Ordering information
TZ 4 M 1 4 R
R Relay output
Control output
S SSR drive voltage output
C Current output(DC4-20mA)
※1
Power supply 2 24VAC/24-48VDC
4 100-240VAC 50/60Hz
TZ4SP/TZN4S
1 Event 1 output
1 Event 1 output
TZ4ST
2 Event 1 + Event 2 output
Auxiliary output
R Event 1 + PV transmission output(DC4-20mA)
1 Event 1 output
2 Event 1 + Event 2 output
Etc. R Event 1 + PV transmission output(DC4-20mA)
A Event 1 + Event 2 + PV transmission output(DC4-20mA)
T Event 1 + RS485 communication output
B Event 1 + Event 2+RS485 communication output
TZN4
S DIN W48×H48mm(terminal type)
M DIN W72×H72mm
TZ4/TZN4 W DIN W96×H48mm
H DIN W48×H96mm
L DIN W96×H96mm
Digit
4 9999(4 digit)
H-72
Dual PID Auto Tuning Control
Specifications (A)
Photo
electric
sensor
TZ4SP TZ4M TZ4W TZ4H TZ4L
Series TZ4ST
TZN4S TZN4M TZN4W TZN4H TZN4L (B)
Fiber
Power AC Power 100-240VAC 50/60Hz optic
sensor
supply AC/DC Power
※1
24VAC 50/60Hz / 24-48VDC
(C)
Allowable voltage range 90 to 110% of rated voltage Door/Area
sensor
Control
output
SSR 12VDC ±3V 30mA Max. (I)
SSR/
Current DC4-20mA (load 600Ω Max.) Power
controller
PV transmission - DC4-20mA (load 600Ω Max.)
(J)
Sub EVENT1 250VAC 1A 1a Counter
output EVENT2 - 250VAC 1A 1a
Communication - - RS485(PV/SV transmission, SV setting) (K)
Timer
Control type ON/OFF, P, PI, PD, PIDF, PIDS control
Display accuracy F.S. ±0.3% or 3℃, select the higher one (L)
Panel
Setting method Front push buttons meter
Dielectric strength 2,000VAC 50/60Hz for 1min. (between power source terminal and input terminal) (Q)
Stepper
Vibration 0.75mm amplitude at frequency of 10 to 55Hz(for 1min.) in each of X, Y, Z direction for 2 hours motor&
Driver&Controller
Relay Main output Mechanical: Min. 10,000,000 operations, Electrical: Min. 100,000 operations(250VAC 3A resistive load)
(R)
life cycle Sub output Mechanical: Min. 20,000,000 operations, Electrical: Min. 500,000 operations(250VAC 1A resistive load) Graphic/
Logic
panel
Insulation resistance Min. 100MΩ (at 500VDC megger)
(S)
Noise resistance ±2kV the square wave noise (pulse width: 1us) by the noise simulator Field
network
Memory retention Approx. 10 years (when using non-volatile semiconductor memory type) device
Approval
(U)
TZ4SP: TZ4W: Other
※1. AC/DC power type is only for TZ4SP, TZ4ST, TZN4M, TZ4L Series.
※Environment resistance is rated at no freezing or condensation.
H-73
TZN/TZ Series
Connections
※RTD: DPt100Ω(3-wire type), JPt100Ω(3-wire type) ※T.C(Thermocouple): K, J, R, E, T, S, W, N
※In case of Analog input, please use T.C(Thermocouple) terminal and be careful about polarity.
TZN4S
EV1 OUT 10 5 MAIN OUT
SOURCE:
250VAC SV2 IN ~ 100-240VAC
Max.5VDC SSR Current
1A 9 250㎂ 4 50/60Hz 5VA
B'
12
8 3 H
3 V
3 mA
T.C
B
11 MAIN OUT 2 2
7 2 250VAC 3A 1c
SENSOR C Resistive load
A L 12VDC ±3V DC4-20mA
6 1 30mA Max. Load 600Ω Max.
RTD
TZN4M
EV1 OUT 14 7 H
250VAC 1A N.O. MAIN OUT
13 6 C
250VAC 3A 1c
EV2 OUT N.O. Resistive load
250VAC 1A L MAIN OUT
12 5
(A+) SSR Current
B'
11 4 PV OUT
T.C B 16 SV2 IN RS485 DC4-20mA
7 7
10 Max.5VDC 3 (B-)
(Transmission output) V mA
SENSOR
A
15 250㎂ 6 6
9 2
RTD SOURCE 12VDC ±3V DC4-20mA
1 100-240VAC 50/60Hz 6VA 30mA Max. Load 600Ω Max.
24VAC 50/60Hz 8VA
24-48VDC 7W
SV2 IN
TZ4SP Max.5VDC
250㎂
PV OUT
TZ4ST DC4-20mA(Transmission output)
EV-2 OUT: 250VAC 1A
TZ4M
EV1 OUT 6 13 H
250VAC 1A MAIN OUT
5 12 C
250VAC 3A 1c MAIN OUT
EV2 OUT Resistive load
250VAC 1A 4 11 L SSR Current
B' (A+)
3 SV2 IN 10 PV OUT
T.C Max.5VDC RS485 DC4-20mA 12 12
B 2 250㎂ 9 (Transmission output) V mA
SENSOR (B-) 13 13
A 1 8
RTD SOURCE: 12VDC ±3V DC4-20mA
14 15 16 7 100-240VAC 30mA Max. Load 600Ω Max.
50/60Hz 6VA
H-74
Dual PID Auto Tuning Control
TZ4W/TZN4W MAIN OUT PV OUT (A)
250VAC 3A 1c DC4-20mA Photo
electric
Resistive load (Transmission output) sensor
H L RS485 RS485 SOURCE:
(A+) (B-) 100-240VAC (B)
C 50/60Hz 5VA Fiber
optic
sensor
MAIN OUT
17 16 15 14 13 12 11 10 9
SSR Current (C)
Door/Area
sensor
8 7 6 5 4 3 2 1 15 15
V mA
(D)
14 14 Proximity
N.O. N.O. B' B A sensor
RTD 12VDC ±3V DC4-20mA
EV1 OUT EV2 OUT SV2 IN 30mA Max. Load 600Ω Max. (E)
250VAC 250VAC Max.5VDC SENSOR Pressure
1A 1A 250㎂ T.C sensor
MAIN OUT
SV2 IN 5 14 C
250VAC 3A 1c (M)
Tacho/
Max.5VDC Resistive load
250㎂ 4 13 L 15 15 Speed/ Pulse
V mA meter
B'
(A+) PV OUT 14 14
3 12 DC4-20mA (N)
T.C RS485 (Transmission Display
B 12VDC ±3V DC4-20mA
2 11 (B-)
output)
30mA Max. Load 600Ω Max.
unit
SENSOR A
RTD
1 10 SOURCE (O)
100-240VAC 50/60Hz 6VA Sensor
9 24VAC 50/60Hz 8VA
※Only for TZ4L.
controller
24-48VDC 7W
(P)
Switching
(Q)
TZN4S 48
● Panel cut-out Stepper
motor&
Min. 55 Driver&Controller
<Bracket> 10 90
(R)
Graphic/
45 +0.6
Logic
0
panel
Min. 62
44.8
61
(S)
45 +0.6
0 Field
network
device
(T)
Software
84 ● Panel cut-out
TZN4M Min. 91
72 10 73
(U)
Other
68 +0.7
0
Min. 91
67
68 +0.7
0
H-75
TZN/TZ Series
46 +0.6
0
44.8
61
Min. 62
45 +0.6
0
TZ4ST 48 12 95
<Bracket>
44.8
61
※Since TZ4SP uses same identification plate with TZ4ST, the lamp does not work even though it has a EV2 output signal lamp.
68 +0.7
0
Min. 90
86
68
68 +0.7
0
TZ4W 108
96
● Panel cut-out
13 100 Min. 112
48
TZN4W 45 +0.6
0
Min. 50
44.8
108 92 +0.8
0
96
48
108
90
96
96
Min. 112
45 +0.6
0
H-76
Dual PID Auto Tuning Control
TZ4L TZN4L ● Panel cut-out (A)
Photo
electric
96 96 Min. 98 sensor
13 100
(B)
Fiber
optic
92 +0.8
sensor
0
Min. 106
(C)
Door/Area
108
108
92 +0.8 sensor
90
0
(D)
Proximity
sensor
(unit: mm)
(E)
Pressure
sensor
1 1 (G)
Connector/
Socket
2
3 9 2 10 (H)
8 3 Temp.
4 4 9 controller
5 5 8 (I)
SSR/
6 7 Power
controller
6 7
TZ4ST/TZ4SP TZ4M (J)
Counter
3 1
4 1 (K)
8 Timer
9 2
2
10 3 10 (L)
4 Panel
5 9 meter
6 7 5 8
(M)
11 6 7 Tacho/
Speed/ Pulse
meter
11
(N)
Display
1: Display Processing value(PV) (Red) 5: Mode key 9: Indicate EVENT 1 output unit
2: Display Setting value(SV) (Green) 6: Autotuning operation key 10: Indicate EVENT 2 output
3: Indicate SV2 operation 7: Setting keys 11: Procedure of setting key (O)
Sensor
4: Indicate Auto-tuning operation 8: Indicate control output operation controller
※Since TZ4SP uses same identification plate with TZ4ST, the lamp does not work even though it has a EV2 output signal lamp.
※There are no ( , ) Key in TZ4SP/TZ4ST/TZ4H/TZ4W and TZN4S/TZN4H/TZN4W. (P)
Switching
※Control output indicator(OUT) does not work when it is used as current output type. mode power
supply
(Q)
SV setting Stepper
motor&
Driver&Controller
1 Press any key among ( )key in 2 Press ( ) key to move the desired (R)
RUN mode, the right digit at SV digit. Graphic/
Logic
display flashes and it enters to (100→101→102→103→100) panel
SV setting. (S)
Field
network
device
(T)
Software
3 Press ( ), ( ) key to move 4 Press key to save the
the desired number (1 → 5). value and it controls with this (U)
set value. Other
※Above explanations are the example of TZ4M. In case of TZ Series. Use the Key in brackets for setting(changing).
There are no ,( )Key in TZN4S, TZ4SP and TZ4ST. It is not used for setting or changing the setting value.
H-77
TZN/TZ Series
Select ON1, changing setting value in the parameter 1 group and AT key in the front
ON1 panel cannot be changed.
※Press ( ) key and the right digit of SV display part flashes. Press ( ) or ( ) key and move to the desired digit.
Press ( ), ( ) keys to change SV and press MD key to complete the set. Press MD key again and it moves to next parameter.
※After completing setting at each parameter, press MD key for 3 sec. and it returns to RUN mode.
※If no key touched for 60sec., it will return to RUN mode automatically.
※ This parameter [ AL1, AL2, LBA, I, D, T, HYS, REST, RAPU, RAPD ] might not be displayed depending on other parameter settings.
H-78
Dual PID Auto Tuning Control
Run mode If pressing MD + key for 3sec. at once in RUN state, it will go to parameter 2 group. (B)
Fiber
MD + 3sec. optic
※2 Control ※1 sensor
Event 1 Event 2 Auto-tuning operating Temperature Scaling Scaling Decimal
Input type mode mode Alarm type type PID type type unit high limit low limit point
MD MD MD MD MD MD MD MD MD MD MD (C)
IN-T EU-1 EU-2 AL-T AtT PIDT O-FT UNIT H-SC L-SC DOT Door/Area
sensor
KCaH LBA LBA AL-A TVN1 PIdS HEAT ?C 1300 -100 0 (D)
Proximity
sensor
ECrL AL-4 AL-4 IN-T LOC ADRS BPS RAMP FS-L FS-H controller
(I)
SSR/
TCcH AL-5 AL-5 OFF 01 2400 OFF -100 1300 Power
controller
S PR 9600
(K)
Timer
NN
(L)
U TT Panel
meter
JPtH (M)
Tacho/
Speed/ Pulse
meter
JPtL IN-T Input type: Select from 19 type L-SC Set scaling low limit (include analog output)
(N)
EU-1 Event 1: Select from 9 type DOT Select decimal point position for Analog input Display
DPtH EU-2 Event 2: Select from 9 type FS-H Set the high-limit when retransmission output is applied. (20mA)
unit
AL-T Alarm type: Select from 4 type FS-L Set the low-limit when retransmission output is applied. (4mA)
DPtL (O)
Sensor
AtT Auto-tuning: Selectable TUN1 or TUN2. RAMP Able to set ON and OFF of Ramp function. controller
A--1 PIDT PID: Selectable PIDF or PIDS. BPS Set communication speed (P)
Switching
O-FT Selectable heat-function or cool-function ADRS Set communication address(01 to 99) mode power
supply
A--2 ※1
UNIT Temperature unit: ℃ or ℉ LOC The data cannot be changed when the lock key is ON
(Q)
H-SC Set scaling high limit (include analog output) Stepper
A--3 motor&
Driver&Controller
※Press ( ) key and the right digit of SV display part flashes. Press ( ) or ( ) key and move to the desired digit. (R)
Graphic/
Press ( ), ( ) keys to change SV and press MD key to complete the set. Press MD key again and it moves to next parameter. Logic
panel
※After completing setting at each parameter, press MD key for 3 sec. and it returns to RUN mode.
※If no key touched for 60sec., it will return to RUN mode automatically. (S)
Field
※1: It may not be displayed by input type switch. network
device
※2: This is displayed only for model with High/Low-limit of transmission output.
(T)
Software
Parameter Factory default Parameter Factory default Parameter Factory default Parameter Factory default
IN-T KCaH AL-T AL-A PIDT PIdS H-SC 1300
EU-1 AL-1 AtT TVN1 O-FT HEAT L-SC -100
EU-2 AL-2 RAMP OFF UNIT ?C LOC OFF
H-79
TZN/TZ Series
SW1 SW2
SW1:1 1 1 mA V SW2: V
SW1 SW2
SW1:2 2 2 mA V SW2: V
SW1 SW2
SW1:2 2 2 mA V SW2: mA
H-80
Dual PID Auto Tuning Control
Alarm (A)
Photo
electric
This unit has output for control and sub(alarm) output. Sub output is optional. (This alarm output is relay contact(1a) and sensor
operates regardless of output for control.) Alarm output operates when the temperature of target is getting higher or lower (B)
Fiber
than setting value. optic
sensor
Select one among 6 alarm operations [AL-1/2/3/4/5/6] of event 1, 2[EU-1, EU-2] at parameter 2 group and set alarm
temperature (deviation or absolute temperature) in AL1, AL2 alarm temperature[AL1, AL2] at parameter 1 group. (C)
Door/Area
sensor
● Since EU-1 and EU-2 operate separately, both EU-1 and EU-2 can be used as a high or low 2nd alarm operation.
● When selecting LBA or SBA function in EU-1, EU-2 of parameter 2 group, alarm cannot be operated. (D)
Proximity
sensor
OFF H ON OFF H ON
(N)
Absolute Display
PV SV SV PV If PV is higher than the absolute value, unit
AL-5 value high
90℃ 100℃ 100℃ 110℃ the output will be ON.
limit alarm
Absolute-value Alarm: Absolute-value Alarm: (O)
Sensor
Set as 90℃ Set as 110℃ controller
AL-A Standard alarm If it is an alarm condition, alarm output is ON. If it is a clear alarm condition, alarm output is OFF.
AL-B Alarm latch If it is an alarm condition, alarm output is ON and maintains ON status. (U)
Other
First alarm condition is ignored and from second alarm condition, standard alarm operates.
AL-C Standby sequence When power is supplied and it is an alarm condition, this first alarm condition is ignored and from the
second alarm condition, standard alarm operates.
If it is an alarm condition, it operates both alarm latch and standby sequence. When power is supplied
Alarm latch and
AL-D and it is an alarm condition, this first alarm condition is ignored and from the second alarm condition,
standby sequence
alarm latch operates.
H-81
TZN/TZ Series
Functions
Auto tuning [ AtT] Sensor Break Alarm [ SBA]
PID auto tuning function automatically measures the This function causes the sub output to turn on when the
thermal characteristics and response of the control system sensor line is cut or open. It is easier to check that whether
and then executes its value under high response & stability the sensor line is cut or not through buzzer or etc by
after calculating the time constant of PID required to control exterior sub output (relay contact).
optimum temperature.
●●For using SBA function, set SBA at EU-1 or EU-2 in
●●Execute the auto tuning function at initial time after
parameter 2 group and SBA output operates as EV1 OUT
connecting the controller & the sensor.
or EV2 OUT contact.
●●Execution of auto tuning is started when pressing AT key
for 3 sec. or more.
Loop Break Alarm [ LBA]
●●When the auto tuning is started, AT lamp will flash, and
when the lamp is OFF, this operation will stop. LBA function is to diagnose an abnormal temperature of
the control system. If the temperature of the control system
●●While the auto tuning function is executing, it is stopped
is not changed within ±2℃ during setting time of LBA, the
by pressing AT key for 5sec. or more.
LBA output will be ON.
●●When the power turns off or the stop signal is applied
Ex) When setting value(SV) is 300℃, process value(PV) is
while auto tuning function is executing, time constant of
50℃, this unit controls 100%. In this time if there is no
PID is not changed and it remembers the value before
change of system temperature, it recognizes Heater is
power turns off.
cut off then LBA output will be ON.
●●Time constant of PID selected by auto tuning function
●●LBA output can be selected at EV1 of the parameter 2
can be changed in parameter 1 group.
group.
●●It has two kinds of auto tuning mode auto tuning
●●If LBA output is not selected at event output, it will not be
operation is executed at setting value(SV) in TUN1 mode
displayed in parameter 1 group.
which is factory default. Auto tuning operation in TUN2
mode is executed in 70% of setting value(SV). Mode ●●Set range of LBA: 1 to 999 sec.
change is available in AtT of the parameter 2 group. ●●If thermal response of the control system is slow, LBA
value should be set to a high value.
(tun 1 mode) ●●LBA output operates when the manipulated value of the
Auto tuning time controller is 0% and 100%.In case the LBA output is ON,
℃
please check the following;
SV
① Short-circuit or cutting of the temp. sensor.
② Abnormal condition of the equipment
(magnet, sub-relay, etc.)
Time(t) ③ Abnormal condition of the load(heater, cooler)
④ Wrong-wiring or cutting of the other cables.
(tun 2 mode)
●●Once SBA is ON due to broken sensor, it will not reset,
℃ Auto tuning time although sensor is connected. In this case, turn off the
SV power then turn on again.
70% of SV Error
Time(t)
If error is occurred while the controller is operating,it will be
●●Execute the auto tuning function again periodically, displayed as follow.
because the thermal characteristics for the control object ●●LLLL is flashing when measured input temperature is
can be changed when the controller is used continuously lower than input range of the sensor.
for a long time. ●●HHHH is flashing when measured input temperature is
higher than input range of the sensor.
Sub output [ EU-1, EU-2]
●●OPEN is flashing when the input sensor is not connected
Sub output can execute as main control output and sub or its wire is cut.
function as well. There is one sub output in this unit.
●●This sub output is relay "1a" contact output.
●●1 mode can be selected among 7 kinds of alarm mode or
LBA operated when the heater line is cut, SBA operated
when the sensor line is cut.
●●The Sub output can be latched ON or automatically reset
depending on the alarm option mode selected.
●●When the sensor line or the heater line is cut, SBA or
LBA output turns on. This "Output on" status must be
reset by turning the power off.
H-82
Dual PID Auto Tuning Control
(A)
Photo
ON/OFF control is called two position control because When controlling temperature, two types of control (B)
Fiber
the output turns on when PV falls lower than SV and the characteristic are available as below. optic
sensor
output turns off when PV is higher than SV. One is when you need to minimize the time which PV
This control method is not only for controlling temperature, reaches to SV as like(Fig. 1). The other is when you need (C)
Door/Area
but also it is basic control method for sequence control. to minimize overshoot even though the reaching time(PV sensor
●●If you set value P as )0 in parameter 1 group, ON/OFF to SV) is slow(Fig. 2).
(D)
control will operate. ●●There are high-speed response type and low-speed Proximity
sensor
●●There is a programmable temperature difference response type built in this unit. Therefore user can select
between ON and OFF in ON/OFF control, if difference each function according to their application. (E)
Pressure
is too small, then hunting(chattering) can occur. ●●You can select dual PID control function in parameter 2 sensor
●●Temperature difference can be set in HYS mode of group. It is selectable PIdFor PIdS in PIDT mode.
(F)
parameter 1 group. Setting range is 1 to 100(or 0.1 to PIdF(high-speed response type) Rotary
encoder
100.0). This mode is applied to machines or systems which
●●HYS mode is displayed when P value is )0, but HYS will require high-speed response. (G)
Connector/
not be displayed, and then jump if P value is not )0. Socket
(Fig. 1) PV
●●This ON/OFF control should not be applied when S (H)
equipment(cooling compressor) to be controlled can be SV Temp.
controller
damaged by frequent ON and OFF. ※ t : Reaching time
S : Overshoot
●●Even if ON/OFF control is stable status, the hunting can SV: Setting value
(I)
SSR/
be occurred by setting value in HYS or capacity of the PV: Process value
Power
controller
heater or response characteristic of the equipment to t
be controlled or installing position of the sensor. Please PIdF (J)
Counter
consider above points to minimize the hunting when
designing the system. PIdS (low-speed response type)
It is PID Slow, used to minimize overshoot even though (K)
Timer
the response is slow. For control temperature of oil,
Manual reset [ REST]
plating machine have a possibility of fire with overshoot,
Proportional control has deviation because rising time is PIdS (limit over) should be used.
(L)
Panel
not same as falling time, even if the unit operates normally. meter
(Fig. 2)
Manual reset function is used at proportional control mode (M)
SV Tacho/
only. PV Speed/ Pulse
meter
※ t : Reaching time
●●If set RESTfunction in parameter 1 group, the manual SV: Setting value (N)
reset will run. t PV: Process value Display
unit
REST value should be smaller. Please select mode according to control system. (P)
Switching
●●REST setting method according to result of control. mode power
H-83
TZN/TZ Series
Cool / Heat function [ O-FT] Ramp function [ RAMP]
Generally there are two ways to control temperature, one Ramp function is to delay the rising time or falling time of
(heat-function) is to heat when PV is getting down(heater). temperature. If you change setting value at stable state of
The other(cool-function) is to cool when PV is getting control, it forces to rise or fall the temperature of control
higher (freezer). system during setting time at RAMP, RAPD in parameter 1
These functions are operating oppositely when it is ON/ group.
OFF control or proportional control. But in this case PID If RAMP is not ON in parameter 2 group, RAPU, RAPD will
time constant will be different due to PID time constant not be displayed in parameter 1 group.
will be decided according to control system when it is PID
●●Set RAMP is ON in parameter 2 group for using ramp
control.
function.
●●Cool-function and heat-function can be set at Parameter 2
●●Set the rising time and falling time at RAPU mode and
group.
RAPD mode of parameter 1 group.
●●Cool-function [ COOL] and heat-function [ HEAT] must
●●Ramp function will be operating when changing the set
be set correctly according to the application, if set as
value at stable control status or supply the power again
opposite function, it may cause a fire. (If set cool-function
after the power was removed.
[ COOL] at heater, it will be maintained ON and it may
cause a fire.) ●●The setting range of rising and falling time is 1 to 99
minute.
●●Avoid changing heat-function to cool-function or cool-
function to heat-function when the unit is operating. Ramp rising[ RAPU] (delay of rising time)
●●It is impossible to operate both function at once in this
Control temperature when
unit. Therefore, only one function should be selected ramp function is not used
only. Changing
●●Factory default setting is heat-function [ HEAT]. SV
Initial SV
SV2 function [ SU-2]
Control temperature
If using SV2 function, it changes the temperature of control when ramp function is used
system to the second setting value by external relay
contact signal. tu tu
It can change the setting value as sequentially by relay
contact without key operation. RAPU RAPU
setting time setting time
In this case, if you set the second setting value It controls falling temperature as like above.
higher than setting value, temperature will rise fast.
Therefore, after installing a micro-switch in order to ※ RAPD time cannot be shorter than falling time(td) of
detect the door Open/Close and connect it to SV2 (the temperature when Ramp function is not used.
second setting value should be higher than SV) then
it controls temperature of oven efficiently.
H-84
Dual PID Auto Tuning Control
Input correction [ IN-B] Output connections (A)
Photo
electric
Input correction is to correct deviation occurred from For more information about output, refer to the H-139 page. sensor
temperature sensor such as thermocouples, RTD, Analog
sensor etc. If you check the deviation of every temperature
● Application of relay output type (B)
Fiber
A optic
sensor precisely, it can measure temperature accurately. TZ Series sensor
●●When you set the Input revise value, you may need Keep power relay as far away as possible from TZ/TZN
to record it, because it will be useful when performing (F)
Series. If wires length of A is short, electromotive force Rotary
maintenance. occurred from a coil of magnet switch & power relay may
encoder
●●In case of measuring or controlling humidity & pressure, condenser 104(630V) across coil of the power relay " " to
flux, etc, it uses the proper converter which is converting protect electromotive force. (H)
Temp.
controller
the measuring value to DC4-20mA or 1-5VDC or 0-10VDC. ● Application of SSR output type
(I)
TZ Series SSR SSR/
Equipment Analog output + Power
to be Converter controller
controlled 1-5VDC I
0-10VDC Voltage L Power
N O
(J)
DC4-20mA output P Counter
terminal A Load
U D
●●To use analog output of converter as controller input, T power
- (K)
select the input type as same as analog output Timer
conditions. (This should be operated in power-off status.) ※SSR should be selected by the capacity of load,
●●This unit has the mode for the converter built-in. otherwise, it may short-circuit and result in a fire. Indirect (L)
Panel
●●Please select A--1(0-10VDC) or A--2(1-5VDC) or A--3 heated should be used with SSR for efficient working. meter
(DC4-20mA) in selection mode of input in parameter 2 group. ※Please use a cooling plate or it may cause the capability (M)
Tacho/
●●Set the input value by High scale[ H-SC] and Low scale [ deterioration, breakdown of SSR for a long usage. Speed/ Pulse
meter
L-SC] mode.
● Application of current output(DC4-20mA) (N)
●●Please connect the analog output of the converte to the Display
temperature sensor terminal of the controller. Please be TZ Series Power controller unit
※It is important to select SCR unit after checking the capacity (Q)
Temperature of the load. Stepper
motor&
controller Driver&Controller
Pressure ※If the capacity is exceeded, it may cause a fire.
IN-Tsetting (R)
Pressure : A--3 Graphic/
Control
system
sensor
Converter
DC4-20mA
H-SCsetting ● Application of transmission output(DC4-20mA) Logic
panel
(0 to 100kg) : 100 Recording instrument
L-SCsetting TZ Series /Panel meter (S)
Field
:0 + + network
device
Feedback Tranmission
output DC4-20mA IN
(T)
terminal Software
- -
(U)
Other
● Application of communication output(RS485)
TZ/TZN Series Converter PC
+ RS485
Communi RxD RxD
cation
output IN TxD TxD
terminal Gnd Gnd
-
H-85
TZN/TZ Series
H-86
Dual PID Auto Tuning Control
● Write of setting value ● Others: In case of no response of ACK (A)
Photo
In case setting value is -100 ① When the address is not the same after receiving STX. electric
sensor
A S E F ② When receiving buffer overflow is occurred.
C T 0 1 W D S 0 Symbol 103 102 101 100 T S ③ When the baud rate or others communication setting (B)
Fiber
K X X C
value are not the same. optic
sensor
A S E B
C T 0 1 W D S 0 - 0 1 0 0 T C ● When there are no ACK response (C)
K X X C
① Check the status of lines Door/Area
sensor
B
06 02 30 31 57 44 53 30 2D 30 31 30 30 03 C ② Check the communication condition(Setting value)
C ③ When assuming the problem is due to noise, try to (D)
Proximity
operate communication 3 times more until recovery. sensor
Proper usage
(F)
Rotary
encoder
drive voltage) after separating output line from the unit. ●●The switch or circuit-breaker should be installed near by
(J)
users.
But, the out lamp is not operated for DC4-20mA Counter
available to display room temperature.) ●●In case of making power line and input signal line close,
line filter for noise protection should be installed at power (O)
● In case of indicating ERR0 in display line and input signal line should be shielded.
Sensor
controller
This Error message is indicated in case of damaging ●●Keep away from the high frequency instruments.(High (P)
inner chip program data by outer strong noise. frequency welding machine & sewing machine, big Switching
mode power
In this case, please send the unit to our after service capacitive SCR controller) supply
center after removing the unit from system. ●●If you want to change the input sensor, reset switches (Q)
Stepper
Noise protection is designed in this unit, but it does not (SW1, SW2) according to each input specification after motor&
Driver&Controller
stand up strong noise continuously. If bigger noise than power off. Turn on power and then set sensor mode by
(R)
specified(Max. 2kV) flows in the unit, it can be damaged. front keys at second flow chart. Graphic/
Logic
●●This SSR and current of this controller are insulate from panel
Installation Category Ⅱ.
H-87