You are on page 1of 108

MillenniumTM LIQUID CHILLERS

AIR-COOLED – RECIPROCATING HERMETIC

INSTALL., OPER., MAINT. Supersedes: See Back Form 150.60-NM5 (398)

60 HZ MODELS
YCAJ110-130

28694A

200, 230, 460-3-60

* With EPROM 031-01652-001 (Standard, Brine & Metric Models, Combined)


TABLE OF CONTENTS
General Information .......................................................................................... 2
Unit Nomenclature ........................................................................................... 3
Compressor Nomenclature ............................................................................... 3
Unit Components ............................................................................................. 4
Compressor Components ................................................................................. 5
Operational Limitations ..................................................................................... 6
Physical Data .................................................................................................. 8
Dimensions ...................................................................................................... 10
Electrical Data ................................................................................................. 12
Installation ........................................................................................................ 16
Weight Distribution and Isolator Locations ........................................................ 18
Wiring Diagrams .............................................................................................. 20
Unit Controls and Operation ............................................................................. 29
Display Keys .................................................................................................... 32
Status Key ....................................................................................................... 37
Entry Keys ....................................................................................................... 40
Program Key .................................................................................................... 41
Clock Keys ...................................................................................................... 45
Selection of Return or Leaving Chilled Liquid .................................................... 48
Setpoints Keys ................................................................................................ 49
System Safeties .............................................................................................. 57
Print Keys ........................................................................................................ 63
Unit On / Off Switch ......................................................................................... 69
Compressor Capacity Control ........................................................................... 77
System Startup Checklist ................................................................................ 78
Preventative Maintenance ................................................................................. 83
Options ............................................................................................................ 85
Troubleshooting Chart ...................................................................................... 102
Temperature Conversion Tables ........................................................................ 106

GENERAL INFORMATION
GENERAL DESCRIPTION CODE STATUS
These packaged liquid chillers are completely self- The units are designed in accordance with UL (200, 230,
contained outdoor units shipped ready for final job instal- 460-3-60), N.E.C., ASHRAE/ANSI STANDARD 15, and
lation requiring only liquid connections, power and control ASME Codes.
wiring. They are designed primarily for central station air
conditioning applications with normal installations being
on roof-tops or on ground level beside the building.

WARNING
  HIGH VOLTAGE
is used in the operation of this equipment.
DEATH OR SERIOUS INJURY
may result if personnel fail to observe safety precautions.
Work on electronic equipment should not be undertaken unless the individual(s) have been trained in the proper
maintenance of equipment and is (are) familiar with its potential hazards.
Shut off power supply to equipment before beginning work and follow lockout procedures. When working inside
equipment with power off, take care to discharge every capacitor likely to hold dangerous potential.
Be careful not to contact high voltage connections when installing or operating this equipment.

LOW VOLTAGE
DO NOT be misled by the term “low voltage”.
Voltages as low as 50 volts may cause death.

2 YORK INTERNATIONAL
FORM 150.60-NM5

UNIT NOMENCLATURE

YC A J 110 — 46 P A

Chiller: Design Level


YC = YORK Chiller
Type Start
P = Part Wind
Air Cooled

Compressor Type
J – Reciprocating Voltage Code:
17 = 200-3-60
Unit Model 28 = 230-3-60
40 = 380-3-60
46 = 460-3-60
58 = 575-3-60

COMPRESSOR NOMENCLATURE

Compressor Series

Compressor Style (G or K)

No. of Active Cylinders (4)

Stroke (3, 4)

Steps of Unloading

Motor Size (M, N, P, Q, S, T, V)

Voltage Code:
17 = 200-3-60
28 = 230-60
40 = 380-3-60
46 = 460-3-60
50 = 380/415-3-50
58 = 575-3-60
64 = 346-3-50

Motor Manufacturer
(S = A.O. Smith, L = Lacy Somer)

J G 4 3 3 T -17 S

YORK INTERNATIONAL 3
POWER
CONDENSER
PANEL
FANS

CONTROL
WIRING
CONDUIT

CONTROL
PANEL
CONDENSER
COILS

DATA PLATE

28694A

COOLER
POWER WIRING

CHILLED WATER
OUTLET

COOLER

28695A

THERMOSTATICALLY CHILLED WATER THERMAL HOT GAS


CONTROLLED INLET EXPANSION BYPASS
HEATER VALVES

25996A

HOT GAS
BYPASS
SYSTEM #1

FIG. 1 – UNIT COMPONENTS


LD02694

4 YORK INTERNATIONAL
FORM 150.60-NM5

COMPRESSOR TERMINAL BOX

MOTOR
TERMINALS

SUPPRESSORS

MOTOR
PROTECTOR
(MP)

27299A

8-CYLINDER
MODEL J COMPRESSOR

DISCHARGE
STOP VALVE RAINTIGHT
TERMINAL
BOX

SUCTION
STOP
VALVE

OIL PRESSURE
ACCESS CONN.

SIGHT CAPACITY
GLASSES CONTROL
SOLENOID
27597A

OIL CHARGING
VALVE

FIG. 2 – COMPRESSOR COMPONENTS

YORK INTERNATIONAL 5
OPERATIONAL LIMITATIONS (English)

VOLTAGE LIMITATIONS

The following voltage limitations are absolute and opera-


tion beyond these limitations may cause serious dam-
age to the compressor.

VOLTAGES
UNIT POWER MIN. MAX.
200-3-60 180 220
230-3-60 207 253
380-3-60 355 415
460-3-60 414 506
380/415-3-50 342 440
346-3-50 311 381
575-3-60 517 633

TEMPERATURES AND FLOWS

LVG.WATER COOLER AIR ON


MODEL
TEMP. °F GPM CONDENSER °F
YCA
MIN.1 MAX. MIN. MAX. MIN.2 MAX.3
J110 40 50 150 640 0 130
J120 40 50 150 640 0 130
J130 40 50 150 640 0 130

NOTES:
1. Standard units cannot be operated below 40°F leaving chilled
liquid temperature.
2. Operation below 25°F requires the Optional Low Ambient kit
(Minimum recommended operating temperature is 0°F).
3. Operation above 115°F requires Optional High Ambient kit
(Maximum recommended operating temperature is 130°F).
4. The evaporator is protected against freeze-up to -20°F with an
electrical heater cable as standard.
LD02695

CAUTION: Excessive flow will cause damage to the


cooler. Do not exceed max. cooler GPM.
COOLER KEY
Special care should be taken when mul-
tiple chillers are fed by a single pump.
CODE MODEL

H YCAJ110, 120, 130

FIG. 3A – COOLER WATER PRESSURE DROP (English)

6 YORK INTERNATIONAL
FORM 150.60-NM5

OPERATIONAL LIMITATIONS (SI)

VOLTAGE LIMITATIONS

The following voltage limitations are absolute and opera-


tion beyond these limitations may cause serious dam-
age to the compressor.

VOLTAGES
UNIT POWER MIN. MAX.
200-3-60 180 220
230-3-60 207 253
380-3-60 355 415
460-3-60 414 506
380/415-3-50 342 440
346-3-50 311 381
575-3-60 517 633

TEMPERATURES AND FLOWS

LVG.WATER COOLER AIR ON


MODEL
TEMP. °C FLOW CONDENSER °C
YCA
MIN.1 MAX. MIN. MAX. MIN.2 MAX.3
J110 4.4 10 9.5 40.4 -17.8 54.4
J120 4.4 10 9.5 40.4 -17.8 54.4
J130 4.4 10 9.5 40.4 -17.8 54.4

NOTES:
1. Standard units cannot be operated below 4.4°C leaving chilled
liquid temperature.
2. Operation below -3.9°C requires the Optional Low Ambient kit
(Minimum recommended operating temperature is -17.8°C).
3. Operation above 46.1°C requires Optional High Ambient kit
(Maximum recommended operating temperature is 54.4°C).
4. The evaporator is protected against freeze-up to -28.9°C with
an electrical heater cable as standard.
LD02696

CAUTION: Excessive flow will cause damage to the


COOLER KEY cooler. Do not exceed max. cooler flow.
Special care should be taken when mul-
CODE MODEL tiple chillers are fed by a single pump.

H YCAJ110, 120, 130

FIG. 3B – COOLER WATER PRESSURE DROP (SI)

YORK INTERNATIONAL 7
PHYSICAL DATA
(ENGLISH)
MODEL
60 HZ J110 J120 J130
YCA
NOMINAL CAPACITY (TONS) 104.7 112.2 119.6
NO. OF REFRIG. CIRCUITS 2 2 2
JG43-M JG44-P JG44-P
SYS. 1
COMPRESSOR MODEL (60 HP) (80 HP) (80 HP)
& MOTOR HORSEPOWER JG43-M JG43-M JG44-P
SYS. 2
(60 HP) (45 HP) (80 HP)

UNIT CAPACITY CONTROL 5 Steps 5 Steps 5 Steps

CONDENSER – DWP 450 PSIG


6 6 6
NO. OF FANS (42"Dia. Direct Drive)
HP/kW Each 1140 RPM 5/2.9 5/2.9 5/2.9
TOTAL AIRFLOW (CFM) 88,533 88,533 88,533
COOLER – DUAL CIRCUITED
DWP – 235 PSIG REF. SIDE,
16" x 8' 16" x 8' 16" x 8'
150 PSIG WATER SIDE
DIA. X LENGTH
WATER VOLUME (GALS.) 48 48 48
MIN. 150 150 150
GPM
MAX. 640 640 640
Alum. Fins 11,489 11,539 11,639
SHIPPING
Copper Fins 13,197 13,297 13,447
WEIGHT (LBS.)
Alum. Fins 11,889 11,989 12,089
OPERATING
Copper Fins 13,597 13,747 13,897
Sys. 1 108 115 125
REFRIG. CHARGE (LBS. R-22)
Sys. 2 121 128 140

8 YORK INTERNATIONAL
FORM 150.60-NM5

PHYSICAL DATA
(SI)
MODEL
60 HZ J110 J120 J130
YCA
NOMINAL CAPACITY (KW) 368.3 394.5 420.7
NO. OF REFRIG. CIRCUITS 2 2 2
JG43-M JG44-P JG44-P
SYS. 1
COMPRESSOR MODEL (44 KW) (59 KW) (59 KW)
& MOTOR KW JG43-M JG43-M JG44-P
SYS. 2
(44 kW) (33 kW) (59 kW)

UNIT CAPACITY CONTROL 5 Steps 5 Steps 5 Steps

CONDENSER – DWP 3 kPa


6 6 6
NO. OF FANS (1066 mm Dia. Direct Drive)
HP/kW Each 1140 RPM 5/3.7 5/2.9 5/2.9
AIRFLOW TOTAL (L/S) 41,783 41,783 41,783
COOLER – DUAL CIRCUITED
406 mm 406 mm 406 mm
DWP – 1.62 kPa REF. SIDE,
x x x
1.0 kPa WATER SIDE
2438 mm 2438 mm 2438 mm
DIA. X LENGTH
WATER VOLUME (L) 182 182 182
MIN. 9.5 9.5 9.5
L/SEC.
MAX. 40.4 40.4 40.4
Alum. Fins 5211 5234 5079
SHIPPING
Copper Fins 5986 6031 6099
WEIGHT (Kg)
Alum. Fins 5393 5438 5483
OPERATING
Copper Fins 6167 6236 6304
Sys. 1 49 52 57
REFRIG. CHARGE (Kg R-22)
Sys. 2 55 58 64

YORK INTERNATIONAL 9
DIMENSIONS
(English)

LD01334

LD01336

LD01337
LD01335

NOTES:
1. Clearances – Recommended YORK clearances for peak performance, reliable operation, and maintenance:
Side to wall – 8'; Rear to wall – 8'; Control panel end to wall – 5'; Over the top – no obstructions allowed; Two units side by side – 12',
(walls should be no higher than the unit). The area within the clearances and under the unit(s) must be kept clean of clutter. Additional height
should be included to allow for snow accumulation for units which are expected to operate at full load during the winter. Reduced
clearances may be used due to jobsite restrictions. The unit(s) with optional controls will allow optimal operation preventing the condenser
pressure from exceeding the maximum limit. The units will continue to operate without nuisance high pressure cutout even though the
airflow may be restricted at these conditions.

2. Panel bottom to be punched in field to accommodate power wiring conduit.


3. Use of isolators (optional) will increase height of unit approximately 6".
4. Drawings not to scale and are for planning purposes only. Contact nearest YORK Sales Office for detailed drawings.

See page 18 for 110 - 130 Ton Unit Isolator Selection.

WATER
WEIGHT DISTRIBUTION (LBS.)
CONN.
MODEL YCA
INLET/OUTLET
A B C D E F
DIA. (INCHES)
J110 1559 1936 2312 1544 1917 2290 8
J120 1559 1936 2312 1544 1917 2290 8
J130 1559 1936 2312 1544 1917 2290 8

10 YORK INTERNATIONAL
FORM 150.60-NM5

DIMENSIONS
(SI)

LD01330

LD01332

LD01331
LD01333

NOTES:
1. Clearances – Recommended YORK clearances for peak performance, reliable operation, and maintenance:
Side to wall – 2440 mm; Rear to wall – 2440 mm; Control panel end to wall – 1525 mm; Over the top – no obstructions allowed; Two
units side by side – 3660 mm, (walls should be no higher than the unit). The area within the clearances and under the unit(s) must be kept
clean of clutter. Additional height should be included to allow for snow accumulation for units which are expected to operate at full load
during the winter. Reduced clearances may be used due to jobsite restrictions. The unit(s) with optional controls will allow optimal operation
preventing the condenser pressure from exceeding the maximum limit. The units will continue to operate without nuisance high pressure
cutout even though the airflow may be restricted at these conditions.

2. Panel bottom to be punched in field to accommodate power wiring conduit.


3. Use of isolators (optional) will increase height of unit approximately 152 mm.
4. Drawings not to scale and are for planning purposes only. Contact nearest YORK Sales Office for detailed drawings.

See page 18 for 387 - 458 kW Unit Isolator Selection.

WATER
WEIGHT DISTRIBUTION (Kg)
CONN.
MODEL YCA
INLET/OUTLET
A B C D E F
DIA. (INCHES)
J110 707 878 1049 700 870 1039 8
J120 707 878 1049 700 870 1039 8
J130 707 878 1049 700 870 1039 8

YORK INTERNATIONAL 11
ELECTRICAL DATA
DUAL COMPRESSOR POWER SUPPLY WIRING (STANDARD)
SYSTEM #1 WIRING SYSTEM #2 WIRING
MODEL MIN2 COND. MIN2 COND.
YCA DUAL ELEM INCOMING CPR CPR FAN DUAL ELEM
NF CKT BKR 4
NF CKT BKR4 INCOMING CPR CPR FAN
MCA 1 FUSE WIRE RANGE 5
8
MCA1 FUSE WIRE RANGE5 RLA LRA8 FLA
DISC RLA LRA FLA DISC
SW (CU ONLY) EACH SW MIN MAX (CU ONLY) EACH
MIN.3 MAX.3 MIN MAX MIN.3 MAX.3
J110 -17 295 350 500 400 350 450 (2) #6 - 250 212 803 10.0 295 350 500 400 350 450 (2) #6 - 250 212 803 10.0
J110 -28 267 350 450 400 350 400 (2) #6 - 250 184 698 12.0 267 350 450 400 350 400 (2) #6 - 250 184 698 12.0
J110 -40 162 200 250 200 200 250 (2) #6 - 250 116 441 5.2 162 200 250 200 200 250 (2) #6 - 250 116 441 5.2
J110 -46 131 175 200 200 175 200 (2) #6 - 250 92 349 5.0 131 175 200 200 175 200 (2) #6 - 250 92 349 5.0
J110 -58 107 150 175 200 150 150 (2) #6 - 250 74 279 4.9 107 150 175 200 150 150 (2) #6 - 250 74 279 4.9
J120 -17 368 450 600 400 450 600 (2) #6 - 250 270 1063 10.0 295 350 500 400 350 450 (2) #6 - 250 212 803 10.0
J120 -28 330 400 500 400 400 500 (2) #6 - 250 235 924 12.0 267 350 450 400 350 400 (2) #6 - 250 184 698 12.0
J120 -40 201 250 300 200 250 300 (2) #6 - 250 148 584 5.2 162 200 250 200 200 250 (2) #6 - 250 116 441 5.2
J120 -46 162 200 250 200 200 250 (2) #6 - 250 117 462 5.0 131 175 200 200 175 200 (2) #6 - 250 92 349 5.0
J120 -58 132 175 225 200 175 200 (2) #6 - 250 94 370 4.9 107 150 175 200 150 150 (2) #6 - 250 74 279 4.9
J130 -17 368 450 600 400 450 600 (2) #6 - 250 270 1063 10.0 368 450 600 400 450 600 (2) #6 - 250 270 1063 10.0
J130 -28 330 400 500 400 400 500 (2) #6 - 250 235 924 12.0 330 400 500 400 400 500 (2) #6 - 250 235 924 12.0
J130 -40 201 250 300 200 250 300 (2) #6 - 250 148 584 5.2 201 250 300 200 250 300 (2) #6 - 250 148 584 5.2
J130 -46 162 200 250 200 200 250 (2) #6 - 250 117 462 5.0 162 200 250 200 200 250 (2) #6 - 250 117 462 5.0
J130 -58 132 175 225 200 175 200 (2) #6 - 250 94 370 4.9 133 175 225 200 175 200 (2) #6 - 250 94 370 4.9

DUAL COMPRESSOR POWER SUPPLY WIRING STANDARD UNIT


UNIT PANELS
SYS.2 SYS.1
TERMINALS TERMINALS

L 2 G 2L1 2L2 2L3 1L1 1L2 1L3 SEE NOTE 5

G G

SYS 1
POWER
SUPPLY

115-1-60
CONTROL
POWER
SUPPLY SYS 2
POWER
SUPPLY
BY OTHERS

SEE NOTE 5

SEE NOTE 6 LD01173

NOTES for Electrical Data, pages 3 - 6:


1. Minimum circuit ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all
other loads included in the circuit, per N.E.C. Article 430-24. If a Factory Mounted Control Transformer is provided, add the following to
the system #1 MCA values in the YCA Tables: -17, add 10 amps; -28, add 9 amps; -40, add 5 amps; -46, add 4 amps; -58, add 3 amps.
2. Minimum Non-Fused Disconnect Switch size is based on a minimum of 115% of the sum of the RLAs for all the loads included in the circuit,
per N.E.C. 440-12A1. Available as factory-mounted option on units with single-point power supply.
3. Minimum Dual Element Fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs. (U.L. Standard 1995,
Section 36.1) Maximum Dual Element Fuse size is based on 225% of the maximum RLA plus 100% of the RLAs for all other loads included
in the circuit, per N.E.C. 440-22. Minimum fuse rating = 1.5 x Largest Compr RLA + Other Compr RLAs + (# fans) x Fan FLA. Maximum
fuse rating = 2.25 x Largest Compr RLA + Other Compr RLAs + (# Fans) x Fan FLA. These sizes are for field-supplied fuses.
4. Minimum and Maximum Circuit Breaker rating required per N.E.C. and U.L. 1995 Fig. 36.2. Minimum C.B. rating = 1.5 x Largest Compr RLA
+ Other Compr RLAs + (# Fans) x Fan FLA. Maximum C.B. rating = 2.25 x Largest Compr RLA + Other Compr RLAs + (# Fans) x Fan FLA.
5. Wire Range is the minimum and maximum wire size that can be accommodated by the unit wiring lugs. The (1), (2), or (3) preceding the
wire range indicates the number of termination points available per phase. The (1-2) preceding the wire range indicates that a single
double-barreled lug is available per phase that can accept up to two wires of the wire range specified. “(1) #1-600 or (2) #1-250”
indicates that a single lug is supplied and it will accept a single wire up to 600MCM or 2 wires up to 250MCM. Actual wire size and number
of wires per phase must be determined based on ampacity and job requirements using N.E.C. wire sizing information. The above
recommendations are based on the National Electrical Code and using copper connectors only. Field wiring must also comply with local
codes.
6. A ground lug is provided for each compr. system to accommodate field grounding conductor per N.E.C. Article 250-54. A control circuit
grounding lug is also supplied. Incoming ground wire range is #6 - 350 MCM (104 - 220 Tons)(334 - 810 kW).
7. The supplied disconnect is a “Disconnecting Means” as defined in N.E.C. 100.B, and is intended for isolating the unit from the available
power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.
8. All unit compressors have a part winding electrical configuration such that the indicated Locked Rotor Amps are Part Wind Locked Rotor
Amps. YCAJ110 - 130 models have part-wind start as standard.

12 YORK INTERNATIONAL
FORM 150.60-NM5

SINGLE POINT POWER SUPPLY WIRING (OPTIONAL)


SYSTEM #1 SYSTEM #2
MIN2
MODEL DUAL ELEM INCOMING
NF YORK SUPPLIED DISCONNECT
YCA MCA1 FUSE WIRE RANGE5 CPR CPR FAN CPR CPR FAN
(CU ONLY)
DISC (CU ONLY) RLA LRA8 FLA RLA LRA8 FLA
SW
MIN.3 MAX.3
J110 -46 238 300 300 400 (2) #2 - 600 (1) #1 - 600 or (2) #1 - 250 92 349 5.0 92 349 5.0
J110 -58 196 225 250 400 (2) #2 - 600 (1) #1 - 600 or (2) #1 - 250 74 279 4.9 74 279 4.9
J120 -46 269 300 350 400 (2) #2 - 600 (1) #1 - 600 or (2) #1 - 250 117 462 5.0 92 349 5.0
J120 -58 221 250 300 400 (2) #2 - 600 (1) #1 - 600 or (2) #1 - 250 94 370 4.9 74 279 4.9
J130 -46 294 350 400 400 (2) #2 - 600 (1) #1 - 600 or (2) #1 - 250 117 462 5.0 117 462 5.0
J130 -58 241 300 300 400 (2) #2 - 600 (1) #1 - 600 or (2) #1 - 250 94 370 4.9 94 370 4.9

POWER SUPPLY WIRING FACTORY DISCONNECT SWITCHES AND FUSES


FACTORY MOUNTED SYSTEM #1 SYSTEM #2
MIN2
MODEL DUAL ELEM NF DISCONNECT SWITCH COND. COND.
YCA CKT BKR4 FACT. MTD. FACT. MTD.
MCA1 FUSE INCOMING CPR CPR FAN CPR CPR FAN
DISC FUSE RLA LRA8 FLA FUSE RLA LRA8 FLA
WIRE RANGE5
SW EACH MIN3 EACH
MIN.3 MAX.3 MIN MAX (CU ONLY) MIN3 MAX3 MAX3
J110 -17 537 600 700 600 600 700 (3) 3/0 - 500 350 500 212 1005 10.0 350 500 212 1005 10.0
J110 -28 487 600 600 600 600 600 (3) 3/0 - 500 350 450 184 874 12.0 350 450 184 874 12.0
J110 -40 293 350 400 400 350 400 (1) #1 - 600 or (2) #1 - 250 200 250 116 552 5.2 200 250 116 552 5.2
J110 -46 238 300 300 400 300 300 (1) #1 - 600 or (2) #1 - 250 175 200 92 437 5.0 175 200 92 437 5.0
J110 -58 196 225 250 400 225 250 (1) #1 - 600 or (2) #1 - 250 150 175 74 350 4.9 150 175 74 350 4.9
J120 -17 610 700 800 800 700 800 (3) 3/0 - 500 450 600 270 1332 10.0 350 500 212 1005 10.0
J120 -28 550 700 700 600 700 700 (3) 3/0 - 500 400 500 235 1158 12.0 350 450 184 874 12.0
J120 -40 333 400 450 400 400 450 (1) #1 - 600 or (2) #1 - 250 250 300 148 731 5.2 200 250 116 552 5.2
J120 -46 269 300 350 400 300 350 (1) #1 - 600 or (2) #1 - 250 200 250 117 579 5.0 175 200 92 437 5.0
J120 -58 221 250 300 400 250 300 (1) #1 - 600 or (2) #1 - 250 175 225 94 463 4.9 150 175 74 350 4.9
J130 -17 668 800 800 800 800 800 (3) 3/0 - 500 450 600 270 1332 10.0 450 600 270 1332 10.0
J130 -28 600 700 800 800 700 800 (3) 3/0 - 500 400 500 235 1158 12.0 400 500 235 1158 12.0
J130 -40 365 450 500 400 450 500 (1) #1 - 600 or (2) #1 - 250 250 300 148 731 5.2 250 300 148 731 5.2
J130 -46 294 350 400 400 350 400 (1) #1 - 600 or (2) #1 - 250 200 250 117 579 5.0 200 250 117 579 5.0
J130 -58 241 300 300 400 300 300 (1) #1 - 600 or (2) #1 - 250 175 225 94 463 4.9 175 225 94 463 4.9

See page 3 for notes.

DISCONNECT OPTION

UNIT PANEL

L 2 G 2L1 2L2 2L3 1L1 1L2 1L3

LEGEND:
L3
L1

L2
GRD

GRD

VOLT = Voltage
MCA = Minimum Circuit Ampacity CONTROL OPTIONAL
DISC = Disconnect POWER FACTORY-
SUPPLY MOUNTED
N/A = Not Available FUSES
CPR-RLA = Compressor Running Load Amps
CPR-RLA = Compressor Part Winding Inrush Amps BY OTHERS
FLA = Full Load Amps
CKT BRK = Circuit Breaker LD1174(R)

HACR = Heating, Air Conditioning and Refrigeration SEE NOTE 5

YORK INTERNATIONAL 13
POWER SUPPLY WIRING SINGLE POINT WITH FACTORY UNIT MOUNTED CIRCUIT BREAKERS
SYSTEM #1 SYSTEM #2
MIN2
MODEL DUAL ELEM NF INCOMING COND. COND.
YCA CKT BKR4 FACT. MTD. FACT. MTD.
MCA1 FUSE WIRE RANGE5 CPR CPR FAN CPR CPR FAN
DISC FUSE RLA LRA8 FLA FUSE RLA LRA8 FLA
(CU ONLY)
SW EACH MIN3 EACH
MIN.3 MAX.3 MIN MAX MIN3 MAX3 MAX3
J110 -17 537 600 700 600 600 700 (3) 3/0 - 500 350 450 212 1005 10.0 350 450 212 1005 10.0
J110 -28 487 600 600 600 600 600 (1) #1 - 600 or (2) #1 - 250 350 400 184 874 12.0 350 400 184 874 12.0
J110 -40 293 350 400 400 350 400 (1) #1 - 600 or (2) #1 - 250 200 250 116 552 5.2 200 250 116 552 5.2
J110 -46 238 300 300 400 300 300 (1) #1 - 600 or (2) #1 - 250 175 200 92 437 5.0 175 200 92 437 5.0
J110 -58 196 225 250 400 225 250 (1) #1 - 600 or (2) #1 - 250 150 150 74 350 4.9 150 150 74 350 4.9
J120 -17 610 700 800 800 700 800 (3) 3/0 - 500 450 600 270 1332 10.0 350 450 212 1005 10.0
J120 -28 550 700 700 600 700 700 (3) 3/0 - 500 400 500 235 1158 12.0 350 400 184 874 12.0
J120 -40 333 400 450 400 400 450 (1) #1 - 600 or (2) #1 - 250 250 300 148 731 5.2 200 250 116 552 5.2
J120 -46 269 300 350 400 300 350 (1) #1 - 600 or (2) #1 - 250 200 250 117 579 5.0 175 200 92 437 5.0
J120 -58 221 250 300 400 250 300 (1) #1 - 600 or (2) #1 - 250 175 200 94 463 4.9 150 150 74 350 4.9
J130 -17 668 800 800 800 800 800 (3) 3/0 - 500 450 600 270 1332 10.0 450 600 270 1332 10.0
J130 -28 600 700 800 800 700 800 (3) 3/0 - 500 400 500 235 1158 12.0 400 500 235 1158 12.0
J130 -40 365 450 500 400 450 500 (1) #1 - 600 or (2) #1 - 250 250 300 148 731 5.2 250 300 148 731 5.2
J130 -46 294 350 400 400 350 400 (1) #1 - 600 or (2) #1 - 250 200 250 117 579 5.0 200 250 117 579 5.0
J130 -58 241 300 300 400 300 300 (1) #1 - 600 or (2) #1 - 250 175 200 94 463 4.9 175 200 94 463 4.9

See page 3 for notes.

SINGLE POINT WITH FACTORY MOUNTED


CIRCUIT BREAKERS

L 2 G 2L1 2L2 2L3 1L1 1L2 1L3


GRD

GRD

CONTROL
POWER
SUPPLY

BY OTHERS

COMPRESSOR
POWER
SUPPLY

LD01556(R)

14 YORK INTERNATIONAL
FORM 150.60-NM5

SINGLE POINT OPTION

UNIT PANEL

L 2 G 2L1 2L2 2L3 1L1 1L2 1L3

G G

L1 L2 L3
SEE NOTE 6 (TYP)

115-1-60
CONTROL
POWER
SUPPLY

COMPRESSOR
SEE NOTE 5 POWER
BY OTHERS SUPPLY

LD01175

See page 3 for notes.

LEGEND:

VOLT = Voltage
MCA = Minimum Circuit Ampacity
DISC = Disconnect
N/A = Not Available
CPR-RLA = Compressor Running Load Amps
CPR-RLA = Compressor Part Winding Inrush Amps
FLA = Full Load Amps
CKT BRK = Circuit Breaker
HACR = Heating, Air Conditioning and Refrigeration

CONTROL POWER SUPPLY

MAXIMUM NON-FUSED
CONTROL MINIMUM
UNIT DUAL- DISC.
POWER CIRCUIT
VOLTAGE ELEMENT SWITCH
SUPPLY AMPACITY
FUSE SIZE SIZE
Standard
Models without 115-1-60 20A 20A, 250V 30A, 240V
Transformers

YORK INTERNATIONAL 15
INSTALLATION
3. Open unit only to install water piping system. Do not
WARNING: remove protective covers from water connections until
piping is ready for attachment. Check water piping to
To protect warranty, this equipment must be in-
insure cleanliness.
stalled and serviced by an authorized YORK ser-
vice mechanic or a qualified service person experi- 4. Pipe unit using good piping practice and consistent
enced in chiller installation. Installation must com- with local code requirements.
ply with all applicable codes, particularly in regard 5. Check to see that unit is installed and operated within
to electrical wiring and other safety elements such LIMITATIONS shown on pages 7 and 8.
as relief valves, HP cutout settings, design work-
ing pressures and ventilation requirements consis- The following pages outline procedures to be followed.
tent with the amount and type of refrigerant charge.
HANDLING
Lethal voltages exist within the control panel. Be-
fore servicing, open and tag all disconnect switches.
These units are shipped as completely assembled units
containing full operating charge, and care should be taken
to avoid damage due to rough handling.
INSTALLATION CHECKLIST
The units are shipped without export crating unless it is
The following items, 1 thru 5, must be checked before
specified by Sales Order.
placing units into operation.
A unit should be lifted by inserting hooks through the
1. Inspect unit for shipping damage. holes provided in unit base rails. Spreader bars should
2. Rig unit per Fig. 4. Remove unpainted shipping braces be used to avoid crushing the unit with the lifting chains.
after installation. (See Fig. 4).

28694A(R)

FIG. 4 – RIGGING THE CHILLER

16 YORK INTERNATIONAL
FORM 150.60-NM5

INSPECTION bonded. Roof installations should have wooden beams


(treated to reduce deterioration), cork, rubber or vibra-
Immediately upon receiving the unit, it should be in-
tion isolators under the base to minimize vibration.
spected for possible damage which may have occurred
during transit. If damage is evident, it should be noted on
SHIPPING BRACES
the carrier’s freight bill. A written request for inspection
by the carrier’s agent should be made at once. See In- Two shipping brackets (typically galvanized steel) which
struction 50.15-NM for more information and details. run diagonally along each side of the unit, must be re-
moved once the unit is mounted on its foundation. A
LOCATION AND CLEARANCES third bracket on the right rear of the unit should also be
removed. This bracket runs across the bottom right cor-
These units are designed for outdoor installations on
ner of the unit behind the compressors.
ground level, rooftop, or beside a building. The location
should be selected for minimum sun exposure and to
SPRING ISOLATORS (OPTIONAL)
insure an adequate supply of fresh air for the condenser.
The units must be installed with sufficient clearances for When ordered, six (6) spring isolators will be furnished.
air entrance to the condenser coil, for air discharge away
1. Identify isolator and locate at proper mounting point
from the condenser, and for servicing access.
using table on page 18.
In installations where winter operation is intended and 2. Block up equipment so as to install spring mounts
snow accumulations are expected, additional height must with pin on top of housing into Equipment Mounting
be provided to insure normal condenser air flow. (See Holes.
DIMENSIONS). 3. Mounting Adjust Nut is inside the isolator mount lo-
cated just below the top plate of the mount. Turn nut
FOUNDATION 2 turns clockwise (down) to load spring mount at each
The unit should be mounted on a flat and level founda- location.
tion, floor or rooftop, capable of supporting the entire 4. Take two additional turns on Adjustment Nut of each
operating weight of the equipment. See PHYSICAL DATA location.
for operating weight. If the unit is elevated beyond the 5. Repeat step No. 3 as many times as necessary to
normal reach of service personnel, a suitable catwalk bring height of isolator to proper height.
must be constructed around the unit. The catwalk must
6. Take additional turns on mounts at low side or corner
be capable of supporting service personnel, their equip-
to level the equipment.
ment, and the reciprocating compressors.
Ground Level Locations COMPRESSOR MOUNTING

It is important that the units be installed on a substantial The compressors are mounted on four (4) isolator pads
base that will not settle. A one piece concrete slab with (one under each compressor foot). (See Fig. 5). The mount-
footers extended below the frost line is highly recom- ing bolts are not to be loosened or adjusted at installation.
mended. Additionally, the slab should not be tied to the
main building foundations as noise and vibration may be
transmitted.
Mounting holes are provided in the steel channel for bolt-
ing the unit to its foundation. (See DIMENSIONS).
For ground level installations, precautions should be taken
to protect the unit from tampering by or injury to unau-
thorized persons. Screws and/or latches on access pan-
els will prevent casual tampering. However, further safety
precautions such as a fenced-in enclosure or locking
devices on the panels may be advisable. A tamperproof
kit is available as an option. Check local authorities for
safety regulations.

Rooftop Locations
Choose a spot with adequate structural strength to safely
support the entire weight of the unit and service person-
nel. Care must be taken not to damage the roof. COMPRESSOR MOUNTING PAD 25112A

Consult the building contractor or architect if the roof is FIG. 5 – COMPRESSOR MOUNTING PAD

YORK INTERNATIONAL 17
WEIGHT DISTRIBUTION AND ISOLATOR LOCATIONS FOR EACH MODEL

LD01089

VMC CP-2-X
NOTE: Standard 1" deflection isolator drawings. Consult your nearest YORK representative for additional isolator options.

ISOLATOR LOCATIONS (95 - 130 TONS [335 - 458 kW])


MODEL A B C D E F
YCAJ110 CP-2-28 CP-2-31 CP-2-32 CP-2-28 CP-2-31 CP-2-32
YCAJ120 CP-2-28 CP-2-31 CP-2-32 CP-2-28 CP-2-31 CP-2-32
YCAJ130 CP-2-28 CP-2-31 CP-2-32 CP-2-28 CP-2-31 CP-2-32

LD02957

WATER
WEIGHT DISTRIBUTION (LBS.)
CONN.
MODEL YCA
INLET/OUTLET
A B C D E F
DIA. (INCHES)
J110 1559 1936 2312 1544 1917 2290 8
J120 1559 1936 2312 1544 1917 2290 8
J130 1559 1936 2312 1544 1917 2290 8

18 YORK INTERNATIONAL
FORM 150.60-NM5

CHILLED LIQUID PIPING ers) MUST be installed in the leaving water piping of
the cooler. There should be a straight horizontal run
GENERAL – When the unit has been located in its final of at least 5 diameters on each side of the switch.
position, the unit liquid piping may be connected. Nor- Adjust the flow switch paddle to the size of pipe in
mal installation precautions should be observed in order which it is to be installed. (See manufacturer’s in-
to receive maximum operating efficiencies. Piping should structions furnished with switch). The switch is to be
be kept free of all foreign matter. All liquid cooler piping wired to terminals in the control panel as shown in
must comply in all respects with local plumbing codes the WIRING DIAGRAM (pages 20 - 28).
and ordinances.

Since elbows, tees and valves decrease pump capacity, WARNING: Flow switch must not be used to stop and
all piping should be kept as simple as possible. start chilier. It is intended only as a safety
switch.
Hand stop valve should be installed in all lines to facili-
tate servicing. COMPRESSOR INSULATION
Piping to the inlet and outlet connections of the chiller In high humidity environments, compressor sweating may
should include high-pressure rubber hose or piping loops be noted. In most applications, this is of no concern. How-
to insure against transmission of water pump vibration. ever, if it is undesirable, it is the responsibility of the in-
This is optional and the necessary components must be staller to make provisions to field insulate the compressor
obtained in the field. or install a factory insulation kit when they become avail-
able. Contact YORK Factory Marketing for availability.
Drain connections should be provided at all low points to
permit complete drainage of liquid cooler and piping sys-
ELECTRICAL WIRING
tem.
Liquid Chillers are shipped with all factory mounted con-
A small valve or valves should be installed at the highest
trols wired for operation.
point or points in the chilled liquid piping to allow any
trapped air to be purged. Vent and drain connections Field Wiring – Power wiring must be provided through
should be extended beyond the insulation to make them a fused disconnect switch to the unit terminals (or op-
accessible. tional molded case disconnect switch) in accordance
The piping to and from the cooler must be designed to with N.E.C. or local code requirements. Minimum circuit
suit the individual installation. It is important that the ampacity and maximum dual element fuse size are given
following considerations be observed: on pages 12 - 15. A 115-1-60/50, 20 amp source must
be supplied for the control panel through a fused discon-
1. The chilled liquid piping system should be laid out so nect when a control panel transformer (optional) is not
that the circulating pump discharges directly into the provided. Refer to WIRING DIAGRAM (pages 20 - 28).
cooler. The suction for this pump should be taken from
the piping system return line and not the cooler. Affiliated apparatus, such as a chilled water flow switch,
2. The inlet and outlet cooler liquid connection sizes are auxiliary contacts from the chilled water pump starter,
given on pages 10 and 11. alarms, etc., should be interlocked into the control panel
3. A strainer, preferably 40 mesh, MUST be installed in circuit. These field modifications may be made as shown
the cooler inlet line just ahead of the cooler. on the WIRING DIAGRAM (pages 20 - 28).
4. All chilled liquid piping should be thoroughly flushed MULTIPLE UNITS
to free it from foreign material before the system is
placed into operation. Use care not to flush any for- For increased compressor protection and to reduce power
eign material into or through the cooler. inrush at start-up on multiple chiller installations, provi-
5. As an aid to servicing, thermometers and pressure sions must be made to prevent simultaneous startup of
gauges should be installed in the inlet and outlet wa- two or more units. Also, some method must be employed
ter lines. One connection point (plugged) is provided to automatically cycle one or more of the units on or off
in each cooler nozzle. Thermometers and gauges are to permit more efficient operation at part load conditions.
not furnished with the unit and are to be furnished by A sequencing kit may be acquired through your local
other suppliers. YORK representative.
6. The chilled liquid lines that are exposed to outdoor
ambients should be wrapped with a supplemental RELIEF VALVES
heater cable and insulated to protect against freeze- An internal relief valve(s) is installed internally in each
up during low ambient periods, and to prevent forma- compressor. A second integral internal relief valve is
tion of condensation on lines in warm humid climates. built into the liquid line solenoid valve of each system.
7. A chilled water flow switch, (either by YORK or oth- All relief valves are resealable type safety devices.

YORK INTERNATIONAL 19
YCAJ110 - 130 WIRING DIAGRAM
ELEMENTARY DIAGRAM

LD02222

NOTES:
LEGEND
1. Field wiring to be in accordance with the current edition of the
TS Transient Voltage Suppression
National Electrical Code as well as all other applicable codes and
Terminal Block for Customer Connections specifications.
Terminal Block for Customer Low Voltage 2. Contacts must be suitable for switching 24VDC, (gold contacts
(Class 2) Connections. See Note 2 recommended). Wiring shall not be run in the same conduit with
Terminal Block for YORK Connections Only any line voltage wiring.
3. To cycle unit on and off automatically with contact shown, install
Wiring and Components by YORK
a cycling device in series with the flow switch (FLSW). See Note
Optional Equipment 2 for contact rating and wiring specifications. Also refer to cau-
Wiring and/or Components by Others tions on the following page.
4. To stop unit (Emergency Stop) with contacts other than those
shown, install the stop contact between terminals 5 and 1. If a
stop device is not installed, a jumper must be connected be-
tween terminals 5 and 1. Device must have a minimum contact
rating of 100VA at 115 volts A.C.
5. Contacts are rated at 115V, 100VA, resistive load only, and must
be suppressed at load by user.
6. See Installation, Operation and Maintenance Manual.
7. Power factor correction capacitors may be installed on the chiller
electrical system (as shown) as a factory installed option.
8. Jumper installed for simultaneous operation of condenser fans 5
& 6.

FIG. 6 – ELEMENTARY DIAGRAM

20 YORK INTERNATIONAL
FORM 150.60-NM5

LD02223

FIG. 6 – ELEMENTARY DIAGRAM (Cont’d)

YORK INTERNATIONAL 21
ELEMENTARY DIAGRAM

22 YORK INTERNATIONAL
YORK INTERNATIONAL

CAUTION:
No Controls (relays,
etc.) should be
mounted in the Smart
Panel enclosure or
connected to power
supplies in the control
panel. Additionally, con-
trol wiring not con-
nected to the Smart
Panel should not be run
through the cabinet.
This could result in nui-
sance faults.

CAUTION:
Any inductive devices
(relays) wired in series
with the flow switch for
start/stop, into the
Alarm circuitry, or pilot
relays for pump start-
ers wired through mo-
tor contactor auxiliary
contacts must be sup-
pressed with YORK
P/N 031-00808-000
suppressor across the
relay/contactor coil.

Any contacts con-


nected to flow switch
inputs or BAS inputs on
terminals 13 - 19 or
TB3, or any other ter-
minals, must be sup-
pressed with a YORK CONTROL POWER SUPPLY
P/N 031-00808-000
suppressor across the MAXIMUM NON-FUSED
CONTROL MINIMUM
relay/contactor coil. UNIT DUAL- DISC.
POWER CIRCUIT
VOLTAGE ELEMENT SWITCH
CAUTION: SUPPLY AMPACITY
Control wiring con- FUSE SIZE SIZE

FORM 150.60-NM5
nected to the control Standard
panel should never be
Models without 115-1-60 20A 20A, 250V 30A, 240V
run in the same con-
duit with power wiring. Transformers

FIG. 6 – ELEMENTARY DIAGRAM (Cont’d)


23

LD02221
CONNECTION DIAGRAM

FIG. 7 – CONNECTION DIAGRAM LD0224

24 YORK INTERNATIONAL
FORM 150.60-NM5

FIG. 7 – CONNECTION DIAGRAM (Cont’d) LD02225

YORK INTERNATIONAL 25
CONNECTION DIAGRAM
TERMINAL BOX AND SYSTEM WIRING

LD02697

FIG. 8 – SYSTEM WIRING

26 YORK INTERNATIONAL
FORM 150.60-NM5

CONNECTION DIAGRAM
TERMINAL BOX AND SYSTEM WIRING

LD02698

FIG. 8 – SYSTEM WIRING (Cont’d)

YORK INTERNATIONAL 27
YCAJ110 - 130 CONNECTION DIAGRAM
TERMINAL BOX AND SYSTEM WIRING

LD02226

FIG. 8 – SYSTEM WIRING (Cont’d)

28 YORK INTERNATIONAL
FORM 150.60-NM5

UNIT CONTROLS AND OPERATION


YORK MILLENNIUM CONTROL CENTER

02711TG

FIG. 9 – CONTROL CENTER KEYPAD

INTRODUCTION MICROPROCESSOR BOARD

The YORK Millennium Control Center is a microproces- The Microprocessor Board is the controller and decision-
sor based control system capable of multi-circuit control maker in the control panel. System inputs from pres-
to maintain chilled liquid temperature. sure transducers, temperature sensors, and C.T.s are
connected directly to the Microprocessor Board. The Mi-
A 40 character display (2 lines of 20 characters) allows croprocessor Board circuitry multiplexes these analog
the operator to display system operating parameters as inputs, digitizes them, and constantly scans them to
well as access programmed information already in keep a constant watch on the chiller operating condi-
memory. A keypad for programming and accessing set- tions. From this information, the Microprocessor then
points, pressures, temperatures, motor current, cutouts, issues commands to the Relay Output Board to control
daily schedule, options, and fault information is provided. contactors, solenoids, etc. for water temperature con-
trol and to react to safety conditions.
A master ON/OFF switch is available to activate or de-
activate the chiller system. Separate system (SYS) Keypad commands are acted upon by the micro to
switches for each refrigerant system (up to 4) are pro- change setpoints, cut-outs, scheduling, operating re-
vided on the Microprocessor Board. quirements, and to provide displays.

Remote cycling, unloading, and chilled water tempera- A +12V REG supply voltage from the Power Supply Board
ture reset can be accomplished by user supplied dry is converted to +5V REG by a voltage regulator located
contacts. on the Microprocessor Board. This voltage is used to
operate integrated circuitry on the board.
Compressor starting/stopping and loading/unloading de-
cisions are performed by the Microprocessor to main- Four system switches located on the Microprocessor
tain leaving water temperatures. These decisions are a Board activate or deactivate the individual systems (com-
function of temperature deviation from setpoint and rate pressors).
of change of temperature.

YORK INTERNATIONAL 29
POWER SUPPLY BOARD CURRENT TRANSFORMER (C.T.)

The on-board switching power supply converts 24VAC A C.T. on the 3φ power wiring of each motor sends AC
from the 2T transformer to +12V REG which is supplied signals proportional to motor current to the Power Sup-
to the Microprocessor Board, Relay Board, and 40 Char- ply Board which rectifies and filters the signal to variable
acter Display to operate integrated circuitry. DC voltage (analog). This analog level is then fed to the
Microprocessor Board to allow it to monitor motor cur-
A rectifier and filtering circuit for each motor current cir- rent.
cuit rectifies and filters these signals to variable DC.
These signals are then fed to the Microprocessor Board. 40 CHARACTER DISPLAY

RELAY OUTPUT BOARD The 40 Character Display (2 lines of 20 characters) is a


liquid crystal display used for displaying system param-
This board converts 0 - 12VDC logic level outputs from eters and operator messages. The display has a lighted
the Microprocessor Board to 120VAC levels used by background for night viewing as well as a special feature
motor contactors, solenoid valves, etc. to control sys- which intensifies the display for viewing in direct sun-
tem operation. The common side of all relays on the light.
Relay Output Board is converted to +12V REG.
KEYPAD
The open collector outputs of the Microprocessor Board
energize the DC relays by pulling the other side of the An operator keypad allows complete control of the sys-
relay coil to ground. When not energized, both sides of tem from a central location. The keypad offers a multi-
the relay coils will be at +12VDC potential. tude of commands available to access displays, pro-
gram setpoints, and initiate system commands.
I/O EXPANSION BOARD
BATTERY BACK-UP
The I/O Expansion Board allows the Micro to receive
additional analog inputs from Oil Temperature Sensors The Microprocessor Board contains a Real Time Clock
and optional Discharge Temperature Sensors. integrated circuit chip with an internal battery back-up.
The purpose of this battery back-up is to assure any
These inputs are multiplexed and sent to the micropro- programmed values (setpoints, clock, cut-outs, etc.) are
cessor board to allow the micro to monitor these inputs not lost during a power failure regardless of the time in-
for display and as safeties. volved in a power outage or shutdown period.

CURRENT TRANSFORMER

FAN FAN
OVERLOADS OVERLOADS

FAN
CONTACTORS
FAN
CONTACTORS

TB

TB1: CONNECTIONS
FOR OPTIONAL GROUND
ALARMS, EVAP. LUG
PUMP, COND. PUMP,
EMERG. STOP AND
L & 2 115VAC
CONTROL PANEL
SUPPLY
28696A

FIG. 10 – POWER PANEL

30 YORK INTERNATIONAL
FORM 150.60-NM5

POWER
SUPPLY
BOARD
LCD DISPLAY
BOARD

2T
TRANSFORMER

RELAY
OUTPUT
MICROPROCESSOR BOARD #1
BOARD

LOCATION
OF OPTIONAL
RELAY
OUTPUT
BOARD #2
UNIT ON/OFF
SWITCH
TB3
CONNECTIONS
FOR FLOW
26000A
SWITCH,
LEAD/LAG
SELECT &
EMS/BAS
FIG. 11 – CONTROL PANEL WITHOUT I/O EXPANSION PANEL CONTROLS

POWER SUPPLY
I /O EXPANSION BOARD
BOARD

LCD DISPLAY 2T TRANSFORMER


BOARD

RELAY OUTPUT
BOARD #1

RELAY OUTPUT
BOARD #2
MICROPROCESSOR
BOARD

28697A
TB3
CONNECTIONS FOR
FLOW SWITCH,
AUXILLIARY CYCLING,
LEAD/LAG SELECTOR
FIG. 12 – CONTROL PANEL WITH I/O EXPANSION PANEL & EMS/BAS CONTROLS

YORK INTERNATIONAL 31
“DISPLAY” KEYS

“DISPLAY”
KEYS

02711TG

GENERAL Chilled Liquid Temps CHILLED


LIQUID TEMPS
The DISPLAY keys allow the user to retrieve system A display indicating chiller leaving and return water tem-
pressures, system motor currents, chilled liquid tem- perature is provided when this push-button is pressed.
peratures, outdoor ambient temperature, compressor
running times, number of compressor starts, and option LW T = 4 9 . 2 D E G F
information on the chiller package. This data is useful for RW T = 5 2 . 0 D E G F
monitoring chiller operation, diagnosing potential future
problems, troubleshooting, and commissioning the chiller. The minimum limit on the display is “8.7 DEG F”. The
maximum limit on the display is “84.5 DEG F”.
Displayed data will be real-time data displayed on a “40”
character display consisting of 2 lines of 20 characters. Ambient Temp AMBIENT
The display will update all information at a rate of about TEMP
“2” seconds. The outdoor ambient temperature is displayed when this
push-button is pressed.
When a DISPLAY push-button is pressed, the corre-
sponding message will be displayed and will remain on O U T S I D E AM B I E N T A I R
the display until another push-button is pressed.
= 7 5 . 9 D E G F

Display Messages may show characters indicating The minimum limit on the display is “0 DEG F”. The
“greater than” (>) or “less than” (<). These characters maximum limit on the display is “ 133.8 DEG F”.
indicate the actual values are greater than or less than
the limit values which are being displayed. System 1 Pressures SYSTEM 1
PRESSURES
If a message is required to be updated faster than every Oil pressure, suction pressure, and discharge* pressure
2 seconds, the appropriate key for the desired display on System 1 will be displayed when this push-button is
may be pushed and held. Updating will be at 0.4 second pressed.
intervals.
S Y S # 1 O I L = 7 2 P S I D
Each of the keys and an example of the typical corre- S P = 6 0 , D P = 2 2 9 P S I G
sponding display messages will be discussed in the text
which follows.

* Discharge Pressure Readout is an option. Without this option, the display will read a fixed value.

32 YORK INTERNATIONAL
FORM 150.60-NM5

The minimum limits are: on each compressor are also displayed. A total of 99999
Oil Pressure: 0 PSID (0 bar) starts can be logged on a system before the counter will
rollover.
Suction Pressure: 0 PSIG (0 bar)
Discharge Pressure: 0 PSIG (0 bar) H R S 1 = 1 4 3 , 2 = 3 8 2
S T R 1 = 2 5 , 2 = 3 7
The maximum limits are:
Oil Pressure: 200 PSID (13.8 bar)
Suction Pressure: 200 PSIG (13.8 bar) The numbers “1” and “2” on the display message indi-
cate compressor #1 and compressor #2.
Discharge Pressure: 400 PSIG (27.6 bar)
These counters are zeroed at the factory or will indicate
SYSTEM 2 only run time and number of starts logged during factory
System 2 Pressures PRESSURES testing at the time of shipment.
Oil pressure, suction pressure, and discharge pressure
on System 2 will be displayed when this push-button is OPTIONS
Options
pressed.
The OPTIONS key provides a display of options which
S Y S # 2 O I L = 6 3 P S I D
have been selected by the user. These options are se-
S P = 6 1 , D P = 1 3 3 P S I G
lected by the S1 Dip Switch on the Microprocessor Board
(Fig. 13). Proper programming of the switch is important
The minimum limits are:
during commissioning of the chiller. The OPTIONS dis-
Oil Pressure: 0 PSID (0 bar) play allows a means of verifying the Dip Switch posi-
Suction Pressure: 0 PSIG (0 bar) tions without looking at or handling the Microprocessor
Discharge Pressure: 0 PSIG (0 bar) Board. It also eliminates visual inspection of the some-
times difficult to determine Dip Switch position.
The maximum limits are:
When the OPTIONS key is pressed, the following mes-
Oil Pressure: 200 PSID (13.8 bar)
sage will first be displayed for 3 seconds:
Suction Pressure: 200 PSIG (13.8 bar)
Discharge Pressure: 400 PSIG (27.6 bar) T H E F O L L OW I N G
A R E P R O G R AMM E D

% MOTOR
% Motor Current CURRENT “8” Option Messages will then follow. Each will be dis-
played for 3 seconds before the next display is auto-
Motor currents for both System 1 and 2 are displayed matically indexed. When all messages are displayed,
when this push-button is pushed. the display message will automatically change to show
a chiller “STATUS” message, just as if the STATUS key
The minimum limits on the display is “0% FLA”. The was pressed.
maximum limit on the display is “115% FLA”.
Refer to Table 1 for a list of the displays and the corre-
1 M T R 1 = 5 7 % F L A sponding switch positions in the order they appear. Two
1 M T R 2 = 6 5 % F L A possible messages may appear for each of the eight
messages depending on the Dip Switch position.

Operating Hours OPER. HOURS A detailed explanation of the meaning of each message
Start Counter START COUNTER and a guide to programming the associated switch is
provided on pages 34 - 36.
Accumulated running hours on each compressor is dis-
played. The counters for an individual system count to a Fig. 13 shows the location and verification of switch po-
total of 99999 hours before rollover. Accumulated starts sitioning of S1.

YORK INTERNATIONAL 33
TABLE 1 – SWITCH POSITION AND DISPLAY

DISPLAY/
SWITCH “OPEN” MESSAGE SWITCH “CLOSED” MESSAGE
SWITCH
COM FO R T B R I N E & P RO C ES S
1
COO L I N G D U T Y

S T A ND A R D L OW A MB I E N T
2
AM B I E N T CO N T R O L

L OC A L CO N T R O L R EM O T E C O N T RO L
3
MO D E M OD E

R E T U R N W A T E R L E A V I N G WA T E R
4
C O N T RO L CO N T RO L

E NG L I S H U N I T S ME T R I C U N I T S
5
R E A DO U T R E A DO U T

S T A N DA R D CO N D E NS E R S H AR E D CO N D E NS E R
6
F AN CO N T RO L F A N C ON T RO L

M A NU A L A U T O MA T I C
7
L E A D / L A G L E A D / L A G

AM B I E N T & D I S CH P R D I S CH A R G E P R E S S U R E
8
F A N C ON T RO L F A N C ON T RO L

TOP VIEW
031-01652-001

EPROM

TOP SIDE

SIDE VIEW
RTC S1

“OPEN” POSITION
(LEFT SIDE OF SWITCH IS
PUSHED DOWN)

“CLOSED” POSITION
(RIGHT SIDE OF SWITCH IS
26001A PUSHED DOWN)

FIG. 13 – DIP SWITCH S1 AND EPROM LOCATION LD01098

34 YORK INTERNATIONAL
FORM 150.60-NM5

SWITCH 1 SWITCH 4
OPEN: OPEN:
C OM F O R T R E T U R N W A T E R
C O O L I N G C O N T R O L

The chilled liquid temperature setpoint can only be pro- Chiller control will be from return water temperature.
grammed from 40 - 70°F* (4.4 - 21.1°C).*

CLOSED: CLOSED:

B R I N E & C O O L I N G L E A V I N G W A T E R
D U T Y C O N T R O L

The chilled liquid temperature setpoint can be pro- Chiller control will be from leaving water temperature.
grammed from 15 - 70°F* (-9.4 - 21.1°C).*

SWITCH 2 SWITCH 5
OPEN: OPEN:
S T A N D A R D E N G L I S H U N I T S
AM B I E N T R E A D O U T

The low ambient cut-out is fixed at 25°F (-3.9°C). Display messages will show units of measure in English
units (°F, PSI, etc.).

CLOSED: CLOSED:

L OW AM B I E N T M E T R I C U N I T S
C O N T R O L R E A D O U T

The low ambient cut-out is programmable from 0 - 50°F Display messages will show units of measure in Metric
(-17.8 - 10°C). A low ambient kit MUST be installed if the units (°C, kPa, etc.).
switch is placed in this position.

SWITCH 3 SWITCH 6
OPEN: OPEN:

L O C A L C O N T R O L S T A N D A R D C O N D E N S E R
M O D E F A N C O N T R O L

This mode allows a Remote Control Center or an ISN This MUST be selected for chillers with “4” or more
panel to only view chiller operating conditions. It will not fans where each refrigerant system will have fans
allow changes to any chiller controls or setpoints. of its own.

CLOSED:
CLOSED:
R E M O T E C O N T R O L
M O D E S H A R E D C O N D E N S E R
F A N C O N T R O L
This mode should be selected in typical applications. It
will allow a Remote Control Center or an ISN panel to This MUST be selected for “2” fan chillers where
not only view chiller operating conditions, but will also fans are shared by both refrigerant circuits.
allow the remote panel to change chiller controls and
setpoints.

* Positioning of this switch also affects the range of adjustments on the Suction Pressure Cut-out (page 44) and the Low Leaving Water Temp.

YORK INTERNATIONAL 35
SWITCH 7 SWITCH 8
OPEN: OPEN:

M A N U A L AM B I E N T & D I S C H P R
L E A D / L A G F A N C O N T R O L

SYS 1 can be selected as the lag compressor by clos- Fan control will be by outside ambient temp. This will be
ing a user supplied contact between Terminals 13 and the standard mode of fan control for normal operation. In
19. See Page 69. this mode, maximum chiller efficiency will be achieved. If
the Low Ambient option is installed, the fan control will
CLOSED: automatically change to pressure control at temperatures
below 25°F (-3.9°C). See page 74 for fan control sequence.
A U T OM A T I C
L E A D / L A G CLOSED:

In this mode, the micro determines which compressor is D I S C H A R G E P R E S S U R E


assigned to the lead and the lag. A new lead/lag assign- F A N C O N T R O L
ment is made whenever both compressors shut down.
The micro will then assign the “lead” to the compressor Fan control is by discharge pressure only. This mode of
with the shortest anti-recycle time. fan control will increase discharge pressure. It should be
used if nuisance low suction pressure faults are experi-
enced. See page 74 for fan control sequence.

NOTE: Discharge pressure transducers must be in-


stalled. These are optional (Discharge Pressure
Read-out Option) unless a Low Ambient Kit is
installed.

36 YORK INTERNATIONAL
FORM 150.60-NM5

“STATUS” KEY

“STATUS”
KEY

02711TG

GENERAL SCHEDULE/HOLIDAY” is keeping the chiller from run-


ning.
Pressing the STATUS key will enable the operator to de-
termine current chiller operating status as a whole and as S Y S # 1 N O R U N P E RM
individual systems. The messages displayed will include S Y S # 2 N O R U N P E RM
running status, cooling demand, fault status, external cy-
cling device status, and anti-recycle timer status. The dis- Run Permissive is an indicator that an external cycling
play will be a single message relating to the highest prior- contact (i.e. flow switch) connected to terminals 13 and
ity message as determined by the micro. Status mes- 14 is open, or a system switch(es) on the Microproces-
sages fall into the categories of General and Fault Status sor Board is in the OFF position. Whenever the contact
with each of the categories discussed below. is open or a switch is OFF, the NO RUN PERM will be
displayed.
GENERAL STATUS MESSAGE
S Y S # 1 N O C O O L L O A D
Each of the general status messages with a description S Y S # 2 N O C O O L L O A D
of its meaning will follow. In the case of messages which
apply to individual systems, SYS 1 and SYS 2 mes- This message informs the operator that the chilled liquid
sages will both be displayed and may be different. “X”s temperature is below the point (determined by the
in the sample displays indicate numerical values will setpoint and control range) that the micro will bring the
appear in actual displays. lead system on, or that the micro has not loaded the
system far enough into the loading sequence to be ready
U N I T SW I T C H I S I N to bring the lag system ON. The lag system will display
T H E O F F P O S I T I O N this message until the loading sequence is ready for the
lag system to start (TEMPERATURE DEMAND in the
This message informs the operator that the “UNIT” switch OPER DATA displays must be “5” or above before cool-
on the Control Panel is in the OFF position which will ing load is established for the lag system to run).
not allow the chiller to run.
S Y S # 1 C OM P R U N N I N G
D A I L Y S C H E D U L E S Y S # 2 C OM P R U N N I N G
S H U T D OW N

The DAILY SCHEDULE SHUTDOWN message indicates


that the schedule programmed into the “CLOCK” “SET

YORK INTERNATIONAL 37
The COMP RUNNING message indicates that the re- down on a manual high pressure cut-out. Reloading will
spective compressor is running due to demand. take place when discharge pressure has dropped 60 PSIG
(413.9 kPa) below the threshold.
S Y S # 1 A R T M R X X X S
S Y S # 2 A R T M R X X X S Optional discharge pressure transducers must be in-
stalled for this feature to operate. This is accomplished
The anti-recycle timer message shows the amount of by adding the Discharge Pressure Readout option.
time left on the respective anti-recycle timer. This mes-
sage is displayed when demand requires the respective S Y S # 1 P UM P I N G D OW N
system to start but is being held off due to the timer. S Y S # 2 P UM P I N G D OW N

S Y S # 1 A C T M R X X S The PUMPING DOWN message indicates that the re-


S Y S # 2 A C T M R X X S spective compressor is presently in the process of pump-
ing the system down. The compressor will either be in a
The anti-coincident timer is a software feature that guards recycling pumpdown or in a pumpdown prior to shut-
against 2 compressors starting simultaneously. This as- down when this message is displayed. The message
sures instantaneous starting current does not become will disappear when the compressor shuts off.
excessively high due to simultaneous starts. The micro
limits the time between compressor starts to 1 minute M A N U A L
regardless of demand of the anti-recycle timer being timed O V E R R I D E
out. The time shown on the anti-coincident timer is the
time left on the timer before the respective system will If the MANUAL OVERRIDE key is pressed, the STATUS
start. Demand must be present for the message to be display will display the message shown above. This will
displayed and will only appear when the anti-recycle timer indicate that the Daily Schedule is being ignored and
has timed out. the chiller will start-up when water temperature allows,
UNIT Switch permits, and SYSTEM Switches permit.
S Y S # 1 C R N T L I M I T I N G
S Y S # 2 C R N T L I M I T I N G This is a priority message and cannot be overridden by
anti-recycle messages, fault messages, etc. when in
This display informs the operator that the micro is limit- the STATUS Display mode. Therefore, do not expect to
ing the loading of the system, based on motor current. see any other STATUS messages when in the MANUAL
By programming the AVERAGE CURR UNLOAD point, OVERRIDE mode. MANUAL OVERRIDE is to be used
the micro will limit the loading of the compressor when- only in emergencies or for servicing.
ever motor current rises above the programmed value.
FAULT STATUS MESSAGES
This feature reduces the chance of a system faulting on
high motor current, motor protector due to motor over- Fourteen possible fault messages may appear when the
heating, or high discharge pressure which causes high STATUS key is pressed. Whenever a fault message ap-
motor current. The feature also assures that motor life is pears, the safety thresholds on the chiller have been
not compromised. Typically, the AVERAGE CURR UN- exceeded and the entire chiller or a single system will
LOAD is programmed for 100% to assure that the com- be shut down and locked out. A detailed explanation of
pressor is allowed to load to its rated FLA. the shutdown thresholds and associated information re-
lated to each fault is covered in the SYSTEM SAFETIES
S Y S # 1 D S C H L I M I T I N G section (Page 57).
S Y S # 2 D S C H L I M I T I N G
Chiller shutdown faults will shut the entire chiller down
Discharge Pressure Limiting takes affect when discharge and lock it out, while system shutdown faults will only
pressure nears the point at which the high pressure cut- shut down and lock out the affected system (compres-
out will shut the system down causing total loss of cool- sor).
ing. When this message appears, discharge pressure
has exceeded the user programmable threshold and the A list of the fault messages are shown on the next page:
micro is unloading the affected system to prevent shut-

38 YORK INTERNATIONAL
FORM 150.60-NM5

CHILLER FAULTS SYSTEM FAULTS

C H I L L E R F A U L T : S Y S # 1 M O T O R C U R R E N T
L OW AM B I E N T T E M P S Y S # 2 M O T O R C U R R E N T

C H I L L E R F A U L T : S Y S # 1 H I G H D S C H
L OW W A T E R T E M P S Y S # 2 H I G H D S C H

C H I L L E R F A U L T : S Y S # 1 L OW O I L P R E S S
H I G H AM B I E N T T E M P S Y S # 2 L OW O I L P R E S S

C H I L L E R F A U L T : S Y S # 1 H I G H O I L T E M P
1 1 5 V A C U N D E R V O L T A G E S Y S # 2 H I G H O I L T E M P

S Y S # 1 L OW S U C T I O N
S Y S # 2 L OW S U C T I O N

S Y S # 1 O I L T E M P I N H I B
S Y S # 2 O I L T E M P I N H I B

S Y S # 1 H I M T R C U R R E N T
S Y S # 2 H I M T R C U R R E N T

S Y S # 1 P U M P D OW N F A I L
S Y S # 2 P U M P D OW N F A I L

YORK INTERNATIONAL 39
“ENTRY” KEYS

“ENTRY”
KEYS

02711TG

GENERAL The ENTER key is also used to scroll through available


data after any one of the following keys is pressed:
The ENTRY key allows the user to change numerical PROGRAM
values programmed in as chiller setpoints, cut-outs,
SET SCHEDULE/HOLIDAY
clock, etc.
OPER DATA
Numerical Keypad HISTORY

1 2 3 Cancel Key CANCEL

4 5 6 The CANCEL key allows the user to change errors in the


data being programmed into memory.
7 8 9
When the CANCEL key is pressed, any data which has
+/- been keyed in, but not entered, will be erased. The origi-
* 0
nal values will re-appear on the display and the cursor
The NUMERICAL keypad provides all keys needed to will return to the first character to be programmed in the
program numerical values as required. display message.

The “*” Key is used to designate holidays when program- AM/PM Key AM/PM
ming special start and stop times for designated holi-
days in the SET SCHEDULE/HOLIDAY display. The AM/PM key allows the user to change AM/PM while
programming the correct time in the SET TIME display.
The “+/-” key allows programming -°C setpoints and cut- The same key allows changing the AM/PM schedule
outs in the metric display mode. while programming daily chiller start and stop times in
the SET SCHEDULE/HOLIDAY display.
Enter Key ENTER
Advance Day Key ADVANCE
DAY
The ENTER key must be pushed after any change is
made to setpoints, cut-outs or the system clock. Press- The ADVANCE DAY key advances the day when the
ing this key tells the micro to accept the new values into SET TIME display is being programmed. The day is nor-
memory. mally advanced to correspond to the current day of the
week. The day will advance a day at a time, each time
If this is not done, the new numbers entered will be lost the key is pressed.
and the original values will be returned.

40 YORK INTERNATIONAL
FORM 150.60-NM5

“PROGRAM” KEY
PROGRAMMING USER PROGRAMMABLE SAFETIES AND LIMITS

“PROGRAM”
KEY

02711TG

GENERAL DISCHARGE CUT-OUT

Pushing the PROGRAM key allows the user to program D I S C H A R G E C U T O U T


“11” system operating limits. These limits include cutout = 3 9 5 P S I G
points for safeties, anti-recycle timer duration, and the
reaction time of the microprocessor to abrupt changes The DISCHARGE CUT-OUT is a microprocessor backup
in the chilled water temperatures. for the mechanical high pressure cut-out located in each
refrigerant circuit. Typically chillers with air-cooled con-
After the PROGRAM key is pressed, the micro will first densers should have the cut-out set at 395 PSIG (2.7
respond by displaying the DISCHARGE CUT-OUT. As mPa). Chillers with water-cooled condensers normal re-
the “11” limits are displayed, they may be reprogrammed quire the cut-out to be set at 275 PSIG (1.9 mPa).
using the “12” ENTRY keys. New values will be pro-
grammed into memory when the ENTER key is pushed. NOTE: In some water cooled condenser installations,
The ENTER key must also be used to advance the dis- the possibility exists for the condenser water
play the operator views the “10” system operating limits. pump or the cooling tower to not be in operation
Each time the key is pushed, the display will advance to when the chiller starts. This causes the dis-
the next limit. charge pressure to rise so rapidly that even
though the mechanical high pressure cut-out is
If the operator attempts to enter an unacceptable value, shutting down the compressor, the flywheel ef-
the micro will respond with a momentary message indi- fect may cause the pressure to continue to rise
cating the value selected has been ignored. This error causing the relief valve to open with a subse-
message is shown: quent refrigerant loss. By programming the cut-
out at the typical manual cut-out at 275 PSIG
O U T O F R A N G E (1.9 mPa), refrigerant loss due to system op-
T R Y A G A I N ! eration problems will be eliminated.

The “11” programmable limit displays are shown and To program the DISCHARGE CUT-OUT, key in the de-
described below along with the range of values which sired value and press the ENTER key. The new value will
the microprocessor will accept for each limit. THESE be entered into memory and the display will advance to
VALUES MUST BE CHECKED AND PROPERLY PRO- the next user programmable limit.
GRAMMED WHEN COMMISSIONING THE CHILLER.
The micro will accept a range of programmable values
FAILURE TO PROPERLY PROGRAM THESE VALUES
between 200 - 399 PSIG (1.4 - 2.8 mPa) for this cut-out.
MAY CAUSE DAMAGE TO THE CHILLER OR OPERA-
For this cut-out to be functional, the Discharge Pressure
TION PROBLEMS.
Readout Option must be installed.

YORK INTERNATIONAL 41
NOTE: It is required to first key in a “0” when program- The OUTSIDE AIR TMP HIGH CUT-OUT is selectable to
ming this cut-out (Example: 0395 PSIG). establish the high ambient cut-out point. If the ambient
rises above this point, the chiller will shut down. Restart
More details on this safety are outlined in the SYSTEM can occur when temperature drops below the cut-out.
SAFETIES section. This only applies to outdoor air-cooled chillers.

OUTSIDE AIR TMP LOW CUT-OUT This cut-out is normally set at 130.0°F (54.4°C) to allow
operation to the absolute maximum temperature capa-
O U T S I D E A I R T M P L OW bility of the electro-mechanical components.
C U T O U T = 2 5 . 0 F
To program the OUTSIDE AIR TMP HIGH CUT-OUT, key
The OUTSIDE AIR TMP LOW CUT-OUT allows the user in the desired value and press the ENTER key. The new
to select the chiller low ambient temperature cutout point. value will be entered into memory and the display will
If the ambient falls below this point the chiller will shut advance to the next user programmable limit.
down. Restart can occur, if demand allows, when tem-
perature rises above the cut-out. This only applies to The micro will accept a range of programmable values
outdoor air-cooled chillers. between 100.0 - 130.0°F (37.8 - 54.4°C) for this cut-out.

For normal ambient applications, the cut-out is set at DISCHARGE PRESSURE UNLOAD
25.0°F (-3.9°C) and is NOT programmable. However, some
users may set the cut-out higher to shut down the chiller D I S C H A R G E P R E S S U R E
and take advantage of other less costly cooling sources. U N L O A D = 3 6 0 P S I G
In this case, S1 Dip Switch #2 on the Micro Logic Board
must be in the CLOSED position for Low Ambient Control The DISCHARGE PRESSURE UNLOAD point is a pro-
to allow programming the cut-out above 25°F (-3.9°C). grammable limit to keep the system from faulting on the
high discharge pressure cut-out should a system prob-
Low ambient applications in ambients less than 25.0°F lem or chiller problem occur. A typical problem would be
(-3.9°C) require a low ambient kit to be installed. Other- if the cooling tower would become dirty on a water-cooled
wise nuisance low pressure and low motor current trips system. Pressure would rise and eventually cause the
will result. If a low ambient kit is installed, the cut-out chiller to fault causing total loss of cooling. By unloading
may be lowered as needed below 25°F (-3.9°C). If opera- the compressors at high discharge pressures, the chiller
tion is occasionally needed below 0°F (-17.8°C) the cut- is allowed to continue to run automatically at reduced
out should be set at 00.0°F (-17.8°C). This will allow capacity until the dirty cooling tower can be attended to.
operation at any temperature since the micro is only
able to recognize temperatures above 1°F (-17.2°C), re- When the unload point is reached, the micro will auto-
gardless of the display. matically totally unload the affected compressor. Typi-
cal maximum programmed limits would be 375 PSIG
NOTE: Operation below 0°F (-17.8°C) may cause other
(2.6 mPa) for air-cooled chillers with 395 or 405 PSIG
types of nuisance safety shutdowns, but occa-
(2.7 or 2.8 mPa) high pressure cut-outs and 255 PSIG
sional shutdowns can usually be tolerated since
(1.8 mPa) water-cooled chillers with 275 PSIG (1.9 mPa)
the need for sustained operation at these tem-
cut-outs.
peratures is unlikely and temperatures rarely sta-
bilize for any length of time below 0°F (-17.8°C).
Reloading will occur when the discharge pressure drops
The micro will accept a range of programmable values to 60 PSIG (413.7 kPa) below the programmed unload
between 00.0° - 50.0°F (-17.8 - 10°C) for this cut-out, if pressure and will increment one stage at a time as dic-
S1 Dip Switch #2 on the Micro Logic Board is in the tated by the loading timers.
CLOSED position. In the OPEN position, a fixed 25°F
(-3.9°C) cutout is recognized. To program the DISCHARGE PRESSURE UNLOAD, key
in the desired value and press the ENTER key. The new
To program the OUTSIDE AlR TMP LOW CUT-OUT, key value will be entered into memory and the display will
in the desired value and press the ENTER key. The new advance to the next user programmable limit.
value will be entered into memory and the display will
advance to the next user programmable limit. The micro will accept a range of programmable values
between 200 - 390 PSIG (1.4 - 2.7 mPa) for the unload
OUTSIDE AIR TMP HIGH CUT-OUT point.

O U T S I D E A I R T M P H I G H NOTE: It is required to first key in a “0” when program-


C U T O U T = 1 3 0 . 0 F ming this cut-out (Example: 0375 PSIG).

42 YORK INTERNATIONAL
FORM 150.60-NM5

AVERAGE CURRENT UNLOAD for programming this control will be discussed in the
SELECTION OF RETURN OR LEAVING CHILLED LIQ-
A V E R A G E C U R R E N T UID CONTROL Section (Page 48).
U N L O A D = 1 0 0 % F L A
ANTI RECYCLE TIME
The purpose of AVERAGE CURRENT UNLOAD is to pro-
vide adequate motor cooling and to prevent the motor from A N T I R E C Y C L E T I M E
faulting on high motor current. The motor current unload = 6 0 0 S E C S
feature only unloads a compressor by a single step. This
provides more cooling to the motor and at the same time The ANTI RECYCLE TIME selection allows the user to
still attempts to pull the water temperature down. select the compressor anti-recycle time to best suit his
needs. Motor heating is a result of inrush current when
Unloading will only occur when a compressor is running the motor is started. This heat must be dissipated be-
with at least one step of loading above a fully unloaded fore another start takes place or motor damage may re-
state. This feature will under no circumstances shut a sult. The anti-recycle timer assures the motor has suffi-
compressor off. cient time to cool before it is again restarted.

Whenever Motor Current Unloading is activated, the com- An adjustable timer allows for the motor cooling required,
pressor will stay in the unloaded state for 5 minutes. but gives the user the ability to extend the timer to cut
After the 5 minute time period, the micro will look at down on cycling. In some applications fast compressor
motor current once again. If motor is 25% below the pro- start response is necessary, in others it is not. These
grammed Motor Current Unload point, the compressor needs should be kept in mind and the timer should be
will be allowed to reload, if water temperature allows. adjusted for the longest period of time tolerable. Although
300 seconds is adequate motor cooling time, longer pe-
To program the Motor Current Unload, key in the desired riods will allow even more heat dissipation, reduce cy-
value and press the ENTER Key. The new value will be cling, and possibly increase motor life.
entered into memory and the display will advance to the
next user programmable limit. To program the ANTI RECYCLE TIME, key in the de-
sired value and press the ENTER key. The new value will
The micro will accept a range of programmable values be entered into memory and the display will advance to
between 80 - 105% for the unload point. A setting of the next user programmable limit.
100% is recommended for the unload point.
The micro will accept a range of programmable values
NOTE: When programming values from 80 - 99%, it is between 300 - 600 seconds for this operating control.
first required to key in a “0”. Example: 090%.
LEAVING WATER TEMP CUT-OUT
RATE CONTROL TEMP
L E A V I N G W A T E R T E M P
R A T E C O N T R O L T E M P C U T O U T = 3 6 . 0 F
= 0 8 . 0 F
The LEAVING WATER TEMP CUT-OUT protects the
The RATE CONTROL TEMP establishes a temperature chiller from an evaporator freeze-up should the chilled
range over which the micro may override normal system liquid temp drop below the freeze point. This situation
loading timers and react to actual rate of change of re- could occur under low flow conditions or if the micro panel
turn and leaving water temperature. This temperature SETPOINT values are improperly programmed. Anytime
range is slightly above the setpoint with its band width the leaving chilled liquid temperature (water or glycol)
being programmable. This control works in conjunction drops to the cut-out point, the chiller will shut down.
with the RATE SENSITIVITY which is also programmable. Restart will occur when temperature rises above the cut-
out if the anti-recycle timers are satisfied.
These controls allow the chiller to adapt to a full range of
applications. Depending on how the controls are set up For chilled water applications (comfort cooling, SW1
the chiller can be adapted to provide maximum response, OPEN), the cut-out is automatically set at 36.0°F (2.2°C).
demand limiting/energy saving, or reduced loader and This covers applications where leaving water tempera-
compressor cycling. Typically this value should be tures are not designed to go below 40.0°F (4.4°C). If
programmed for 00.1°F (0.05°C). When programming chilled liquid (glycol) temperatures are required below
values like 00.1°F (0.05°C), it is first required to key 40°F, the cut out should be programmed for 4°F (2.2°C)
in “00”. Example: 00.1°F (0.05°C). Additional details below the desired leaving chilled liquid temperature.

YORK INTERNATIONAL 43
To program the LEAVING WATER TEMP CUT-OUT the The RATE SENSITIVITY is active when the leaving chilled
BRINE & PROCESS MODE (SW1 CLOSED) must be liquid temperature is in the RATE CONTROL TEMP
selected, key in the desired value and press the ENTER RANGE. In this range, if water temperature is dropping
key. The new value will be entered into memory and the faster than the RATE SENSITIVITY setting, the micro will
display will advance to the next programmable limit. not load any more stages because water temperature is
dropping quickly. This provides demand limiting and re-
The micro will accept a range of programmable values duces loader/compressor cycling and overshoot. If quick
between 08.0 - 36.0°F (4.4 - 20°C) for this cut-out. response is needed, RATE SENSITIVITY can be pro-
grammed accordingly. When temperatures are in the RATE
SUCTION PRESSURE CUT-OUT CONTROL TEMP RANGE, loading will occur in intervals
according to both rate of water temperature change and
S U C T I O N P R E S S U R E error in water temperature versus setpoint. This will over-
C U T O U T = 4 4 P S I G ride the typical 30 - 150 seconds per stage based on error
in setpoint versus actual water temperatures. If water tem-
The SUCTION PRESSURE CUT-OUT protects the chiller perature is dropping faster than the RATE SENSITIVITY,
from an evaporator freeze-up should the system attempt no further loading will result and in some cases, the chiller
to run with a low refrigerant charge. Anytime the suction will unload to slow temperature drop.
pressure drops below the cut-out point, the system will
shut down. RATE SENSITIVITY is also active in the CONTROL
RANGE in RETURN OR LEAVING WATER CONTROL.
NOTE: There are some exceptions, where suction pres- Further loading will not occur if water temperature is drop-
sure is permitted to temporarily drop below the ping too fast regardless of whether temperature calls for
cut-out point. Details are outlined in the SYS- further loading.
TEM SAFETIES section.
Typically this value should be programmed for 5.0°F
For chilled water applications, the cut-out should be set (2.7°C). Additional details of programming this control
at 44 PSIG (303.3 kPa). If glycol or brine is utilized with will be discussed in the SELECTION OF RETURN OR
leaving water temperature designs below 40°F (4.4°C), LEAVING CHILLED LIQUID CONTROL Section (Page
the cut-out should be adjusted according to concentra- 48).
tion. A rule-of-thumb cut-out design is to drop the cut-
out 1 PSIG (6.9 kPa) below 44 PSIG (303.4 kPa) for NUMBER OF LOAD STEPS
every degree of leaving glycol below 40°F (4.4°C). In other
words, 30°F (-1.1°C) glycol requires a 34 PSIG (234.4 N UM B E R O F L O A D S T E P S
kPa) suction pressure cut-out. = 1 0 ( E N T E R 5 7 O R 1 0 )

To program the SUCTION PRESSURE CUT-OUT, key in The number of steps of loading must be programmed to
the desired value and press the ENTER key. The new assure proper loading sequence and temperature con-
value will be entered into memory and the display will trol. This is done at the factory, but should be checked
advance the next programmable limit. against the table below:
J110 J120 J130
The micro will accept a range of programmable values be-
STD. 5 STEPS 5 STEPS 5 STEPS
tween 20 - 70 PSIG (137.9 - 482.6 kPa) for this cut-out. In OPT. NA NA NA
the COMFORT COOLING MODE (SW1 OPEN), the cut-
out is adjustable from 44 - 70 PSIG (303.4 - 482.6 kPa). In Standard unloading requires programming for “5” steps.
the BRINE & PROCESS MODE (SWI CLOSED), the cut- Optional unloading is not available on YCAJ110 - 130
out is adjustable from 20 - 70 PSIG (137.9 - 482.6 kPa). chillers. Therefore, all YCAJ110 - 130 must be pro-
grammed for 5 steps. These chillers are limited to 5 steps
RATE SENSITIVITY due to the 4-cylinder compressors which are equipped
with only a single unloading solenoid.
R A T E S E N S I T I V I T Y
= 5 . 0 F / M I N . NOTE: Hot Gas Bypass (Loadminder) should not be
counted as a load step for programming pur-
The RATE SENSITIVITY establishes the rate of change poses.
of return or leaving water temperature where the micro
will over-ride the normal 30 - 150 seconds per stage load- Program the number of steps as required. To program 5
ing rate which is based on error between setpoint and steps, the “0” key (05) must be pressed first.
actual temperature.

44 YORK INTERNATIONAL
FORM 150.60-NM5

“CLOCK” KEYS
PROGRAMMING THE SYSTEM CLOCK AND DAILY START/STOP SCHEDULE

“CLOCK”
KEYS

02711TG

GENERAL To program the day, time and date, first press the AD-
VANCE DAY key until the appropriate day of the week is
The “CLOCK” is an internal system feature that allows displayed. The day will advance each time the key is
the microprocessor to continuously monitor the time of pressed.
the day. The micro will display actual time as well as the
day of the week and the date when programmed. This The cursor will already be below the first digit of the time.
feature allows the microprocessor to provide an internal Key in the new time, if required. Be sure to key in a “0”
automatic time clock feature for starting and stopping before the other digits for times before 10 o’clock., i.e.
the chiller for each individual day of the week. Also pro- 08:01.
vided is a “HOLIDAY” feature which allows special start/
stop programming for designated holidays. After the time is keyed in, the cursor will advance to the
AM/PM designation. To reprogram, press the AM/PM
The internal clock and schedule programming eliminates key. When the key is pressed, the display will change
the need for an external time clock. Automatic chiller to the opposite time period. If no change is required,
start and stop will occur according to the programmed begin keying in the required date (the cursor will auto-
schedule. matically skip to the first digit of the date [month] when
a “number key” is pressed and the number will be placed
If the user desires not to utilize the schedule feature, the in the first position).
SET SCHEDULE/HOLIDAY can be programmed to run
the chiller on demand as long as the “UNIT” and “SYS” NOTE: The AM/PM key can only be pressed once. If
switches are ON. an error is made, press the CANCEL key and
begin again.
Typical display messages will be shown which apply to
each key. The date may be keyed in after AM/PM. The sequence
of the message display is month, day and year. Two
PROGRAMMING THE DAY, TIME AND THE DATE digits must be entered for each of these items. There-
fore, a leading “0” may be required.
Set Time SET
TIME Once the desired information is keyed in, it may be stored
A message showing the day, time and date will be dis- in memory by pressing the ENTER key. After the EN-
played when the SET TIME key is pressed. TER key is pressed, the cursor will move under the “T” of
TODAY.
T O D A Y I S S U N 1 1 : 1 2 AM The micro will accept any valid time or date. If an out of
0 2 / 1 4 / 9 8 range value is entered, the micro will display the follow-

YORK INTERNATIONAL 45
ing message for 3 seconds before it reverts back to the ule. This can be done manually for each day or by press-
SET TIME display message to let the user know that ing CANCEL and ENTER when the MONDAY START/
another try at reprogramming is necessary. STOP schedule appears.
O U T O F R A N G E
NOTE: This will have no effect on the holiday schedule.
T R Y A G A I N !
Continue to program each day as needed. After MON
PROGRAMMING THE DAILY START/STOP AND through SUN has been entered, the HOLIDAY message
HOLIDAY SCHEDULE will be displayed.
SET SCHEDULE/ H O L S T A R T = 0 8 : 3 0 AM
Set Schedule/Holiday HOLIDAY
S T O P = 1 2 : 0 0 P M
Messages showing the start/stop schedule of each day
of the week as well as the holiday start/stop schedule The Holiday (HOL) START/STOP allows the user to des-
can be displayed after the SET SCHEDULE/HOLIDAY ignate a specific day(s) for special requirements. This is
key is pressed. The display can be scrolled through day- provided so that day(s) needing special start/stop re-
by-day simply by repetitively pressing the ENTER or quirements can be programmed without disturbing the
ADVANCE DAY key. A typical daily schedule display is normal working schedule.
shown below:
The start/stop times for the Holiday schedule are pro-
M O N S T A R T = 0 6 : 0 0 AM grammed just as for any other day.
S T O P = 0 5 : 3 0 P M
NOTE: Only one start/stop time can be programmed
To reprogram any of the daily schedules, key in the which will apply to each of the “HOLIDAY” days
new START time. To change the AM/PM associated selected.
with the START time, press the “AM/PM” key. This will
change the AM/PM message to the opposite time pe- After the ENTER key is pressed, a new message will be
riod. The “AM/PM” key can only be pressed once. If an displayed to designate which days of the week are to be
error is made, press CANCEL and begin reprogram- holidays.
ming again.
S M T* W T F S
After the START time and the associated AM/PM have H O L I D A Y N O T E D B Y *
been programmed, the cursor will move to the STOP
time. Key in the STOP TIME and press the “AM/PM” In the above sample display, an * designates Tuesday
key if AM/PM requires changing. as a holiday.

When the ENTER key is pressed, the new START/STOP When the display appears, the cursor will first stop be-
time is entered and the display will scroll to the next hind Sunday. To designate a day as a holiday, press the
day. If an unacceptable time is entered, the following “*” key. If a day is not to be a holiday, press the “0” key.
message will be displayed. Whenever the “*” or the “0” keys are pressed, the cursor
will advance to the next day. After all the holiday days
O U T O F R A N G E are programmed, press ENTER to store the new data
T R Y A G A I N ! into memory. The display will then advance to the begin-
ning of the Daily Schedule (MON).
For ease of programming, any values “ENTERED” for
MONDAY will automatically be put in for the other days The Holiday Schedule is only executed once by the mi-
of the week. Be aware of this anytime the MONDAY cro before it is erased from memory. This is done be-
SCHEDULE is changed, since it changes times previ- cause in most cases a special Holiday Schedule is only
ously programmed into other days. For scrolling through necessary once in a several month period. It also elimi-
the days to view times programmed use the ADVANCE nates the need for operator intervention to erase the
DAY KEY, not the ENTER KEY. This will assure that schedule after the holiday passes.
after viewing MONDAY, that the ENTER KEY is not
pressed changing times programmed for the rest of the If an error is made while programming, press CANCEL.
week. This will clear all programmed (*) “holiday” days. The
schedule can then be reprogrammed.
If the chiller is not cycled by the DAILY SCHEDULE, but
is required to run whenever the system switches are on, The “0” key will not cancel out a “*” and cannot be used
all 00.00s should be programmed into the daily sched- for correcting a programming error.

46 YORK INTERNATIONAL
FORM 150.60-NM5

MANUAL programmed Daily Schedule is calling for the chiller to


Manual Override OVERRIDE be OFF (Daily Schedule Shutdown).

When the MANUAL OVERRIDE key is pressed, the Daily M A N U A L


Schedule programmed into the chiller will be ignored and O V E R R I D E
the chiller will start-up when water temperature allows,
unit switch permits, and system switches permit. Once activated, MANUAL OVERRIDE is only active for
a period of 30 minutes. It is for servicing only and is
Normally this key is not used unless an emergency forces designed so that if left on accidentally, the microproces-
the chiller to require operation during a period where the sor will automatically return to the Daily Schedule.

YORK INTERNATIONAL 47
SELECTION OF RETURN OR LEAVING CHILLED LIQUID

GENERAL the micro panel must be interrogated to determine whether


it is programmed for RETURN or LEAVING WATER CON-
The user has the ability to select the type of chilled liq- TROL. This can be accomplished by pressing the OP-
uid temperature control by choosing either Return or TION key in the DISPLAY section of the keypad. This
Leaving Temperature Control. This provides the ability to allows the user to determine the present mode of control
fine tune the method of control for comfort cooling or without gaining access to the Microprocessor Board and
batch/process cooling loads. visually checking the sometimes difficult to determine
Dip Switch position. When the OPTION key is pressed,
In many cases, comfort cooling will be best controlled a message “THE FOLLOWING ARE PROGRAMMED”
by RETURN WATER CONTROL. This will assure a mini- will appear on the display for 3 seconds. The display will
mum of cycling compressors/loaders with stable leaving then scroll through the 8 dip switch selections, each
chilled liquid temperatures as long as water flow GPM is appearing for 3 seconds. The 4th display will tell the
held constant and the Control Range (CR) is correctly user whether leaving or return temperature is programmed
programmed. on Switch 4. The 4th display message will read either
“RETURN WATER CONTROL” or “LEAVING WATER
LEAVING WATER CONTROL is also suitable for com- CONTROL“ and will appear for 3 seconds.
fort cooling, but may produce slightly more cycling de-
pending upon the RATE SENSITIVITY programmed. If a change is required, position Switch #4 on dip switch
Optional stages of loading are recommended to reduce S1 on the Microprocessor Board (Fig. 13) as indicated:
cycling. In most cases, Leaving Water Control will be
RWT CONTROL: SW 4 OPEN
more precise unless compressor cycling is encountered.
(left side pushed down)
“Anticipation” and timers are built into the micro-
processor’s control algorithms to eliminate compressor LWT CONTROL: SW 4 CLOSED
and loader cycling enabling LEAVING WATER CONTROL (right side pushed down)
to be used in most applications. The control algorithm
utilizes “PID” control. NOTE: In LWT CONTROL, water temperature may un-
desirably rise when a compressor cycles off and
For batch and process applications, LEAVING WATER cannot restart because the anti-recycle timer is
CONTROL will allow for precise temperature control. In still timing out. The effects can be reduced by
these applications chilled liquid temperature control is programming the anti-recycle timer (Page 43)
more important than compressor/loader cycling. When for a minimum of 300 seconds if it isn’t already
LEAVING WATER CONTROL is utilized, it is recom- programmed for 300 seconds. If problems still
mended to have optional steps of loading on each com- arise, switch to RWT CONTROL.
pressor. This assures minimum tonnage per step which
reduces the possibility of compressor and loader cycling Once the dip switch #4 on the Microprocessor Board is
that is critical to precisely controlling temperature. properly positioned, the user will be able to view the ap-
propriate display when the CHILLED LIQUID TEMP/
RETURN WATER CONTROL may also be used on batch RANGE is pressed. This display will show one of the
and process application and should provide adequate following messages depending upon S1 positioning:
control. However, it will prove to be less responsive with
slightly more leaving chilled liquid temperature variation.
R E T U R N W A T E R
RETURN WATER CONTROL may become necessary
T E M P C O N T R O L
to use if too much compressor cycling is noted with cor-
responding water temperature fluctuation when in Leav-
ing Water Control.
L E A V I N G W A T E R
After determining the mode of control best suited for the T E M P C O N T R O L
application (RETURN OR LEAVING WATER CONTROL),

48 YORK INTERNATIONAL
FORM 150.60-NM5

“SETPOINTS” KEYS
PROGRAMMING CHILLED LIQUID SETPOINTS AND REMOTE RESET TEMP RANGE

“SETPOINTS”
KEYS

02711TG

GENERAL If this message is incorrect, see the “SELECTION OF


RETURN OR LEAVING CHILLED LIQUID CONTROL”
After Return or Leaving Chilled Liquid Control is selected section (Page 48) for instructions to reprogram the Mi-
according to the user’s application and Switch #4 of Dip croprocessor Dip Switch S1, Switch #4.
Switch S1 on the Micro Board is properly configured to
select Return or Leaving control, the chilled liquid set- The display will then scroll to a second message & hold:
points can then be programmed into the control panel.
Switch #4 of S1 must be properly programmed or an LW T = 4 4 . 0 F
incorrect display message will appear when the CHILLED C R = 4 4 . 0 T O 5 4 . 0 F
LIQUID TEMP/RANGE key is pressed. SEE “SELEC-
TION OF RETURN OR LEAVING CHILLED LIQUID This message will display the user’s “Design Leaving
CONTROL” Page 48 if needed. Water Temperature” (LWT) setpoint (44.0° F [6.7°C] in
the sample above). Even though return water tempera-
If remote temperature setpoint is being utilized, the RE- ture control is being utilized, the object is to provide con-
MOTE RESET TEMP RANGE must be programmed. stant design leaving water temperature. It is the “Design
The following information will cover programming both Leaving Water Temperature” setpoint (LWT) which must
return and leaving control. Refer to either the RETURN be programmed into the microprocessor.
or LEAVING WATER CONTROL section as required be-
low. Programming the REMOTE RESET TEMP RANGE Also included in this message is the “CONTROL RANGE”
is discussed later in this manual on Page 72. (CR). The “CONTROL RANGE” is the temperature range
which loading/unloading will take place. The lower limit
PROGRAMMING RETURN WATER CONTROL of the CONTROL RANGE is always equal to the setpoint
and automatically appears when the setpoint is keyed
Chilled Liquid CHILLED LIQUID in. The upper limit of the CR must be programmed.
Temp/Range TEMP / RANGE
In the above sample message, with a “CR = 44.0 - 54.0°F
When the CHILLED LIQUID TEMP/RANGE key is (6.7 - 12.2°C)”, the chiller will be completely off at a re-
pressed, the following message will be displayed for 3 turn water temperature of 44.0°F (6.7°C) and fully loaded
seconds indicating Dip Switch S1, Switch #4 on the Mi- at a return water temperature of 54.0°F (12.2°C). Partial
croprocessor Board is programmed properly: loading will occur in equal temperature intervals between
44° and 54°F (6.7 and 12.2°C). Unloading will occur as
R E T U R N W A T E R return temperature drops below 54°F (12.2°C) with the
T E M P C O N T R O L chiller cycling completely off at 44.0°F (6.7°C). These

YORK INTERNATIONAL 49
temperatures provide a Control Range differential of 54.0 The micro will accept a range of programmable LWT val-
- 44.0 = 10.0°F (12.2 - 6.7 = 5.6°C). ues from 10.0 - 70.0°F (-12.2 - 21.1°C) (See “SWITCH
1”, Page 35). It will also accept a value for the upper limit
Once the upper limit of the CR is programmed, the “CON- of the CR of 4 - 20°F (2.2 - 11.1°C) above the LWT
TROL RANGE” (CR) differential must always equal the Setpoint.
actual water temperature drop (∆T) across the evapora-
tor with the chiller completely loaded. Keep this in mind If brine or glycol is used in the system, chilled liquid
when programming the high end of the CR. In many cases, temperatures below 40°F (4.4°C) may be desired. To pro-
due to improper flows, actual temperature drop occurs gram setpoints below 40°F (4.4°C), Dip Switch S1, Switch
across the evaporator (∆T) will not equal design. For #1 on the Microprocessor Board must be properly pro-
proper operation, adjust flow as needed or program the grammed. (See Page 34, Fig. 13). If the switch is incor-
“CONTROL RANGE” as needed. However accomplished, rect, when setpoints below 40°F (4.4°C) are entered as
the “CONTROL RANGE” differential must equal the well as when unacceptable values are entered, the fol-
evaporator temperature drop when fully loaded or leaving lowing message will be displayed.
water temperatures well above or well below the desired
setpoint will result. O U T O F R A N G E
T R Y A G A I N !
To program the Chilled Liquid Setpoints, press the
CHILLED LIQUID TEMP/RANGE key. The display will Loading and unloading occurs in defined increments
first exhibit a message that “RETURN WATER TEMP throughout the Control Range according to the difference
CONTROL” is selected and 3 seconds later automati- between return water temperature and the LWT setpoint.
cally scroll to the next display of LWT and CR. The cur- Loading is limited by a 60 second timer, while unloading
sor will stop at the first digit of LWT. Key in the “Design is not.
Leaving Water Temperature” (LWT) that is required in
the system. See the following: Loading may be inhibited or unloading may occur if the
micro senses that the Rate Sensitivity is exceeded in
Design Leaving the Control Range or Rate Control Range to prevent over-
Water Temperature shoot. This action will override incremental unloading.
Further details regarding loading/unloading and Rate
LW T = 4 4 . 0 F
Control will follow.
C R = 4 4 . 0 T O 5 4 . 0 F
PROGRAMMING
After the Design Leaving Water Temperature (LWT) is RETURN WATER RATE CONTROL
keyed in, the lower limit of the CR (Control Range) in the
display message will automatically change to a value Programmable RATE CONTROL is designed to limit com-
identical to the “LWT”. See below: pressor/loader cycling thus saving energy and reducing
wear on mechanical components. It also reduces the
possibility of “overshoot”. RATE CONTROL will allow the
micro to react to fast changes in water temperature be-
LW T = 4 4 . 0 F yond normal responses dictated by the difference be-
C R = 4 4 . 0 T O 5 4 . 0 F tween actual return water temperature and setpoint.

The lower limit of the CR RATE CONTROL requires programming the temperature
will always automatically range (RATE CONTROL TEMP) above the CONTROL
equal LWT. RANGE (CR) where rate control is desired. Additionally,
the actual rate of change (RATE SENSITIVITY) of water
The cursor will advance to the final entry which is the temperature which the micro uses as a control refer-
upper limit of the CR (Control Range). This value must ence must also be programmed.
be programmed to equal the design LWT plus the CR
differential (∆T across the evaporator fully loaded). In the Refer to Fig. 14 as you read the following text. A typical
above examples it would be 44.0 + 10.0 = 54.0°F (6.7 + leaving water temperature setpoint of 45°F (7.2°C) is used
5.6 = 12.2°C): with a 45° - 55°F (7.2 - 12.8°C) CONTROL RANGE. A
RATE CONTROL TEMP OF 65°F (18.3°C), which is typi-
Key in the upper limit of the CR and press ENTER. Oth- cal (10°F [5.5°C] above the high end the Control Range),
erwise the new values will not be entered into memory. is shown.
After pressing the ENTER key, the display will continue
to show the LWT and Control Range message until an-
other key is pressed.

50 YORK INTERNATIONAL
FORM 150.60-NM5

ABOVE THE RATE CONTROL UPPER LIMIT OF RATE This may be required for small water loops. However, if
TEMP RANGE CONTROL TEMP problems arise where the chiller does not load and pull
65°
h RANGE
(18.3°) temperature down, select 0.1°F (0.05°C).
RATE CONTROL TEMP RANGE
(RATE CONTROL TEMP = 10°F [5.5°C])
i UPPER LIMIT OF To program the RATE CONTROL TEMP, first press the
55° CONTROL PROGRAM key. Repetitively press the ENTER key until
(12.8°) h
CONTROL RANGE RANGE (CR) the display below appears.
(CR = 45 - 55°F [7.2 - 12.8°C])
i R A T E C O N T R O L T E M P
45° SETPOINT
BELOW THE CONTROL RANGE = 1 0 . 0 F
(7.2°)

FIG. 14 – RETURN WATER TEMPERATURE Key in the desired value and press the ENTER key. The
CONTROL °F (°C) new value will be entered into memory and the display
will advance to the next user programmable limit.
The RATE CONTROL TEMP establishes a temperature
range (0.1 - 20°F [.05 - 11.1°C]) above the “Upper Limit The micro will accept a range of programmable values
of CONTROL RANGE” where the micro will limit loading between 0.1 - 20°F (0.05 - 11.1°C).
or cause unloading if the rate of change of water tem-
NOTE: When programming values between 0.1 - 9.9°F
perature reduction exceeds the programmed RATE SEN-
(0.05 - 11.1°C), it is required to first key in a “0 “
SITIVITY. In Fig. 14 RATE CONTROL TEMP of 10°F
or “00”. Example: 05.9°F.
(5.5°C) is used.
The next item which will require programming is the RATE
In the CONTROL RANGE and RATE CONTROL RANGE,
SENSITIVITY. The RATE SENSITIVITY is a means of
loading/unloading will normally occur according to devia-
“overriding” the loading/unloading timers when water tem-
tion from setpoint. “Rate Control” will function to prevent
peratures are in the RATE CONTROL RANGE or the
loading if the water temperature change (leaving or re-
CONTROL RANGE. This allows the micro to react to
turn) exceeds the RATE SENSITIVITY, even though de-
abrupt downward changes in leaving or return water tem-
viation from setpoint requires loading. This will reduce
peratures. The ability to respond to “rate of change” varia-
the chance of overshoot.
tions in water temperatures gives the micro “anticipa-
tion” capabilities to reduce the possibility of “overshoot”
Above THE RATE CONTROL TEMP RANGE the micro
in leaving water temperature.
will attempt to load the chiller every 60 seconds per stage.
This allows the chiller to gain control of the water tem-
In demand limiting applications, to avoid cycling or to
perature as quickly as possible.
avoid overshoot, RATE SENSITIVITY should be low. This
allows the micro to go into rate control to prevent loading
Since RWT Control utilizes the buffering of the water
whenever water temperatures drop faster than the pro-
loop and a wide control (loading/unloading) range, com-
grammed RATE SENSITIVITY. Rate Control can go into
pressor/loader cycling is reduced, wear and tear on me-
effect whenever water temperatures are in RATE CON-
chanical parts is reduced, and pulldown demand is au-
TROL RANGE or the CONTROL RANGE. For these ap-
tomatically limited. This makes the selection of RATE
plications, a 3 - 5°F/min (1.7 - 2.8°C/min) RATE SENSI-
CONTROL TEMP and RATE SENSITIVITY values less
TIVITY is recommended. This may be required for small
critical unless short water loops are encountered.
water loops. However, if problems arise where the chiller
does not load and pull temperature down, select 5°F/
Before programming the RATE CONTROL TEMP, the user
min (2.8°C/min).
should first determine if typically the normal fastest al-
lowable pulldowns are required or whether pulldown de- NOTE: Too small of a RATE SENSITIVITY value se-
mand limiting is desired. Programmable values from 00.1 lection may prevent loading due to varying flows
- 20°F (0.05 - 11.1°C) are possible. or if the water system allows a slug of cold water
to enter which falsely fools the micro into think-
For normal pulldowns and quick response, a RATE ing the RATE SENSITIVITY has been exceeded,
CONTROL TEMP of 0.1°F (0.05°C) is appropriate un- preventing loading and allowing leaving water
less excessive overshoot is noted. temperature to rise above the desired tempera-
ture. In some cases, unloading or compressor
For demand limiting, energy efficiency and minimum shutdown my result.
cycling, RATE CONTROL TEMPS of 10° - 20°F (5.6 -
11.1°C) are advisable with temperatures around 20°F For normal comfort cooling, batch, or process applica-
(11.1°C) most appropriate. This will cause the control to tions, select a high RATE SENSITIVITY of 5°F/min (2.8°C/
react to water temperature rate of change well before the min). Before RATE CONTROL can go into effect, the
water temperature drops into the CONTROL RANGE. water temperature would have to change at a very high
YORK INTERNATIONAL 51
rate to exceed the RATE SENSITIVITY value pro- will attempt to control to. The “Target” temperature is not
grammed. This will assure normal loading will occur. 5°F/ programmable, but it is always the midpoint of the Con-
min (2.8°C/min) also works well in comfort cooling appli- trol Range (CR). Example: A control range of 44° - 46°F
cations. If unsure of a RATE SENSITIVITY selection, (6.7 - 7.8°C) will have a “Target” Temp of 45°F (7.2°C),
use 5°F/min (2.8°C/min). which should equal the desired system leaving water
temperature. As mentioned before, the micro will be sat-
To program the RATE SENSITIVITY, first press the PRO- isfied with a leaving temperature between 44° - 45°F (6.7
GRAM key. Repetitively press the ENTER key until the - 7.2°C) unless the rate control is exceeded. The
display below appears. microprocessor’s rate control is designed to be less re-
sponsive in the upper half of the Control Range (i.e. 45 -
R A T E S E N S I T I V I T Y
46°F [7.2 - 7.8°C]) than in the lower half (i.e. 44° - 45°F
= 5 . 0 F / M I N . [6.7 - 7.2°C]). This is to prevent overshoot.

Key in the desired value and press the ENTER key. The To program the Low-Limit Water Temperature (LWT) and
new value will be entered into memory and the display the Control Range (CR), press the CHILLED LIQUID
will advance to the next user programmable limit. TEMP/RANGE key. This display will first exhibit a mes-
sage that “LEAVING WATER TEMP CONTROL” is se-
The micro will accept a range of programmable values lected and 3 seconds later automatically scroll to the
between 0.5° - 5.0°F/min (0.3 - 2.8°C/min). next display of LWT and CR. The cursor will stop at the
first digit of LWT. Key in the Low-Limit Water Tempera-
PROGRAMMING LEAVING WATER CONTROL ture (LWT) that is acceptable in the system. See below:
Chilled Liquid Temp/Range Low-Limit Water Temperature (LWT)

When the CHILLED LIQUID TEMP/RANGE key is


pressed, the following message will be displayed for 3 LW T = 4 4 . 0 F
seconds indicating Dip Switch S1, Switch #4 on the Mi- C R = 4 4 . 0 T O 4 6 . 0 F
croprocessor Board is programmed properly:

L E A V I N G W A T E R The micro will accept a range of programmable values


T E M P C O N T R O L
from 10.0 - 70.0°F (-12.2 - 21.1°C) (See “SWITCH 1”,
Page 35). If brine or glycol is used in the system, chilled
liquid temperatures below 40°F (4.4°C) may be desired.
If this message is incorrect, see the “SELECTION OF
RETURN OR LEAVING CHILLED LIQUID CONTROL” To program setpoints below 40°F (4.4°C), Dip Switch 1,
Section (Page 50) for instructions to reprogram the Mi- Switch #1 on the Microprocessor Board must be prop-
croprocessor Dip Switch S1, Switch #4. erly programmed. (See Page 35). If the switch is incor-
rect, when setpoints below 40°F (4.4°C) are entered as
The display will then scroll to a second message and hold:
well as when unacceptable values are entered, the fol-
LW T = 4 4 . 0 F lowing message will be displayed:
C R = 4 4 . 0 T O 4 6 . 0 F O U T O F R A N G E
T R Y A G A I N !
This message will display the Low-Limit Water Tempera-
ture (LWT) and the Control Range (CR). In the sample
After the Low-Limit Water Temperature (LWT) is keyed
above, the LWT is 44.0°F (6.7°C) and the CR is 44° -
in, the lower limit of the CR (Control Range) in the dis-
46°F (6.7 - 7.8°C).
play message will automatically change to a value iden-
The Control Range (CR) is the variation in leaving water tical to the “LWT”. See below:
temperature which is acceptable in the system applica-
tion. As long as leaving water temperature stays between
the low limit and midpoint of the Control Range (CR), the
Microprocessor will consider the temperature acceptable LW T = 4 4 . 0 F
and will not initiate any loading/unloading reaction un- C R = 4 4 . 0 T O 4 6 . 0 F
less “Rate Control” requires. The Low-Limit Water Tem-
perature (LWT) is the minimum acceptable leaving water The lower limit of the CR
temperature in the Control Range (CR), not the actual will always automatically
user desired leaving water temperature setpoint. equal LWT.

The desired leaving water temperature is known as the


“Target” temperature which is the temperature the micro
52 YORK INTERNATIONAL
FORM 150.60-NM5

The cursor will advance to the final entry which is the wear on mechanical components. It also reduces the
upper limit of the CR (Control Range). This value is pro- possibility of “overshoot”. RATE CONTROL will allow the
grammed for the highest leaving water temperature which micro to react to fast changes in water temperature be-
is acceptable in the system application. Typically, 2°F yond normal responses dictated by leaving water tem-
(1.1°C) above the Low-Limit Water Temperature is ap- perature and setpoint.
propriate. The micro will accept a value 1 - 5°F (0.5 -
2.8°C) above the LWT for this value. 2°F (1.1°C) above RATE CONTROL requires programming the temperature
the LWT is the default value. range (RATE CONTROL TEMP) above the CONTROL
RANGE (CR) where rate control is desired. Additionally,
Key in upper limit of the CR and press the ENTER key. the actual rate of change (RATE SENSITIVITY) of water
Otherwise the new values will not be entered into memory. temperature which the micro uses as a control refer-
After pressing the ENTER key, the display will continue ence must also be programmed.
to show the LWT and Control Range message until an-
other key is pressed. Refer to Fig.15 as you read the following text. A typical
low limit water temperature of 44°F (6.7°C) is used with
CAUTION: Too small of a CR selection will cause com- a 44 - 46°F (6.7 - 7.8°C) CONTROL RANGE (CR). A
pressor/loader cycling. If compressor cycling RATE CONTROL TEMP of 10°F (5.5°C), which is typical
occurs, leaving water temperature may vary (10°F [5.5°C] above upper limit of the Control Range), is
considerably as a result of a compressor shown.
that cannot restart due to the anti-recycle
timer. To eliminate this, increase the ∆T ABOVE THE RATE CONTROL
(temperature differential) of the CR and/or TEMP RANGE UPPER LIMIT OF RATE
56°
program the anti-recycle timer for a mini- (13.3°) h CONTROL TEMP RANGE
mum of 300 seconds if it isn’t already pro- RATE CONTROL TEMP RANGE
grammed for 300 seconds. (RATE CONTROL TEMP = 10°F [5.5°C])
i
46° UPPER LIMIT OF
NOTE: Whenever reprogramming the LWT and CR, (7.8°) h CONTROL RANGE (CR)
keep in mind that the desired leaving water temp. CONTROL RANGE
45° TARGET
or “target” should be midpoint of the CR. (7.2°)
(CR = 44 - 46°F [6.7 - 7.8°C])
i LOW LIMIT
44° OF CONTROL
Normal pulldown loading is limited by a 150 sec. loading (6.7°) BELOW THE
RANGE (LWT)
timer between stages, with loading occurring whenever CONTROL RANGE
leaving water temperature is in the upper half of the CON-
TROL RANGE or above. FIG. 15 – LEAVING WATER TEMPERATURE
CONTROL °F (°C)
Below the Control Range, unloading will occur at 20 sec.
intervals until temperatures fall back into the Control Zone. The RATE CONTROL TEMP establishes a temperature
Unloading is controlled by a 20 sec. timer below the range (0.1 - 20°F [0.05 - 11.1°C]) above the “Upper Limit
Control Zone. of CONTROL RANGE” where the micro will limit loading
if the rate of change of water temperature exceeds the
The Rate Control software may prevent loading or cause RATE SENSITIVITY. In the above example a RATE CON-
unloading in the Rate Control Range or Control Range if TROL TEMP of 10°F (5.5°C) is used. In the Rate Control
temperature drops faster than 2X the programmed Rate Range, the micro will prevent loading or may cause un-
Sensitivity. This is to prevent overshoot. loading if the temperature drop exceeds 2X the Rate
Sensitivity regardless of whether the 150 sec. loading
In the lower half of the Control Range between the Low timer and the deviation from setpoint is calling for load-
Limit and the Target, Rate Control will cause unloading if ing.
temperature falls faster than 1X the programmed Rate
Sensitivity. As before, this is to prevent overshoot. At temperatures below the CONTROL RANGE, unload-
ing will occur to bring temperatures back to within the
Further details loading/unloading and Rate Control will CONTROL RANGE. The unloading timer will cause un-
follow: loading at 20 sec. intervals until temperatures fall back
into the CONTROL RANGE.

PROGRAMMING LEAVING WATER RATE CONTROL In the lower half of the Control Range between the Low
Limit Water Setpoint (LWT) and the “Target” Tempera-
Programmable RATE CONTROL is designed to limit com- ture (Desired Leaving Water Temperature), Rate Control
pressor/loader cycling thus saving energy and reducing software will cause unloading if temperature drops faster

YORK INTERNATIONAL 53
than 1X the Rate Sensitivity. Otherwise, no other loading NOTE: When programming values between 0.1 - 9.9°F,
or unloading will result in this temperature range. it is required to first key in a “0” or “00”. Ex-
ample: 05.9°F.
In the upper half of the Control Range between the TAR-
GET and the High Limit of the Control Range and in the The next item which will require programming is the RATE
Rate Control Range, loading will take place in 150 sec. SENSITIVITY.
intervals until temperature drops below the TARGET tem-
perature. The Rate Control software may prevent loading The RATE SENSITIVITY is a means of “overriding” the
or initiate unloading if temperature drops faster than 2X loading/unloading timers when water temperatures are
the programmed Rate Sensitivity. in the RATE CONTROL RANGE or the CONTROL
RANGE. This allows the micro to react to abrupt down-
Above the RATE CONTROL TEMP RANGE, the micro ward changes in leaving or return water temperatures.
will attempt to load the chiller as fast as it can (150 The ability to respond to “rate of change” variations in
seconds per stage). This allows the chiller to gain con- water temperatures gives the micro “anticipation” capa-
trol of the water temperature as quickly as possible while bilities to reduce the possibility of “overshoot” in leaving
still avoiding overshoot and limiting pulldown demand as water temperature.
temperature drops and rate control is implemented.
In demand limiting applications, to avoid cycling, or to
Since LWT Control does not have the water loop for buff- avoid overshoot, RATE SENSITIVITY should be low. This
ering after a load/unload response and utilizes a narrow allows the micro to go into rate control to prevent loading
control (loading/unloading) range, compressor/loader or cause unloading whenever water temperatures drop
cycling can be a problem. This makes the selection of faster than the programmed RATE SENSITIVITY. Rate
RATE CONTROL TEMP and RATE SENSITIVITY values Control can go into effect whenever water temperatures
very critical. are in RATE CONTROL RANGE or the CONTROL
RANGE. For these applications, a 3 - 5.0°F/min (1.7 -
Before programming the RATE CONTROL TEMP, the user 2.8°C/min). RATE SENSITIVITY is recommended. This
should first determine if typically the fastest allowable may be needed for small water loops. However, if prob-
pulldowns are required or whether pulldown demand lim- lems arise where the chiller does not load or abruptly
iting is desired. Programmable values from 0.1 - 20° F turns a compressor off and fails to pull temperature down,
(0.05 - 11.1°C) are possible. select 5.0°F/min (2.8°C/min).

For normal pulldowns and quick response, a RATE NOTE: Too small of a RATE SENSITIVITY Selection
CONTROL TEMP of 0.1°F (0.05°C) is appropriate un- may prevent loading due to varying flows or if the
less excessive overshoot is noted. water system allows a slug of cold water to enter
which falsely fools the micro into thinking the
For demand limiting, energy efficiency, elimination of RATE SENSITIVITY has been exceeded, pre-
overshoot, and minimum cycling, RATE CONTROL venting loading and allowing leaving water tem-
TEMPS of 10 - 20°F (5.6 - 11.1°C) are advisable. This perature to rise above the desired temperature.
will cause the controls to react to water temperature rate
of change well before the water temperature drops into For normal comfort cooling, batch, or process applica-
the CONTROL RANGE. This may be required for small tions, select a high RATE SENSITIVITY of 5.0°F/min
water loops. However, if problems arise where the chiller (2.8°C/min). Before Rate Control can go into effect, the
does not load and pull temperature down, select 0.1°F water temperature would have to change at a very high
(0.05°C). rate to exceed the RATE SENSITIVITY value pro-
grammed. This will assure normal loading will occur at
To program the RATE CONTROL TEMP, first press the the fastest possible speed. In most applications, 5.0°F/
PROGRAM key. Repetitively press the ENTER key until min (2.8°C/min). is suggested. If unsure of a RATE
the display below appears. SENSITIVITY selection, use 5.0°F/min (2.8°C/min).

R A T E C O N T R O L T E M P To program the RATE SENSITIVITY, first press the PRO-


= 1 0 . 0 F GRAM key. Repetitively press the ENTER key until the
display below appears.
Key in the desired value and press the ENTER key. The R A T E S E N S I T I V I T Y
new value will be entered into memory and the display
= 5 . 0 F / M I N .
will advance to the next user programmable limit.

The micro will accept a range of programmable values Key in the desired value and press the ENTER key. The
between 0.1 - 20°F (0.05 - 11.1°C). new value will be entered into memory and the display
will advance to the next user programmable limit.
54 YORK INTERNATIONAL
FORM 150.60-NM5

The micro will accept a range of programmable values The micro will unload a stage 2°F (1.1°C) below the
between 0.5 - 5.0°F/min (0.3 - 2.8°C). temperature at which it was loaded assuming unload-
ing timers and rate control software allows.
LOADING AND UNLOADING
RETURN WATER TEMPERATURE CONTROL Listed in Fig. 16 are the loading and unloading sequences
for 5 steps of control. A typical setpoint of 45°F (7.2°C)
In return water temperature control, loading and unload- with a cooling range of 10°F (5.5°C) is shown for ex-
ing will take place according to the difference between ample purposes. The chiller will be completely loaded at
the leaving water temperature setpoint and the actual a return water temperature of 55°F (12.8°C) and will be
return water temperature. By programming the CONTROL completely off at a temperature of 45°F (7.2°C), thus
RANGE equal to the actual temperature drop across the maintaining a leaving water temperature of 45°F (7.2°C).
evaporator fully loaded, the microprocessor will be able As mentioned before, loading/unloading timers as well
to maintain the desired leaving water temperature by as rate control software must be satisfied before load-
controlling off of the return water temperature (RWT). ing/unloading will occur. This reduces the possibility of
Simply, the micro will know that the chiller should be cycling.
fully loaded when the RWT is equal to the SETPOINT +
CONTROL RANGE. As the RWT drops, the micro will 5 STEP (STANDARD)
unload the chiller which reduces the capacity (tempera-
ture drop across the evaporator). This maintains the leav-
ing water temperature at the desired setpoint.

Normal loading will occur at intervals of 60 seconds,


according to temperatures determined by the formula
below. Loading may be prevented due to the rate control
circuitry. Anytime the return water temperature falls within
the CONTROL RANGE or the RATE CONTROL RANGE,
RATE CONTROL is in effect and loading may be pre-
vented, if water temperature changes faster than the rate
sensitivity. Loading will never occur in intervals faster
than 60 sec. under any circumstances. This prevents
cycling of the compressors and loaders.

Unloading occurs on temperature drop at temperatures


determined by the formula below. Internal timers have no
effect on unloading.
NOTE:

The micro is capable of providing 5, 7, or 10 steps of The micro controls loading and unloading
loading/unloading. The chiller MUST be programmed for on a 10 STEP scale regardless of the num- LD02664

ber of stages present. Therefore, loading


the number of steps which were ordered. Otherwise, and unloading responses on 5 Step (stan-
improper operation and water temperature control prob- dard) chillers may appear delayed (time
lems will result. YCAJ110 - 130 chillers MUST always between stages increased) when miss-
be programmed for 5 steps since optional unloading is ing steps are activated or deactivated by
the micro.
not available.

The temperature between stages of loading/unloading is FIG. 16 – 5 STEP LOADING/UNLOADING (RETURN


equal to the CONTROL RANGE divided by the number WATER CONTROL) °F (°C)
of stages. For example:
CONTROL RANGE= 10°F (5.5°C) LOADING AND UNLOADING
Number of Stages = 5 LEAVING WATER TEMPERATURE CONTROL

10°F ) 5 = 2°F (5.5°C ) 5 = 1.1°C) between stages In leaving water temperature control, loading and unload-
ing will take place as needed to keep water temperature
In this example, the micro will add a stage of loading in the CONTROL RANGE between the TARGET and LOW
each time the return water temperature rises 2°F LIMIT WATER TEMPERATURE. As mentioned earlier in
(1.1°C) assuming loading timers and rate control soft- this manual, the CONTROL RANGE is the temperature
ware allows. range of leaving water temperature that is acceptable to
the user and has been previously programmed into

YORK INTERNATIONAL 55
memory using the CHILLED LIQUID TEMP RANGE KEY. If leaving water temperature rises into the upper half of
Usually this is a window of water temperatures of about CONTROL RANGE or above, the microprocessor will load
2 - 3°F (1.1 - 1.7°C). The micro will cause loading and the chiIler as needed in 150 sec. intervals until tempera-
unloading actions to occur as needed to keep leaving tures fall into the lower half of the CONTROL RANGE. If
water temperatures in the lower half of this range. Refer the rate of drop in water temperature exceeds 2X the
to Fig. 17 to aid in understanding the loading and un- programmed Rate Sensitivity, no further loading or un-
loading scheme performed by the microprocessor. loading will result since the micro sees the temperature
dropping at an excessive rate anticipating temperature
ABOVE THE RATE CONTROL RANGE will soon fall into the CONTROL RANGE.
RATE CONTROL TEMP RANGE UPPER LIMIT OF
CONTROL RANGE The micro is capable of providing 5, 7, or 10 steps of
loading/unloading. The chiller MUST be programmed for
CONTROL RANGE (CR) TARGET
the number of steps which were ordered. Otherwise,
LOW LIMIT WATER improper operation and water temperature control prob-
BELOW THE CONTROL RANGE TEMPERATURE
lems will result. YCAJ110 - 130 chillers MUST always
be programmed for 5 steps since optional unloading is
FIG. 17 – LEAVING WATER TEMPERATURE CONTROL not available.

NOTE. The micro controls loading and unloading re-


Within the lower half of the CONTROL RANGE, the mi- sponses on a 10 step scale regardless of the
croprocessor may call for further unloading if the Rate number of stages present. Therefore, loading
Sensitivity is exceeded. If temperature drop exceeds 1X and unloading responses on 5 step chillers may
the Rate Sensitivity, the micro will unload the chiller to appear delayed (time between steps increased)
prevent overshoot. when missing steps are activated or de-activated
by the micro, 5 STEP CONTROL IS STAN-
Normal unloading will occur if leaving water temperature DARD.
should fall into the temperature range “BELOW THE
CONTROL RANGE” which is below the programmed Low Fig. 18 shows the loading and unloading sequences for
Limit WATER TEMPERATURE. The microprocessor will 5 steps of control.
unload the chiller in 20 sec. intervals until water tem-
perature rises back into the CONTROL RANGE.

5 STEP (STANDARD)
TEMPERATURE
RISE LOAD UNLOAD
5 LEAD COMP + 1 STEP, LAG COMP + 1 STEP – – – – – – – – – – – – – – – – – – – – –
4 LEAD COMP + 1 STEP, LAG COMP UNLOADED – – – LEAD COMP + 1 STEP, LAG COMP UNLOADED
3 LEAD COMP UNLOADED, LAG COMP UNLOADED – – – LEAD COMP UNLOADED, LAG COMP UNLOADED
2 LEAD COMP + 1 STEP, LAG COMP OFF – – – LEAD COMP + 1 STEP, LAG COMP OFF
1 LEAD COMP UNLOADED, LAG COMP OFF – – – LEAD COMP UNLOADED, LAG COMP OFF
LEAD COMP OFF, LAG COMP OFF – – – LEAD COMP OFF, LAG COMP OFF
TEMPERATURE
FALL

FIG. 18 – LEAVING WATER CONTROL LOADING/UNLOADING

56 YORK INTERNATIONAL
FORM 150.60-NM5

“SYSTEM SAFETIES”
There are three types of System Safeties: The Manual Monitoring motor current assures that motor life is not
Reset type, the Automatic Reset type, and Anticipation compromised due to low motor current. Low motor cur-
Safety Controls. These safeties protect the chiller from rent may be caused by loss or low voltage on the high
damage anytime a safety threshold is exceeded by ei- voltage supply which could quickly result in motor fail-
ther shutting the system(s) down or by altering system ure. Low motor current may also result from low refriger-
loading. Continuous monitoring by the microprocessor ant charge. This assures that the compressor does not
assures that instantaneous reactions result. A status run with a low suction pressure condition while the low
display message will indicate when a system(s) or the pressure bypass is de-activated.
entire chiller is shut down due to a fault or when Antici-
pation safeties are operating. The micro begins monitoring for low motor current after 4
seconds after a compressor starts. If after 4 seconds
An explanation of these safeties will follow. the motor current drops below 15% FLA, the micro will
shut the compressor down.
MANUAL RESET SAFETIES (3 Faults and Lockout)
NOTE: Do not confuse FLA and RLA. FLA (full-load
amps) is approximately 1.2 x RLA. RLA (run-
A Manual Reset Safety will shut the affected system
ning load amps) specified on the motor name-
down whenever the safety threshold is exceeded. Auto-
plate is typical current demand under rated op-
matic restart will occur after the first 2 shutdowns when
erating conditions in a fully loaded system. There-
the anti-recycle timer times out, if temperature demand
fore, do not expect to see 100% FLA when the
exists. After any combination of 3 Manual Reset Safe-
system is fully loaded. In this condition, cur-
ties in a 90-minute time period, the affected system will
rents may run approximately 65 - 85% FLA.
shut down and lock out on a FAULT.
Three internal temperature sensors are built into the motor
After a system has shut down 3 times and locked out, a
stator. These sensors are wired into the motor protector
fault display indicating the last system fault will appear
module located inside the Motor terminal box. As the
on the STATUS display message. This is accessible by
motor windings heat and cool, the resistance of the mo-
pressing the STATUS key.
tor temperature sensors will change. If the windings over-
heat, the change in resistance in the sensors will be
To reset a locked out system, turn the affected system
sensed by the Motor protector module. The module will
switch on the Microprocessor Board (Page 69) to the
open its MP contacts breaking the 115VAC fed to the
OFF position.
motor contactor. When the motor contactor de-energizes,
motor current falls to zero. The low motor current is sensed
CAUTION: Before returning a locked out system to
by the microprocessor and the system is shut down.
service, a thorough investigation of the cause
of the fault should be made. Failure to re-
Once tripped, the Motor Protector Module will not reset
pair the cause of the fault while manually
unless power (115VAC) is removed for at least 5 sec-
allowing repetitive restarts may cause fur-
onds from the control panel. Therefore, after 2 more start
ther expensive damage to the system.
attempts, the micro will lock out on a low motor current
safety and requires 115VAC control power to be removed
Each of the Manual Reset Safeties will be discussed in
and reapplied along with manual reset via the system
detail below.
switch.
MOTOR CURRENT
A mechanical high pressure cut-out is located on each
(Low Motor Current, Motor Protector, and
compressor discharge or in the compressor head. This
Mechanical High Pressure Cutout Safety)
is the primary high pressure safety in the system. Any
microprocessor controls are secondary.
This safety combines several safeties into one. The mi-
cro monitors for low motor current as sensed by the C.T.,
Anytime discharge pressure exceeds 405 PSIG (2.8
the mechanical motor protector, and the high pressure
mPa), the contacts in the high pressure cut-out will open
cutout.
which removes 115VAC from the motor protector mod-
ule. When 115VAC control power is lost to the module,
An example of the fault display is shown below:
the module’s MP contacts open breaking the 115VAC
S Y S # 1 M O T O R C U R R E N T fed to the motor contactor. The motor contactor de-ener-
S Y S # 2 M O T O R C U R R E N T gizes and motor current falls to zero. The low motor cur-
rent is sensed by the microprocessor and the system is
shut down. For more information see the MOTOR CUR-
RENT SAFETY section (Page 59).
YORK INTERNATIONAL 57
Auto-restart will be permitted after a shutdown when dis- The Discharge Pressure Safety Cut-out is programmable
charge pressure drops to below 330 PSIG (2.3 mPa) by the user (Page 41). An example of a discharge pres-
which allows the mechanical high pressure cut-out to sure fault display message is shown below.
reset and its contacts to close. This re-applies 115VAC
to the motor protector closing the MP contact. A fault S Y S # 1 H I G H D S C H
lock-out will result if safety thresholds are exceeded three S Y S # 2 H I G H D S C H
times in a 90-minute period.
NOTE: This safety is only operable if optional discharge
Suction Pressure Safety pressure transducers are installed.

The Suction Pressure Safety assures that the system is


not run under low refrigerant conditions or due to a prob- Oil Pressure Safety
lem which will not allow proper refrigerant flow.
The Oil Pressure Safety assures that the compressor’s
For the first 30 seconds of operation, the low suction mechanical components receive proper lubrication. The
pressure bypass is in operation. After 30 seconds of micro begins monitoring compressor oil pressure after 4
operation, the micro begins monitoring suction pressure seconds of operation. For operating periods of 4 sec-
and continues to do so as long as the compressor runs. onds to 30 seconds, oil pressure must be greater than 5
For operation periods of 30 seconds to 240 seconds, PSID. From 30 seconds to 240 seconds, oil pressure
suction pressure must be greater than 50% of the Suc- must be greater than 20 PSID. After 240 seconds, oil
tion Pressure Cut-out. After 240 seconds, suction pres- pressure must be greater than 25 PSID for as long as
sure must be greater than the cut-out. the compressor continues to run. If the required oil pres-
sure limits are not met, the system will shut down.
NOTE: A transient timer is built into software to assure
that short term fluctuations in suction pressure The micro computes “differential oil pressure” by mea-
due to fan cycling, loading, etc. do not cause suring oil pump pressure and subtracting suction pres-
nuisance trips on low suction pressure. sure (Oil - Suction = Oil PSID).

After the system has pumped down and suction An example of an oil pressure fault display message is
pressure reaches cut-out plus 5 PSIG, the tran- shown below.
sient timer is readied for action. If suction pres-
sure drops below the cut-out point, the 120 sec- S Y S # 1 L OW O I L P R E S S
ond transient timer begins timing. As long as S Y S # 2 L OW O I L P R E S S
suction pressure doesn’t drop below 50% of cut-
out during the 120 second period and rises above
cut-out before the timer times out, the system Pumpdown Safety
will continue to run.
The Pumpdown Safety assures that a compressor does
The Suction Pressure Safety Cut-out is programmable not run unless it completes a proper pumpdown. This
by the user (Page 44). An example of a suction pres- prevents operation of a refrigerant system which has a
sure fault message is shown below. leaking liquid line solenoid valve.
S Y S # 1 L OW S U C T I O N On shutdown, the system must pump down to the suc-
S Y S # 2 L OW S U C T I O N tion pressure cut-out within 300 seconds or the system
will shut down. If the system performs 3 unsuccessful
pumpdowns in a row, the system will fault & lock out.
Discharge Pressure Safety
An example of the Pumpdown Fault display message is
The Discharge Pressure Safety assures that the sys- shown below.
tem pressure does not exceed safe working limits which S Y S # 1 P U M P D OW N F A I L
could open a relief valve or other pressure relief device
S Y S # 2 P U M P D OW N F A I L
causing refrigerant loss.

This safety is a back-up for the mechanical safety in the


system. Anytime the cut-out point is exceeded, the sys- High Oil Temp Safety
tem will shut down.
This safety protects the compressor from catastrophic
failure by sensing when an internal problem occurs that

58 YORK INTERNATIONAL
FORM 150.60-NM5

causes high internal compressor temperatures. It also NOTE: Do not confuse FLA and RLA. FLA (full load
protects the compressor from overheating, due to im- amps) is approximately 1.2 x RLA. RLA (run-
proper cooling from hot suction gas, high water tempera- ning load amps) specified on the motor name-
tures, or high discharge pressures. plate, is typical current demand under rated op-
erating conditions in a fully loaded system. There-
The compressor will shut down whenever the sump tem- fore, do not expect to see 100% FLA when the
perature exceeds 180°F (82.2°C) for the first minute of system is fully loaded In this condition, currents
operation or 160°F (71.1°C) after one minute of opera- may run approximately 65 - 85% FLA.
tion.
INDIVIDUAL START INHIBIT SAFETIES
An example of the Oil Temp Inhibit safety display is
shown below: An Individual System Start Inhibit Safety will shut the
respective system down on a fault when the safety thresh-
S Y S # 1 H I G H O I L T E M P old is exceeded and allows automatic restart after the
S Y S # 2 H I G H O I L T E M P condition causing the shutdown clears. Restart will oc-
cur only after anti-recycle timers are satisfied and de-
mand requires.
MANUAL RESET SAFETIES (1 Fault and Lockout)
When the chiller is shut down on one of these safeties,
A Manual Reset Safety will shut the affected system a message will appear on the STATUS display informing
down and lock it out whenever the safety threshold is the operator of the problem. This is accessible by press-
exceeded. ing the STATUS key.

After a system has shut down and locked out, a fault Low Oil Temperature Inhibit Safety
display indicating the last system fault will appear on
the STATUS display message. This is accessible by Low oil temperature assures the compressor is not al-
pressing the STATUS key. lowed to start until the oil is free of liquid refrigerant. This
is accomplished by assuring that the oil temperature is
To reset a locked out system, turn the affected system a minimum of 15°F (8.3°C) above ambient temperature.
switch on the Microprocessor Board (Page 69) to the
OFF position. In effect, this safety assures that the compressor oil
heater is operating and that it has been on long enough
CAUTION: Before returning a locked out system to after power application for all refrigerant to have been
service, a thorough investigation of the cause expelled from the oil.
of the fault should be made. Failure to re-
pair the cause of the fault while manually NOTE: This safety will only be operational if the chiller
allowing repetitive restarts may cause fur- is equipped with an I/O Expansion Board.
ther expensive damage to the system.
An example of the High Oil Temp safety display is shown
Each of the Manual Reset Safeties will be discussed in below.
detail below.
S Y S # 1 O I L T E M P I N H I B
High Motor Current Safety S Y S # 2 O I L T E M P I N H I B

The High Motor Current Safety assures that motor life is


not diminished due to operating beyond the current rat- AUTOMATIC RESET SAFETIES
ing of the motor. The Micro begins monitoring motor cur-
rent after 3 seconds of operation. If motor current ex- An Automatic Reset Safety will shut the entire chiller
ceeds 120% FLA after 3 seconds of operation, the com- down on a fault when the safety threshold is exceeded
pressor will shut down. After 4 seconds of operation, and allows automatic restart after the condition causing
motor current must be less than 115% FLA as long as the shutdown clears. Restart will occur only after anti-
the compressor continues to run. recycle timers are satisfied and demand requires.

An example of the High Motor Current display is shown A reset hysteresis is built in so repetitive faulting and
below: clearing will not occur in a short time period. An ex-
ample would be if ambient temperature dropped below
S Y S # 1 H I G H M T R C U R R
the cut-out, temperature would have to rise 5°F (2.8°C)
S Y S # 2 H I G H M T R C U R R
above the cut-out before the fault lockout would clear
and restart can occur.
YORK INTERNATIONAL 59
When the chiller is shut down on one of these safeties, Under Voltage Safety
a message will appear on the STATUS display informing
the operator of the problem. This is accessible by press- The Under Voltage Safety assures that the system is
ing the STATUS key. not operated at voltages where malfunction of the micro-
processor could result in system damage. Whenever the
Details concerning each of the three Automatic Reset microprocessor senses an onboard power supply fail-
Safeties follow. ure, the chiller is shut down. Restart will occur when
power is restored. The microprocessor circuitry is ca-
Low Water Temperature Safety pable of operating at voltages 10% below the nominal
115VAC supply to the panel.
The Low Water Temperature Safety assures that the
evaporator is not damaged from freezing due to improp- An example of the Under Voltage Safety display mes-
erly set control points. Whenever the chilled liquid tem- sage is shown below:
perature drops below the programmable cut-out, the C H I L L E R F A U L T :
chiller will shut down. Restart will not occur until tem-
1 1 5 V A C U N D E R V O L T A G E
perature rises 5°F (2.8°C) above the cut-out point, load
demand requires, and anti-recycle timers allow.
Flow Switch
The Low Water Temperature Safety Cut-out is program-
mable by the user (Page 43). An example of the Low The microprocessor monitors the closure of the flow
Water Temperature Fault display message is shown switch to assure that water flow is present in the evapo-
below: rator which prevents freeze-ups. The flow switch “dry”
contacts are connected between terminals 13 & 14 of
C H I L L E R F A U L T :
the TB3 terminal block (Fig. 12). If the flow switch opens,
L OW W A T E R T E M P
the chiller will shut down and the following status mes-
sage will be displayed.
Low Ambient Temperature Safety
S Y S # 1 N O R U N P E RM
S Y S # 2 N O R U N P E RM
The Low Ambient Temperature Safety assures that the
chiller does not run in low ambients where potential dam-
age could result due to low system pressures. Closure of the flow switch, when flow is present, will cause
the message to disappear and auto-restart will occur.
The Low Ambient Cut-out is programmable by the user
(Page 44). An example of the Low Ambient Temperature CAUTION: NEVER BYPASS A FLOW SWITCH. THIS
Fault display message is shown below: WILL CAUSE DAMAGE TO THE CHILLER
AND VOID ANY WARRANTIES.
C H I L L E R F A U L T :
L OW AM B I E N T T E M P
Power Failure Safety

High Ambient Temperature Safety Whenever power is removed or lost and then reapplied,
auto-restart will occur after a 2 minute anti-recycle timer
The High Ambient Temperature Safety assures that the elapses. This is the same anti-recycle timer which is
chiller does not run in ambients above 130°F (54.4°C) programmable from 5-10 minutes; however, it automati-
where potential malfunction of system mechanical and cally is set to 2 minutes after a power failure.
electrical components may result. Whenever the out-
door ambient exceeds 130°F (54.4°C) (non-programmable) This safety assures that the motor has a minimum of 2
the chiller will shut down. Restart will not occur until minutes to cool under any circumstances allowing much
temperature drops to 2°F (1.1°C) below the cut-out point, of the internal heating due to starting to be dissipated
load demand requires, and anti-recycle timers allow. before another start occurs.

The High Ambient Cut-out is programmable (Page 44) ANTICIPATION SAFETY CONTROLS
for chiller cut-out at temperatures below 130°F (100° -
130°F) [54.4°C (37.8°C - 54.4°C)]. An example of the Anticipation controls are built into the software to pre-
High Ambient Temperature Fault display message is vent safety shutdowns by automatically overriding tem-
shown below: perature controls if system pressures near safety thresh-
olds. This allows the chiller to continue to run under re-
C H I L L E R F A U L T : duced capacity to avoid total loss of cooling resulting
H I G H AM B I E N T T E M P from a lockout on a safety.

60 YORK INTERNATIONAL
FORM 150.60-NM5

Anticipation safeties monitor suction and discharge pres- pressor start). Even though the Anti-recycle timer has
sure and unload the compressors as needed. The micro timed out, a minimum of 2 minutes (2-minute start-up
will display a message on the STATUS DISPLAY when- timer) must always elapse after a compressor stop be-
ever these controls are in operation. fore it may again restart.

CURRENT LIMITING If a power failure occurs, the anti-recycle timers will re-
set to 2 minutes after power is re-applied.
If current exceeds the value programmed by the user
(Page 45), the micro will unload the affected compressor. If the anti-recycle timer is preventing a start, the timer
position in seconds may be viewed by pressing the STA-
Whenever Current Limiting is activated, the compressor TUS key. A sample display is shown below.
will stay in the unloaded state for 5 minutes. After the 5
S Y S # 1 A R T M R 1 0 2 S
minute time period, the micro will look at motor current
once again. If motor is 25% below the programmed Mo- S Y S # 2 A R T M R 1 0 2 S
tor Current Unload point, the compressor will be allowed
to reload, if water temperature allows. ANTI-COINCIDENCE TIMER

This safety assures that the motor will receive proper The Anti-Coincidence Timer assures that 2 compressors
cooling from the refrigerant which promotes longer motor can never start simultaneously. This assures that ex-
life. cessive current demand will never result. A one minute
time delay will always separate compressor starts.
An example of the message displayed when current lim-
iting is in effect is shown below: The Anti-Coincidence Timer can be viewed, when it is
active, by pressing the STATUS key. A sample display
S Y S # 1 C U R R L I M I T I N G
is shown below.
S Y S # 2 C U R R L I M I T I N G
S Y S # 1 C OM P R U N N I N G
Discharge Pressure Unloading S Y S # 1 A C T M R 5 6 S

If the discharge pressure exceeds the value programmed PUMPDOWN CONTROLS


by the user (Page 42), the micro will unload the affected
compressor. Automatic reloading will occur when pres- Pumpdown control will pump down a system to the suc-
sure drops 60 PSI (413.7 kPa) below the programmed tion pressure cut-out whenever the compressor shuts
value. This feature reduces the chance of faulting on the down on a normal shutdown. Additionally, a recycling
high discharge pressure cut-out. pumpdown is employed on an as needed basis to as-
sure that liquid does not accumulate in the evaporator
On water cooled chillers, this safety reduces the chance on an OFF system, while cold chilled liquid is flowing,
of tripping the relief valve due to a very high rate of rise in through the evaporator. Since pumpdown at start-up is
pressure resulting from a controls problem which would not employed, the liquid line solenoid valve will open
cause condenser water flow to be interrupted. In this immediately when a compressor starts.
case, the pressure rise is so fast, refrigerant loss may
occur through the relief valve even though the high pres- “Pumpdown on shutdown” will pump a system down
sure cut-out has opened and the compressor is in the whenever a system shuts down, except in two circum-
midst of stopping. stances. A pumpdown will not occur whenever a fault
causes a shutdown or when “UNIT” rocker switch is
An example of the message displayed when discharge turned off. Pumpdown will continue until the suction pres-
pressure unloadings in effect is shown below: sure falls below the suction pressure cut-out. If the pres-
S Y S # 1 D S C H L I M I T I N G
sure never drops below the cut-out, pumpdown will con-
tinue until a 3-minute pumpdown timer has expired.
S Y S # 2 D S C H L I M I T I N G

During pumpdown, the following STATUS message will


INTERNAL TIMERS AND PUMPDOWN CONTROLS be displayed:
S Y S # 1 P UM P I N G D OW N
ANTI-RECYCLE TIMER
S Y S # 2 P UM P I N G D OW N
Anytime a compressor shuts down for any reason, re-
start cannot occur until the programmable Anti-recycle The PUMPING DOWN message indicates that the re-
Timer (Page 43) has timed out (timer starts with the com- spective compressor is presently in the process of pump-
ing the system down. The compressor will either be in a
YORK INTERNATIONAL 61
recycling pumpdown or in a pumpdown prior to shut- A pumpdown failure fault will occur if a system performs
down when this message is displayed. The message 3 unsuccessful pumpdowns in a row. “Unsuccessful”
will disappear when the compressor shuts off. assumes that the system was not able to pump down to
the suction pressure cut-out in 3 minutes. The system
“Recycling pumpdown” is initiated while a compressor will require a manual reset to restart. The following is an
is off, able to run, and is in a “No Cooling Load” state. It example of this safety message.
can be initiated 45 minutes after either of the following
two conditions are met: NOTE: Under some circumstances, a pumpdown may
occur when a compressor is called to come on
1. Sat Suction Temp > LCHWT - 1.5°F (0.8°C) for cooling. If this occurs, the compressor will
and restart to provide cooling after the pumpdown is
Ambient Temp > LCHWT - 6°F (3.3°C) complete and the anti-recycle timer times out.

2. The compressor has been idle for 2 hours and Suc- Recycling pumpdown will increase the number of starts
tion Pressure is greater than the cut-out. logged in the micropanel; however, it will have no effect
upon the life of the compressors.
The 45-minute timer assures that excessive pumpdowns
do not occur. Pumpdown Safety

After 120 pumpdowns, uninterrupted by a cooling start, The Pumpdown Safety assures that a compressor does
the system will cease to pump down. Pumpdowns will not run unless it completes a proper pumpdown. This
begin again after a cooling start occurs. This is to pre- prevents operation of a refrigerant system which has a
vent oil loss in the system. However, if one system leaking liquid line solenoid valve.
reaches 120 pumpdowns while the other system is run-
ning for cooling, the running (lead) compressor will be On shutdown, the system must pump down to the suc-
shut off if the off (lag) compressor is available for start. tion pressure cut-out within 300 seconds or the system
At this point, the lead compressor will pump down and will shut down. If the system performs 3 unsuccessful
shut off while the lag compressor starts and assumes pumpdowns in a row, the system will fault and lock out.
the lead. The previous running compressor will now have
120 pumpdowns available. An example of the Pump down fault display message is
shown below.
S Y S # 1 P U M P D OW N F A I L
S Y S # 2 P U M P D OW N F A I L

62 YORK INTERNATIONAL
FORM 150.60-NM5

“PRINT” KEYS

“PRINT”
KEYS

02711TG

YORK INTERNATIONAL CORPORATION


GENERAL RECIPROCATING WATER CHILLERS
SYSTEM STATUS
The PRINT keys allow the operator to obtain a remote 8:45AM 4/17/98
printout of real-time system operating data and a print- SYS 1 COMPRESSOR RUNNING
SYS 2 ANTI-COIN TIMER 13 SEC.
out of system data at the “instant of the fault” on the last
three faults which occurred on the chiller. RETURN WATER TEMP 65.0 DEGF
LEAVING WATER TEMP 54.0 DEGF
LOW WATER CUTOUT 36.0 DEGF
SETPOINT TEMP 45.0 DEGF
If a remote printer is not being used, or the desire is to OUTSIDE AIR TEMP 75.0 DEGF
obtain data locally at the panel, the same keys allow LOW AMBIENT CUTOUT 10.0 DEGF
LOW PRESSURE CUTOUT 4 4 PSIG
access to identical fault data. Identical and additional LEAD SYSTEM SYS 1
real-time information is available by using a combination CONTROL TYPE LCHWT
COOLING RANGE 45.0 TO 47.0 DEGF
of the PRINT keys and the other keys on the keypad.
SYSTEM 1 DATA
COMPRESSOR STATUS ON
An explanation of the use of the keys for remote printer MOTOR AMPS 50 %FLA
SUCTION PRESSURE 61 PSIG
or local data retrieval will follow. An optional printer (Page DISCHARGE PRESSURE 143 PSIG
87) will be required for remote printout. OIL PRESSURE 75 PSID
LIQUID LINE SOLENOID OFF
RUN PERMISSIVE ON
REMOTE PRINTOUT STAGES OF LOADING 1
FORWARD FANS OFF
REVERSE FANS OFF
OPER HOT GAS BYPASS VALVE OFF
Oper Data
DATA SYSTEM 2 DATA
COMPRESSOR STATUS ON
The OPER DATA key allows the operator to remotely MOTOR AMPS 0 %FLA
obtain a printout of current system operating parameters. SUCTION PRESSURE 61 PSIG
DISCHARGE PRESSURE 80 PSIG
When the key is pressed, a snapshot will be taken of OIL PRESSURE 1 PSID
system operating conditions and panel programming LIQUID LINE SOLENOID OFF
RUN PERMISSIVE ON
selections. This data will be temporarily stored in memory STAGES OF LOADING 1
FORWARD FANS 1
and transmission of this data will begin to the remote REVERSE FANS OFF
printer. As the data is transmitted, it will be erased from HOT GAS BYPASS VALVE OFF
memory. S M T W T F S *=HOLIDAY
SUN START=06:00AM STOP=11:00AM
MON START=06:00AM STOP=11:00AM
A sample printout is shown in Fig. 19. TUE START=06:00AM STOP=11:00AM
WED START=06:00AM STOP=11:00AM
THU START=06:00AM STOP=11:00AM
FRI START=06:00AM STOP=11:00AM
SAT START=06:00AM STOP=11:00AM
HOL START=00:00AM STOP=11:00AM

FIG. 19 – OPERATING DATA PRINTOUT


YORK INTERNATIONAL 63
(storage area) for data related to each of the last 3 safety
History HISTORY shutdowns.

The HISTORY key allows the operator to remotely ob- The printout will begin with the most recent fault which
tain a printout of information relating to the last 3 Safety occurred. The most recent fault will always be stored as
Shutdowns which occurred. The information is stored at SAFETY SHUTDOWN NO. 1 (See printout Fig. 20). Iden-
the instant of the fault regardless of whether the fault tically formatted fault information will then be printed for
caused a lockout to occur. The information is also not SAFETY SHUTDOWN NO. 2 and SAFETY SHUTDOWN
affected by power failures (long term internal memory NO. 3.
battery backup is built into the circuit board) or manual
resetting of a fault lockout. Information contained in the SAFETY SHUTDOWN Buff-
ers is very important when attempting to troubleshoot a
When the HISTORY key is pressed, a Printout is trans- system problem. This data reflects the system condi-
mitted of all system Operating conditions which were tions at the instant the fault occurred and often reveals
stored at the “instant the fault occurred” for each of the 3 other system conditions which actually caused the safety
SAFETY SHUTDOWN BUFFERS. There is one buffer threshold to be exceeded. (See Fig. 20)

YORK INTERNATIONAL CORPORATION YORK INTERNATIONAL CORPORATION YORK INTERNATIONAL CORPORATION


RECIPROCATING WATER CHILLERS RECIPROCATING WATER CHILLERS RECIPROCATING WATER CHILLERS
•

•
SAFETY SHUTDOWN NUMBER 1 SAFETY SHUTDOWN NUMBER 2 SAFETY SHUTDOWN NUMBER 3
SHUTDOWN @ 8:48AM 4/17/98 SHUTDOWN @ 8:47AM 4/17/98 SHUTDOWN @ 8:47AM 4/17/98
SYS 1 STATUS: NO FAULTS SYS 1 STATUS: NO FAULTS SYS 1 STATUS: NO FAULTS
SYS 2 MOTOR CURRENT SHUTDOWN SYS 2 MOTOR CURRENT SHUTDOWN SYS 2 MOTOR CURRENT SHUTDOWN
RETURN WATER TEMP 65.0 DEGF RETURN WATER TEMP 65.0 DEGF RETURN WATER TEMP 65.0 DEGF
LEAVING WATER TEMP 54.0 DEGF LEAVING WATER TEMP 54.0 DEGF LEAVING WATER TEMP 54.0 DEGF
LOW WATER CUTOUT 36.0 DEGF LOW WATER CUTOUT 36.0 DEGF LOW WATER CUTOUT 36.0 DEGF
SETPOINT TEMP 45.0 DEGF SETPOINT TEMP 45.0 DEGF SETPOINT TEMP 45.0 DEGF
OUTSIDE AIR TEMP 75.0 DEGF OUTSIDE AIR TEMP 75.0 DEGF OUTSIDE AIR TEMP 75.0 DEGF
LOW AMBIENT CUTOUT 10.0 DEGF LOW AMBIENT CUTOUT 10.0 DEGF LOW AMBIENT CUTOUT 10.0 DEGF
LOW PRESSURE CUTOUT 44 PSIG LOW PRESSURE CUTOUT 44 PSIG LOW PRESSURE CUTOUT 44 PSIG
LEAD SYSTEM SYS 1 LEAD SYSTEM SYS 1 LEAD SYSTEM SYS 1
CONTROL TYPE LCHWT CONTROL TYPE LCHWT CONTROL TYPE LCHWT
COOLING RANGE 45.0 TO 47.0 DEGF COOLING RANGE 45.0 TO 47.0 DEGF COOLING RANGE 45.0 TO 47.0 DEGF
SYSTEM 1 DATA SYSTEM 1 DATA SYSTEM 1 DATA
COMPRESSOR STATUS ON COMPRESSOR STATUS ON COMPRESSOR STATUS ON
MOTOR AMPS 50 %FLA MOTOR AMPS 50 %FLA MOTOR AMPS 50 %FLA
SUCTION PRESSURE 61 PSIG SUCTION PRESSURE 61 PSIG SUCTION PRESSURE 61 PSIG
DISCHARGE PRESSURE 143 PSIG DISCHARGE PRESSURE 143 PSIG DISCHARGE PRESSURE 143 PSIG
OIL PRESSURE 75 PSID OIL PRESSURE 75 PSID OIL PRESSURE 75 PSID
LIQUID LINE SOLENOID OFF LIQUID LINE SOLENOID ON LIQUID LINE SOLENOID ON
RUN PERMISSIVE ON RUN PERMISSIVE ON RUN PERMISSIVE ON
STAGES OF LOADING 1 STAGES OF LOADING 1 STAGES OF LOADING 1
FORWARD FANS 2 FORWARD FANS 2 FORWARD FANS 2
REVERSE FANS OFF REVERSE FANS OFF REVERSE FANS OFF
HOT GAS BYPASS VALVE OFF HOT GAS BYPASS VALVE OFF HOT GAS BYPASS VALVE OFF
SYSTEM 2 DATA SYSTEM 2 DATA SYSTEM 2 DATA
COMPRESSOR STATUS ON COMPRESSOR STATUS ON COMPRESSOR STATUS ON
MOTOR AMPS 0 %FLA MOTOR AMPS 0 %FLA MOTOR AMPS 0 %FLA
SUCTION PRESSURE 61 PSIG SUCTION PRESSURE 61 PSIG SUCTION PRESSURE 61 PSIG
DISCHARGE PRESSURE 80 PSIG DISCHARGE PRESSURE 80 PSIG DISCHARGE PRESSURE 80 PSIG
OIL PRESSURE 1 PSID OIL PRESSURE 1 PSID OIL PRESSURE 1 PSID
LIQUID LINE SOLENOID OFF LIQUID LINE SOLENOID OFF LIQUID LINE SOLENOID OFF
RUN PERMISSIVE ON RUN PERMISSIVE ON RUN PERMISSIVE ON
STAGES OF LOADING 1 STAGES OF LOADING 1 STAGES OF LOADING 1
FORWARD FANS 1 FORWARD FANS 1 FORWARD FANS 1
REVERSE FANS OFF REVERSE FANS OFF REVERSE FANS OFF
HOT GAS BYPASS VALVE OFF HOT GAS BYPASS VALVE OFF HOT GAS BYPASS VALVE OFF

NOTE: In actual print-outs, this would be one continuous print-out.

FIG. 20 – HISTORY PRINTOUT


64 YORK INTERNATIONAL
FORM 150.60-NM5

LOCAL DISPLAY READOUT 5 STAGE


Oper Data STEP
0: Both Compressors OFF
The OPER DATA key also allows the user to scroll through
additional real time display information about the chiller *1: Lead Compr Unloaded, Lag Compr OFF
system which is not available from the DISPLAY keys. *2: Lead Compr Unloaded, Lag Compr OFF
This information covers a wide range of data which in-
*3: Lead Compr Loaded, Lag Compr OFF
cludes fan status, loading status, liquid line solenoid
*4: Lead Compr Loaded, Lag Compr OFF
status, run time, etc. A total of 20 different displays are
offered. *5: Lead Compr Unloaded, Lag Compr Unloaded
*6: Lead Compr Unloaded, Lag Compr Unloaded
When the OPER DATA key is pressed, the following
*7: Lead Compr Loaded, Lag Compr Unloaded
message will appear:
*8: Lead Compr Loaded, Lag Compr Unloaded
P R E S S E N T E R T O
*9: Lead Compr Loaded, Lag Compr Loaded
D I S P L A Y D A T A
*10: Lead Compr Loaded, Lag Compr Loaded
* On some “STEPS”, actual Loading will NOT change.
Repetitively pressing the ENTER key allows the opera-
tor to scroll through the 20 available displays.

In the information that follows, a sample message along


with an explanation of its meaning is provided for all 20 T E M P E R A T U R E R A T E
messages. – 1 . 5 D E G F / M I N

This message provides a real time display of the aver-


L O A D T I M E R age rate of change of leaving chilled water as seen by
1 4 0 S E C S the micro. A (-) or (+) sign is also shown to indicate a
temperature fall or a temperature rise.
This message provides a real time display of the time
left on the Load Timer. The Load Timer is a constantly
recycling timer that the micro utilizes in conjunction with L E A D S Y S T E M I S
“rate control” and “temperature deviation from setpoint” S Y S T E M N UM B E R 1
to determine when loading should occur. The timer will
This message informs the operator which system is in
always start at 150 sec.; however, it may count to “0” at
the lead.
a rate of up to 5 secs. per actual second of time.

U N L O A D T I M E R E V A P O R A T O R W A T E R
P UM P S T A T U S O N
1 2 2 S E C S
This message informs the operator that the micro has
This message provides a real timer display of the time
commanded the auxiliary contacts (optional) for the
left on the Unload Timer. The Unload Timer is a con-
chilled water pump to close.
stantly recycling timer that the micro utilizes in conjunc-
tion with “rate control” and “temperature deviation from
setpoint” to determine when unloading should occur. The E V A P O R A T O R H E A T E R
timer will always start at 150 sec.; however, it may count S T A T U S O F F
to “0” at a rate of up to 5 secs. per actual second of time.
This message informs the operator that the micro senses
the outdoor ambient temperature is below 40°F (4.4°C)
T E M P E R A T U R E D E M A N D and is commanding the Evaporator Heater to turn on.
Once turned on, the heater will turn off at 45°F (7.2°C).
This message informs the operator what stage of load-
ing the chiller system is presently on as a result of com- C O N D E N S E R W A T E R
mands from the microprocessor. This is a coded number P UM P S T A T U S O F F
and the steps must be decoded to be meaningful. The
This message informs the operator that the micro has
decoding varies according to the number of stages pro-
commanded the auxiliary contacts (optional) for the con-
grammed (Page 44). Tables for decoding the display mes-
denser water pump to close.
sage are shown at the top of the next column:

YORK INTERNATIONAL 65
S Y S 1 L I Q U I D L I N E S Y S 2 R E V E R S E F A N
S O L E N O I D S T A T U S O F F S T A T U S O F F

“OFF”: SYS 1 Liquid Line Solenoid De-energized This message informs the operator whether the revers-
(Closed). ing fan is active on SYS 2.
“ON”: SYS 1 Liquid Line Solenoid Energized (Open).
S Y S 2 H O T G A S B Y P A S S
S Y S 1 S T A G E S O F V A L V E S T A T U S O N
L O A D I N G 2
This message informs the operator whether the Hot Gas
This message informs the operator of the number of Solenoid is ON or OFF. The Micro will activate the Hot
stages of loading which are active on SYS 1. Gas signal regardless of whether or not this option is
installed.
S Y S 1 F O RW A R D F A N S
S T A T U S O N S Y S 2 R U N T I M E
0 S E C S
This message informs the operator of the number of for-
ward running fans which are active on SYS 1. The Run Time for SYS 2 since the last start is displayed.

S Y S 1 R E V E R S E F A N
History
S T A T U S O F F
The HISTORY key also allows the user to scroll through
This message informs the operator whether the revers- the SAFETY SHUTDOWN buffers to display information
ing fan is active on SYS 1. relating to the last 3 Safety Shutdowns which occurred.
Information contained in the SAFETY SHUTDOWN Buff-
S Y S 1 H O T G A S B Y P A S S ers is very important when attempting to troubleshoot a
V A L V E S T A T U S O F F system problem. This data reflects system conditions
at the instant the fault occurred.
This message informs the operator whether the Hot Gas
Solenoid is ON or OFF. The micro will activate the Hot Information is stored in the SAFETY SHUTDOWN Buff-
Gas signal regardless of whether or not this option is ers on every fault regardless of whether the fault caused
installed. a Lockout to occur. The information is also not affected
by power failures (long term internal memory battery
S Y S 1 R U N T I M E backup is built into the circuit board) or manual resetting
2 0 0 S E C S of a fault lockout.

The Run Time for SYS 1 since the last start is displayed. When the HISTORY key is passed, the following mes-
sage will appear.
S Y S 2 L I Q U I D L I N E D I S P L A Y S A F E T Y S H U T -
S O L E N O I D S T A T U S O F F D OW N N O . 1 ( 1 T O 3 )
“OFF”: Sys 2 Liquid Line Solenoid De-energized
(Closed). The operator must then select which SAFETY SHUT-
DOWN Buffer which is desired. When deciding this, keep
“ON”: Sys 2 Liquid Line Solenoid Energized (Open). in mind that Buffer No. 1 is always the most recent fault.
As new fault information is stored, it is always placed in
S Y S 2 S T A G E S O F
Buffer No. 1, No. 1 is loaded to No. 2, No. 2 is loaded to
No. 3, and information previously in No. 3 is discarded.
L O A D I N G 1

This message informs the operator of the number of To select a buffer, simply press the “1”, “2”, or “3” EN-
stages of loading which are active on SYS 2. TRY key and press ENTER. Repetitively pressing the
ENTER key will allow the operator to scroll through the
S Y S 2 F O RW A R D F A N S
information available in the SAFETY SHUTDOWN Buffer.
S T A T U S O F F
In the information that follows, a sample message along
This message informs the operator of the number of for- with an explanation is provided for all available messages.
ward running fans which are active on SYS 2.

66 YORK INTERNATIONAL
FORM 150.60-NM5

S H U T D OW N O C C U R R E D C O N T R O L T Y P E
3 : 2 4 P M 6 / 3 / 9 8 L C HW T

This message informs the operator of the time and date This message indicates the type of chilled water control
of the fault. selected at the time of the fault. LCHWT = Leaving Wa-
ter Control. ECHWT = Entering or Return Water Control.
S Y S # 1 L OW O I L P R E S S
S Y S # 2 N O F A U L T S C O O L I N G R A N G E
4 5 . 0 T O 4 7 . 0 D E G F
This message informs the operator of the nature of the
fault which occurred. This display shows the Cooling Range (CONTROL
RANGE, CR) which was selected at the time of the fault.
R E T U R N W A T E R T E M P
5 2 . 7 D E G F E N T E R I N G C O N D W A T E R
8 0 . 1
This message indicates the Return Water Temperature
at the time of the fault. This message indicated the entering condenser water
temperature at the time of the fault. A fixed value will be
L E A V I N G W A T E R T E M P displayed if the optional sensor is not installed.
4 4 . 3 D E G F
L E A V I N G C O N D W A T E R
This message indicates the Leaving Water Temperature 9 0 . 5
at the time of the fault.
This message indicates the leaving condenser water tem-
L OW W A T E R C U T O U T perature at the time of the fault. A fixed value will be
3 6 . 0 D E G F displayed if the optional sensor is not installed.

This display shows the Low Water Cutout (Leaving) which S Y S 1 C OM P R E S S O R


was programmed at the time of the fault. O N

S E T P O I N T T E M P This message indicates whether Compressor 1 was ON


4 4 . 0 D E G F or OFF at the time of the fault.

This display shows the Setpoint Temp which was pro- S Y S 1 M O T O R AM P S


grammed at the time of the fault.
7 4 % F L A

O U T S I D E A I R T E M P This message indicates SYS 1 motor current at the time


7 7 . 6 D E G F of the fault.

This message indicates the Outdoor Ambient Tempera- S Y S 1 S U C T I O N P R E S S


ture at the time of the fault. 5 9 P S I G

L OW AM B I E N T C U T O U T This display shows the suction pressure of SYS 1 at the


3 5 . 0 D E G F time of the fault.

This display shows the Low Ambient Cutout programmed S Y S 1 D S C H P R E S S


at the time of the fault. 2 2 0 P S I G

L OW P R E S S U R E C U T O U T This message indicates SYS 1 discharge pressure at


4 4 P S I G the time of the fault.

This display shows the Low Pressure Cutout programmed S Y S 1 O I L P R E S S U R E


at the time of the fault. 7 0 P S I D

L E A D S Y S T E M This display shows the oil pressure of SYS 1 at the time


S Y S 1 of the fault.

This message indicates which system was in the lead


at the time of the fault.
YORK INTERNATIONAL 67
S Y S 1 L I Q L I N E S Y S 1 D S C H P R E S S
O N 2 4 0 P S I G

This display informs the operator whether SYS 1 liquid


This message indicates SYS 2 discharge pressure at
line solenoid was energized (ON) or de-energized (OFF)
the time of the fault.
at the time of the fault.

S Y S 2 O I L P R E S S U R E
S Y S 1 R U N P E RM I S S I V E
7 4 P S I D
O N
This display shows the oil pressure of SYS 2 at the time
This message informs the operator if SYS 1 Run Per-
of the fault.
missive (flow switch, remote START/STOP) was in the
RUN mode (ON) or (STOP) mode (OFF).
S Y S 2 L I Q L I N E
O N
S Y S 1 L O A D I N G S T A G E S
1 This display informs the operator whether SYS 2 liquid
line solenoid was energized (ON) or de-energized (OFF)
This message indicates the number of stages which were at the time of the fault.
loaded on SYS 1 at the time of the fault.
S Y S 2 R U N P E RM I S S I V E
S Y S 1 F O RW A R D F A N S O N
2
This message informs the operator if SYS 2 Run Per-
This display indicates the number of fans on SYS 1 which missive (flow switch, remote START/STOP) was in the
were running forward at the time of the fault. RUN mode (ON) or STOP mode (OFF).

S Y S 2 L O A D I N G S T A G E S
S Y S 1 R E V E R S E F A N S
O F F 1

This message indicates the number of fans on SYS 1 This message indicates the number of stages which were
which were running in the reverse direction at the time of loaded on SYS 2 at the time of the fault.
the fault.
S Y S 2 F O RW A R D F A N S
S Y S 1 H O T G A S V A L V E O F F
O F F
This display indicates the number of fans on SYS 2 which
This display indicates whether the Hot Gas Solenoid were running forward at the time of the fault.
Valve was energized on SYS 1 at the time of the fault.
NOTE: The micro will attempt to control the Hot Gas S Y S 2 R E V E R S E F A N S
Solenoid Valve regardless of whether the option O F F
is installed.
This message indicates the number of fans on SYS 2
which were running in the reverse direction at the time of
S Y S 2 C OM P R E S S O R
the fault.
O F F

This message indicates whether Compressor 2 was ON S Y S 1 H O T G A S V A L V E


or OFF at the time of the fault. O F F

This display indicates whether the Hot Gas Solenoid


S Y S 2 M O T O R AM P S Valve was energized on SYS 2 at the time of the fault.
6 0 % F L A

This message indicates SYS 2 motor current at the time NOTE: The micro will attempt to control the Hot Gas
of the fault. Solenoid Valve regardless of whether the option
is installed.
S Y S 2 S U C T I O N P R E S S
6 2 P S I G

This display shows the suction pressure of SYS 2 at the


time of the fault.
68 YORK INTERNATIONAL
FORM 150.60-NM5

“UNIT” ON/OFF SWITCH

“UNIT”
ON / OFF
SWITCH

02711TG

UNIT ON/OFF SWITCH ALARM CONTACTS (ANNUNCIATION ALARM)

A master UNIT ON/OFF switch is located on the key- *Dry” contacts connected to terminals 23 and 24 (Fig.
pad. This rocker switch allows the operator to turn the 22) are supplied, which will transition to function as a
entire chiller OFF if desired. The switch must be placed warning whenever a fault shutdown occurs on any sys-
in the ON position for the chiller to operate. tem or if power is lost to the control panel. The dry con-
tacts are normally open (N.O.) and will close when con-
Whenever the switch is placed in the OFF position, a trol power is applied to the panel, if no fault conditions
STATUS display indicating the condition will be displayed. are present. If power is not lost or a fault lockout occurs,
This message is shown below. the contact will open.
U N I T SW I T C H I S I N
T H E O F F P O S I T I O N
A 28VDC or 120VAC external alarm circuit (by others)
may be wired into the YORK supplied alarm contacts.
Any inductive load devices (relay, contactor), supplied
SYSTEM SWITCHES by the user which are connected to the dry contacts,
MUST be suppressed at the load. Use YORK P/N 031-
SYSTEM SWITCHES 1-4 are located on the Micropro- 00808-000 suppressor (not supplied). Failure to do this
cessor Board (See Fig. 21). These allow the operator to will result in nuisance faults and possible damage to the
selectively turn a given system on or off as desired. On a chiller.
2 system chiller, switches 3 & 4 should be OFF. The
System Switch for a designated system must be ON CAUTION: If the alarm circuit is applied in an applica-
(Switch to right) for the system to operate. tion used for critical duty (such as process
duty or cooling other critical equipment) and
Whenever a switch is placed in the OFF position, a STA- the alarm circuit should fail to function,
TUS display indicating the condition will be displayed YORK will not be liable for damages.
indicating that the system does not have a Run Permis-
sive signal. A sample of this message is shown below. LEAD/LAG COMPRESSOR SELECTION
S Y S # 1 N O R U N P E RM
The Chiller may be set up for AUTO or MANUAL Lead/
S Y S # 2 N O R U N P E RM Lag. This is accomplished by properly configuring the
S1 Dip Switches on the Microprocessor Board. Details
NOTE: This message will not appear if Anti-recycle or for configuring the switches are discussed in the DIS-
Anti-coincident timers are in effect and are be- PLAY KEY Section of the IOM under the “OPTIONS”
ing displayed. key.

YORK INTERNATIONAL 69
28697A

MICROPROCESSOR
BOARD
26001A
SYSTEM SWITCHES 1-4
FIG. 21 – LOCATION OF THE MICROPROCESSOR BOARD ON MICROPROCESSOR BOARD

When AUTO Lead/Lag is utilized, the micro attempts to


balance run time between the two compressors. A num-
ber of conditions can occur which will prevent this from
happening. Factors determining lead/lag selection and
the resulting lead/lag determination are discussed be-
low:

1. The micro automatically defaults the lead to SYS 1


and the lag to SYS 2 if both compressors are ready
to start (Anti-recycle Timers timed out) and com-
pressors have equal run time.

2. If both compressors are ready to start (Anti-recycle


Timers timed out), the compressor with the lowest
run hours will start first.

3. If both compressors are waiting to start (Anti-recycle LD02092

Timers are not timed out), the micro will assign the
FIG. 22 – ALARM CONTACT CONNECTION LOCATION
lead to the compressor with the shortest anti-recycle
time in an effort to provide cooling quickly.
If MANUAL Lead/Lag is selected, an external “dry” con-
4. If the lead compressor is locked out, faulted and tact (switch) must be wired into the chiller. This contact
waiting to restart, SYS switch on the micro board is is field supplied. With the contact open, SYS 1 is placed
off, or a run permissive is keeping an individual sys- in the lead. When the contact is closed, SYS 2 will be
tem from running, the lag compressor is swapped to the lead system.
the lead. This is true regardless of whether the lag
compressor is on or off. Manual Lead/Lag selection will be automatically overrid-
den by the micro to allow the lag compressor in a mod-

70 YORK INTERNATIONAL
FORM 150.60-NM5

CLOCK JUMPER
ule to automatically become the lead anytime the se-
lected lead compressor shuts down due to a lockout,
lead system faults and is waiting to restart, lead system
switch on the micro board is in the OFF position, or if a
run permissive is keeping the lead system off. Automatic
switchover in the “MANUAL” mode is provided to try to
maintain chilled liquid temperature as close to setpoint
as possible.

The “dry” contact for manual lead/lag selection is wired


into terminals 13 and 19 on the TB3 Terminal block. The
location of these terminals is shown in Fig. 23.

LD02093

FIG. 23 – LEAD/LAG CONTACT CONNECTION


LOCATION

MEMORY BATTERY BACK-UP

The Microprocessor board contains a Real Time Clock


(RTC) I.C. Chip with an internal battery back-up. The
battery back-up assures that any programmed values,
clock, all fault information, accumulated information such
as starts/run time, etc. stored in the RTC memory is not 26001A

lost when a power failure occurs regardless of the time FIG. 24 – CLOCK JUMPER
period.
To disable the clock, place the jumper (Fig. 24) in the
The battery is a 10-year lithium type. The life of the bat- OFF positions, To activate it, place the jumper in the ON
tery with power removed will depend upon whether the position.
Real Time Clock’s internal clock circuit is energized.
With the clock OFF, approximately 10 years can be ex- On power-up, the microprocessor will check the Real
pected, with the clock ON, approximately 5 years. Time Clock (RTC Chip) battery to assure that the inter-
nal battery is still operational. This is accomplished by
The clock is turned ON and OFF by a jumper on the performing an RTC RAM location check. As long as the
Microprocessor Board. While a chiller is operating, the battery checks out, the microprocessor will continue on
clock must be ON. Otherwise the internal clock on the with business without interruption.
microprocessor will not be active and the micro cannot
keep track of time, although all other functions will oper- If a check is made and the battery has failed, the micro-
ate normally. This could result in the chiller not starting processor will not allow the chiller to run and the follow-
due to the time frozen on the clock falling outside the ing STATUS message will appear:
START/STOP time window that is programmed in the ! ! W A R N I N G ! !
DAILY SCHEDULE. ! ! L OW B A T T E R Y ! !

If the chiller is shut down for extended periods of months,


it may be desirable to disable the clock to save battery The only way to run the chiller is to press the MANUAL
life. The clock can then be reactivated and reprogrammed OVERRIDE key. Under low battery conditions, the manual
when the chiller is returned to service. override key will function differently than it normally does
in service situations where it overrides the daily sched-
NOTE: ALL PROGRAMMED VALUES AND STORED ule for only 30 min. In a low battery condition, the
DATA, OTHER THAN THE INTERNAL CLOCK MANUAL OVERRIDE key will zero out the daily sched-
TIME-KEEPING, WILL BE MAINTAINED IN ule to allow unlimited operation regardless of the time on
MEMORY REGARDLESS OF WHETHER THE the internal clock. Default values will also be loaded into
CLOCK IS ON OR OFF AND REGARDLESS memory for all setpoints and cut-outs. These may re-
OF THE LENGTH OF THE POWER FAILURE. quire reprogramming to assure they meet chiller operat-

YORK INTERNATIONAL 71
ing requirements. In addition, the low battery message EMS/BAS CONTROLS
which is displayed for this condition will disappear.
The microprocessor is capable of REMOTE START/
NOTE: If a power failure should again occur, the above STOP, REMOTE UNLOADING (Pulldown demand limit-
process will again need to be repeated to bring ing), and REMOTE SETPOINT RESET. These functions
the chiller back on line. can be easily utilized by connecting use supplied “dry”
contacts to the terminals on the TB3 Terminal Block.
In the unlikely event the low battery message should
ever appear, it will require the RTC Chip U13 on the Mi- REMOTE START/STOP BY A CYCLING DEVICE OR
croprocessor Board (Fig. 13 to be replaced. Care should TIME CLOCK
be taken to assure that the chip is properly installed.
Pin 1 (dimple in the top of the chip) must be oriented as Remote START/STOP is accomplished by connecting a
shown (Fig. 13. The part number for the RTC Chip is time clock or other “dry” contact in series with the flow
031-00955-000. switch on terminals 13 & 14. See Fig. 12 for the location
of the terminals. The contact must be closed to allow
CRANKCASE HEATER the chiller to run. Any time the contact opens, the chiller
will shut down and the following status message will be
The crankcase heater for a compressor will be ON when- displayed.
ever the compressor is not running. The heater is inter-
S Y S # 1 N O R U N P E RM
locked into the compressor motor contactor and is not
S Y S # 2 N O R U N P E RM
controlled by the microprocessor.

The purpose of the crankcase heater is to prevent the Wiring from these contacts should not exceed 25 ft. and
migration of refrigerant to the crankcase during shutdown should be run in grounded conduit that does not carry
assuring proper lubrication of the compressor on start- any wiring other than control wiring. Additionally, if an
up. inductive device (relay, contactor) is supplying these
contacts, the coil of the device must be suppressed with
Anytime power is removed from the chiller for more than a user supplied YORK P/N 031-00808 suppressor.
an hour, the crankcase heater should be left on for 24
hours prior to start. This can be accomplished by apply- REMOTE SETPOINT RESET
ing 115VAC to the control panel. (REMOTE RESET TEMP RANGE)

EVAPORATOR HEATER Remote Setpoint Reset allows resetting the setpoint


upward from the programmed value in memory. This is
The evaporator heater prevents water standing in the accomplished by connecting a “dry” contact between
evaporator from freezing. Whenever outdoor ambient tem- terminals 13 & 17. See Fig. 12 for the location of these
perature drops below 40°F (4.4°C), the microprocessor terminals. Closing the contact for a defined period of time
will turn the evaporator ON. If temperature rises above allows reset of the setpoint upward by up to 40°F (22.2°C)
45°F (7.2°C) the heater will be turned off. above the setpoint programmed in memory.

METRIC DISPLAY The maximum desired reset must be programmed into


memory and can be a value of 02 to 40°F (1.1 - 22.2°C).
The control panel is capable of providing displays of pres- This value will vary according to the user’s requirements.
sure and temperature in metric values. Temperatures will To program the reset, press the REMOTE SETPOINT
be displayed in °C and pressures in kPa. TEMP RANGE key. The following message will appear.
R E M S E T P O I N T = 4 0 . 0
A Metric to English temperature conversion table is pro-
R E M R A N G E = 2 0 D E G F
vided on the rear cover of this manual. Pressure can be
converted from PSI to kPa using the formula PSI x 6.89
= kPa. The display will indicate the REM SETPOINT which is
always equal to the chilled liquid setpoint plus the offset
To obtain panel displays in metric, Switch 5 of Dip Switch from the reset signal. The display will also show the
S1 on the Microprocessor Board must be placed in the REM RANGE which is the same as the maximum reset
OPEN position (Page 35). The positioning of this switch required. Key in the maximum reset for the REM RANGE
can then be verified by pushing the OPTIONS key and and press the ENTER Key to store the new value in
verifying that “METRIC UNITS READOUT” is programmed memory.
(Page 35).

72 YORK INTERNATIONAL
FORM 150.60-NM5

Once the maximum reset is programmed, it will require NOTE: Remote Setpoint Reset will not operate when a
a contact closure of 21 seconds to achieve the maxi- Remote Control Center Option Kit is connected
mum reset. Closure for less than 21 seconds will provide to the Micro Panel, The Remote Control Center
a smaller reset. For noise immunity, the micro will ig- will always determine the setpoint.
nore closures of less than 1 second.
REMOTE UNLOADING
To compute the offset for a given timer closed, use the
formula below: The microprocessor is capable of remote unloading or
pulldown demand limiting in two steps. The first step
1. Programmed max. reset shuts down the lag system. The second step unloads
= Reset per sec.
20 seconds the lead system to its minimum step of capacity which
places the entire system at minimum possible capacity.
2. (Time Closed - 1) Reset per sec. = Reset
To shut down the lag compressor, a “dry” contact should
Example: be connected between terminals 13 & 16. See Fig. 12
for the location of these terminals. When the contact is
Programmed max reset = 30°; Time Closed = 9 sec. closed, the lag compressor will shut down.

1. 30° Before the lead system can be unloaded to its minimum


= 1.5° per sec.
20 sec. step of capacity, the lag compressor must already be
disabled with a “dry” contact closure between terminal
2. (9 sec. -1 sec.) 1.5° per sec. = 12° = Reset 13 & 16 as described in the preceding paragraph.

To determine the new setpoints, add the reset to the With contacts on Terminals 13 & 16 closed, the lead
setpoint programmed into memory. In the example above, system can be unloaded to its minimum step of capac-
if the programmed setpoint = 44°F, the new setpoint af- ity by closing a “dry” contact connected between termi-
ter the 9 second contact closure would be 44°F + 12°F nals 13 & 17. See Fig. 12 for location of this terminal.
= 56°F. This new setpoint can be viewed on the display The lead system will remain totally unloaded as long as
by pressing the REMOTE RESET TEMP/RANGE key. the contacts remain closed on both 13 & 16 and 13 &
17. It should be noted that terminals 13 & 17 are nor-
To maintain a given offset, the micro must be refreshed mally used for Remote Setpoint Reset. However, it is
every 30 seconds - 30 minutes with a contact closure of assumed that if the lag system is purposely being shut
the required time period. It will not accept a refresh sooner down, Remote Setpoint Reset and temperature control
than 30 seconds after the end of the last PWM signal, is of no importance. This is generally true since capacity
but must be refreshed before a period of 30 minutes ex- control of the load is lost when a large portion of the
pires from the end of the last PWM signal. capacity is disabled.

After 30 minutes, if no refresh is provided, the setpoint CAUTION: Two cautions should be observed when us-
will change back to its original value. A refresh is nothing ing these functions. Observing these cau-
more than a contact closure for the period required for tions will assure that undesirable operation
the desired offset. does not result.

NOTE: After an offset signal, the new setpoint may be 1. Terminals 13 & 17 contact should always
viewed on the REMOTE RESET TEMP RANGE be closed after or simultaneous with those
DISPLAY However, if this display is being viewed on 13 & 16, when unloading of the lead sys-
when the reset pulse occurs, the setpoint will tem is desired. Otherwise, the microproces-
not change on the display. To view the new off- sor may mistake the closed contacts on 13
set, first press any other display key on the key- & 17 as a signal for a setpoint reset.
pad and then press the REMOTE RESET TEMP
RANGE key. The new setpoint will then appear. 2. Terminal 13 & 17 contact should always be
opened before or simultaneous with those
Wiring from these contacts should not exceed 25 ft. and on 13 & 16 when loading is desired. Other-
should be run in grounded conduit that does not carry wise, the microprocessor may mistake the
any wiring other than control wiring. Additionally, if an closed contacts on 13 & 17 as a signal for
inductive device (relay, contactor) is supplying these con- a setpoint reset.
tacts, the coil of the device must be suppressed with a
user supplied YORK P/N 031-00808 suppressor.

YORK INTERNATIONAL 73
“STANDARD AMBIENT” FAN CONTROL ther system is running. These fans are shared fans
(ABOVE 25°F [-3.9°C]) and do not require the respective system to run. Op-
eration of either system will activate both of these
“Standard Ambient” fan control above 25°F (-3.9°C) can fans, after one of the systems has run for a period of
be selected by placing S1, Dip Switch 2 on Micropro- 30 sec. These fans will continue to run until the ambi-
cessor Board in the “OPEN” position (See page 28). ent drops below 40°F (4.4°C).
SYS. 1 SYS. 2 AMBIENT AMBIENT
Above 25°F, fans can either be controlled by ambient
FANS FANS ON OFF
temperature (“Ambient and Discharge Pr Fan Control”)
1&2 3&4 25°F (-3.9°C) 24°F (-4.4°C)
or solely by discharge pressure control (“Discharge Pres-
sure Fan Control”). This is selected by the operator 5 & 6* 5 & 6* 45°F (7.2°C) 40°F (4.4°C)
through S1, Dip Switch 8 on the Microprocessor Board * These fans will operate when either system is running and the
ambient is above 45°F (7.2°C).
(See page 34). Each of these methods of operation will
be discussed below. The contactor which activates the
fans is noted in the description of operation (i.e. 5M). “Discharge Pressure Fan Control”
System fan location is shown in Fig. 25.
This mode can be selected by placing S1, Dip Switch 8
on the Microprocessor Board in the “CLOSED” position
(See page 34). In “Standard Ambient” Fan Control above
25°F (-3.9°C), fan control will be solely be discharge
pressure.

1. Fans 5 (6M) of SYS 1 and 6 (12M) of SYS 2 will both


run when either system’s discharge pressure reaches
320 PSIG (2.2 mPa). These fans are shared fans and
do not require the respective system to run. These
fans will continue to operate until the discharge pres-
LD02699
sure of the sytem that turned the fans on drops to 120
PSIG (827.4 kPa) or discharge pressure of the sys-
FIG. 25 – FAN LOCATIONS tem that turned the fans on exceeds 340 PSIG (2.3
mPa).

2. Fans 1 (5M) and 2 (7M) or SYS 1 or fans 3 (11M) and


“Ambient and Discharge Pr Fan Control” 4 (13M) of SYS 2 will run when the discharge pres-
sure of the respective system reaches 340 PSIG (2.3
This control mode can be selected by placing S1, Dip mPa). These fans will continue to run until the dis-
Switch 8 on the Microprocessor Board in the “OPEN” charge pressure drops below 120 PSIG (827.4 kPa).
position (See page 34). In “Standard Ambient” Fan Con-
trol (operation at temperatures above 25°F [-3.9°C] only),
discharge pressure will have no effect when operating in 3. Fans 5 (6M) or SYS 1 and 6 (12M) of SYS 2 will both
the “Ambient and Discharge Pr Fan Control” mode. In run when the discharge pressure of either system
this mode, fan control will be a function of ambient tem- reaches 360 PSIG (2.5 mPa). These are shared fans
perature only. and do not require the respective system to run. Op-
eration of either system will activate both fans. These
fans will operate until the discharge pressure drops to
1. Fans 1 (5M) & 2 (7M) of SYS 1 or fans 3 (11M) & 4
140 PSIG (965.3 kPa) on the system which activated
(13M) of SYS 2 will run when the ambient is above
the fans.
25°F (-3.9°C) and the respective system has run for a
period of of 4 sec. These fans will continue to run until SYS. 1 SYS. 2
ON OFF
the system shuts down at 25°F (-3.9°C). FANS FANS
5 & 6** 5 & 6** 320 PSIG (2.2 mPa) 120 PSIG (827.4 kPa)
2. Fans 5 (6M) of SYS 1 and 6 (12M) of SYS 2 will both 1&2 3&4 340 PSIG (2.3 mPa) 120 PSIG (827.4 kPa)
run when the ambient is above 45°F (7.2°C) and ei- 5 & 6** 5 & 6** 360 PSIG (2.5 mPa) 140 PSIG (965.3 kPa)
** These fans will operate when discharge pressure of either
system reaches 360 PSIG (2.5 mPa).

74 YORK INTERNATIONAL
FORM 150.60-NM5

“LOW AMBIENT CONTROL” Fan operation below 25°F (-3.9°C) is controlled only by
discharge pressure. 4 steps of fan operation will operate
The chiller is designed to operate in low ambients down as follows:
to 0°F (-17.8°C) by merely placing S1, Dip Switch 2 on
the Microprocessor Board in the “CLOSED” position 1. Until discharge pressure reaches 320 PSIG (2.2 mPa)
(See page 28) and reprogramming the low ambient cut- on one of the systems, all fans will remain off.
out, page 35, to the desired cut-out point.

NOTE: Occasional operation below 0°F (-17.8°C) is nor- 2. Fans 5 (6M) of SYS 1 and 6 (12M) of SYS 2 will both
mally possible. In these situations, low suction run when the ambient is below 25°F (-3.9°C) and ei-
pressure shutdowns may sometimes occur. A cut- ther system’s discharge pressure reaches 320 PSIG
out of 0.00°F will allow operation in ambients below (2.2 mPa). These fans are shared fans and do not
0°F (-17.8°C). require the respective system to run. These fans will
continue to operate until the discharge pressure of
The fundamental purpose of the “Low Ambient Control” the system that turned the fans on drops to 120 PSIG
mode is to reduce the condenser capacity when the (827.4 kPa), the ambient temperature rises above 35°F
ambient is in the 0 - 25°F (-17.8 to -3.9°C) temperature (1.7°C), or discharge pressure of the system that
range. This assures that adequate discharge pressures turned the fans on exceeds 340 PSIG (2.3 mPa).
can be maintained at low ambient temperatures which
will eliminate low suction pressure faults. Operation at 3. If the discharge pressure of the system that turned
low ambients is accomplished by cycling fans acording fans 5 and 6 on rises to 340 PSIG (2.3 mPa), fans 5
to discharge pressure. When the micro is programmed and 6 will shut off and SYS 1 fans 1 (5M) and 2 (7M)
for the low ambient mode, an extra step of fan cycling is or SYS 2 fans 3 (11M) and 4 (13M) will turn on. These
automatically added. fans will stay on until discharge pressure of the re-
spective system drops to 120 PSIG (827.4 kPa).
The fans can be controlled by a combination of ambient
and discharge pressure control or solely by discharge NOTE: If the other system’s discharge pressure ex-
pressure control. ceeds 320 PSIG (2.2 mPa), fans 5 & 6 will
continue to run.
“Ambient and Discharge Pr Fan Control”
0 - 25°F (-17.8 to -3.9°C) 4. The final stage of fan control will operate fans 5 (6M)
and 6 (12M) when the discharge pressure of either
To operate the fans throughout the entire ambient range system reaches 360 PSIG (2.5 mPa). These fans will
by a combination of both ambient and discharge pres- remain on until the discharge pressure of the system
sure, the S1, Dip Switch 8 on the Microprocessor Board that turned the fans on falls to 140 PSIG (965.3 kPa).
must be placed in the “OPEN” position.

LOW AMBIENT MODE FAN CYCLING (Ambient Temperature / Discharge Pressure Control)
CONTROL BY
TEMPERATURE & PRESSURE
SYS FAN CONTACTOR BELOW 25°F (-3.9°C) ABOVE 25°F (-3.9°C)
PRESSURE CONTROL TEMPERATURE CONTROL ONLY

ON OFF ON OFF
320 PSIG 120 PSIG (827.4 kPa) Will Not Start 35°F (1.7°C) or
5&6 6M & 12M
(2.2 mPa) or 340 PSIG (2.3 mPa) Above 25°F (-3.9°C) 340 PSIG (2.3 mPa)
Turns OFF by
1 340 PSIG 120 PSIG Pressure
1&2 5M & 7M 25°F (-3.9°C)
(2.3 mPa) (827.4 kPa) Only at 120 PSIG
(827.4 kPa)
5&6 6M & 12M 360 PSIG (2.5 mPa) 140 PSIG (965.3 kPa) 45°F (7.2°C) 40°F (4.4°C)
320 PSIG 120 PSIG (827.4 kPa) Will Not Start 35°F (1.7°C) or
5&6 6M & 12M
(2.2 mPa) or 340 PSIG (2.3 mPa) Above 25°F (-3.9°C) 340 PSIG (2.3 mPa)
Turns OFF by
2 340 PSIG 120 PSIG Pressure
3&4 11M & 13M 25°F (-3.9°C)
(2.3 mPa) (827.4 kPa) Only at 120 PSIG
(827.4 kPa)
5&6 6M & 12M 360 PSIG (2.5 mPa) 140 PSIG (965.3 kPa) 45°F (7.2°C) 40°F (4.4°C)

YORK INTERNATIONAL 75
“Ambient and Discharge Pr Fan Control” sure of the system that turned the fans on drops to
Above 25°F (-3.9°C) 120 PSIG (827.4 kPa) or discharge pressure of the
system that turned the fans on exceeds 340 PSIG
Fan operation above 25°F (-3.9°C) will primarily be by (2.3 mPa).
ambient temperature except for situations where tem-
NOTE: These fans may continue to run if the sys-
peratures rose from the low ambient range to above 25°F
tem that has not yet reached a discharge pres-
(-3.9°C) and situations where fans are operating and dis-
sure of 340 PSIG (2.3 mPa) is operating at a
charge pressures drop very low as ambients fall below
discharge pressure above 340 PSIG (2.3
25°F (-3.9°C).
mPa).

1. Fans 1 (5M) and 2 (7M) of SYS 1 or fans 3 (11M) and


4 (13M) of SYS 2 will run when the ambient is above 3. Fans 1 (5M) and 2 (7M) of SYS 1 or fans 3 (11M) and
25°F (-3.9°C) and the respective system has run for a 4 (13M) of SYS 2 will run when the discharge pres-
period of 4 sec. These fans will continue to run until sure of the respective system reaches 340 PSIG (2.3
the system shuts down at 25°F (-3.9°C). mPa). These fans will continue to run until the dis-
charge pressure drops below 120 PSIG (827.4 kPa).

2. Fans 5 (6M) of SYS 1 and 6 (12M) SYS 2 will both run


when the ambient is above 45°F (7.2°C) and either 4. Fans 5 (6M) of SYS 1 and 6 (12M) of SYS 2 will both
system is running. These fans are shared fans and do run when the discharge pressure of either system
not require the respective system to run. Operation of reaches 360 PSIG (2.5 mPa). These are shared fans
either system will activate both of these fans, after and do not require the respective system to run. Op-
one of the systems has run for a period of 30 sec. eration of either system will activate both fans. These
These fans will continue to run until the ambient drops fans will operate until the discharge pressure drops to
below 40°F (4.4°C). 140 PSIG (965.3 kPa) on the system which activated
the fans.
If fans 5 and 6 were the only fans running as tempera- CONTROL BY
tures rose from below 25°F (-3.9°C) to above 25°F (-3.9°C), PRESSURE ONLY
the fans would continue to run until the ambient rose to
SYS FAN CONTACTOR TEMPERATURE
35°F (1.7°C) or discharge pressure of the system that HAS NO EFFECT
caused the fans to start rose to 340 PSIG (2.3 mPa). In
either case, fans 1 and 2 of SYS 1 and/or fans 3 and 4 of ON OFF
SYS 2 will come on if the system is running. 320 PSIG 120 PSIG (827.4 kPa)
1 & 3 REV 9M & 10M
(2.2 kPa) or 340 PSIG (2.3 mPa)
If fans 1 and 2 SYS 1 or fans 3 or 4 SYS 2 are running
and ambient is above 25°F (-3.9°C), the fans will con- 1 340 PSIG 120 PSIG
2&4 6M & 8M
(2.3 mPa) (827.4 kPa)
tinue to run as ambient drops below 25°F (-3.9°C) until
the system shuts down or the system’s discharge pres-
1 & 3 FWD 5M & 7M 360 PSIG (2.5 mPa) 140 PSIG (965.3 kPa)
sure drops below 120 PSIG (827.4 kPa).
320 PSIG 120 PSIG (827.4 kPa)
5 & 7 REV 15M & 16M
(2.2 mPa) or 340 PSIG (2.3 mPa)
“Discharge Pressure Fan Control”
(All Temperatures in Low Ambient Mode) 320 PSIG 120 PSIG
2 6&8 12M & 14M
(2.2 mPa) (827.4 kPa)
Fan operation in this mode will be solely by discharge
pressure. 4 steps of fan operation will be noted. This 5 & 7 FWD 11M & 13M 340 PSIG (2.3 mPa) 140 PSIG (965.3 kPa)
mode may be selected by placing S1, Dip Switch 8 on
the Microprocessor Board in the “CLOSED” position (See
page 36).

1. Until discharge pressure reaches 320 PSIG (2.2 mPa)


on one of the systems, all fans will remain off.

2. Fans 5 (6M) of SYS 1 and 6 (12M) of SYS 2 will both


run when either system’s discharge pressure reaches
320 PSIG (2.2 mPa). These fans are shared fans and
do not requrie the respective system to run. These
fans will continue to operate until the discharge pres-

76 YORK INTERNATIONAL
FORM 150.60-NM5

COMPRESSOR CAPACITY CONTROL

4 CYLINDER

LD02754

CHILLER # OF
# OF
MODEL SYSTEM UNLOADING STEPS
CYLINDERS
YCA STANDARD
J110 1 6
J120 5
J130 2 6

FIG. 26 – COMPRESSOR UNLOADING SEQUENCE

The function of the compressor capacity control system UNLOADING


is to automatically adjust the compressor pumping ca-
pacity to balance with the cooling load at a pre-deter- When the solenoid valve is energized, discharge gas pres-
mined return water temperature and to permit the com- sure is applied to the top of the unloader piston, forcing
pressor to start under partial load. The compressor ca- it down. The bottom end of the piston seats against the
pacity control system is actuated by means of gas pres- recessed opening to the suction plenum, effectively block-
sure from the discharge side of the compressor. Gas ing the flow of suction gas into the cylinders (blocked
pressure to the unloader piston unloads the associated suction unloading). The cylinders are now unloaded.
cylinders, and release of this pressure loads them. Con-
trol of the gas pressure to the unloader elements is the LOADING
function of the compressor capacity control solenoids.
When the solenoid valve is de-energized, gas pressure
on top of the unloader piston is relieved to the suction
plenum. This forces the piston up, uncovering the re-
cessed opening which allows the suction gas to flow
through the port and into the cylinders. The cylinders
are now loaded.

YORK INTERNATIONAL 77
SYSTEM START-UP CHECKLIST
CHECKING THE SYSTEM 24 HOURS PRIOR TO
INITIAL START-UP (NO POWER)
9 5. The compressor oil level must be maintained
between the middle of the upper and middle of
the lower sight glass at all operating condi-
JOB NAME: __________________________________ tions. At part load operating conditions, it is
SALES not abnormal for the oil level to be in the lower
ORDER #: ___________________________________ sight glass. If it is necessary to add oil, con-
nect a YORK oil pump to the oil charging valve,
LOCATION: __________________________________ but do not tighten the flare nut on the delivery
tubing. With the bottom (suction end) of the
SOLD BY: ___________________________________ pump submerged in oil to avoid the entrance of
air, operate the pump until oil drips from the
INSTALLING flare nut joint, allowing the air to be expelled,
CONTRACTOR: ______________________________ and tighten the flare nut. Open the compres-
sor oil charging valve and pump in oil until the
STARTUP: ___________________________________ oil reaches the proper level as described above.
TECHNICIAN/ Close the compressor oil charging valve.
COMPANY: __________________________________

DATE: ______________________________________
9 6. Assure water pumps are on. Check and adjust
water pump flow rate and pressure drop across
cooler.
CHILLER
MODEL #: _________________________________ 9 7. Check panel to see that it is free of foreign
material (wires, metal chips, etc.).
SERIAL #: _________________________________

COMPRESSOR #1
9 8. Visually inspect wiring (power & control). Must
meet NEC and all local codes.
(See Fig. 10 & 12)
MODEL #: _________________________________
SERIAL #: _________________________________ 9 9. Check for proper size fuses in main and con-
trol power circuits.
COMPRESSOR #2
MODEL #: _________________________________ 9 10. power
Verify that field wiring matches the 3-phase
requirements of the compressor. See
SERIAL #: _________________________________ nameplate. (See Fig. 10)
9 11. Assure 115VAC Control Power to TB1 has 30A
minimum capacity. (See Fig. 10)

Unit Checks 9 12. pletely


Be certain all control bulbs are inserted com-
in their respective wells and are coated
9 1. Inspect the unit for shipping or installation dam-
age.
with heat conductive compound.

PANEL CHECKS (POWER ON, BOTH SYSTEM


9 2. Assure that all piping has been completed. SWITCHES “OFF”)

9 3. Check that the unit is properly charged and


that there are no piping leaks.
9 1. Apply 3-phase power and verify its value. (See
Fig. 10). φ A: ____, φ B: ____, φ C: ____ VAC

9 4. Suction and discharge stop valves and the re-


frigerant liquid stop valves are open (ccw).
9 2. Apply 115VAC and verify its value on the termi-
nal block in the lower left of the Power Panel.
Make the measurement between terminals 5
CAUTION: Compressor lubrication circuit must be and 2. Should be 115VAC ± 10%. (See Fig.
primed with YORK “C” oil prior to start-up. 10). ______ VAC
Priming should be done through the
Schrader fitting at the compressor oil pump.
Stroke oil pump 10 times to prime the lubri-
9 3. Assure crankcase heaters are on. Allow crank-
case heaters to remain on a minimum of 24
cation circuit.

78 YORK INTERNATIONAL
FORM 150.60-NM5

hours before start-up. This is important to as-


sure no refrigerant is in the oil at start-up!
9 Place the System Switches to the ON position.
See the OPERATING SEQUENCE for unit opera-
tion.
9 4. Program the Dip Switches on the Micropro-
cessor Board (Page 34) and verify the selec-
tion by pressing the OPTIONS key.
9 The compressor will start and a flow of liquid should
be noted in the liquid indicator. After several min-
Switch 3 should always be closed. utes of operation, the bubbles will disappear and
Switch 6 should always be open. there will be a solid column of liquid when the unit
is operating normally. On startup, foaming of the
NOTE: It is IMPORTANT that all switches are properly oil may be evident in the compressor oil sight
programmed. Otherwise, undesirable operation glass. After the water temperature has been pulled
will result. down to operating conditions, the oil should be
clear. Normal operation of the unit is evidenced
9 5. Press the PROGRAM key and program each
of the 11 limits and record them. They are as
by a hot discharge line (discharge superheat
should not drop below 50°F [10°C]), clear oil in
follows: the compressor crankcase, solid liquid refriger-
ant in the liquid indicator and usually no more
9 •• Discharge Cutout ____ PSIG than 2 PSIG variation in suction pressure for any
9 • Outside Air Temp High Cutout
Outside Air Temp Low Cutout ____ °F given set of operating conditions.
9 • Discharge Pressure Unload Pressure____ PSIG
____ °F
9 • Suction Pressure Unload Pressure ____ PSIG
9 • Leaving Water Temp Cutout
9 Allow the compressor to run for a short time, be-
ing ready to stop it immediately if any unusual
9 • Suction Pressure Cutout ____ °F noise or other adverse condition should develop.
9 • Rate Control Temp ____ PSIG When starting the compressor, always make sure
9 • Anti Recycle Time ____ °F the oil pump is functioning properly. Compressor
9 • Rate Sensitivity ____ SEC oil pressure must be as described in the SYS-
9 • Number of Load Steps ____ °F/MlN TEM SAFETIES Section, page 57.
9 ____

See page 41 for assistance in programming


9 Check the system operating parameters. Do this
by selecting various readouts such as pressures
these values. and temperatures. Compare these to test gauge
readings.
9 6. Program the date and time by first assuring
that the CLK jumper J18 on the Microproces- CHECKING SUPERHEAT AND SUBCOOLING
sor Board (Fig. 26) is in the ON position (Top 2
pins). The subcooling should always be checked when charg-
ing the system with refrigerant and/or before setting the
Press the SET TIME key and set the date and superheat.
time (Page 45).
When the refrigerant charge is correct, there will be no
9 7. Program the Daily and Holiday Start/Stop
Schedule by pressing the SET SCHEDULE/
bubbles in the liquid sightglass with the system operat-
ing under full load conditions, and there will be 10°F to
HOLIDAY key (Page 46). 15°F (5.5 to 8.3°C) subcooled liquid refrigerant leaving
the condenser.
9 8. Program the Chilled Liquid Setpoint and Con-
trol Range by pressing the CHILLED LIQUID An overcharged system should be guarded against. Evi-
TEMP/RANGE key (Page 49). dences of overcharge are as follows:

9 9. If the Remote Reset is to be used, the maxi-


mum reset must be programmed. This can be
a. If a system is overcharged, the discharge pressure
will be higher than normal. (Normal discharge/con-
densing pressure can be found in refrigerant tem-
programmed by pressing the REMOTE RESET
perature/pressure chart; use entering air tempera-
TEMP RANGE key (Page 72).
ture +30°F (16.7°C) for normal condensing tem-
peratures.)
INITIAL STARTUP
b. The temperature of the liquid refrigerant out of the
After the operator has become thoroughly familiar with condenser should not be more than 15°F (8.3°C)
the control panel and has performed the preceeding less than the condensing temperature. (The tem-
checks 24 hours prior to startup, the unit can be put into perature corresponding to the condensing pressure
operation. from refrigerant temperature/pressure chart).
YORK INTERNATIONAL 79
The subcooling temperature should be taken by record- Proper subcooling and superheat will assure optimum
ing the temperature of the liquid line at the outlet of the performance and reliability of the system. Checks should
condenser and recording the liquid line pressure at the always be made when commissioning a chiller and on a
liquid stop valve with the system fully loaded after steady yearly basis.
state operation has been established and converting it
to temperature from a temperature/pressure chart. Be If the unit has been functioning satisfactorily during the
sure to insulate the thermometer or thermocouple at- initial operating period, it is ready for continuous opera-
tached to the piping. tion.

Example:
LIQUID LINE PRESSURE
9 Leak check compressors, fittings, and piping to
assure no leaks are present from improper handling.
202 PSIG converted to 102°F(38.9°C)
Minus Liquid Line Temperature - 90°F(32.2°C) OPERATING SEQUENCE UTILIZING
Subcooling = 12°F (6.7°C) RETURN WATER CONTROL

Record: SYS 1______, SYS 2______ NOTE: The operating sequence described below relates
to operation after power has been applied on a
The proper refrigerant charge is attained when subcooling hot water start such as startup commissioning
is measured at 10 - 15°F (5.6 - 8.3°C). Add charge as or a hot water start at the beginning of the day.
needed to increase subcooling and remove charge as It also assumes that 10 steps of loading are
necessary to reduce subcooling. Whenever removing available and programmed. If less than 10 steps
charge, be sure to recover it in an approved container. are available, no chiller response will take place
at some of the operating points described.
After the subcooling is set at 10 - 15°F (5.6 - 8.3°C) by
adding or removing charge and steady state fully loaded 1. For the system compressors to run, all Manual
operation is established, system superheat should also Reset Cutouts must be reset, the Flow Switch
be adjusted for 10 - 15°F (5.6 - 8.3°C). A factory recom- must be closed, the System Switches must be
mended superheat setting of 15°F (8.3°C) is appropriate ON, the Daily Schedule must be scheduling the
for systems that operate over a variety of ambient tem- chiller to run, and temperature demand must be
peratures, chilled liquid temperatures, and loading con- present.
ditions. It also compensates for gauge and temperature
sensor inaccuracy. When measuring superheat, be sure 2. As long as power is applied, the Crankcase Heat-
to insulate a thermometer or thermocouple attached to ers will be on and stay on as long as the com-
the piping to assure a true temperature is measured. pressors are not running.

The superheat is the difference between the actual tem- 3. If power has just been applied to the system, the
perature of the returned refrigerant gas entering the com- microprocessor will start a 2 minute timer. This is
pressor and the temperature corresponding to the suc- the same timer that prevents an instantaneous
tion pressure as shown in a standard pressure/tempera- start after a power failure.
ture chart. The suction temperature should be taken 6"
before the compressor service valve, and the suction pres- NOTE: Compressor Crankcase Heaters should
sure is taken at the compressor suction service valve. be on for a period of 24 hours prior to
commissioning. Failure to allow the
Example: heater sufficient time to warm the oil may
Suction Temperature 46°F (7.8°C) damage the compressor due to liquid re-
Minus Suction Pressure - 56 PSIG frigerant in the oil.
Converted to Temperature - 31°F (-0.6°C)
Superheat = 15°F (8.3°C) 4. At the end of the 2 minute timer, the micropro-
cessor will check for cooling demand as well as
Superheat SYS 1 ____, SYS 2 ____ check to see if any system safeties have been
exceeded. If all conditions allow for start, the lead
Normally, the thermal expansion valve need not be ad- compressor will start unloaded. Coincident with
justed in the field. If, however, an adjustment is to be the start, the programmable anti-recycle timer will
made, the expansion valve adjusting screw should be be set and begin counting downward to “0”. The
turned not more than one turn at a time, allowing suffi- liquid line solenoid of the compressor will open.
cient time (approximately 15 minutes) between adjust-
ments for the system and the thermal expansion valve
to respond and return to settled operation.

80 YORK INTERNATIONAL
FORM 150.60-NM5

5. After 4 seconds of run time, the motor current 15. After 7 minutes of run time, the lag compres-
of the lead compressor must be > 14% FLA and sor will load to its 2nd step of loading, if cooling
< 115% FLA. Oil pressure must be > 5 PSID (345 demand requires.
kPa). If these conditions are not met, the lead
compressor will shut down. 16. After 8 minutes of operation, the oil pressure
of the lag compressor must be > 25 PSID (172.4
6. After 30 seconds of run time, the oil pressure kPa) and the suction pressure must be > cutout .
of the lead compressor must be > 20 PSID (137.9 If these conditions are not met, the lag compres-
kPa) and the suction pressure must be > 50% of sor will shut down (temperature and rate control).
cutout. If these conditions are not met, the lead The lead compressor will load to its 3rd and final
compressor will shut down. step of loading, if cooling demand requires (tem-
perature and rate control). The lag compressor
7. After 1 minute of run time, the lead compres- remains unchanged at the 2nd step of loading.
sor will load the 1st step, if cooling demand (tem-
perature and rate control) requires. 17. After 9 minutes of run time, the lag compres-
sor will load its 3rd and final step, if cooling de-
8. After 2 minutes of run time, the lead compres- mand requires (temperature and rate control). The
sor will load the 2nd step, if cooling demand (tem- lead compressor remains unchanged at the 3rd
perature and rate control) requires. step of loading.

9. After 3 minutes of run time, the lead compres- OPERATING SEQUENCE UTILIZING
sor will load its 3rd step, if temperature demand LEAVING WATER CONTROL
(temperature and rate control) requires.
NOTE: The operating sequence described below relates
10. After 4 minutes of operation, the oil pressure to operation after power has been applied on a
of the lead compressor must be >25 PSID (172.4 hot water start such as at start-up commission-
kPa) and the suction pressure must be > cutout. ing or a hot water start up at the beginning of
If these conditions are not met, the lead com- the day. It also assumes that 10 steps of load-
pressor will shut down. If cooling demand requires ing are available and programmed. If less than
(temperature and rate control), the lag compres- 10 steps are available, no chiller response will
sor will start unloaded and its anti-recycle counter take place at some of the operating points de-
will begin counting back to “0”. The liquid line so- scribed.
lenoid will open. The lead compressor will unload
2 steps to its 1st step of 3 loading steps. 1. For the system compressors to run, all Manual
Reset Cut-outs must be reset, the Flow Switch
11. After 4 minutes and 4 seconds of run time, must be closed, any Remote Cycling Contracts
the motor current of the lag compressor must be must be closed, the System Switches must be
>14% FLA and < 115% FLA. Oil pressure must ON, the Daily Schedule must be scheduling the
be > 5 PSID (34.5 kPa). If these conditions are chiller to run, and temperature demand must be
not met, the lag compressor will shut down. present.

12. After 4 minutes and 30 seconds of run time, 2. As long as power is applied, the Crankcase Heat-
the oil pressure of the lag compressor must be ers will be on and stay on as long as the com-
>20 PSID (137.9 kPa) and the suction pressure pressors are not running.
must be > 50% cutout. If these conditions are not
met, the lag compressor will shut down. 3. If power has just been applied to the system, the
microprocessor will start a 2-minute timer. This is
13. After 5 minutes of run time, the lag compres- the same timer that prevents an instantaneous
sor will load to the 1st step of loading, if cooling start after a power failure. NOTE: Compressor
demand requires (temperature and rate control). Crankcase Heaters should be on for a period of
The lead compressor remains unchanged at the 24 hours prior to commissioning. Failure to allow
1st step of loading. the heater sufficient time to warm the oil may
damage the compressor due to liquid refrigerant
14. After 6 minutes of run time, the lead compres- in the oil.
sor will load to its 2nd step of loading, if cooling
demand requires (temperature and rate control). 4. At the end of the 2 minute timer, the micropro-
The lag compressor remains unchanged at the cessor will check for cooling demand as well as
1st step of loading. check to see if any system safeties have been

YORK INTERNATIONAL 81
exceeded. If all conditions allow for start, the lead 12. After 10 minutes and 4 seconds of run time,
compressor will start unloaded. Coincident with the motor current of the lag compressor must be
the start, the programmable anti-recycle timer will > 14% FLA and < 115% FLA. Oil pressure must
be set and begin counting downward to “0”. The be > 5 PSID (34.5 kPa). If these conditions are
liquid line solenoid of the lead compressor will not met, the lag compressor will shut down.
open.
13. After 10 minutes and 30 seconds of run time,
5. After 4 seconds of run time, the motor current the oil pressure of the lag compressor must be >
of the lead compressor must be > 14% FLA and 20 PSID (137.9 kPa) and the suction pressure
<115% FLA. Oil pressure must be > 5 PSID (34.5 must be > 50% cutout. If these conditions are not
kPa). If these conditions are not met, the lead met, the lag compressor will shut down.
compressor will shut down.
14. After 12 minutes and 30 seconds of run time,
6. After 30 seconds of run time, the oil pressure the lag compressor will load to the 1st step of
of the lead compressor must be > 20 PSID (137.9 loading, if cooling demand requires (temperature
kPa) and the suction pressure must be > 50% of and rate control). The lead compressor remains
cut-out. If these conditions are not met, the lead unchanged at the 1st step of loading.
compressor will shut down.
15. After 14 minutes of operation, the oil pressure
7. After 2 minutes and 30 seconds of run time, of the lag compressor must be > 25 PSID (172.4
the lead compressor will load the 1st step, if cool- kPa) and the suction pressure must be > cutout .
ing demand (temperature and rate control) re- If these conditions are not met, the lag compres-
quires. sor will shut down.

8. After 4 minutes of operation, the oil pressure 16. After 15 minutes of run time, the lead com-
of the lead compressor must be > 25 PSID (172.4 pressor will load to its 2nd step of loading, if cool-
kPa) and the suction pressure must be > cut-out. ing demand requires (temperature and rate con-
If these conditions are not met, the lead com- trol). The lag compressor remains unchanged at
pressor will shut down. the 1st step of loading.

9. After five minutes of run time, the lead com- 17. After 17 minutes and 30 seconds of run time,
pressor will load the second step, if cooling de- the lag compressor will load to its 2nd step of
mand (temperature and rate control) requires. loading, if cooling demand requires (temperature
and rate control). The lead compressor remain
10. After 7 minutes and 30 seconds of run time, unchanged at the 2nd step on loading.
the lead compressor will load its 3rd step, if tem-
perature demand (temperature and rate control) 18. After 20 minutes of run time, the lead com-
requires. pressor will load to its 3rd and final step of load-
ing, if cooling demand requires (temperature and
11. After 10 minutes of run time, if cooling demand rate control). The lag compressor remains un-
requires (temperature and rate control), the lag changed at the 2nd step of loading.
compressor will start unloaded and its anti-recycle
counter will begin counting back to “0”. The liquid 19. After 22 minutes and 30 seconds of run time,
line solenoid will open. The lead compressor will the lag compressor will load to its 3rd and final
unload two steps to its 1st step of 3 loading steps. step, if cooling demand requires (temperature and
rate control). The lead compressor remains un-
changed at the 3rd step of loading.

82 YORK INTERNATIONAL
FORM 150.60-NM5

PREVENTATIVE MAINTENANCE

It is the responsibility of the owner to provide the neces- for a reasonable length of operating time. Discolora-
sary daily, monthly and yearly maintenance requirements tion of the oil, either turning darker brown or in some
of the system. cases lighter, is an indication of contamination, ba-
sically due to moisture. If it is necessary to charge
oil refer to item #3 under the ANNUAL MAINTE-
NANCE section.
IMPORTANT
3. Check the refrigerant circuit for leaks.
If a system failure occurs due to improper main-
tenance during the warranty period; YORK will 4. Operating Pressures and Temperatures – Check to
not be liable for costs incurred to return the sys- see that operating pressures and temperatures are
tem to satisfactory operation. The following is in- within the LIMITATIONS shown in this book.
tended only as a guide and covers only the chiller
unit components. It does not cover other related ANNUAL MAINTENANCE
system components which may or may not be
furnished by YORK. System components should It is recommended that the following items be checked
be maintained according to the individual annually.
manufacturer’s recommendations as their opera-
tion will affect the operation and life of the chiller. 1. All items under WEEKLY MAINTENANCE.

2. Operating Controls – Check to see if controls are


set and operating within the proper limits. See Unit
DAILY MAINTENANCE Controls and OPERATION section of this book.

It is recommended that the following items be checked 3. Compressor Oil – Drain, inspect and refill with new
daily. oil. This requires pumping out the compressor. If
possible, this should be done after the unit has been
1. Oil Level – Correct oil level is when oil appears in in operation for some time, when the oil in the crank-
either of the compressor oil sight glasses after the case will contain the least amount of refrigerant. To
unit has been in operation for about two hours. If it is pump out the compressor, proceed as follows:
necessary to add oil after this operating period, see
item #3 under the ANNUAL MAINTENANCE sec- A. Close the suction stop valve.
tion.
B. Open the discharge stop valve two turns of the
2. Oil Pressure – Oil pressure should be a minimum of stem.
50 PSI (344.7 kPa) above suction pressure. Typical
pressure is 65 - 70 PSI (448.2 to 482.6 kPa). C. Operate the compressor until 15 to 20 inches
(381 to 508 mm) vacuum is obtained. Do this by
3. Compressor Superheat – Correct superheat is 10 - disconnecting the wiring to LLSV and repeat-
15°F (5.6 to 8.3°C) measured at the compressor. edly starting the compressor. Recycle 115VAC
power to the Logic Panel to reduce anti-recycle
4. Operating Pressures and Temperatures – Check to time to 2 minutes if needed. The compressor
see that operating pressures and temperatures are should in no case be operated under vacuum
within the LIMITATIONS shown in this book. conditions for longer than 10 to 15 seconds.

WEEKLY MAINTENANCE D. Stop the compressor and immediately close the


discharge stop valve. The procedures outlined
It is recommended that the following items be checked in steps (B) and (C) above should be repeated if
weekly. the suction pressure rises rapidly to 15 PSIG
(103.4 kPa) or more which would indicate con-
1. All items listed under DAILY MAINTENANCE. siderable refrigerant remaining in the crankcase
oil. Do not expect to retain 0 PSIG since some
2. Color of Compressor Oil – New oil is clear, and if the refrigerant will continually be released from the
system is not contaminated with moisture and/or oil in the crankcase.
foreign material, should retain its new appearance

YORK INTERNATIONAL 83
E. After pumping down the compressor, wait until I. Before opening the suction or discharge stop
the pressure builds up to 2 or 3 PSIG before valves, connect a vacuum pump to the pumpout
opening up any part of the hermetic compres- port in the discharge stop valve. (Pumpout port
sor. is port on valve stem side of valve). With the
vacuum line shutoff valve open, run the vacuum
F. Open the coil drain valve slowly and drain as pump until a vacuum of at least 1000 microns is
much oil from the compressor as possible. reached. Stop the vacuum pump, close the shut-
off valve and open the discharge valve fully be-
G. Examine the oil for any metal particles which fore disconnecting the line from the vacuum
would indicate wear on the bearings, crankshaft pump. Disconnect the vacuum pump and replace
or connecting rods. If metal particles are found, the plug in the pumpout port.
the need for closer examination by factory ser-
vice personnel is indicated. NOTE: If suction or discharge valves are not seated
properly, a 1000 micron vacuum can not be ob-
H. If the oil is clean and free of metal particles, refill tained. Do not evacuate for long periods of time.
the compressor with YORK oil “C”. To add oil or
to fill the compressor crankcase, connect the J. Be sure both discharge and suction stop valves
delivery tube of the YORK Hand Oil Pump. YORK are open before operating the unit.
Part No. 470-10654 or equal to the compressor
oil charging and drain valve. Expel all air from 4. Suction and Discharge Valves and Springs - The
the delivery tube by pumping it full of oil, allowing condition of the suction and discharge valves and
a few drips to drip out before tightening the flare springs should be checked by YORK service per-
nut to the oil charging valve. Then open the oil sonnel on a yearly basis or every 5000 hours, which-
charging valve and pump oil into the crankcase ever comes first.
to the proper level. It is necessary that the suc-
tion end of the hand oil pump be kept submerged
under the oil level in the container at all times, to
avoid entrance of air into the compressor.

84 YORK INTERNATIONAL
FORM 150.60-NM5

OPTIONS
This section is devoted to options which may be ordered or retrofitted to the unit. Listed below are the options which
are covered in this section.

1. HOT GAS BYPASS (LOADMINDER) OPTION


2. HIGH AMBIENT OPTION
3. LOCAL PRINTER OPTION
4. OPTIONAL TAMPERPROOF ENCLOSURE (WIRE GRILLE)
5. OPTIONAL DECORATIVE TAMPERPROOF ENCLOSURE (LOUVERED & WIRE GRILLE)
6. OPTIONAL DECORATIVE TAMPERPROOF ENCLOSURE (LOUVERED)
7. OPTIONAL TAMPERPROOF CONDENSER COIL ENCLOSURE (LOUVERED)
8. BAS INTERFACE OPTION (REMOTE RESET OPTION)

HOT GAS BYPASS (LOADMINDER) OPTION the control range and the micro turns the compressor
off. Details for setting the pressure regulator follow.
General
RWT Control Hot Gas Operation
The Hot Gas Bypass Option is available as a factory
installed option to prevent compressor cycling and water The hot gas solenoid is energized if the compressor is
temperature fluctuation at low load. This is accomplished on its minimum stage of loading and the return water
by providing further capacity reduction below the last step temperature falls below the following point:
of compressor cylinder unloading by introducing an arti-
ficial load to the cooler, which keeps the compressor on ULCR - CR + CR/20
the line. The option will provide hot gas bypass on both
compressors enabling hot gas to be active regardless of Where: UCLR = Upper Limit of Control Range
which compressor is in the lead. CR = Control Range Differential

NOTE: The microprocessor will only activate the hot gas Example: In a typical system that requires a 45°F
on the lead compressor. (7.2°C) leaving water temperature, we will
have a 10° (5.6°C) control range (CR) differ-
The hot gas bypass consists of a pilot operated regulat- ential which gives us an Upper Limit of Con-
ing valve with an integral solenoid. The pilot operated trol Range (ULCR) of 55°F (12.8°C). There-
solenoid is controlled by the microprocessor according fore, plugging the numbers into the formula:
to water temperature. The regulating valve which becomes
activated when the solenoid is energized, is controlled 55 - 10 + (10/20) = 45-1/2°F
by suction pressure to modulate the flow of gas in a (12.8 - 10 + [10/20] = 7.5°C)
bypass connected from the compressor discharge to the
cooler inlet. The following text will explain how the hot The hot gas solenoid will be activated at 45-1/2°F (7.5°C)
gas solenoid is activated by the microprocessor in both in the example above and hot gas may then be fed ac-
return and in leaving water control. cording to the suction pressure and the pressure regu-
lated valve setting. Once activated, the micro will keep
LWT Control Hot Gas Operation the solenoid energized until the return water temperature
rises above the temperature designated by the formula:
The hot gas solenoid is energized when the leaving wa-
ter temperature falls below the “Target” water tempera- ULCR - CR + CR/10
ture, if the compressor is on its minimum stage of load-
ing. Hot gas may then be fed according to the suction Where: UCLR = Upper Limit of Control Range
pressure and the pressure regulating valve setting. Once CR = Control Range Differential
activated, the micro will keep the solenoid energized until
Example: 55 - 10 + 10/10 = 46°F
the leaving water temperature rises above the high limit
(12.8 - 10 + 10/10 = 7.8°C)
of the Control Range or until the load becomes so low
that the hot gas can no longer keep temperature within
If temperature continues to drop while the Hot Gas is
energized, the Hot Gas will be de-energized when the
compressor cycles off on temperature.
YORK INTERNATIONAL 85
Procedure For Setting The Hot Gas Regulator Field Installation
(Ref. Fig. 27)
If it becomes necessary to field install the Hot Gas
1. If desired, set the control panel data to show suction (Loadminder) Option, kit # 375-21491-000 should be or-
pressure. dered.

2. Adjust the pilot power assembly adjustment screw


2 to approximately the middle of its adjustment HIGH AMBIENT OPTION
range.
The High Ambient Option consists of two kits, P/Ns 471-
3. The chiller must be running and stabilized on the 01232-131 and 475-19195-000. The option allows opera-
minimum stage capacity. In establishing this condi- tion of the chiller in ambients up to 115°F (46.1°C). Typi-
tion, it may be necessary to deactivate the regulator cally, standard operation is limited to 105°F (40.6°C).
by de-energizing the solenoid 1 . High ambient operation is accomplished by discharge
pressure unloading to assure that the chiller does not
4. Adjust the adjustment screw 2 in the clockwise fault due to the high pressure cutout opening during high
direction to open the valve at a higher pressure temperature operation. A sun shield is also installed on
(sooner) or in the counterclockwise direction to open the control panel to prevent direct sunlight from over-
the valve at a lower pressure (slower response). The heating the control panel causing subsequent malfunc-
valve is feeding when the valve outlet feels warm to tion of the electromechanical and electronic components
the touch. in the control panel. Additionally, actual discharge pres-
sure readouts can now be obtained from the micro panel.
The adjustment is correct when system suction pres-
sure rises to a point nearly equal to normal running Discharge Pressure unloading allows the microproces-
pressure at the midpoint in the “Control Zone”. sor to unload a compressor when the discharge pres-
sure approaches a point nearing the discharge pressure
5. Further minor adjustment may be necessary to be cutout. This assures that the system does not shut down
certain that the valve opens fully before the tempera- completely if the cutout were to open. See Page 42 for
ture point at which the compressor stops due to a programming the unloading pressure.
fall in Return or Leaving Water Temp.
Fan cycling by discharge pressure is also available when
6. Repeat this procedure on the other system. this option is installed (See DISCHARGE PRESSURE
READOUT OPTION this page), however it is of little use
NOTE: Hot gas should not be considered as an addi- in areas where ambients are generally high and stan-
tional step of unloading when programming the dard temperature control of the fans provides good con-
number of steps of loading/unloading. trol and maximum efficiency.

LD02099

FIG. 27 – PIPING DIAGRAM

86 YORK INTERNATIONAL
FORM 150.60-NM5

LOCAL PRINTER OPTION Installation Limitations

The Micro Panel is capable of supplying a printout of The following limitations must be adhered to. Failure to
chiller conditions or fault shutdown information at any do so may result in improper printer and/or chiller opera-
given time. This allows operator and service personnel tion.
to obtain data and system status with the touch of the
keypad. In addition to manual print selection, the micro 1. The printer option is adaptable to all versions and
panel will provide an automatic printout whenever a fault revisions of Microprocessor boards and EPROMs.
occurs. An explanation of the keypad use to obtain a No modifications are necessary to the panel.
print-out is discussed in the “PRINT” KEY Section on
Page 67. 2. Maximum cable length between the printer and the
Microprocessor Board is 25 feet (7.6 m). Twisted
YORK recommends the field tested WEIGH-TRONIX pair shielded cable is required.
IMP-24, Model 2600 printer. This is a compact low cost
printer that is ideal for service work and data logging. 3. The printer must be supplied a 115VAC source.
Paper is in the form of a compact roll and is easily handled
compared to larger printers using wider business form 4. The printer may be left connected to the micro panel.
style paper. The paper is 2.25" (5.7 cm) wide desk-top
calculator paper that can be easily and inexpensively YORK INTERNATIONAL CORPORATION
purchased at most stationery stores. Shown in Fig. 28 RECIPROCATING WATER CHILLERS
and 29 is the WEIGH-TRONIX printer and a typical sample
SYSTEM STATUS
printout. 8:45AM 4/17/98

SYS 1 COMPRESSOR RUNNING


The WEIGH-TRONIX IMP-24 Model 2600 printer can be SYS 2 ANTI-COIN TIMER 13 SEC
purchased for approximately $150.00. Contact Weigh-
Tronix for purchase information: RETURN WATER TEMP 65.0 DEGF
LEAVING WATER TEMP 54.0 DEGF
LOW WATER CUTOUT 36.0 DEGF
Weigh-Tronix SETPOINT TEMP 45.0 DEGF
OUTSIDE AIR TEMP 75.0 DEGF
2320 Airport Blvd. LOW AMBIENT CUTOUT 10.0 DEGF
LOW PRESSURE CUTOUT 4 4 PSIG
Santa Rosa, CA 95402 LEAD SYSTEM SYS 1
Phone: 1-800-358-9110 or 1-707-527-5555 CONTROL TYPE LCHWT
COOLING RANGE 45.0 TO 47.0 DEGF
(International Orders Only)
SYSTEM 1 DATA
NOTE: The print-out is made to be universal to all types
COMPRESSOR STATUS ON
of chillers both air and water cooled with or with- MOTOR AMPS 50 %FLA
out options. Items may be indicated on the print- SUCTION PRESSURE 61 PSIG
DISCHARGE PRESSURE 143 PSIG
out which may not be present on the chiller. OIL PRESSURE 75 PSID
LIQUID LINE SOLENOID OFF
RUN PERMISSIVE ON
STAGES OF LOADING 1
FORWARD FANS OFF
REVERSE FANS OFF
HOT GAS BYPASS VALVE OFF

SYSTEM 2 DATA

COMPRESSOR STATUS ON
MOTOR AMPS 0 %FLA
SUCTION PRESSURE 61 PSIG
DISCHARGE PRESSURE 80 PSIG
OIL PRESSURE 1 PSID
LIQUID LINE SOLENOID OFF
RUN PERMISSIVE ON
STAGES OF LOADING 1
FORWARD FANS 1
REVERSE FANS OFF
HOT GAS BYPASS VALVE OFF

S M T W T F S *=HOLIDAY
SUN START=06:00AM STOP=11:00AM
MON START=06:00AM STOP=11:00AM
TUE START=06:00AM STOP=11:00AM
WED START=06:00AM STOP=11:00AM
THU START=06:00AM STOP=11:00AM
FRI START=06:00AM STOP=11:00AM
SAT START=06:00AM STOP=11:00AM
23889A
HOL START=00:00AM STOP=00:00AM

FIG. 28 – WEIGH-TRONIX IMP-24 MODEL 2600


FIG. 29 – PRINTOUT
PRINTER
YORK INTERNATIONAL 87
Parts by the micro of current operating conditions. These con-
ditions will be stored in memory until they can be trans-
The following parts are required: mitted to the printer and printed. A sample printout is
shown in Fig. 19 on page 63.
1. Weigh-Tronix IMP-24, Model 2600 printer.
A printout of the fault shutdown history may be obtained
2. 2.25" (5.7 cm) wide desk top calculator paper. by pressing the HISTORY key. A printout showing the
last 3 faults with all system conditions at the time of the
3. 25 ft. (7.62 m) Twisted Pair Shielded Cable (mini- fault will be transmitted. A sample printout is shown in
mum 3 conductor), # 18 AWG Stranded, 300V min. Fig. 20 on page 64.
insulation.
An automatic printout will be sent to the printer when-
4. (1 ea.) 25pin Cannon connector and shell. Connec- ever the chiller shuts down on a fault, regardless of
tor: Cannon P/N DB-25P or equivalent. Shell: Can- whether the fault causes a system or the entire chiller to
non P/N DB-C2-J9. lockout or whether restart is permitted. This is the same
printout that is obtained when the OPER DATA Key is
Assembly and Wiring pressed, however it will be a snapshot of system operat-
ing conditions at the instant fault occurred. Additionally,
All components should be assembled and wired as fol- the Status indication that is noted in the printout will
lows in Fig. 30. Strip the outside insulation back several note the specific fault that occurred.
inches and individual wires about 3/8" (9.5 mm) to con-
nect the cable at the Micro Logic Board. Connect the Using Other Printers
shield of the cable as shown on the Micro Logic Board.
Do not connect at the printer end of the cable. Control codes vary from printer to printer. This will result
in unusual formatting of printed data from many printers.
Printer Configuration In addition, “handshaking” lines and “handshaking” se-
quence will differ between printers. This makes the equip-
2 Switches on the printer must be properly configured. ment susceptible to operation problems or mis-wiring
Remove the paper roll to access these switches. Place which may cause damage to the printer or the Micropro-
the switches in the following positions: cessor Board. YORK assumes no responsibility for as-
sistance or damage in the use of non-specified printers.
SW. 1 OFF
SW. 2 ON Warranty

Obtaining a Printout YORK assumes no warranty responsibility in the use of


the printer. This includes damages to the printer and the
A printout of current operating data may be obtained by Microprocessor Boards or chiller operation problems
pressing the OPER DATA key. A snapshot will be taken which may result.

LD02100

FIG. 30 – ASSEMBLY AND WIRING

88 YORK INTERNATIONAL
FORM 150.60-NM5

OPTIONAL TAMPEPROOF ENCLOSURE


(WIRE GRILLE)

General
2. All holes for mounting kit parts are provided in both
A wire grille tamperproof enclosure is available for the
the chiller frame and the added supports, therefore,
chiller for the prime purpose of deterring unauthorized
it should be unnecessary to drill holes.
access to components on the chiller.
3. Install grilles using the proper hardware and sup-
Kit 475-21467-000 is the tamperproof enclosure which
ports. Refer to Fig. 32 and the Parts List for place-
consists of weather resistant steel grilles as well as the
ment of the grilles and the proper hardware required.
necessary mounting hardware.
4. Notch grilles to suit water connection and wiring
Installation
harnesses as needed.
1. Refer to Fig. 31 and the associated parts list. Before
5. If the High Ambient Sunshield Kit or Disconnect
starting installation, all of the items in the kit should
Option is installed, field adaptation will be required
be identified by comparing with Fig. 32 and the as-
where parts of the kits interfere. Touch up exposed
sociated parts list.
metal parts to prevent rust.

27577A

FIG. 31 – COMPLETE GRILLE INSTALLATION


(Different unit shown)

YORK INTERNATIONAL 89
NOTES:
90

1. Notch grilles to suit water connections and wiring harnesses.


2. Discard hardware kit items 56, 59, and 60.
YORK INTERNATIONAL

LD02700

FIG. 32 – WIRE GRILLE INSTALLATION


FORM 150.60-NM5

OPTIONAL DECORATIVE TAMPEPROOF ENCLOSURE


(LOUVERED & WIRE GRILLE)

General
2. All holes for mounting kit parts are provided in both
A combination louvered and wire grille enclosure is avail- the chiller frame and the added supports, therefore,
able for the chiller for the prime purpose of deterring un- it should be unnecessary to drill holes.
authorized access to components of the chiller.
3. Install the louvered panels and wire grilles using the
Kit 475-21466-000 is a decorative/tamperproof enclosure proper hardware and supports. Refer to Fig. 37a,
which consists of a combination of louvered sheet metal 37b, 37c and the Parts List for placement of the
panels and weather resistant wire grilles along with mount- grilles/panels and the proper hardware required. Dis-
ing hardware. This kit has a further purpose of present- card existing grilles to attach the louvered panels
ing a pleasing appearance to the chiller when it is lo- where necessary.
cated in a highly visible area.
4. Notch grilles to suit water connection and wiring
Installation harnesses as needed.

1. Before starting installation, all of the items in the kit 5. If the High Ambient Sunshield Kit or Disconnect
should be identified by comparing with Fig. 33A and Option is installed, field adaptation will be required
33B and the associated parts lists. where parts of the kits interfere. Touch up exposed
metal parts to prevent rust.

YORK INTERNATIONAL 91
92
YORK INTERNATIONAL

NOTES: LD02701

1. Discard hardware kit items 55 - 57, 59 - 61, and 63.


2. Notch grilles to suit water connections and wiring harnesses.
3. Discard existing grilles to attach louver panels where necessary.

FIG. 33A – GRILLE AND LOUVER INSTALLATION (SIDES)


YORK INTERNATIONAL

LD02702

FORM 150.60-NM5
NOTES:
1. Discard hardware kit items 55 - 57, 59 - 61, and 63.
2. Notch grilles to suit water connections and wiring harnesses.
FIG. 33B – GRILLE AND LOUVER INSTALLATION (FRONT AND BACK) 3. Discard existing grilles to attach louver panels where necessary.
93
OPTIONAL DECORATIVE TAMPERPROOF ENCLOSURE
(LOUVERED)

General

A louvered tamperproof enclosure is available for the 2. All holes for mounting kit parts are provided in both
chiller for the prime purpose of deterring unauthorized the chiller frame and the added supports, therefore,
access to components of the chiller. it should be unnecessary to drill holes.

Kit 475-02834-000 is the decorative/tamperproof enclo- 3. Install the louvered panels using the proper hard-
sure which consists entirely of louvered sheet metal pan- ware and supports. Refer to Fig. 35A, 35B and the
els along with mounting hardware. This kit has a further Parts List for placement of the panels and the proper
purpose of presenting a pleasing appearance to the chiller hardware required. Discard existing grilles to attach
when it is located in a highly visible area. the louvered panels where necessary.

Installation 4. Notch panels to suit water connections and wiring


harnesses as needed.
1. Refer to Fig. 34 for a photo of the completed instal-
lation. Before starting installation, all of the items in 5. If the High Ambient Sunshield Kit or Disconnect
the kit should be identified by comparing with Figs. Option is installed, field adaptation will be required
35A, 35B and the associated parts lists. where parts of the kits interfere. Touch up exposed
metal parts to prevent rust.

28364A

FIG. 34 – COMPLETE LOUVER INSTALLATION


(Different unit shown)

94 YORK INTERNATIONAL
YORK INTERNATIONAL

LD02703

NOTES:
1. For standard units (with
cooler) discard items
9007, 9008, and neces-
sary hardware.

FORM 150.60-NM5
2. Discard hardware kit
items 55 - 63.
3. For single point wiring
option, discard items
9007, 9010, 9016, and
FIG. 35A – LOUVER INSTALLATION (SIDES) necessary hardware.
95
NOTES:
96

1. For standard units (with cooler) discard items 9007, 9008, and neces-
sary hardware.
2. Discard hardware kit items 55 - 63.
3. For single point wiring option, discard items 9007, 9010, 9016, and
necessary hardware.

LD02704
YORK INTERNATIONAL

FIG. 33B – GRILLE AND LOUVER INSTALLATION (FRONT AND BACK)


FORM 150.60-NM5

OPTIONAL TAMPERPROOF CONDENSER Installation


COIL ENCLOSURE (LOUVERED)
1. Before starting installation, all of the items in the kit
General should be identified by comparing with Fig. 36A, 36B
and the associated parts list.
A condenser coil tamperproof enclosure is available for
the chiller for the prime purpose of protecting the con- 2. All holes for mounting kit parts are provided in both
denser coils. the chiller frame and the added supports; therefore,
it should be unnecessary to drill holes.
Kit 475-23840-000 is the tamperproof enclosure which
consists of louvered sheet metal as well as the neces- 3. Install louvered panels using the proper hardware and
sary mounting hardware. supports. Refer to Fig. 36A and 36B and the Parts
List for placement of the panels and the proper hard-
ware required.

YORK INTERNATIONAL 97
98
YORK INTERNATIONAL

NOTES: LD02705

1. Discard existing grilles to attach louver panels where necessary.


2. Discard items 51 - 53, and 55 - 63 from hardware kit.

FIG. 36A – CONDENSER COIL LOUVER INSTALLATION (SIDES)


YORK INTERNATIONAL

LD02706

FORM 150.60-NM5
NOTES:
1. Discard existing grilles to attach louver panels where necessary.
FIG. 36B – CONDENSER COIL LOUVER INSTALLATION (BACK) 2. Discard items 51 - 53, and 55 - 63 from hardware kit.
99
REMOTE RESET OPTION 4 - 20mA

The Remote Reset Option allows resetting of the water Jumpers JU3 and JU5 must be IN. All other jumpers
temperature setpoint using a 0 - 10VDC input, a 4 - 20mA should be OUT. Program the REMOTE TEMP SETPOINT
input, or a dry contact. The electronic circuitry in the RANGE (page 72) for 40°F (4.4°C) which will allow a
option converts the signals mentioned above into pulse 20°F (11.1°C) offset with an input of 20mA. There will be
width modulated (PWM) signals which the microproces- no offset with an input of 4mA. The temperature will be
sor can understand. Whenever an offset is called for, the offset linearly according to the current (4 - 20mA) ap-
change may be noted by the user by pressing the RE- plied.
MOTE RESET TEMP/RANGE Key on the Keypad. All
refresh requirements normally associated with PWM in- The 4 - 20mA input signal should be connected to the +
puts will be automatically taken care of by the electron- and - terminals on the TB3 Terminal Block at the right
ics in the option. of the Microprocessor Board. Be sure polarity is correct.

It is important to note that the maximum offset, when CAUTION: THE 4 - 20mA INPUT SIGNAL WIRING
this option is installed, is 20°F (11.1°C). This is due to MUST NOT BE EARTH GROUNDED!
the electronic’s limitation of maximum 11 sec. pulse. If
an offset greater than 20°F (11.1°C) is required, a user Dry Contact
supplied PWM signal of up to 21 sec. is needed and the
Remote Reset Option cannot be installed. A dry contact may also be used to offset temperature.
This allows a single offset whenever the contact is closed.
The Remote Reset Option P/N 471-01232-181 consists The offset is determined by the adjustment of the R11
of a Remote Reset printed circuit board, a mounting potentiometer on the Remote Reset Board. Adjust the
bracket and associated wiring. Each of the 3 signal types potentiometer as needed to obtain the desired offset.
will require individual jumpering of the printed circuit board.
This will be discussed in the following text. Jumper JU1 must be IN. All other jumpers must be OUT.
Program the REMOTE RESET TEMP SETPOINT
0 - 10VDC RANGE (page 72) for 40°F (4.4°C) which will allow the
R11 pot to be adjusted for an offset of as much as 20°F
Jumpers JU2 and JU4 must be IN. All other jumpers (11.1°C) when the contact is closed.
should be OUT. Program the REMOTE TEMP SETPOINT
RANGE (page 72) for 40°F (4.4°C) which will allow a The dry contact should be connected directly to the P1-
20°F (11.1°C) offset with an input of 10VDC. The tem- 1 (J1-1) and P1-2 (J1-2) terminals on the Remote Reset
perature will be offset linearly according to the voltage (0 Board (Fig. 41).
- 10VDC) applied.
NOTE: The coil of the controls used for reset must be
The 0 - 10VDC signal should be connected to the + and suppressed. Use YORK P/N 031-00808-000 sup-
- terminals on the TB3 Terminal Block at the right of the pressor.
Microprocessor Board. Be sure polarity is correct. The Remote Setpoint Reset will not operate
when a Remote Control Center Option is con-
CAUTION: THE 0 - 10VDC INPUT SIGNAL WIRING nected to the Micropanel. The Remote Con-
MUST NOT BE EARTH GROUNDED! trol Center will always determine the setpoint.

100 YORK INTERNATIONAL


FORM 150.60-NM5

LD02707

FIG. 37 – REMOTE RESET BOARD

YORK INTERNATIONAL 101


TROUBLESHOOTING CHART
PROBLEM CAUSE SOLUTION
No display on panel 1. No 115VAC to 2T. 1. Checking wiring and fuses (1 FU and 2
Unit will not operate FU). Check emergency stop contacts
5 to 1 .

2. No 24VAC to Power Supply Board. 2. Check wiring 2T to Power Supply Board.


3. 2T defective, no 24VAC output. 3. Replace 2T.
4. No +12V output from Power Supply 4. Replace Power Supply Board or isolate
Board excessive load on the board.
Contact YORK Service Before Replacing Circuit Boards!

“NO RUN PERM” 1. No Flow 1. Check chilled liquid flow.


2. Flow switch installed improperly. 2. Check that flow switch is installed
according to manufacturer’s instructions.
3. Defective flow switch. 3. Replace flow switch.
4. Remote cycling device open. 4. Check cycling devices connected to
terminals 13 & 14 of the TB3 Terminal
Block.
5. “System” switch in the OFF position 5. Place switches to the ON position.

“MOTOR CURRENT” CONTACTOR DOES NOT ENERGIZE


FAULT 1. External high pressure 1. Check external high pressure switch, fan
switch tripped. operation, and discharge pressure stored
in memory. Air flow from fans must be up.
2. External motor protector tripped. 2. Check for defective External motor
protector, wiring and motor problems. As-
sure that motor protector is not tripped due
Motor contactor may to external high pressure switch.
or may not energize 3. Defective relay output board. 3. Replace relay output board.
CONTACTOR ENERGIZES
1. Improper system high voltage. 1. Check system high voltage supply.
2. Defective contactor contacts 2. Check contacts and contactors.
and contactor.
3. Faulty high voltage wiring. 3. Check wiring.
4. High motor current stored in memory.4. Loose calibration resistors in J9 (SYS 1)
or J10 (SYS 2) of power supply board.
5. Defective current transformer (CT). 5. CT resistance 42-44Ω.
Contact YORK Service Before Replacing Circuit Boards or C.T.s!

“LOW OIL PRESS” 1. Low oil charge. 1. Oil level should be visible in either sight
FAULT glass at all times. Add YORK “C” oil if
necessary.
2. Too much refrigerant-in oil, partic- 2. Check crankcase oil heater operation.
ularly on start-up. (350 Watt heater should be “ON” when
unit is “OFF”. Measure heater current.
(Should be min. 2 amps.)
3. Liquid Line Solenoid Valve (LLSV) 3. Check wiring and LLSV.
not operating.
4. Suction Press. Transducer or wiring 4. Compare display to a gauge (SYS OFF).
defective. Replace defective component.
5. Oil Press. Transducer or wiring 5. Compare suction and oil gauges to display.
defective. Replace defective component.

102 YORK INTERNATIONAL


FORM 150.60-NM5

PROBLEM CAUSE SOLUTION


“Low Suction” Fault 1. Improper Suction Pressure Cut-out 1. Adjust per recommended settings and
adjustment. restart unit.
2. Low refrig. charge. 2. Repair leak / add refrigerant.
3. Fouled filter drier. 3. Change drier core.
4. Thermal expansion valve adjust- 4. Adjust compressor suction superheat to
ment / failure. 11°F (6.1°C) or replace power element
(or valve).
5. Reduced flow of chilled liquid 5. Check GPM (See OPERATING LIMIT-
through cooler. ATIONS) Check operation of pump.
Clean pump strainer, purge chilled liquid
system of air.
6. Defective suction press. transducer. 6. Replace transducer.
7. Fouled compressor suction strainer. 7. Remove and clean strainer.
8. Faulty wiring to transducer. 8. Check wiring.

“High Dsch” Fault 1. Condenser fans not operating or 1. Check fans, fuses, and contactors.
Cuts out on High Dis- rotating backwards.
charge Pressure as 2. Too much refrigerant. 2. Remove refrigerant.
sensed by Micropro- 3. Air in Refrigerant System. 3. Evacuate and recharge.
cessor via high dis- 4. Defective discharge pressure 4. Replace discharge pressure transducer.
charge pressure transducer.
transducer. 5. Assure Programmable H.P. Cut-out 5. Adjust per recommended settings and
is correctly set. restart unit.
NOTE: If external H.P. 6. Assure OAT sensor is reading 6. Place a thermometer next to the sensor
Cut-out Switch opens, properly. and compare reading to the display. Op-
a “Motor Current” Fault eration should not suffer if thermometer
will result. is +/– 10°F (5.6°C).

“Chiller Fault: High 1. Temperature sensed incorrectly 1. Verify actual ambient temperature at probe
Ambient Temp” by thermistor. +/– 10°F (5.6°C) with a thermometer placed
Cuts out on high ambi- next to the OAT sensor.
ent temperature. 2. Fans rotating backwards. 2. Air flow must be up. Correct fan rotation.
(Max. = 130°F (54.4°C) 3. Air flow to unit restricted (or being 3. Check installation clearances.
will restart automatically re-circulated). (See pages 10 and 11).
if temperature drops 4. High ambient cut-out set too low. 4. Reprogram cut-out.
below 128°F [53.3°C]).

“Chiller Fault: Low 1. Temperature of outside air is below 1. No problem exists.


Ambient Temp” cut-out setting.
Cuts out on low 2. Temperature sensed incorrectly by 2. Verify actual ambient temperature imme-
ambient temperature. thermistor. diately at probe with thermometer.
(25°F [-3.9°C] min. for 3. Check low ambient temperature 3. Adjust if necessary.
std. adjustable for low Cut-out setting on the display. NOTE: For occasional operation below
ambient unit) 0°F (-17.8°C) , set the cut-out at 0°F
NOTE: Operation below (-17.8°C) chiler is then allowed to operate
25°F (-3.9°C) requires regardless of temperature. A low ambient
low ambient accessory. kit must be installed.

“Chiller Fault: Low 1. RWT Control ONLY: Control range 1. Flow is lower than design. Increase flow or
Water Temp” is too small and does not match increase the control range to match actual
actual ∆T across evaporator under evaporator ∆T.
Low water temperature full load conditions.
shutdown 2. Check LWT cut-out point on panel. 2. Adjust if necessary, and restart unit.
(See page 45).

YORK INTERNATIONAL 103


PROBLEM CAUSE SOLUTION
“Chiller Fault: Low 3. Defective LWT or RWT sensor. 3. Check according to following table (use
Water Temp” (Assure the sensor is properly in- digital volt meter)*. Replace if necessary.
(Cont’d) stalled in the bottom of the well
with a generous amount of heat TEMP. VOLTAGE (DC)
conductive compound. 20.0°F 1.65
NOTE: It is not unusual to find up 22.0°F 1.71
to a +/–2°F difference between the 25.0°F 1.82
display and a thermometer located 27.0°F 1.88
in water piping. 30.0°F 1.99
33.0°F 2.09
36.0°F 2.22
38.0°F 2.28
41.0°F 2.37
43.0°F 2.43
46.0°F 2.54
48.0°F 2.60
50.0°F 2.67
53.0°F 2.77
55.0°F 2.83
57.0°F 2.89
59.0°F 2.95
61.0°F 3.02
63.0°F 3.08
65.0°F 3.14
67.0°F 3.20
70.0°F 3.28
* Check voltage on Microprocessor Board.
LWT: J11-7 to J11-1
RWT: J11-8 to J11-1

Low Compressor Oil 1. Low oil charge. 1. Oil level should be visible in either sight
Level glass at all times. Add YORK “C” oil if
(Particularly at necessary.
start-up) 2. Excessive flood back of liquid 2. Adjust Thermal Expansion Valve (TXV) or
refrigerant. replace power element. Check TXV bulb
location. Should be located on suction line
at least 8" - 10" from nearest elbow. Bulb
should be at 4 o’clock or 8 o’clock position,
have good contact with suction line and be
well insulated.

Crankcase Heater 1. Open at 115VAC wiring to heater. 1. Check wiring.


won’t Energize 2. Defective heater. 2. Replace heater.
(Should energize any- 3. Auxiliary contacts of compressor 3. Replace contactor.
time unit is “OFF”) contactor defective.
(Min. current draw = 2
amps)

Compressor won’t 1. Suction pressure > programmed un- 1. Excessive load. Check OPERATING LIMI-
load load point or operating limitations TATIONS. Check programmed unloading
(Solenoid valve de- have been exceeded. point.
energizes to load 2. Discharge pressure > programmed 2. Check OPERATING LIMITATIONS.
compressor) unload point or operating limitations Check programmed unloading point.
have been exceeded.
3. Demand not great enough. 3. OK. Become familiar with control operation.
4. Defective loading solenoid. 4. Replace compressor loading solenoid.

104 YORK INTERNATIONAL


FORM 150.60-NM5

PROBLEM CAUSE SOLUTION


Compressor won’t 5. Faulty wiring to loading solenoid. 5. Check wiring.
load 6. Defective water temperature sensor. 6. Compare sensor with a thermometer. Var-
(Cont’d) iation of sensor vs. thermometer of +/–2°F
is not unusual. Replace if necessary.
7. Defective evaporator or optional 7. Replace transducer after verifying with a
discharge transducer. gauge.

Lack of Cooling 1. Fouled evaporator surface. 1. Contact the local YORK service represen-
Effect tative.
2. Faulty compressor suction and / or 2. Contact the local YORK service represen-
charge valves. tative.

YORK INTERNATIONAL 105


TEMPERATURE CONVERSION TABLES
The numbers in bold-face type in the center column refer to the temperature, either in Centigrade or Fahrenheit, which is to
be converted to the other scale. Converting Fahrenheit to Centigrade the equivalent temperature will be found in the left
column. If converting Centigrade to Fahrenheit, the equivalent temperature will be found in the column on the right.
TEMPERATURE TEMPERATURE TEMPERATURE TEMPERATURE
°C °C or °F °F °C °C or °F °F °C °C or °F °F °C °C or °F °F
-40.0 -40 -40.0 -6.7 +20 +68.0 +26.7 +80 +176.0 +60.0 +140 +284.0
-39.4 -39 -38.2 -6.1 +21 +69.8 +27.2 +81 +177.8 +60.6 +141 +285.8
-38.9 -38 -36.4 -5.5 +22 +71.6 +27.8 +82 +179.6 +61.1 +142 +287.6
-38.3 -37 -34.6 -5.0 +23 +73.4 +28.3 +83 +181.4 +61.7 +143 +289.4
-37.8 -36 -32.8 -4.4 +24 +75.2 +28.9 +84 +183.2 +62.2 +144 +291.2
-37.2 -35 -31.0 -3.9 +25 +77.0 +29.4 +85 +185.0 +62.8 +145 +293.0
-36.7 -34 -29.2 -3.3 +26 +78.8 +30.0 +86 +186.8 +63.3 +146 +294.8
-36.1 -33 -27.4 -2.8 +27 +80.6 +30.6 +87 +188.6 +63.9 +147 +296.6
-35.6 -32 -25.6 -2.2 +28 +82.4 +31.1 +88 +190.4 +64.4 +148 +298.4
-35.0 -31 -23.8 -1.7 +29 +84.2 +31.7 +89 +192.2 +65.0 +149 +300.2
-34.4 -30 -22.0 -1.1 +30 +86.0 +32.2 +90 +194.0 +65.6 +150 +302.0
-33.9 -29 -20.2 -0.6 +31 +87.8 +32.8 +91 +195.8 +66.1 +151 +303.8
-33.3 -28 -18.4 0.0 +32 +89.6 +33.3 +92 +197.6 +66.7 +152 +305.6
-32.8 -27 -16.6 +.6 +33 +91.4 +33.9 +93 +199.4 +67.2 +153 +307.4
-32.2 -26 -14.8 +1.1 +34 +93.2 +34.4 +94 +201.2 +67.8 +154 +309.2
-31.7 -25 -13.0 +1.7 +35 +95.0 +35.0 +95 +203.0 +68.3 +155 +311.0
-31.1 -24 -11.2 +2.2 +36 +96.8 +35.6 +96 +204.8 +68.9 +156 +312.8
-30.6 -23 -9.4 +2.8 +37 +98.6 +36.1 +97 +206.6 +69.4 +157 +314.6
-30.0 -22 -7.6 +3.3 +38 +100.4 +36.7 +98 +208.4 +70.0 +158 +316.4
-29.4 -21 -5.8 +3.9 +39 +102.2 +37.2 +99 +210.2 +70.6 +159 +318.2
-28.9 -20 -4.0 +4.4 +40 +104.0 +37.8 +100 +212.0 +71.1 +160 +320.0
-28.3 -19 -2.2 +5.0 +41 +105.8 +38.3 +101 +213.8 +71.7 +161 +321.8
-27.8 -18 -0.4 +5.5 +42 +107.6 +38.9 +102 +215.6 +72.2 +162 +323.6
-27.2 -17 +1.4 +6.1 +43 +109.4 +39.4 +103 +217.4 +72.8 +163 +325.4
-26.7 -16 +3.2 +6.7 +44 +111.2 +40.0 +104 +219.2 +73.3 +164 +327.2
-26.1 -15 +5.0 +7.2 +45 +113.0 +40.6 +105 +221.0 +73.9 +165 +329.0
-25.6 -14 +6.8 +7.8 +46 +114.8 +41.1 +106 +222.8 +74.4 +166 +330.8
-25.0 -13 +8.6 +8.3 +47 +116.6 +41.7 +107 +224.6 +75.0 +167 +332.6
-24.4 -12 +10.4 +8.9 +48 +118.4 +42.2 +108 +226.4 +75.6 +168 +334.4
-23.9 -11 +12.2 +9.4 +49 +120.2 +42.8 +109 +228.2 +76.1 +169 +336.2
-23.3 -10 +14.0 +10.0 +50 +122.0 +43.3 +110 +230.0 +76.7 +170 +338.0
-22.8 -9 +15.8 +10.6 +51 +123.8 +43.9 +111 +231.8 +77.2 +171 +339.8
-22.2 -8 +17.6 +11.1 +52 +125.6 +44.4 +112 +233.6 +77.8 +172 +341.6
-21.7 -7 +19.4 +11.7 +53 +127.4 +45.0 +113 +235.4 +78.3 +173 +343.4
-21.1 -6 +21.2 +12.2 +54 +129.2 +45.6 +114 +237.2 +78.9 +174 +345.2
-20.6 -5 +23.0 +12.8 +55 +131.0 +46.1 +115 +239.0 +79.4 +175 +347.0
-20.0 -4 +24.8 +13.3 +56 +132.8 +46.7 +116 +240.8 +80.0 +176 +348.8
-19.4 -3 +26.6 +13.9 +57 +134.6 +47.2 +117 +242.6 +80.6 +177 +350.6
-18.9 -2 +28.4 +14.4 +58 +136.4 +47.8 +118 +244.4 +81.1 +178 +352.4
-18.3 -1 +30.2 +15.0 +59 +138.2 +48.3 +119 +246.2 +81.7 +179 +354.2
-17.8 0 +32.0 +15.6 +60 +140.0 +48.9 +120 +248.0 +82.2 +180 +356.0
-17.2 +1 +33.8 +16.1 +61 +141.8 +49.4 +121 +249.8 +82.8 +181 +357.8
-16.7 +2 +35.6 +16.7 +62 +143.6 +50.0 +122 +251.6 +83.3 +182 +359.6
-16.1 +3 +37.4 +17.2 +63 +145.4 +50.6 +123 +253.4 +83.9 +183 +361.4
-15.6 +4 +39.2 +17.8 +64 +147.2 +51.1 +124 +255.2 +84.4 +184 +363.2
-15.0 +5 +41.0 +18.3 +65 +149.0 +51.7 +125 +257.0 +85.0 +185 +365.0
-14.4 +6 +42.8 +18.9 +66 +150.8 +52.2 +126 +258.8 +85.6 +186 +366.8
-13.9 +7 +44.6 +19.4 +67 +152.6 +52.8 +127 +260.6 +86.1 +187 +368.6
-13.3 +8 +46.4 +20.0 +68 +154.4 +53.3 +128 +262.4 +86.7 +188 +370.4
-12.8 +9 +48.2 +20.6 +69 +156.2 +53.9 +129 +264.2 +87.2 +189 +372.2
-12.2 +10 +50.0 +21.1 +70 +158.0 +54.4 +130 +266.0 +87.8 +190 +374.0
-11.7 +11 +51.8 +21.7 +71 +159.8 +55.0 +131 +267.8 +88.3 +191 +375.8
-11.1 +12 +53.6 +22.2 +72 +161.6 +55.6 +132 +269.6 +88.9 +192 +377.6
-10.6 +13 +55.4 +22.8 +73 +163.4 +56.1 +133 +271.4 +89.4 +193 +379.4
-10.0 +14 +57.2 +23.3 +74 +165.2 +56.7 +134 +273.2 +90.0 +194 +381.2
-9.4 +15 +59.0 +23.9 +75 +167.0 +57.2 +135 +275.0 +90.6 +195 +383.0
-8.9 +16 +60.8 +24.4 +76 +168.8 +57.8 +136 +276.8 +91.1 +196 +384.8
-8.3 +17 +62.6 +25.0 +77 +170.6 +58.3 +137 +278.6 +91.7 +197 +386.6
-7.8 +18 +64.4 +25.6 +78 +172.4 +58.9 +138 +280.4 +92.2 +198 +388.4
-7.2 +19 +66.2 +26.1 +79 +174.2 +59.4 +139 +282.2 +92.8 +199 +390.2

106 YORK INTERNATIONAL


FORM 150.60-NM5

YORK INTERNATIONAL 107


Proud Sponsor
of the 1998
U.S. Olympic Team

36USC380

P.O. Box 1592, York, Pennsylvania USA 17405-1592 Subject to change without notice. Printed in USA
Copyright © by York International Corporation 1998 ALL RIGHTS RESERVED

Form 150.60-NM5 (298)


Supersedes: 150.60-NM3 in ERR only.

You might also like