Standard for
Ventilation Control
and Fire
Protection
of Commercial
Cooking
Operations
1998 Edition
National Fire Protection Association, 1 Batterymarch Park, PO Box 9101, Quincy, MA 02269-9101
An International Codes and Standards Organization
Copyright ©
National Fire Protection Association, Inc.
One Batterymarch Park
Quincy, Massachusetts 02269
NFPA codes and standards, of which the document contained herein is one, are developed through a consensus stan-
dards development process approved by the American National Standards Institute. This process brings together volunteers
representing varied viewpoints and interests to achieve consensus on fire and other safety issues. While the NFPA admin-
isters the process and establishes rules to promote fairness in the development of consensus, it does not independently test,
evaluate, or verify the accuracy of any information or the soundness of any judgments contained in its codes and standards.
The NFPA disclaims liability for any personal injury, property or other damages of any nature whatsoever, whether
special, indirect, consequential or compensatory, directly or indirectly resulting from the publication, use of, or reliance on
this document. The NFPA also makes no guaranty or warranty as to the accuracy or completeness of any information pub-
lished herein.
In issuing and making this document available, the NFPA is not undertaking to render professional or other services
for or on behalf of any person or entity. Nor is the NFPA undertaking to perform any duty owed by any person or entity to
someone else. Anyone using this document should rely on his or her own independent judgment or, as appropriate, seek the
advice of a competent professional in determining the exercise of reasonable care in any given circumstances.
The NFPA has no power, nor does it undertake, to police or enforce compliance with the contents of this document.
Nor does the NFPA list, certify, test or inspect products, designs, or installations for compliance with this document. Any
certification or other statement of compliance with the requirements of this document shall not be attributable to the NFPA
and is solely the responsibility of the certifier or maker of the statement.
NOTICES
All questions or other communications relating to this document and all requests for information on NFPA procedures
governing its codes and standards development process, including information on the procedures for requesting Formal
Interpretations, for proposing Tentative Interim Amendments, and for proposing revisions to NFPA documents during
regular revision cycles, should be sent to NFPA headquarters, addressed to the attention of the Secretary, Standards Coun-
cil, National Fire Protection Association, 1 Batterymarch Park, P.O. Box 9101, Quincy, MA 02269-9101.
Users of this document should be aware that this document may be amended from time to time through the issuance of
Tentative Interim Amendments, and that an official NFPA document at any point in time consists of the current edition of
the document together with any Tentative Interim Amendments then in effect. In order to determine whether this document
is the current edition and whether it has been amended through the issuance of Tentative Interim Amendments, consult ap-
propriate NFPA publications such as the National Fire Codes® Subscription Service, visit the NFPA website at
www.nfpa.org, or contact the NFPA at the address listed above.
A statement, written or oral, that is not processed in accordance with Section 16 of the Regulations Governing Com-
mittee Projects shall not be considered the official position of NFPA or any of its Committees and shall not be considered
to be, nor be relied upon as, a Formal Interpretation.
The NFPA does not take any position with respect to the validity of any patent rights asserted in connection with any
items which are mentioned in or are the subject of this document, and the NFPA disclaims liability of the infringement of
any patent resulting from the use of or reliance on this document. Users of this document are expressly advised that deter-
mination of the validity of any such patent rights, and the risk of infringement of such rights, is entirely their own responsi-
bility.
Users of this document should consult applicable federal, state, and local laws and regulations. NFPA does not, by the
publication of this document, intend to urge action that is not in compliance with applicable laws, and this document may
not be construed as doing so.
Licensing Policy
This document is copyrighted by the National Fire Protection Association (NFPA). By making this document avail-
able for use and adoption by public authorities and others, the NFPA does not waive any rights in copyright to this docu-
ment.
1. Adoption by Reference – Public authorities and others are urged to reference this document in laws, ordinances,
regulations, administrative orders, or similar instruments. Any deletions, additions, and changes desired by the adopting
authority must be noted separately. Those using this method are requested to notify the NFPA (Attention: Secretary, Stan-
dards Council) in writing of such use. The term “adoption by reference” means the citing of title and publishing information
only.
2. Adoption by Transcription – A. Public authorities with lawmaking or rule-making powers only, upon written no-
tice to the NFPA (Attention: Secretary, Standards Council), will be granted a royalty-free license to print and republish this
document in whole or in part, with changes and additions, if any, noted separately, in laws, ordinances, regulations, admin-
istrative orders, or similar instruments having the force of law, provided that: (1) due notice of NFPA’s copyright is con-
tained in each law and in each copy thereof; and (2) that such printing and republication is limited to numbers sufficient to
satisfy the jurisdiction’s lawmaking or rule-making process. B. Once this NFPA Code or Standard has been adopted into
law, all printings of this document by public authorities with lawmaking or rule-making powers or any other persons desir-
ing to reproduce this document or its contents as adopted by the jurisdiction in whole or in part, in any form, upon written
request to NFPA (Attention: Secretary, Standards Council), will be granted a nonexclusive license to print, republish, and
vend this document in whole or in part, with changes and additions, if any, noted separately, provided that due notice of
NFPA’s copyright is contained in each copy. Such license shall be granted only upon agreement to pay NFPA a royalty.
This royalty is required to provide funds for the research and development necessary to continue the work of NFPA and its
volunteers in continually updating and revising NFPA standards. Under certain circumstances, public authorities with law-
making or rule-making powers may apply for and may receive a special royalty where the public interest will be served
thereby.
3. Scope of License Grant – The terms and conditions set forth above do not extend to the index of this document.
(For further explanation, see the Policy Concerning the Adoption, Printing, and Publication of NFPA Documents,
which is available upon request from the NFPA.)
96–1
NFPA 96
Standard for
Ventilation Control and Fire Protection of
Commercial Cooking Operations
1998 Edition
This edition of NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial
Cooking Operations, was prepared by the Technical Committee on Venting Systems for Cooking
Appliances and acted on by the National Fire Protection Association, Inc., at its Annual
Meeting held May 18–21, 1998, in Cincinnati, OH. It was issued by the Standards Council
on July 16, 1998, with an effective date of August 5, 1998, and supersedes all previous editions.
Changes other than editorial are indicated by a vertical rule in the margin of the pages
on which they appear. These lines are included as an aid to the user in identifying changes
from the previous edition.
This edition of NFPA 96 was approved as an American National Standard on August 6,
1998.
Alternates
Frans S. Andrews, Commercial Vent Cleaning Co., Ltd, Harry P. Jones, Underwriters Laboratories Inc., IL [RT]
BC, Canada [IM] (Alt. to D. P. Restelli)
(Alt. to P. Ackland) Fred E. Kahn, Guardian Power Cleaning of Dallas, Inc.,
David C. Bixby, Gas Appliance Mfrs. Assn., Inc., VA [M] TX [IM]
(Alt. to A. Arvin) (Alt. to R. Leonard)
Dennis N. Gage, Insurance Services Office, Inc., NY [I] Richard Kukla, Robert Rippe & Assoc., MN [SE]
(Alt. to D. L. Foster) (Alt. to H. Schildkraut)
Leonard E. Griffes, NEVTEC Ltd, VT [M] Michael J. Laderoute, Badger Fire Protection, Inc./
(Alt. to D. L. Griffes) Williams Holdings, VA [M]
Ross Hancock, Uno Restaurants Inc., MA [U] (Alt. to W. Klingenmaier)
(Alt. to L. E. Stahl) Laurie K. Szumla, Lane Fire & Safety, NY [IM]
Edward Hard, T. J. Hard Cos., OH [IM] (Voting Alt. to LFS Rep.)
(Alt. to T. J. Hard)
Robert J. James, MountainStar Enterprises, Ltd, MN
[M]
(Alt. to M. A. O’Hara)
Nonvoting
Joseph F. Schulz, Van-Packer Products Inc., NJ
This list represents the membership at the time the Committee was balloted on the text of this edition. Since that time,
changes in the membership may have occurred. A key to classifications is found at the back of this document.
NOTE: Membership on a committee shall not in and of itself constitute an endorsement of the Association
or any document developed by the committee on which the member serves.
Committee Scope: This Committee shall have primary responsibility for documents on fire safety in the
design, installation, and use of exhaust systems (including hoods, grease removal devices, exhaust ducts,
dampers, air-moving devices, and auxiliary equipment) for the removal of products of combustion, heat,
grease, and vapors from cooking equipment, including the application of associated fire-extinguishing
systems.
1998 Edition
CONTENTS 96–3
Contents
1998 Edition
96–4 VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS
1998 Edition
GENERAL 96–5
Ducts (or Duct System). A continuous passageway for the some future time, leaving the exiting air with a lower amount
transmission of air and vapors that, in addition to the contain- of combustible matter.
ment components themselves, might include duct fittings,
Greasetight. Constructed and performing in such a man-
dampers, plenums, and/or other items or air-handling equip-
ner as not to permit the passage of any grease under normal
ment.
cooking conditions.
Easily Accessible. Within comfortable reach, with limited
dependence on mechanical devices, extensions, or assistance. High Broiler. See Upright Broiler.
Factory-Built Grease Duct Enclosures. A listed factory- High Limit Control. An operating device installed in and
built grease duct enclosure system evaluated for reduced clear- serving as an integral component of a deep fat fryer. Its pur-
ances to combustibles and as an alternative to a duct with its pose is the secondary limitation of temperature allowed by
fire-rated enclosure. the cooking operation and, if that temperature is exceeded,
the automatic interruption of the thermal energy input.
Field-Applied Grease Duct Enclosure. A listed system eval-
uated for reduced clearances to combustibles and as an alter- Hood.* A device provided for a cooking appliance(s) to
native to a duct with its fire-rated enclosure. direct and capture grease-laden vapors and exhaust gases.
Hood, Fixed Baffle. A listed unitary exhaust hood design
Fire Barrier Wall. A wall assembly complying with the re- where the grease removal device is a nonremovable assembly
quirements of NFPA 221, Standard for Fire Walls and Fire Barrier that contains an integral fire-activated water-wash fire-extin-
Walls, having a fire resistance rating of 4 hours. guishing system listed for this purpose.
Fire Partition. An interior wall or partition of a building Interconnected. Mutually assembled to another compo-
that separates two areas and serves to restrict the spread of nent in such a manner that the operation of one directly
fire but does not qualify as a fire wall. affects the other or that the contents of one specific duct
Fire Resistance Rating. A relative value in minutes or system are allowed to encounter or contact the products being
hours assigned to materials or assemblies that have withstood moved by another duct system.
a fire exposure as established in accordance with NFPA 251,
Labeled. Equipment or materials to which has been
Standard Methods of Tests of Fire Endurance of Building Construction
attached a label, symbol, or other identifying mark of an orga-
and Materials.
nization that is acceptable to the authority having jurisdiction
Fume Incinerators. Devices utilizing intense heat or fire and concerned with product evaluation, that maintains peri-
to break down and/or oxidize vapors and odors contained in odic inspection of production of labeled equipment or materi-
gases or air being exhausted into the atmosphere. als, and by whose labeling the manufacturer indicates
Fusible Link. A form of fixed temperature heat detecting compliance with appropriate standards or performance in a
device sometimes employed to restrain the operation of an specified manner.
electrical or mechanical control until its designed temperature Limited-Combustible Material.* A building construction
is reached. Such devices are to be replaced following each material that does not comply with the definition of noncom-
operation. bustible material, that, in the form in which it is used, has a
Grease. Rendered animal fat, vegetable shortening, and potential heat value not exceeding 3500 Btu/lb (8141 kJ/kg)
other such oily matter used for the purposes of and resulting (see NFPA 259, Standard Test Method for Potential Heat of Building
from cooking and/or preparing foods. Grease might be liber- Materials), and that complies with either of the following (a)
ated and entrained with exhaust air or might be visible as a or (b). Materials subject to an increase in combustibility or
liquid or solid. flame-spread rating beyond the limits herein established
through the effects of age, moisture, or other atmospheric
Grease Ducts. A containment system for the transporta- conditions shall be considered combustible.
tion of air and grease vapors that is designed and installed
to reduce the possibility of the accumulation of combustible (a) Materials having a structural base of noncombustible
condensation and the occurrence of damage if a fire occurs material, with a surfacing not exceeding a thickness of 1⁄8 in.
within the system. (3.2 mm), and with a flame-spread rating not greater than 50
Grease Filter. A removable component of the grease re- (b) Materials in the form and thickness used, other than
moval system designed to capture grease and direct it to a as described in (a), having neither a flame-spread rating
safe collection point. Filters are expected to minimize the greater than 25 nor evidence of continued progressive com-
projection of flames downstream when attacked by flame on bustion and of such composition that surfaces that would be
the upstream side and are expected to maintain their strength, exposed by cutting through the material on any plane would
shape, and integrity when exposed to the anticipated rough have neither a flame-spread rating greater than 25 nor evi-
handling, cleaning, and service found in the field. dence of continued progressive combustion.
Grease Filter Mesh Type. A general-purpose air filter de- Liquidtight. Constructed and performing in such a man-
signed to collect and retain lint and grease from the air passing ner as not to permit the passage of any liquid at any tempera-
through it. This type of filter is not tested, listed, or acceptable ture.
for commercial cooking operations due to the increased fire Listed.* Equipment, materials, or services included in a
hazard. list published by an organization that is acceptable to the
Grease Removal Devices. A system of components de- authority having jurisdiction and concerned with evaluation
signed for and intended to process vapors, gases, and/or air of products or services, that maintains periodic inspection
as it is drawn through such devices by collecting the airborne of production of listed equipment or materials or periodic
grease particles and concentrating them for further action at evaluation of services, and whose listing states that either the
1998 Edition
96–6 VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS
equipment, material, or service meets identified standards or exhaust system and to transfer the thermal energy so re-
has been tested and found suitable for a specified purpose. claimed to a location whereby a useful purpose can be served.
Noncombustible Material. A material that, in the form in Trap. A cuplike or U-shaped configuration located on the
which it is used and under the conditions anticipated, will not inside of a duct system component where liquids can accumu-
ignite, burn, support combustion, or release flammable vapors late.
when subjected to fire or heat. Materials that are reported as Upright Broiler. An appliance used in the preparation of
passing ASTM E 136, Standard Test Method for Behavior of Materi- food whereby foods are exposed to intense radiant heat, and
als in a Vertical Tube Furnace at 750 ⬚C, shall be considered perhaps to convective heat, with the food or the food and the
noncombustible materials. radiant source not limited to a horizontal mode.
Open Combustible Construction.* Combustible building
1-3 General Requirements.
construction including wall, structural framing, roof, roof ceil-
ing, floor and floor ceiling assemblies adjacent to a grease 1-3.1 Cooking equipment used in processes producing
duct on three or fewer sides where one or more sides require smoke or grease-laden vapors shall be equipped with an ex-
protection per 1-3.2. haust system that complies with all the equipment and perfor-
mance requirements of this standard, and all such equipment
Pitched. To be fixed or set at a desired angle or inclination.
and performance shall be maintained per this standard during
Recirculating Systems. Systems for control of smoke or all periods of operation of the cooking equipment. Specifically,
grease-laden vapors from commercial cooking equipment that the following equipment shall be kept in good working condi-
do not exhaust to the outside. tion:
Removable. Capable of being transferred to another loca- (a) Cooking equipment
tion with a limited application of effort and tools. (b) Hoods
Replacement Air. Air deliberately brought into the struc- (c) Ducts (if applicable)
ture, then specifically to the vicinity of either a combustion (d) Fans
process or a mechanically or thermally forced exhausting de-
vice, to compensate for the vapor and/or gases being con- (e) Fire suppression systems
sumed or expelled. (f) Special effluent or energy control equipment
Salamander Broiler. See Upright Broiler. All airflows shall be maintained. Maintenance and repairs
shall be performed on all components at intervals necessary
Shall. Indicates a mandatory requirement. to maintain these conditions.
Single Hazard Area. As considered in the applicable extin- 1-3.1.1* All solid fuel cooking equipment shall comply with
guishing system standard (see Section 7-2) or as determined by the requirements of Chapter 11.
the authority having jurisdiction.
1-3.1.2 Multiple tenancy applications shall require the con-
Solid Cooking Fuel. Any solid, organic, consumable fuel certed cooperation of design, installation, operation, and
such as briquettes, mesquite, hardwood, or charcoal. maintenance responsibilities by tenants and by the building
Solid Fuel Cooking Equipment. Cooking equipment that owner.
is fired with solid cooking fuel. This equipment includes ovens, 1-3.1.3 All interior surfaces of the exhaust system shall be
tandoori charcoal pots, grills, broilers, rotisseries, barbecue reasonably accessible for cleaning and inspection purposes.
pits, or any other type of cooking equipment that derives all
or part of its heat source from the burning of solid cooking 1-3.1.4* Cooking equipment used in fixed, mobile, or tem-
fuel. porary concessions, such as trucks, buses, trailers, pavilions,
tents, or any form of roofed enclosure, shall comply with this
Solvent. A substance (usually liquid) capable of dissolving standard unless all or part of the installation is exempted by
or dispersing another substance; a chemical compound de- the authority having jurisdiction.
signed and used to convert solidified grease into a liquid or
semiliquid state in order to facilitate a cleaning operation. 1-3.2* Clearance.
Spark Arrester. A device or method that minimizes the 1-3.2.1 Except where enclosures are required, hoods, grease
passage of airborne sparks and embers into a plenum, duct, removal devices, exhaust fans, and ducts shall have a clearance
and flue. of at least 18 in. (457.2 mm) to combustible material, 3 in.
(76.2 mm) to limited-combustible material, and 0 in. (0 mm)
Standard. A document, the main text of which contains
to noncombustible material. [See Figures A-1-3.2(a) through (e).]
only mandatory provisions using the word ‘‘shall’’ to indicate
requirements and which is in a form generally suitable for Exception No. 1: Where the hood, duct, or grease removal device is
mandatory reference by another standard or code or for adop- listed for lesser clearances.
tion into law. Nonmandatory provisions shall be located in Exception No. 2: Reduced clearance to combustible material if the
an appendix, footnote, or fine-print note and are not to be combustible material is protected as follows:
considered a part of the requirements of a standard.
(a) 0.013-in. (0.33-mm) (28-gauge) sheet metal spaced out 1 in.
Termination. The final or intended end-portion of a duct (25.4 mm) on noncombustible spacers shall have 9-in. (228.6-mm)
system that is designed and functions to fulfill the obligations clearance to combustible material.
of the system in a satisfactory manner. (b) 0.027-in. (0.69-mm) (22-gauge) sheet metal on 1-in. (25.4-
Thermal Recovery Unit. A device or series of devices mm) mineral wool bats or ceramic fiber blanket reinforced with wire
whose purpose is to reclaim only the heat content of air, mesh or equivalent spaced out 1 in. (25.4 mm) on noncombustible
vapors, gases, or fluids that are being expelled through the spacers shall have 3-in. (76.2-mm) clearance to combustible material.
1998 Edition
HOODS 96–7
See Figures A-1-3.2(f) and (g) for examples of clearance reduction Exception: When the duct is protected with a material or product
systems. listed for the purpose of reducing clearance to zero.
Exception No. 3: Reduced clearance to limited-combustible materials 1-3.2.5 For clearances between the duct and interior surfaces
to zero clearance where protected by metal lath and plaster, ceramic of enclosures, see 4-7.2.3.
tile, quarry tile, other noncombustible materials or assembly of noncom-
bustible materials, or materials and products that are listed for the 1-3.3 A drawing(s) of the exhaust system installation along
purpose of reducing clearance and are acceptable to the authority with a copy of operating instructions for subassemblies and
having jurisdiction. The listed materials shall be installed in accor- components used in the exhaust system, including electrical
dance with the conditions of the listing and the manufacturer’s instruc- schematics, shall be available on the premises.
tions and shall be acceptable to the authority having jurisdiction.
1-3.4 If required by the authority having jurisdiction, notifi-
1-3.2.1.1 Measures shall be taken to prevent physical damage cation in writing shall be given of any alteration, replacement,
to any material or product used for the purpose of reducing or relocation of any exhaust or extinguishing system or part
clearances. In the event of damage, the material or product thereof or cooking equipment. Satisfaction shall be provided
shall be repaired and restored to meet its intended listing or to the authority having jurisdiction that the complete exhaust
clearance requirements and shall be acceptable to the author- system as addressed in this standard is installed and operable in
ity having jurisdiction. In the event of a fire within a kitchen accordance with the approved design and the manufacturer’s
exhaust system, the duct and its enclosure (rated shaft, factory- instructions.
built grease duct enclosure, or field applied grease duct enclo-
sure) shall be inspected by qualified personnel to determine 1-3.5 Alternative Methods. Nothing in this standard is in-
whether the duct and protection method are structurally tended to prevent the use of other methods or devices, pro-
sound, capable of maintaining their fire protection function, vided that sufficient technical data are submitted to the
and suitable for continued operation. authority having jurisdiction to demonstrate that the proposed
method or device is equivalent in quality, strength, fire endur-
1-3.2.2 The protection methods for ducts to reduce clear- ance, effectiveness, durability, and safety to that prescribed by
ance shall be applied to the combustible or limited-combusti- this standard.
ble construction, not to the duct itself.
Exception: Field applied grease duct enclosures and factory-built
grease duct enclosures. Chapter 2 Hoods
1-3.2.3 Field applied grease duct enclosures and factory-built
grease duct enclosures shall demonstrate that they provide 2-1 Construction.
sufficient mechanical and structural integrity, resiliency, and 2-1.1 The hood or that portion of a primary collection means
stability when subjected to expected building environmental designed for collecting cooking vapors and residues shall
conditions, duct movement under general operating condi- be constructed of and be supported by steel not less than
tions, and duct movement due to fire conditions. Measures 0.043 in. (1.09 mm) (No. 18 MSG) in thickness, stainless steel
shall be taken to prevent physical damage to any material or not less than 0.037 in. (0.94 mm) (No. 20 MSG) in thickness,
product used for the purpose of reducing clearances. or other approved material of equivalent strength and fire
Exception: When the duct is protected with a field applied grease and corrosion resistance.
duct enclosure or factory-built grease duct enclosure.
Exception: Listed exhaust hoods with or without exhaust dampers.
1-3.2.3.1 The specifications of material, gauge, and construc-
2-1.2 All seams, joints, and penetrations of the hood enclo-
tion of the duct used in the testing and listing of field applied
sure that direct and capture grease-laden vapors and exhaust
grease duct enclosures and factory-built grease duct enclo-
gases shall have a liquidtight continuous external weld to
sures shall be included as minimum requirements in their
the hood’s lower outermost perimeter. Internal hood joints,
listing and installation documentation.
seams, filter support frames, and appendages attached inside
1-3.2.3.2* The following clearance options for which field the hood need not be welded but shall be sealed or otherwise
applied grease duct enclosures and factory-built grease duct made greasetight.
enclosures have been successfully evaluated shall be clearly Exception No. 1: Penetrations shall be permitted to be sealed by
identified in their listing and installation documentation and devices that are listed for such use and whose presence does not detract
on their label. from the hood’s or duct’s structural integrity.
(a) Open combustible clearance at manufacturer’s requested Exception No. 2: Eyebrow-type hoods over gas or electric ovens shall
dimensions be permitted to have a duct constructed as in Chapter 4 from the oven
(b) Closed combustible clearance at manufacturer’s re- flue(s) connected to the hood canopy upstream of the exhaust plenum
quested dimensions, with or without specified ventilation as shown in Figure 2-1.2. The duct shall be connected to the hood
(c) Rated shaft clearance at manufacturer’s requested dimen- with a continuous weld or have a duct-to-duct connection as shown
sions, with or without specified ventilation in Figures 5-1.2.1(b), (c), or (d).
Exception No. 3: Seams, joints, and penetrations of the hood shall
1-3.2.4 A duct shall be permitted to contact noncombustible
be permitted to be internally welded, provided that the weld is formed
floors, interior walls, and other noncombustible structures
smooth or ground smooth, so as to not trap grease, and is readily
or supports, but it shall not be in contact for more than
cleanable.
50 percent of its surface area per each lineal foot of contact
length. Where such direct contact is made, the duct shall be Exception No. 4: Listed exhaust hoods with or without exhaust
protected from corrosion due to this contact. dampers.
1998 Edition
96–8 VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS
2-3.1 The construction of the outer shell or the inner exhaust 3-2.3 Grease filters shall be listed and constructed of steel
shell shall comply with 2-1.2. If the outer shell is welded, the or listed equivalent material and shall be of rigid construction
inner shell shall be of greasetight construction. that will not distort or crush under normal operation, han-
dling, and cleaning conditions. Filters shall be tightfitting and
2-3.2* A fire-actuated damper shall be installed in the supply firmly held in place.
air plenum at each point where a supply air duct inlet or a
3-2.4 Filters shall be easily accessible and removable for
supply air outlet penetrates the continuously welded shell of
cleaning.
the assembly. The damper shall be listed for such use or be
part of a listed exhaust hood with or without exhaust damper. 3-2.5 Filters shall be installed at an angle not less than
The actuation device shall have a maximum temperature rat- 45 degrees from the horizontal.
ing of 286⬚F (141⬚C). Supply air plenums that discharge air 3-2.6 Filters shall be equipped with a drip tray beneath their
from the face rather than from the bottom or into the exhaust lower edges. The tray shall be kept to the minimum size
hood and that are isolated from the exhaust hood by the needed to collect grease and shall be pitched to drain into
continuously welded shell extending to the lower outermost an enclosed metal container having a capacity not exceeding
perimeter of the entire hood assembly shall not require a fire- 1 gal (3.785 L).
actuated damper. (See Figure A-2-3.2.)
3-2.7 Grease filters that require a specific orientation to drain
2-4 Listed Hood Assemblies. Listed hood assemblies shall grease shall be clearly so designated, or the hood shall be
be installed in accordance with the terms of their listing and constructed so that filters cannot be installed in the wrong
the manufacturer’s instructions. orientation.
2-5 Solid Fuel Hood Assemblies. Where solid fuel cooking 3-3 Solid Fuel Grease Removal Devices. Where solid fuel
equipment is to be used, the solid fuel hood assembly shall cooking equipment is provided with grease removal devices,
comply with Chapter 11. these devices shall comply with Chapter 11.
1998 Edition
EXHAUST DUCT SYSTEMS 96–9
Chapter 4 Exhaust Duct Systems wing nuts, used to secure the access panels shall be carbon
steel or stainless steel and shall not penetrate duct walls.
4-1 General. Exception: Listed grease duct access door assemblies (access panels)
4-1.1 Ducts shall not pass through fire walls or fire partitions. shall be installed in accordance with the terms of the listing and the
manufacturer’s instructions.
4-1.2* All ducts shall lead as directly as is practicable to the
exterior of the building, so as not to unduly increase any fire 4-3.4.5 Openings for installation, servicing, and inspection
hazard. of listed fire protection system devices and for duct cleaning
shall be provided in ducts and enclosures and shall conform
4-1.3 Duct systems shall not be interconnected with any other to the requirements of 4-3.4 and 4-7.5. Enclosure openings
building ventilation or exhaust system. required to reach access panels in the ductwork shall be large
4-1.4 All ducts shall be installed without forming dips or enough for the removal of the access panel.
traps that might collect residues. In manifold (common duct) 4-4 Listed Grease Ducts. Listed grease ducts shall be in-
systems, the lowest end of the main duct shall be connected stalled in accordance with the terms of the listing and the
flush on the bottom with the branch duct. manufacturer’s instructions.
4-1.5 Openings required for accessibility shall comply with
4-5 Other Grease Ducts. Other grease ducts shall comply
Section 4-3.
with 4-5.1 through 4-5.2.2.
4-1.6 A sign shall be placed on all access panels stating the
following: 4-5.1 Materials. Ducts shall be constructed of and supported
ACCESS PANEL—DO NOT OBSTRUCT by carbon steel not less than 0.054 in. (1.37 mm) (No. 16
MSG) in thickness or stainless steel not less than 0.043 in.
4-2 Clearance. (1.09 mm) (No. 18 MSG) in thickness.
4-2.1 Clearance between ducts and combustible materials 4-5.2 Installation.
shall be provided in accordance with the requirements of
4-5.2.1 All seams, joints, penetrations, and duct-to-hood col-
1-3.2.
lar connections shall have a liquidtight continuous external
4-2.2 For listed grease ducts, see Section 4-4. weld.
4-3 Openings. Exception No. 1: Duct-to-hood collar connections as shown in Figure
4-3.1 Openings shall be provided at the sides or at the top 4-5.2.1 shall be permitted.
of the duct, whichever is more accessible, and at changes of Exception No. 2: Penetrations shall be permitted to be sealed by other
direction. Openings shall be protected by approved access listed devices that are tested to be greasetight and are evaluated under
panels that comply with 4-3.4.4. the same conditions of fire severity as the hood or enclosure of listed
Exception: Openings shall not be required in portions of the duct grease extractors and whose presence does not detract from the hood’s
that are accessible from the duct entry or discharge. or duct’s structural integrity.
4-3.2 For hoods with dampers in the exhaust or supply collar,
an access panel for cleaning and inspection shall be provided
in the duct or the hood collar. This access panel shall be
as close to the hood as possible but shall not exceed 18 in. •
• •
(457.2 mm). • •
• •
Exception: Dampers that are accessible from under the hood.
4-3.3 Exhaust fans with ductwork connected to both sides
shall have access for cleaning and inspection within 3 ft
(0.92 m) of each side of the fan. •
• •
•
1998 Edition
96–10 VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS
Exception No. 3: Internal welding shall be permitted, provided the 4-6.2 All ducts shall be protected on the exterior by paint
joint is formed or ground smooth and is readily accessible for inspec- or other suitable weather-protective coating or shall be con-
tion. structed of noncorrosive stainless steel. Ductwork subject to
4-5.2.2 Overlapping duct connections of either the telescop- corrosion shall have minimal contact with the building sur-
face.
ing or the bell type shall be used for welded field joints, not
butt-weld connections. The inside duct section shall always be 4-7 Interior Installations.
uphill of the outside duct section. The difference between
inside dimensions of overlapping sections shall not exceed 1⁄4 4-7.1 In all buildings more than one story in height, and in
in. (6.4 mm). The overlap shall not exceed 2 in. (50.8 mm). one-story buildings where the roof–ceiling assembly is re-
(See Figure 4-5.2.2.) quired to have a fire resistance rating, the ducts shall be en-
closed in a continuous enclosure extending from the lowest
4-6 Exterior Installations. fire-rated ceiling or floor above the hood, through any con-
4-6.1 The exterior portion of the ductwork shall be vertical cealed spaces, to or through the roof so as to maintain the
wherever possible and shall be installed and adequately sup- integrity of the fire separations required by the applicable
ported on the exterior of a building. Bolts, screws, rivets, building code provisions. The enclosure shall be sealed
and other mechanical fasteners shall not penetrate duct walls. around the duct at the point of penetration of the lowest fire-
Clearance of any ducts shall comply with 1-3.2. rated ceiling or floor above the hood in order to maintain
the fire resistance rating of the enclosure and shall be vented
to the exterior of the building through weather-protected
openings.
Telescoping duct joint Exception: The continuous enclosure provisions shall not be required
• Duct size decreases (going upward) with each telescope.
where a field applied grease duct enclosure or a factory-built grease
• Smaller (inside) duct section is always above or uphill (on duct enclosure (see 1-3.2.3) is protected with a listed duct-through-
sloped duct), to be self-draining into larger (outside) duct. penetration protection system equivalent to the fire resistance rating
of the assembly being penetrated and the materials are installed in
accordance with the conditions of the listing and the manufacturer’s
instructions and are acceptable to the authority having jurisdiction.
Exhaust duct
Inside section I.D. in. 4-7.2 The enclosure required in 4-7.1 shall conform to
4-7.2.1 through 4-7.2.3.
Weld around
4-7.2.1 If the building is less than four stories in height, the
enclosure wall shall have a fire resistance rating of not less
2 in. (max) than 1 hour.
4-7.2.2 If the building is four stories or more in height, the
enclosure wall shall have a fire resistance rating of not less
I.D. in. + ¹⁄₄ in. than 2 hours.
Outside section 16-gauge (¹⁄₁₆-in.)
black iron 4-7.2.3* Clearance from the duct or the exhaust fan to the
interior surface of enclosures of combustible construction
shall be not less than 18 in. (457.2 mm), and clearance from
the duct to the interior surface of enclosures of noncombusti-
ble or limited-combustible construction shall be not less than
6 in. (152.4 mm). Provisions for reducing clearances as de-
Bell duct joint
• Duct size stays the same throughout the duct system. scribed in 1-3.2 are not applicable to enclosures.
• Smaller (inside) male duct end is always above or uphill (on sloped
Exception: Clearance from the outer surfaces of field applied grease
duct), to be self-draining into larger (outside) female duct end. duct enclosures and factory-built grease duct enclosures to the interior
surfaces of construction installed around them shall be permitted to
be reduced where the field applied grease duct enclosure materials and
factory-built grease duct enclosures are installed in accordance with
Exhaust duct
the conditions of the listing and manufacturer’s instructions and are
Male end I.D. in. acceptable to the authority having jurisdiction.
4-7.3 For field applied grease duct enclosures and factory-
Weld around built grease duct enclosures, the materials and products shall
conform to 4-7.3.1 through 4-7.3.3.
I.D. in. + ¹⁄₄ in.
2 in. (max)
4-7.3.1 Field applied grease duct enclosures and factory-built
grease duct enclosures shall demonstrate that they provide
sufficient mechanical and structural integrity, resiliency, and
Female end I.D. in. stability when subjected to expected building environmental
16-gauge (¹⁄₁₆-in.)
black iron conditions, duct movement under general operating condi-
tions, and duct movement due to interior and exterior fire
conditions.
4-7.3.2 Measures shall be taken to prevent physical damage
to any covering or enclosure material. Any damage to the
Figure 4-5.2.2 Telescoping and bell-type duct connections. covering or enclosure shall be repaired and the covering or
1998 Edition
EXHAUST DUCT SYSTEMS 96–11
enclosure restored to meet its intended listing and fire-resistive (f) Other approved fan, provided (1) it meets the require-
rating and to be acceptable to the authority having jurisdic- ments of 4-8.2.1(c) and 5-1.3 and (2) its discharge or its ex-
tion. tended duct discharge meets the requirements of 4-8.2.1(b).
4-7.3.3 In the event of a fire within a kitchen exhaust system, (See 5-1.3.)
the duct, the enclosure, or the covering directly applied to the 4-8.2.2* Fans shall be provided with safe access and a work
duct shall be inspected by qualified personnel to determine surface for inspection and cleaning.
whether the duct, the enclosure, and the covering directly
4-8.3 Wall Terminations.
applied to the duct are structurally sound, capable of main-
taining their fire protection functions, suitable for continued 4-8.3.1 Wall terminations shall be arranged with or provided
operation, and acceptable to the authority having jurisdiction. with the following properties:
4-7.4 For listed grease ducts, see Section 4-4. (a) Through a noncombustible wall with a minimum of
10 ft (3.05 m) of clearance from the outlet to adjacent
4-7.5 If openings in the enclosure walls are provided, they buildings, property lines, grade level, combustible con-
shall be protected by approved self-closing fire doors of proper struction, electrical equipment or lines, and the closest
rating. Fire doors shall be installed in accordance with NFPA point of any air intake or operable door or window at or
80, Standard for Fire Doors and Fire Windows. Openings on other below the plane of the exhaust termination. The closest
listed materials or products shall be clearly identified and point of any air intake or operable door or window above
labeled according to the terms of the listing and the manufac- the plane of the exhaust termination shall be a minimum
turer’s instructions and shall be acceptable to the authority of 10 ft (3.05 m) distant, plus 0.25 ft (0.076 m) for each
having jurisdiction. The panels shall be readily accessible. 1 degree from horizontal, the angle of degree being mea-
4-7.6 Each duct system shall constitute an individual system sured from the center of the exhaust termination to the
serving only exhaust hoods in one fire zone on one floor. center of the air intake or operable door or window. [See
Multiple ducts shall not be permitted in a single enclosure Figure 4-8.3.1(a).]
unless acceptable to the authority having jurisdiction.
4-8* Termination of Exhaust System.
FAI
4-8.1 The exhaust system shall terminate as follows:
(a)* Outside the building with a fan or duct
(b) Through the roof, or to the roof from outside, as in
4-8.2, or through a wall, as in 4-8.3
4-8.2 Rooftop Terminations.
4-8.2.1 Rooftop terminations shall be arranged with or pro-
vided with the following:
(a) A minimum of 10 ft (3.05 m) of clearance from the
32 ft 6 in.
outlet to adjacent buildings, property lines, and air intakes.
Where space limitations absolutely prevent a 10-ft (3.05-m)
horizontal separation from an air intake, a vertical separation FAI
shall be permitted, with the exhaust outlet being a minimum
of 3 ft (0.92 m) above any air intake located within 10 ft
.
in
3
(3.05 m) horizontally.
ft
21
(b) The exhaust flow directed up and away from the surface
of the roof and a minimum of 40 in. (1.02 m) above the roof
surface 12 ft 6 90°
FAI
in.
(c) The ability to drain grease out of any traps or low points
10° 45°
formed in the fan or duct near the termination of the system Horizontal
into a collection container that is noncombustible, closed, Exhaust
ft FAI
rainproof, structurally sound for the service to which it is 10 10 ft
applied, and will not sustain combustion. A grease collection 30°
10 ft
1998 Edition
96–12 VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS
Exception: A wall termination in a secured area can be at a lower flanges securely bolted as shown in Figures 5-1.2(b), (c), (d),
height above grade if acceptable to the authority having jurisdiction. or (e) or by a system specifically listed for such use. Flexible
connectors shall not be used.
(b) The exhaust flow directed perpendicularly outward from
the wall face or upward 5-1.2.2* If the design or positioning of the fan allows grease
(c) All the ductwork pitched to drain the grease back into to be trapped, a drain directed to a readily accessible and
the hood(s), or with a drain provided to bring the grease visible grease receptacle, not exceeding 1 gal (3.8 L), shall be
back into a container within the building or into a remote provided. In-line exhaust fans shall be located in an easily
grease trap accessible area of adequate size to allow for service or removal.
If the duct system connected to the fan is in an enclosure,
(d) A listed grease duct complying with Section 4-4, or other
the space or room in which the exhaust fan is located shall
ducts complying with Section 4-5
have the same fire resistance rating as the enclosure.
(e) An approved fan, provided it meets the requirements of
4-8.3.1(c) and 5-1.1 or 5-1.3 5-1.3* Utility set exhaust fans (see Figure 5-1.3), if installed at
the rooftop termination point, shall meet the requirements
4-9 Solid Fuel Duct Systems. Where solid fuel cooking
equipment is to be vented, the duct system shall comply with
Chapter 11. Flanges to be positioned ¹⁄₄-in. carbon steel
so that the gasket is 1500°F (815.6°C) or stainless steel
protected from direct rated gasket bolts (max) 4 in.
Chapter 5 Air Movement contact with grease on center
1 in. × 1 in. × ¹⁄₈ in.
5-1 Exhaust Fans for Commercial Cooking Equipment. angle flange (min)
Where solid fuel cooking equipment is to be vented, the duct
system shall comply with Chapter 11. ¹⁄₂ in. (min)
5-1.1* Approved upblast fans with motors surrounded by the
airstream shall be hinged, supplied with flexible weatherproof
electrical cable and service hold-open retainers, and listed for
this use (see Figure 5-1.1). Installation shall conform to the
requirements of Section 4-8.
1998 Edition
AIR MOVEMENT 96–13
¹⁄₄-in. carbon steel of 4-8.2.1(a) through (c) and 4-8.2.2. If the fan is installed
1500°F (815.6°C) or stainless steel within the building, it shall be located in an easily accessible
rated sealant bolts (max) 4 in.
on center
area of adequate size to allow for service or removal. If the
1-in. flange duct system connected to the fan is in an enclosure, the space
(min) or room in which the exhaust fan is located shall have the
same fire resistance rating as the enclosure. The fan shall be
connected to the exhaust duct by flanges securely bolted as
shown in Figures 5-1.2.1(b), (c), (d), or (e) or by a system
specifically listed for such use. Flexible connectors shall not
be used. Exhaust fans shall have a drain directed to a readily
accessible and visible grease receptacle not to exceed 1 gal
(3.8 L).
5-1.4 Exhaust fan housings shall be constructed of carbon
Lock washer steel not less than 0.054 in. (1.37 mm) (No. 16 MSG) in
thickness or stainless steel not less than 0.043 in. (1.09 mm)
Unassembled position Assembled position (No. 18 MSG) in thickness or, if listed, constructed in accor-
dance with the terms of the listing.
Note: For SI units, 1 in. = 25.4 mm.
5-1.5 Openings for cleaning, servicing, and inspection shall
Figure 5-1.2.1(d) Typical section of duct-to-fan connection—sealant
conform to the requirements of 4-3.3. Clearances shall con-
method. form to the requirements of 1-3.2 or 4-7.2.3 if installed within
an enclosure.
5-1.6 All wiring and electrical equipment shall comply with
NFPA 70, National Electrical Code娀 (see also Chapter 6).
¹⁄₄-in. carbon steel 5-2 Airflow.
1500°F (815.6°C)
or stainless steel
rated gasket
weld studs (max)
5-2.1 The air velocity through any duct shall be not less than
4 in. on center 1500 ft (457.2 m) per minute.
Lock washer
Fan inlet
Exception: Transition duct sections shall be permitted to be connected
1 in. × 1 in. × ¹⁄₈ in. to hoods and exhaust fans that do not meet this velocity, provided
cone angle flange (min)
that they do not exceed 3 ft (0.92 m) in length and do not contain
traps for grease.
5-2.2 Exhaust air volumes for hoods shall be of sufficient
level to provide for capture and removal of grease-laden cook-
ing vapors. Test data, performance acceptable to the authority
having jurisdiction, or both, shall be provided, displayed, or
both, upon request.
Continuous
perimeter Exception: Lower exhaust air volumes shall be permitted during no-
weld load cooking conditions, provided they are sufficient to capture and
Unassembled position Assembled position remove flue gases and residual vapors from cooking equipment.
Note: For SI units, 1 in. = 25.4 mm. 5-2.3 A hood exhaust fan(s) shall continue to operate after
the extinguishing system has been activated, unless fan shut-
Figure 5-1.2.1(e) Typical section of duct-to-fan connection—direct down is required by a listed component of the ventilation
to fan inlet cone method. system or by the design of the extinguishing system. It shall
not be required to restart the hood exhaust fan when the
extinguishing system is activated if the exhaust fan and all
cooking equipment served by the fan had previously been
shut down.
Discharge 5-3* Replacement Air. Replacement air quantity shall be ad-
equate to prevent negative pressures in the commercial cook-
ing area(s) from exceeding 0.02 in. water column (4.98 kPa).
Exception: When its fire-extinguishing system discharges, makeup
air supplied internally to a hood shall be shut off.
5-4 Common Duct (Manifold) Systems. Master kitchen ex-
haust ducts that serve multiple tenants shall include provision
to bleed air from outdoors or from adjacent spaces into the
master exhaust duct where required to maintain the necessary
minimum air velocity in the master exhaust duct. This bleed
air duct shall connect to the top or side of the master exhaust
duct. The bleed air duct shall have a fire damper at least
12 in. (304.8 mm) from the exhaust duct connection. The
Figure 5-1.3 Utility set fan. bleed air duct shall have the same construction and clearance
1998 Edition
96–14 VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS
requirements as the main exhaust duct from the connection be installed in ducts or hoods or located in the path of travel
to the exhaust duct to at least 12 in. (304.8 mm) on both of exhaust products where specifically approved for such use.
sides of the fire damper. Each bleed air duct shall have a Downgrading other parts of the exhaust system due to the
means of adjusting (e.g., using volume dampers) the bleed installation of these approved devices, whether listed or not,
air quantity. Such means shall be installed in between the fire shall not be allowed.
damper and the source of bleed air (see Figure 5-4). A bleed 6-3.2 Any equipment, listed or otherwise, that provides sec-
air duct shall not be used for the exhaust of grease-laden vapors ondary filtration or air pollution control and that is installed
and shall be so labeled. Unused tenant exhaust connections in the path of travel of exhaust products shall be provided
to the master exhaust duct that are not used as bleed air with an approved automatic fire-extinguishing system for the
connections shall be disconnected and sealed at the main protection of the component sections of the equipment and
duct. shall include protection of the ductwork downstream of the
5-5 Solid Fuel Air Movement Requirements. Where solid equipment, whether or not the equipment is provided with a
fuel cooking equipment is used, exhaust and replacement air damper. If the equipment can be a source of ignition, it shall
also shall comply with Chapter 11. be provided with appropriate detection to operate the fire-
extinguishing system.
6-3.3 Where a cooking exhaust system employs an air pollu-
Chapter 6 Auxiliary Equipment tion control device that recirculates air into the building, the
provisions of Chapter 10 shall apply.
6-1 Dampers. Dampers shall not be installed in exhaust
ducts or exhaust duct systems. 6-4 Solid Fuel Auxiliary Equipment. Where solid fuel cook-
Exception: Where specifically listed for such use or where required ing comprises any part of a cooking operation, additional
as part of a listed or approved device or system. provisions and equipment as described in Chapter 11 shall
be used where required.
6-2 Electrical Equipment.
6-2.1 Wiring systems of any type shall not be installed in
ducts. Chapter 7 Fire-Extinguishing Equipment
6-2.2 Motors, lights, and other electrical devices shall not be 7-1 General Requirements.
installed in ducts or hoods or located in the path of travel of
exhaust products. 7-1.1 Fire-extinguishing equipment for the protection of
grease removal devices, hood exhaust plenums, and exhaust
Exception: Where specifically approved for such use. duct systems shall be provided.
6-2.3 Lighting units in hoods shall be listed for use over 7-1.2 Cooking equipment that produces grease-laden vapors
commercial cooking appliances and installed in accordance (such as, but not limited to, deep fat fryers, ranges, griddles,
with the terms of their listing. broilers, woks, tilting skillets, and braising pans) shall be pro-
6-2.4 Lighting units on hoods shall not be located in con- tected by fire-extinguishing equipment.
cealed spaces.
7-2 Types of Equipment.
Exception No. 1: Where part of a listed exhaust hood.
7-2.1 Fire-extinguishing equipment shall include both auto-
Exception No. 2: Where specifically listed for such use and installed matic fire-extinguishing systems as primary protection and
in accordance with the terms of the listing. portable fire extinguishers as secondary backup.
6-2.5 All electrical equipment shall be installed in accor- 7-2.1.1 A placard identifying the use of the extinguisher as
dance with NFPA 70, National Electrical Code, with due regard a secondary backup means to the automatic fire suppression
to the effects of heat, vapor, and grease on the equipment. system shall be conspicuously placed near each portable fire
6-3 Other Equipment. extinguisher in the cooking area.
6-3.1 Fume incinerators, thermal recovery units, air pollu- 7-2.2* Automatic fire-extinguishing systems shall comply
tion control devices, or other devices shall be permitted to with standard UL 300, Fire Testing of Fire Extinguishing Systems
Fire damper
Volume control 12 in. 12 in.
(305 mm) (305 mm)
(min) (min)
Exhaust
Figure 5-4 System for introducing bleed air into a master exhaust duct.
1998 Edition
FIRE-EXTINGUISHING EQUIPMENT 96–15
for Protection of Restaurant Cooking Areas, or other equivalent identify the hazard protected. The automatic and manual
standards and shall be installed in accordance with their list- means of system activation external to the control head or
ing. releasing device shall be separate and independent of each
Exception: Automatic fire-extinguishing equipment provided as part other so that failure of one will not impair the operation of
of listed recirculating systems complying with standard UL 197, Stan- the other.
dard for Safety—Commercial Electric Cooking Appliances. Exception No. 1: The manual means of system activation shall be
7-2.2.1 Automatic fire-extinguishing systems shall be in- permitted to be common with the automatic means if the manual
stalled in accordance with the terms of their listing, the manu- activation device is located between the control head or releasing device
facturer’s instructions, and the following standards where and the first fusible link.
applicable. Exception No. 2: An automatic sprinkler system.
(a) NFPA 12, Standard on Carbon Dioxide Extinguishing Systems 7-5.2 The means for manual actuator(s) shall be mechanical
(b) NFPA 13, Standard for the Installation of Sprinkler Systems and shall not rely on electrical power for actuation.
(c) NFPA 17, Standard for Dry Chemical Extinguishing Systems Exception: Electrical power shall be permitted to be used for manual
activation if a standby power supply is provided or if supervision is
(d) NFPA 17A, Standard for Wet Chemical Extinguishing Systems
provided as per 7-7.1.
7-2.3 Grease removal devices, hood exhaust plenums, and
exhaust ducts requiring protection in accordance with 7-1.1 7-6 System Annunciation.
shall be permitted to be protected by a listed fixed baffle hood 7-6.1 Upon activation of an automatic fire-extinguishing sys-
containing a constant or fire-actuated water-wash system that tem, an audible alarm or visual indicator shall be provided to
is listed to extinguish a fire in the grease removal devices, show that the system has activated.
hood exhaust plenums, and exhaust ducts. Each such area
7-6.2 Where a fire alarm signaling system is serving the occu-
not provided with a listed water-wash extinguishing system
pancy where the extinguishing system is located, the activation
shall be provided with an appropriate fire suppression system
of the automatic fire-extinguishing system shall activate the
listed for the purpose.
fire alarm signaling system.
7-2.3.1 The water for listed fixed baffle hood assemblies shall
be permitted to be supplied from the domestic water supply 7-7 System Supervision.
when the minimum water pressure and flow are provided in 7-7.1 Where electrical power is required to operate the auto-
accordance with the terms of the listing. The water supply matic fire-extinguishing system, it shall be monitored by a
shall be monitored by an annunciated low–water pressure supervisory alarm, with a standby power supply provided.
switch. Exception No. 1: Where automatic fire-extinguishing systems include
7-2.3.2 The water wash in the fixed baffle hood shall be automatic mechanical detection and actuation as a backup detection
activated by the cooking equipment extinguishing system. system.
7-3 Simultaneous Operation. Fixed pipe extinguishing sys- Exception No. 2: Where fire-extinguishing systems are interconnected
tems in a single hazard area (see Section 1-2 for the definition of or interlocked with the cooking equipment power sources so that if the
single hazard area) shall be arranged for simultaneous auto- fire-extinguishing system becomes inoperable due to power failure, all
matic operation upon actuation of any one of the systems. sources of fuel or electric power that produce heat to all cooking
equipment serviced by that hood shall automatically shut off.
Exception No. 1: Where the fixed pipe extinguishing system is an
automatic sprinkler system. 7-8 Special Design and Application.
Exception No. 2: A dry or wet chemical system shall be permitted to 7-8.1 Hoods containing automatic fire-extinguishing systems
be used to protect common exhaust ductwork by one of the methods are protected areas; therefore, these hoods are not considered
specified in NFPA 17, Standard for Dry Chemical Extinguishing obstructions to overhead sprinkler systems and shall not re-
Systems, or NFPA 17A, Standard for Wet Chemical Extinguishing quire floor coverage underneath.
Systems, in lieu of simultaneous automatic operation.
7-8.2 A single listed detection device shall be permitted for
7-4 Fuel Shutoff. more than one appliance when installed in accordance with
the terms of the listing.
7-4.1 Upon activation of any fire-extinguishing system for a
cooking operation, all sources of fuel and electric power that 7-9 Review and Certification.
produce heat to all equipment requiring protection by that
7-9.1 Where required, complete drawing of the system instal-
system shall automatically shut off.
lation, including the hood(s), exhaust duct(s), and appliances,
Exception No. 1: Steam supplied from an external source. along with the interface of the fire-extinguishing system detec-
Exception No. 2: Solid fuel cooking operations. tors, piping, nozzles, fuel shutoff devices, agent storage con-
tainer(s), and manual actuation device(s), shall be submitted
7-4.2 Any gas appliance not requiring protection, but located to the authority having jurisdiction.
under the same ventilating equipment, shall also automatically
shut off upon activation of any extinguishing system. 7-9.2* Installation of systems shall be performed only by
persons properly trained and qualified to install the specific
7-4.3 Shutoff devices shall require manual reset. system being provided. The installer shall provide certification
7-5 Manual Activation. to the authority having jurisdiction that the installation is in
agreement with the terms of the listing and the manufacturer’s
7-5.1 A readily accessible means for manual activation shall instructions and/or approved design.
be located between 42 in. and 60 in. (1067 mm and 1524 mm)
above the floor, located in a path of exit or egress, and clearly 7-10 Portable Fire Extinguishers.
1998 Edition
96–16 VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS
7-10.1* Portable fire extinguishers shall be installed in Exception: Where automatic bulb-type sprinklers or spray nozzles are
kitchen cooking areas in accordance with NFPA 10, Standard used and annual examination shows no buildup of grease or other
for Portable Fire Extinguishers. Such extinguishers shall use material on the sprinkler or spray nozzles.
agents that saponify upon contact with hot grease such as
sodium bicarbonate and potassium bicarbonate dry chemical 8-2.3 If required, certificates of inspection and maintenance
and potassium carbonate solutions. Class B gas-type portables shall be forwarded to the authority having jurisdiction.
such as CO2 and halon shall not be permitted in kitchen 8-3 Cleaning.
cooking areas. Manufacturer’s recommendations shall be fol-
lowed. 8-3.1* Hoods, grease removal devices, fans, ducts, and other
appurtenances shall be cleaned to bare metal at frequent
7-10.1.1 Portable fire extinguishers listed specifically for use intervals prior to surfaces becoming heavily contaminated with
in the kitchen cooking areas shall also be permitted. grease or oily sludge. After the exhaust system is cleaned to
7-10.2 Other fire extinguishers in the kitchen area shall be bare metal, it shall not be coated with powder or other sub-
installed in accordance with NFPA 10, Standard for Portable Fire stance. The entire exhaust system shall be inspected by a
Extinguishers. properly trained, qualified, and certified company or per-
son(s) acceptable to the authority having jurisdiction in accor-
7-11 Solid Fuel Fire-Extinguishing Equipment. Where solid dance with Table 8-3.1.
fuel cooking equipment is served by fire-extinguishing equip-
ment, the provisions of Chapter 11 shall apply.
Table 8-3.1 Exhaust System Inspection Schedule
Chapter 8 Procedures for the Use and Maintenance Type or Volume of Cooking Frequency
of Equipment Systems serving solid fuel cooking operations Monthly
8-1 Operating Procedures. Systems serving high-volume cooking operations Quarterly
such as 24-hour cooking, charbroiling or wok
8-1.1 Exhaust systems shall be operated whenever cooking cooking
equipment is turned on. Systems serving moderate-volume cooking Semiannually
operations
8-1.2 Filter-equipped exhaust systems shall not be operated
with filters removed. Systems serving low-volume cooking operations, such Annually
as churches, day camps, seasonal businesses, or
8-1.3 Openings provided for replacing air exhausted senior centers
through ventilating equipment shall not be restricted by cov-
ers, dampers, or any other means that would reduce the op-
erating efficiency of the exhaust system.
8-3.1.1 Upon inspection, if found to be contaminated with
8-1.4 Instructions for manually operating the fire-extinguish- deposits from grease-laden vapors, the entire exhaust system
ing system shall be posted conspicuously in the kitchen and shall be cleaned by a properly trained, qualified, and certified
shall be reviewed periodically with employees by the manage- company or person(s) acceptable to the authority having juris-
ment. diction in accordance with Section 8-3.
8-1.5 Listed exhaust hoods shall be operated in accordance 8-3.1.2 When a vent cleaning service is used, a certificate
with the terms of their listings and the manufacturer’s instruc- showing date of inspection or cleaning shall be maintained
tions. on the premises. After cleaning is completed, the vent cleaning
contractor shall place or display within the kitchen area a
8-1.6 Cooking equipment shall not be operated while its fire-
label indicating the date cleaned and the name of the servicing
extinguishing system or exhaust system is nonoperational or
company. It shall also indicate areas not cleaned.
otherwise impaired.
8-3.2 Flammable solvents or other flammable cleaning aids
8-2* Inspection. An inspection and servicing of the fire- shall not be used.
extinguishing system and listed exhaust hoods containing a
constant or fire-actuated water system shall be made at least 8-3.3 At the start of the cleaning process, electrical switches
every 6 months by properly trained and qualified persons. that could be activated accidentally shall be locked out.
8-2.1 All actuation components, including remote manual 8-3.4 Components of the fire suppression system shall not
pull stations, mechanical or electrical devices, detectors, actua- be rendered inoperable during the cleaning process.
tors, and fire-actuated dampers, shall be checked for proper Exception: Servicing by properly trained and qualified persons in
operation during the inspection in accordance with the manu- accordance with Section 8-2.
facturer’s listed procedures. In addition to these requirements,
the specific inspection requirements of the applicable NFPA 8-3.5 Care shall be taken not to apply cleaning chemicals
standard shall also be followed. on fusible links or other detection devices of the automatic
extinguishing system.
8-2.2 Fusible links (including fusible links on fire-actuated
damper assemblies) and automatic sprinkler heads shall be 8-3.6 When cleaning procedures are completed, all electrical
replaced at least annually, or more frequently if necessary, to switches and system components shall be returned to an opera-
ensure proper operation of the system. Other detection de- ble state. All access panels (doors) and cover plates shall be
vices shall be serviced or replaced in accordance with the replaced. Dampers and diffusers shall be positioned for proper
manufacturer’s recommendations. airflow.
1998 Edition
RECIRCULATING SYSTEMS 96–17
8-4 Operation, Maintenance, and Inspection of Solid Fuel Exception: References to ducts in 7-1.1 and 7-5.1.
Cooking Equipment. Where solid fuel cooking equipment
(g) The use and maintenance requirements of Chapter 8
is used, the special provisions of Chapter 11 shall apply.
(h) The minimum safety requirements of Chapter 9
(i) All the requirements of this chapter
Chapter 9 Minimum Safety Requirements 10-2 Design Restrictions. All recirculating systems shall com-
for Cooking Equipment ply with 10-2.1 through 10-2.7.
10-2.1 Only gas- or electrically fueled cooking appliances
9-1 Cooking Equipment. shall be used. Gas-fueled appliances shall not have the combus-
9-1.1 Cooking equipment shall be approved based on one tion flue outlet(s) directly connected to the recirculating sys-
of the following criteria: tem. Gas-fueled appliances shall have a minimum 18-in.
(457.2-mm) clearance from the flue outlet to the filter inlet
(a) Listings by a testing laboratory in accordance with 3-2.2 and shall meet the installation re-
(b) Test data acceptable to the authority having jurisdiction quirements of NFPA 54, National Fuel Gas Code, or NFPA 58,
Liquefied Petroleum Gas Code.
9-1.2 Installation.
10-2.2 Recirculating systems shall be listed with a testing
9-1.2.1 All listed appliances shall be installed in accordance laboratory. There shall be no substitution or exchange of
with the terms of their listings and the manufacturer’s instruc- cooking appliances, filter components, blower components,
tions. or fire-extinguishing system components that would violate
9-1.2.2* Cooking appliances requiring protection shall not the listing of the appliance.
be moved, modified, or rearranged without prior reevaluation 10-2.3 A recirculating system shall use cooking equipment
of the fire-extinguishing system by the system installer or ser- that exceeds that system’s labeled maximum limits for that type
vicing agent, unless otherwise allowed by the design of the of equipment, stated in maximum energy input, maximum
fire-extinguishing system. cooking temperature, and maximum square area of cooking
Exception: Cooking appliances moved to perform maintenance and surface or cubic area of cooking cavity. The listing label shall
cleaning provided the appliances are returned to their original position- show the type(s) of cooking equipment tested and the preced-
ing prior to cooking operations, and any disconnected fire-extinguish- ing maximum limits.
ing system nozzles attached to the appliances are reconnected in 10-2.4 A fire-actuated damper shall be installed at the ex-
accordance with the manufacturer’s listed design manual. haust outlet of the system. The damper shall be constructed
9-1.2.3 All deep fat fryers shall be installed with at least a of at least the same gauge as the shell. The actuation device
16-in. (406.4-mm) space between the fryer and surface flames shall have a maximum temperature rating of 375⬚F (190⬚C).
from adjacent cooking equipment. 10-2.5 No electrical wiring shall be installed in the interior
Exception: Where a steel or tempered glass baffle plate is installed sections of the hood plenum that might become exposed to
at a minimum 8 in. (203 mm) in height between the fryer and surface grease.
flames of the adjacent appliance. Exception: As permitted by NFPA 70, National Electrical Code.
9-2 Operating Controls. Deep fat fryers shall be equipped 10-2.6 The power supply of any electrostatic precipitator
with a separate high-limit control in addition to the adjustable (ESP) shall be of the ‘‘cold spark,’’ ferro-resonant type in
operating control (thermostat) to shut off fuel or energy when which the voltage falls off as the current draw of a short
the fat temperature reaches 475⬚F (246⬚C) at 1 in. (25.4 mm) increases.
below the surface. 10-2.7 Listing evaluation shall include the following:
(a) Capture and containment of vapors at published and
labeled airflows
Chapter 10 Recirculating Systems
(b) Grease discharge at the exhaust outlet of the system not
10-1 General Requirements. Recirculating systems con- to exceed an average of 5 mg/m3 of exhausted air sam-
taining or for use with appliances used in processes producing pled from that equipment at maximum amount of prod-
smoke or grease-laden vapors shall be equipped with compo- uct that is capable of being processed over a continuous
nents complying with the following: 8-hour test per EPA Test Method 202, Determination of
Condensable Particulate Emissions for Stationary Sources, with
(a) The clearance requirements of 1-3.2 the system operating at its minimum listed airflow.
(b) A hood complying with the requirements of Chapter 2 (c) Listing and labeling of clearance to combustibles from
(c) Grease removal devices complying with Chapter 3 all sides, top, and bottom
(d) The air movement requirements of Chapter 5, Excep- (d) Electrical connection in the field in accordance with
tions to 5-2.1 and 5-2.2 NFPA 70, National Electrical Code
(e) Interlocks on all removable components that lie in the
(e) Auxiliary equipment (such as particulate and odor re-
path of airflow within the unit to ensure that they are in
moval devices) complying with Chapter 6
place during operation of the cooking appliance
Exception: As permitted by 10-2.5.
10-3 Interlocks. The recirculating system shall be provided
(f) Fire-extinguishing equipment complying with the re- with interlocks of all critical components and operations as
quirements of Chapter 7 indicated in 10-3.1 through 10-3.4 such that, if any of these
1998 Edition
96–18 VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS
interlocks are interrupted, the cooking appliance shall not be Chapter 11 Solid Fuel Cooking Operations
able to operate.
11-1 Venting Application. Venting requirements of solid fuel
10-3.1 All closure panels encompassing airflow sections shall
cooking operations shall be determined in accordance with
have interlocks to ensure the panels are in place and fully
11-1.1 through 11-1.6.
sealed.
11-1.1 Where solid fuel cooking equipment is required by
10-3.2 Each filter component (grease and odor) shall have the manufacturer to have a natural draft, the vent shall comply
an interlock to prove the component is in place. with Section 11-4.
10-3.3 Each ESP shall have a sensor to prove its performance 11-1.2 Where the solid fuel cooking equipment has a self-
is as designed, with no interruption of the power to exceed contained top, is the only appliance to be vented in an isolated
2 minutes. This sensor shall be a manual reset device or circuit. space (except for a single water heater with its own separate
vent), has a separate makeup air system, and is provided with
10-3.4 An airflow switch or transducer shall be provided after supply and return air (not supplied or returned from other
the last filter component to ensure that a minimum airflow spaces), the system shall comply with Sections 11-4 and 11-6.
is maintained. This device opens the interlock circuit when
the airflow falls 25 percent below the system’s normal op- 11-1.3 Where the solid fuel cooking equipment is located in
erating flow or 10 percent below its listed minimum rating, a space with other vented equipment, all vented equipment
whichever is lower. This switch or transducer shall be a manual shall have an exhaust system interlocked with a makeup air
reset device or circuit. system for the space as per Section 11-6.
10-4 Location and Application Restrictions. The location of 11-1.4 Natural draft ventilation systems and power-exhausted
recirculating systems shall be approved by the authority having ventilation systems shall comply with Sections 11-3, 11-4, and
jurisdiction. Items to be reviewed in the fire risk assessment 11-6.
shall include, but not be limited to, life safety, combustibility 11-1.5 Where a solid fuel cooking appliance allows effluent
of surroundings, proximity to air vents, and total fuel load. to escape from the appliance opening, this opening shall be
covered by a hood and an exhaust system that meets the
10-5 Additional Fire Safety Requirements. requirements of Sections 11-3, 11-4, and 11-6.
10-5.1 In addition to the appliance nozzle(s), a recirculating 11-1.6 Solid fuel cooking operations shall have spark arresters
system shall be listed with the appropriate fire protection to minimize the passage of airborne sparks and embers into
for grease filters, grease filtration, odor filtration units, and plenums and ducts. Where the solid fuel cooking operation
ductwork where applicable. is not located under a hood, a spark arrester shall be provided
to minimize the passage of sparks and embers into flues and
10-5.2 In addition to any other fire-extinguishing system ac- chimneys.
tuation device, there shall be a fire-extinguishing system actua-
tion device installed downstream of any ESP. 11-2 Location of Appliances.
10-5.3 The requirements of Section 7-6 shall also apply to 11-2.1 Every appliance shall be located with respect to build-
recirculating system locations. ing construction and other equipment so as to permit access
to the appliance.
10-6 Use and Maintenance.
11-2.2 Solid fuel cooking appliances shall not be installed
10-6.1 Automatic or manual covers on cooking appliances, in confined spaces. The space or room shall be of ample size
especially fryers, shall not interfere with the application of to permit adequate circulation of heated air.
the fire suppression system. Exception: Solid fuel cooking appliances listed for installation in
10-6.2 All filters shall be cleaned or replaced in accordance confined spaces such as alcoves shall be installed in accordance with
with the manufacturer’s instructions. the terms of the listing and the manufacturer’s instructions.
11-2.3 Solid fuel cooking appliances shall not be installed
10-6.3 All ESPs shall be cleaned a minimum of once per
in any location where gasoline or any other flammable vapors
week following manufacturer’s cleaning instructions.
or gases are likely to be present.
10-6.4 The entire hood plenum and the blower section shall 11-3 Hoods for Solid Fuel Cooking.
be cleaned a minimum of once every 3 months.
11-3.1 Hoods shall be sized and located in a manner capable
10-6.5 Inspection and testing of the total operation and all of capturing and containing all of the effluent discharging
safety interlocks in accordance with the manufacturer’s in- from the appliances. The hood and its exhaust system shall
structions shall be performed by qualified service personnel comply with Chapters 2 through 7.
a minimum of once every 6 months or more frequently if
required. 11-3.2 All solid fuel cooking equipment served by hood and
duct systems shall be separate from all other exhaust systems.
Exception: Fire extinguishing equipment shall be inspected in accor-
dance with Section 8-2. Exception: Cooking equipment not requiring automatic fire-extin-
guishing equipment (as per the provisions of Chapter 7) shall be
10-6.6 A signed and dated log of maintenance as performed permitted to be installed under a common hood with solid fuel cooking
in accordance with 10-6.4 and 10-6.5 shall be available on the equipment that is served by a duct system separate from all other
premises for use by the authority having jurisdiction. exhaust systems.
1998 Edition
SOLID FUEL COOKING OPERATIONS 96–19
11-4 Exhaust Systems for Solid Fuel Cooking. Where a hood 11-7.5 All solid fuel appliances (whether or not under a
is not required, a duct complying with Chapter 4 shall be hood) with fireboxes of 5-ft3 (0.14-m3) volume or less shall at
provided. least have a 2-A-rated water-type or wet chemical fire extin-
guisher in accordance with NFPA 10, Standard for Portable Fire
11-4.1 If a hood is used, the duct system shall conform with
Extinguishers, in the immediate vicinity of the appliance. Two
Chapter 4.
portable fire extinguishers of at least 11⁄2 gal (5.7 L) each and
11-4.2 Wall terminations of solid fuel exhaust systems shall containing potassium citrate, potassium acetate, or potassium
be prohibited. carbonate solutions shall be permitted to be used instead of
the one 2-A-rated portable fire extinguisher.
11-5 Grease Removal Devices for Solid Fuel Cooking.
Grease removal devices shall be constructed of steel or stainless 11-7.6 Solid fuel appliances with fireboxes exceeding 5 ft3
steel or be approved for solid fuel cooking. (0.14 m3) shall be provided with a fixed water pipe system
with a hose in the immediate vicinity of the appliance. The
11-5.1 If airborne sparks and embers can be generated by
system shall have a minimum operating pressure of 40 psi
the solid fuel cooking operation, spark arrester devices shall
(275.8 kPa) and shall provide a minimum of 5 gpm.
be used prior to the grease removal device to minimize the
entrance of these sparks and embers into the grease removal 11-7.7 Fire suppression for fuel storage areas shall comply
device and into the hood and duct system. with Section 11-9 of this standard.
11-5.2 Filters shall be a minimum of 4 ft (1.2 m) above the 11-7.8 In addition to the requirements of 11-7.5 or 11-7.6,
appliance cooking surface. where any solid fuel cooking appliance is also provided with
auxiliary electric, gas, oil, or other fuel for ignition or supple-
11-6 Air Movement for Solid Fuel Cooking. Exhaust system mental heat and the appliance is also served by any portion
requirements shall comply with Chapter 5 for hooded opera- of a fire-extinguishing system complying with Chapter 7, such
tion or shall be installed in accordance with the manufactur- auxiliary fuel shall be shut off upon actuation of the fire-
er’s recommendation for unhooded applications. extinguishing system.
11-6.1 A replacement or makeup air system shall be provided 11-8 Procedures for Inspection, Cleaning, and Maintenance
to ensure a positive supply of replacement air at all times for Solid Fuel Cooking. Solid fuel cooking appliances shall
during cooking operations. be inspected, cleaned, and maintained in accordance with
11-6.2 Makeup air systems serving solid fuel cooking opera- procedures outlined in Chapter 8, and with 11-8.1 through
tions shall be interlocked with the exhaust air system and 11-8.4.
powered, if necessary, to prevent the space from attaining a 11-8.1 The combustion chamber shall be scraped clean to
negative pressure while the solid fuel appliance is in operation. its original surface once each week and inspected for deterio-
11-7 Fire-Extinguishing Equipment for Solid Fuel Cooking. ration or defects. Any significant deterioration or defect that
might weaken the chamber or reduce its insulation capability
11-7.1 Approved fire-extinguishing equipment shall be pro- shall be immediately repaired.
vided to protect all solid fuel burning cooking appliances that
11-8.2 The flue or chimney shall be inspected weekly for the
might be a source of ignition of grease in the hood, grease
following conditions:
removal device, or duct.
Exception: If acceptable to the authority having jurisdiction, solid (a) Residue that might begin to restrict the vent or create
fuel burning cooking appliances constructed of solid masonry or rein- an additional fuel source. The flue or chimney shall be
forced portland or refractory cement concrete and vented in accordance cleaned before these conditions exist.
with NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid (b) Corrosion or physical damage that might reduce the
Fuel-Burning Appliances, Chapters 3 and 4, shall not require fixed flue’s capability to contain the effluent. The flue or chim-
automatic fire-extinguishing equipment. ney shall be repaired or replaced if any unsafe condition
is evident.
11-7.2 Approved fire-extinguishing equipment shall be pro-
vided for the protection of grease removal devices, hoods, and 11-8.3 Spark arrester screens located at the entrance of the
duct systems. flue or in the hood assembly shall be cleaned prior to becom-
ing heavily contaminated and restricted.
Exception: If acceptable to the authority having jurisdiction, solid
fuel burning cooking appliances constructed of solid masonry or rein- 11-8.4 Filters and filtration devices installed in a hood shall
forced portland or refractory cement concrete and vented in accordance be cleaned per 11-8.3.
with NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid 11-9 Minimum Safety Requirements: Fuel Storage, Handling,
Fuel-Burning Appliances, Chapters 3 and 4, shall not require auto- and Ash Removal for Solid Fuel Cooking.
matic fire-extinguishing equipment.
11-9.1 Installation Clearances.
11-7.3 Approved fire-extinguishment equipment for solid
fuel burning cooking appliances, where required, shall comply 11-9.1.1 Solid fuel cooking appliances shall be installed
with Chapter 7, ‘‘Fire-Extinguishing Equipment,’’ and shall on floors of noncombustible construction that extend 3 ft
be comprised of water-based agents. (0.92 m) in all directions from the appliance.
Exception No. 1: Floors with noncombustible surfaces that have been
11-7.4 Fire-extinguishing equipment shall be rated and de- approved for such use by the authority having jurisdiction.
signed to extinguish solid fuel cooking fires, in accordance
with the manufacturer’s recommendations. The fire-extin- Exception No. 2: Floor assemblies that have been listed for such
guishing equipment shall be of sufficient size to totally extin- applications.
guish fire in the entire hazard area and prevent reignition of Exception No. 3: Solid fuel cooking appliances that have been listed
the fuel. for zero clearance to combustibles on the bottom and sides; they shall
1998 Edition
96–20 VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS
have an approved hearth extending 3 ft (0.92 m) in all directions 11-9.3.4 The ash shall be sprayed adequately with water be-
from the service door(s). fore removal in order to extinguish any hot ash or cinders
11-9.1.2 Combustible and limited-combustible surfaces or and to control the dust when the ash is moved. For these
construction within 3 ft (0.92 m) of the sides or 6 ft (1.8 m) purposes, and to cool a fire that has become too hot and to
above a solid fuel cooking appliance shall be protected in a stop all fire before leaving the premises, a water supply with
manner acceptable to the authority having jurisdiction. a flexible hose shall be provided at the solid fuel appliance.
For appliances with fireboxes not exceeding 5 ft3 (0.14 m3),
Exception No. 1: Construction that is approved for less clearance. the water source shall be permitted to be a 10-gal (37.9-L)
Exception No. 2: Solid fuel cooking appliances that are specifically container with a gravity arrangement or a hand pump for
listed for less clearance to combustibles. pressure. For appliances with fireboxes over 5 ft3 (0.14 m3),
the water source shall be a fixed pipe water system with a hose
11-9.2 Solid Fuel Storage.
of adequate length to reach the combustion and cooking
11-9.2.1 Fuel storage shall not exceed a one-day supply where chambers of the appliance. For either application, the nozzle
stored in the same room as the solid fuel appliance or in the shall be fitted with a manual shutoff device and shall be of
same room as the fuel-loading or clean-out doors. the type to provide a fine-to-medium spray of adequate length
11-9.2.2 Fuel shall not be stored above any heat-producing to reach all areas of the combustion and cooking chambers.
appliance or vent or closer than 3 ft (0.92 m) to any portion A full flow or strong stream shall not be used.
of a solid fuel appliance constructed of metal or to any other 11-9.3.5 A heavy metal container or cart (minimum
cooking appliance that could ignite the fuel. 16 gauge) with a cover shall be provided for the removal of
Exception: A solid fuel appliance or other cooking appliance that is ash. It shall not exceed a maximum of 20-gal (75.7 L) capacity,
listed or approved for less clearance to combustibles. shall be assigned for this one purpose, shall be able to be
11-9.2.3 Fuel shall not be stored in the path of the ash re- handled easily by any employee assigned the task, and shall
moval. pass easily through any passageway to the outside of the build-
ing. The container or cart shall always be covered when it is
11-9.2.4 Where stored in the same building as the solid fuel being moved through the premises. When any hole occurs in
appliance, fuel shall be stored only in an area with walls, floor, a container from corrosion or damage, it shall be repaired or
and ceiling of noncombustible construction extending at least replaced immediately.
3 ft (0.92 m) past the outside dimensions of the storage pile.
11-9.3.6 Tools shall be provided so that ash removal can be
Exception: Combustible or limited-combustible materials protected in
accomplished without having to reach into the chamber. The
accordance with 1-3.2.1, Exception No. 2 or 3.
ash shall be spread out gently in small lots on the chamber
11-9.2.5 Fuel shall be separated from all flammable liquids, floor or on a shovel to be sprayed before it is removed to the
all ignition sources, all chemicals, and all food supplies and metal container or cart. If the floor of the chamber is of a
packaging goods. metal that is subject to rapid corrosion from water, then a
11-9.2.6 All fuel storage areas shall be provided with a sprin- noncombustible, corrosion-resistant pan shall be placed just
kler system meeting the requirements of NFPA 13, Standard outside the clean-out door for this purpose.
for the Installation of Sprinkler Systems, and acceptable to the 11-9.3.7 The ash shall be carried to a separate heavy metal
authority having jurisdiction or with a fixed pipe system with container (or dumpster) used exclusively for the purpose.
a hose in the immediate vicinity of the storage area able to
reach all parts of the area. This fixed pipe system shall meet 11-9.4 Other Safety Requirements.
the requirements of 11-7.1 through 11-7.8.
Exception: The portable fire extinguisher specified in 11-7.5 shall 11-9.4.1 Metal-fabricated solid fuel cooking appliances shall
be permitted to be used for a solid fuel pile, provided that the fuel pile be listed for the application where produced in practical quan-
does not exceed 5 ft3 (0.14 m3). tities or shall be approved by the authority having jurisdiction.
When listed, they shall be installed in accordance with the
11-9.3 Solid Fuel Handling and Ash Removal. terms of their listing and with the applicable requirements of
11-9.3.1 Solid fuel shall be ignited with a match or an ap- this standard.
proved built-in gas flame or other approved ignition source. 11-9.4.2 Site-built solid fuel cooking appliances shall be sub-
Combustible or flammable liquids shall not be used to assist mitted for approval to the authority having jurisdiction before
ignition. Matches and other portable ignition sources shall being considered for installation. All units submitted to the
not be stored in the vicinity of the solid fuel appliance, where authority having jurisdiction shall be installed, operated, and
they might ignite by radiant heat or spark. maintained in accordance with the approved terms of the
11-9.3.2 Solid fuel shall be added to the fire as required in manufacturer’s instructions and any additional requirements
a safe manner and in quantities and ways not creating a higher set forth by the authority having jurisdiction.
flame than is required. Long-handled tongs, hooks, and other
required devices shall be provided and used in order to safely 11-9.4.3 Except for the spark arrester required in 11-1.6,
add fuel, adjust the fuel position, and control the fire without there shall be no additional devices of any type in any portion
having to reach into the firebox. of the appliance, flue pipe, and chimney of a natural draft
solid fuel operation.
11-9.3.3 Ash, cinders, and other fire debris shall be removed
from the firebox at adequately regular intervals to prevent 11-9.4.4 No solid fuel cooking device of any type shall be
interference with the draft to the fire and to minimize the permitted for deep fat frying involving more than one quart
length of time the access door is open. All ash shall be removed of liquid shortening, nor shall any solid fuel cooking device
from the chamber a minimum of once a day. be permitted within 3 ft (0.92 m) of any deep fat frying unit.
1998 Edition
APPENDIX A 96–21
Chapter 12 Referenced Publications A-1-1 The application of this standard is concerned with the
potential fire hazard of cooking operations, irrespective of
12-1 The following documents or portions thereof are refer- the type of cooking equipment used and whether used in
enced within this standard as mandatory requirements and public or private facilities.
shall be considered part of the requirements of this standard. This standard is also intended to include residential cooking
The edition indicated for each referenced mandatory docu- equipment where used for purposes other than residential
ment is the current edition as of the date of the NFPA issuance family use, such as employee kitchens or break areas and
of this standard. Some of these mandatory documents might church and meeting hall kitchens, regardless of frequency of
also be referenced in this standard for specific informational use. Because this standard cannot address specific installa-
purposes and, therefore, are also listed in Appendix B. tions, the judgment should be made by the authority having
jurisdiction.
12-1.1 NFPA Publications. National Fire Protection Associ-
ation, 1 Batterymarch Park, P.O. Box 9101, Quincy, MA 02269- A-1-2 Approved. The National Fire Protection Association
9101. does not approve, inspect, or certify any installations, proce-
NFPA 10, Standard for Portable Fire Extinguishers, 1998 edition. dures, equipment, or materials; nor does it approve or evaluate
NFPA 12, Standard on Carbon Dioxide Extinguishing Systems, testing laboratories. In determining the acceptability of instal-
1998 edition. lations, procedures, equipment, or materials, the authority
NFPA 13, Standard for the Installation of Sprinkler Systems, 1996 having jurisdiction may base acceptance on compliance with
edition. NFPA or other appropriate standards. In the absence of such
NFPA 17, Standard for Dry Chemical Extinguishing Systems, 1998 standards, said authority may require evidence of proper in-
edition. stallation, procedure, or use. The authority having jurisdiction
NFPA 17A, Standard for Wet Chemical Extinguishing Systems, may also refer to the listings or labeling practices of an organi-
1998 edition. zation that is concerned with product evaluations and is thus
NFPA 54, National Fuel Gas Code, 1996 edition. in a position to determine compliance with appropriate stan-
NFPA 58, Liquefied Petroleum Gas Code, 1998 edition. dards for the current production of listed items.
NFPA 70, National Electrical Code娀, 1999 edition.
NFPA 80, Standard for Fire Doors and Fire Windows, 1995 edi- A-1-2 Authority Having Jurisdiction. The phrase ‘‘authority
tion. having jurisdiction’’ is used in NFPA documents in a broad
NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid manner, since jurisdictions and approval agencies vary, as do
Fuel-Burning Appliances, 1996 edition. their responsibilities. Where public safety is primary, the au-
NFPA 259, Standard Test Method for Potential Heat of Building thority having jurisdiction may be a federal, state, local, or
Materials, 1998 edition. other regional department or individual such as a fire chief;
fire marshal; chief of a fire prevention bureau, labor depart-
12-1.2 Other Publications. ment, or health department; building official; electrical in-
12-1.2.1 ASTM Publications. American Society for Testing spector; or others having statutory authority. For insurance
and Materials, 100 Barr Harbor Drive, West Conshohocken, purposes, an insurance inspection department, rating bureau,
PA 19428-2959. or other insurance company representative may be the author-
ity having jurisdiction. In many circumstances, the property
ASTM E 84, Standard Test Method for Surface Burning Character-
owner or his or her designated agent assumes the role of the
istics of Building Materials, 1977.
authority having jurisdiction; at government installations, the
ASTM E 119, Standard Test Methods for Fire Tests of Building
commanding officer or departmental official may be the au-
Construction and Materials, 1995.
thority having jurisdiction.
ASTM E 136, Standard Test Method for Behavior of Materials
in a Vertical Tube Furnace at 750⬚C, 1993. A-1-2 Closed Combustible Construction. See Figure
12-1.2.2 EPA Publication. Environmental Protection Agency A-1-3.2.3.2.
(EPA), Crystal Station, 2800 Crystal Drive, Arlington, VA 22202.
A-1-2 Continuous Weld. Welding is a fabrication technique
EPA Test Method 202, Determination of Condensable Particulate for joining metals by heating the materials to the point that
Emissions for Stationary Sources. they melt and flow together to form an uninterrupted surface
12-1.2.3 UL Publications. Underwriters Laboratories Inc., of no less strength than the original materials.
333 Pfingsten Road, Northbrook, IL 60062.
A-1-2 Hood. Hoods as used in this document are often re-
UL 197, Standard for Safety—Commercial Electric Cooking Appli- ferred to as Type I hoods, meaning those applied to grease
ances. exhaust applications. They are built in various styles referred
UL 300, Fire Testing of Fire Extinguishing Systems for Protection to as island canopy, wall canopy, noncanopy, backshelf, high
of Restaurant Cooking Areas, 1996. sidewall, eyebrow, and so on. All such type and style hoods
UL 723, Standard for Test for Surface Burning Characteristics of are applicable to this document provided they meet all the
Building Materials, 1996. material and performance requirements of this document.
UL 1046, Grease Filters for Exhaust Ducts, 1979. (See Figure A-1-2.)
(a) Types of hoods
Appendix A Explanatory Material 1. Type I. Hoods designed for grease exhaust applica-
Appendix A is not a part of the requirements of this NFPA document tions
but is included for informational purposes only. This appendix con- 2. Type II. Hoods designed for heat and steam removal
tains explanatory material, numbered to correspond with the applica- and other nongrease applications. These hoods are
ble text paragraphs. not applicable to the standard.
1998 Edition
96–22 VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS
1998 Edition
APPENDIX A 96–23
(b) Style of hoods reasons, solid fuel cooking operations should comply with
1. Wall-mounted Chapter 11.
2. Single island A-1-3.1.4 The authority having jurisdiction might exempt
3. Double island temporary facilities, such as a tent, upon evaluation for com-
pliance to the applicable portions of this standard.
4. Backshelf
Although it might not be practical to enforce all require-
5. Eyebrow ments of this standard in temporary facilities, the authority
A-1-2 Limited-Combustible Material. See Table A-1-2. having jurisdiction should determine that all necessary provis-
ions that impact on the personal safety of the occupants are
A-1-2 Listed. The means for identifying listed equipment considered.
may vary for each organization concerned with product evalu-
ation; some organizations do not recognize equipment as A-1-3.2 See Figures A-1-3.2(a) through (g).
listed unless it is also labeled. The authority having jurisdiction A-1-3.2.3.2 See Figure A-1-3.2.3.2.
should utilize the system employed by the listing organization A-2-3.2 See Figure A-2-3.2.
to identify a listed product.
A-4-1.2 Vertical or substantially pitched ducts are preferred
A-1-2 Open Combustible Construction. See Figure over horizontal ducts because of their capacity to drain grease
A-1-3.2.3.2. and to transfer heated vapors more rapidly to the exterior of
A-1-3.1.1 When solid fuel is burned in cooking operations, a building.
increased quantities of carbon, creosote, and grease-laden va- A-4-7.2.3 Noncombustible materials such as reinforced con-
pors are produced that rapidly contaminate surfaces, produce crete floors or protected steel beams, which might protrude
airborne sparks and embers, and are subject to significant into an enclosure and cause reduced clearance, may be permit-
flare-ups. Also, solid fuel cooking requires fuel storage and ted by the authority having jurisdiction if the installation and
handling and produces ash that requires disposal. For these accessibility of the duct system are considered adequate.
Limited-
Type of Assembly Noncombustible Combustible Combustible
Wall assemblies
Brick, clay tile, or concrete masonry products X
Plaster, ceramic, or quarry tile on brick, clay X
tile, or concrete masonry products
Plaster on metal lath on metal studs X
Gypsum board on metal studs X
Solid gypsum board† X
Plaster on wood or metal lath on wood studs X
Gypsum board on wood studs X
Plywood or other wood sheathing on wood or X
metal studs
Floor–ceiling or roof–ceiling assemblies
Plaster applied directly to underside of X
concrete slab
Suspended membrane ceiling
With noncombustible mineral wool X
acoustical material
With combustible fibrous tile X
Gypsum board on steel joists beneath concrete X
slab
Gypsum board on wood joists X
Notes:
1. Wall assembly descriptions assume same facing material on both sides of studs.
2. Categories are not changed by use of fire-retardant-treated wood products.
3. Categories are not changed by use of Type X gypsum board.
4. See definitions of combustible, limited-combustible, and noncombustible in Section 1-2, Definitions.
*See clearance requirements in 1-3.2.
†Solid gypsum walls and partitions, 2-in. (50.8-mm) or 21⁄4-in. (57.15-mm) thickness, are described in the
Fire Resistance Design Manual published by the Gypsum Association, Washington, DC.
1998 Edition
96–24 VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS
1-3.2: 1-3.2:
• 0-in. clearance to noncombustibles • 0-in. clearance to noncombustibles
• 3-in. clearance to limited-combustibles • 3-in. clearance to limited-combustibles
• 18-in. clearance to combustibles, unless protected • 18-in. clearance to combustibles,
in accordance with Exception No. 2 or 3 unless protected in accordance with
Exception No. 2 or 3
4-7.1: sealed around the duct at this point, Exhaust hood
because of fire-rated floor–ceiling assembly
Figure A-1-3.2(a) Typical section view for building with two stories or more with fire-rated floor–ceiling
assembly.
4-8.2.1(a)
Discharge
10 ft 0 in. Exhaust fan
4-3.3 and 1-3.1.3: access panel
Exhaust hood
Figure A-1-3.2(b) Typical section view for one-story building with fire-rated roof–ceiling assembly.
1998 Edition
APPENDIX A 96–25
Discharge
10 ft 0 in. Exhaust fan
4-8.2.1(a) 4-3.3 and 1-3.1.3: access panel
Second story
Fire-rated floor
Exhaust hood
Figure A-1-3.2(c) Typical section view for building with two stories or more with non-fire-rated ceiling and
fire-rated floor.
40 in.
4-8.2.1(e)
Roof 18 in.
Ceiling
1-3.2:
1-3.2: • 0-in. clearance to noncombustibles
• 0-in. clearance to noncombustibles • 3-in. clearance to limited-combustibles
• 3-in. clearance to limited-combustibles • 18-in. clearance to combustibles,
• 18-in. clearance to combustibles, unless protected in accordance with
unless protected in accordance with Exception No. 2 or 3
Exception No. 2 or 3
Exhaust hood
Figure A-1-3.2(d) Typical section view for one-story building without fire-rated roof–ceiling assembly.
1998 Edition
96–26 VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS
Duct
Combustible
material Combustible material
9 in. Duct
3 in. 33 in.
in.
Wire mesh
3 in.
9 9 1-in. mineral wool
in. in. bat or ceramic fiber
9 in. 1-in. blanket
noncombustible
spacer 22-gauge sheet
Plan section metal
28-gauge
sheet metal 1-in. noncombustible spacer, such as
stacked washers. Small-diameter pipe,
1-in. Plan section 1-in. tubing, or electrical conduit
noncombustible air
spacer space Nail or screw anchor
Nail or screw anchor
Combustible
18
28-gauge
.
in
material
in
sheet metal
18
1
.
18
in.
in
Combustible
18
in
1-in.
in
.
in
1998 Edition
APPENDIX B 96–27
1998 Edition
96–28 VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS
A B C D
E F G H
Figure A-2-3.2 Examples of exhaust hood assemblies with integrated supply air plenums. See requirements
in Section 2-3.
Index
䉷 1998 National Fire Protection Association. All Rights Reserved.
The copyright in this index is separate and distinct from the copyright in the document which it indexes. The licensing provisions set forth for
the document are not applicable to this index. This index may not be reproduced in whole or in part by any means without the express written
permission of the National Fire Protection Association, Inc.
1998 Edition
INDEX 96–29
1998 Edition
96–30 VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS
1998 Edition
INDEX 96–31
FP 1998 Edition