You are on page 1of 14

Sl. NO.

Item Description Unit


Quantity (301) Quantity (322 A)
A B Total C D E Total Quantity

1 132 kV EQUIPMENT
1.1 Power Transformer
i) 50MVA, 132/33kV, 3-ph Auto Transformer with 10% extra oil Nos. 1 1 2 2 1 1 4

Type testing of one no 50 MVA Transformer (type test include impulse Nos. 0 1 1 1 0 0 1
iit test and short circuit test ) (optional to be decided by BSPTCL)
1.2 Circuit Breakers (3 Ph.) 0 0

145KV,1600 A, 31.5 kA SF6 CircuitBreaker with support structure,


marshalling boxes, terminal connectors etc. (The current rating should Nos. 0 0 0 2 1 1 4
i) also conform to the type test report)
145KV,1250 A, 31.5 kA SF6 CircuitBreaker with support structure,
marshalling boxes, terminal connectors etc.
1 1 2
ii)
1.3 Isolators (3 Ph.) Motor operated 0 0

1250A, 31.5 kA , 145 KV Low Level Isolator without earth switch but Nos. 3 2 5 6 3 0 9
i) with insulators, marshalling boxes, terminal connectors etc (Motorised)

1250A, 31.5 kA , 145 KV Low Level Isolator with 1 earth switch but Nos 1 1 0 0 0 0
ii) with insulators, marshalling boxes, terminal connectors etc (Motorised)

1250A, 31.5 kA , 145 KV Low Level Isolator without earth switch but Nos 0 0 0 2 2
with insulators, marshalling boxes, terminal connectors etc (Motorised)
iii) (2 nos shall be normal Horizontal normal DBR type)
1250A, 31.5 kA , 145 KV Low Level Isolator without earth switch but
with insulators, marshalling boxes, terminal connectors etc Nos 0 0 0 1 1
iv) (Motorised)Tandum type
1.4 Current Transformers (1-Ph.) 0 0

600-300-150/1-1-1-1-1A, 31.5kA, 145 KV multicore single phase Nos. 3 3 6 6 3 3 12


Current Transformers(with 5 Core) with 120% extended current rating
i) with marshalling boxes, terminal connectors etc.

120 kV Gap less Surge Arrestors (1-Ph.) withsurge/discharge counters Nos. 3 3 6 6 3 3 12


1.5 and with marshalling boxes, terminal connectors etc (class-III)
1.6 132 KV 8800 pF CVT Single phase Nos. 0 0 0 0 0
ERECTION HARDWARE WITHOUT BPI 0 0
1.7 Hardware, Spacers, bus-bar material, Bay MB, clamps, connectors
including equipment connectors (Suitable for Moose , Moose to 0 0
Zebra/Panther Conductor - as per site requirement), Junction Box,
earthwire, buried cable trenches/ PVC pipes for equipment , all
accessories etc.(these include all materials required for construction of
all bays/ buses with provision of high level 132 KV Isolator whether
specifically mentioned or not) for the following :
132 kV 'Main & Transfer'bus type 0 0
i) Transformer Bay (For 2 bays) Lot 1 1 2 1 1 1 3

ii) Line bays (for 2 bays) Lot 0 0 0 0 0 0

132 kV Bus post Insulators for erection hardware for 2 nos of 132KV Nos. 4 4 8 23 3 3 29
1.8 bays (Quantity to be furnished by tenderer)
2 33 kV EQUIPMENT 0 0
2.1 Circuit Breakers (3 Ph.) 0 0

1250 A, 25 kA Vacuum CB with support structure, marshalling boxes,


terminal connectors etc. (The current rating should also conform to the Nos. 3 3 6 8 4 4 16
i) type test report)
2.2 Isolators (3 Ph.) Manually operated 0 0

1250A, 25 kA Low Level Isolator without earth switch but with Sets 7 6 13 18 9 9 36
i) insulators,marshalling boxes,terminal connectors etc (Double break)

1250A, 25 kA Low Level Isolator with earth switch but with Sets 2 3 5 6 3 3 12
ii) insulators,marshalling boxes,terminal connectors etc (Double break)
2.3 Current Transformers (1-Ph.) 0 0

1200-600-300-150/1-1-1-1-1A, 25 kA , 33 KV multicore single phase Nos. 9 12 21 24 12 12 48


Current Transformers(with 5 Core) with 120% extended current rating
i) with marshalling boxes, terminal connectors etc.

30KV GAPLESS type Surge Arrestors , 1-ph, withsurge/discharge


counters and with marshalling boxes, terminal connectors etc. (class Nos. 9 9 18 24 12 12 48
2.4 -III)
2.5 ERECTION HARDWARE WITHOUT BPI 0 0
Hardware, Spacers, bus-bar material, Bay MB, clamps, connectors 0 0
including equipment connectors (Suitable for Moose Conductor, Moose
to Zebra/Panther- as per site requirement), Junction Box, earthwire,
buried cable trenches/ PVC pipes for equipment , all accessories etc.
(these include all materials required for construction of all bays/ buses
whether specifically mentioned or not) for the following:
33 kV Main & Transfer type 0 0
i) Transformer Bay (For 2 bays) Lot 1 1 2 1 1 1 3
ii) Line/feeder bays (for 6 bays) Lot 1 1 2 1 1 1 3
33 kV Bus Post Insulators for erection hardware (Quqntity to be Nos. 6 6 12 20 8 8 36
2.6 furnished by the tenderer)
2.7 (a) BMK/Junction boxes for 132 KV new bay as per requirement Nos. 0 0 0 2 1 1 4
2.7 (b) BMK/Junction boxes for 33 KV new bay as per requirement Nos. 0 0 0 8 4 4 16

Material for replacement of conductor in 33 KV side of 50 MVA Power Meters 0 0 0 0 0


2.8 transformer (Jack bus, Droppers, etc.) by single AAAC Bull
3 CONTROL & RELAY PANELS 0 0
3.1 132kV (Duplex Panels) 0 0

132/33KV, Transformer control & relay panels with Numerical type of


differential protection and Numerical E/F-O/C relays complying IEC Sets 1 1 2 2 1 1 4
61850 and 0.2s class energy meters on both HV & LV sidewithout auto
i) reclose etc.

132 KV, Line control & relay panels with Numerical type of distance Sets 0 0 0 0 0
protection and Numerical E/F-O/C relays complying IEC 61850 and
iii) 0.2s class energy meters on both HV & LV sidewithout auto reclose etc.
3.2 33kKV Simplex Panels 0 0

33KV Line control & relay panels with Numerical type of E/F-O/C relays 2 3 5 6 3 3 12
complying IEC 61850 and 0.2s class energy meter etc.
Relay Test Kit Nos. 1 1 2 1 1 1 3

132 KV PLCC equipments (matching with other end of the 0 0 0 0 0


4 transmission line)
a) 1250 A, 0.5/1.0 mH line traps Nos. 0 0 0 0 0 0 0

b) Coupling device Nos. 0 0 0 0 0 0 0

c) H.F Cable KM 0 0 0 0 0 0 0

d) Carrier equipment Nos. 0 0 0 0 0 0 0


e) Protection cuppler Nos. 0 0 0 0 0 0 0

f) Testing and mentanance equipment (print testing kit) Sets 0 0 0 0 0 0 0

Cable along with associated accessories like clamps,glands, lugs and 0 0


5 straight joints etc. (Quantity to be furnished by the tenderer)
5.1 Power Cables(XLPE) 1.1 kV 0 0
a) 1Cx150 sq mm kM 0.1 0.1 0.2 0.2 0.23 0.23 0.66
b) Any other as per requirement kM 0 0
5.2 Power Cables(PVC) 1.1 kV 0 0
a) 4Cx16 sqmm kM 0.4 0.4 0.8 0.2 0.2 0.2 0.6
b) 4Cx6 sqmm kM 0.3 0.3 0.6 0.3 0.3 0.3 0.9
c) 2Cx6 sqmm kM 0.3 0.3 0.6 0.2 0.2 0.2 0.6
d) Any other as per requirement kM 0 0
5.3 Control Cables Copper(PVC) 1.1 kV 0 0
a) 2Cx2.5 sqmm KM 1 1 2 4 2.1 2.1 8.2
b) 3Cx2.5 sqmm KM 0.5 0.5 1 0.1 0.1 0.1 0.3
c) 5Cx2.5 sqmm kM 2 2 4 7 6.6 6.6 20.2
d) 7Cx2.5 sqmm kM 0.5 0.5 1 0.1 0.1 0.1 0.3
e) 10Cx2.5 sqmm kM 0.9 0.9 1.8 3 2.3 2.3 7.6
f) 14Cx2.5 sqmm kM 0.9 0.9 1.8 3 2.3 2.3 7.6
g) 27Cx2.5 sqmm kM 0.3 0.3 0.6 4 2.8 2.8 9.6
h) 4Cx6 sqmm kM 0.5 0.5 1 0.1 0.1 0.1 0.3
i) Any other size as per requirement KM 0 0
33 KV XLPE cable for inter connection between 33 KV side of power KM 0 0.3 0.3 0.45 0 0 0.45
5.4 transformer to 33 KV switchyard with joints.
6 Substation structure MT 20 20 40 60 30 30 120
7 Cable rack (Quantity to be furnished by the tenderer) MT 0.3 0.3 0.6 3 1.5 1.5 6

11KV 90 KN Anti fog typeDisc Insulators(for 2 nos of 132 KV bays and Nos 350 350 700 727 364 364 1455
8 8 nos of 33KV bays)(Quantity to be furnished by the tenderer)

Earthing mat with GI flats of following sizes for risers with spikes as
per design including all materials for comlete earthing of the 0 0
substation (Quantity to be furnished by the tenderer) For bay
9 extension portion
MT 6 6 12 23 11 11 45
a) i) 75*12mm GI flats for equipments, columns and aux structures
ii) 50*6mm GI Flats for all others MT 3 3 6 9 5 5 19
M.S.Rod of 40 mm suitable sizes as required as per approved design as MT 2.5 2.5 5 7 4 4 15
b) per IEEE80 & IS
c) Materials for earthing for 50 MVA transformer MT 1.5 1.5 3 3 2 2 7
10 Earthing pits with supply of all materials including base plate Lot 1 1 2 1 1 1 3

Overhead shielding against lightning by galvanised steel wires & Lot 1 1 2 1 1 1 3


11 fittings as required.

Supply of material for change of complete Bus bar with extension LS 0 0 0 0 0 0 0


of bus system (main and transfer bus) with all jumpers, clamps and
12 connectors for 5 nos of 132 KV bays and 8 nos of 33 KV bays
Supply of AAC bull conductor to Replace the existing 33 kv Main bus
conductor
Meter 0.4 0.4 0.8 0 0 0 0

13 i) 300 AH, 250 V, VRLA battary set. Sets 0 0 0 0 0 0 0

ii) Battery charger for charging of 300 AH, 250V, VRLA battary set. Sets 0 0 0 0 0 0 0
14 Wheel/trolley mounted fire extingusher 0
a) 22.5 Kg. DCP type No. 2 2 4 2 2 2 6
b) 22.5 Kg. CO2 type No. 2 2 4 2 2 2 6
c) Bucket with stand having 5 nos .in each Set Sets 5 2 7

Light fittings 400 Watts with CG Box, lamps etc complete (bajaj cat.
15 a) ref. BGENF-14 or similar) Bajaj/Philips make with MCB switch board, Sets 5 5 10 10 10 10 30
cable termination at lighting panel/locally complete in all respect for
switch yard lighting.
(b) Lighting panel. No 0 0 0 1 1 1 3
(c) DSLP Complete with conductor. LS 0 0 0 1 1 1 3
16 LT Switch gear. 0 0
i) AC Distribution board. No 1 1 2 1 1 0 2
ii) DC Distribution board. No 1 1 2 1 1 0 2
17 Spares 0 0
A) 132 KV Circuit Breaker 0 0
i) Closing coil Nos. 1 1 2 2 2 2 6
ii) Tripping Coil Nos. 1 1 2 2 2 2 6
iii) Spring Charging Motor Nos. 2 2 4 1 1 1 3
iv) Gas filling device Set 1 1 2
v) Pole assembly Nos. 1 1 2
B) 33KV VCB 0 0
i) Closing coil Nos. 1 1 2 2 2 2 6
ii) Tripping Coil Nos. 1 1 2 2 2 2 6
iii) Spring Charging Motor Nos. 1 1 2 1 1 1 3
iv) Indicating bulb Nos. 100 100 200
v) Indicating bulb holder Nos. 12 12 24
vi) Pole assembly No 1 1 2
C) 132 KV C & R 0
i) 132 KV Ammeter( as fitted in panel) Nos. 5 5 10
ii) 132 KV Voltmeter( as fitted in panel) Nos. 5 5 10
iii) Auxiliary Relay , 3 pole Nos. 5 5 10
D) 33 KV C & R 0
i) 33 KV Ammeter( as fitted in panel) Nos. 5 5 10
ii) 33KV Voltmeter( as fitted in panel) Nos. 5 5 10
iii) Auxiliary Relay , 3 pole Nos. 5 5 10
E) For 50 MVA Transformer 0
i) Bucholz Relay No 1 1 2
ii) OSR No 1 1 2
iii) Winding Temp. Meter No 1 1 2
iv) Oil Temp. Meter No 1 1 2
v) Silica zel Breather set 1 1 2
v) Silica zel ( Sealed Tin) Kg 15 15 30

Supply of 7 nos of 2 tons capacity 5 star rated split AC with stablizer Lot 0 0 0 1 1 0 2
18 i) and necessary materail for Air Conditioning of the control room.

Supply of 12 nos of 2 tons capacity 5 star rated split AC with stablizer Lot 0 0 0
ii) and necessary materail for Air Conditioning of the control room.
Any other item as per the Bidder (Quantity to be furnished by the LS 0 0 0 1 0 1 2
19 tenderer)
Quantity (322 B) Grand Total
of 301, 322A
F G H I J Total Quantity and 322B

1 2 1 1 2 7 13

0 1 0 0 1 3

0 0

3 0 1 1 5 10 14

2
0 0

7 0 2 2 12 23 37

2 0 1 1 3 7 8

0 0 0 2

0 0 0 1

0 0

9 0 3 3 15 30 48

9 0 3 3 15 30 48

6 0 9 15 15
0 0
0 0

0 0
1 1 1 1 1 5 10
1 0 0 0 1 2 2
16 5 3 3 30 57 94
0 0
0 0

4 4 4 4 8 24 46

0 0

9 8 9 9 18 53 102

3 4 3 3 6 19 36

0 0

12 18 12 12 24 78 147

12 12 12 12 24 72 138

0 0
0 0

0 0
1 1 1 1 1 5 10
1 1 1 1 1 5 10
14 9 8 8 26 65 113
3 0 1 1 5 10 14
4 4 4 4 8 24 40

0 200 0 0 0 200 200

0 0
0 0

1 2 1 1 2 7 13

2 0 0 0 3 5 5

0 0

3 4 3 3 6 19 36

1 1 1 1 1 5 10
0 0
4 0 0 0 4 8 8
2 0 0 0 4 6 6
0.5 0 0 0 1 1.5 1.5
4 0 0 0 8 12 12
2 0 0 0 6 8 8
2 0 0 0 3 5 5

0 0

0 0
0.32 0.05 0.23 0.23 0.6 1.43 2.29
0 0
0 0
0.1 0.1 0.2 0.2 0.2 0.8 2.2
0.1 0.2 0.3 0.3 0.2 1.1 2.6
0.1 0.1 0.2 0.2 0.2 0.8 2
0 0
0 0
2.5 1.3 2.1 2.1 3 11 21.2
0.1 0.1 0.1 0.1 0.1 0.5 1.8
5 4 6.6 6.6 10 32.2 56.4
0.1 0.1 0.1 0.1 0.1 0.5 Dispatch Under Process
2 1.2 2.3 2.3 3 10.8 20.2
2 1.2 2.3 2.3 3 10.8 20.2
2.1 2 2.8 2.8 5 14.7 24.9
0.1 0.1 0.1 0.1 0.1 0.5 1.8
0 0
0 0 0 0 0.25 0.25 1
50 20 30 30 90 220 380
3 1 1.5 1.5 6 13 19.6

886 160 364 364 1510 3284 5439

0 0

12 9 11 11 30 73 130
5 4 5 5 12 31 56
6 2 4 4 10 26 46
3 0.1 2 2 5 12.1 22.1
1 1 1 1 1 5 10
1 1 1 1 1 5 10

0 0 0 0 1 1 1

0 0 0 0 0 0 0.8
0 0 0 0 1 1 1
0 0 0 0 1 1 1
0 0
2 2 2 2 2 10 20
2 2 2 2 2 10 20
7

10 10 10 10 10 50 90

1 1 1 1 1 5 8
1 1 1 1 1 5 8
0 0
1 1 0 1 1 4 8
1 1 0 1 1 4 8
0 0
0 0
2 2 2 5 11 19
2 2 2 5 11 19
1 1 1 1 4 11
2
2
0 0
2 2 2 2 8 16 24
2 2 2 2 8 16 24
1 1 1 1 1 5 10
200
24
2
0
10
10
10
0
10
10
10
0
2
2
2
2
2
30

1 1 1 0 3 5

1 1 1

1 1 1 1 1 5 7
Sl. NO. Item Description Unit Qty Unil Rate Total Rate
1 132 kV EQUIPMENT
1.1 Power Transformer
50MVA, 132/33kV, 3-ph Auto Transformer with 10% extra
i) Nos. 1 75000 75000
oil
1.2 Circuit Breakers (3 Ph.) 0

145KV,1600 A, 31.5 kA SF6 CircuitBreaker with support


i) structure, marshalling boxes, terminal connectors etc. (The Nos. 1 21000 21000
current rating should also conform to the type test report)

1.3 Isolators (3 Ph.) Motor operated 0

1250A, 31.5 kA , 145 KV Low Level Isolator without earth


i) switch but with insulators, marshalling boxes, terminal Nos. 1 9500 9500
connectors etc (Motorised)

1250A, 31.5 kA , 145 KV Low Level Isolator with 1 earth


ii) switch but with insulators, marshalling boxes, terminal Nos 1 7500 7500
connectors etc (Motorised)
1.4 Current Transformers (1-Ph.)

600-300-150/1-1-1-1-1A, 31.5kA, 145 KV multicore single


phase Current Transformers(with 5 Core) with 120%
i) Nos. 1 2500 2500
extended current rating with marshalling boxes, terminal
connectors etc.

120 kV Gap less Surge Arrestors (1-Ph.)


1.5 withsurge/discharge counters and with marshalling boxes, Nos. 1 3100 3100
terminal connectors etc (class-III)

1.6 132 KV 8800 pF CVT Single phase Nos. 1 2500 2500

1.7 ERECTION HARDWARE WITHOUT BPI

i) 132 kV 'Main & Transfer'bus type Mtr 2000 110 220000


ii) Transformer Bay (For 2 bays) Mtr 1000 110 110000
iii) Line bays (for 2 bays) Mtr 1000 110 110000

132 kV Bus post Insulators for erection hardware for 2 nos


1.8 Nos. 1 900 900
of 132KV bays (Quantity to be furnished by tenderer)

4 132 KV PLCC equipments (matching with other end of 1 3500 3500


Nos
the transmission line)
a) H.F Cable Mtr 600 8 4800
5.1 Power Cables(XLPE) 1.1 kV
a) 1Cx150 sq mm Mtr 100 18 1800
b) Any other as per requirement Mtr
5.2 Power Cables(PVC) 1.1 kV
a) 4Cx16 sqmm Mtr 300 20 6000
b) 4Cx6 sqmm Mtr 500 15 7500
c) 2Cx6 sqmm Mtr 300 8 2400
d) Any other as per requirement Mtr
5.3 Control Cables Copper(PVC) 1.1 kV
a) 2Cx2.5 sqmm Mtr 1 8 8
b) 3Cx2.5 sqmm Mtr 1 9 9
c) 5Cx2.5 sqmm Mtr 1 11 11
d) 7Cx2.5 sqmm Mtr 1 12 12
e) 10Cx2.5 sqmm Mtr 1 13 13
f) 14Cx2.5 sqmm Mtr 1 15 15
g) 27Cx2.5 sqmm Mtr 1 19 19
h) 4Cx6 sqmm Mtr 1 9 9
i) Any other size as per requirement Mtr
5.4 Cable Glands & Termination In No
a) 2Cx2.5 sqmm Nos 1 145 145
b) 3Cx2.5 sqmm Nos 1 155 155
c) 5Cx2.5 sqmm Nos 1 165 165
d) 7Cx2.5 sqmm Nos 1 175 175
e) 10Cx2.5 sqmm Nos 1 185 185
f) 14Cx2.5 sqmm Nos 1 200 200
g) 27Cx2.5 sqmm Nos 1 210 210
h) 4Cx6 sqmm Nos 1 230 230
6 132KV & 33KV Substation structure MT 1 7200 7200

Earthing mat with GI flats of following sizes for risers with


spikes as per design including all materials for comlete
7 earthing of the substation (Quantity to be furnished by
the tenderer) For bay extension portion

i) 75*12mm GI flats for equipments, columns and aux


a) Mtr 1 75 75
structures
b) ii) 50*6mm GI Flats for all others Mtr 1 55 55
M.S.Rod of 40 mm suitable sizes as required as per
c) Mtr 1 145 145
approved design as per IEEE80 & IS
d) Auxilary Mat 1.5mtrX1.5mtr & eqquipment rise Nos 1 2900 2900
8 300 AH, 250 V, VRLA battary set. Sets

ii) Battery charger for charging of 300 AH, 250V, VRLA 1 25000 25000
Sets
battary set.
9 Junction Box
a) CT Junction Box No. 1 1200 1200
b) CVT junction Box No. 1 1200 1200
11 LT Switch gear.
i) AC Distribution board. No 1 6500 6500
ii) DC Distribution board. No 1 6500 6500
Shield wire including hardware,PG Clamp Cleat type
12 Mtr 1 75 75
Clamp ,Pad type clamp etc
Control Panel Nos 1 4500 4500
Any other item as per the Bidder (Quantity to be
13 LS 644911
furnished by the tenderer)

You might also like