You are on page 1of 8

Sheet 2 of 8

HM AW JB

1. DATA SHEET FOR BATTERIES AND BATTERY CHARGER

1.1. BATTERIES

1. Manufacturer Fiamm

2. Equipment Number 6P-3003-BAT

3. Applicable standard IEC 60896-2

4. Type Valve Regulated Lead Acid

5. Mounting Method Rack mounting

6. Configuration 1 x 100%

7. Rating
a. Nominal DC voltage (VDC) 125
b. Maximum system voltage (VDC) 135
c. Minimum system voltage (VDC) 112
d. Maximum battery output voltage (VDC) 132
e. Capacity (at 10 hour) (Ah) 800Ah
f. Number of unit cell (cell) 60
g. Battery nominal voltage (VDC) 2
h. Battery float voltage (VDC) 2.25
i. Battery end voltage (VDC) 1.88
j. Maximum discharge current (A) 320A

8. Spare batteries (cell) 2

9. Dimension of battery
a. Height (mm) 525
b. Depth (mm) 254
c. Width (mm) 210

10. Dimension of mounting structure


a. Height (mm) 1700 rack only /1910 incl.battery
b. Depth (mm) 3300
c. Width (mm) 650

11. Weight
a. Cell (including electrolyte) (kg) 64
b. Total (including mounting structure (kg) 4214 (incl.spare batteries)
and conductor)

1.2. BATTERY CHARGERS

1. Manufacturer Chloride - Emerson Network Power

2. Type full wave SCR


Sheet 3 of 8

HM AW JB

3. Equipment number 6P-3001-DC

4. Minimum degree of protection IP41 ext/ IP20 int

5. Thickness of enclosure sheet steel (mm) 2 mm

6. Rectification system redundant configuration with


common battery bank

7. Cooling system Forced ventilation

8. Minimum rectifier capacity (A) 400

9. Minimum efficiency (%) 93% (tolerance +/-1%)

10. Rating Input (AC side)


a. Input voltage (VAC) 440
b. Supply voltage variation (%) ± 10%
c. Frequency (Hz) 50
d. Supply frequency variation (%) ± 5%

11. Rating Output (DC side)


a. Set voltage
- Floating (V) 135.0V (before dropper)
- Equalizing (V) 135.0V
b. Voltage adjustment range
- Floating (V) 132.0V (after dropper)
- Equalizing (V) 132.0V

12. Dropper diode (ea) 4

13. Dropper diode voltage (V) 0.8V per dropper

14. Cubicle dimension (including rectifier)


a. Height (mm) 1982
b. Width (mm) 3600
c. Depth (mm) 808

15. Weight (including rectifier) (kg) 1170

16. Painting Munsell N7

1.3. DC DISTRIBUTION PANEL

A. GENERAL

1. Manufacturer Emerson Chloride

2. Type Form 1
Sheet 4 of 8

HM AW JB

3. Minimum degree of protection IP 41

4. Mounting method Free standing

5. Applicable standard IEC 60439-1

6. Rated voltage (VDC) 125

7. Rated continuous current (A) 400

8. Rated short circuit current (kA) 25

9. Thickness of enclosure sheet steel (mm) 2 mm

10. Painting Munsell N7

11. Drawing enclosed Yes

B. BUSES AND ENCLOSURES

1. High Potential test in factory on (V) 2000 (rms)


assembled panel for 1 minute

2. Temperature rise of bus and (oC) as per DC Type Test Report


connections at rated load above
outside ambient of 40oC

3. Value of short circuit which buses are (kA) 25 kA


braced to withstand

4. Minimum clearance
- Between positive and negative buses (mm) 20 mm
- Live parts-to-ground (mm) 20 mm

C. CIRCUIT BREAKERS

1. Manufacturer ABB

2. Type MCCB and MCB

3. Maximum design voltage (VDC) 250


Sheet 5 of 8

HM AW JB

2. DATA SHEET FOR UNINTERRUPTIBLE POWER SUPPLY (UPS)

2.1 GENERAL

1. Manufacturer EmersonChloride

2. Type CP-70Z

3. Equipment number 6P-3001-UPS

4. Minimum degree of protection IP 41

5. Thickness of enclosure sheet steel (mm) 2 mm

6. Painting Munsell N7

2.2 BATTERIES

1. Manufacturer Fiamm,

2. Equipment Number 6P-3001-BAT


6P-3002-BAT

3. Applicable standard IEC 60896-2

4. Type Valve Regulated Lead Acid

5. Mounting Method Rack mounting

6. Configuration 2 x 100%

7. Rating
a. Nominal DC voltage (VDC) 125
b. Maximum system voltage (VDC) 135
c. Minimum system voltage (VDC) 108
d. Capacity (at 10 hour) (Ah) 1500Ah
e. Number of unit cell (cell) 60
f. Battery nominal voltage (VDC) 2
g. Battery float voltage (VDC) 2.25
h. Battery end voltage (VDC) 1.80
i. Maximum discharge current (A) 650

8. Spare batteries (cell) 2

9. Dimension of battery
a. Height (mm) 660
b. Depth (mm) 275
c. Width (mm) 210
Sheet 6 of 8

HM AW JB

10. Dimension of mounting structure


a. Height (mm) 1800 rack only / 2010 incl. battery
b. Depth (mm) 822
c. Width (mm) 3600

11. Weight
a. Cell (including electrolyte) (kg) 110
b. Total (including mounting structure (kg) 7154 (incl. spare batteries)
and conductor)

2.3 INVERTER

1. Rated DC input (VDC) minimum 108 VDC


maximum 135 VDC

2. Rated AC output (VAC) 110

3. Output voltage variation (%) ± 1% (balanced load)

4. Distortion (%)

5. Rated output of frequency (Hz) 50

6. Internal frequency control (%) ± 0.5%

7. Minimum capacity (kVA) 75

8. Capability of overload (%) Refer to Emerson datasheet

9. Rated output power factor (pf) 0.80 PF lagging to 1.0 PF

10. Is the inverter provided with (Yes/No) Yes


synchronizing control

11. Efficiency at full rated load and unity (%) 86%


power factor

12. Total Harmonic Distortion (linear load) (%) <3%

2.4 RECTIFIER UNIT

1. Type full wave SCR

2. Input voltage (VAC) 440

3. Supply voltage variation (%) ± 10%

4. Voltage regulation (%) less than ±1% from no load to full


load
Sheet 7 of 8

HM AW JB

5. Input frequency (Hz) 50

6. Supply frequency variation (%) ± 5%

7. Minimum rectifier capacity (A) 800

8. DC output voltage (VDC) minimum 108 VDC


maximum 135 VDC

9. Ripple voltage (battery connected) (%) <2%

2.5 STATIC TRANSFER SWITCH

1. Type A22 Module

2. Manufacturer Emerson Chloride

3. Continuous current rating (A) 920 A

4. Withstand rating at 440V (A) 850 A

5. Number of poles 2

2.6 AC DISTRIBUTION PANEL

A. GENERAL
1. Manufacturer Emerson Chloride

2. Type Form 1

3. Minimum degree of protection IP 41

4. Mounting method Free standing

5. Applicable standard IEC 60439-1

6. Rated voltage (VAC) 110

7. Rated continuous current (A) 800

8. Rated short circuit current (kA) 16

9. Thickness of enclosure sheet steel (mm) 2 mm

10. Painting Munsell N7


Sheet 8 of 8

HM AW JB

B. BUSES AND ENCLOSURES


1. High Potential test in factory on (V) 2000 (rms)
assembled panel for 60 minutes

2. Temperature rise of bus and (oC) as per AC Type Test Report


connections at rated load above
outside ambient of 40oC

3. Value of short circuit which buses are (kA) 16 kA


braced to withstand

4. Minimum clearance

- Live parts-to-ground (mm) 20 mm

C. CIRCUIT BREAKERS
1. Manufacturer ABB

2. Type MCCB and MCB

3. Maximum design voltage (VAC) 500

You might also like