Plate Heat Exchanger

Technical specification
Customer : National Dev. Eng. Ltd.
Model : M6-FG
Project: :
Item : HX 6100 Date : 27-09-2017
______________________________________________________________________________
Hot side Cold side
Fluid Water Water
Volume flow rate m³/h 18.0 27.0
Inlet temperature °C 82.0 55.0
Outlet temperature °C 71.4 62.0
Pressure drop kPa 19.1 39.0

Heat Exchanged kW 215.7


Heat transfer area m² 5.1
Relative directions of fluids Countercurrent
Number of plates 36
Effective plates 34
Number of passes 1 1

Plate material / thickness ALLOY 316 / 0.50 mm


Sealing material NBRP Clip-on NBRP Clip-on
Connection material Stainless steel Stainless steel
Connection diameter mm 50 50
Nozzle orientation S1 -> S2 S4 <- S3

Pressure vessel code ALS


Flange rating ASME 150#
Design pressure bar 10.0 10.0
Test pressure bar 13.0 13.0
Design temperature °C 110.0 110.0

Overall length x width x height mm 574 x 320 x 920


Liquid volume dm³ 5.26 5.56
Net weight, empty / operating kg 204 / 215
Packed weight ( PLYWOOD BOX OCEAN LYING ) kg 224
volume m³ 0.3
length x width x height mm 960 x 420 x 680
_________________________________________________________________________
The performance of the equipment is conditioned by the process media and process parameters being consistent
with the provided customer data.

Data, specifications, and other kind of information of technological nature set out in this document and submitted
by Alfa Laval to you (Proprietary Information) are intellectual proprietary rights of Alfa Laval. The Proprietary
Information shall remain the exclusive property of Alfa Laval and shall only be used for the purpose of evaluating
Alfa Laval's quotation. The Proprietary Information may not, without the written consent of Alfa Laval, be used or
copied, reproduced, transmitted or communicated or disclosed in any other way to a third party., and other kind of
information of technological nature set out in this document and submitted by Alfa Laval to you (Proprietary
Information) are intellectual proprietary rights of Alfa Laval. The Proprietary Information shall remain the exclusive
property of Alfa Laval and shall only be used for the purpose of evaluating Alfa Lavals quotation. The Proprietary
Information may not, without the written consent of Alfa Laval, be used or copied, reproduced, transmitted or
communicated or disclosed in any other way to a third party.

You might also like