General

Service Alert

Fan coils
ZN regulation improvement

UNT-SVB08A-E4
ZN regulation improvement

1. Introduction
Control of fan coils equipped with a ZN control and a thermal actuator valve can
be improved through the following modification.

2. Units potentially affected


Fan coils UNITRANE and HFO/R manufactured before september 2003, equipped
with a ZN control and a thermal actuator valve.

3. Discussion
The following abnormal operations may occur:

ƒ wide discharge temperature range,


ƒ low minimum discharge temperature,
ƒ electric heater ON during cooling mode operation.

The first two points only affect comfort while the third one has an impact on energy
consumption. Since none of them concern safety or performance of the unit, the
modification must be done only when required by the customer.

These inconveniences can be solved by replacing the thermal motor by a 3 point


one and modifying ZN parameters.

4. Action
First of all, download from http://stadoc/menupublic/IndexTechnicalService.asp
(Software download/ Fan Coils) the 6 configuration files onto your laptop where
ROVER is installed.

You should only use ROVER versions 4 or 5 with the last Service Pack and
relating Patch (you can download them from the following page:
http://tranenetlax1s/GCC_Downloads/Home/Downloads/Rover.asp).

2- UNT-SVB08A-E4
ZN regulation improvement

First step: motor replacement

Re Replace thermal motor by 3 point motor and modify the cabling in accordance with
the diagram provided with the KIT.

Program to
Coil type Drawing #
download
23094218 (UNITRANE or HF*)
2 pipes cooling 23094114 (UNITRANE or HF*) PG51
23094110 (UNITRANE or HF*)

23094218 (UNITRANE or HF*)


2 pipes heating 23094114 (UNITRANE or HF*) PG52
23094110 (UNITRANE or HF*)

23091220 (UNITRANE)
2 pipes cooling with heater 23094116 (UNITRANE) PG53
23094112 (HF*)

23094219 (UNITRANE or HF*)


2 pipes reversible with 2 or
23094115 (UNITRANE or HF*) PG54
3 way valve
23094111 (UNITRANE or HF*)

2 pipes reversible with 23094221 (UNITRANE)


heater and 2 or 3 way 23094117 (UNITRANE) PG56
valve 23094113 (HF*)

23094218 (UNITRANE or HF*)


4 pipes 23094114 (UNITRANE or HF*) PG58
23094110 (UNITRANE or HF*)

Second step: configuration file

Connect ROVER to the unit (or network when available) using your ROVER
Service Pack.

a) Save the current parameter file of the unit

In the Active Group tree, click the device. The Active Device View appears in the
workspace.
Click the Configuration Button in the Active Device View. The Configuration dialog
box appears.
From the File menu of the Configuration dialog box, choose Save. The Save As
dialog box appears.
Select the location and type a file name in the Save dialog box.
Click Save. The configuration file (.RCF) is saved in the location you specified.

b) Identify the program you need to download on the unit

From the Configuration dialog box, select the Unit tab. The Unit Configuration view
appears.
Compare this view to the ones of the Annex 1 in order to determine which program
you need to download on the device.

3- UNT-SVB08A-E4
ZN regulation improvement

c) Note down all the customized parameters


You may have customized some parameters. Downloading the configuration file
will put all parameters to default value. Thus in order to retrieve the customization,
you shall note down all the parameters different from the configuration file default
value in order to enter them back afterwards.

Please find attached in Annex 2 the form to note down the values.

d) Download the proper program

IT IS MANDATORY TO DOWNLOAD THE PROGRAM BECAUSE IT CONTAINS


SOME PARAMETERS NOT AVAILABLE FROM ROVER WHICH HAVE A
GREAT IMPACT ON CONTROL IMPROVEMENT.

From the File menu of the Configuration dialog box, choose Open. The Open
dialog box appears.
Select the location and file name in the Open dialog box.
Click Open and then Download on the Configuration dialog box. A message box
appears to confirm the download.

e) Modify the customized parameters


From the Configuration dialog box, go through Setpoints, Inputs, Fan and Other
tabs in order to enter the customized parameters previously noted.
Click Download. A message box appears to confirm the download.

f) Save the new parameter file of the unit

From the File menu of the Configuration dialog box, choose Save. The Save As
dialog box appears.
Select the location and type a file name in the Save dialog box.
Click Save. The configuration file (.RCF) is saved in the location you specified.
Click Close.

NB: If some units have the same customized parameters and the same program,
you can follow the here above procedure for the first one and download its file to
the following instead of points d) and e).

5. Part
Order one KIT1095E per unit, it contains:
ƒ 1 three point actuator
ƒ 1 seven wire connector
ƒ 2 lead connections
ƒ revised electrical diagram (sticker to cut and place on the unit diagram)

6. Labor coverage
Motor replacement: 30 minutes per unit

Configuration (test included): 1 hour per unit

4- UNT-SVB08A-E4
ZN regulation improvement

Appendix 1
a) PG51 (2 pipes cooling only)

b) PG52 (2 pipes heating only)

5- UNT-SVB08A-E4
ZN regulation improvement

c) PG53 (2 pipes cooling with electric heater)

d) PG54 (2 pipes reversible with 2 or 3 way valve)

6- UNT-SVB08A-E4
ZN regulation improvement

e) PG56 (2 pipes reversible with heater and 2 or 3 way valve)

f) PG58 (4 pipes)

7- UNT-SVB08A-E4
6. Appendix 2

Unit Values
Default
Configuration Menu
Values Unit ………………… Unit ………………… Unit ………………… Unit …………………

Setpoints Default Setpoints Unoccupied Cooling 30 °C

Occupied Standby Cooling 25 °C

Occupied Cooling 21,7 °C

Occupied Heating 20 °C

Occupied Standby Heating 16,7 °C

Unoccupied Heating 13,9 °C


Setpoint Limits Cooling Setpoint High Limit 28,3 °C

Cooling Setpoint Low Limit 13,9 °C

Heating Setpoint High Limit 26,1 °C

Heating Setpoint Low Limit 12,2 °C


Inputs Binary I2 Condensate Overflow

Not Used yes

Device Contacts Normally Open


Binary I3 Occupancy

Generic yes

Not Used

Device Contacts Normally Open yes


Analog I3 Outdoor Air Temperature yes

Generic Temperature

8- UNT-SVB08A-E4
Unit Values
Default
Configuration Menu
Values
Unit ………………… Unit ………………… Unit ………………… Unit …………………

Fan Default Fan Off


Speed, Cooling
Low

Medium

High

Auto yes
Default Fan Off
Speed, Heating
Low

Medium

High

Auto yes
Enable Zone Sensor Fan Switch yes
Other Space Effective Value
Temperature
Sensor Offset 0 °C
Hardwired Setpoint Effective Value

Offset 0 °C
Timers Fan Run Time
Maintenance Required Time
300 h
Setpoint
Occupied Bypass Time 120 mn

Power-up Control Wait 0s

9- UNT-SVB08A-E4
Literature Order Number UNT-SVB08A-E4
Date 06-04
New
www.trane.com Stocking Location Europe

Trane has a policy of continuous product and product data improvement and reserves the right to change
For more information contact design and specifications without notice. Only qualified technicians should perform the installation and
your local sales office servicing of equipment referred to in this publication.
or e-mail us at comfort@trane.com
10 - UNT-SVB08A-E4