LIST OF 230 KV SWICHYARD ELECTRICAL EQUIPMENT AND ACCESSORIES

A. OUTDOOR EQUIPMENT

QTY UNIT DESCRIPTION

1. 04 Units 230 KV SF6 Circuit Breaker, outdoor type, overhead line bushing termination
Model : 242PA40
Maker : ABB
Max. voltage : 242 KV, Continuous rated current : 2000 A, Short circuit
current : 40 KA, Basic impulse level : 900 KV, Frequency : 60 Hz
3 Poles, Dead tank type, Motorized operated mechanism, motor voltage :125 Vdc
Year of service : about 8 years

2. 02 Sets 230 KV SF6 Circuit Breaker, outdoor type, overhead line bushing termination
(R,Y&B/set) Type : LW10E-245 SF6 Circuit Breaker
Maker : Pingdingshan Tian Ying High Voltage Switchgear Co. Ltd. in China
Max. voltage : 245 KV, Continuous rated current : 3150 A, Short circuit current :
50 KA, Basic Impulse level : 1050 KV, Frequency : 60 Hz
3 Single pole, Non-ganged motorized operated mechanism, Live type, Coil
control voltage : 110 Vdc
Year of service : about 2 years

3. 03 Units 230 KV Center Break Disconnector, outdoor type


Type : SSB -11-245
Maker : HAPAM
Max. voltage : 245 KV, Continuous rated current : 2000 A, Basic impulse level :
1050 KV, Frequency : 60 Hz
3 Poles, Ganged operated mechanism, Motor voltage : 125 Vdc
Year of service : about 8 years

4. 02 Units 230 KV Disconnector with earthing switch , outdoor type


Type : SSB -11-AM-245
Maker : HAPAM
Max. voltage : 245 KV, Continuous rated current : 2000 A, Basic impulse level :
1050 KV, Frequency : 60 Hz
3 Poles, Ganged operated mechanism, Motor voltage : 125 Vdc
Year of service : about 8 years

5. 02 Units 230 KV Disconnector with earthing switch, outdoor type


Model : GW4A-245D
Maker : Pingdingshan Tian Ying High Volage Switchgear co. Ltd. in China
Rated voltage : 245 KV, Continuous rated current : 1600 A, Frequency : 60 Hz
Rated short time withstand current : 40 KA
Dual post, Rotating horizontal break mechanism
Year of service : about 2 years

6. 03 Units 13.8/230 KV Power Transformer, outdoor type


Maker : ABB Powertech
Rated capacity : 37.5 MVA, ONAF-37.5 MVA, ONAN-22.5 MVA, 3 phase,
60 Hz, Tap changer : Off circuit, Tap range : +7.5% / -2.5%
Victor group : Ynd1
Insulation class : High voltage side-900 KV, Low voltage side-110 KV
Page 2 of 5

Termination : Overhead line bushing termination


Year of service : 2 years

7. 02 Units 13.8/230 KV Power Transformer, outdoor type


Maker : Meiden in Japan
Rated capacity : 63.5 MVA, ONAF-63.5 MVA, ONAN-47.6 MVA, 3 phase,
60 Hz, Tap changer : Off circuit, Tap range : +7.5% / -2.5%
Vector group : Ynd1
Insulation class : High voltage side-1050 KV, Low voltage side-110 KV
Termination : Overhead line bushing termination
Year of service : about 2 years

8. 06 Sets 230 KV Surge Arrester with surge counter


(R,Y&B/set) Maker : Nanyang Jin Koon Electric in China
Model : Y10W series
Termination : Overhead line bushing termination
Year of service : about 2 years

9. 02 Sets Capacitive Voltage Transformer


(R,Y,&B/set) Maker : Trench Electric
Type : TEMF 230HH
BIL : 1050 KV
VT ratio : 230 KV/115 V, Burden : 275 VA
Termination : Overhead line bushing termination
Year of service : about 2 years

10. 03 Sets Post Type Current Transformer, 230 KV


(R,Y&B/set) Maker : Trench Electric
Type : OSKF 1050 TH6, BIL : 1050 KV
Creepage distance : Not less than 21.5 mm/KV
CT ratio : 600 A/ 5 A, Burden-20 VA, 5P10, Metering accuracy 100 VA, cl. 0.1
Termination : Overhead line bushing termination
Year of service : about 2 years

11. 11 Each 230 KV Post Insulator, porcelain

12. 04 Each Marshalling Kiosk Panelboard, outdoor type

13. 05 Sets 13.8 KV Cable Gantry Tower

14. 04 Sets 230 KV Bus Bar Cable Gantry Tower

15. 21 Sets 230 KV Disk Suspension Insulator, porcelain

16. 10 Each 220 V Floodlighting


B. SWITCHYARD CONTROL ROOM

QTY UNIT DESCRIPTION

17. 61 Each Industrial Free Maintenance Battery


Battery voltage – 2 Vdc
Maker – ENERSYS in Brazil
Page 3 of 5

Type – NVRA
Total voltage – 122 Vdc
Capacity – 350 AH for 10 H

18. 18 Each Industrial Free Maintenance Battery


Battery voltage – 12 Vdc
Maker – ENERSYS in Brazil
Type – DM 90-12
Total voltage – 216 Vdc
Capacity – 90 AH for 20 H

19. 01 Unit 220 Vdc Battery Charger


Maker – ADELCO in Brazil
Supply voltage – 230 Vac
Phase – 3
Freq. – 60 Hz
Power – 10 KVA
Current – 25 A
Output voltage – 220 Vdc
Nominal charging current – 30 A

20. 01 Unit 125 Vdc Load Voltage Compensator (USA)


Maker – Nife Gem Assembly
Model – EJ1201-16

21. 02 Units 125 Vdc Battery Charger (USA)


Maker – Nife
Model – SCB-310F-130-150
Input voltage – 230 Vac
Phase – 3
Freq. – 60 Hz
Current – 82 A
Output voltage – 130 Vdc
Charging current – 150 A

22. 02 Units Dry Type Transformer


Maker – Niagara
KVA – 150, HV – 480 Vac Delta, LV – 230 Vac Wye/133 Vac
Imp. – 3.9 %, Ins. Class – 220 deg. C, Nema 1enclosure type
Date manufactured – 07/1993

23. 03 Units Panelboard for Transformer Protection ( Transformer 1, 2 & 3 )


consist of : 1 ea. – Differential Protection Relay (Main) with test block by ABB
1 ea. – Restricted Earth Fault Relay with test block by ABB
1 ea. – Trip/Lock-out Relay by ABB
2 ea. – OC/EF Relay (230 KV) with test block by ABB
1 ea. – Neutral OC Relay (Back-up) with test block by ABB
1 ea. – OC Relay for 13.8 KV (back-up) with test block by ABB
1 ea. – Differential Protection Relay (Back-up) with test block , ABB

24. 01 Unit Panelboard for Line Protection


consist of : 1 ea. – Line Differential Protection Relay (Main) with test block
by ABB
1 ea. – Trip/Lock-out Relay (Line Protection) by ABB
Page 4 of 5

2 ea. – Directional OC Relay (Main/Back-up) with test block, ABB


2 ea. – Directional EF Relay (Main/Back-up) with test block by ABB

25. 01 Unit Panelboard for Bus Bar & Breaker Failure Protection
consist of : 1 ea. – Bus Bar Differential Protection Relay with test block by ABB
1 ea. – Breaker Failure Relay D1 with test block by ABB
1 ea. – Breaker Failure Relay D2 with test block by ABB
1 ea. – Breaker Failure Relay D3 with test block by ABB
1 ea. – Breaker Failure Relay D4 with test block by ABB

26. 01 Unit Panelboard for Monitoring System of 230 KV Transformer 1 & 2


consist of : 2 ea. – MW Meter (0-40 MW)
2 ea. – MVAR Meter (0-20 MVAR)
2 ea. – Ammeter (0-150 A)
2 ea. – Digital Meter (MGE) by ABB
1 ea. – Annunciator (SACO 16 D2) by ABB

27. 01 Unit Panelboard for Monitoring System of 230 KV Transformer 3 & 230 KV Line
consist of : 2 ea. – MW Meter (0-40 MW) & (0-200 MW)
2 ea. – MVAR Meter (0-20 MW) & (0-200 MVAR)
2 ea. – Ammeter (0-150 A) & (0-600 A)
1 ea. – KV Meter (0-300 KV)
1 ea. – HZ Meter (55-65)
1 ea. – Digital Meter (MGE) by ABB

28. 02 Units Panelboard for Transformer D5 & D6 Incomer Protection Relays


consist of : 1 ea. – Transformer Differential Protection Relay with test block
by Reyrolle Protection
1 ea. – OC & EF Relay with test block by Rerolle Protection
1 ea. - Tripp Cct. Supervision Protection (Main) with test block
by Reyrolle Protection
1 ea. - Tripp Cct. Supervision Protection (Back-up) with test block
by Reyrolle Protection
1 ea. – Circuit Breaker Fail Protection with test block by Rerolle
1 ea. – Stand-by Earth Fault Protection by Rerolle Protection
1 ea. – Master Trip Protection (Main) with test block by EE
1 ea. – Master Trip Protection (Back-up) with test block by EE

29. 01 Unit Panelboard for Monitoring system of D5 & D6 Transformer 230 KV Metering
consist of : 2 ea. – Ammeter (0-400 A)
2 ea. – MW Meter (0-75 MW)
2 ea. - MVAR Meter (0-75 MVAR)
1 ea. – Annunciator Panel by PANALARM
2 ea. – Digital Meter (MGE) by ABB

30. 01 Unit Panelboard for Conversor CC/CC, CDC 125/24


consist of : 1 ea. – MW Meter (0-150 MW) , not in use
1 ea. – HZ Meter (55-65 HZ) , not in use
1 ea. – MVAR Meter (0-150 MVAR) , not in use
1 ea. – Ammeter (0-800 A) , not in use
1 ea. – KV Meter (0-150 KV) , not in use
1 ea. – Conversor CC/CC, CDC 125/24 by ADELCO in Brazil

31. 01 Unit Panelboard for Protection Relays (Not in use)


Page 5 of 5

consist of : 1ea. --Distance Protection Relay with 2 test block by GEC Alsthom
1 ea. – Directional OC & EF Protection Relay with test block
by Rerolle Protection
1 ea. – Under/Over Frequency Relay by EE

1 ea. – Trip Cct. Supervision Protection (Main) with test block


by Rerolle Protection
1 ea. - Trip Cct. Supervision Protection (Back-up) with test block
by Rerolle Protection
1 ea. – Busbar Zone Protection with test block by Rerolle Protection
1 ea. – Under/Over Voltage Protection with test block by EE
1 ea. – Master Trip Protection (Main) by EE
1 ea. – Master Trip Protection (Back-up) by EE
1 ea. -- Circuit Breaker Fail Protection with test block by Rerolle

32. 01 Unit AC Main Distribution Board (480 Vac)


consist of : 3 ea. – Voltmeter (0-600 Vac)
4 ea. – ACB (400 A/ 600 V/ 3 Pole) by ABB
2 ea. – ACB (80 A/ 600 V/ 3 Pole) by ABB
3 ea. – ACB (20 A/ 600 V/ 3 Pole) by ABB

33. 01 Unit AC Main Distribution Board (230 Vac)


consist of : 2 ea. – Voltmeter (0-250 Vac) by ABB
2 ea. – Ammeter (0-400 A) by ABB
3 ea. – ACB (100 A / 600 V / 3 pole) by ABB
3 ea. – ACB (80 A / 600 V / 3 pole) by ABB
7 ea. – ACB (32 A / 600 V / 3 pole) by ABB
6 ea. – ACB (20 A / 600 V / 3 pole) by ABB
2 ea. – ACB (6 A / 600 V / 3 pole) by ABB
3 ea. – ACB (400 A / 600 V / 3 pole) by ABB

34. 01 Unit DC Main Distribution Board (125 Vdc)


consist of : 2 ea. – Voltmeter (0-150 Vdc)
2 ea. – ACB (160 A / 600 V / 2 Pole) by ABB
4 ea. – ACB (40 A / 600 V / 2 Pole) by BBC
32 ea. – ACB (16 A / 600 V / 2 Pole) by BBC
2 ea. – ACB (16 A / 600 V / 2 Pole) by Siemens
2 ea. – ACB (10 A / 600 V / 2 Pole) by Siemens

35. 01 Unit DC Main Distribution Board (220 Vdc)


consist of : 1 ea. – Voltmeter (0-300 Vdc)
1 ea. – ACB (63 A / 600 V / 2 Pole) by Siemens
6 ea. – ACB (15 A / 600 V / 2 Pole) by LG BKM

36. 01 Unit Power and Lighting Distribution Board (220 Vac)


consist of : 1 ea. – ACB (100 A / 600 V/ 3 Pole) by ABB
8 ea. – ACB (20 A / 600 V/ 2 Pole) by ABB

37. 01 Unit Panelboard for Billing Meter


consist of : 2 ea. – Digital Billing Meter by Power Measurement
Type – 8400
38. 01 Unit Panelboard for Teleprotection FOX 515 by ABB
39. 01 Unit Panelboard for Distance Relay (Relay 511 V 2.3) by ABB