You are on page 1of 11

Applied Thermal Engineering 110 (2017) 115–125

Contents lists available at ScienceDirect

Applied Thermal Engineering


journal homepage: www.elsevier.com/locate/apthermeng

Research Paper

Experimental investigation of the first prototype ejector refrigeration


system with HFO-1234ze(E)
Kamil Śmierciew a, Jerzy Gagan a, Dariusz Butrymowicz a,⇑, Michał Łukaszuk a, Henryk Kubiczek b
a
Białystok University of Technology, ul. Wiejska 45C, 15-351 Białystok, Poland
b
EDF Polska S.A., Research and Development Centre, ul. Ciepłownicza 1, 31-587 Kraków, Poland

h i g h l i g h t s

 Experimental investigation of ejector refrigeration system for low GWP refrigerant.


 Application of heat sources below 70 °C to drive the refrigeration system.
 Heat source of 90 kW capacity was used, over 30 kW of cooling capacity was produced.
 Entrainment ratio, COP, cooling capacity, and compression ratio were presented.

a r t i c l e i n f o a b s t r a c t

Article history: One of possibilities of reduction of F-gas emission is application of low grade heat to drive the refriger-
Received 20 May 2016 ation systems as well as application of natural or low GWP working fluids. The own experimental inves-
Revised 16 August 2016 tigation of ejector refrigeration system operating with refrigerant R-1234ze(E) are presented and
Accepted 22 August 2016
discussed. The system is driven with low grade heat source of temperature below 70 °C and thermal
Available online 23 August 2016
capacity approximately 90 kW. The experiments covered the effect of condensation, evaporation and
generation temperatures on the capacity and thermal efficiency of the ejector refrigeration system oper-
Keywords:
ating for air-conditioning purposes. Obtained results showed that the proposed system may be thought
Ejector
Low GWP refrigerants
as the promising thermally driven refrigeration system with application of low grade motive heat
Low-grade heat source sources.
Ejector refrigeration systems Ó 2016 Elsevier Ltd. All rights reserved.
Coefficient of performance

1. Introduction Air-conditioning creates two sources of environmental pollu-


tion: (1) direct emission of greenhouse gases, especially for work-
Buildings represent a very high energy consumption percentage ing fluids belonging to HFC group, and (2) emission of the
compared to other economy sectors. Although percentages vary greenhouse gases during generation of electric power to drive
from country to country, buildings are responsible for about 30– the system. Both sources are contributing significantly to the glo-
45% of the global energy demand. Residential air-conditioning bal warming effect. Additionally, with energy cost rising con-
and refrigeration consumes over 21 percent of electric energy used stantly, industry is looking for reduction of electric energy
for household purposes. Compressors use an average of 70% of the expenses as a means of lowering their fixed costs in order to stay
energy consumed by HVAC and refrigeration systems. For build- competitive. Cogeneration is one of the possible way to increase
ings with applied central air-conditioning systems it comprises a efficiency of electric energy production. While the production of
substantially larger share [1]. Many sources show a significant electricity and heat can be conducted in an efficient manner during
increase in the use of air conditioning, especially in southern coun- the heating season due to sale of the heat for the heating systems,
tries, creating serious supply difficulties during peak load periods. utilization of combined production of electricity and heat
Moreover, predictions indicate a massive growth in energy con- decreases in summer due to the low demand for the heat. This
sumption and air-conditioned area in the EU during the next means that the solution for increasing the share of electricity pro-
15 years, increasing approximately in 50% [2]. duced in combination - is to develop effective ways of managing of
the district heat in the summer. This heat is used for domestic tap
water heating mainly, which involves not only the small amount of
⇑ Corresponding author. heat that is supplied to the heating system, but also the low or
E-mail address: d.butrymowicz@pb.edu.pl (D. Butrymowicz).

http://dx.doi.org/10.1016/j.applthermaleng.2016.08.140
1359-4311/Ó 2016 Elsevier Ltd. All rights reserved.
116 K. Śmierciew et al. / Applied Thermal Engineering 110 (2017) 115–125

Nomenclature

pg motive vapour pressure, MPa tcs condensation temperature, °C


tgs saturation temperature of motive vapour corresponding Qg capacity of motive heat source, kW
to pg, °C Qe cooling capacity, kW
tg motive vapour temperature, °C U mass entrainment ratio, –
pe evaporation pressure, MPa P compression ratio, –
tes evaporation temperature corresponding to pe, °C

even very low parameters. This significantly reduces the possibility the heating system. This is much more attractive way for produc-
of effective use of sorption refrigeration systems for the production tion of chilled water in terms of application, because it allows for
of cold. In addition, sorption systems requires generally very high utilization of low temperature heat (in summer season) for the
investment costs. Moreover, the control possibilities of these sys- air conditioning purposes. Application of absorption system for
tems are limited. Therefore the application of ejector refrigeration chilled water production may be thought as a common approach.
system can be attractive. However, most of absorption systems require temperature of the
Ejector refrigeration system (Fig. 1) is a modification of a well- heat source tg that significantly exceeds 80 °C. Although it is possi-
known vapour compression cycle. Instead of pressurizing the ble to find data showing the operation of the absorption systems
refrigerant by a mechanical compressor, an ejector compresses under lower generator temperature, they have low value of COP
refrigerant vapour flowing from the evaporator and discharges it in such cases. The most recent research on low temperature heat
to the condenser. The motive vapour is generated in the vapour source absorption refrigeration systems [13,14] deals with temper-
generator which is heated by low-temperature heat source. This atures in range 110–130 °C, however. These authors showed that
paper presents development of refrigeration system equipped with for operating conditions suitable for air-conditioning (evaporator
vapour ejector operating with environmentally friendly new refrig- coupling fluid temperature tev,CF 12 °C ? 8 °C) COP reaches approx-
erant HFO-1234ze(E). Selection of this fluid was based on the com- imately 0.14 under real operating conditions. For higher tempera-
prehensive analysis of the working fluids for the ejector system ture tev,CF 18 °C ? 14 °C COP reaches approximately 0.17. These
with respect to Regulation of the European Parliament and the authors emphasized that reducing the heat source temperature
EU Council No. 517/2014 enacted on April 16th, 2014 [3,4]. It for absorption systems is possible by adoption of alternate
was shown by several researchers that ejector system can effec- refrigerant-absorbent pairs. Few references are given for investiga-
tively operate with various natural and low GWP synthetic refrig- tions were several different fluids had been tested. Due to very low
erants [5–8]. vapour generation temperature inevitably low COP of the ejector
Ejector refrigeration systems have been extensively investi- refrigeration systems should be expected for all of the working flu-
gated numerically and experimentally in recent years. The most ids under conditions of the standard parameters of chilled water
comprehensive state-of-the-art study recent on ejector technology for air-conditioning systems [12].
was presented by Chen et al. [9], while Besagni et al. [10] presented In reference to ejector refrigeration systems Besagni et al. [15]
review on ejector refrigeration. These reviews gave all detail infor- have studied the influence of working fluids on the performance
mation on ejector working principles, selection of the working flu- of heat driven ejector refrigeration systems performance by using
ids and ejector technology as well. Elbel and Lawrence [11] a lumped parameter model. These authors have found the refriger-
presented review focused on ejectors applied for work recovery. ant R-134a as suitable for low generator temperature (<100 °C),
Butrymowicz et al. [12] presented the first experimental results hydrocarbons R-600 as suitable for medium generator tempera-
of the ejector refrigeration system operating with isobutane driven tures (100–130 °C) and R-601 for high generator temperatures
by low grade heat source. Results presented in [12] showed that it (>130 °C). Experimental investigation of the ejector refrigeration
is possible to use the ejector refrigeration system driven by heat system operating with R-134a have been made by Zegenhagen
gained from the heat distribution network. During summer season and Ziegler [16]. Hybrid ejector-based refrigeration system with
the temperature of hot water is below 70 °C, and sometimes even compressor as a low step compressor operating with R134a was
below 65 °C. This means that application of the ejector refrigera- conducted by Wang et al. [17]. Both papers [16,17] indicated the
tion system may be thought as an effective solution for the produc- automobile air-conditioning as potential application since waste
tion of chilled water with cooperation with district heating system. heat from engine can be utilized as a motive heat for the ejector
The motive heat for the ejector system can be gained directly from system. Unal [18] proposed application of two-phase ejector for
air-conditioning system for midibuses. Again, refrigerant R-134a
was used as a working fluid. The refrigerant R-134a is often used
as a working medium despite its elevated global warming potential
of GWP = 1300, since this refrigerant is commonly used in air-
conditioning systems, However, the use of refrigerants of GWP
exceeding 150 in air-conditioning systems of vehicles was prohib-
ited since 2011 [19]. Other refrigerants in ejector systems has been
also investigated recently. Chen et al. [19] have studied the opera-
tion of the ejector with refrigerant R-236fa. Ejector was equipped
with the movable nozzle in order to enhance the performance of
the ejector. Shestopalov et al. [20] investigated the ejector refriger-
ation machine operating with refrigerant R-245fa at the on-design
and off-design operating regimes. Results presented in [15–20]
were obtained for the ejector system operating with high GWP
refrigerants, which are banned now or will be banned soon. Also,
Fig. 1. Schematic of the ejector refrigeration system. in near future refrigerants of GWP > 150 will be banned in
K. Śmierciew et al. / Applied Thermal Engineering 110 (2017) 115–125 117

commercial and domestic air-conditioning whose refrigerant 2. Testing stand


charge is higher than 3 kg. Therefore it is a clear need to investigate
operation of the ejector systems operating with refrigerants with The experimental rig presented in Figs. 2 and 3 was build at the
low GWP. One of the promising working fluid is HFO-1234. Wang Białystok University of Technology in Białystok, Poland. The main
[21] gives an overview of the system performance of R-1234yf in elements of the stand are listed in Fig. 2 caption. The geometry
air-conditioning and heat-pump technology. Refrigerant R-1234yf of the tested ejector is presented in Fig. 4. The motive nozzle throat
is substitute for R-134a and is currently used in mobile air- diameter was 11 mm. The testing stand was equipped with the
conditioning. temperature sensors and pressure transducers (marked as (RTD)
In this paper the own investigation of the ejector refrigeration and (P) respectively, in Fig. 2) installed at the critical locations
system operating with HFO group refrigerant R-1234ze(E) have and other locations of interest. The pressure transducers accuracy
been presented and discussed. It was shown by the authors in 0.25% were used during the experiments. The RTD temperature
[22] that the ejector air-conditioning system driven by solar heat sensors were applied for the experiments. The Coriolis mass flow
can effectively operate with low GWP refrigerant R-600a. However, meters accuracy 0.15% were used.
isobutane is classified as explosive, therefore, it might be consid- The test rig was equipped with three auxiliary loops: the first
ered as dangerous in large commercial refrigeration or air- one for the thermal load for the evaporator, the second one for
conditioning. Here, ejector based refrigeration system with safe the condenser cooling, and the third one is the heat source for
R-1234ze(E) driven by low temperature heat source with app. the generator. These systems were equipped with mass flow
90 kW capacity is presented. It must be pointed out that according meters and temperature sensors at inlets and outlets of the heat
to authors knowledge there are no reports dealing with either exchangers. Auxiliary systems allowed for adjusting refrigerant
numerical or experimental investigation of ejector operating with flow rates as well as for changing of operation parameters in a wide
this fluid at this scale. range. In the evaporator heat load system glycol was used as a heat

Fig. 2. Schematic of testing stand: vapour generator (G), condenser (C), evaporator (E), ejector (EJ), refrigerant pump, regenerative heat exchanger (R), throttling valve.
118 K. Śmierciew et al. / Applied Thermal Engineering 110 (2017) 115–125

transfer fluid, in the condenser cooling system and the generator The only exception were the results presented in Figs. 5–8 that
heat source system water was used as a working fluid. The con- were carried out under the transient operating conditions. Pressure
denser cooling system was equipped with an automatically con- and temperatures profiles were observed during stabilization and
trolled dry cooler. The motive heat load system was equipped when no significant changes were observed - excluding, minor
with automatically controlled electrical heater of the capacity change operating parameters, which are typical for the working
100 kW. The stand is also equipped with the control valves system - the operating conditions were taken as steady-state.
enabling the adjustment of the operating parameters of the motive The average operating parameters are listed in Tables 1 and 2.
vapour at the inlet to the motive nozzle of the ejector. The dia-
phragm pump HYDRA-CELL with 3 kW/700 RPM motor was used
as a circulation pump for refrigerant. Plate heat exchangers as gen- 3. Experimental results and discussion
erator, condenser and evaporator were used. The testing stand was
also equipped with the regenerative plate heat exchanger located 3.1. Startup investigation
between the ejector outlet and the condenser.
The data acquisition facility was based on two National Instru- The start-up investigations were conducted in order to inden-
ment systems. The computer used LabVIEW software. In addition, tify the maximum potential performance of the system. The
software dedicated to the experimental stand was capable to authors found as interesting to find how low pressure the ejector
receive on-line data from software REFPROP [23]. The real time can produce for the fixed motive temperature. The present investi-
measurements were shown on the computer screen while all mea- gations covered the ejector system operation for very low temper-
sured data were stored in a data file. During the experiments 100 ature of the motive heat source, therefore the knowledge of lowest
readings (one reading per one second) at the steady-state condi- pressure or temperature available for this systems can be taught as
tions were taken and averaged to make one experimental run. valuable. Note that these issues has not been previously
investigated.
Four series of start-up runs investigations were conducted. Dur-
ing experiments the condensation temperature, and as an effect
condensation pressure were variable parameters, while parame-
ters in the vapour generator were kept constant. Expansion valve
was closed, so the evaporator was refrigerant free. Under such con-
ditions the pressure lift produced by the ejector may be thought as
the maximum possible. Therefore, the parameters in the evapora-
tor were observed in this case. Operating parameters for investiga-
tions are presented in Table 1. As it can be seen in Table 1, the
operation conditions are similar to each other, however, the results
proved that the operation of the ejector is repeatable. In Table 1 the
maximum value of the motive pressure and corresponding satura-
tion temperature and minimum pressure and corresponding tem-
perature produced by the ejector for various temperatures of
condensation are shown. Last column in Table 1 presents the pres-
sure difference between condensation and evaporation pressure,
i.e. pressure lift produced by the tested ejector. In graphic form
the results are shown in Figs. 5–8.
The results shows that the ejector was operating with motive
pressure at the level of approximately 1.2 MPa, which corresponds
to temperature approximately 57–58 °C. For this motive parame-
ters the ejector can produce evaporation pressure at the level of
0.1 MPa corresponding to temperature at the level of 20 °C. The
pressure lift produced by the ejector was in this cases approxi-
mately 0.40–0.45 MPa.
It is seen in these figures that at the beginning of the test run all
pressures were basically the same, therefore the ejector was under
thermodynamic balance. When the ejector was started running the
parameters have been changed. At first motive pressure rises and
evaporation pressure decreases. Steady state have been achieved
at level 1.2 MPa in the generator and 0.11 MPa in the evaporator.
One of the most interesting parameters of the performance of
Fig. 3. Photo of testing stand. the ejector is the dependence of the evaporation pressure on the

Fig. 4. Tested ejector.


K. Śmierciew et al. / Applied Thermal Engineering 110 (2017) 115–125 119

condensation pressure. This relationship can be also analysed increasing of the condensation temperature between approx. 17–
using saturation temperature instead of pressure. Evaporation 22 °C (see Fig. 6a). Such relationship between evaporation and con-
temperature versus condensation temperature for run No. 1 is densation temperatures is typical for the ejector operating under
shown in Fig. 5, and for run No. 3 is shown in Fig 7. Distributions on-design conditions. In presented cases this relationship is valid
of the parameters for runs No. 2 and No. 4 were not shown since until the condensation temperature is lower than 22 °C for run
they were very similar for presented runs No. 3 and No. 1, respec- No. 1, and lower than 19 °C for run No. 3. For higher condensation
tively. This similarity results from the motive parameters which temperatures, pressure in the evaporator increases which may be
are very close by pairs to each other, namely runs No. 1 and 4 thought as typical for the off-design operating conditions.
and runs No. 2 and 3. Presented temperature and pressure distribu-
tions correspond to maximum and minimum values of the motive 3.2. Preliminary results of investigations
pressure, see Table 1.
It is seen in Figs. 6 and 8 that when the steady-state operation In this section results of five test runs were shown and dis-
was achieved (1.2 MPa in the generator and 0.11 MPa in the evap- cussed. Experiments cover wide range of the evaporation temper-
orator) the evaporation temperature was not changing with atures. Motive parameters, i.e. generation pressure and motive

Fig. 5. Parameters distribution during experiments for run no. 1: (a) pressure distribution, (b) saturation temperature distribution.
120 K. Śmierciew et al. / Applied Thermal Engineering 110 (2017) 115–125

vapour temperature were kept constant. Saturation temperature in as critical mass flow rate were calculated using classic gas dynamic
the vapour generator was fixed at 56 °C with superheating of 15 K. equations. We have proved that this approach gives the results that
Condensation pressure was varied by means of control of cooling differ within the measurement error for the measurement with use
conditions of the condenser. Parameters for each run are presented of the Coriolis flow meter. Therefore in the present investigations
in Table 2. we have decided to not use flow meter to measure motive vapour
Motive heat flux (Q_ g ) was calculated as follows: mass flow rate but we have applied the above procedure. In Fig. 9
the performance line in relation of mass flow ratio vs. condensation
Q_ g ¼ m
_ g  Dh g ð1Þ temperature is shown. Saturation temperatures of primary (gener-
ator) and secondary (evaporator) flows were given in the figure
where m_ g is refrigerant mass flow rate, and Dhg is enthalpy differ- caption. It is shown in Fig. 9 that the ejector operated in both on-
ence at the vapour generator outlet and inlet. As it is seen from design and off-design regimes. Critical temperature at which the
Table 2 the capacity of the vapour generator was in the range 78– ejector is changing the operation regime can be easily identified,
89 kW. e.g. for test runs No. 1 and No. 2 it is tccrit1 = tccrit2 = 24 °C, and for
Mass entrainment ratio was calculated as: the test run No. 4 it is tccrit4 = 19 °C.
_e
m Maximum mass entrainment ratio Umax = 0.45 was reported for
U¼ ð2Þ test run No. 5 with tes5 = 5.7 °C and tgs5 = 53.4 °C. Note that
_g
m
tgs5 = 53.4 °C is the lowest value of all runs. However, for run No.
where m _ e is mass flow rate of vapour flows through the evaporator 5 the superheating of the motive vapour is the highest, therefore
and m_ g is mass flow rate of the motive vapour. motive temperature is tg = 73.4 °C. The opposed results should be
The motive stream was chocked in motive nozzle of the ejector expected in that case. The mass entrainment ratio should increase
under all of the operating conditions during the tests. Therefore with increase of the motive pressure since the motive fluid reaches
vapour velocity exceeded the critical velocity. This velocity as well higher velocity and momentum. On the other hand increase of the

Fig. 6. Parameters distribution in evaporator during experiments as a function of temperature of condensation for run no. 1: (a) pressure distribution, (b) saturation
temperature distribution.
K. Śmierciew et al. / Applied Thermal Engineering 110 (2017) 115–125 121

Fig. 7. Parameters distribution during experiments for run no. 3: (a) pressure distribution, (b) saturation temperature distribution.

motive pressure results in increase of the motive mass flow rate. It attainable cross-section area for the secondary fluid inside the
is also reflecting on the motive vapour momentum. Since the sec- ejector. Due to the above effect this cross-section area decreases
ondary fluid is also chocked, and the operating conditions for the that deteriorates mass entrainment ratio.
evaporation have not changed so that the mass flow rate of the sec- For run No. 5 the critical flow temperature tccrit5 = 22.5 °C and
ondary fluid is fixed. According to the definition of the mass ejector malfunction occurred at 25 °C. The lowest critical tempera-
entrainment ratio increase of the primary (motive) fluid when sec- ture tccrit4 = 19 °C for run No. 4 was reported. This can be result of
ondary fluid is not changed should cause the increase of the very low evaporator parameters, i.e. tes4 = 6.7 °C. Corresponding
entrainment ratio. However, on the basis of CFD simulations it evaporation pressure was 0.168 MPa, which means that for that
was found that the increasing of the motive pressure for the fixed evaporation parameters at such low level the motive parameters
geometry of ejector causes reflection in geometry of the supersonic may be thought as inadequate for operation at higher condensation
jet at the nozzle outlet [24,25]. When the motive pressure parameters. Note that such low evaporation parameters are not
increases then the cross-section of the supersonic jet at a certain needed frequently in industry where the ejector system can be
distance from the nozzle outlet also increases; this distance is often applied. The highest critical flow temperature tccrit3 = 29 °C for test
called as the hypothetical throat of the ejector. This affects the run No. 3 was reported. On the other hand, the mass entrainment
122 K. Śmierciew et al. / Applied Thermal Engineering 110 (2017) 115–125

Fig. 8. Parameters distribution in evaporator during experiments as a function of temperature of condensation for run no. 3: (a) pressure distribution, (b) saturation
temperature distribution.

Table 1 Table 2
Operating parameters of the system during start-up investigations. Operating conditions of the ejector refrigeration system.

pg (max) tgs pe (min) tes tcs pc-pe Run pg tgs tg pe tes Qg tcs (°C)
(MPa) (max) (MPa) (min) (variable) (max) no. (MPa) (°C) (°C) (MPa) (°C) (kW)
(°C) (°C) (°C) (MPa)
1 1.15 55.7 72.2 2.37 2.3 83.4 22.8–
Run no. 1 1.236 58.6 0.088 22.7 10.1–28.1 25.2
0.459 2 1.14 55.3 70.8 2.35 2.1 83.2 23.0–
Run no. 2 1.190 57.1 0.095 20.9 11.9–24.8 25.0
0.401 3 1.17 56.5 70.3 3.38 12.5 82.2 27.5–
Run no. 3 1.189 57.0 0.094 21.1 12.2–27.0 30.2
0.435 4 1.17 56.4 72.1 1.69 6.7 89.1 18.0–
Run no. 4 1.221 58.2 0.098 20.2 12.8–29.7 20.0
0.477 5 1.09 53.4 73.4 2.68 5.7 78.1 22.0–
24.5

ratio is the lowest in this case, Umin = 0.12. High critical tempera- in Section 3.1 showed that the ejector can produce very low pres-
ture might be result of high evaporation temperature, tes3 = 12.5 °C. sure, therefore there is a large pressure difference between nozzle
For high evaporation temperature or pressure the mass entrain- outlet and suction chamber (or evaporator). For such conditions
ment ratio at higher level might be expected. However, it must be nozzle might be over-expanded and oblique shocks might occur
pointed out, that the ejector was designed for evaporation param- decreasing the ejector efficiency. For all test runs the performance
eters corresponding to approximately +5 °C. Also, result presented line is steep in off-design operating regime.
K. Śmierciew et al. / Applied Thermal Engineering 110 (2017) 115–125 123

Fig. 9. Performance line U = f(tc).

Analogically, for performance line U ¼ f ðtc Þ characteristics with maximum Q_ emax = 36 kW. The coefficient of performance of
Q_ e ¼ f ðt c Þ and COP ¼ f ðtc Þ were shown in Figs. 10 and 11, respec- 0.30 and higher were achieved under reported tests excluding test
tively. Cooling capacity (Q_ e ) of the tested ejector was calculated as: run No. 3. Maximum cooling capacity Q_ emax and COPmax = 0.45 cor-
responding to the maximum mass entrainment ratio U, and mini-
Q_ e ¼ m
_ e  Dh e ð3Þ mum cooling capacity Q_ emax and COPmin = 0.12 corresponded to the
where m _ e is refrigerant mass flow rate, and Dhe is enthalpy differ- minimum mass entrainment ratio.
ence at the evaporator outlet and inlet. Coefficient of performance It is seen in Fig. 11 that COP for tes1 = 2.3 °C is less than that of
of the system was calculated as: tes2 = 3.4 °C, at on-design operating regime, despite the fact
that the motive temperature is the same for both runs,
Q_ e tgs1 = tgs2 = 55.7 °C. The reason is the evaporation temperature, for
COP ¼ ð4Þ the series S2 it was higher than for the series S1, namely tes1 = 2.3 °-
_
Q g þ Pp
C, and tes2 = 3.4 °C. Such conditions could be thought as more
where Pp is circulation pump input power. For analysis presented favourable for the ejector operation since the ejector has to cover
here the maximum motor input power of 3 kW was measured. the lower pressure difference at the same motive parameters. In
Shape and slope of presented in Figs. 10 and 11 lines are the that case the performance of the ejector, i.e. entrainment ratio
same as shown in Fig. 9. The ejector and testing stand were and COP increased. Note that for both runs (S1 and S2) transition
designed for cooling capacity of app. 20–22 kW. Motive heat was from on-design into off-design operating regime occurs at conden-
design as 80 kW, therefore coefficient of performance of 0.20 was sation temperature approximately 24.3 °C. On the other hand it is
expected. As it can be seen from Fig. 10 only for the test run No. also seen in Fig. 11 that for temperature 24.3 °C COP is much lower
3 required cooling capacity was not achieved, Q_ emin = 10 kW. For for the series S5 than for the series S1 and S2 despite the fact that
the other test runs at least 25 kW of cooling capacity was produced the evaporation temperature was higher for series S5 than for

Fig. 10. Performance line Qe = f(tc).


124 K. Śmierciew et al. / Applied Thermal Engineering 110 (2017) 115–125

Fig. 11. Performance line COP = f(tc).

Fig. 12. Performance line P = f(U).

series S1 and S2, namely tes5 = 5.4 °C. However, for the series S5, it It is seen in Fig. 12 that operation of the ejector system pro-
can be seen that the motive temperature is lower than for other ceeded typically for all of the test runs. Experimental results pre-
two compared series, namely tgs5 = 53.4 °C. As a result of such oper- sented in Fig. 12 not clearly shows the on-design operation
ating conditions the pressure difference for the motive nozzle conditions, therefore vertical part of performance lines were
between the inlet and outlet was lower, and as an effect the lower approximated on the basis of the results presented in Fig. 9. Com-
momentum for the motive vapour was produced. This was the rea- pression ratio achieved by the ejector was in the range 0.23–0.30.
son for decrease of the performance of the ejector. Note that for the
series S5 condensation temperature 24.3 °C lies in the off-design 4. Conclusions
operating regime. Under such conditions the ejector operation
was very limited as it was close to the malfunction point of the The results of the first experimental investigations of the ejector
ejector. refrigeration system operating with HFO-1234ze(E) were pre-
Performance of the ejector system is usually presented as a rela- sented in the paper. This fluid was selected on the basis of the anal-
tionship between the compression ratio versus mass entrainment ysis of the working fluids for ejector system with respect to
ratio, P ¼ f ðUÞ. This relation is shown in Fig. 12. Compression ratio Regulation of the European Parliament and the EU Council No.
was calculated using equation: 517/2014.
pc  pe The low temperature motive heat source of 90 kW was used in
P¼ ð5Þ investigation. The influence of the operating parameters such as
pg  pe
condensation and evaporation temperature for given motive tem-
where pc is condensation pressure, pg – generator pressure, pe – perature on the performance of the ejector refrigeration system
evaporator pressure. were presented and discussed.
K. Śmierciew et al. / Applied Thermal Engineering 110 (2017) 115–125 125

At first the results of limiting parameters were investigated, e.g. [7] H.K. Ersoy, S. Yalcin, R. Yapici, M. Ozgoren, Performance of a solar ejector
cooling-system in the southern region of Turkey, Appl. Energy 84 (2007) 971–
the minimum pressure which can be produce by the ejector for
983.
given motive parameters. It was found that for motive saturation [8] A. Selvaraju, A. Mani, Analysis of an ejector with environment friendly
temperatures at level 55 °C the ejector is able to produce pressure refrigerants, Appl. Therm. Eng. 24 (2004) 827–838.
corresponding to temperature 20 °C. For this condition was found [9] J. Chen, S. Jarall, H. Havtun, B. Palm, A review on versatile ejector applications
in refrigeration systems, Renew. Sustain. Energy Rev. 49 (2015) 67–90.
also that the critical temperature under on-design operating [10] G. Besagni, R. Mereu, F. Inzoli, Ejector refrigeration: a comprehensive review,
regime was in the range of 19–22 °C. Renew. Sustain. Energy Rev. 53 (2016) 373–407.
Secondly, the typical ejector investigations have been con- [11] S. Elbel, N. Lawrence, Review of recent developments in advanced ejector
technology, Int. J. Refrig. 62 (2016) 1–18.
ducted and performance lines according to the following relation- [12] D. Butrymowicz, K. Śmierciew, J. Karwacki, J. Gagan, Experimental
ships: U ¼ f ðt c Þ, Q_ e ¼ f ðtc Þ, COP ¼ f ðt c Þ, P ¼ f ðUÞ were analysed. investigations of low-temperature driven ejection refrigeration cycle
operating with isobutane, Int. J. Refrig. 39 (2014) 196–209.
The experimental investigations confirmed that the ejector cycle
[13] A.S. Rattner, S. Garimella, Low-source-temperature diffusion absorption
operating with HFO-1234ze(E) can effectively be driven by low refrigeration. Part I: Modeling and cycle analysis, Int. J. Refrig. (in press)
temperature heat source, e.g. lower that tg = 70 °C. Under this range (2015), http://dx.doi.org/10.1016/j.ijrefrig.2015.10.010.
[14] A.S. Rattner, S. Garimella, Low-source-temperature diffusion absorption
of motive temperature heat sources the ejector cycles can be con-
refrigeration: Part II: Experiments and model assessment, Int. J. Refrig. (in
sidered as truly competitive in comparison with most of the ther- press) (2016), http://dx.doi.org/10.1016/j.ijrefrig.2015.11.016.
mally driven refrigeration systems. [15] G. Besagni, R. Mereu, G. Di Leo, F. Inzoli, A study of working fluids for heat
On the basis of the experimental results it can be concluded that driven ejector refrigeration using lumped parameter models, Int. J. Refrig. 58
(2015) 154–171.
for the case of HFO-1234ze(E) as the working fluid the motive sat- [16] T. Zegenhagen, F. Ziegler, Experimental investigation of the characteristics of a
uration temperature at level approximately 55 °C ejector system jet-ejector and a jet-ejector cooling system operating with R134a as a
can be applied if required amount of cooling is 20–25 per cent of refrigerant, Int. J. Refrig. 56 (2015) 173–185.
[17] H. Wang, W. Cai, Y. Wang, J. Yan, L. Wang, Experimental study of the behavior
the motive heat source capacity. of a hybrid ejector-based air-conditioning system with R134a, Energy Convers.
The system was operating with COP higher than 0.30 for motive Manage. 112 (2016) 31–40.
temperature 56 °C and evaporation temperature 2–5 °C. For this [18] S. Unal, Determination of the ejector dimensions of a bus air-conditioning
system using analytical and numerical methods, Appl. Therm. Eng. 90 (2015)
cases of the critical flow temperature was found at level 24 °C, 110–119.
however. Moreover, HFO-1234ze(E) may be thought as prospective [19] S. Chen, G. Chen, L. Fang, An experimental study and 1-D analysis of an ejector
working fluid for low grade ejector refrigeration systems. Therefore with a movable primary nozzle that operates with R236fa, Int. J. Refrig. 60
(2015) 19–25.
future developments of the ejector refrigeration system operating
[20] K.O. Shestopalov, B.J. Huang, V.O. Petrenko, O.S. Volovyk, Investigation of an
with this fluid may be expected. experimental ejector refrigeration machine operating with refrigerant R245fa
at design and off-design working conditions. Part 2. Theoretical and
experimental results, Int. J. Refrig. 55 (2015) 212–223.
[21] C.-C. Wang, System performance of R-1234yf refrigerant in air-conditioning
References
and heat pump system: an overview of current status, Appl. Therm. Eng. 73
(2014) 1412–1420.
[1] M. Suozzo, J. Thorne, Market transformation initiatives: successes and [22] K. Smierciew, J. Gagan, D. Butrymowicz, J. Karwacki, Experimental
remaining challenges. Int. Energy Programme Evaluation Conf., Denver, investigations of solar driven ejector air-conditioning system, Energy Build.
Paper No. 010, 1999. 80 (2014) 260–267.
[2] L. Perez-Lombard et al., A review on buildings energy consumption [23] E.W. Lemmon, M.L. Huber, M.O. McLinden, NIST standard reference database
information, Energy Build. 40 (2008) 394–398. 23: reference fluid thermodynamic and transport properties-REFPROP, Version
[3] Regulation (EU) No 517/2014 of the European Parliament and of the Council on 9.1, National Institute of Standards and Technology, Standard Reference Data
fluorinated greenhouse gases and repealing Regulation (EC) No 842/2006. Program, Gaithersburg, 2013.
[4] K. Śmierciew, D. Butrymowicz, J. Gagan, Assessment of refrigerant selection for [24] T. Sriveerakul, S. Aphornratana, K. Chunnanond, Performance prediction of
ejection system driven by low-grade heat, in: 2016 Purdue Compressor steam ejector using computational fluid dynamics: Part 2. Flow structure of a
Engineering, Refrigeration and Air Conditioning and High Performance steam ejector influenced by operating pressures and geometries, Int. J. Therm.
Buildings Conferences, Purdue, USA, 2016. ID 2667. Sci. 46 (2007) 823–833.
[5] A. Arbel, M. Sokolov, Revisiting solar-powered ejector air conditioner – the [25] N. Ruangtrakoon, T. Thongtip, S. Aphornratana, T. Sriveerakul, CFD simulation
greener the better, Sol. Energy 77 (2004) 57–66. on the effect of primary nozzle geometries for a steam ejector in refrigeration
[6] J.M. Abdulateef et al., Review of solar-driven ejector refrigeration technologies, cycle, Int. J. Therm. Sci. 63 (2013) 133–145.
Renew. Sustain. Energy Rev. 13 (2009) 1338–1349.

You might also like