1 BLOCK - A
a 3BHK - 3T 1 16 15.56 248.92 276.58
b 3BHK - 2T 1 16 14.46 231.36 257.07
620.44 620.4
c PENTHOUSE 1 2 18.44 36.87625 40.97
d Common Area 1 41.24 41.24 45.82
2 BLOCK - B
a 3BHK - 3T 1 16 15.56 248.92 276.58
b 3BHK - 2T 1 16 14.46 231.36 257.07
620.44 620.4
c PENTHOUSE 1 2 18.44 36.87625 40.97
d Common Area 1 41.24 41.24 45.82
3 BLOCK - C
a 3BHK - 3T 1 16 15.56 248.92 276.58
b 3BHK - 2T 1 16 14.46 231.36 257.07
620.44 620.4
c PENTHOUSE 1 2 18.44 36.87625 40.97
d Common Area 1 41.24 41.24 45.82
4 BLOCK - D
a 3BHK - 3T 1 16 15.75 251.92 279.91
b 2BHK - 2T 1 16 12.64 202.29 224.77
591.05 591.1
c PENTHOUSE 1 2 18.25 36.50125 40.56
d Common Area 1 41.24 41.24 45.82
5 BLOCK - E
a 1BHK - 1T 1 54 6.43 347.11875 385.69
Common Area 435.67 435.7
b 1 44.99 44.99 49.99
6 CLUB HOUSE
a Club House 1 - - 167.10 185.67 185.67 185.7
J.G.CONSULTANTS
ELECTRICAL ENGINEERS, Signature of the vendor with seal
CHENNAI-17
FALLING WATER PROJECT
“PROPOSED RESIDENTIAL DEVELOPMENTS, PERUNGUDI ” CHENNAI
J.G.CONSULTANTS
ELECTRICAL ENGINEERS, Signature of the vendor with seal
CHENNAI-17
FALLING WATER PROJECT
“PROPOSED RESIDENTIAL DEVELOPMENTS, PERUNGUDI ” CHENNAI
AS PER THE SITE CONSTRAINT THERE ARE 3 NUMBER OF SUBSTATIONS TO BE LOCATED WHICH CONTTRIBUTION ARE LISTED AS BELOW:
ROUND OFF TO
SL.NO SUBSTATION DESCRIPTION AS PER LOAD CLOSURE REQUIRED 500KVA REQUIRED 250KVA
ESTIMAITON TRANFORMER TRANSFORMER TRANSFORMER
CAPACITY
(QTY) (QTY)
1 Substation-1 is designed for Clubhouse & Block-A building loads 806.11 1000 2 0
2 Substation-2 is designed for Block-B & Block-C building loads 1240.88 1250 2 1
3 Substation-3 is designed for Block-D & Block-E building loads 1026.73 1000 2 0
J.G.CONSULTANTS
ELECTRICAL ENGINEERS, Signature of the vendor with seal
CHENNAI-17
FALLING WATER PROJECT
“PROPOSED RESIDENTIAL DEVELOPMENTS, PERUNGUDI ” CHENNAI
Maximum
Total No Demand Total MD Considering Total Nearest D.G set No of D.G set
Sl.No Product Mix No of 85%
apartments of Load in load in Maximum capacity required requirement
apartme KVA(For KVA(for efficiency Demand Load as per the MD in QTY
nts per each typical in KVA(for
Block apartment) apartment) Blocks)
1 BLOCK - A
● 3BHK - 3T 1 16 1 16 18.82
● 3BHK - 2T 1 16 1 16 18.82
88.52 82.5 1
● PENTHOUSE - 3BHK - 3T 1 2 1 2 2.35
● Common Area 1 41.24 41.24 48.52
2 BLOCK - B
● 3BHK - 3T 1 16 1 16 18.82
● 3BHK - 2T 1 16 1 16 18.82
88.52 82.5 1
● PENTHOUSE - 3BHK - 3T 1 2 1 2 2.35
● Common Area 1 41.24 41.24 48.52
3 BLOCK - C
● 3BHK - 3T 1 16 1 16 18.82
● 3BHK - 2T 1 16 1 16 18.82
PENTHOUSE - 3BHK - 3T 88.52 82.5 1
● 1 2 1 2 2.35
● Common Area 1 41.24 41.24 48.52
4 BLOCK - D
● 3BHK - 3T 1 16 1 16 18.82
● 2BHK - 2T 1 16 1 16 18.82
88.52 82.5 1
● PENTHOUSE - 3BHK - 3T 1 2 1 2 2.35
● Common Area 1 41.24 41.24 48.52
5 BLOCK - E
● 1BHK - 1T 1 54 5 270 317.65
370.57 380 1
● Common Area 1 44.99 44.99 52.93
6 CLUB HOUSE
● Club House 1 - - 167.10 196.59 196.59 200 1
J.G.CONSULTANTS
ELECTRICAL ENGINEERS, Signature of the vendor with seal
CHENNAI-17
DETAILED LOAD ESTIMATION
BLOCK -A,B & C
3BHK - 3T : Each apartment LOAD:
Foot 5A Socket 6/16A 6/16A 20A socket 20A socket Calling Exhaust
Light Lamp & Fan 5A Socket along away from 6A socket Telephone TV Data Total
Sl.No Area Description Chandelier socket socket for for A/C for Bell Fan
Points Mirror points with Switch Box the Switch (TV Points) (Others) Geyser (2TR) A/C(1.5TR) points points Points points point Load
Light Box
1 Entrance 1
2 Living 3 1 1 1 1 3 1 1 1
3 Dining 2 1 2 1 1
4 Balcony 2
5 Kitchen 1 1 1 4 2 1
6 Utiliy 1 1 2
7 Passage 1
8 Bed Room-1 2 1 2 3 1 1 1 1
9 Terrace
10 Bed Room-2 2 1 1 2 1 1 1 1
11 Bed Room-Toilet 1 1 1 1 1 1
12 M.Bed Room 2 1 1 2 3 3 1 1 1 2
13 M.Bed Room-Toilet 1 1 1 1 1 1
14 Common Toilet 1 1 1 1 1 1
15 Total No of points 19 5 1 6 14 13 9 4 3 2 3 1 4 4 3 4
Max.Demand in KVA 0.33 0.06 0.19 0.23 0.53 0.49 0.56 2.50 2.81 3.50 4.22 0.04 0.11 - - - 15.56 KVA
21
Foot
Lamp & 5A Socket
Mirror away from 6/16A 6/16A 20A socket 20A socket Calling Exhaust
Light Light Fan 5A Socket along the Switch 6A socket socket socket for for A/C for Bell Fan Telephone TV Data Total
Sl.No Area Description Points Chandelier points with Switch Box Box (TV Points) (Others) Geyser (2TR) A/C(1.5TR) points points Points points point Load
1 Entrance 1 1
2 Living 2 1 1 1 1 3 1 1 1
3 Dining 2 1 2 1 1
4 Balcony 1
5 Kitchen 1 1 1 4 2 1
6 Utiliy 1 2
7 Passage 1
8 Bed Room-1 2 1 2 1 3 1 1 1 1
9 Terrace 1 1
10 Bed Room-2 2 1 1 2 1 1 1 1
11 M.Bed Room 2 1 1 2 2 3 1 1 1 2
12 M.Bed Room-Toilet 1 1 1 1 1
13 Common Toilet 1 1 1 1 1 1
14 Total No of points 18 4 1 6 13 12 9 4 2 2 3 1 2 4 3 4
Max.Demand in KVA 0.32 0.05 0.19 0.23 0.49 0.45 0.56 2.50 1.88 3.50 4.22 0.04 0.06 - - - 14.46 KVA
20
Foot 5A Socket 6/16A 6/16A 20A socket 20A socket Calling Exhaust
Light Lamp & Fan 5A Socket along away from 6A socket Telephone TV Data Total
Sl.No Area Description Points Mirror Chandelier points with Switch Box the Switch (TV Points) socket socket for for A/C for Bell Fan Points points point Load
(Others) Geyser (2TR) A/C(1.5TR) points points
Light Box
1 Foyer 1 1
2 Living-1(Lounge) 1 1 1 3 1 1
Living-2(Family
3 Lounge) 2 1 1 1 1 1
4 Dining 1 1 1 1
5 Balcony 2
6 Kitchen 1 1 1 4 2 1
7 Utiliy 1 1 2
8 Store 1
9 Passage 2
10 Terrace 1
11 Bed Room-1 2 1 2 3 1 1 1 1
12 Bed Room-1 Toilet 1 1 1 1 1 1
13 Bed Room-2 2 1 1 2 1 1 1 1
14 Bed Room-2 Toilet 1 1 1 1 1 1
15 M.Bed Room 2 1 1 2 2 3 1 1 1 1
16 M.Bed Room-Toilet 1 1 1 1 1 1
17 Bed Room-3 2 1 2 1 3 1 1 1 2
18 Common Toilet 1 1 1 1 1 1
19 Pooja room 1 1
20 Total No of points 26 6 1 8 17 13 12 4 4 2 4 1 5 5 4 6
Connected Load in
Watts of each 28 18 300 60 60 60 100 1000 1500 2800 2250 60 45 - - -
21
22 Total CL in Watts 728 108 300 480 1020 780 1200 4000 6000 5600 9000 60 225 0 0 0 29501 W
23 Total CL in KW 0.73 0.11 0.30 0.48 1.02 0.78 1.20 4.00 6.00 5.60 9.00 0.06 0.23 0 0 0 29.50 KW
24 Total CL in KVA 0.91 0.14 0.38 0.60 1.28 0.98 1.50 5.00 7.50 7.00 11.25 0.08 0.28 - - - 36.88 KVA
25 Diversity factor 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 - - - 0.50 D.f
Max.Demand in KVA 0.46 0.07 0.19 0.30 0.64 0.49 0.75 2.50 3.75 3.50 5.63 0.04 0.14 - - - 18.44 KVA
26
COMMON AREA :
● Total Max.Demand in KVA for Block A (Assumed 1 KVA per apartment/Flat) = 34.00 KVA
● Total Max.Demand in KVA for Common Area = 41.24 KVA
● Total Max.Demand in KVA for Block A apartment & Common Area = 75.24 KVA
● Considering 85% efficiency of DG set for 100 % Load = 0.85 ף
● Minimum DG set capacity required as per the above MD for Common Area for each Block = 88.52 KVA
Nearest DG set Capacity selected for each block = 82.5 KVA each
Total No.of DG sets = 3 Nos
DETAILED LOAD ESTIMATION
3BHK - 3T : Each Apartment Load:
1 Entrance 1
2 Living 3 1 1 1 1 3 1 1 1
3 Dining 2 1 2 1 1
4 Balcony 2
5 Kitchen 1 1 1 4 2 1
6 Utiliy 1 1 2
7 Passage 1
8 Bed Room-1 2 1 2 3 1 1 1 1
9 Terrace
10 Bed Room-2 2 1 1 2 1 3 1 1 1
11 Bed Room-Toilet 1 1 1 1 1 1
12 M.Bed Room 2 1 1 2 3 3 1 1 1 2
13 M.Bed Room-Toilet 1 1 1 1 1 1
14 Common Toilet 1 1 1 1 1 1
15 Total No of points 19 5 1 6 14 13 12 4 3 2 3 1 4 4 3 4
Max.Demand in KVA 0.33 0.06 0.19 0.23 0.53 0.49 0.75 2.50 2.81 3.50 4.22 0.04 0.11 - - - 15.75 KVA
21
Foot
Lamp & 5A Socket 6/16A
Mirror 5A Socket away from 6/16A socket 20A socket 20A socket Calling Exhaust Telepho
Light Light along with the Switch 6A socket socket for for A/C for Bell Fan ne Data
Sl.No Area Description Points Chandelier Fan points Switch Box Box (TV Points) (Others) Geyser (2TR) A/C(1.5TR) points points Points TV points point Total Load
1 Entrance 1 1
2 Living 2 1 1 1 1 3 1 1 1
3 Dining 2 1 2 1 1
4 Balcony 1
5 Kitchen 1 1 1 4 2 1
6 Utiliy 1 2
7 Passage 1
8 Bed Room-1 2 1 2 1 1 1 1
12 M.Bed Room 2 1 1 2 2 3 1 1 1 2
1
13 M.Bed Room-Toilet 1 1 1 1 1
14 Common Toilet 1 1 1 1 1 1
15 Total No of points 15 3 1 5 10 11 6 4 2 2 2 1 3 3 2 3
Max.Demand in KVA 0.26 0.03 0.19 0.19 0.38 0.41 0.38 2.50 1.88 3.50 2.81 0.04 0.08 - - - 12.64 KVA
21
Foot 5A Socket 5A Socket 6/16A 6/16A 20A socket 20A socket Calling Exhaust Telepho
Light Lamp & away from 6A socket socket Data
Sl.No Area Description Points Mirror Chandelier Fan points along with the Switch (TV Points) socket for for A/C for Bell Fan ne TV points point Total Load
Switch Box (Others) (2TR) A/C(1.5TR) points points Points
Light Box Geyser
1 Foyer 1 1
2 Living-1(Lounge) 1 1 1 3 1 1
Living-2(Family
Lounge) 2 1 1 1 1 1
3 Dining 1 1 1 1
4 Balcony 2
5 Kitchen 1 1 1 4 2 1
6 Utiliy 1 1 2
7 Store 1
8 Passage 2
9 Terrace 1
10 Bed Room-1 2 1 2 3 1 1 1 1
11 Bed Room-1 Toilet 1 1 1 1 1 1
12 Bed Room-2 2 1 1 2 1 1 1 1
13 Bed Room-2 Toilet 1 1 1 1 1 1
14 M.Bed Room 2 1 1 2 2 3 1 1 1 1
15 M.Bed Room-Toilet 1 1 1 1 1 1
16 Bed Room-3 2 1 2 1 1 1 1 2
17 Common Toilet 1 1 1 1 1 1
18 Pooja room 1 1
19 Total No of points 26 6 1 8 17 13 9 4 4 2 4 1 5 5 4 6
Connected Load in
Watts of each 28 18 300 60 60 60 100 1000 1500 2800 2250 60 45 - - -
20
21 Total CL in Watts 728 108 300 480 1020 780 900 4000 6000 5600 9000 60 225 0 0 0 29201 W
22 Total CL in KW 0.73 0.11 0.30 0.48 1.02 0.78 0.90 4.00 6.00 5.60 9.00 0.06 0.23 0 0 0 29.20 KW
23 Total CL in KVA 0.91 0.14 0.38 0.60 1.28 0.98 1.13 5.00 7.50 7.00 11.25 0.08 0.28 - - - 36.50 KVA
24 Diversity factor 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 - - - 0.50 D.f
Max.Demand in KVA 0.46 0.07 0.19 0.30 0.64 0.49 0.56 2.50 3.75 3.50 5.63 0.04 0.14 - - - 18.25 KVA
25
5A Socket 6/16A
5A Socket away from 6A socket
Light Foot Lamp & Chandelier Fan points along 6/16A socket 20A socket 20A socket Calling Exhaust Telephone Data
Sl.No Area Description with socket for A/C for Bell Fan TV points Total Load
Points Mirror Light Switch Box the Switch (TV Points) (Others) for (2TR) A/C(1.5TR) points points Points point
Box Geyser
1 Entrance 1 1
2 Living 2 1 1 1 1 3 1 1 1
3 Dining 1 1 1
4 Kitchen 1 1 1 4 2
5 Bed Room 2 1 1 2 1 3 1 1 1 2
6 Bed Room-Toilet 1 1 1 1 1 1
7 Total No of points 8 2 1 4 6 7 6 2 1 0 2 1 1 2 2 2
Connected Load in 28 18 300 60 60 60 100 1000 1500 2800 2250 60 45 - - -
8 Watts of each
9 Total CL in Watts 224 36 300 240 360 420 600 2000 1500 0 4500 60 45 0 0 0 10285 W
10 Total CL in KW 0.22 0.04 0.30 0.24 0.36 0.42 0.60 2.00 1.50 0.00 4.50 0.06 0.05 0 0 0 10.29 KW
11 Total CL in KVA 0.28 0.05 0.38 0.30 0.45 0.53 0.75 2.50 1.88 0.00 5.63 0.08 0.06 - - - 12.86 KVA
12 Diversity factor 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 - - - 0.50 D.f
Max.Demand in KVA 0.14 0.02 0.19 0.15 0.23 0.26 0.38 1.25 0.94 0.00 2.81 0.04 0.03 - - - 6.43 KVA
13
CL in
Watts of Total CL in Total CL Total CL Diversity Total MD load in KVA
Sl.no Description No of QTY each Watts in KW in KVA Factor
1 Access Lobby(Ground Floor)=2 x 18W 4 36 144 0.144 0.18 0.8 0.14
2 9 Floors Lift Lobby (Corrioder) Light points = (10x4) 40 36 1440 1.44 1.8 0.8 1.44
3 stilt + 9 Floors Lift Shaft Light points = (10x2) 20 9 180 0.18 0.225 0.8 0.18
4 Lift fan Points 2 60 120 0.12 0.15 0.8 0.12
5 9 floors lift shaft socket 6A socket = 9+1 10 60 600 0.6 0.75 0.8 0.60
6 stilt + 9 Floors
Security SystemStaircase Light Point
& PA System, = (11X3)
Landscape Lighting, Water Cascade , Facade 33 36 1188 1.188 1.485 0.8 1.19
7 Lighting & others etc. Watts ( Assumed) 1 1000 1000 1 1.25 0.8 1.00
8 Lift load in Watts(For Passenger usage) 2 10000 20000 20 25.00 0.8 20.00
9 Lift load in Watts(For Service usage) in future 1 10000 10000 10 12.50 0.8 10.00
10 Bore well pumps 1 1500 1500.00 1.50 1.88 0.8 1.50
11 Booster Pump 1 7500 7500.00 7.50 9.38 0.8 7.50
12 Car Parking Lighting Load considered 34 28 952.00 0.95 1.19 0.8 0.95
13 Terrace Light(1 x 26W) 14 26 364.00 0.36 0.46 0.8 0.36
Total Max.Demand KVA in Common Area Block - E = 44.99
● Total Max.Demand in KVA for Block-E(By taking ACCL feature 5KVA per apartment) 270 KVA
● Total Max.Demand in KVA for Common Area 44.988 KVA
● Total Max.Demand in KVA for Block-E = Overall Apartment load + Common Area 314.988 KVA
● Considering 85% efficiency of DG set for 100 % Load 0.85
● Minimum DG set capacity required as per the above MD for Block - E 370.574118 KVA
Nearest DG set Capacity selected for block-E 380 KVA
Total No.of DG sets = 1 Nos
DETAILED LOAD ESTIMATION
CLUB HOUSE ELECTRICAL LOAD:
CL in
Sl.no Description No of Watts of Total CL Total CL Total CL Diversity Total MD load in KVA
QTY in Watts in KW in KVA Factor
each
1 STILT FLOOR
1 x 28 watts 17 18 306 0.306 0.3825 0.8 0.31
5 A socket 5 60 300 0.3 0.375 0.8 0.30
2 1st FLOOR
1 x 18 watts 15 18 270 0.27 0.3375 0.8 0.27
2 x 18 watts 27 36 972 0.972 1.215 0.8 0.97
4 x 14 watts 27 56 1512 1.512 1.89 0.8 1.51
5 A socket 12 60 720 0.72 0.9 0.8 0.72
2 ton A/C 7 7000 49000 49 61.25 0.8 49.00
1.5 ton A/C 3 3500 10500 10.5 13.125 0.8 10.50
3 2nd FLOOR
1 x 18 watts 8 18 144 0.144 0.18 0.8 0.14
2 x 18 watts 15 36 540 0.54 0.675 0.8 0.54
4 x 14 watts 8 56 448 0.448 0.56 0.8 0.45
5 A socket 12 60 720 0.72 0.9 0.8 0.72
2 ton A/C 1 7000 7000 7 8.75 0.8 7.00
1.5 ton A/C 5 3500 17500 17.5 21.875 0.8 17.50
SWIMMING POOL 6 50 300 0.3 0.38 0.8 0.30
4 3rd FLOOR
1 x 18 watts 4 18 72 0.072 0.09 0.8 0.07
2 x 18 watts 17 36 612 0.612 0.765 0.8 0.61
4 x 14 watts 27 56 1512 1.512 1.89 0.8 1.51