.3 15
External Cleaning 6.4 16
Operational Faults 6.5 16-17
Warranty 18

SAVIO PLUS COMBI USER MANUAL 3


WARNING
Boiler is certified as an indoor appliance. Do not install boiler outdoors or locate where it will
be exposed to freezing temperatures.

WARNING: If the information in this manual is not followed


exactly, a fire or explosion may result causing property dam-
age, personal injury or loss of life.

— Do not store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance.

— WHAT TO DO IF YOU SMELL GAS


• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your build-
ing.
• Immediately call your gas supplier from a neighbor’s phone. Follow the
gas supplier’s instructions.
• If you can not reach your gas supplier call the fire department.

— Installation and service must be performed by a qualified installer, ser-


vice agency or the gas supplier.

DANGER
Caution: Do not store or use flammable materials, chemicals or flammable liquids,
especially gasoline, in the vicinity of this heating appliance.

Caution: Should overheating occur or the gas supply fail to shut off, do not turn off
or disconnect the electrical supply to the pump. Instead, shut off the gas supply at a
location external to the appliance.

Caution: Do not use this boiler if any part has been under water. Immediately call a
qualified service technician to inspect the boiler and to replace any part of the control
system and any gas control which has been under water.

4 SAVIO PLUS COMBI USER MANUAL


WARNING
Any appliance that burns natural gas, propane gas, fuel oil, wood or coal is capable of pro-
ducing carbon monoxide (CO). Carbon Monoxide (CO) is a gas which is odorless, colorless
and tasteless but is very toxic. CO is lighter than air and thus may travel throughout the
building.

BRIEF EXPOSURE TO HIGH CONCENTRATIONS OF CO, OR PROLONGED EXPO-


SURE TO LESSER AMOUNTS OF CO MAY RESULT IN CARBON MONOXIDE POISON-
ING. EXPOSURE CAN BE FATAL AND EXPOSURE TO HIGH CONCENTRATIONS MAY
RESULT IN THE SUDDEN ONSET OF SYMPTOMS INCLUDING UNCONSCIOUSNESS.

Symptoms of CO poisoning include the following:


dizziness vision problems shortness of breath
headache loss of muscle control unclear thinking
nausea weakness unconsciousness

The symptoms of CO poisoning are often confused with those of influenza, and the highest
incidence of poisoning occurs at the onset of cold weather or during flu season.
A victim may not experience any symptoms, only one symptom, or a few symptoms.
Suspect the presence of carbon monoxide if symptoms tend to disappear when you
leave your home.

The following signs may indicate the presence of carbon monoxide:

• Hot gasses from appliance, venting system pipes or chimney, escaping into the living
space.
• Flames coming out around the appliance.
• Yellow colored flames in the appliance.
• Stale or smelly air.
• The presence of soot or carbon in or around the appliance.
• Very high unexplained humidity inside the building.

If any of the symptoms of CO occur, or if any of the signs of carbon monoxide are
present, VACATE THE PREMISES IMMEDIATELY AND CONTACT A QUALIFIED
HEATING SERVICE COMPANY OR THE GAS COMPANY OR THE FIRE
DEPARTMENT.

ONLY QUALIFIED, LICENSED SERVICE CONTRACTORS SHOULD PERFORM WORK


ON YOUR SAVIO SAVIO PLUS COMBI BOILER.

SAVIO PLUS COMBI USER MANUAL 5


IMPORTANT INFORMATION
Please read this page carefully.

• ALL BOILERS MUST BE INSTALLED IN ACCORDANCE WITH NATIONAL,


STATE AND LOCAL PLUMBING, HEATING AND ELECTRICAL CODES
AND ORDINANCES, AS WELL AS THE REGULATIONS OF THE SERVING
ELECTRICAL, WATER AND GAS UTILITIES.

• All systems should be designed by competent contractors, and only persons


knowledgeable in the layout and installation of heating systems should attempt
the installation of any boiler. It is the responsibility of the installing contractor
to see that all controls are correctly installed and operating properly when the
installation is completed.

• This boiler is intended for use, only with propane or natural gas. All flammable
liquids (especially gasoline), chemicals, rags, paper, wood scraps, debris, etc.,
should be kept away from the boiler at all times. Keep the boiler area clean and
free of all fire hazards.

• Please read the literature and warranties supplied by the manufacturers of the
various accessory equipment. This equipment is warranted by the respective
manufacturers, not by BOYERTOWN Each piece of equipment must be installed
and used according to the recommendations of the manufacturer.

Codes and Regulations:


Installation of the boiler and related equipment must conform to national, state and
local regulating agencies and codes applicable to the installation of the equipment. In
the absence of local requirements, the following codes apply:

A. ANSI/NFPA - #70 National Electric Code


B. ANSI/NFPA - #211 Chimneys and Vents
C. ANSI/NFPA - #Z223.1 National Fuel Gas Code
C. ANSI/NFPA - Domestic Gas Conversion Burner
D. CAN/CGA - B149 Installation Codes
E. ANSI/ASME - CSD-1

The above codes are available from:

National Fire Protection Association (NFPA) CSA International


Battery March Park 8501 E. Pleasant Valley Road
Quincy, Massachusetts, 02269 Cleveland, OH 44134-5575
http://www.nfpa.org http://www.csa-international.org

6 SAVIO PLUS COMBI USER MANUAL


1. General Information
The SAVIO Plus Combi is a high efficiency condensing, wall mounted gas boiler which pro-
vides central heat. The boiler features a gas valve which modulates the energy input from
49,476 BTU/h to 116,008 BTU/h. The boiler is shipped fully assembled. All units are pressure
and combustion tested at the factory prior to shipping.

Key Features:

• Wall mountable - saving valuable floor • Boiler operation recognition system -


space. should the boiler not be used for longer
• Several flue options available than 24 hours, it then performs a control-
• Electronic spark ignition led system test to ensuring the motorized
• Safety flow switch - positioned on the components within the boiler do not be-
main circuit, which monitors the flow and come inoperable due to lack of use.
protects the main heat exchanger from • Gas valve modulation - the gas input
thermal shock should there be a lack of modulates based off central heating tem-
water in the system. perature to within ± 2 ºF
• Frost protection - contains an integral frost • Diagnostic information system equipped
protection system to prevent frost dam- with three LED diagnostic lights for quick
age which can occur in areas susceptible error assessment.
to very cold weather conditions.

2. Technical Information (M135.30CM)

GENERAL INJECTORS No. Size


Height in 31.6 Natural 14 130
Width in 15.7 Propane 14 85
Depth in 13.8
Weight lb 109.5 CENTRAL HEATING
Maximum working temp. °F 185
ELECTRICAL Temp. Regulation range* °F 100-176
Voltage V 120 Maximum pressure psi 30.0
Frequency Hz 60 Minimum pressure psi 4.35
Current A 1.6 Max head loss (at 4.4 GPM) ft 8.25
Power consumption W 180 *At the minimum useful output

SAVIO PLUS COMBI USER MANUAL 7


2. Technical Information Cont.

ENERGY CAPACITY GAS FLOW RATE


Nominal heat input Gas Min Max
MBH 116.0
(0/2000ft)
Natural ft³/h 48.7 115.1
Nominal heat input
MBH 110.2 Propane lb/h 2.2 5.2
(2000/4500ft)
Minimum heat input MBH 49.5
CLEARANCE TO COMBUSTIBLES
Maximum useful output
MBH 102.0 Front in 18
(0/2000ft)
Maximum useful output Back in 0
MBH 97.2
(2000/4500ft) Top in 8
Minimum useful output MBH 41.6 Sides in 2
Bottom in 8
GAS SUPPLY PRESSURE Flue pipe enclosed in 2
Gas Normal Min Max Flue pipe free air in 0
Natural inwc 7.0 3.5 10.5 Hot water pipes in 1”
Propane inwc 11.0 8.0 13.0

FLUE GAS FIGURES


GAS PRESSURE AT BURNER Gas Min Max
Gas Min Max Ignition
CO2 2.5% 6.3%
Natural inwc 1.0 4.8 2.4
O2 16.5% 9.7%
Propane inwc 2.0 10.3 5.2

DOMESTIC HOT WATER


FLUE DESIGN Maximum temperature °F 131
Minimum Venturi pressure inwc 0.64
Minimum temperature °F 95
Flue pipe diameter
Maximum pressure psi 145
2.25/4
Minimum pressure psi 4.35
Coaxial in 3.25/5
D.h.w. ΔT 25K gal/h 4.5
Twin split pipes in 3.25/3.25 D.h.w. ΔT 30 K gal/h 3.8
Nominal heat flow rate MBH 116.0 D.h.w. ΔT 35 K gal/h 3.2
Nominal heat flow rate D.h.w. ΔT 40 K gal/h 2.8
MBH 110.2
(2000/4500ft)
Min Exhaust temperature °F 120
Max Exhaust temperature °F 190

8 SAVIO PLUS COMBI USER MANUAL


3. Appliance Description
3.1 Overview:

1 Case front panel


2 Control panel
3 Control panel cover

3.2 Control Panel:

4 Central heating circuit temperature and


pressure gauge
5 Lock-out signal lamp
6 Boiler reset button
7 Function switch and Central heating tem-
perature adjustment knob
8 Domestic hot water, temperature control
knob
3 1 2
9 Appliance operation lights Figure 3.1

9 8 7 6 5 4
Figure 3.2

3.3 Piping Connections:

A Gas inlet pipe


B Main circuit drain cock
C C.h. supply copper pipe
D C.h. return copper pipe
E C.h PRV discharge copper pipe
F D.h.w. hot water outlet pipe
G D.h.w. cold water inlet pipe
H Condensate drain connection area

Figure 3.3

SAVIO PLUS COMBI USER MANUAL 9


4. Operation Lights

Three lights (9 in Fig. 3.2) give detailed indication regarding the operation of the boiler. The
following table gives the relationship between each of the possible light combinations and their
meaning.

A short pulse every 4 seconds: stand-by condition


Function selector in position. Anti-freeze system active
1 second pulse every 2 seconds: normally operating boiler.
Function selector in on position
Central heating operation

Frost protect operation

Faulty central heating temperature probe NTC

Faulty primary circuit (no water or absence of flow)


Lack of burner ignition (no ignition signal from the full
sequence ignition device)
Ignition gas pressure adjustment

Minimum gas pressure adjustment

Flashing lamp, alone Flashing lamp, al-


Lamp OFF Lamp ON or simultaneously ternate with another
with another lamp. lamp

10 SAVIO PLUS COMBI USER MANUAL


5. Instructions For Use

5.1 Warnings:
• In order to guarantee safety and correct operation, it is essential that all the tests are carried
out by a competent and responsible licensed service person before lighting up the boiler.
• The tests are described in the installation, operation and service instructions manual in Sec-
tion 15 Commissioning.
• Ensure that the Central Heating circuit is regularly filled with water checking that the pres-
sure indicated on the temperature and pressure gauge (4 on figure 3.2) is not lower than 1
bar (14.5 psi) as shown on figure 5.1.
• If the pressure reading on the pressure gauge is below 1 bar (14.5 psi), then the system will
require filling. An automatic filling valve is normally provided by the installer for this purpose.
• If you are in any doubt regarding this procedure you are advised to contact your In-
staller or an Approved Service Person.
• This appliance is provided with a built in anti-freeze system that operates the boiler when
the temperature is below 41 °F
• Therefore, when the boiler is not lit or used in cold weather, with consequent risk of freezing
do not switch off the boiler at the circuit breaker or close the gas inlet cock.
• When you expect not to use the boiler for a long period follow the instructions given in sec-
tion 5.6 on page 14.

5.2 Refilling procedure:

• Isolate the boiler from the electrical sup-


ply at the circuit breaker.
• The boiler should have been installed with
an automatic fill valve, external to the unit.
Open the cold water supply to the auto- 4
3
0
2 1
matic fill valve.
• The pressure should be 1 – 1,5 bar (14.5
– 22 psi). Figure 5.1
• The automatic fill valve should maintain
this pressure, but not exceed it.

Air introduced into the boiler during this filling process will vent through the automatic air purger
fitted to the boiler. You may also find it necessary to vent air from your heating circuit using the
installed vents, however be aware that excessive venting will cause the pressure in the system
to drop. Always ensure that the pressure gauge is set at the required pressure.

SAVIO PLUS COMBI USER MANUAL 11


5. Instructions For Use Cont.
5.3 Lighting/Operating Instructions:

Warnings: Do not attempt to start the boiler unless all cleanout doors are secured and
sealed. Do not attempt to light the burner by hand.

1 Check that the cocks connected to the 4 If the appliance will not operate, follow
gas inlet pipe and to the supply cold wa- the extinguishing instructions on page 13
ter inlet pipe (see section 3.3 for pipes) and call your service technician or gas
are open. supplier.
2 Turn on the electricity supply to the boiler,
switching on the circuit breaker. The ap-
pliance operation light A (figure 5.2) will
flash every 4 seconds (stand-by condi-
tion).
3 If the boiler is to be used for c.h position
the function selector B as in figure 5.2. A B C D E
The appliance operation light A will flash
every 2 seconds (operating boiler). Figure 5.2

5.4 Central Heating Circuit Temperature:

1 The output temperature of c.h. water is


adjustable from a minimum of about 100
°F to a maximum of about 176 °F (Figure
5.3), by turning the knob B
2 Adjustment of the boiler temperature al-
ters the gas flow at the burner according
to the thermal demand in the system. So
it is usual to see the burner lit at the mini-
mum level for more or less long periods.
3 Adjustment of central heating. Output on
the boiler is automatic. The greatest out-
put is factory pre-set, however, it can be
reduced according to actual system re-
quirements. These adjustments must be
carried out by a qualified person; there-
fore we advise you to contact your install- Figure 5.3
er or Service Agent.

12 SAVIO PLUS COMBI USER MANUAL


5. Instructions For Use Cont.
Adjustment:
• In order to achieve optimal settings for From 41 to 59°F Between 23 and 41°F
economy and comfort, we recommend
adjusting the operating temperature of
the central heating water according to the
outside temperature, positioning the knob
as in figure 5.4
• Your installer may have installed addi-
tional energy saving equipment and will
be able to recommend the most suitable
adjustment for your system.
• The temperature and pressure gauge (Fig.
5.1 on page 11) will allow you to check
that the set temperature is obtained.
Lower than 23°F
Figure 5.4

5.5 Extinguishing Instructions:


• To turn the boiler off set the function selector A C
B to the position shown in the Figure 5.5.
• The appliance operation light A (figure
5.2) will flash every 4 seconds (stand-by
mode).
• Turn off electric power to the appliance
at the circuit panel of boiler serviceman’s
switch.

Figure 5.5

When you expect not to use the boiler for a long period:

• Switch off the electricity supply to the boiler, by means of the circuit breaker;
• Shut off the gas supply cock connected to the gas inlet pipe and the cock connected to the
supply cold water inlet pipe (see section 3.3 for pipes)
• Empty the water circuit, if necessary, as shown in the installation, operation and service
instructions manual in the maintenance section.

SAVIO PLUS COMBI USER MANUAL 13


5. Instructions For Use Cont.
5.6 Domestic hot water temperature:

The temperature of the domestic hot water coming out from the boiler can be regulated from a
minimum of approximately 95° F to a maximum of approximately 131° F by turning the control
shown in fig. 5.6

Minimum

Maximum

Figure 5.7

Figure 5.6

Adjustment of the d.h.w. temperature is completely separate from that of the c.h. circuit.
The adjustment system integrated within the boiler automatically controls the flow of gas to
the burner in order to keep the temperature of d.h.w. delivered constant ,between the limits of
maximum and minimum output.
Where the demand is at a low level or with the temperature set to the minimum,it is normal to
see a cycle of lighting and extinguishing of the burner when running.
Regulate the domestic hot water temperature to a value suitable for your requirements.
Reduce the need to mix the hot water with cold water.
In this way, you will appreciate the characteristics of automatic regulation.
If the water is particularly hard, we recommend regulating the boiler at a temperature lower
than 120° F fig.
In these cases, we nevertheless recommend the installation of a water-softener on the domes-
tic hot water system.
If the maximum flow rate of the domestic hot water is too high for a sufficient temperature to be
reached, it is advisable to have a suitable flow rate limiter installed by an Authorised Assistance
Technician.

14 SAVIO PLUS COMBI USER MANUAL


6. Useful Advice
6.1 Central Heating:
• For reasonably economical service install
a room thermostat.
C
• Never shut off the radiator in the area
where the room thermostat is installed.
• If a radiator (or a convector) does not heat
up, check that no air is present in it and
that its valve is open.
• If the ambient temperature is too high, do
not alter the radiator valves. Reduce the
central heating temperature instead by
means of the room thermostat and the
knob (C in Fig. 6.1).

Figure 6.1
6.2 Frost Protection:

• The built in antifreeze system and any additional system protect the boiler from possible
damages due to the icing.
• This system doesn’t guarantee the protection of the whole central heating system.
• In the case that the external temperature may be lower than 32°F it is suggested to leave
the system running setting the room thermostat at a low temperature.
• When the boiler is completely switched off for a long period, it is recommended to empty
completely central heating circuit.

6.3 Periodic Maintenance:

• For efficient and continuous operation of the boiler, it is advisable to arrange maintenance
and cleaning by an Authorised Service Person, at least once a year.
• During the service, the most important components of the boiler will be inspected and
cleaned. This service can be part of a maintenance contract.

In particular, you are advised to have the following checks carried out:
• primary heat and domestic hot water exchanger;
• burner;
• exhaust fume duct and flue;
• pressurization of the expansion vessel;
• filling up of the central heating circuit;
• bleeding of air from the central heating system;
• general check of the appliance’s operation.
• check the condensate trap

SAVIO PLUS COMBI USER MANUAL 15


6. Useful Advice Cont.
6.4 External Cleaning:
• Before performing any cleaning, disconnect the appliance from the electrical mains, using
the dedicated circuit breaker or serviceman’s switch located adjacent to the appliance.
• To clean the external panels, use a cloth soaked in soapy water. Do not use solvents, abra-
sive powders or sponges.
• Do not carry out cleaning of the appliance and/or its parts with readily flammable substanc-
es (for example petrol, alcohols, naphtha, etc.).

6.5 Operational Faults:

If the lock-out signal lamp comes on:


• This indicates that the safety lock-out 1 A C
(Fig. 6.2) has stopped the boiler
• To re-start the boiler, it is necessary to
turn the function selector C in the position
and then press the boiler reset button
2 (Fig. 6.2).
• For the first light up and following main-
tenance procedures for the gas supply, it
may be necessary to repeat the resetting
operation several times so as to remove Figure 6.2
the air present in the pipework.

If noises due to air bubbles are heard during operation:


• You should check that the pressure on the temperature and pressure gauge (Fig. 5.1 on
page 11) is not below the correct setting.
• If required, fill up the system correctly, as described in the section 5.2 of this manual.
• Bleed any air present in the radiators, if necessary.

If the pressure on the temperature and pressure gauge (Figure 5.1 on page 11) has
gone down:
• It is necessary to fill up the appliance with water again, so as to raise the pressure to an
adequate level as described in the section 5.2 of this manual.
• If filling up with water has to be done very frequent, have the system checked for leaks.

16 SAVIO PLUS COMBI USER MANUAL


6. Useful Advice Cont.
If water comes out of the pressure relief valve pipe 3 in Fig. 6.3:
• Check on the temperature and pressure gauge (figure 5.1 on page 12) that the pressure in
the central heating circuit is not close to 3 bars (43.5 psi). In this case, temperature rise in
the circuit can cause the pressure relief valve to open.
• So that this does not happen and to decrease the pressure to a normal value, it is advisable
to vent some of the water in the appliance through the bleed valves present in the heating
system.

Figure 6.3

If water should occasionally leak from the boiler:

• Close the cocks connected to the inlet gas pipe and to the domestic cold water inlet pipe
under the boiler and call an Authorised Service Person.

In case of problems other than those mentioned here, switch off the boiler, as described
in Section 5.6 on page 14 and call a competent and responsible service person.

SAVIO PLUS COMBI USER MANUAL 17


Warranty
For SAVIO Residential
Wall Hung Gas Boilers
FIRST 2 YEARS-WARRANTY FOR SAVIO SERIES ponents to BOYERTOWN, PA, freight pre-paid.
RESIDENTIAL HOT WATER BOILERS: BOYERTOWN BOYERTOWN and SAVIO will not be responsible for:
warrants that itswall hung boiler and casing are free 1. Components that are part of the heating system,
from defects in material and workmanship for 2 years but were not manufactured by SAVIO or BOYERTOWN
from the date of installation. If any part on the boiler is as part of the boiler.
found to be defective within this period, BOYERTOWN 2. The workmanship of the installers of SAVIO boil-
will replace the part free of charge. ers. Furthermore, this warranty does not assume any
liability for unsatisfactory performance caused by im-
FIRST 10 YEARS-WARRANTY FOR SAVIO SERIES proper installation.
RESIDENTIAL HOT WATER BOILERS: SAVIO war- 3. Any costs for labor to remove or replace the faulty
rants that the copper tube heat exchanger of the SAVIO component.
boilers are free from defects in material and workman- 4. Improper boiler application or adjustments, control
ship for 10 years from the date of installation. If the cop- settings, care or maintenance.
per tube heat exchanger is found to be defective within 5. Any damage associated with corrosion or leakage
the first 10 years after installation, BOYERTOWN and due to the use of “non-barrier”, plastic pipe in the heat-
SAVIO will replace the copper tube heat exchanger. ing system.

These warranties are subject to the condition that a *IMPLIED WARRANTIES OF FITNESS FOR A PAR-
heating contractor whose principal occupation is the TICULAR PURPOSE AND MERCHANTABILITY
sale and installation of heating equipment must have SHALL BE LIMITED TO THE DURATION OF THE
installed the boiler. PARTS, WHICH ARE COVERED, EXPRESSED WARRANTY. SAVIO AND BOYER-
consists of all materials supplied by SAVIO, identified TOWN EXPRESSLY DISCLAIM AND EXCLUDE ANY
by BOYERTOWN’s part numbers in its literature. Other LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL
parts supplied by the installer carry their own warranty DAMAGES FOR BREACH OF ANY EXPRESSED OR
and each manufacturer has responsibility for its own IMPLIED WARRANTY.
products.
THIS WARRANTY GIVES YOU SPECIFIC LEGAL
NOTE: ANY PART, WHICH IS REPLACED UNDER RIGHTS, AND YOU MAY HAVE OTHER RIGHTS
WARRANTY, CARRIES ONLY THE UNEXPIRED THAT VARY FROM STATE TO STATE.
PORTION OF THE ORIGINAL WARRANTY.
For prompt warranty service, notify the installer, who,
OWNER RESPONSIBILITIES: in turn, will notify the distributor from whom the boiler
1. Provide for proper installation, which includes pres- was purchased. If this does not result in corrective ac-
sure relief and pressure reducing valves and high limit tion, contact SAVIO through BOYERTOWN Hydronic
safety controls on closed systems. Technologies (Address Below) with details in support
2. Provide qualified periodic service to prolong proper of the warranty claim. All claims must be processed
operation and service. through proper trade channels. Contact with SAVIO di-
3. Insure that boiler is installed in accordance with all rectly is not recommended for rapid claim settlement.
codes and ordinances.
4. This warranty does not apply to boilers, which are BOYERTOWN Furnace Co.
subject to misuse, abuse, neglect, alteration, accident, PO Box 100
excessive temperature, excessive pressure, or corro- Boyertown,PA 19512
sive water or atmosphere. 1-610-369-1450
5. Owner will be responsible for return of faulty com- www.boyertownfurnace.com

SAVIO BOILER WARRANTY REGISTRATION


IMPORTANT., Registration required. To gain complete warranty
Protection, fill in and mail this card, within 1 year of installation to the address listed below

NAME:____________________________________ ADDRESS:____________________________
CITY:______________________ STATE:________ ZIP:______________
BOILER SERIAL NO.: _______________________ DATE OF INSTALL:_____________________
NAME OF INSTALL CO.:_____________________ ADDRESS:____________________________
CITY:______________________ STATE:________ ZIP:____________
RETURN TO: BOYERTOWN, FURNACE CO. PO Box 100 BOYERTOWN, PA 19512 1-610-369-1450