You are on page 1of 16

Engineering Structures 164 (2018) 243–258

Contents lists available at ScienceDirect

Engineering Structures
journal homepage: www.elsevier.com/locate/engstruct

Collapse performance of seismically isolated buildings designed by the T


procedures of ASCE/SEI 7

Shoma Kitayama , Michael C. Constantinou
Department of Civil, Structural and Environmental Engineering, University at Buffalo, State University of New York, Buffalo, NY 14260, USA

A R T I C LE I N FO A B S T R A C T

Keywords: This article presents an analytical study of the seismic collapse performance of seismically isolated buildings and
Seismic isolation comparable non-isolated buildings. The study is based on archetypical 6-story perimeter frame seismically
ASCE 7 standard isolated buildings designed with special concentrically braced frames (SCBF), ordinary concentrically braced
Friction pendulum isolator frames (OCBF) and special moment resisting frames (SMF) for a location in California using the minimum cri-
Collapse probability
teria of ASCE/SEI 7-10 and ASCE/SEI 7-16 and also using a number of enhanced designs. The isolation system
Risk assessment
Moment frame
consists of triple Friction Pendulum (FP) isolators with stiffening behavior at large displacement. Additionally,
Braced frame double concave sliding isolators are considered and designed per minimum criteria of ASCE/SEI 7 and without a
displacement restrainer, a practice permitted by the standards. Non-isolated structures, also with braced and
moment frame configurations, are designed using the minimum criteria of ASCE/SEI 7 and studied. The study
concludes that seismically isolated buildings designed by the minimum criteria of ASCE/SEI 7 of either 2010 or
2016 may have unacceptable probability of collapse in the Risk-Targeted Maximum Considered Earthquake
(MCER). The probability of collapse in the MCER becomes acceptable when they are designed with enhanced
criteria of RI=1.0 and with isolators having a displacement capacity at initiation of stiffening equal to 1.5 times
the demand in the MCER. It is also observed that designs that meet the minimum criteria of ASCE/SEI 7 of either
2010 or 2016 and without any displacement restrainer have unacceptably high probabilities of collapse.

1. Introduction exceptions in which stringent criteria have been employed. Examples


are hospitals in California where often project-specific design criteria
Many seismically isolated buildings have been designed and ana- require the use of an RI factor of unity for the effects of the DE or MCER
lyzed according to the minimum requirements of Chapter 17 of ASCE/ and larger displacement capacity isolators than the minimum allowed
SEI 7-10 standard [1]. ASCE/SEI 7-16 [2] specifies the current ASCE by ASCE/SEI 7.
minimum requirements for isolated structures. Both ASCE standards The use of the minimum requirements of the ASCE/SEI 7 standards
require that the isolation system be detailed to accommodate the dis- presumably ensures the minimum acceptable level of safety by pre-
placement demand calculated in the Risk-Targeted Maximum Con- serving the lives of the occupants. It is well recognized that these
sidered Earthquake (MCER), where this displacement is the average of minimum ASCE design requirements do not serve the resiliency ob-
peak values calculated in seven nonlinear response history analyses. jective of avoiding damage in order to maintain facility functionality.
Both procedures permit the use of a response modification coefficient An Executive Order issued in 2016 by the President of the United States
(RI factor) between 1.0 and 2.0 depending on the seismic force-resisting (Executive Order 13717 [3,4]) clearly recognizes this fact and states the
system used. For the case of the ASCE/SEI 7-10 standard, the forces and following: “The Federal Government recognizes that building codes and
drifts for the design are based on calculations using the design response standards primarily focus on ensuring minimum acceptable levels of
(DE) spectrum, which is defined as being 2/3 of the MCER spectrum. earthquake safety for preserving the lives of building occupants. To
For the case of the ASCE/SEI 7-16 standard, the forces and drifts for the achieve true resilience against earthquakes, however, new and existing
design are based on calculations using the MCER spectrum. While many buildings may need to exceed those codes and standards to ensure, for
seismically isolated buildings in the United States have been designed example, that the buildings can continue to perform their essential
using the minimum requirements of ASCE/SEI 7-10, there are functions following future earthquakes.” The Executive Order continues


Corresponding author at: Department of Civil, Structural and Environmental Engineering, 131 Ketter Hall, University at Buffalo, State University of New York, Buffalo, NY 14260,
USA.
E-mail address: shomakit@buffalo.edu (S. Kitayama).

https://doi.org/10.1016/j.engstruct.2018.03.008
Received 5 November 2017; Received in revised form 31 December 2017; Accepted 6 March 2018
0141-0296/ © 2018 Elsevier Ltd. All rights reserved.
S. Kitayama, M.C. Constantinou Engineering Structures 164 (2018) 243–258

to instruct all federal agencies to “go beyond the codes and standards utilized three-dimensional building models with an improved moat wall
and ensure that buildings are fully earthquake resilient.” model and bi-directional seismic excitation but did not consider failure
Questions may then arise. (a) Is the probability of collapse of seis- of the isolators. The results showed that steel intermediate moment
mically isolated structures designed by the minimum design criteria frames designed for the DE with an RI = 1.67 and steel ordinary con-
acceptably low? (b) What should be the criteria for design in terms of RI centrically braced frames designed with RI = 1 had acceptable collapse
and isolator displacement capacity to achieve an acceptable probability margin ratios per FEMA [7] when the size of isolators was sufficiently
of collapse? (c) What does isolation achieve in terms of performance large to avoid failure of the isolator. Barely acceptable probabilities of
measures like peak story drift, residual story drift and floor accelera- collapse were calculated when the moat wall was placed at the
tions? minimum required displacement capacity in the MCER. The calculations
Some studies have already addressed issues related to these ques- were based on the use of adjusted values for accounting for the spectral
tions. Kikuchi et al. [5] studied the inelastic response of a two-degree- shape effects (epsilon) using the FEMA P695 procedures [7]. It will be
of-freedom (2-DOF) representation of seismically isolated structures argued in this paper that the correction factors for the spectral shape
without any consideration for failure of either the structural or the effects provided in FEMA P695 do not apply for seismically isolated
isolation system. The study raised a concern that designs of seismically structures and that special studies are required to properly calculate the
isolated structures with reduced lateral shear force (equivalently, with a effects of spectral shape.
large R factor) can have significant inelastic action and unacceptable Chimamphant and Kasai [12] investigated the seismic response of
behavior. A more recent study [6] again made use of the 2-DOF system nonstructural components in seismically isolated buildings and com-
but enhanced to have non-simulated generic isolation system failure pared it to that of comparable conventionally designed buildings by
and superstructure failure (assumed to occur at ductility of 4.0) and using multi-degree-of-freedom shear-beam models. Failure in the su-
employed contemporary procedures to determine the collapse margin perstructure or the isolation system was ignored and mechanisms that
ratio based on the FEMA P695 procedures [7]. The main contribution of limit the isolator displacement (ex. retaining walls) were not con-
the work was to study the effects of limiting the displacement demand sidered. The study used the methodologies described in FEMA P695 [7]
on the isolators by use of moat walls of varied clearance and behavior. and FEMA P58 [13] and demonstrated that seismically isolated build-
Following the Japanese practice of seismic design, the strength of the ings have better performance than comparable non-isolated buildings
superstructure was assumed in the range of 0.15–0.40 of the super- but the improvement of performance reduces as the height of the
structure weight (common practice in Japan is the use of 0.3). The building increases.
study observed that isolated structures have a low level of damage Recently, Shao et al. [14] focused on a 3-story concentrically braced
(essentially elastic response) until a certain level of seismic intensity is steel frame structure designed for RI = 1 in the MCER and investigated
reached where significant inelastic action occurs for small increases in the reliability of the ASCE/SEI 7-16 minimum provisions [2], as well as
the seismic intensity. enhanced designs by providing either increased isolator displacement
Studies of Erduran et al. [8] and Sayani et al. [9] compared the capacity or providing isolators with hard (moat wall) or soft stopping
inelastic response of conventional and seismically isolated steel braced mechanisms. The main conclusions of the study were that: (a) the iso-
and moment-resisting 3-story frames designed by the minimum criteria lator displacement capacity needs to be increased by at least 1.8 of the
of ASCE 7 (that of 2005) and with unlimited capacity for the isolators. minimum code-prescribed value in order to achieve the code-targeted
The studies concluded that the seismically isolated frames exhibited reliability when no displacement restrainers are provided; (b) smaller
lower structural yielding, story drifts, residual story drifts and floor displacement capacities can be used when displacement restrainers are
accelerations than comparable conventional frames for seismic events utilized but with additional requirements for increased ductility capa-
characterized as frequent, design and maximum earthquake. The stu- city in the superstructure and (c) a total isolator displacement capacity
dies did not provide any information on the collapse of the analyzed (including the capacity of soft stops) of at least 1.5 times the dis-
structures as the structural model did not have capability of simulating placement demand in the MCER and an isolator shear strength of at
large deformations in the elements of the structural system. However, least 3.0 times the base shear in the MCER are needed to achieve the
the studies pointed to interesting observations that (a) allowing for required reliability. The study did not consider the spectral shape ef-
inelastic behavior of the isolated structure limited the displacement fects as the simplified method presented in FEMA P695 [7] for con-
demand in the isolators and (b) designing for elastic behavior could sidering these effects does not truly apply for seismically isolated
have resulted in failure of the isolators if they had limited displacement structures of large effective period. Accordingly, probabilities of failure
capacity. must have been slightly overestimated.
A study of Terzic et al. [10] compared the lifecycle cost of seismi- This paper also investigates the reliability of the ASCE/SEI 7 pro-
cally isolated structures designed with different structural systems of visions by concentrating on an archetypical 6-story perimeter frame
various RI factors. The study demonstrated improved performance and building that has been previously studied in examples of seismic iso-
significant reduction of lifecycle cost when the design utilizes an RI lation design and analysis in McVitty and Constantinou [15]. Perimeter
factor of unity in the DE. steel special concentrically braced frames (SCBF) and special moment
The development of the performance assessment methodologies of resisting frames (SMF) for this building are designed for a location in
FEMA P695 [7] allowed for more rigorous studies of the performance of California with an RI factor of 2.0 (per minimum requirements of ASCE/
isolated structures. One of the examples in FEMA P695 involves seis- SEI 7-10), 1.5 and 1.0 in the DE and with RI = 2.0 (per minimum re-
mically isolated buildings in which failure of the superstructure was quirements of ASCE/SEI 7-16) and 1.0 in the MCER when seismically
simulated and the isolation system was represented by a generic model isolated. Also, the case of steel ordinary concentrically braced frames
together with a displacement-limiting moat wall of various clearances. (OCBF) permitted by ASCE/SEI 7-16 with RI = 1.0 is considered. The
The structure was a 4-story reinforced concrete building of either a isolation system for these cases consists of triple Friction Pendulum (FP)
special perimeter moment frame or a special space frame. Con- isolators having a displacement capacity at initiation of stiffening equal
centrating on the code-complaint designs (with RI = 2 in the DE), the to 1.0DM (per minimum requirements of ASCE/SEI 7-10 and 7-16),
study demonstrated acceptable collapse margin ratios, which progres- 1.25DM and 1.5DM, where DM is the displacement demand in the MCER
sively reduced as the moat wall clearance reduced and the space frame (torsion is not accounted for so the displacement considered is DM in-
was changed to a perimeter frame. stead of DTM, which would be 1.1–1.2 times larger than DM in the
A more recent study of Masroor and Mosqueda [11] utilized models studied systems). For the OCBF the displacement capacity of the iso-
similar to those in the studies of [8,9] and followed the paradigm of lators at initiation of stiffening is 1.25DM, which is required by ASCE/
examples of the seismically isolated buildings in FEMA P695 [7], SEI 7-16. The stiffening behavior of the triple FP isolators serves as a

244
S. Kitayama, M.C. Constantinou Engineering Structures 164 (2018) 243–258

displacement restrainer for displacements larger than the assumed ca- considered, having displacement capacities of (a) the minimum re-
pacities. Additionally, double concave sliding isolators are considered quired by the criteria of ASCE/SEI 7 (capacity DM at initiation of stif-
and designed per minimum criteria and without a displacement re- fening) and (b) increased capacities of 1.25DM and 1.5DM at initiation
strainer, a practice permitted by the ASCE/SEI 7 standards (and a of stiffening. Note that the internal construction of the three isolators is
common practice in Europe, e.g., [16]). Non-isolated structures, also the same so that their frictional properties are the same for the same
with braced and moment frame configurations, are designed and stu- conditions of load and motion. The force-displacement relationship for
died. these isolators is shown in Fig. 3 together with values of the displace-
Results are presented for the conditional probability of collapse on ment capacity at initiation of stiffening, DCapacity, and the ultimate
the occurrence of the MCER of the designed isolated structures and displacement, DUltimate, when the isolator internal parts collapse as
comparable non-isolated structures. It is shown that (a) seismically calculated on the basis of the theory of Sarlis and Constantinou [18] in
isolated buildings designed by the minimum criteria of ASCE/SEI 7 of the lower bound friction condition. Note that the isolators may also
either 2010 or 2016 may have unacceptable probability of collapse in yield prior to reaching DUltimate when the lateral force in the stiffening
the MCER, (b) the probability of collapse in the MCER is acceptable (and regime of the bearings exceeds the strength of the restrainer ring. While
depending on the structural system much less than 10%) when the this was modelled in the analysis it did not occur as the shear force did
structure is designed for RI = 1.0 (either for the DE or the MCER) and not reach the strength of the ring as calculated using the theory of [18].
the isolators have a displacement capacity at initiation of stiffening The displacement capacity provided was DM (or a multiple of it) and not
equal to 1.5DM, (c) reducing the RI factor may not provide any ad- DTM (which includes the effects of torsion) as the analysis for the col-
vantage unless the displacement capacity of the isolators is accordingly lapse performance assessment was based on two-dimensional re-
increased (as then collapse is due to failure of the isolators), (d) designs presentations of the building and torsion was not included.
that meet the minimum criteria of ASCE/SEI 7 of either 2010 or 2016 Two more isolator types were considered without a restrainer ring
and without any displacement restrainer have unacceptably high so that they did not exhibit stiffening behavior. They were designed as
probabilities of collapse, and (e) OCBF designed by the minimum cri- Double Concave (DC) isolators (Fenz and Constantinou [19]) with the
teria of ASCE/SEI 7-16 have marginally unacceptable probabilities of same curvature as the triple FP isolators. Both isolators have the same
collapse which can be improved by increasing the displacement capa- contact area of 279 mm as the triple FP isolators. Of the two DC iso-
city of the isolators. lators, isolator DC-1 has an ultimate displacement capacity equal to DM,
whereas isolator DC-2 has the same concave plate diameter as the
smallest triple FP isolator (TFP-1) and thus a larger ultimate displace-
2. Structures and isolation systems considered ment capacity than DM, determined to be 1.25DM (displacement when
the inner slider reaches the edge of the concave plate plus half of the
A 6-story archetypical steel building is considered. The building was contact diameter of 279 mm). Isolators DC-1 is permitted by the ASCE/
used in examples in the SEAONC Volume 5 Seismic Design Manual [17] SEI 7 standards. Isolators with the characteristics of DC-1 and DC-2
and later used in examples of application of the ASCE/SEI 7-16 analysis have been used in applications in Europe and South America. Force-
and design procedures for isolated buildings in [15]. Fig. 1 shows plan displacement relationships for these isolators are presented in Fig. 3.
and view of the building. Its lateral force resisting system consists of The frictional properties of the triple FP isolators for high speed
four perimeter frames that are configured as special concentrically conditions are presented in Table 1 together with values of the property
braced frames (SCBF), or special moment resisting frame (SMF) or or- modification factors used to determine the frictional properties [15].
dinary concentrically braced frames (OCBF). The total seismic weight of Note that the properties were determined on the basis of prototype test
the building when seismically isolated is 53,670 kN. When non-isolated data for similar isolators and use of the procedures in ASCE/SEI 7-16.
the weight is 45,285 kN. The building is assumed located on soil class D The values of friction in Table 1 are different for the interior and ex-
in San Francisco, CA (Latitude 37.783°, Longitude −122.392°) with terior isolators due to the different gravity load carried by them. The
MCER spectral acceleration values of SMS = 1.5 g and SM1 = 0.9 g. For large difference between the lower and upper bound values of friction
the DE, the parameters are SDS = 1.0 g and SD1 = 0.6 g. reflect (a) the uncertainties due to availability of test data on similar
The isolation system consists of triple FP isolators (placed below rather than the actual isolators, and (b) the large pressure at which the
each column) having the geometric and frictional properties de- isolators operate that result in more variability due to heating [15]. For
termined in [15] but the outer concave plates of the isolators were the DC bearings the values of friction coefficient are also presented in
selected to have three different sizes so that the displacement capacities Table 1 where are seen to be slightly less than those of the outer surface
were varied. Fig. 2 shows cross sections of the three triple FP isolators

Fig. 1. Archetypical building plan and views of braced and moment frames.

245
S. Kitayama, M.C. Constantinou Engineering Structures 164 (2018) 243–258

Fig. 2. Triple FP (TFP) and Double Concave (DC) isolators of different displacement capacities: (a) TFP-1, (b) TFP-2, (c) TFP-3, (d) DC-1 and (e) DC-2.

TFP-1 DCapacity=518mm (DM), DUltimate=683mm (1.3DM) DC-1 DCapacity=518mm (DM), DUltimate=526mm (DM)
TFP-2 DCapacity=663mm (1.25DM), DUltimate=828mm (1.6DM) DC-2 DCapacity=518mm (DM), DUltimate=645mm (1.25DM)
TFP-3 DCapacity=808mm (1.5DM), DUltimate=973mm (1.9DM)
Fig. 3. Force-displacement relationships of triple FP (left) and double concave (right) isolators.

Table 1 ASCE/SEI 7 for the MCER to determine the isolator displacement de-
Upper and lower bound friction properties of triple FP and double concave isolators. mands and the base shear force. Analyses were also conducted for the
DE per ASCE/SEI 7-10 in order to calculate the base shear force in the
Interior Isolators Exterior Isolators
DE. Response History Analysis (RHA) and Equivalent Lateral Force
Isolator Type Sliding Outer Inner Outer Inner (ELF) procedures were used. For the RHA, the model of analysis was
Surface (μ1 = μ4 or μ) (μ2 = μ3) (μ1 = μ4 or μ) (μ2 = μ3) three-dimensional of which details, including details on the motions
used and the scaling procedure, are presented in [15]. Results are
Triple Friction Nominal 0.052 0.017 0.073 0.017
Pendulum λmax 1.67 1.29 1.39 1.29
summarized in Tables 2 and 3. These results were obtained using seven
λmin 0.81 0.85 0.58 0.85 pairs of amplitude-scaled motions per procedures in ASCE/SEI 7 (both
Upper 0.087 0.022 0.101 0.022 2010 and 2016). The superstructure was assumed elastic. Torsion was
bound not considered. That is, the calculation of the isolator displacement
Lower 0.042 0.015 0.042 0.015
demand included the effects of bi-directional excitation but not tor-
bound
sional effects. The frame properties used in the RHA and ELF are those
Double Upper 0.080 NA 0.093 NA
in Tables 4 and 5 for SCBF and SMF with RI=2.0. The effects that the
Concave bound
Lower 0.039 NA 0.039 NA
superstructure increased stiffness for the other designs may have had on
bound the isolator displacement demand and base shear force were assumed
insignificant.
The tables include design values of base shear per frame and the
of the triple FP isolators. The friction force has been calculated as the value of isolator displacement DM for design based on the criteria of
zero displacement force intercept for the triple FP bearings divided by ASCE/SEI 7. There are no or insignificant differences in the calculated
the normal load. The system property modification factors were as- isolator displacements and in the base shear force for the two config-
sumed to be the same. urations. Accordingly, for both configurations the following values
Analyses of the isolated building were conducted per procedures in were used in design: isolator displacement DM = 526 mm (average of

246
S. Kitayama, M.C. Constantinou Engineering Structures 164 (2018) 243–258

Table 2

Non-isolated

W21 × 147

W21 × 147

W27 × 194

W27 × 194

W27 × 217

W27 × 217
Isolator displacement, peak story drift ratio and base shear force for braced frame.

RI = 8.0
Earthquake Quantity Lower bound Upper bound


friction friction

W24 × 131

W24 × 131

W24 × 162

W24 × 162

W27 × 235

W27 × 235
DE RHA Base Shear X (kN) 2290 3136

RI = 2.0
RHA Base Shear Y (kN) 2158 3140
ELF Base Shear (kN) 3112 3556
Design Base Shear (kN) per 3237


ASCE/SEI 7-10
ELF Peak Story Drift Ratio 0.0018

W24 × 146

W24 × 146

W24 × 207

W24 × 207

W27 × 307

W27 × 307
ASCE 7-16

RI = 1.0
MCER RHA Base Shear X (kN) 3541 3793
RHA Base Shear Y (kN) 3057 3810
ELF Base Shear (kN) 4668 5393


Design Base Shear (kN) 3930

W27 × 129

W27 × 129

W27 × 146

W27 × 146
per ASCE/SEI 7-16

W21 × 93

W21 × 93
ELF Peak Story Drift Ratio 0.0018

RI = 2.0
RHA Isolator Resultant 536 345
Displacement (mm)


ELF Isolator Displacement 638 401
(mm)

W21 × 111

W21 × 111

W21 × 111

W21 × 111

W27 × 146

W27 × 146
DM (mm) 535

RI = 1.5
Base shear force is per frame


Table 3

W24 × 146

W24 × 146

W27 × 235

W27 × 235
ASCE 7-10

W24 × 94

W24 × 94
Isolator displacement, peak story drift ratio and base shear force for moment frame.

RI = 1.0
Isolated
SMF
Earthquake Quantity Lower bound Upper bound


friction friction

HSS8.625 × 0.5

HSS8.625 × 0.5
DE RHA Base Shear X (kN) 2293 3231

HSS5 × 0.25
Non-isolated
RHA Base Shear Y (kN) 2187 2922

HSS6 × 0.5

HSS7 × 0.5

HSS7 × 0.5
W12 × 35

W12 × 35

W12 × 58

W12 × 58

W12 × 96

W12 × 96
ELF Base Shear (kN) 3112 3556

RI = 6.0
Design Base Shear (kN) per 3237
ASCE/SEI 7-10
ELF Peak Story Drift Ratio 0.0148

MCER RHA Base Shear X (kN) 3370 3940

HSS6.625 × 0.5

HSS6.625 × 0.5
HSS4 × 0.237
RHA Base Shear Y (kN) 3095 3657

HSS5 × 0.5

HSS6 × 0.5

HSS6 × 0.5
W12 × 35

W12 × 35

W12 × 58

W12 × 58

W12 × 96

W12 × 96
ELF Base Shear (kN) 4668 5393
RI = 2.0

Design Base Shear (kN) per 3930


ASCE/SEI 7-16
ELF Peak Story Drift Ratio 0.0144
RHA Isolator Resultant 518 348
HSS4.5 × 0.337

HSS8.625 × 0.5

HSS8.625 × 0.5
Displacement (mm)
HSS7.5 × 0.5

ELF Isolator Displacement 638 401 HSS7.5 × 0.5


HSS6 × 0.5
ASCE 7-16

W12 × 35

W12 × 35

W12 × 58

W12 × 58

W12 × 96

W12 × 96
(mm)
RI = 1.0

DM (mm) 518
Base shear force is per frame
Sections of columns and braces of SCBF and SMF in isolated and non-isolated buildings.

HSS6.875 × 0.312

HSS6.875 × 0.312

the two values) and base shear force of 3237kN in the DE and 3930kN
HSS4 × 0.188

HSS5 × 0.312

HSS6 × 0.375

HSS6 × 0.375

in the MCER (shear force for elastic conditions). Based on these values,
W12 × 35

W12 × 35

W12 × 58

W12 × 58

W12 × 96

W12 × 96

frames were designed as follows: (a) per minimum criteria for RI = 2.0
RI = 2.0

for the DE (per ASCE/SEI 7-10) and for the MCER (per ASCE/SEI 7-16),
(b) for RI = 1.5 and 1.0 for the DE and (c) for RI = 1 for the MCER. Also,
comparable non-isolated structures were designed with R = 6, Ω0 = 2,
HSS7 × 0.375

HSS7 × 0.375

Cd = 5 for the SCBF and with R = 8, Ω0 = 3, Cd = 5.5 for the SMF. The
HSS4 × 0.22

HSS5 × 0.5

HSS6 × 0.5

HSS6 × 0.5
W12 × 35

W12 × 35

W12 × 58

W12 × 58

W12 × 96

W12 × 96

design utilized member forces determined in static analysis using the


RI = 1.5

lateral forces prescribed by the ELF procedures of ASCE/SEI 7. Note


that for the non-isolated structures the lateral forces were based on the
DE (2/3rd of the MCER) for both versions of the ASCE/SEI 7 standard.
HSS4.5 × 0.237

HSS6.875 × 0.5

HSS6.875 × 0.5

The section properties for the beams, columns and braces of the de-
HSS6 × 0.375

HSS7.5 × 0.5

HSS7.5 × 0.5

signed frames are presented in Tables 3 and 4. Steel has minimum yield
ASCE 7-10

W12 × 35

W12 × 35

W12 × 58

W12 × 58

W12 × 96

W12 × 96
RI = 1.0

strength Fy equal to 290 MPa for braces (round HSS) and 345 MPa for
Isolated
SCBF

columns and beams. The expected yield strengths Fye are 406 MPa and
380 MPa, respectively [20].
Note that the location of the analyzed buildings is considered to be
Column

Column

Column

Column

Column

Column

representative of far-field conditions. Accordingly, the results in Tables


Brace

Brace

Brace

Brace

Brace

Brace

2 and 3 and the assessment of collapse performance that follows apply


for far-field conditions. Near-fault conditions require consideration of
Table 4

Story

different motions for RHA and the frame and isolator designs will likely
6

be different. To assess the implications, further studies are needed but

247
S. Kitayama, M.C. Constantinou Engineering Structures 164 (2018) 243–258

Table 5
Sections of beams of SCBF and SMF in isolated and non-isolated buildings.

Floor SCBF SMF

Isolated Non-isolated Isolated Non-isolated

ASCE 7-10 ASCE 7-16 ASCE 7-10 ASCE 7-16

RI = 1.0 RI = 1.5 RI = 2.0 RI = 1.0 RI = 2.0 RI = 6.0 RI = 1.0 RI = 1.5 RI = 2.0 RI = 1.0 RI = 2.0 RI = 8.0

Roof W16 × 26 W16 × 26 W16 × 26 W16 × 26 W16 × 26 W16 × 26 W18 × 65 W18 × 50 W16 × 45 W18 × 86 W18 × 71 W21 × 62
6 W16 × 26 W16 × 26 W16 × 26 W16 × 26 W16 × 26 W16 × 26 W18 × 65 W18 × 50 W16 × 45 W18 × 86 W18 × 71 W21 × 62
5 W16 × 26 W16 × 26 W16 × 26 W16 × 31 W16 × 26 W16 × 26 W24 × 117 W24 × 84 W24 × 76 W24 × 176 W24 × 131 W24 × 146
4 W16 × 26 W16 × 26 W16 × 26 W16 × 31 W16 × 26 W16 × 26 W24 × 117 W24 × 84 W24 × 76 W24 × 176 W24 × 131 W24 × 146
3 W16 × 26 W16 × 26 W16 × 26 W16 × 31 W16 × 26 W16 × 26 W18 × 175 W24 × 103 W24 × 94 W18 × 192 W18 × 175 W24 × 176
2 W16 × 26 W16 × 26 W16 × 26 W16 × 31 W16 × 26 W16 × 26 W18 × 175 W24 × 103 W24 × 94 W18 × 192 W18 × 175 W24 × 176
1 W18 × 50 W18 × 50 W18 × 50 W18 × 50 W18 × 50 – W21 × 201 W30 × 124 W27 × 129 W21 × 201 W21 × 201 –

past studies on other seismic protective systems have shown increases the REDi criteria for gold rating has a 30% probability of exceeding the
in the collapse risk when near-fault motions were considered [21]. limit of 0.5% in peak drift ratio and 37% probability of exceeding the
The results in Tables 2 and 3 demonstrate that the frames meet the peak floor acceleration limit of 0.3 g in 50 years. In contrast, the SCBF
drift criteria of the ASCE/SEI 7 standards [1,2], Section 17.5.6 as the design that meets the REDi criteria for gold rating has, respectively,
maximum story drift is less than 0.015 of the story height. Note that probabilities of 2.3% and 6.9%. The SCBF design that has these low
analysis was performed for the frames designed with RI = 2.0 (the drift probabilities of developing any damage in a lifetime of 50 years also
is less than the values in Tables 2 and 3 when RI is less than 2.0). The meets the criteria of a seismic isolation standard for continued func-
results of RHA on drift are not presented as the superstructure was tionality developed by Zayas [25] and implemented in the design and
assumed elastic and there are no specified limits for such conditions construction of some hospitals and important structures. A commentary
(rather there are limits in Section 17.6.4.4 of ASCE/SEI 7 for analysis to this standard explains the basis and justifies its provisions [26]. In
using nonlinear force-displacement characteristics for the structural this standard, seismically isolated structures meet the REDi “gold”
elements). rating when designed with RI = 1 in the DE, the peak story drift ratio is
The SCBF designed with RI = 1.0 in the MCER was also analyzed limited to 0.4% and the 5%-damped floor acceleration response spectra
assuming that it behaves as an ordinary concentrically braced frame are less than 0.6 g (in a sense that the median value within the period
(OCBF) with isolators having the characteristics of isolators TFP-2 with range of zero to 5 s is less than 0.6 g) in the DE. In the same standard the
displacement capacity equal to 1.25DM and TFP-3 with displacement criteria for the REDi “platinum” rating call for limits of 0.3% on peak
capacity equal to 1.5DM. This structural configuration is permitted per drift ratio and 0.4 g on floor spectral accelerations in the DE. The SCBF
Section 17.2.5.4 of ASCE/SEI 7-16 provided that the isolators have a design meets the criteria of the standard for continued functionality for
displacement capacity of at least 1.2DM. In the RHA for the assessment “platinum” rating [25] as it has a peak story drift ratio of 0.15% and a
of performance, the story drift ratio limit at collapse was assumed to be median floor spectral acceleration of 0.3 g. The SMF design does not
2% for the OCBF [11], whereas it was 5% for the SCBF [22]. meet the criteria of the standard for continued functionality as the peak
Two of the developed designs (SCBF and SMF, RI = 1.0 in the DE, story drift ratio is 0.87%.
triple FP isolator TFP-3 with DCapacity = 1.5DM and DUltimate = 1.9DM,
see Fig. 3) were further analyzed to investigate whether they meet the
3. Model for analysis
“Enhanced Structural and Non-structural Design Criteria” of the REDi
Rating System (Arup, [23]) for a rating of “Gold” or “Platinum”. This
Analysis was performed in program OpenSees [27] using a two-di-
enhanced design includes a recommendation to design for an isolator
mensional representation of the structure as illustrated in Figs. 4 and 5.
displacement capacity of 1.9DM, and to have essentially elastic response
Fig. 4 presents the model for the braced isolated building. One of the
with a residual drift ratio of less than 0.5% for the “Design Level
two seismic force-resisting frames in a principal direction was explicitly
Earthquake”, defined as having a 475 year return period. Analysis of the
modelled with details that will be described below. Each of the columns
isolated structures was conducted with the inelastic two-dimensional
of the seismic force-resisting frame was supported by one exterior iso-
representation used in the incremental dynamic analysis (to be de-
lator. Half of the remaining building (two rows of columns) was also
scribed later) using the fault-normal (FN) components of the seven
modelled with all its beams simply connected to the columns but for the
motions used in the three-dimensional analysis. These components
connections of the girders on top of the isolators. Each of the columns of
needed to be scaled by a different factor than in the three-dimensional
the gravity frame was supported by two interior isolators. The gravity
analysis. (see Table A1 in [15] where the scale factors are 3.9, 1.7, 3.0,
and seismic force-resisting frames were placed parallel to each other
3.2, 3.9, 3.9 and 3.9 for motions 1–7). In the two dimensional analysis,
and interconnected with horizontal rigid links at the locations marked
the FN components of these motions were scaled by factors 4.0, 1.3, 1.2,
in Fig. 4 with “H” and with rigid links in the horizontal, vertical and
3.0, 3.5, 5.0 and 5.0, respectively, based on Sections 16.1.3.1 and
rotational directions at the locations marked “H”, “V” and “R”, re-
17.3.2 of ASCE/SEI 7-10 and 16.2.3 and 17.3.3 of ASCE/SEI 7-16. The
spectively. Tributary weights are also shown in the figure. Fig. 5 pre-
analysis resulted in peak drift ratio (average of seven analyses) of
sents the model for a non-isolated building where now is possible to
0.15% and a residual drift ratio of 0.01% for the SCBF (also OCBF) and
locate the columns of the gravity frame at the two sides of the seismic
in a peak drift ratio of 0.87% and a residual drift ratio of 0.03% for the
force-resisting frame. The total seismic weight is 26,835 kN for the
SMF. Both designs meet the criteria of the REDi Rating System [23] for
isolated model and 22,643 kN for the non-isolated model.
a rating of “gold” or “platinum”.
Columns, girders and braces were modelled based on Uriz and
However, Kitayama and Constantinou [24] have shown that the
Mahin [28] and Chen and Mahin [29]. The column and girder sections
SMF design has higher mean annual frequencies of exceeding specific
were modelled with eight fibers for each flange and with eight fibers for
residual drift ratio and floor peak acceleration limits than the SCBF
the web as shown in Fig. 6. HSS round hollow tubes used for the braces
design. Particularly, it has been shown that the SMF design that meets
were modelled with two fibers along the thickness and 16 fibers along

248
S. Kitayama, M.C. Constantinou Engineering Structures 164 (2018) 243–258

Gravity Frame Seismic force-resisting frame


Fig. 4. Representation of gravity and seismic force-resisting frames of isolated building.

the perimeter for a total of 32 fibers. Force-based nonlinear beam- damping matrix, which is then used in the RHA. The application of the
column elements with four integration points were used to model the procedure for the isolated building model is complicated by the fact
spread of plasticity across each fiber. The Giuffre-Menegotto-Pinto that the isolator models are extremely stiff in the elastic range (the
model (“Steel02” material in OpenSees [27,30]) was used for the elastic stiffness is the friction force at initiation of motion divided by
braces, girders and columns to describe smooth bi-linear behavior. The some very small “yield” displacement which was 1.3 mm). Instead, the
strain-hardening modulus was assigned values of 3% of the elastic correct stiffness of the isolators for the construction of the damping
modulus for the beams, 0.2% for the columns and 1% for the braces. matrix is the post-elastic stiffness (or the stiffness when friction is dis-
The connections of girders to columns and to braces were modelled regarded and sliding occurs on the main concave surfaces) [32]. Ac-
as shown in Fig. 7. The connections between braces and their gusset cordingly, horizontal, vertical and rotational springs were placed below
plates were modelled as pins with zero-length as has been used in the each isolator element to represent the desired stiffness in the horizontal
many studies [8,29]. An initial camber of 1% of the effective brace direction only for the construction of the damping matrix. These springs
length (see Fig. 7 for details) was applied at the brace midpoint to in- were restrained to only deflect by 0.025 mm so that under inelastic
itiate buckling (Fig. 7, bottom left). Gusset plates ware modelled using conditions in the nonlinear RHA they do not affect the behavior of the
the “Elastic Beam Column” element in OpenSees with 10 times the area isolators.
and moment of inertia of the connecting brace element as re- The model used in the analysis of the SMF was developed with due
commended in [8]. Panel zones were modelled as essentially rigid by considerations for the ultimate behavior of the components and large
using the “Elastic Beam Column” element with length equal to half the rotation and displacement effects. Important details of the model follow
section depth and with 10 times the area and moment of area of the (more details are presented in [33]): (a) beams and columns were
corresponding beam or column element. Member capacities were cal- modelled using the Modified Ibarra-Krawinkler bilinear-hysteretic
culated using the expected yield strength of the materials: 380 MPa for model [34], which is capable of simulating deteriorating hysteretic
beams and columns and 406 MPa for braces. moment-rotation relationship, (b) columns were modelled using a
Failure of braces, girders and columns was not explicitly modelled. concentrated plasticity bi-linear hysteretic model without strength or
Rather, the deteriorating behavior of the elements was modelled and stiffness deterioration and with a ratio of elastic to post-elastic stiffness
failure was implicitly accounted for by considering limits on the story of 0.002 and (c) plastic hinges in columns were located at beam faces
drift. and plastic hinges at the column bases were located at a distance equal
Inherent damping in the isolated buildings was modelled using the to the column depth from the base.
“modal damping” [31] to provide a damping ratio of 0.02 in all modes The triple FP isolators were modelled using a modification of the
but the first two (“isolated” modes) for which the damping ratio was set series model [35] in order to simulate the ultimate behavior of the
equal to zero per directions in [32]. For the non-isolated buildings, the isolator as predicted by the theory of [18] including uplift. Specifically,
damping ratio was specified as 0.02 in all modes. In the modal damping the modified series model includes the stiffness of the restraining ring kr
model, the elastic properties of the structure are used to construct a and its ultimate capacity. The shear stiffness of the restraining ring was

249
S. Kitayama, M.C. Constantinou Engineering Structures 164 (2018) 243–258

Fig. 5. Representation of non-isolated building.

half of the diameter of the rigid slider (see Figs. 2 and 3). Note that the
model does not explicitly simulate collapse. Simply when this limit of
displacement is exceeded, the isolator is considered failed and execu-
tion of the program is terminated. Given that collapse is not directly
simulated, a user of this model may opt to use a different limit for the
ultimate displacement as for example the one calculated by more ad-
vanced models in [18]. Moreover, uplift of the isolators was modelled.
The interested reader is referred to [37,38] for details of the modified
series model. Note that while there are more detailed models that can
simulate failure of the isolator [18,39], these models are computa-
tionally very expensive to be used in this study where over 10,000
Fig. 6. Fiber discretization used for HSS brace and wide flange column and beam sec- nonlinear RHA were conducted.
tions. Failure of the analyzed structures was assumed when any of the
following conditions occurred: (a) the maximum story drift ratio ex-
calculated by the following equation, which is based on the shear ceeded 0.02 [11] for buildings with OCBF, 0.05 [22] for buildings with
strength of a 60° wedge of the ring divided by an appropriate value of a SCBF and 0.1 [40] for buildings with SMF, (b) the isolator displacement
yield displacement Yr: exceeded DUltimate, (c) the triple FP isolator uplift displacement ex-
ceeded the height of the restraining ring (38 mm), (d) there was in-
π (b−tr ) tr Fry stability detected by termination of the analysis program or (e) the
kr =
6Yr (1) slope of the Sa(T1) vs maximum story drift ratio curve (e.g., the slope of
the incremental dynamic analysis or IDA curve [41]) was less than 0.1
In Eq. (1), b and tr are the outside diameter and thickness of the times the slope of the same curve in the initial analysis (a condition that
restraining ring, respectively, and Fry is the shear yield stress of the indicates a “flat” IDA curve).
material (172 MPa is a representative value for ductile iron per [18]).
The strength of the restraining ring is equal to krYr. The value of Yr was 4. Structural collapse evaluation
set equal to the thickness tr. The restrainer is considered acting as long
as the restraining ring deformation is less than the thickness tr. When Structural collapse of the developed designs was evaluated based on
this displacement is exceeded for the first time, the restraining ring is FEMA P695 [7] using the set of 44 far-field ground motions in this
removed from the model. FEMA document. First, incremental dynamic analysis (IDA) [41] was
The model is assumed valid until the displacement reaches a critical conducted and data were obtained and used to calculate the collapse
value, which results in collapse or overturning of the internal parts of capacity. This collapse capacity does not include the spectral shape
the bearing. This displacement is denoted as DUltimate and is equal to the effects, which are known to be important [42,43]. While FEMA [7]
displacement capacity DCapacity as predicted by the theory in [36] plus includes a simple procedure for accounting for these effects, the

250
S. Kitayama, M.C. Constantinou Engineering Structures 164 (2018) 243–258

Fig. 7. Details of model of connections.

procedure is based on the analysis of non-isolated concrete moment spectral shape effects (as directly obtained from the IDA results), the
frame and wood frame buildings. Application of the procedure to median collapse capacity with due consideration for the spectral shape
seismically isolated buildings is questionable given the large funda- effects per Eq. (2), Sa  Col,adj (T1) , the dispersion coefficient due to the
mental period and the fact that collapse may occur in the isolator rather record-to-record variability (as obtained from the IDA results), βRTR,
than the structure above. A specific study, presented in Appendix A, and the assumed total system collapse uncertainty βTOT. Note that the
was conducted to determine the median collapse spectral acceleration ratio Sa  Col (T1) is the spectral shape factor or SSF per FEMA
 Col,adj (T1) /Sa
at the fundamental period with the spectral shape effects accounted for P695 [7]. Also, the adjusted collapse margin ratio or ACMR per FEMA
based on the approach proposed in [42]. The median collapse spectral P695 is given by:
acceleration at the fundamental period Sa  Col,adj (T1) , with due con-
 Col,adj (T1)
Sa
sideration for the spectral shape effects, is provided by Eq. (2) in which ACMR =
factors c0 and c1 were obtained by regression analysis of IDA data and SaMCE (T1) (3)
are presented in Tables 6 and 7. In Eq. (3), SaMCE(T1) is the MCER spectral acceleration at the fun-
 Col,adj (T1)(units g) = exp[c0 + c1·ε0 (T1)] damental period T1 (=TM for isolated structures). Values of SaMCE(T1)
Sa (2) are 1.5 g for the non-isolated SCBF structure, 0.759 g for the non-iso-
lated SMF structure and 0.246 g for all isolated structures. The total
Values of period T1 were 0.524 s for the non-isolated SCBF, 1.186 s
system uncertainty βTOT was calculated using Equation (4) per FEMA
for non-isolated SMF and 3.66 s (=TM, which is the effective period of
P695 [7] where each component of uncertainty is related to a quality
the isolated structure in the MCER) for all isolated structures. Values of
rating.
the target epsilon ε0 (T1) are 1.44 for all isolated structures, 1.46 for the
non-isolated SCBF and 1.71 for the non-isolated SMF (see Table A1). βTOT = 2
βRTR 2
+ βDR 2
+ βTD 2
+ βMDL (4)
Tables 6 and 7 present the results of the collapse evaluation for all
considered systems in terms of parameters c0 and c1 of Eq. (2), the In Eq. (4) βDR is the design requirements-related collapse un-
median collapse capacity, Sa  Col (T1) , without due consideration for the certainty, βTD is the test data-related collapse uncertainty and βMDL is

251
S. Kitayama, M.C. Constantinou Engineering Structures 164 (2018) 243–258

Table 6
Results of collapse fragility analysis for buildings with SCBF and OCBF.

System Coeffs. in Eq. (2) SaCol(T1) (w/o epsilon SaCol,adj(T1) (with epsilon βTOT (βRTR) Prob. Collapse at MCER
adjustment) adjustment) (%)
c0 c1 (g) (g)

Designed per ASCE 7- RI = 1.0, TFP-1 −1.219 0.146 0.281 0.365 0.366 14.08
10 (0.209)
RI = 1.0, TFP-2 −1.083 0.129 0.320 0.408 0.350 7.47
(0.181)
RI = 1.0, TFP-3 −0.990 0.115 0.355 0.438 0.341 4.52
(0.163)
RI = 1.0, TFP-3 −0.551 0.156 0.557 0.729 0.391 1.23
(Upper bound (0.255)
friction)

RI = 1.5, TFP-1 −1.241 0.121 0.271 0.344 0.352 17.05


(0.185)
RI = 1.5, TFP-2 −1.138 0.109 0.307 0.375 0.343 10.95
(0.166)
RI = 1.5, TFP-3 −1.056 0.097 0.331 0.400 0.339 7.59
(0.158)

RI = 2.0, TFP-1 −1.262 0.123 0.275 0.338 0.348 18.06


(0.176)
RI = 2.0, DC-1 −1.389 0.148 0.237 0.309 0.378 27.37
no restraining ring (0.230)
RI = 2.0, DC-2 −1.228 0.134 0.274 0.356 0.368 15.83
no restraining ring (0.213)
RI = 2.0, TFP-2 −1.166 0.107 0.293 0.364 0.343 12.74
(0.166)
RI = 2.0, TFP-3 −1.083 0.093 0.323 0.387 0.340 9.09
(0.159)

Designed per ASCE 7- RI = 1.0, TFP-1 −1.302 0.129 0.253 0.328 0.356 21.09
16 (0.193)
RI = 1.0, TFP-2 −1.140 0.114 0.300 0.377 0.350 11.13
(0.181)
RI = 1.0, TFP-3 −1.020 0.105 0.341 0.419 0.341 5.87
(0.161)

RI = 1.0, TFP-2 −1.153 0.105 0.299 0.368 0.346 12.31


OCBF (0.173)
RI = 1.0, TFP-3 −1.060 0.088 0.332 0.393 0.333 7.96
OCBF (0.145)

RI = 2.0, TFP-1 −1.215 0.139 0.279 0.362 0.357 13.94


(0.194)
RI = 2.0, TFP-2 −1.103 0.115 0.312 0.392 0.346 8.93
(0.173)
RI = 2.0, TFP-3 −1.026 0.096 0.343 0.412 0.338 6.38
(0.156)

– Non-isolated 0.809 0.238 2.821 3.179 0.538 8.15


(0.412)

the modeling-related collapse uncertainty. For the seismically isolated isolator of DCapacity = 1.5DM would become 2.7% instead of 4.5% (see
structures with SCBF and SMF the following quality ratings and related Table 5). The values of probabilities of collapse in the tables are based
uncertainties were used: good with βMDL = 0.2 for modeling; good with on reasonably conservative assumptions on the values of uncertainties.
βTD = 0.2 for test data and superior with βDR = 0.1 for design re- Also, the results in Tables 6 and 7 are based on analyses using the lower
quirements (same assumptions made in [7,11]). For the non-isolated bound values of friction for the isolators which systematically resulted
structure with SCBF, βMDL = 0.2, βTD = 0.2, and βDR = 0.2 were used in the largest probabilities of collapse. Results are presented for one
based on [29,44]. For the non-isolated structure with SMF, βMDL = 0.2, case using the upper bound values of friction per Table 1 to demon-
βTD = 0.2, and βDR = 0.1 were selected based on [44,45]. strate the effect. The reason for the reduction in the probability of
Instead of values of the ACMR, Tables 6 and 7 present the condi- collapse is the fact that failure is dominated by excessive isolator dis-
tional probability of collapse caused by the MCER or PCOL,MCE, calcu- placements (they lead to isolator failure or to superstructure collapse
lated as: after the isolators enter the stiffening regime) and higher values of
friction result in smaller displacement demands.
1 1 (lns−ACMR)2 ⎤ In discussing the results of Tables 6 and 7, the target reliabilities
PCOL,MCE = ∫0 exp ⎡
⎢− 2 ⎥ ds
sβTOT 2π ⎣ 2βTOT ⎦ (5) that are stipulated in Section 1.3.1.1 of ASCE 7-16 [2] can be used. This
requires conditional probabilities of collapse caused by the MCER not to
Note that the calculated probabilities of collapse depend on the exceed 10% for typical buildings of risk category I or II, 2.5% for es-
assumed values of uncertainty parameters. For example, if the total sential buildings of risk category IV and 5% for other structures. The
uncertainty βTOT is assumed equal to 0.3, as in [14], the probability of following are observed:
collapse for the isolated SCBF system with RI = 1.0 in the DE and TFP-3

252
S. Kitayama, M.C. Constantinou Engineering Structures 164 (2018) 243–258

Table 7
Results of collapse fragility analysis for buildings with SMF.

System Coeffs. in Eq. (2) SaCol(T1) (w/o epsilon SaCol,adj(T1) (with epsilon βTOT (βRTR) Prob. Collapse at MCER
adjustment) adjustment) (%)
c0 c1 (g) (g)

Designed per ASCE 7- RI = 1.0, TFP-1 −1.042 0.177 0.331 0.455 0.387 5.58
10 (0.245)
RI = 1.0, TFP-2 −0.911 0.164 0.383 0.510 0.372 2.53
(0.221)
RI = 1.0, TFP-3 −0.827 0.154 0.398 0.546 0.365 1.44
(0.208)
RI = 1.0, TFP-3 −0.402 0.190 0.635 0.891 0.428 0.56
(Upper bound (0.305)
friction)

RI = 1.5, TFP-1 −0.996 0.141 0.373 0.453 0.378 5.32


(0.230)
RI = 1.5, TFP-2 −0.896 0.121 0.393 0.486 0.368 3.20
(0.213)
RI = 1.5, TFP-3 −0.855 0.098 0.411 0.490 0.360 2.77
(0.199)

RI = 2.0, TFP-1 −0.998 0.134 0.364 0.447 0.385 6.06


(0.241)
RI = 2.0, DC-1 −1.462 0.105 0.223 0.270 0.360 39.92
no restraining ring (0.200)
RI = 2.0, DC-2 −1.307 0.091 0.266 0.309 0.357 26.30
no restraining ring (0.194)
RI = 2.0, TFP-2 −0.954 0.128 0.390 0.463 0.377 4.67
(0.229)
RI = 2.0, TFP-3 −0.892 0.091 0.390 0.467 0.358 3.65
(0.195)

Designed per ASCE 7- RI = 1.0, TFP-1 −1.143 0.155 0.292 0.398 0.371 9.68
16 (0.218)
RI = 1.0, TFP-2 −1.008 0.142 0.327 0.448 0.374 5.46
(0.223)
RI = 1.0, TFP-3 −0.896 0.131 0.377 0.493 0.369 2.98
(0.215)

RI = 2.0, TFP-1 −1.037 0.191 0.333 0.467 0.389 4.97


(0.247)
RI = 2.0, TFP-2 −0.918 0.176 0.386 0.515 0.376 2.46
(0.226)
RI = 2.0, TFP-3 −0.831 0.153 0.401 0.543 0.363 1.46
(0.204)

– Non-isolated 0.475 0.242 1.675 2.432 0.448 0.46


(0.333)

1) SCBF buildings designed by the minimum criteria of ASCE/SEI 7-10 probabilities of collapse less than 5% as required for important
or 7-16 (isolator TFP-1 or DC-1, RI = 2.0) have unacceptable prob- structures can be achieved when RI = 1 in the DE per ASCE/SEI 7-10
abilities of collapse in the MCER (exceeding 10%). These prob- [1] but not when RI = 1 in the MCER per ASCE/SEI 7-16 [2]. For the
abilities of collapse are also larger than that of the non-isolated latter case, the isolator displacement capacity should be further in-
comparable structure designed by the minimum criteria of ASCE/ creased to be consistent with the strength of the superstructure per
SEI 7, which has an acceptable probability of collapse in the MCER. comments in item 2 above.
2) The probability of collapse decreases with increasing isolator dis- 4) The importance of the stiffening behavior of the triple FP isolators
placement capacity while RI is fixed. However, the probability of (or equivalently of some displacement restrainer) is evident in the
collapse may increase as RI is reduced while the isolator displace- increase of the probability of collapse when the restrainer ring is
ment capacity is fixed. The latter case may appear counterintuitive, removed. (For RI = 2 per ASCE/SEI 7-10, SCBF buildings with TFP-1
as it would be expected that increases in the strength of the super- and DC-1 isolators have probability of collapse of 18.1% and 27.3%,
structure would result in reduction of the probability of collapse. respectively).
While this is true for non-isolated structures, it is not always true for 5) The collapse performance of the OCBF design per criteria of ASCE/
isolated structures where collapse is dominated by excessive isolator SEI 7-16 [2] (RI = 1.0 in MCER, isolators with DCapacity ≥ 1.2DM) is
displacement. As the strength of the superstructure is increased, unacceptable as the probability of collapse exceeds 10%. To achieve
inelastic action in the superstructure is delayed leading to larger acceptable probability of collapse the isolator displacement capacity
isolator displacement demands. Accordingly, specifications for va- has to be increased to DCapacity = 1.5DM. Note that the study of [11]
lues of RI should be consistent with specifications for the displace- computed a just acceptable probability of collapse (just over 10%)
ment capacity of isolators. for a 3-story OCBF building designed by criteria that meet the
3) Use of isolators with DCapacity = 1.5DM and DUltimate = 1.9DM (TFP- minimum criteria of ASCE/SEI 7-16. The differences are likely due
3), and designed for any acceptable value of parameter RI have a to the differences in height of the two buildings with the taller
probability of collapse that is less than 10%, thus acceptable for building of this study having a larger probability of collapse. This
typical structures of risk category I and II [2]. However, observation is consistent with the results of the study of [12].

253
S. Kitayama, M.C. Constantinou Engineering Structures 164 (2018) 243–258

6) The results in Table 7 for the SMF are qualitatively similar to those with and without the epsilon adjustment) is higher for the SCBF,
for the SCBF but the probabilities of collapse are lower. This is due leading to lower probabilities of collapse. The difference is the result of
to the capability of the SMF to deform more than the SCBF before differences in the period of the systems but it should also depend on the
collapse (assumed 10% story drift ratio for SMF and 5% for SCBF). motions used in the analysis.
Nevertheless, SMF designed by the minimum criteria of ASCE/SEI 7- The calculated probability of collapse for the 6-story SCBF of the
10 without a restrainer ring (RI = 2.0, isolator DC-1) still has un- enhanced design with RI = 1.0 and isolators with displacement capacity
acceptable probability of collapse (39.9%). Even when the dis- at initiation of stiffening equal to 1.5DM and an ultimate displacement
placement capacity is increased (design with isolator DC-2), still the capacity of 1.9DM are very close to those calculated in the study of Shao
probability of collapse is unacceptable (26.3%). et al. [14] for a 3-story SCBF designed by similar procedures. Particu-
7) All isolated SMF structures of whatever design details have higher larly, Shao et al. [14] calculated a 2.5% probability of collapse in the
probabilities of collapse than the comparable non-isolated design. A MCER when assuming a dispersion factor of 0.3, whereas this study
question then arises: what does seismic isolation offer? This has calculated a 4.5% probability of collapse for a dispersion factor of 0.341
been investigated in [24] where studies of the performance of the as obtained from the analysis and after adjustment for uncertainties.
designed structures in terms of peak floor acceleration, peak story The probability of collapse is 2.7% when a dispersion factor of 0.3 is
drift ratio and peak residual drift ratio are presented. assumed, thus essentially the same as that of the study in [14].
The results of this study demonstrate that designing by the
Explanation for the collapse behavior of the studied isolated struc- minimum requirements of ASCE/SEI 7 [1,2] may result in unacceptable
tures is provided in the results of Fig. 8 which presents the calculated probabilities of collapse in the MCER. Probabilities of collapse less than
peak isolator displacement when collapse occurs for the SCBF in the 5% in the MCER were achieved for designs with RI = 1.0 (either for DE
designs with RI = 1.0 and 2.0 (for the MCER) per ASCE/SEI 7-16 and or the MCER) and designing triple FP isolators with a displacement
the three cases of TFP isolators. Each graph contains two types of lines: capacity at initiation of stiffening equal to 1.5DM and an ultimate dis-
dashed that denote the displacement capacity DCapacity and solid that placement capacity of 1.9DM. The stiffening behavior of the isolators is
denote the ultimate displacement capacity DUltimate. Colors are used to important in preventing collapse. Without it, as when using double
distinguish different size isolators. Results are presented for each of the concave isolators without a restrainer ring, there are unacceptably high
44 motions used in the analysis. The results show that for all motions probabilities of collapse. Also, a design with OCBF that satisfies the
and designs with RI = 1.0 all collapses occur by failure of the isolator. minimum criteria of ASCE/SEI 7-16 resulted in a marginally un-
As the RI factor is increased to the value of 2.0, there is an increasing acceptable probability of collapse in the MCER, which could be im-
number of collapses by failure of the superstructure. For example, it proved to acceptable by using isolators with displacement capacity at
may be seen in Fig. 8 that the percentage of cases when the isolator initiation of stiffening equal to 1.5DM instead of 1.2DM.
ultimate capacity is exceeded is about: 35% in the design with the While this study is based on the behavior of FP isolators, the results
minimum displacement capacity isolators TFP-1, is 23% in the design have some applicability to structures with elastomeric isolators. First
with isolators TFP-2 and is 12% in the design with isolators TFP-3. It is the results obtained for the DC isolators apply for elastomeric isolators
apparent that reducing the RI factor requires also increases in the dis- of the same displacement capacity and without any restrainer on dis-
placement capacity of the isolators in order to affect the probability of placements. The results obtained for the stiffening isolators would be
collapse. applicable to squatty (so instability is avoided) high quality elastomeric
It may be noted in the results of Tables 6 and 7 that the probabilities isolators that are capable of large deformations with stiffening behavior
of collapse for the SMF are lower than those of comparable SCBF [e.g., [46]]. Nevertheless, specialized studies are needed to evaluate the
structures except for the cases of the DC isolators without the re- collapse performance of isolated structures with elastomeric isolators as
straining ring that produces stiffening behavior. The lack of stiffening there are numerous means of restraining displacements, from the ex-
behavior results in very large displacement demands for which small treme of using moat walls [11] to providing no restraint.
differences in values alter the probabilities of collapse. There is also
another effect seen in the results of Tables 6 and 7. The spectral shape 5. Conclusions and discussion
effects are different in the cases of the SMF and SCBF with DC isolators.
Specifically, the spectral shape factor (ratio of the spectral accelerations It has been shown that seismically isolated structures designed by

1000
Isolator displacement (mm)

900
800
700
600 DUltimate DCapacity RI=1.0 for MCER per ASCE/SEI 7-16
500
1 6 11 16 21 26 31 36 41

1000
Isolator displacement (mm)

900
800
700
600 Isolator TFP-1 (red), TFP-2 (black), TFP-3 RI=2.0 for MCER per ASCE/SEI 7-16
500 ( )
1 6 11 16 21 26 31 36 41
Ground Motion
Fig. 8. Peak isolator displacements at collapse of buildings with SCBF.

254
S. Kitayama, M.C. Constantinou Engineering Structures 164 (2018) 243–258

the minimum criteria of ASCE/SEI 7-10 or 16 [1,2] may have un- Nearly all studied isolated structures of whatever design details had
acceptable probabilities of collapse in the MCER, whereas comparable higher probabilities of collapse than the comparable non-isolated de-
non-isolated structures, also designed by the minimum criteria of signs (actually all isolated SMF but not all other buildings had higher
ASCE/SEI 7 [1,2], have acceptable probabilities of collapse. Improve- probability of collapse). Given this fact, probabilistic evaluation studies
ment of the collapse performance is achieved by designing for an of the performance of the designed isolated and non-isolated structures
RI = 1.0 in the DE and providing isolators with stiffening behavior and in terms of the mean annual frequency of exceeding specific values of
with a displacement capacity at initiation of stiffening equal to 1.5DM the peak floor acceleration, peak story drift ratio and peak residual drift
and ultimate displacement capacity of 1.9DM, where DM is the dis- ratio are needed in order to clarify the advantages offered by seismic
placement capacity in the MCER as stipulated by the minimum criteria isolation. Results of one such study are presented in [24] where also
of ASCE/SEI 7. In general, increasing the strength of seismically iso- probabilities of developing minor damage to the structural and non-
lated structures (by reducing RI) does not result in improvement of the structural systems, and to the building contents during the lifetime of
collapse performance unless the displacement capacity of the isolators the structure are presented.
is proportionally increased. The reason for this behavior is that by in- The presented studies were limited to examples of perimeter braced
creasing the strength, inelastic action in the superstructure is delayed so and moment 6-story steel frames with sliding isolators. A study in [14]
that the isolator displacement demand is increased, leading to collapse included similar 3-story braced frames, also with sliding isolators.
by failure of the isolators. There is a need to extend these studies to taller structures, to other
The significance of providing isolator displacement restraint structural systems (e.g., concrete space frames), to other seismic iso-
through the use of stiffening isolators as in this study, or by other means lation systems and to other sites, including near-fault sites, in order to
as studied in [11], was demonstrated by the substantial increase in the cover a wider range of structures of interest in seismic isolation.
probability of collapse when the restrainer ring of the isolators was Nevertheless, the results of these studies clearly show a need to re-visit
removed. For example, the probability of collapse in the MCER of the the ASCE/SEI 7 [1,2] criteria for the design of seismically isolated
isolated SMF designed by the minimum criteria of ASCE/SEI 7-10 [1] structures. Ideally, the specified RI factor, minimum displacement ca-
and triple FP isolators (TFP-1) was 6.1%. It was 39.9% when the iso- pacity of the isolators and isolator stiffening characteristics should be
lator restrainer ring was removed and the isolators were converted to dependent on the seismic force-resisting system. In the absence of such
double concave with the minimum displacement capacity per ASCE/SEI detailed studies, it justified to require designs with RI = 1.0 and iso-
7-10 [1] (isolator DC-1) (the probabilities were 18.1% and 27.4%, re- lators with DCapacity = 1.5DM and DUltimate = 1.9DM in order to ensure
spectively, for the SCBF designed by the minimum criteria of ASCE/SEI acceptable collapse performance. Such a design also offers additional
7-10 [1]). benefits in terms of reducing the probability to develop minor damage
The conclusions of this study in terms of requirements for the su- to non-structural components and the building contents, and in redu-
perstructure design and the isolator displacement capacity to achieve cing the probability of having to demolish the building in its lifetime.
acceptable collapse performance are consistent with the results of a This has been demonstrated in a probabilistic evaluation study in [24].
similar study conducted for 3-story isolated structures [14].

Appendix A. Procedure for calculating the median collapse spectral acceleration when considering spectral shape effects

The procedure involves the following steps:

1. Obtain the target epsilon ε0 (T1) , magnitude M, and distance R from de-aggregation of the ground motion hazard (probabilistic seismic hazard
analysis) for the specific location of the structure (longitude and latitude), site class (average shear-wave velocity Vs30 = 259 m/s for class D),
spectral period and return period. The return period of 2475 years (corresponding to a probability of exceedance of 2% in 50 years) is used based
on [42] because the primary purpose of collapse evaluation is to compute the conditional collapse probability for a 2% in 50 years ground
motion. Information was obtained from the USGS website (https://earthquake.usgs.gov/hazards/interactive/ accessed on July 16, 2017) where
results of de-aggregation for period of 0.2, 1.0 and 2.0 s were available. Linear interpolation and extrapolation in logarithmic space of the seismic
hazard curves (annual frequency of exceedance vs spectral acceleration) was used for other values of period (T1 = 0.524 s for non-isolated SCBF,
T1 = 1.186 s for non-isolated SMF and T1 = TM = 3.66 s for all isolated structures).
2. Perform incremental dynamic analysis (IDA) [41] (for this study the 44 ground motions of FEMA P695) to obtain the collapse capacity in terms of
the spectral acceleration at fundamental period T1 at collapse for each ground motion, SaCol,j(T1) (TM in case of base-isolated structures and j is
the identification number for the ground motions; j = 1–44).
3. Calculate epsilon at T1, εj(T1) for the jth ground motion (j = 1–44), defined as the number of standard deviations by which the natural logarithm
of Saj(T1), ln[Saj(T1)], differs from the mean predicted ln[Sa(T1)] for a given magnitude and distance [47]:
ln[Saj (T1)]−μlnSa (M ,R,T1)
εj (T1) =
σlnSa (T1) (A.1)

In Eq. (A.1), μlnSa(M,R,T1) is the predicted mean of ln[Sa(T1)] at a given magnitude M, distance R and period T1, and σlnSa(T1) is the predicted
standard deviation of ln[Sa(T1)] at a given M, R and T1. Note that μlnSa(M,R,T1) and σlnSa(T1) are obtained from any ground motion prediction
model (herein the model of Abrahamson and Silva (1997) [48] was used, which was also used by [42]). Quantity ln[Saj(T1)] in Eq. (A-1) is the

Table A1
Values of ε0 (T1) , M and R for considered site and 2475 years return period.

ε0 (T1) M R (km)

Isolated 1.44 7.96 16.0


Non-isolated (SCBF) 1.46 7.35 16.0
Non-isolated (SMF) 1.71 7.63 16.0

255
S. Kitayama, M.C. Constantinou Engineering Structures 164 (2018) 243–258

2.5
Predicted median spectrum for isolated structure (case SCBF)

Spectral acceleration (g)


2.0
Predicted median spectrum for non-isolated structure (case SCBF)
1.5
5%-damped spectra of 44 far-field ground motions in FEMA
1.0

0.5

0.0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
Period (second)
Fig. A1. Response spectra of FEMA far-field motions and predicted median spectra.

0.75
0.7
0.65
σ lnSa(T1)

0.6
0.55 For isolated and non-isolated structures
0.5
0.45
0.4
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
Period (second)
Fig. A2. Standard deviation of natural logarithm of spectral acceleration.

4.0
Isolated SCBF Non-isolated SCBF
3.0
2.0
İj(T1)

1.0
0.0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44
-1.0
-2.0
Ground motion
-3.0

Fig. A3. Calculated values of εj(T1) for each of 44 ground motions.

Fig. A4. Sample relationship between ln[SaCol,j(T1)] and εj(T1) for SCBF buildings.

256
S. Kitayama, M.C. Constantinou Engineering Structures 164 (2018) 243–258

natural logarithm of the spectral acceleration at T1 of each of 44 original (before scaling) ground motions.
4. Perform a linear regression analysis between ln[SaCol,j(T1)] and εj(T1) and determine parameters c0 and c1 based on the following equation:
ln[SaCol (T1)] = c0 + c1·ε (T1) (A.2)

Note that based on Appendix B of [7], for establishing a relationship between the ln[SaCol(T1)] and ε(T1), the p-value [49] must be less than 0.05
for the trend to be statistically defensible.
 Col,adj (T1) :
5. Replace ε(T1) with ε0 (T1) in Eq. (A.2) and solve to obtain the adjusted mean collapse capacity, Sa
 Col,adj (T1)(units g) = exp[c0 + c1·ε0 (T1)]
Sa (A.3)

The record-to-record dispersion coefficient, βRTR, is calculated as the standard deviation of the natural logarithm of SaColj(T1) of the 44 motions
without any further adjustment. Note that [42] described a procedure for further reduction of the dispersion using the residuals of the regression
analysis but the effect was found to be insignificant in this study and was not included in the presented results.

Values of the target epsilon ε0 (T1) , magnitude M and distance R for return period of 2475 years obtained by de-aggregation of the seismic hazard
are presented in Table A1.
Using the ground motion prediction model of [48] the median 5%-damped response spectra were constructed for isolated and non-isolated
structures and are presented in Fig. A1 together with the spectra of the 44 ground motions used in the IDA. Program OpenSHA [50] was used to
construct the spectra using the Abrahamson and Silva prediction model [48]. The same model also predicted the standard deviation, which is
presented in Fig. A2. The standard deviation is the same for the isolated and non-isolated structures.
The values of εj(T1) for each of the 44 ground motions (j = 1–44) for the isolated and non-isolated structures where then calculated by use of Eq.
(A-1) and are presented in Fig. A3 for the case of the SCBF where it is seen that the values of epsilon are higher for the non-isolated structure.
Based on the results of IDA and the information on εj(T1) in Fig. A3, linear regression analysis was performed to establish the relationship
between the ln[SaCol,j(T1)] and εj(T1). For example, Fig. A4 presents the relationship between ln[SaCol,j(T1)] and εj(T1) for the isolated SCBF structure
designed for RI = 1.0 in the DE and isolator TFP-1 (DUltimate = 683 mm) and the non-isolated SCBF structure. The figure also presents the fitted linear
regression model of Eq. (A.2). The calculated p-values [49] were less than 10−3, thus statistically meaningful (less than 0.05). Relationships like
those of Fig. A4 were constructed for each analyzed structure.

References design guidance for buildings. Buffalo, NY: Multidisciplinary Center for Earthquake
Engineering Research; 2015.
[16] Ponzo FC, Cesare AD, Leccese G, Nigro D. Shake table testing on restoring capability
[1] ASCE/SEI 7. Minimum design loads for buildings and other structures. VA, U.S.A.: of double concave friction pendulum seismic isolation systems. Earthquake Eng
American Society of Civil Engineers; 2010. Struct Dynam 2017;46(14). http://dx.doi.org/10.1002/eqe.2907.
[2] ASCE/SEI 7. Minimum design loads for buildings and other structures. American [17] Structural Engineers Association of California. SEAOC structural/seismic design
Society of Civil Engineers, 2017, VA, U.S.A. manual. Volume 5: Examples for seismically isolated buildings and buildings with
[3] Executive Order 13717, Establishing a federal earthquake risk management stan- supplemental damping. Published January 2014.
dard; February 2, 2016. [18] Sarlis AA, Constantinou MC. A model of triple friction pendulum bearing for general
[4] Hayes J, McCabe SL. Mahoney M. ICSSC recommended practice (RP) 9. geometric and frictional parameters. Earthquake Eng Struct Dynam
Implementation guidelines for executive order 13717: Establishing a federal 2016;45(11):1837–53. http://dx.doi.org/10.1002/eqe.2738.
earthquake risk management standard. National Institute of Standards and [19] Fenz DM, Constantinou MC. Behaviour of the double concave friction pendulum
Technology (NIST) Technical Note 1922; 2017. http://dx.doi.org/10.6028/NIST. bearing. Earthquake Eng Struct Dynam 2006;35(11):1403–24.
TN.1922. [20] American Institute of Steel Construction. Steel construction manual. 14th ed. Third
[5] Kikuchi M, Tamura K, Wada A. Safety evaluation of base-isolated structures. J Struct Printing. Chicago, IL: AISC; 2010.
Constr Eng, AIJ 1995;470:65–73. (in Japanese). [21] Tzimas AS, Kamaris GS, Karavasilis TL, Galasso C. Collapse risk and residual drift
[6] Nakazawa N, Kishiki S, Qu Z, Miyoshi A, Wada A. Fundamental study on prob- performance of steel buildings using post-tensioned MRFs and viscous dampers in
abilistic evaluation of the ultimate state of base isolated structures. 8CUEE near-fault regions. Bull. Earthq. Eng. 14(6), 1643–1662.
Conference proceedings, 8th international conference on urban earthquake en- [22] Sabelli R, Roeder CW, Hajjar JF. Seismic design of steel special concentrically
gineering, March 7–8. Tokyo, Japan: Tokyo Institute of Technology; 2011. braced frame systems – A guide for practicing engineers. NEHRP Seismic Design
[7] FEMA. Quantification of building seismic performance factors. Report FEMA P695. Technical Brief No. 8, NIST GCR 13-917-24; 2013.
Washington DC, USA: Federal Emergency Management Agency; 2009. [23] Arup. Resilience-based Earthquake Design Initiative (REDiTM) Rating System.
[8] Erduran E, Dao ND, Ryan KL. Comparative response assessment of minimally Version 1.0; 2013.
compliant low-rise conventional and base-isolated steel frames. Earthquake Eng [24] Kitayama S, Seismic ConstantinouC. Seismic Performance assessment of seismically
Struct Dynam 2011;40(10):1123–41. isolated buildings designed by the procedures of ASCE/SEI 7. MCEER-17-xxxx.
[9] Sayani PJ, Erduran E, Ryan KL. Comparative response assessment of minimally Buffalo, NY: Multidisciplinary Center for Earthquake Engineering Research; 2017.
compliant low-rise base-isolated and conventional steel moment-resisting frame [25] Zayas V. Seismic isolation standard for continued functionality. Berkeley:
buildings. J Struct Eng 2011;137(10):1118–31. Department of Civil and Environmental Engineering. University of California; 2017.
[10] Terzic V, Mahin SA, Comerio MC. Lifecycle cost comparisons for different structural https://goo.gl/h82Fnk.
systems designed for the same location. Proceedings of the 10th national conference [26] Zayas V, Mahin SA, Constantinou MC. Commentary to the seismic isolation stan-
in earthquake engineering. Anchorage, AK: Earthquake Engineering Research dard for continued functionality. Berkeley: Department of Civil and Environmental
Institute; 2012. Engineering. University of California; 2017. https://goo.gl/r6sdwL.
[11] Masroor A, Mosqueda G. Assessing the collapse probability of base-isolated build- [27] McKenna FT. Object-oriented finite element programming: frameworks for analysis,
ings considering pounding to moat walls using the FEMA P695 methodology. algorithms and parallel computing Ph.D. Thesis Berkeley: Department of Civil and
Earthquake Spectra 2015;31(4):2069–86. Environmental Engineering, University of California; 1997.
[12] Chimamphant S, Kasai K. Comparative response and performance of base-isolated [28] Uriz P, Mahin SA. Toward earthquake-resistant design of concentrically braced
and fixed-base structures. Earthquake Eng Struct Dynam 2016;45(1):5–27. http:// steel-frame structures. PEER 2008/08, Pacific Earthquake Engineering Research
dx.doi.org/10.1002/eqe.2612. Center. PEER; November 2008.
[13] FEMA. Seismic performance assessment of buildings. Report FEMA P-58. [29] Chen CH, Mahin SA. Performance-based seismic demands assessment of con-
Washington DC, USA: Federal Emergency Management Agency; 2012. centrically braced steel frame buildings. PEER 2012/103. Pacific Earthquake
[14] Shao B, Mahin SA, Zayas V. Member capacity factors for seismic isolators as re- Engineering Research Center, PEER; December 2012.
quired to limit isolated structure collapse risks to within ASCE 7 stipulated structure [30] Filippou FC, Popov EP, Bertero VV. Effects of bond deterioration on hysteretic
collapse risk limits. Project draft report. Structural Engineering, Mechanics and behavior of reinforced concrete joints. Report EERC 83-19. University of California,
Materials Department of Civil and Environmental Engineering University of Berkeley: Earthquake Engineering Research Center; 1983.
California, Berkeley; June 24, 2017. [31] Chopra AK, McKenna F. Modeling viscous damping in nonlinear response history
[15] McVitty WJ, Constantinou MC. Property modification factors for seismic isolators: analysis of buildings for earthquake excitation. Earthquake Eng Struct Dynam

257
S. Kitayama, M.C. Constantinou Engineering Structures 164 (2018) 243–258

2016;45(2):193–211. http://dx.doi.org/10.1002/eqe.2622. buildings. Report FEMA 350, 2000; Washington DC, USA: Federal Emergency
[32] Sarlis AA, Constantinou MC. Modeling triple friction pendulum isolators in program Management Agency; 2009.
SAP2000. Report distributed to the engineering community together with example [41] Vamvatsikos D, Cornell CA. Incremental dynamic analysis. Earthquake Eng Struct
files. University at Buffalo; 2011. Dynam 2002;31(3):491–514.
[33] Kitayama S, Constantinou MC. Probabilistic collapse resistance and residual drift [42] Haselton CB, Baker JW, Liel AB, Deierlein GG. Accounting for ground-motion
assessment of buildings with fluidic self-centering systems. Earthquake Eng Struct spectral shape characteristics in structural collapse assessment through an adjust-
Dynam 2016;45(12):1935–53. http://dx.doi.org/10.1002/eqe.2733. ment for epsilon. J Struct Eng 2011;137(3):332–44.
[34] Lignos DG, Krawinkler H. Deterioration modeling of steel components in support of [43] Baker JW, Cornell CA. Spectral shape, epsilon and record selection. Earthquake Eng
collapse prediction of steel moment frames under earthquake loading. J Struct Eng Struct Dynam 2006;35(9):1077–95.
2011;137(11):1291–302. http://dx.doi.org/10.1061/(ASCE)ST.1943-541X. [44] NIST. Evaluation of the FEMA P-695 Methodology for quantification of building
0000376. seismic performance factors. NIST GCR 10-917-8. 2010; Technical Report, prepared
[35] Fenz DM, Constantinou MC. Modeling triple friction pendulum bearing for re- by the NEHRP Consultants Joint Venture for the National Institute of Standards and
sponse-history analysis. Earthquake Spectra 2008;24(4):1011–28. http://dx.doi. Technology: Gaithersburg, Maryland.
org/10.1193/1.2982531. [45] Elkady A, Lignos DG. Modeling of the composite action in fully restrained beam-to-
[36] Fenz DM, Constantinou MC. Spherical sliding isolation bearings with adaptive be- column connections: implications in the seismic design and collapse capacity of
havior: theory. Earthquake Eng Struct Dynam 2008;37(2):163–83. steel special moment frames. Earthquake Eng Struct Dynam 2014;43(13):1935–54.
[37] Kitayama S, Constantinou MC, Procedures Lee D. Procedures and results of as- [46] Masaki N, Mori T, Murota N, Kasai K. Validation of hysteresis model of deforma-
sessment of seismic performance of seismically isolated electrical transformers with tion-history integral type for high damping rubber bearings. 16th World Conference
due consideration for vertical isolation and vertical ground motion effects. MCEER- on Earthquake, 16WCEE. 2017.
16-0010. Buffalo, NY: Multidisciplinary Center for Earthquake Engineering [47] Baker JW. Conditional mean spectrum: Tool for ground-motion selection. J Struct
Research; 2016. Eng 2011;137(3):332–44.
[38] Kitayama S, Lee D, Constantinou MC, Kempner L. Probabilistic seismic assessment [48] Abrahamson NA, Silva WJ. Empirical response spectral attenuation relations for
of seismically isolated electrical transformers considering vertical isolation and shallow crustal earthquakes. Seismol Res Lett 1997;68(1):94–127.
vertical ground motion. Eng Struct 2017;152:888–900. [49] Neter J, Kutner M, Wasserman W, Nachtsheim C. Applied linear statistical models.
[39] Bao Y, Becker TC, Hamaguchi H. Failure of double friction pendulum bearings 4th ed. McGraw-Hill/Irwin; 1996.
under pulse-type motions. Earthquake Eng Struct Dynam 2016;46(5):715–32. [50] Field EH, Jordan TH, Cornell CA. OpenSHA: a developing community-model-ling
http://dx.doi.org/10.1002/eqe.2827. environment for seismic hazard analysis. Seismol Res Lett 2003;74(4):406–19.
[40] FEMA. Recommended seismic design criteria for new steel moment-frame

258

You might also like