Professional Documents
Culture Documents
1
5.2.2 Static Pressure Control
In spaces requiring a constant positive or negative pressure with respect to their
surroundings, the outside, return, and relief air dampers will be controlled by static
pressure controllers. In Figure 5.3, the static pressure controller senses the difference in
pressure between the controlled space and a reference location (either next to the
controlled space or outdoors) and adjusts the dampers to maintain that pressure
differential. The amount of outside air provided must be sufficient to make up any
exhaust and to pressurize the space. Proportional plus integral controls are required
because low proportional gain is needed to prevent instability due to pressure surges that
occur when doors are opened.
2
Figure 5.4 Return damper controls mixing box pressure.
If the air streams enter opposite sides of the mixing plenum, as in Figures (5.6 - 5.7) then
good mixing may occur. Good mixing is more likely if the comparatively high damper
velocities recommended are used.
3
Figure 5.6 Air streams at 90"angle, good mixing.
Unfortunately, in many existing systems damper velocities can be low and outdoor and
return air stream will not mix, especially in cold weather, without modifying the mixing
box. One approach is to block off part of the dampers to increase velocities. Static
mixers also can be used. They impart a whirling, mixing motion to the air, but complete
mixing does not occur for several diameters past the mixer. If an obstruction such as a
filter or heating or cooling coil is encountered, mixing stops. Some system pressure drop
is added.
Another approach is to add baffles to promote mixing, as shown in Figure 5.8.
Experience has shown that this method is the most effective in producing a fully mixed
air stream at the cost of some additional system pressure drop.
4
Figure 5.8 Baffles to improve mixing.
5.4 HEATING
Heating in HVAC systems usually is provided by steam or hot water coils with remote
boilers. Electric heating coils, heat pumps, and direct gas-fired duct heaters also are used
and are discussed in other sections of this book. Heating may be done to preheat outside
air or heat mixed air, to heat part of the air stream, or to reheat for humidity control or
individual zone temperature control.
5.4.1 Preheat
Preheating is used when large percentages of outside air could cause freezing of
downstream heating and cooling coils. The main problem in preheating is freeze-up of
the preheat coil itself. Several methods are used to prevent this. Figure 5.9 shows the
simplest approach. This is a two-position valve in the steam or hot water supply with an
outdoor thermostat that opens the valve whenever the outdoor temperature is below
35oFor 40oF. (an open-loop control.) The filter is downstream of the coil to prevent snow
loading in severe winter storm weather. Because no control of leaving air temperature is
provided, the preheat coil must be carefully selected to prevent overheating at, say, 30 oF
outside, while still providing adequate capacity at perhaps -10oF or - 20oF outside design
conditions. This is a difficult, if not impossible, compromise.
Face and bypass dampers are added at the coil and controlled by means of a downstream
thermostat (T2, Figure 5.10) to provide a controlled mixture temperature. The difficulty
here is stratification of the two air streams. In some cases where a downstream cooling
coil has been frozen by a bypass air stream while the preheat coil was in full operation.
The preheat coil should always be located in the bottom of the duct, and, even so, it is
desirable to provide mixing baffles.
5
Figure 5.9 Preheat: outside air thermostat.
6
Alternatively, the supply valve may be controlled to provide a variable discharge air
temperature with reset from the zone temperature (Figure 5.12). Either of these systems
can be used for cooling, heating, or a combination of the two, with heating and cooling
coils in series.
A different approach adds a variable back-pressure valve in the refrigerant suction line,
controlled by the room thermostat (Figure 5.15). As the room temperature decreases, the
valve is throttled, increasing the suction temperature at the coil and decreasing the coil
capacity. A reversing relay allows the back-pressure valve to be normally open, a
necessary condition when the solenoid valve is first opened.
Hot gas bypass also may be used for capacity control, as shown in Figure 5.16. A
constant pressure expansion valve is used to maintain the evaporator pressure (and
temperature) at a constant level, regardless of load. There are limitations on the
percentage of total refrigeration flow that may be bypassed, and on pressure drops in the
piping system.
8
Figure 5.16 Hot gas bypass capacity control
Two-stage direct expansion will often provide adequate capacity control. The stages
should be made by rows of coil rather than by sectioning the coil. Otherwise the active
section may ice up, forcing most of the air flow through the inactive section and
reducing the coil capacity. In a multi-row coil the first stage should be the first row in
the direction of air flow and the second stage the rest of the rows, since the first row of a
three or four row coil does at least half the cooling.
The recirculation pump arrangement is very useful in two cases: (1) for extremely
accurate temperature control and (2) to avoid freezing in those situations where system
geometry make it impossible to avoid stratification of mixed or partially preheated air.
9
5.6 HUMIDITY CONTROL
It may be necessary to raise or to lower the humidity of the supply air to maintain
selected humidity conditions in the air-conditioned space.
10