(NTS: Apply TVSS at service entrance equipment, motor control centers and at 480V
panels more than 50 cable feet from a TVSS protected bus. Apply TVSS at all
panelboard(s) connected to the secondary of distribution transformers or at separately
derived systems. Show TVSS locations on electrical diagrams and schedules.)
PART 1 - GENERAL
1.01 DESCRIPTION:
A. Provide transient voltage surge suppression (TVSS) components integral to the electrical
distribution system equipment. The distribution system includes switchgears,
switchboards, motor control centers and 380V/220V distribution panels.
B. The components shall provide protection for electrical and electronic devices against the
damaging effects of surges, transients and electrical line noise.
(NTS: Select and list specification sections for inserting into this subsection based on the
following:
1. Specification sections that contain products and construction that the reader might
expect to find in this section BUT are specified elsewhere.
2. Specification sections referenced in the body of this section.)
1.02 RELATED WORK:
(NTS: Identify specification sections which are to utilize surge protection components.)
A. Section 16050: Electrical Work - General
E. Military Standard:
F. Equivalent British/European codes and standards may be used; however, the equivalency
shall be demonstrated and submitted by the Contractor and approved by the CM/CS.
1.04 SUBMITTALS:
3. List all required installation criteria including circuit breaker trip rating to meet
UL 1449, Second Edition.
4. Identify all cable sizes, distance limits and accessory devices when TVSS units
are to be provided in separate enclosures, where applicable.
2. Pack spare parts in containers bearing labels clearly designating contents and
pieces of equipment for which intended.
3. Deliver spare parts after installation but before start-up of system as specified.
Deliver to Owner after completion of work.
C. Storage:
PART 2 - PRODUCTS
2.01 MANUFACTURERS:
2. Eaton/Cutler-Hammer.
3. Siemens.
2.02 PROVISIONS:
A. Environmental Requirements:
B. Electrical Requirements:
2. UL 1449 clamping voltage or the suppressed voltage rating (SVR) shall not
exceed the following:
3. The ANSI/IEEE C62.41-1991 Category C3 let through voltages shall not exceed
the following
(NTS: Service entrance voltage of 208V – use 480V surge protection ratings).
380V Service Entrance 250 kA per phase
at each structure 125 kA per mode
B. Each unit shall include a high-performance EMI/RFI noise rejection filter. Noise
attenuation for electric line noise shall be 50 dB at 100 kHZ.
C. TVSS shall provide surge current diversion between each phase conductor and the neutral
conductor, between each phase conductor and ground and between the neutral conductor
and ground. For delta systems, the TVSS shall have components directly connected
between each phase conductor and between each phase conductor and ground.
D. The TVSS shall provide a low impedance path for surge current using over sized
conductors with equal impedance paths to each suppression element. Plug-in style
connections or printed circuit boards for use in the path of surge current shall not be used.
E. Operating Parameters
2. Provide with a noise filtering system capable of managing noise levels produced
by electro-magnetic interference and radio frequency interference. The noise
filtering system shall reject a minimum of 50db at 100 kHz as measured by the 50
Ohm Insertion Loss Method (Military Standard 220A).
3. The parallel system components shall operate over a minimum frequency range of
47 hertz to 63 hertz.
4. The TVSS components shall limit total harmonic distortion produced to less than
one percent.
6. Each unit shall be factory tested at the maximum continuous operating voltage
and short circuit tested, prior to delivery.
F. Product Components:
3. Provide red and green solid-state status lights which indicate operational status of
each unit and visual diagnostic monitoring of each component and module.
Provide audible alarm to activate on fault condition, with a silence switch and
push-to-test alarm switch.
4. Provide surge counter with battery backup to retain memory upon loss of AC
power.
5. Provide remote status monitoring with form C dry contacts monitoring all phases.
(NTS: Utilize paragraph A for large projects. At this time, Section 01680 has not been
issued as a Masterspec.)
A. Provide in accordance with Section 01680.
B. Perform factory performance testing on each unit. The test to consist of the following:
2. Current test.
2. ANSI/IEEE C62.45.
B. Provide one spare protection module of each type for on-site spare parts purposes.
PART 3 - EXECUTION
3.01 INSPECTION:
A. Visually inspect delivered unit(s) and accessories for conformance with drawings and
specifications. Replace all components found to exhibit defects.
3.02 INSTALLATION:
A. Install unit in compliance with the manufacturers printed instructions. All electrical
installation work shall be in accordance with UL Listing Requirements and applicable
National or Local Electrical Codes.
B. For units mounted adjacent to electrical distribution equipment, verify conduit and wire
for the TVSS components are as specified by the TVSS manufacturer and installed in
strict accordance with the National Electric Code.
END OF SECTION