DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.

Fire Dampers Catalogue

CRFD - Type A, B, CR & CO


Rectangular, Round & Flat Oval UL 555 Classified

2013
For Use in Static
& Dynamic Systems
3 Hour Rating

Made in Qatar
Fire Dampers
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

The Fire Dampers have been investigated by UL Laboratories


in Chicago - USA on February 12, 2013 in accordance with
UL 555 - Standard for Fire Dampers.

UNDERWRITERS LABORATORIES' STANDARD UL 555


The UL 555 Standard for Fire Dampers
UL 555 - FIRE DAMPERS includes Significant Test Criteria.

Fire Dampers are intended for use where air ducts • Operational Reliability
penetrate or terminate at openings in walls To ensure operation through 250 cycles for dampers
Static & Dynamic

or partitions, in air transfer openings in partitions, for use without actuators, or 20,000 cycles for dampers
and where air ducts extend through floors with actuators and Cycle Testing following Salt Spray
as specified in the Standard for Installation of Air Exposure.
Conditioning and Ventilating Systems, NFPA 90A.
• Fire Endurance
In a fire emergency the Fire Damper is designed For either 1.5 or 3 hours to determine the hourly
to close and prevent the spread of fire from classification of the damper assembly.
one side of the wall or partition to the other.
• Hose Stream Test
To verify the damper assembly and associated
Fire Dampers are evaluated for use as either: installation components remain intact during explosive
fire conditions.
a) Fire Dampers for Static Systems -
For HVAC systems that are automatically • Salt-Spray Exposure
shut down in the event of a fire. To simulate the dust and other debris that accumulates
on a fire damper mounted in a duct or opening within
b) Fire Dampers for Dynamic Systems - a building and to investigate the performance of the Fire
For HVAC systems that are operational Damper while subjected to such accumulations.
in the event of a fire.
• Dynamic Closure
c) Combination Fire and Smoke Dampers - To verify the damper assembly will close against heated
For locations in HVAC systems where a air flow velocity of at least 2000 fpm and 4 inches of water.
Fire Damper and a Smoke Damper are (Not required for Dampers Classified for Static
required at a single location. "fans off" Systems).

Type of Fire Damper


Section or Static Fire Dynamic Fire Combination Fire and
Test Standard Damper Damper Smoke Damper
1. Fire Endurance & Hose Stream 10 x x x

2. Operational Reliability 11 x x x

3. Salt-Spray Exposure 12 x x x

4. Spring Closing Force 13 x - -

5. Dynamic Closure 14 - x x

6.Operation UL555S - - x

7. Leakage UL555S - - x

x. Test applicable
-. Test not applicable

2
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

Static Fire Dampers: Page


Static Fire Damper (Type A) ................................................. 4
Table Of Contents
Static Fire Damper (Type B) ................................................. 5

Static Fire Damper (Type CR) .............................................. 6

Static Fire Damper (Type CO) .............................................. 7

Dynamic Fire Dampers:


Dynamic Fire Damper (Type A) ............................................ 8

Dynamic Fire Damper (Type B) ............................................ 9

Dynamic Fire Damper (Type CR) ......................................... 10

Dynamic Fire Damper (Type CO) ......................................... 11

Fire Damper Installation Instructions:


Fire Dampers Installation Instructions .................................. 12---16

Certificate & Approvals:


UL Certificate of Compliance ................................................ 18-19

Civil Defense Approval .......................................................... 20-21

3
Static Fire Dampers (Type A)
Rectangular
Code: CRFD-A-S
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Curtain Rectangular Fire Damper (TYPE A)

. FOR USE IN STATIC SYSTEMS


. 3 HOUR RATING
. UL 555 CLASSIFIED

Description:
The Rectangular Curtain Type Fire Damper provides an efficient solution to separate areas of Fire in Ventilation Systems.
The Curtain Type Fire Damper will stop the spread of fire through ducts, walls or floors.

Damper Size (Vertical):


- Min. size - WxH 100x100mm
- Max. size - WxH 900x900mm

Damper Size (Horizontal):


- Min. size - WxH 100x100mm
- Max. size - WxH 900x900mm

Features:
Casing : - 20 Gage (1.0mm) Galvanized Steel
H - 5mm
Blades : - 22 Gage (0.8mm) Galvanized Steel
Spring : - 301 Stainless Steel Closure Spring.
Fusible Link : - 165 ⁰F (74 ⁰C) is Standard.

W - 5mm
1
2 105
1 Casing mm12.0

3 2 Interlocking Curtain Blades


3 UL Listed Fusible Link
4
4 Closure Spring
5 Catch Plate
Ordering example
6 Steel Rivet CRFD A S 300X150

5
Code
7
Type
Static / Dynamic
Dim. Width x Height

Fire Damper Sleeve:

DVAC Fire Dampers Sleeves ensure proper damper mounting in sleeve and
can be shipped direct to job site for immediate installation.
H
Note: Sleeves can be field fabricated.

L12.0

Type 'A' - Blades and frame in the airstream


Installation: Min. size - WxH 100x100mm
Please refer to Fire Damper Installation Instructions (Page 12---16). Max. size - WxH 900x900mm

* Materials Used for CRFD:


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.

4
Static Fire Dampers - Type B
Rectangular
Code: CRFD-B-S
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Curtain Rectangular Fire Damper (TYPE B)

. FOR USE IN STATIC SYSTEMS


. 3 HOUR RATING
. UL 555 CLASSIFIED

Description:
The Rectangular Curtain Type Fire Damper provides an efficient solution to separate areas of Fire in Ventilation Systems.
The Curtain Type Fire Damper will stop the spread of fire through ducts, walls or floors.

Damper Size (Vertical):


- Min. size - WxH 100x100mm
- Max. size - WxH 900x800mm

Damper Size (Horizontal):


- Min. size - WxH 100x100mm
- Max. size - WxH 900x800mm Damper Height (H) Dim. (A)
A
100 thru 400mm 50mm
410 thru 650mm 75mm
Features: 660 thru 800mm 100mm
Casing : - 20 Gage (1.0mm) Galvanized Steel
Blades : - 22 Gage (0.8mm) Galvanized Steel H - 5mm
Spring : - 301 Stainless Steel Closure Spring.
Fusible Link : - 165 ⁰F (74 ⁰C) is Standard.

W - 5mm
1
2
1 Casing 105
mm12.0

3 2 Interlocking Curtain Blades


3 UL Listed Fusible Link
4
4 Closure Spring
5 Catch Plate
Ordering example
6 Steel Rivet CRFD B S 300X150

5
Code
7
Type
Static / Dynamic
Dim. Width x Height

Fire Damper Sleeve:

DVAC Fire Dampers Sleeves ensure proper damper mounting in sleeve and A
can be shipped direct to job site for immediate installation.
H
Note: Sleeves can be field fabricated.

L12.0

Type 'B' - Blades partially in airstream


Installation: Min. size - WxH 100x150mm
Please refer to Fire Damper Installation Instructions (Page 12---16). Max. size - WxH 900x900mm

* Materials Used for CRFD:


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.

5
Static Fire Dampers - Type CR
Round
Code: CRFD-CR-S
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Curtain Round Fire Damper (TYPE CR)

. FOR USE IN STATIC SYSTEMS


. 3 HOUR RATING
. UL 555 CLASSIFIED

Description:
The Round Curtain Type Fire Damper provides an efficient solution to separate areas of Fire in Ventilation Systems.
The Curtain Type Fire Damper will stop the spread of fire through ducts, walls or floors.

Damper Size (Vertical):


- Min. size - WxH 150mm Diameter
- Max. size - WxH 750mm Diameter

Damper Size (Horizontal):


- Min. size - WxH 150mm Diameter
- Max. size - WxH 750mm Diameter Diameter (D) Height (H) Width (W)
150 thru 400mm +75mm +50mm
410 thru 550mm +125mm +50mm
560 thru 750mm +150mm +50mm
Features:
Casing : - 20 Gage (1.0mm) Galvanized Steel
Blades : - 22 Gage (0.8mm) Galvanized Steel Diameter (D) Collar Thickness H
150 thru 400mm 22 Gage (0.8mm)
Spring : - 301 Stainless Steel Closure Spring. 410 thru 750mm 20 Gage (1.0mm)

Fusible Link : - 165 ⁰F (74 ⁰C) is Standard. D

W
105
1 mm 12.0

2
1 Casing
3 2 Interlocking Curtain Blades
3 UL Listed Fusible Link
4
4 Closure Spring
Ordering example
5 Catch Plate CRFD CR S 300

6 Steel Rivet Code


5 Type
Static / Dynamic
6 D = Diameter

Fire Damper Sleeve:

DVAC Fire Dampers Sleeves ensure proper damper mounting in sleeve and
can be shipped direct to job site for immediate installation.
H
Note: Sleeves can be field fabricated.

12.0

L
W

Type 'CR' - Blades partially in airstream


Installation: Min. size - WxH 250x250mm
Please refer to Fire Damper Installation Instructions (Page 12---16). Max. size - WxH 900x900mm

* Materials Used for CRFD:


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.

6
Static Fire Dampers - Type CO
Flat Oval

DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.) Code: CFOFD-CO-S

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Curtain Flat Oval Fire Damper (TYPE CO)

. FOR USE IN STATIC SYSTEMS


. 3 HOUR RATING
. UL 555 CLASSIFIED

Description:
The Flat Oval Curtain Type Fire Damper provides an efficient solution to separate areas of Fire in Ventilation Systems.
The Curtain Type Fire Damper will stop the spread of fire through ducts, walls or floors.

Damper Size (Vertical):


- Min. size - 150mm Minor or Major Axis
- Max. size - 750mm Minor or Major Axis

Damper Size (Horizontal):


- Min. size - 150mm Minor or Major Axis
- Max. size - 750mm Minor or Major Axis Minor Axis (Mi) Height (H)
150 thru 400mm +75mm
410 thru 550mm +125mm
560 thru 750mm +150mm
Features:
Casing : - 20 Gage (1.0mm) Galvanized Steel H
Blades : - 22 Gage (0.8mm) Galvanized Steel Minor Axis (Mi) Collar Thickness
Mi
150 thru 400mm 22 Gage (0.8mm) Ma
Spring : - 301 Stainless Steel Closure Spring. 410 thru 750mm 20 Gage (1.0mm)

Fusible Link : - 165 ⁰F (74 ⁰C) is Standard.

W= Major Axis
+ 50mm 105
mm12.0

1
2
1 Casing
3 2 Interlocking Curtain Blades
3 UL Listed Fusible Link
4
4 Closure Spring
Ordering example
5 Catch Plate CFOFD CO S 300

6 Steel Rivet Code


5 Type
Static / Dynamic
6 D = Diameter

Fire Damper Sleeve:

DVAC Fire Dampers Sleeves ensure proper damper mounting in sleeve and
can be shipped direct to job site for immediate installation.
H
Note: Sleeves can be field fabricated.

L12.0

12.0

Type 'CR' - Blades partially in airstream


Installation: Min. size - WxH 350x250mm
Please refer to Fire Damper Installation Instructions (Page 12---16). Max. size - WxH 900x800mm

* Materials Used for CFOFD:


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.

7
Dynamic Fire Dampers - Type A
Rectangular
Code: CRFD-A-D
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Curtain Rectangular Fire Damper (TYPE A)

. FOR USE IN DYNAMIC SYSTEMS


. 3 HOUR RATING
. UL 555 CLASSIFIED

Description:
The Rectangular Curtain Type Fire Damper provides an efficient solution to separate areas of Fire in Ventilation Systems.
The Curtain Type Fire Damper will stop the spread of fire through ducts, walls or floors.
There is a wide choice of sizes available for Low, Medium and High Velocity applications.
The Dampers are fitted with standard release 74⁰C fusible links.

Ratings:
- Pressure : Up to 4"w.g. (Up to 1000 Pa)
- Velocity : Up to 2000 fpm (Up to 10.16 m/s)

Damper Size (Vertical):


- Min. size - WxH 100x150mm
- Max. size - WxH 900x900mm
Features: H - 5mm
Casing : - 20 Gage (1.0mm) Galvanized Steel
Blades : - 22 Gage (0.8mm) Galvanized Steel
Spring : - 301 Stainless Steel Closure Spring.
Fusible Link : - 165 ⁰F (74 ⁰C) is Standard.

W - 5mm
105
1 mm12.0

2
1 Casing
3 2 Interlocking Curtain Blades
3 UL Listed Fusible Link
4
4 Closure Spring
Ordering example
5 Catch Plate CRFD A D 300X150

6 50mm, 18 Gage (1.2mm) GI Flat Code


5 Type
6 7 Steel Rivet
Static / Dynamic
7 Dim. Width x Height

Fire Damper Sleeve:

DVAC Fire Dampers Sleeves ensure proper damper mounting in sleeve and
can be shipped direct to job site for immediate installation.
H
Note: Sleeves can be field fabricated.

L12.0

Type 'A' - Blades and frame in the airstream


Installation: Min. size - WxH 100x150mm
Please refer to Fire Damper Installation Instructions (Page 12---16). Max. size - WxH 900x900mm

* Materials Used for CRFD:


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.

8
Dynamic Fire Dampers - Type B
Rectangular
Code: CRFD-B-D
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Curtain Rectangular Fire Damper (TYPE B)

. FOR USE IN DYNAMIC SYSTEMS


. 3 HOUR RATING
. UL 555 CLASSIFIED

Description:
The Rectangular Curtain Type Fire Damper provides an efficient solution to separate areas of Fire in Ventilation Systems.
The Curtain Type Fire Damper will stop the spread of fire through ducts, walls or floors.
There is a wide choice of sizes available for Low, Medium and High Velocity applications.
The Dampers are fitted with standard release 74⁰C fusible links.

Ratings:
- Pressure : Up to 4"w.g. (Up to 1000 Pa)
- Velocity : Up to 2000 fpm (Up to 10.16 m/s)
Damper Height (H) Dim. (A)
Damper Size (Vertical): A
100 thru 400mm 50mm
- Min. size - WxH 100x100mm 410 thru 650mm 75mm
- Max. size - WxH 900x800mm 660 thru 800mm 100mm

Features:
Casing : - 20 Gage (1.0mm) Galvanized Steel H - 5mm
Blades : - 22 Gage (0.8mm) Galvanized Steel
Spring : - 301 Stainless Steel Closure Spring.
Fusible Link : - 165 ⁰F (74 ⁰C) is Standard.

W - 5mm
105
1 mm12.0

2
1 Casing
3 2 Interlocking Curtain Blades
3 UL Listed Fusible Link
4
4 Closure Spring
Ordering example
5 Catch Plate CRFD B D 300X150

6 50mm, 18 Gage (1.2mm) GI Flat Code


5 Type
6 7 Steel Rivet
Static / Dynamic
7 Dim. Width x Height

Fire Damper Sleeve:

DVAC Integral Sleeve Fire Dampers ensure proper damper mounting in sleeve and A
can be shipped direct to job site for immediate installation.
H
Note: Sleeves can be field fabricated.

L12.0

Type 'B' - Blades partially in airstream


Installation: Min. size - WxH 100x150mm
Please refer to Fire Damper Installation Instructions (Page 12---16). Max. size - WxH 900x900mm

* Materials Used for CRFD:


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.

9
Dynamic Fire Dampers - Type CR
Round
Code: CRFD-CR-D
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Curtain Round Fire Damper (TYPE CR)

. FOR USE IN DYNAMIC SYSTEMS


. 3 HOUR RATING
. UL 555 CLASSIFIED

Description:
The Round Curtain Type Fire Damper provides an efficient solution to separate areas of Fire in Ventilation Systems.
The Curtain Type Fire Damper will stop the spread of fire through ducts, walls or floors.
There is a wide choice of sizes available for Low, Medium and High Velocity applications.
The Dampers are fitted with standard release 74⁰C fusible links.

Ratings:
- Pressure : Up to 4"w.g. (Up to 1000 Pa)
- Velocity : Up to 2000 fpm (Up to 10.16 m/s)
Diameter (D) Height (H) Width (W)
Damper Size (Vertical): 150 thru 400mm +75mm +50mm

- Min. size - 150mm Diameter 410 thru 550mm


560 thru 750mm
+125mm
+150mm
+50mm
+50mm
- Max. size - 750mm Diameter
Features:
Diameter (D) Collar Thickness H
Casing : - 20 Gage (1.0mm) Galvanized Steel 150 thru 400mm 22 Gage (0.8mm)
410 thru 750mm 20 Gage (1.0mm)
Blades : - 22 Gage (0.8mm) Galvanized Steel
D
Spring : - 301 Stainless Steel Closure Spring.
Fusible Link : - 165 ⁰F (74 ⁰C) is Standard.

W
105
1 mm 12.0

2
1 Casing
3 2 Interlocking Curtain Blades
3 UL Listed Fusible Link
4
4 Closure Spring
Ordering example
5 Catch Plate CRFD CR D 300

6 Steel Rivet Code


5 Type
Static / Dynamic
6 D = Diameter

Fire Damper Sleeve:

DVAC Integral Sleeve Fire Dampers ensure proper damper mounting in sleeve and
can be shipped direct to job site for immediate installation.
H
Note: Sleeves can be field fabricated.

12.0

L
W

Type 'CR' - Blades partially in airstream


Installation: Min. size - WxH 250x250mm
Please refer to Fire Damper Installation Instructions (Page 12---16). Max. size - WxH 900x900mm

* Materials Used for CRFD:


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.

10
Dynamic Fire Dampers - Type CO
Flat Oval
Code: CFOFD-CO-D
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Curtain Flat Oval Fire Damper (TYPE CO)

. FOR USE IN DYNAMIC SYSTEMS


. 3 HOUR RATING
. UL 555 CLASSIFIED

Description:
The Flat Oval Curtain Type Fire Damper provides an efficient solution to separate areas of Fire in Ventilation Systems.
The Curtain Type Fire Damper will stop the spread of fire through ducts, walls or floors.
There is a wide choice of sizes available for Low, Medium and High Velocity applications.
The Dampers are fitted with standard release 74⁰C fusible links.

Ratings:
- Pressure : Up to 4"w.g. (Up to 1000 Pa)
- Velocity : Up to 2000 fpm (Up to 10.16 m/s)
Minor Axis (Mi) Height (H)
Damper Size (Vertical): 150 thru 400mm +75mm

- Min. size - 150mm Minor or Major Axis 410 thru 550mm


560 thru 750mm
+125mm
+150mm
- Max. size - 750mm Minor or Major Axis
H
Features:
Minor Axis (Mi) Collar Thickness
Casing : - 20 Gage (1.0mm) Galvanized Steel Mi
150 thru 400mm 22 Gage (0.8mm) Ma
410 thru 750mm 20 Gage (1.0mm)
Blades : - 22 Gage (0.8mm) Galvanized Steel
Spring : - 301 Stainless Steel Closure Spring.
Fusible Link : - 165 ⁰F (74 ⁰C) is Standard.
W= Major Axis
+ 50mm 105
mm12.0

1
2
1 Casing
3 2 Interlocking Curtain Blades
3 UL Listed Fusible Link
4
4 Closure Spring
Ordering example
5 Catch Plate CFOFD CO D 300

6 Steel Rivet Code


5 Type
Static / Dynamic
6 D = Diameter

Fire Damper Sleeve:

DVAC Integral Sleeve Fire Dampers ensure proper damper mounting in sleeve and
can be shipped direct to job site for immediate installation.
H
Note: Sleeves can be field fabricated.

L12.0

Type 'CR' - Blades partially in airstream


Installation: Min. size - WxH 350x250mm
Please refer to Fire Damper Installation Instructions (Page 12---16). Max. size - WxH 900x800mm

* Materials Used for CFOFD:


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.

11
Fire Dampers Installation Instructions
Rectangular
Code: CRFD (Type: A & B)
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

INSTALLATION INSTRUCTIONS
1.) Wall/Floor Opening and Clearance Required

The Opening in wall or floor shall be larger than the fire Damper sleeve due to the expansion during periods
of intense heat.

- Minimum clearance required is 10mm per linear meter for Damper Width & Height.
- Sleeve may rest on Bottom of the opening.

Wall/Floor opening
d1

Height Height

Damper w/ Sleeves

Width Width
d2 d3 d4
d1 = 10mm * (Height/1000mm)
d2 = 10mm * (Width/1000mm)
where : d2 = d3 + d4

2.) Duct sleeve connections listed in UL 555, Sixth Edition, Standard for Fire Dampers
Breakaway Joints

Plain “S” Slip Hemmed “S” Slip Inside Slip Joint Double “S” Slip

Standing “S” Slip Standing “S” Slip Standing “S” Slip Standing “S” Slip
(Alternate Bar) (Angle Reinforced) (Bar Reinforced)

The breakaway connections shown in fig. above can be applied with maximum 2 nos. # 10 sheet metal screw
on each side and on the bottom located in the center of the slip pocket and penetrating both sides of the slip pocket.

The illustrated joint above can be applied as the top and bottom joints and the sides with a drive slip joint as long as
the duct height is less than 500mm.

Drive Slip Joint

* Materials Used for CRFD:


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.

12
Fire Dampers Installation Instructions
Rectangular
Code: CRFD (Type: A & B)
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Slip-on Flange System:

UL tested Slip-on Flange System are approved as breakaway connection when installed as shown below:

150mm Long, 1.59mm Maximum thickness plastic cleats


305 mm C-C (Minimum: 1 per side)

Flanged System angles


(Attached per manufacturers
instruction)

Do not bolt corners

Neoprene gasket
between all angles

3.) Sleeve Thickness & Length

All Fire Dampers must be installed in a sleeve of the required gauge and length. It could be factory Installed
or field fabricated.

- Sleeve shall extend a maximum of 150mm from the wall or floor opening from each side.
- Sleeve may extend with a maximum length of 400mm from wall or floor if a factory installed access door is required).

Type of Connection Duct Dimension Sleeve Thickness


Rigid or Breakaway All Duct Sizes 2mm
Maximum width 900mm
Rigid or Breakaway 1.5mm
Maximum height 600mm
Up to 300mm 0.55mm
301 to 750mm 0.7mm
Breakaway Only 751 to 1350mm 0.85mm
1351 to 2100mm 1.0mm
2001 and up 1.2mm

N.B.: Any Duct connection other than breakaway is considered rigid.

* Materials Used for CRFD:


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.

13
Fire Dampers Installation Instructions
Rectangular
Code: CRFD (Type: A & B)
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

4.) Damper-Sleeve Attachment

All four sides of the damper frame must be attached to the sleeve with one row of attachments on each sides
of the blade channel. Attachment must be spaced a maximum of 150mm on centers and a max of 50mm from corners
and minimum of 4 attachments per side with a total of 16.
Secure damper to sleeve with 12mm long welds

50mm

Weld
150mm

5.) Securing the fire damper sleeve to the Opening

Centerline of the Fire Damper blade should be positioned within the confines of the wall or floor opening.
Fire Damper and Sleeve assembly must be installed in opening using retaining angles on each side of the wall or floor.
Retaining angle thickness should be 1.5mm minimum
Retaining angles should be secured to the damper sleeve ONLY.
Retaining angles should cover the gap + 25mm overlap with the wall
Retaining angles should be attached to 4 (four) sides of the damper sleeve using 6mm bolts & nuts methods
with a maximum spacing of 50mm from corners and 150mm on center.

Wall or Floor

Retaining Angle

Min. 25mm overlay

Sleeve
Duct

Duct
50m
m

Sleeve 150m
m

150m
m

50m
m
Damper

* Materials Used for CRFD:


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.

14
Fire Dampers Installation Instructions
Rectangular, Round & Flat Oval
Code: CRFD (Type: A, B, CR & CO)
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Vertical mount without factory mounted sleeve

See
Section 1

Wall or floor Wall or floor

Wall or floor On types CR & CO


factory furnished duct
Retaining angle collar qualifies as
leg shall not breakaway connection,
See Section 3 See Section 3 exceed 178mm see Section 5
Sleeve Sleeve

Damper Damper Damper

Duct
Duct Duct
Sleeve
Retaining Angles (See Section 3 & 4)
(See Section 5)

TYPE A TYPE B TYPE CR & CO

Note: When Dampers installed vertically, the blade stack must be on the top.

Horizontal mount without factory mounted sleeve

Retaining Angles
Retaining Angles (See Section 5)
(See Section 5) See Wall or Wall or
Wall or Section 3 floor
See Section 3 floor
floor

Sleeve Sleeve Sleeve


See Section 3 See
(See Section 3 & 4) (See Section 3 & 4) On types CR & CO
Damper Section 3 Damper Damper
factory furnished duct
Duct Duct collar qualifies as Duct
breakaway connection,
see Section 5

TYPE A TYPE B TYPE CR & CO

Note: When Dampers installed horizontally, the ramp must be positioned up as shown in above drawings.

* Materials Used for CRFD:


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.

15
Fire Dampers Installation Instructions
Rectangular, Round & Flat Oval
Code: CRFD (Type: A, B, CR & CO)
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Vertical mount with factory mounted sleeve

See
Section 5

Wall or floor
Wall or floor
Wall or floor
On types CR & CO
factory furnished duct
Max. Max. collar qualifies as
Damper
150mm 150mm breakaway connection.
See See Damper
Section 3 Section 3

Duct
Duct
Damper
Retaining Angles Duct
(See Section 5)

TYPE CR & CO
TYPE A TYPE B

Note: When Dampers installed vertically, the blade stack must be on the top.

Horizontal mount with factory mounted sleeve

Retaining Angles
Retaining Angles (See Section 5)
(See Section 5) Wall or
Wall or See Section 3 floor Wall or
floor floor
See Section 3

Sleeve Sleeve
See Section 3 See Section 3 Sleeve Damper
(See Section 3 & 4) On types CR & CO
Damper (See Section 3 & 4)
Damper factory furnished duct
Duct collar qualifies as Duct
Duct breakaway connection,
see Section 5

TYPE A TYPE B TYPE CR & CO

Note: When Dampers installed horizontally, the ramp must be positioned up as shown in above drawings.

* Materials Used for CRFD:


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.

16
Fire Dampers Catalogue
Fire Dampers UL Certificate DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

And Civil Defense Approval

CRFD - Type A, B, CR & CO


Rectangular, Round & Flat Oval UL 555 Classified

2013

17
Fire Dampers Catalogue
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

18
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

19
Fire Dampers Catalogue
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

20
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

21
Remarks:

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117


22
Remarks:

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117


23
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

Small Industries Zone - Pink Area


Zone 81 - Street 13 - Bldg. 57

Tel: +974 445 00 118 - 445 00 119


Fax: +974 445 00 117
P.O. Box: 55619 - Doha, State Of Qatar

Email: info@dvac-duct.com
Website: www.dvac-duct.com

You might also like