You are on page 1of 5

ASME PTC 4-2013

MoFg 2 MoDFg (approximately ½°F/1 in. Wg fan pressure rise2) may


DVpH 2O 5 100 , % H 2 O dry be considered to establish the fan discharge tempera-
MoDFg
(5-12-20) ture in the design stage.
When air preheating coils are utilized and the energy
where
is supplied from outside the envelope, the entering air
C1 5 5.2023 lbf/ft2/in.wc (U.S. Customary), 1.0 J/m3 temperature is the temperature leaving the air preheat-
Pa (SI)
ing coils. When the energy to an air preheating coil is
C2 5 27.68 in. wg/psi (U.S. Customary), 1.0
supplied from within the envelope (steam from the
Pa/Pa (SI)
steam generator), the entering air temperature is the
C3 5 459.7°F (U.S. Customary), 273.2°C (SI)
temperature entering the air preheating coils. Refer to
DVpH2O 5 percent H2O in flue gas, dry basis,
location 8 in Figs. 1-4-1 through 1-4-7.
% volume
When there is more than one fan of the same type,
MoDFg 5 moles dry gas. Refer to eq. (5-11-18) for
such as two forced draft fans, it is normally sufficiently
calculation.
accurate to assume balanced airflows between the fans
MoFg 5 moles wet gas. Refer to eq. (5-11-28) for
and use the arithmetic average of the air temperatures
calculation.
in each stream. When there is evidence of unbalance,
MwDFg 5 molecular weight of dry flue gas, lbm/
weighted averages should be used.
mole (kg/mole)
When there is more than one source of air entering
MwFg 5 molecular weight of wet flue gas, lbm/
at different temperatures, the average entering air tem-
mole (kg/mole)
perature must be determined. The general philosophy
Pa 5 barometric pressure, psia (Pa). To con-
for determining the mass fraction of individual streams
vert in. Hg to psia, divide by 2.0359.
is that all air streams may be measured or some streams
static pressure of flue gas at point z,
PFgz 5 
may be measured (and/or calculated by energy balance)
in. wg (Pa)
and the balance calculated by difference from the total
R 5  universal molar gas constant, 1,545 ft
airflow (calculated stoichiometrically). It should be noted
lbf/lbm mole R (8 314.5 J/kg mole K)
that some amount of air (usually not more than 2% or 3%
Rk 5 specific gas constant for gas k,
at full load) enters the unit as leakage through the set-
ft  lbf ¥ J ´ ting and the actual temperature is indeterminate. Unless
¦ µ
lbm  R § kg  K ¶ otherwise specified or agreed to by the parties to the test,
temperature of flue gas at point z,
TFgz 5  the infiltration air is considered to enter the unit at the
°F (°C) same temperature as the measurable air streams and the
uncertainty accounted for in the measurement systematic
uncertainty. Typical examples of units with multiple air
5-13 AIR AND FLUE GAS TEMPERATURE sources are pulverized-coal-fired units with cold primary
air fans (TA8A) or pulverizer tempering air supplied from
5-13.1 TRe, Reference Temperature, °F (°C)
the environment (TA5). The weighted average air temper-
The reference temperature is the datum tempera- ature entering the unit, TMnAEn, shall be calculated.
ture to which streams (e.g., air, fuel, sorbent, and flue
gas) entering and leaving the steam generator enve- TMnAEn 5 MFrAz1 TAz11 MFrAz2 TAz2{
lope are compared for calculation of sensible heat
1 MFrAzi TAzi , 8F (8 C)
(5-13-1)
credits and losses. The reference temperature for this
Code is 77°F (25°C) and is not related to any spe- When the entering air temperature at the various loca-
cific stream temperature. The energy credit will be tions differs significantly, it is more correct to determine
negative for any stream entering the steam generator the average entering air temperature from the average
envelope at a temperature lower than the reference entering enthalpy of the entering air.
temperature.
HMnAEn 5 MFrAz1 HAz11 MFrAz2 HAz2{
5-13.2 TMnAEn, Average Entering Air Temperature,
1 MFrAzi HAzi , Btu/lbm (J/kg)
°­ F (°C) (5-13-2)
The air temperature entering the steam generator where
envelope is required to calculate the credit due to the HAz 5 enthalpy of wet air at temperature TAz,
difference between the entering air temperature and Btu/lbm (J/kg)
the reference temperature, TRe. The air temperature HMnAEn 5 average enthalpy of wet air entering the
entering the fan(s) is usually taken as the design ambi- boundary, Btu/lbm (J/kg). The average
ent condition but may be some other specified condi-
tion such as when the fan inlets are supplied by air 2  The temperature rise above is based upon a fan efficiency of
from within the building. The fan compression energy approximately 75% and an air density of 0.075 lbm/ft3.

87
ASME PTC 4-2013

5-15.4 QpBSlf, Sulfation Credit, Percent 5-15.6 QrBSb, Sensible Heat in Sorbent Credit,
Sulfation is the reaction of sulfur dioxide (SO2) with Btu/hr (W)
calcium oxide (CaO) and oxygen to form calcium sulfate QrBSb 5 MrSb HSbEn, Btu/hr (W)(5-15-7)
(CaSO4). The reaction is exothermic.
where
MpSF
QpBSlf 5 MFrSc HrSlf , %(5-15-4) HSbEn 5 enthalpy of the sorbent entering the steam
HHVF generator envelope, Btu/lbm (J/kg)
MrSb 5 mass flow rate of sorbent, lbm/hr (kg/s)
where
HrSlf 5 heat generated in the reaction of sulfur
dioxide, oxygen, and calcium oxide to 5-15.7 QrBWAd, Energy Supplied by Additional
form calcium sulfate per pound of sulfur Moisture Credit, Btu/hr (W)
capture, 6,733 Btu/lbm (15 660 kJ/kg) Typical examples of additional moisture are sootblow-
MFrSc 5 mass fraction of sulfur capture, lbm/lbm ing and atomizing steam.
(kg/kg) 5 ¤ MrStEnz
QrLClh5
QrBWAd MrSbk MFrClhk
(HStEnzHrk , Btu/hrBtu/hr
– HWRe), (W) (W)
(5-15-8)
5-15.5 QrBX, Auxiliary Equipment Power Credits, where
Btu/hr (W) HStEnz 5 enthalpy of additional moisture entering
Typical auxiliary equipment includes pulverizers, gas the envelope, Btu/lbm (J/kg)
recirculating fans, hot primary air fans, and boiler circu- HWRe 5 enthalpy of water at the reference tem-
lating pumps. Note that credits shall not be calculated perature, Btu/lbm (J/kg)
for forced draft fans, cold primary air fans, and other MrStEnz 5 mass flow rate of additional moisture,
equipment when credits are calculated based on the lbm/hr (kg/s) at location z
measured fluid temperature exiting the equipment. For
example, when a credit is calculated for entering air in 5-15.8 Conversion of Credits on Rate Basis to Percent
accordance with para. 5-15.1, the energy added by the Input Fuel Basis
forced draft and primary air fans is included; thus, add- The credit calculated on a rate or unit of time basis
ing the credit for fan power would be accounting for the may be used to calculate efficiency directly. If the credit
energy added twice. on a percent input from fuel basis is desired, it may be
calculated after completion of the efficiency calculations
5-15.5.1  For Steam Driven Equipment using the calculated fuel input.

MrStX ( HStEn 2 HStLv) EX QrBk


QrBX 5 , Btu/hr (W) QpB 5100 ,% (5-15-9)
100 QrF
(5-15-5)
where 5-16 UNCERTAINTY
EX 5  overall drive efficiency, percent; includes
Subsection 5-2, Measurement Data Reduction, dis-
turbine and gear efficiency
cussed calculation of the standard deviation of the mean
HStEn 5 enthalpy of the steam supplied to drive the
and degrees of freedom for individual parameters. This
auxiliaries, Btu/lbm (J/kg)
Section presents calculations for overall standard devia-
HStLv 5 enthalpy at the exhaust pressure and the
tion of the mean and degrees of freedom for the ran-
initial entropy of steam supplied to drive
dom uncertainty. This Section also presents calculation
the auxiliaries, Btu/lbm (J/kg)
methods for sensitivity coefficients and the combina-
tion of random and systematic components into overall
5-15.5.2  For Electrically Driven Equipment
test uncertainty. For post-test uncertainty calculation,
EX all steam generator performance calculations must be
QrBX 5 QX C1 , Btu/hr (W) (5-15-6)
100 complete prior to the beginning of the uncertainty calcu-
lations presented in this Section. The uncertainty calcula-
where tions presented in this Section, as well as those presented
C1 5 3,412 Btu/kWh in para 5-2.4, can be used for pretest as well as post-test
EX 5 overall drive efficiency, percent; includes such uncertainty analysis.
items as motor efficiency, electric and hydrau- The pretest uncertainty analysis can provide impor-
lic coupling efficiency, and gear efficiency tant information and reduce the effort required to calcu-
QX 5 average power, kW late uncertainty after completion of a performance test.

97
ASME PTC 4-2013

5-18.9 Miscellaneous Efficiency Corrections corrected density will normally be very


close to the test density, DnAFg, and this
Other minor losses and/or credits that are measured
correction can usually be disregarded.
should be reviewed by the parties to the test and agree-
The density correction is included if
ment reached as to whether corrections to the efficiency
the density at the test conditions is sig-
are applicable.
nificantly different from the density cor-
rected to design conditions.
5-18.10 Corrected Input–Output Efficiency
Ht 5 height between the pressure locations
When efficiency is determined by the Input–Output [i.e., the difference in elevation between
method, the test result is corrected to the standard or the downstream and upstream pressure
design conditions by adding the difference between the locations, ft (m)]. Ht will be positive if
corrected efficiency and test efficiency (both as calculated the fluid is flowing upward.
by the energy balance method) to the Input–Output test MrAFg 5 mass flow rate of air or flue gas for test
results. Design boundary conditions (such as entering conditions, lbm/hr (kg/s)
air and exit gas temperatures) shall be used if they are MrAFgCr 5 corrected mass flow rate of air or flue
not measured. The most significant corrections are typi- gas, lbm/hr (kg/s)
cally fuel analysis, entering air temperature and exit gas PDiAFg 5  measured air resistance or draft loss,
temperature corrected for entering air temperature (for in. wg (Pa)
unit with air-to-gas heat exchangers). Correcting for the PDiAFgCr 5 corrected air resistance or draft loss,
test fuel versus the design fuel requires that the ultimate in. wg (Pa)
analysis be determined for the test fuel as well as the Se 5 stack effect or difference in static pres-
heating value. For units with air-to-gas heat exchang- sure between the air/gas side of boiler
ers, if the entering air temperature is measured, the exit and surrounding ambient air. Se will be
gas temperature (expected temperature if not measured) negative if the fluid is flowing upward.
should be corrected in accordance with para. 5-18.2.
Any other corrections discussed above can be applied if The pressure drop characteristics of each system must
measurements of necessary parameters are made. be examined in detail, and a detailed pressure drop
correction procedure for the specific system must be
5-18.11 Air and Gas Resistance developed. The above general pressure drop equation
may not be applicable for all equipment (pulverizers,
The measured resistance shall be corrected to stand- for example) and systems (for example, where pressure
ard or design conditions for the difference in mass flow drop is controlled, such as cyclone furnaces).
of the flowing fluid and the density of the fluid between
the test condition and the conditions corrected to design.
5-18.12 Steam or Water Pressure Loss
The general equations for correcting air resistance or
draft loss are The general equations for correcting steam/water
pressure drop between the test and design or contract
¨ 2
¥ MrAFgCr ´ ¥ DnAFg ´ ·
PDiAFgCr 5 C1 ©  PDiAFg 2 Se ¦ 1Se ¸ , conditions are as follows:
§ MrAFg µ
¶ § ¦ DnAFgCr µ

©ª ¸¹
2
¥ DnSt ´ ¥ MrStDs ´
in. wg (Pa) PDiStCr 5  PDiSt 2 C13 Ht 3 DnSt ¦
(5-18-15) § DnStDs µ¶ ¦§ MrSt µ¶
1 C13 Ht 3 DnStDs 2 VhCr , psi (Pa)
2.31 (5-18-17)
Se 5 C 2 Ht  DnAFg 2 DnA , in. wg (Pa)
12 where
(5-18-16)
C1 5  unit conversion factor, 0.00694 for psi
where (4.788026E101 for Pa)
C1 5  unit conversion factor, 1.0 for in. wg DnSt 5 density of the steam/water at the test con-
(2.4884E102 for Pa) ditions, lbm/ft3 (kg/m3)
C2 5  unit conversion factor, 1.0 for in. wg DnStDs 5 density of the steam/water at the design
(2.4884E102 for Pa) conditions, lbm/ft3 (kg/m3)
DnA 5  density of ambient air in vicinity of Ht 5  height between the pressure locations
pressure measurement, lbm/ft3 (kg/m3) [i.e., the difference in elevation between
DnAFg 5 density of air or flue gas, lbm/ft3 (kg/ the downstream and upstream pressure
m3). For the furnace shaft, use a value of locations, ft (m)]. Ht will be positive if the
0.0125 lbm/ft3 (0.20 kg/m3). fluid is flowing upward.
DnAFgCr 5 density of air or flue gas corrected to MrSt 5 mass flow rates of the steam/water at the
design conditions, lbm/ft3 (kg/m3). The test condition, lbm/hr (kg/s)

107
ASME PTC 4-2013

MrStDs 5 mass flow rates of the steam/water at the (c) the test main steam and reheat mass flow rates
design condition (for feedwater flow and utilized to calculate actual absorptions are corrected for
intermediate superheater flows, calcu- offdesign load by multiplying by the ratio of the design
lated based on the corrected spray water main steam flow divided by the test main steam flow,
flow), lbm/hr (kg/s) MFrStCr.
PDiSt 5 the measured pressure drop, psi (Pa) (d) main steam temperature and desuperheater spray
PDiStCr 5 the corrected pressure drop, psi (Pa) for once-through steam generators are not functions of
VhCr 5  velocity head correction (if applicable) surface arrangement, and corrections are not necessary.
calculated as follows: Main steam temperature is a matter of steam genera-
2 2 tor controls and should be acknowledged as achievable
1 ¨¥ MrStDs ´ ¥ MrStDs ´
VhCr 5 C2 © -

unless there are other limiting design considerations.


DnSt ª¦§ Aid µ¶ ¦§ AidDs µ¶ (e) certain designs, such as divided gas flow units,
¥ MrStDs ´· may require test and/or correction procedures not
1 VhCf ¦ ¸ , psi (Pa) addressed by this Code (a simplified approach for
§ AidDs µ¶ ¹
divided gas flow units is presented below).
(5-18-18) Actual and design required superheat and reheater
where absorptions are defined below. The main steam and
Aid 5  area of the pipe where pressure tap is reheat steam mass flow rates used to calculate actual
installed, ft2 (m2) absorptions are corrected for off-design main steam
AidDs 5 area of the pipe at the contractual terminal flow by multiplying the test main steam/reheat steam
point, ft2 (m2) flow by the ratio of the design main steam flow divided
C2 5  unit conversion factor, 8.327E–12 for psi by the test main steam flow (MFrStCr). The resulting
(5.741E–8 for Pa) absorption term generally referred to as “actual absorp-
VhCf 5 loss coefficient for the change in cross section tion” above is referred to as corrected absorption in the
geometry involved based on the diameter following Sections. While a second stage of reheat is not
of the pipe at the terminal point. Parties to addressed directly, the same principles apply as for the
test to agree upon value based on geometry first stage of reheat.
involved utilizing fluid flow reference text.
5-18.13.1  Superheater Absorption Corrected, QrShCr.
The measured pressure differential across a steam gener- The superheater absorption corrected for design main
ating unit or a portion of the unit shall be corrected to stand- steam flow is calculated from
ard or design conditions due to the difference in mass flow QrShCr 5 MrSt32Ds (HSt32 – HSt31) + MrW25 (HSt31
of the flowing fluid and the specific volume between the test – HW25) + MrSt46A (HSt46A – HSt31), Btu/hr (W)
condition and the design conditions. A correction for veloc- (5-18-19)
ity pressure may also be required if the static pressure meas- where
urement tap is located at a point with a cross-sectional area MrSt32Ds5 design main steam flow, lb/hr (kg/s)
different from the terminal point for the guarantee. MrSt46A 5 superheater extraction flow for the test
conditions, lb/hr (kg/s)
5-18.13 Steam Temperature and Desuperheating MrW25 5 desuperheating water flow for the test
Spray conditions, lb/hr (kg/s)
Steam temperature and desuperheating spray guar-
antees shall be evaluated based on actual and design 5-18.13.2  Required Superheater Absorption, RqQrSh. 
superheater (and reheater if applicable) absorptions The required superheater absorption for the design main
rather than actual temperature due to potential devia- steam flow is calculated from
tions from the target steam temperature during the test RqQrSh 5 MrSt32d (HSt32d 2 HSt31Cr)
and/or deviations from the design cycle conditions. The 1 MrSt46Ad (HSt46A 2 HSt31Cr), Btu/hr (W)
actual main steam and reheat mass flow rates utilized to (5-18-20)
calculate actual absorptions are corrected for off-design
where
test conditions. In general
HSt31Cr 5 enthalpy of saturated steam calculated
(a) the steam temperature shall be evaluated by
from the design superheater outlet pres-
comparing the actual superheater/reheater absorp-
sure and corrected superheater pressure
tion to the design required superheater/reheater
drop
absorption.
HSt46A 5 enthalpy of auxiliary or extraction steam
(b) desuperheating spray shall be evaluated based
at the test conditions, Btu/lbm (J/kg)
on the calculated spray required for the actual versus
design required superheater/reheater absorption. Other terms are based on design conditions.

108
ASME PTC 4-2013

QrF 5 MrF  HHVF , Btu/hr ( W )  (D-3-2) for hFG at 778F (258C) and 1 psia (0.01 MPa) (the partial
pressure of water vapor in the combustion gas at one
where
atmosphere) for solid and liquid fuels is 1,050 Btu/lbm
HHVF 5 higher heating value of fuel, Btu/lbm
(2 422 kJ/kg). Calculation of LHV from HHV is then
(J/kg). Refer to subsection 5-8.
MrF 5 measured mass flow rate of fuel, lbm/hr
 H 2F  8.937  H 2OF 
(kg/s) LHV 5 HHV  C1   , Btu/lbm (kJ/kg)
 100 
QrF 5 heat input from fuel, Btu/hr (W)
QrB 5 summation of credits, Btu/hr (W) basis. (D-4-1)
Refer to Section 5 for the general method where
of calculation. For the credits calculated on C1 5 1,050 Btu/lbm (2 442 kJ/kg)
a percent input from fuel basis, multiply H2F 5 the quantity of H2 in the fuel, % mass
by (QrF/100) to convert to Btu/hr (W). H2OF 5 the quantity of H2O in the fuel, % mass
Below are supplementary comments on the
calculation of credits that are not measured For gaseous fuels, the LHV should be calculated based
directly. on the LHVs specified for the individual gas fuel con-
stituents in ASTM D3588.
The credits due to heat in entering dry air (QrBDA) It is recognized that calculation of LHV (and fuel effi-
and moisture in entering dry air (QrBWA) require the ciency) is dependent upon the temperature at which the
mass flow rate of dry air. The mass flow rate of dry test is conducted. However, the difference in the cal-
air is calculated stoichiometrically from the ultimate culated LHV due to the difference between 77°F (25°C)
fuel analysis and unburned carbon in the refuse (refer and the temperatures of the laboratory test is minor and
to Section 5 and the Combustion Calculation Form, within the uncertainty of the measured HHV.
Nonmandatory Appendix B). For units that do not LHV will be on the same basis, constant pressure or
utilize sorbent for reduction of sulfur emissions, it may constant volume, as HHV.
be necessary to calculate unburned carbon in the refuse The systematic uncertainty of the LHV must consider
(refer to the Unburned Carbon in Refuse Calculation the uncertainty of determining the quantity of hydrogen
Form, Nonmandatory Appendix A). For units that do and moisture in the fuel as well as systematic uncertainty;
use sorbent, it will be necessary to calculate the mass however, the additional uncertainty is usually minimal.
fraction of sulfur capture as well as the unburned carbon Efficiency on a lower heating value basis is calculated
in the refuse (refer to the Sorbent Calculation Form, by substituting the lower heating value for the higher
Nonmandatory Appendix A). The credit due to sulfation heating value in all computations. Since the LHV is
(QrBSlf) is calculated from the mass fraction of sulfur calculated by reducing the fuel HHV by the latent heat
capture that is calculated above. The use of sorbent also of vaporization of the water formed from the combus-
impacts the mass flow rate of dry air. tion of the H2 in fuel and the water content of solid or
liquid fuels, the method of calculating the LHV losses
D-4 EFFICIENCY ON A LOWER HEATING VALUE, due to water from fuel are different depending upon
LHV, BASIS whether calculated on a HHV or LHV basis. The energy
loss on an HHV basis is based on the difference in the
This Code uses the higher heating value of the fuel enthalpy of steam at the exit gas temperature, HStLvCr,
as the preferred method to determine fuel energy input. and the enthalpy of water, HWRe, at the reference
This Section explains how to compute efficiency on a temperature. The energy loss on an LHV basis is based
lower heating value (LHV), or net calorific value, basis. on the difference in the enthalpy of water vapor, at the
Refer to para. 3-1.2 regarding the disadvantages of exit gas temperature, HWvLvCr, and the enthalpy of
expressing efficiency on a lower heating value basis. water vapor, at the reference temperature, HWvRe. Thus,
It is necessary to calculate LHV from the measured HHV. the loss due to water formed from the combustion of H2
There is no universally accepted standard for calculation on an LHV basis, QpLH2FLHV, is calculated per the fol-
of LHV; the constant used for heat of combustion and the lowing equation:
temperature used to determine the latent heat of vaporiza-
tion (hFG) vary between references. Some published meth- QpLH 2FLHV 5 100 MqWH 2F ( HWvLvCr  HWv Re) HHV LHV, %
ods are incorrect for SOLID OR LIQUID fuels that contain (D-4-6)
water. It is important that the temperature used for the cal-
culation of hFG be consistent with the basis for the boiler where
efficiency calculations, otherwise the calculated fuel mass MqWH2F 5 water produced from the combustion of
flow rate for a given boiler output will be incorrect. H2 in the fuel on a mass per energy input
This Code specifies a reference temperature of 778F on an HHV basis
(258C). Based on the ASME International Steam Tables It is recommended that parameters associated with
for Industrial Use, IAWPS-IF97, the recommended value the fuel or input from fuel continue to calculated on an

267

You might also like