Professional Documents
Culture Documents
(Page-EN)
Protection Of Industrial
7th issue, Feb 2018 Power Supply Systems
(Page-EE)
SF6 Sampling
Editor Talk
It is our 7th consecutive
edition and we are still
facing the "writing
deficit disorder" in our
engineering community,
I appreciate some of our
professionals who dared to
express their experience in
writing, but again issue is
the silent majority, we try to reach each and every
possible group of creative engineering professionals, but
most of them think that it is hard for them to convert
their experience in Scribd form. I saw enthusiasm but
no practical approach, let me assure all our readers
although we are facing this scenario we will bring the
best material from available writers and we will never
compromise on the quality of content.
Another issue we would like to discuss in later editions
is Fraud practices by fake recruiters, we tried to present
our claims with evidence, in this issue, we add the story
about MTMM fraud recruitment drive, I hope you will
read it and get awareness of this practice.
Send your articles and views, Our
Team will add them in our March
edition.
enpak2017@gmail.com
Feedback
1. Fuse Co-ordination
2. Grading of Fuses / MCCBs / Overcurrent Relays
3. Determination of relay current setting
4. Relay characteristic and time multiplier selection
5. Protection of a Dual-Fed Substation
6. General considerations
7. Motor protection relay settings
8. Relay B settings
9. Relays C settings
10. Comments on grading
1. Fuse Co-ordination
An example of the application of fuses is based
on the arrangement in Figure 1(a). This shows an
unsatisfactory scheme with commonly encountered
shortcomings.
4
The solution, shown in Figure 1(b), is to feed the 400A
circuit E direct from the busbars. The sub-circuit fuse D
may now have its rating reduced from 500A to a value,
of say 100A, appropriate to the remaining sub-circuit.
5
However, there
are industrial
applications
where
discrimination
is a secondary
factor. In the
application
shown in Figure
2,a contactor
having a fault
rating of 20kA
controls the load in
one sub-circuit.
A fuse rating of
630A is selected
for the minor fuse
in the contactor
circuit to give
protection within
the through-fault
capacity of the
contactor.
6
The major fuse of 800A is chosen, as the minimum
rating that is greater than the total load current on the
switchboard. Discrimination between the two fuses is
not obtained, as the pre-arcing I2t of the 800A fuse is
less than the total I2t of the 630A fuse.
Therefore, the major fuse will blow as well as the minor
one, for most faults, so that all other loads fed from the
switchboard will be lost.
This may be acceptable in some cases. In most cases,
however, loss of the complete switchboard for a fault on
a single outgoing circuit will not be acceptable, and the
design will have to be revised.
8
With the CT ratio of 2000/1A and a relay reset ratio of
95% of the nominal current setting, a current setting of
at least 80% would be satisfactory, to avoid tripping and/
or failure to reset with the transformer carrying full load
current.
However, choice of a value at the lower end of
this current setting range would move the relay
characteristic towards that of the MCCB and
discrimination may be lost at low fault currents.
It is therefore prudent to select initially a relay current
setting of 100%.
9
0.4s, the required relay operating time becomes 0.4 +
0.014 = 0.414s.
With a CT ratio of 2000/1A, a relay current setting
of 100%, and a relay TMS setting (Time Multiplier
Setting) of 1.0, the extremely inverse curve gives a relay
operating time of 0.2s at a fault current of 40kA. This is
too fast to give adequate discrimination and indicates
that the EI curve is too severe for this application.
Turning to the VI relay characteristic, the relay
operation time is found to be 0.71s at a TMS of 1.0.
To obtain the required relay operating time of 0.414s:
TMS setting = 0.414 / 0.71 = 0.583
10
11
3. Protection of a Dual-Fed Substation
As an example of how numerical protection relays can
be used in an industrial system, consider the typical
large industrial substation of Figure 5 below. Two
1.6MVA, 11/0.4kV transformers feeding a busbar whose
bus-section CB is normally open.
The LV system is solidly earthed. The largest outgoing
feeder is to a motor rated 160kW, 193kVA, and a
starting current of 7 x FLC.
12
The transformer impedance is to IEC standards. The LV
switchgear and busbars are fault rated at 50kA rms. To
simplify the analysis, only the phase-fault LV protection
is considered.
18
19
3e. Comments on grading
While the above grading may appear satisfactory, the
protection on the primary side of the transformer has
not been considered.
IDMT protection at this point will have to grade
with relays C and with the through-fault short-time
withstand curves of the transformer and cabling. This
may result in excessively long operation times. Even
if the operation time at the 11kV level is satisfactory,
there is probably a Utility infeed to consider, which will
involve a further set of relays and another stage of time
grading, and the fault clearance time at the Utility infeed
will almost certainly be excessive.
One solution is to accept a total loss of supply to the
0.4kV bus under conditions of a single infeed and bus
section CB closed.
This is achieved by setting relays C such that grading
with relay B does not occur at all current levels, or
omitting relay B from the protection scheme. The
argument for this is that network operation policy is to
ensure loss of supply to both sections of the switchboard
does not occur for single contingencies.
As single infeed operation is not normal, a contingency
(whether fault or maintenance) has already occurred, so
that a further fault causing total loss of supply to the
20
switchboard through tripping of one of relays B is a
second contingency. Total loss of supply is therefore
acceptable. The alternative is to accept a lack of
discrimination at some point on the system.
Another solution is to employ partial differential
protection to remove the need for Relay A, but this is
seldom used. The strategy adopted will depend on the
individual circumstances.out
About Author:
21
Standstill Position
of Pakistan’s Steam
Power Plants
Engr. Naveed Ahmed Unar
G
As stated in Daily Dawn, keeping in view the
historical electrical power surplus capacity in Pakistan
approximately 3400 MW, Prime Minister of Pakistan
on Friday, 28 October ordered short-term standstill of
steam power plants to keep an eye on the fiscal deficit
because of an unwanted capacity trap. Meanwhile, a
separate load management plan has been chalked out
based on the demand-supply situation by the National
Power Control Center.
The Electrical Power Generation industry in the
United States after entering the new millennium had
more than 1300 steam turbine power plants at least
some thirty years old. With the emergence of a cut-
throat competition in an industrial market and revised
policy frameworks, electric power utilities must aim at
optimization of the operation and maintenance of such
power plants. It is rather more economical and cost-
effective to upgrade these power plants with computer-
supported technological advances like design and
development of energy-efficient turbine blades with
improvised pitch angles ensuring aerodynamic
advantage instead of shutting down for a vigilant
check and balance that may lead to an unending crisis.
Pakistan cannot afford to boycott a technology that has
25
space for improvement is provided with latest
overhauling techniques and upgradation schemes.
Therefore, the retirement of old power plants which
have the infrastructure and manpower available may
further deteriorate load management problem in the
country. We must invest in power system optimization
with available resources. As stated by Ministry of
Energy, Power Division, the targeted electrical energy
surplus for the next four months has been estimated
to range between 2400 to 3400 MW approximately. In
addition to it, the peak demand for next year summer is
estimated to be 25,300 MW against expected generation
capacity of 27,700 MW which when compared with
India is less than of a single state of India, which has an
overall generation capacity of 1,50000 MW.
National Power Control Center had devised a load
management plan on Saturday, October 28 to tackle the
load demand after the Ministry of Energy decided to
close all expensive furnace oil/diesel-run power plants
of a cumulative capacity of 4250 MW to compensate
financial debt with electrical energy surplus in MWs.
The furnace oil plants include 950 MW HUBCO, 1000
MW NPGCL Muzaffargarh, 400 MW JPCL Jamshoro
and 700 MW.
26
KAPCO. After the introduction of cascaded tripping
in South Punjab and Upper Sindh almost leading to a
Domino Effect, the Power Division directed the NPCC
to chalk out a separate emergency load management
plan for 72 hours till the restoration of transmission
lines.
In many countries, wind energy now forms a substantial
portion of energy production. A few years ago, the
Alternate Energy Development Board (AEDB) of
Pakistan prepared a wind energy development plan.
This targeted 3000 MW by 2016 and 5000 MW by 2020.
Germany produces 100 GW from wind energy and 20
GW from solar energy and thus generates 5% more than
the current energy demand in the country. Therefore,
Germany could completely negate the supply-demand
gap in 2016 only via clean energy. Today, Germany
produces more electricity than it is demanded where
consumers are paid in turn to consume electricity
through net metering. Geographically, Japan and
Sindh province share a size of equivalence. Having said
that, Japan produces more electricity than the overall
generation capacity of Pakistan.In summary, Pakistan
is lagging in its power generation as compared to most
of the developing countries and to accelerate its power
generation, it will have to develop 50000 MW from its
27
hydel energy resources. Pakistan has 185 billion tons of
coal in Tharparkar desert, which unfortunately has not
been efficiently utilized. Wind and solar energy sources
to have not been particularly exploited.
About Author:
28
Overseas Recruitmen
I
nt Fraud –MTMM
31
When we respond by asking details of company,
recruiter’s response was,
32
After submitting this all information, we received below
mention email.
33
34
After that there was no communication from recruiter,
when on contacting multiple time with the recruiter, we
received a similar mention below response
35
The Art of CV Design: A
Lesson learnt Approach
Short talk by Engr. Shahbaz Muhammad
N
Sampling Method-SF6
EE
Engr. Qazi Arsalan
hamid
SF6 is highly electronegative gas, by electronegative
we mean it captured free electron (the main part of the
arc which needs to be extinguished while parting of
contacts). Since 1960s SF6 is used as insulation medium
in Electrical medium and high voltage distribution
system.
At normal temperature, it remains stable and inert
5 times dense than air
Once used in system, engineer need to maintain close
look on the impurity level, up to certain impurity level
there is no issue , like if in 1Kg of SF6 air content is
1gram then it is ok , but more then 1 gram is found it is
alarming, recommended is 3 to 35 gm/kg of SF6.
Engineers need to kept close check on below mention
impurities
41
This clearance must be ensured by the vacuum pump,
also connection pipes must be clean. Pipe purging is one
of the methods to ensure clearance of connection pipes.
42
Pipes are made of stainless steel because stainless steel
is chemical resistant, normal lengths of connection pipe
should be up to 2 meter, an outer diameter of pipe will
be in between 3 mm to 6 mm. end seals of pipes must
be tight. Cylinder volume shall be in the range of 150 ml
to 1000 ml. like pipes, cylinder shall be developed from
stainless steel.
(Continued)Excerpts from "High Voltage Switchgear
Testing" by Engr. Qazi Arsalan Hamid
43
Engineer making
difference
R
Book For this month
Hybrid Intelligent Techniques f
or Pattern Analysis and Unde-
-rstanding outlines the latest
research on the development
and application of synergistic
approaches to pattern analysis
in real-world scenarios.
An invaluable resource for
lecturers, researchers, and
graduates students in
computer science and engine-
-ering, this book covers a diverse range of hybrid
intelligent techniques, including image segmentation,
character recognition, human behavioral analysis,
hyperspectral data processing, and medical image
analysis.
Siddhartha Bhattacharyya was born in 1975 in Kolkata,
India. He received the Gold Medal from the University
of Calcutta for his Masters.He has been involved in
academics for the last 16 years. In 2016, he received
the National Award for Excellence in Education and
Research "Adarsh Vidya Saraswati Rashtriya Puraskar".
S
enpak2017@gmail.com