Professional Documents
Culture Documents
(UNIT-II)
FORM IV A
[Regulation 4 (C) (IV)]
CERTIFICATE OF MANUFACTURE AND RESULT OF TESTS IN LIEU OF ORIGINAL TEST CERTIFICATES
It is hereby certified that original Test Certificate contain the following information in respect of the material used in the manufacture of The
Boiler Or Components There Of Bearing Maker’s Number IEPL/IBR/3645 According To Drawing No. - A1-33065-MEC-104, REV.00.
CHEMICAL ANALYSIS % PHYSICAL PROPERTIES Name of
LENGTH, HEAT/ STEEL NAME OF Inspecting
NAME QTY. SPECIFI- CERTIFICATE NO. HEAT ELONGATION%
OD & CAST MAKING STEEL Y.S UTS BEND Authority
OF PART CATION & DATE TREAT- % C % SI % MN %P %S & GAUGE
THK. NO. PROCESS MAKER MPa MPa TEST
MENT LENGTH
DN 40 X WELL
HOT MAHARASTRA MSL-
SCH.80 X NORMAL 31.2% KNOWN
BARE PIPE 08 Y-118 FINISHED SA335 P22 SEAMLESS 7/IBR/0275/13/2016 0.10 0.22 0.45 0.016 0.004 441.91 565.62 OK
100MM
SEAMLESS LIMITED DT.-24.04.2016
ISED 50 PIPE
LG. MAKER
DN 40 X 6-0600 & WELL
SCH.80 X G- ELECTRIC SA182 F22 CHW FORGE NWD/1700984/01 NORMAL 25% KNOWN
FLANGES 04 0.10 0.20 0.38 0.003 0.001 497 619 OK
CL.300 X G7756A/ FURNACE CL.3 PVT. LTD. DT.-30.08.2017 ISED 4D FORGE
WNRF G7757 MAKER
6-0600 & WELL
DN 40 X KNOWN
BLIND G- ELECTRIC SA182 F22 CHW FORGE NWD/1700984/01 NORMAL 25%
04 CL.300 X 0.10 0.20 0.38 0.003 0.001 497 619 OK
FLANGE G7756A/ FURNACE CL.3 PVT. LTD. DT.-30.08.2017 ISED 4D FORGE
BLRF
G7757
MAKER
DN 40 X 6-0600 & WELL
SCH.80 X G- ELECTRIC SA182 F22 CHW FORGE NWD/1700984/01 NORMAL 25% KNOWN
FLANGES 01 0.10 0.20 0.38 0.003 0.001 497 619 OK
CL.300 X G7756A/ FURNACE CL.3 PVT. LTD. DT.-30.08.2017 ISED 4D FORGE
WNRF G7757
MAKER
6-0600 & WELL
DN 40 X KNOWN
BLIND G- ELECTRIC SA182 F22 CHW FORGE NWD/1700984/01 NORMAL 25%
01 CL.300 X 0.10 0.20 0.38 0.003 0.001 497 619 OK
FLANGE G7756A/ FURNACE CL.3 PVT. LTD. DT.-30.08.2017 ISED 4D FORGE
BLRF
G7757
MAKER
141.3 OD DIRECTOR OF
ELECTRIC AKSHAR
X SCH.40 SA 335 JHF-702/IIIA/2017/20675 NORMAL BOILER
FINS TUBE 04 E65499 ARC PRECISION 0.11 0.17 0.400 0.010 0.002 393.21 526.28 39 ---
X 7221 P22 CS DT.-13/10/2017 ISED GUJARAT
FURNACE TUBES PVT LTD
MM LG. STATE
Page 1 of 3
ISHAN EQUIPMENTS PVT. LTD.(UNIT-II)
141.3 OD E65499 0.11 0.17 0.400 0.010 0.002 393.21 526.28 39 --- DIRECTOR OF
ELECTRIC AKSHAR JHF-
X SCH.40 SA 335 P22 NORMAL
FINS TUBE 52 ARC PRECISION 702/IIIA/2017/20675 BOILER
X 6480 CS ISED
K80152 FURNACE TUBES PVT LTD DT.-13/10/2017 GUJARAT STATE
MM LG. 0.12 0.20 0.450 0.009 0.002 383.45 532.12 39.2 ---
141.3 OD DIRECTOR OF
ELECTRIC AKSHAR JHF-
X SCH.40 SA 335 P22 NORMAL
FINS TUBE 04 E65499 ARC PRECISION 702/IIIA/2017/20675 0.11 0.17 0.400 0.010 0.002 393.21 526.28 39 --- BOILER
X 7221 CS ISED
FURNACE TUBES PVT LTD DT.-13/10/2017 GUJARAT STATE
MM LG.
DIRECTOR OF
ELECTRIC
180° SR DN 125 X SA 234 CSA/163/17-18 NORMAL BOILER
54 C/877 ARC CSA FITTINGS 0.078 0.025 0.42 0.011 0.004 348.10 484.34 34.00 ---
BEND SCH.40 WP22 CL1 DT.-23/02/2017 ISED MAHARASTRA
FURNACE
STATE
DN 125 DIRECTOR
ELECTRIC OF BOILER
SCH.40 X SA182 F22 CSA/04/17-18 NORMAL 32.80
WELDOLET 04 C/922 ARC CSA FITTINGS 0.11 0.33 0.52 0.02 0.011 444.81 547.41 ---
DN 40 CL3 DT.-12/05/2017 ISED 50 MAHARAST
FURNACE
SCH.STD RA STATE
DIRECTOR
ELECTRIC OF BOILER
180° SR DN 125 X SA 234 CSA/163/17-18 NORMAL
06 C/877 ARC CSA FITTINGS 0.078 0.025 0.42 0.011 0.004 348.10 484.34 34.00 --- MAHARAST
BEND SCH.40 WP22 CL1 DT.-23/02/2017 ISED
FURNACE RA STATE
DN 125 DIRECTOR
ELECTRIC
SCH.40 X SA182 F22 CSA/04/17-18 NORMAL 32.80 OF BOILER
WELDOLET 01 C/922 ARC CSA FITTINGS 0.11 0.33 0.52 0.02 0.011 444.81 547.41 ---
DN 40 CL3 DT.-12/05/2017 ISED 50 MAHARAST
FURNACE
SCH.STD RA STATE
Page 2 of 3
ISHAN EQUIPMENTS PVT. LTD.(UNIT-II)
COMPETENT
DN 40 X PERSON TUV
GATE SA182 GM VALVES PVT. 0530
05 CL.800 1093 --- --- 0.086 0.200 0.426 0.034 0.018 269.5 584 32.3 OK INDIA PVT.
VALVE F22CL3 LTD. DT.02/02/2018
SW ENDS LTD.
Certified that the particulars entered herein by us are correct. This satisfies the requirements of Indian Boiler Regulations, 1950.
Maker’s Representative Maker Name, signature and stamp of Name, signature and stamp of
(Name, signature and stamp) (Name, signature and stamp) Competent Person Inspecting Authority
Dated ……the day of …………… 2017.
Page 3 of 3